Ceiling Concealed TM-FDBM-0515-C TECHNICAL MANUAL

Upload: lamduong

Post on 16-Apr-2018

319 views

Category:

Documents


21 download

TRANSCRIPT

Page 1: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

Ceiling Concealed

TM-FDBM-0515-CTECHNICAL MANUAL

Page 2: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

1. Model Name .......................................................................................................... 1 2. Features ................................................................................................................ 3

3. Specifications ........................................................................................................ 4 GeneralData .............................................................................................. 4 SafetyDevices .......................................................................................... 26

4. SelectionProcess ................................................................................................ 28 FanPerformanceCurve ........................................................................... 28

5. ApplicationInformation ........................................................................................ 52 OperatingRange ...................................................................................... 52 RefrigerantDiagram ................................................................................. 53 Controllers ................................................................................................ 56

6. Installation ........................................................................................................... 60

7.WiringDiagram .................................................................................................... 72

8. Servicing&Maintenance .................................................................................... 87

9. Troubleshooting .................................................................................................. 88

10.DimensionalData ................................................................................................ 92

11.ExplodedView&PartList ................................................................................... 98

Note:Installationandmaintenancearetobeperformedonlybyqualifiedpersonnelwhoare familiarwithlocalcodesandregulations,andexperiencedwiththistypeofequipment.

Caution:Sharpedgesandcoilsurfacesareapotentialinjuryhazard.Avoidcontactwiththem.

Warning:Movingmachineryandelectricalpowerhazard.Maycauseseverepersonnel injuryordeath.Disconnectandlockoffpowerbeforeservicingequipment.

TableofContents

Page 3: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

1

TM-F

DB

M-0

515-

C

1. Model Name

Indoor

FDB 10 C V1 M

Type of Air Conditioner

FDB : Ceiling Concealed (Lower Static Pressure)FDM : Ceiling Concealed (Higher Static Pressure)

Series

C : C Series

Power Supply

V1 : Single Phase, 220-240V, 50Hz

Controller

M : Wired Controller

Refrigerant

Blank : R22N : R410A

Capacity Index

10 : Based on Btu/hr

Page 4: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

2

TM-F

DB

M-0

515-

C

Outdoor

R 10 C V1

Type of Air Conditioner

R : Single Split Condensing Unit

Series

C : C seriesD : D seriesF : F series

Power Supply

V1 : Single Phase, 220-240V, 50HzY1 : Three Phase, 380-415V, 50Hz

Refrigerant

Blank : R22N : R410A

Capacity Index

10 : Based on Btu/hr

Page 5: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

3

TM-F

DB

M-0

515-

C

2. Features

Space Saving, Elegance and PrestigeThe unit is installed above the ceiling with only the supply and return air grille exposed to view. This ceiling concealed type of design has made it an “Evergreen” model without sacrificing the precious floor space. The air-conditioned space will appear as elegant and prestigious as centralized air-conditioned area but with only a fraction of the cost. This model is ideal for small offices, hotel rooms, hospitals and restaurant applications.

Double Protection Drainage SystemHigh humidity inside the ceiling area is always the main cause of water leaking. By introducing “Built In” double drain pans solution, i.e. primary drain pan and secondary drain pan, water leaking will not be a problem anymore. The high quality Polystyrene (PS) primary drain pan come with a layer of thermal forming High Impact Polystyrene (HIPS) coating. The primary drain pan is specially designed, with mould in gradient, for better condensate water drainage. Furthermore, the drain pan is made of PS, which is a very good insulation material to prevent sweating. The secondary drain pan will act as a drip pan to block any water that might be dripped down thus offering an additional protection to the ceiling. In such a case, additional drain pan will not be necessary during installation which means more cost saving. A drain socket is supplied to connect both drain pans to the drainage pipe.

Easy and Flexible InstallationThe physical height of the unit is only 378mm or less depends on the model, it is therefore offering greatest flexibility in selecting installation location. With its special designed installation accessories, the installation job become easy and better air distribution can be achieved without extra spending on duct works.

Easy MaintenanceThe simple design concept has a friendly maintenance and servicing in mind. Just loosening a few screws, remove secondary drain pan and drain guide, you can access to all the internal parts from the bottom of the unit. No water will splash down when removing the secondary drain pan makes the servicing work never easier before.

Medium Static Pressure with a Low Noise LevelThis series has a static pressure between 0 to 15 mmAq depend on duct work installation. The casing is well insulated internally to reduce the noise level.

Page 6: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

4

TM-F

DB

M-0

515-

C

3.Specifications

Specification (R22)Ceiling Concealed Type - FDBM-C Series

FDB10CV1MFDM10CV1M

R10CV1

FDB15CV1MFDM15CV1M

R15CV1Btu/h 10,000 13,000

W 2,930 3,809

HIGH ESP 924 1,331LOW ESP 903 1,277

HIGH ESP 4.1 6.0LOW ESP 4.0 5.7

V/Ph/Hz

HIGH l/s / CFM

142 / 300 241 / 510

MEDIUM l/s / CFM

135 / 285 231 / 490

LOW l/s / CFM

123 / 260 189 / 400

ESP (H/M/L) Pa (in.wg.)

49 / 44 / 36 (0.20 / 0.18 / 0.15) 49 / 42 / 28 (0.20 / 0.17 / 0.11)

HIGH l/s / CFM

142 / 300 241 / 540

MEDIUM l/s / CFM

135 / 275 231 / 500

LOW l/s / CFM

123 / 225 189 / 380

ESP (H/M/L) Pa (in.wg.)

10 / 8 / 5 (0.04 / 0.03 / 0.02) 10 / 8 / 5 (0.04 / 0.03 / 0.02)

1 2

mm/inmm/in

HIGH ESP 36 / 35 / 33 40 / 38 / 33LOW ESP 33 / 30 / 25 36 / 33 / 28

V/Ph/Hz

HIGH ESP 89 160LOW ESP 68 106

HIGH ESP 0.40 0.78LOW ESP 0.30 0.47

HIGH ESP 38 72LOW ESP 20 40

POLES 4

220-240 / 1 / 50

RATED INPUT POWER W

RATED RUNNING CURRENT

A

MOTOR OUTPUT W

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) 20INSULATION GRADE BPOWER SOURCE

SOUND PRESSURE LEVEL (H/M/L) dBA

GALVANIZED STEELDRIVE DIRECTDIAMETER 164 / 6.46LENGTH 202 / 7.95

FAN

IND

OO

R U

NIT

HIGH STATIC FAN MOTOR*

AIR FLOWLOW STATIC FAN MOTOR

AIR FLOW

TYPE CENTRIFUGAL FANQUANTITYMATERIAL

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE

CONTROLAIR DISCHARGE DUCTED

OPERATION WIRED REMOTE CONTROL

TOTAL RUNNING CURRENT - 1Ø [3Ø] A

POWER SOURCE 220-240 / 1 / 50REFRIGERANT TYPE R-22

MODEL INDOOR UNITSTANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE

OUTDOOR UNIT

TOTAL COOLING CAPACITY

TOTAL INPUT POWER W

FANMOTOR

COIL

AIRQUALITY

UNITDIMENSION

kg/lb 0.63 / 1.39 0.60 / 1.32REFRIGERANT CHARGE

mm/inmm/in

mm/inm2/ft2 0.115 / 1.238 0.143 / 1.542

12 14FIN PER INCH

ALUMINIUMTHICKNESS 0.11 / 0.004FACE AREAROW 3

TUBEMATERIAL COPPERDIAMETER 9.52 / 3/8THICKNESS 0.28 / 0.011

FIN

MATERIAL

pc

LENGTH mm/in 560 / 22.05 700 / 27.56WIDTH mm/in 195 / 7.68THICKNESS mm/in

AIRFILTER

TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 1

SIZE5 / 0.20

mm/in 261 / 10.3mm/in 765 / 30.1 905 / 35.6mm/in 411 / 16.2

HEIGHTWIDTHDEPTH

mm/in 376 / 14.8mm/in 951 / 37.4 1091 / 43.0mm/in 541 / 21.3

PACKINGDIMENSION

CASING

HEIGHTWIDTHDEPTH

kg/lb 18 / 39.7 22 / 48.5UNIT WEIGHT

COLOUR WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4

Page 7: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

5

TM-F

DB

M-0

515-

C

Specification (R-22)Ceiling Concealed Type - FDBM-C Series (CONT’D)

mm/in 7.00 / 0.276mm/in 0.28 / 0.011

ALUMINUM (RAISE LANCE)mm/in

m2/ft2 0.43 / 4.62120

TYPE

OIL TYPE

OIL AMOUNT cm3 / fl.oz. 320 / 11.3 350 / 11.8

INSULATION GRADE

POWER SOURCE V/Ph/Hz

CAPACITOR µF 30

RATED INPUT POWER W 783 1112

RATED RUNNING CURRENT A 3.5 5.0

LOCKED ROTOR AMP. A 19 21

mm/in

mm/in

mm/inmm/in

mm/in

mm/in

kg/lb 30 / 66 32 / 71

COLOUR IVORY WHITE

UNIT WEIGHT

CASING

HEIGHT 620 / 24.4WIDTH 810 / 31.9

DEPTH 330 / 13.0

UNITDIMENSION

HEIGHT 540 / 21.3

WIDTH 700 / 27.6

DEPTH 250 / 9.8

PACKING DIMENSION

0.11 / 0.004

FACE AREA

ROW

FIN PER INCH

COMPRESSOR

ROTARY

ATMOS NM56M or SUNISO 4GDID

E

220-240 / 1 / 50

TUBE

MATERIAL SEAMLESS INNER GROOVE COPPER

DIAMETER

THICKNESS

FIN

MATERIAL

THICKNESS

MODELINDOOR UNIT

OUTDOOR UNIT

l/s / CFM 453 / 960

mm/in

dBA 46 49

DRIVE DIRECTDIAMETER 401 / 15.8

SOUND PRESSURE LEVEL

AIR FLOW

TYPE PROPELLERQUANTITY 1MATERIAL ASG20

mm/in 6.35 / 1/4mm/in 9.52 / 3/8 12.7 / 1/2GAS

PIPE

FAN

FAN MOTOR

CONNECTION

COIL

TYPE FLARE

SIZELIQUID

V/Ph/HzW 52 74A 0.23

190.33

W 30RPM 730 860MOTOR SPEED

POLES 6

BPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUT

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) IP23INSULATION GRADE

OU

TD

OO

R U

NIT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

FDB10CV1M

FDM10CV1M

R10CV1

FDB15CV1M

FDM15CV1M

R15CV1

STANDARD STATIC PRESSURE

NON-STANDARD STATIC PRESSURE

Page 8: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

6

TM-F

DB

M-0

515-

C

Specification (R-22)Ceiling Concealed Type - FDBM-C Series

R18CV1 R20CV1Btu/h 18,000 20,000

W 5,274 5,860

HIGH ESP 1,945 1,930LOW ESP 1,907 1,892

HIGH ESP 8.5LOW ESP 8.5 8.3

V/Ph/Hz

HIGH l/s / CFMMEDIUM l/s / CFMLOW l/s / CFM

ESP (H/M/L) Pa (in.wg.)HIGH l/s / CFMMEDIUM l/s / CFMLOW l/s / CFM

ESP (H/M/L) Pa (in.wg.)

mm/inmm/in

HIGH ESPLOW ESP

V/Ph/Hz

HIGH ESPLOW ESP

HIGH ESPLOW ESP

HIGH ESPLOW ESP

mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4

MOTOR OUTPUT W8060

POLES 4

220-240 / 1 / 50RATED INPUTPOWER W 170

132

RATED RUNNING CURRENT A 0.79

0.54

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) 20INSULATION GRADE BPOWER SOURCE

181

0.820.58

DIAMETER 164 / 6.46LENGTH 202 / 7.95

SOUND PRESSURE LEVEL(H/M/L) dBA

42 / 41 / 4038 / 37 / 35

QUANTITY 2MATERIAL GALVANIZED STEELDRIVE DIRECT

330 / 703319 / 675302 / 640

20 / 19 / 15 (0.08 / 0.07 / 0.06)

TYPE CENTRIFUGAL FAN

HIGH STATIC FAN MOTOR*

AIR FLOW

330 / 700319 / 675302 / 640

49 / 45 / 41 (0.20 / 0.18 / 0.17)

LOW STATIC FAN MOTOR

AIR FLOW

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE

CONTROL AIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL

TOTAL RUNNING CURRENT - 1Ø [3Ø] A

POWER SOURCE 220-240 / 1 / 50REFRIGERANT TYPE R-22

MODEL INDOOR UNIT FDB20CV1MFDM20CV1M

OUTDOOR UNIT

TOTAL COOLING CAPACITY

TOTAL INPUT POWER W

kg/lb 0.90 / 1.98 0.83 / 1.83REFRIGERANT CHARGE

mm/inmm/inmm/inmm/inmm/inmm/inkg/lbUNIT WEIGHT

FAN

IND

OO

R U

NIT

FAN MOTOR

COIL

24 / 53

PACKINGDIMENSION

HEIGHT 376 / 14.8WIDTH 1251 / 49.3DEPTH 541 / 21.3

UNITDIMENSION

HEIGHT 261 / 10.3WIDTH 1065 / 41.9DEPTH 411 / 16.2

mm/inmm/in

mm/inm2/ft2

ROW 3FIN PER INCH 12

MATERIAL ALUMINIUMTHICKNESS 0.11 / 0.004FACE AREA 0.176 / 1.892

TUBEMATERIAL COPPERDIAMETER 9.52 / 3/8THICKNESS 0.28 / 0.011

FIN

pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in 5 / 0.20

AIRFILTER

CASING

TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 1

SIZE860 / 33.86195 / 7.68

COLOUR WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

STANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE

Page 9: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

7

TM-F

DB

M-0

515-

C

mm/in 7.00 / 0.276mm/in 0.23 / 0.009

ALUMINUMmm/inm2/ft2

IVORY WHITE

COMPRESSOR

FIN

COLOUR

MATERIALTHICKNESS 0.11 / 0.004FACE AREA 0.51 / 5.49

120

ROWFIN PER INCH

TUBEMATERIAL SEAMLESS INNER GROOVE COPPERDIAMETERTHICKNESS

COIL

CASING

MODEL INDOOR UNIT

OUTDOOR UNIT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

dBASOUND PRESSURE LEVEL 5152mm/inmm/inmm/inmm/inmm/inmm/inkg/lb 43 / 94.8UNIT WEIGHT

PACKING DIMENSION

HEIGHT 693 / 27.3WIDTH 990 / 39.0DEPTH 415 / 16.3

UNIT DIMENSION

HEIGHT 654 / 25.7WIDTH 855 / 33.7DEPTH 328 / 12.9

mm/in 6.35 / 1/4mm/in 15.88 / 5/8

PIPE CONNECTION

FAN

FAN MOTOR

OU

TD

OO

R U

NIT

TYPE

SIZELIQUIDGAS

FLARE

mm/inDIAMETER 457 / 17.9

TYPE PROPELLERQUANTITY 1MATERIAL ASG 20DRIVE DIRECT

l/s / CFMAIR FLOW 614 / 1300

V/Ph/HzWAW

RPMPOLES 68

220-240 / 1 / 50RATED INPUT POWER 77RATED RUNNING CURRENT 0.34MOTOR OUTPUTMOTOR SPEED

32680

TYPE INDUCTION

QUANTITY 1INDEX OF PROTECTION (IP) IP23INSULATION GRADE FPOWER SOURCE

cm3 / fl.oz.

V/Ph/HzµF 40 35

16727.3441

W 1698A 7.37

36A

POWER SOURCE 220-240 / 1 / 50CAPACITORRATED INPUT POWERRATED RUNNING CURRENTLOCKED ROTOR AMP.

TYPE ROTARYOIL TYPE SUNISO-4GSI/FREOL-K56OIL AMOUNT 600 / 20.3INSULATION GRADE E

FDB20CV1M

FDM20CV1M

STANDARD STATIC PRESSURE

NON-STANDARD STATIC PRESSURE

R18CV1 R20CV1

Specification (R-22)Ceiling Concealed Type - FDBM-C Series (CONT’D)

Page 10: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

8

TM-F

DB

M-0

515-

C

Specification (R-22)Ceiling Concealed Type - FDBM-C Series

R20CV1 R25CV1Btu/h 22,000 25,000

W 6,446 7,325

HIGH ESP 1,941 2,625LOW ESP 1,921 2,625

HIGH ESP 8.6 11.7LOW ESP 8.4 11.6

V/Ph/Hz

HIGH l/s / CFMMEDIUM l/s / CFMLOW l/s / CFM

ESP (H/M/L) Pa (in.wg.)HIGH l/s / CFMMEDIUM l/s / CFMLOW l/s / CFM

ESP (H/M/L) Pa (in.wg.)

mm/inmm/in

HIGH ESPLOW ESP

V/Ph/Hz

HIGH ESPLOW ESP

HIGH ESPLOW ESP

HIGH ESPLOW ESP

POLES 4

RATED RUNNING CURRENT A

0.820.70

MOTOR OUTPUT W9080

20INSULATION GRADE BPOWER SOURCE 220-240 / 1 / 50

RATED INPUT POWER W 181161

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP)

DIAMETER 164 / 6.46LENGTH 202 / 7.95

SOUND PRESSURE LEVEL (H/M/L) dBA41 / 40 / 3640 / 39 / 35

QUANTITY 2MATERIAL GALVANIZED STEELDRIVE DIRECT

345 / 730311 / 660270 / 580

20 / 18 / 11 (0.08 / 0.07 / 0.04)

TYPE CENTRIFUGAL FAN

FAN

FAN MOTOR

COIL

IND

OO

R U

NIT

HIGH STATIC FAN MOTOR*

AIR FLOW

345 / 730311 / 660274 / 580

49 / 43 / 30 (0.20 / 0.17 / 0.12)

LOW STATIC FAN MOTOR

AIR FLOW

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE

CONTROL AIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL

TOTAL RUNNING CURRENT - 1Ø [3Ø] A

POWER SOURCE 220-240 / 1 / 50REFRIGERANT TYPE R-22

MODEL INDOOR UNIT FDB25CV1MFDM25CV1M

OUTDOOR UNIT

TOTAL COOLING CAPACITY

TOTAL INPUT POWER W

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

kg/lb 1.40 / 3.08 1.10 / 2.43REFRIGERANT CHARGE

mm/inmm/inmm/inmm/inmm/inmm/inkg/lbUNIT WEIGHT 26 / 57.3

HEIGHT 376 / 14.8WIDTH 1386 / 54.6DEPTH 541 / 21.3

UNIT DIMENSION

HEIGHT 261 / 10.3WIDTH 1200 / 47.2DEPTH 411 / 16.2

PACKING DIMENSION

mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4

mm/inmm/in

mm/inm2/ft2

ROW 3FIN PER INCH 12

MATERIAL ALUMINIUMTHICKNESS 0.11 / 0.004FACE AREA 0.203 / 2.187

TUBEMATERIAL COPPERDIAMETER 9.52 / 3/8THICKNESS 0.28 / 0.011

FIN

pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in

AIR FILTER

CASING

TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 1

SIZE995 / 39.17195 / 7.685 / 0.20

WITHOUT POWDER PAINTCOLOUR

STANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE

Page 11: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

9

TM-F

DB

M-0

515-

C

mm/inmm/in

mm/inm2/ft2 0.51 / 5.49 0.61 / 6.58

120

cm3 / fl.oz. 600 / 20.3 700 / 24.6

V/Ph/HzµF 35 50W 1683 2323A 7.44 10.35A 41 56

220-240 / 1 / 50CAPACITORRATED INPUT POWERRATED RUNNING CURRENTLOCKED ROTOR AMP.

TYPE ROTARYOIL TYPE SUNISO 4GSI /FREAOL-K56 ATMOS NM56M OR SUNISO 4GDIDOIL AMOUNTINSULATION GRADE EPOWER SOURCE

THICKNESS 0.23 / 0.009

FIN

MATERIAL ALUMINUM (RAISE LANCE)THICKNESS 0.11 / 0.004FACE AREAROWFIN PER INCH

TUBEMATERIAL SEAMLESS INNER GROOVE COPPERDIAMETER 7.00 / 0.276

MODELINDOOR UNIT

OUTDOOR UNIT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

l/s / CFM 755 / 1600AIR FLOW 614 / 1300

dBA 51 52SOUND PRESSURE LEVELmm/in 654 / 25.7 756 / 29.8mm/in 855 / 33.7mm/in 328 / 12.9mm/in 693 / 27.3 793 / 31.2

mm/in 990 / 39.0

mm/in 415 / 16.3kg/lb 43 / 94.8 50 / 110

DEPTHUNIT WEIGHT

UNIT DIMENSION

HEIGHTWIDTHDEPTH

PACKING DIMENSION

HEIGHTWIDTH

mm/in 6.35 / 1/4 9.52 / 3/8mm/in 15.88 / 5/8

PIPE CONNECTION

FAN

FAN MOTOR

COMPRESSOR

OU

TDO

OR

UN

IT

COIL

CASING

TYPE

SIZELIQUIDGAS

FLARE

mm/inDIAMETER 455 / 17.9

TYPE PROPELLERQUANTITY 1

MATERIAL ASG 20DRIVE DIRECT

V/Ph/HzW 77

0.3432

680

1210.5360

840

AW

RPMPOLES 6

FPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTMOTOR SPEED

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) IP23INSULATION GRADE

COLOUR IVORY WHITE

R20CV1 R25CV1

FDB25CV1M

FDM25CV1M

STANDARD STATIC PRESSURE

NON-STANDARD STATIC PRESSURE

Specification (R-22)Ceiling Concealed Type - FDBM- C Series (CONT’D)

Page 12: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

10

TM-F

DB

M-0

515-

C

R28CV1 R30CV1Btu/h 28,000 30,000

W 8,204 8,790HIGH ESP 3,104 3,410LOW ESP 3,015 3,321HIGH ESP 15.5 14.6LOW ESP 15.5 14.2

V/Ph/Hz

HIGHSUPER HIGH

SUPER HIGH

l/s / CFMl/s / CFM

MEDIUM l/s / CFMLOW l/s / CFM

ESP (SH/H/M/L) Pa (in.wg.)

HIGH l/s / CFMl/s / CFM

MEDIUM l/s / CFMLOW l/s / CFM

ESP (SH/H/M/L) Pa (in.wg.)

mm/inmm/in

DIAMETER 214 / 8.43LENGTH 203 / 8.00

QUANTITY 2MATERIAL GALVANIZED STEELDRIVE DIRECT

392 / 830359 / 760335 / 710

49 / 39 / 29 / 20 (0.2 / 0.16 / 0.12 / 0.08)TYPE CENTRIFUGAL FAN

FAN

FAN MOTOR

COIL

AIRQUALITY

CASING

IND

OO

R U

NIT

HIGH STATIC FAN MOTOR

AIR FLOW 392 / 830425 / 900

425 / 900

359 / 760335 / 710

206 / 167 / 127 / 880.8 / 0.7 / 0.5 / 0.4)

LOW STATIC FAN MOTOR*

AIR FLOW

REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR CAP. TUBE

CONTROL AIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL

TOTAL RUNNING CURRENT - 1Ø [3Ø] A

POWER SOURCEREFRIGERANT TYPE R-22

MODEL INDOOR UNITFDM30CV1MFDB30CV1M

OUTDOOR UNITTOTAL COOLING CAPACITY

TOTAL INPUT POWER W

220-240 / 1 / 50

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

kg/lb 1.75 / 3.86 2.00 / 4.41REFRIGERANT CHARGE

HIGH ESPLOW ESP

SOUND PRESSURE LEVEL (H/M/L) dBA 46 / 44 / 42

41 / 40 / 39 / 36mm/inmm/inmm/inmm/inmm/inmm/inkg/lbUNIT WEIGHT 42 / 92.6

PACKING DIMENSION

HEIGHT 415 / 16.3WIDTH 1126 / 44.3DEPTH 631 / 24.8

UNIT DIMENSION

HEIGHT 378 / 14.9WIDTH 929 / 36.6DEPTH 541 / 21.3

mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4

V/Ph/HzHIGH ESPLOW ESPHIGH ESPLOW ESPHIGH ESPLOW ESP

POLES 4

RATED RUNNINGCURRENT A 1.36

0.95

MOTOR OUTPUT W 15085

INSULATION GRADE BPOWER SOURCE 220-240 / 1 / 50RATED INPUTPOWER W 306

217

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) 20

mm/inmm/in

mm/inm2/ft2

FIN PER INCH 12

ALUMINIUM (CORR. BARE FIN)THICKNESS 0.11 / 0.004FACE AREA 0.28 / 3.01ROW 3

TUBEMATERIAL COPPERDIAMETER 9.52 / 3/8THICKNESS 0.28 / 0.011

FIN

MATERIAL

pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in 5 / 0.20

AIR FILTER

COLOUR

TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 2

SIZE449 / 17.68305 / 12.01

WITHOUT POWDER PAINT

STANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE

Specification (R-22)Ceiling Concealed Type - FDBM-C Series

Page 13: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

11

TM-F

DB

M-0

515-

C

mm/inmm/in

mm/inm2/ft2

mm/in 756 / 29.8mm/in 855 / 33.7mm/in 328 / 12.9mm/in 793 / 31.2mm/in 990 / 39.0mm/in 416 / 16.4kg/lb 57 / 126

COLOUR IVORY WHITE

DEPTHUNIT WEIGHT

UNIT DIMENSION

HEIGHTWIDTHDEPTH

PACKING DIMENSION

HEIGHTWIDTH

18

FIN

MATERIAL ALUMINIUM (RAISE LANCE)THICKNESS 0.10 / 0.004FACE AREA 0.61 / 6.58ROW 2FIN PER INCH

TUBEMATERIAL INNER GROOVE COPPERDIAMETER 7.00 / 0.276THICKNESS 0.23 / 0.009

MODELINDOOR UNIT

OUTDOOR UNIT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

l/s / CFM 808 / 1712AIR FLOWdBA 54 56SOUND PRESSURE LEVEL

mm/inmm/in

PIPE CONNECTION

FAN

FAN MOTOR

COMPRESSOR

OU

TD

OO

R U

NIT

COIL

CASING

TYPE FLARE VALVE

SIZELIQUID 9.52 / 3/8GAS 15.88 / 5/8

mm/in 455 / 18DIAMETER

TYPE PROPELLERQUANTITY 1MATERIAL ASG 20DRIVE DIRECT

IP23

V/Ph/HzW 124A 0.54W

RPM66874

6 6

POWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTMOTOR SPEEDPOLES

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP)INSULATION GRADE F

cm3 / fl.oz. 1050 / 36 900 / 30

V/Ph/HzµF 60

W 2674 2980

A 13.6 12.7A 62 66

POWER SOURCE 220-240 / 1 / 50CAPACITORRATED INPUT POWERRATED RUNNING CURRENTLOCKED ROTOR AMP.

TYPE ROTARY TWIN ROTARY

OIL TYPE ATMOS NM32A1SUNISO 4GSIOIL AMOUNTINSULATION GRADE E

R28CV1 R30CV1

FDM30CV1MFDB30CV1M

STANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE

Specification (R-22)Ceiling Concealed Type - FDBM-C Series (CONT’D)

Page 14: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

12

TM-F

DB

M-0

515-

C

R35DV1 R40DY1Btu/h 35,000 40,000

W 10,255 11,720HIGH ESP 3,341 3,441LOW ESP 3,293 3,393HIGH ESP 16.2 [5.8]LOW ESP 15.91 [7.41]

220-240 / 1 / 50 380-415 / 3 / 50

HIGHSUPER HIGH

SUPER HIGH

l/s / CFMl/s / CFM

MEDIUM l/s / CFMLOW l/s / CFM

ESP (SH/H/M/L) Pa (in.wg.)

HIGH l/s / CFMl/s / CFM

MEDIUM l/s / CFMLOW l/s / CFM

ESP (SH/H/M/L) Pa (in.wg.)

mm/inmm/in

HIGH ESPLOW ESP

V/Ph/HzHIGH ESPLOW ESPHIGH ESPLOW ESPHIGH ESPLOW ESP

MOTOR OUTPUT W 180120

POLES 4

RATED INPUTPOWER W 384

336RATED RUNNING CURRENT A 1.75

1.46

INDEX OF PROTECTION (IP) 20INSULATION GRADE BPOWER SOURCE 220-240 / 1 / 50

IND

OO

R U

NIT

TYPE INDUCTIONQUANTITY 1

LENGTH 203 / 8.00

SOUND PRESSURE LEVEL(H/M/L)

dBA 51 / 49 / 45 / 4143 / 41 / 40 / 38

MATERIAL GALVANIZED STEELDRIVE DIRECTDIAMETER 214 / 8.43

467 / 990425 / 900

49 / 39 / 29 /20 (0.20 / 0.16 / 0.12 / 0.08)TYPE CENTRIFUGAL FANQUANTITY 2

HIGHSTATICFANMOTOR

AIR FLOW 500 / 1060519 / 1110

519 / 1110

467 / 990425 / 900

206 / 176 / 127 / 93 (0.8 / 0.7 / 0.5 / 0.4)

LOW STATIC FAN MOTOR*

AIR FLOW 500 / 1060

CONTROL AIR DISCHARGE DUCTEDWIRED REMOTE CONTROLOPERATION

FAN

FAN MOTOR

COIL

CASING

TOTAL RUNNING CURRENT - 1Ø [3Ø] A

POWER SOURCEREFRIGERANT TYPE R-22REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR CAP. TUBE

MODEL INDOOR UNITFDM40CV1MFDB40CV1M

OUTDOOR UNIT

TOTAL COOLING CAPACITY

TOTAL INPUT POWER W

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

kg/lb 1.90 / 4.19 2.50 / 5.51REFRIGERANT CHARGE

mm/inmm/inmm/inmm/inmm/inmm/inkg/lbUNIT WEIGHT 44 / 97

1045 / 41.1DEPTH 541 / 21.3

PACKING DIMENSION

HEIGHT 415 / 16.3WIDTH 1245 / 49.0DEPTH 631 / 24.8

UNIT DIMENSION

HEIGHT 378 / 14.9WIDTH

mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4

mm/inmm/in

mm/inm2/ft2

ROW 3FIN PER INCH 14

MATERIAL ALUMINIUM (CORR. BARE FIN)THICKNESS 0.11 / 0.004FACE AREA 0.31 / 3.34

TUBEMATERIAL SEAMLESS INNER SMOOTH COPPERDIAMETER 9.52 / 3/8THICKNESS 0.28 / 0.011

FIN

COLOUR WITHOUT POWDER PAINT

pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in

SIZE507 / 19.96305 / 12.01

5 / 0.20

AIR FILTER

AIR QUALITY

TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 2

STANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE

Specification (R-22)Ceiling Concealed Type - FDBM-C Series

Page 15: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

13

TM-F

DB

M-0

515-

C

mm/in 9.52 / 3/8 7.00 / 0.2760.23 / 0.009mm/in 0.28 / 0.011

ALUMINIUM (CORRUGATED)mm/in 0.11 / 0.004m2/ft2 0.87 / 9.36 0.85 / 9.15

1 216 18

COLOUR IVORY WHITE

COMPRESSOR

FIN

MATERIALTHICKNESSFACE AREAROWFIN PER INCH

TUBEMATERIAL INNER GROOVE COPPERDIAMETERTHICKNESS

COIL

CASING

MODEL INDOOR UNIT

OUTDOOR UNIT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

l/s / CFMAIR FLOW 1605 / 3400dBA 58SOUND PRESSURE LEVEL

mm/inmm/inmm/inmm/inmm/inmm/inkg/lb 78 / 172 85 / 187UNIT WEIGHT

PACKING

DIMENSION

HEIGHT 1010 / 39.8WIDTH 1180 / 46.5DEPTH 514 / 20.2

UNIT

DIMENSION

HEIGHT 852 / 33.5WIDTH 1030 / 40.6DEPTH 400 / 15.7

mm/inmm/inGAS 19.05 / 3/4

PIPE CONNECTION

FAN

FAN MOTOR

OU

TD

OO

R U

NIT

TYPE FLARE VALVE

SIZELIQUID 9.52 / 3/8

mm/inDIRECT

DIAMETER 610 / 24

TYPE PROPELLERQUANTITY 1MATERIAL ASG 20DRIVE

IP54

V/Ph/HzWAW

RPMPOLES 8

RATED INPUT POWER 257RATED RUNNING CURRENT 1.10MOTOR OUTPUTMOTOR SPEED

145625

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP)INSULATION GRADE BPOWER SOURCE 220-240 / 1 / 50

SUNISO 3GS MINERAL OILcm3 / fl.oz. 1242 / 42

B1400 / 47

FV/Ph/Hz 220-240 / 1 / 50 380-415 / 3 / 50

N/AµF 60

W 2700 2800A 13.35 [4.85]A 97 [48]

RATED INPUT POWERRATED RUNNING CURRENT - 1Ø [3Ø]LOCKED ROTOR AMP. - 1Ø [3Ø]

TYPE SCROLLOIL TYPEOIL AMOUNTINSULATION GRADEPOWER SOURCECAPACITOR

R35DV1 R40DY1

FDM40CV1M

FDB40CV1MSTANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE

Specification (R-22)Ceiling Concealed Type - FDBM-C Series (CONT’D)

Page 16: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

14

TM-F

DB

M-0

515-

C

FDM50CV1MFDB50CV1M

R50DY1

FDM60CV1MFDB60CV1M

R61DY1Btu/h 50,000 60,000

W 14,650 17,580HIGH ESP 5,067 7,010LOW ESP 4,984 7,005HIGH ESP [8.7] [11.5]LOW ESP [10.77] [14.14]

V/Ph/Hz

V/Ph/HzHIGH ESP 603 610LOW ESP 520 605HIGH ESP 2.60 2.68LOW ESP 2.20 2.68HIGH ESP 400 500LOW ESP 210 320MOTOR OUTPUT W

POLES 4

POWER SOURCE 220-240 / 1 / 50RATED INPUTPOWER W

RATED RUNNING CURRENT A

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) 20INSULATION GRADE B

FAN

FAN MOTOR

COIL

AIRQUALITY

CASING

INDOOR CAP. TUBE

CONTROLAIR DISCHARGE DUCTEDOPERATION

IND

OO

R U

NIT

WIRED REMOTE CONTROL

TOTAL RUNNING CURRENT - 1Ø [3Ø] A

POWER SOURCE 380-415 / 3 / 50REFRIGERANT TYPEREFRIGERANT CONTROL (EXPANSION DEVICE)REFRIGERANT CHARGE

R-22

MODEL INDOOR UNIT

OUTDOOR UNIT

TOTAL COOLING CAPACITY

TOTAL INPUT POWER W

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

COLOUR WITHOUT POWDER PAINT

kg/lb 2.45 / 5.40 4.80 / 10.58

HIGH ESP 53 / 52 / 50 / 47 55 / 53 / 50 / 47LOW ESP 46 / 44 / 43 / 42 48 / 47 / 46 / 45

SOUND PRESSURE LEVEL(H/M/L) dBA

mm/in 378 / 14.9mm/in 1299 / 51.1 1499 / 59.0mm/in 541 / 21.3mm/in 415 / 16.3mm/in 1497 / 59.0 1701 / 67.0mm/in 631 / 24.8kg/lb 50 / 110 56 / 123

HEIGHTWIDTHDEPTH

UNIT WEIGHT

UNIT DIMENSION

HEIGHTWIDTHDEPTH

PACKING DIMENSION

mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4

HIGH l/s / CFM

651 / 1380 722 / 1530

MEDIUM l/s / CFM

604 / 1280 675 / 1430

LOW l/s / CFM

571 / 1210 609 / 1290

ESP (SH/H/M/L) Pa (in.wg.)

78 / 59 / 39 / 20 (0.31 / 0.24 / 0.16 / 0.08) 69 / 49 / 29 / 20 (0.28 / 0.20 / 0.12 / 0.08)

mm/inmm/inLENGTH 203 / 8.00

MATERIAL GALVANIZED STEELDRIVE DIRECTDIAMETER 214 / 8.43

HIGHSUPER HIGH

SUPER HIGH

l/s / CFMl/s / CFM

651 / 1380

750 / 1590

722 / 1530

779 / 1650

750 / 1590 779 / 1650

MEDIUM l/s / CFM

604 / 1280 675 / 1430

LOW l/s / CFM

571 / 1210 609 / 1290

ESP (SH/H/M/L) Pa (in.wg.)

176 / 157 / 137 / 108 (0.7 / 0.6 / 0.6 / 0/4) 176 / 157 / 137 / 98 (0.7 . 0.6 / 0.6 / 0.4)

HIGH STATIC FAN MOTOR

AIR FLOWLOW STATIC FAN MOTOR*

AIR FLOW

TYPE CENTRIFUGAL FANQUANTITY 2

mm/inmm/in

mm/inm2/ft2 0.40 / 4.31 0.47 / 5.06

3FIN PER INCH 14

9.52 / 3/8THICKNESS 0.28 / 0.011

FIN

MATERIAL ALUMINIUMTHICKNESS 0.11 / 0.004FACE AREAROW

TUBEMATERIAL COPPERDIAMETER

pcLENGTH mm/in 634 / 24.96 734 / 28.90WIDTH mm/in 305 / 12.01THICKNESS mm/in

2

SIZE5 / 0.20

AIR FILTER

TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY

STANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE

Specification (R-22)Ceiling Concealed Type - FDBM-C Series

Page 17: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

15

TM-F

DB

M-0

515-

C

mm/in 7.00 / 0.276 9.52 / 3/8mm/in 0.23 / 0.009

ALUMINIUM (COPRRUGATED)mm/in 0.11 / 0.004m2/ft2 0.85 / 9.15 0.87 / 9.36

2 318 16

MINERAL OIL (SONITEX 200LT)cm3 / fl.oz. 1400 / 47

F1705 / 57.7

V/Ph/HzµFW 4207 6128A [7.47] [10.18]A [59] [74]

COLOUR IVORY WHITE

N/ARATED INPUT POWERRATED RUNNING CURRENT - 1Ø [3Ø]LOCKED ROTOR AMP. - 1Ø [3Ø]

TYPE SCROLL

OIL TYPEOIL AMOUNTINSULATION GRADE -POWER SOURCECOMPRESSOR 380-415 / 3 / 50CAPACITOR

MATERIALTHICKNESSFACE AREAROWFIN PER INCH

TUBEMATERIAL INNER GROOVE COPPERDIAMETERTHICKNESS

FIN

COIL

CASING

MODEL

OU

TD

OO

R U

NIT

INDOOR UNIT

OUTDOOR UNIT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

l/s / CFM 1605 / 3400 1793 / 3800AIR FLOWdBA 58 61SOUND PRESSURE LEVEL

mm/in 852 / 33.5mm/in 1030 / 40.6mm/in 400 / 15.7mm/in 1010 / 39.8mm/in 1180 / 46.5mm/in 514 / 20.2kg/lb 88 / 194

HEIGHTWIDTHDEPTH

UNIT WEIGHT

UNIT DIMENSION

HEIGHTWIDTHDEPTH

PACKING DIMENSION

105 / 231

mm/in 9.52 / 3/8 12.7 / 1/2mm/in

PIPE CONNECTION

FAN

FAN MOTOR

TYPE FLARE VALVE

SIZE LIQUIDGAS 19.05 / 3/4

mm/in 610 / 24

MATERIAL ASG 20DRIVE DIRECTDIAMETER

TYPE PROPELLERQUANTITY 1

IP54F

V/Ph/HzW 257 272A 1.10 1.28W

RPM145625

8POLES

INSULATION GRADEPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTMOTOR SPEED

TYPE INDUCTION

QUANTITY 1INDEX OF PROTECTION (IP)

FDM50CV1MFDB50CV1M

R50DY1

FDM60CV1MFDB60CV1M

R61DY1

STANDARD STATIC PRESSURE

NON-STANDARD STATIC PRESSURE

Specification (R-22)Ceiling Concealed Type - FDBM-C Series (CONT’D)

Page 18: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

16

TM-F

DB

M-0

515-

C

FDMN10CV1MRN10FV1

FDMN15CV1MRN15FV1

Btu/h 9,000 12,000W 2,638 3,517W 970 1,430A 4.35 6.41

V/Ph/Hz

S. HIGH l/s / CFM - -HIGH l/s / CFM 118 / 250 193 / 410MEDIUM l/s / CFM 111 / 235 174 / 370LOW l/s / CFM 99 / 210 118 / 250

ESP (H/M/L) Pa (in.wg.) 29 / 20 / 10 (0.11 / 0.08 / 0.04)

1 2

mm/inmm/in

SOUND PRESSURE LEVEL (H/M/L) dBA 33 / 30 / 26 37 / 34 / 29

V/Ph/HzW 61 107A 0.27 0.48W 30 50

MODELINDOOR UNITOUTDOOR UNIT

TOTAL COOLING CAPACITY

TOTAL INPUT POWERTOTAL RUNNING CURRENT - 1Ø [3Ø]POWER SOURCE 220-240 / 1 / 50REFRIGERANT TYPE R-410AREFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE

CONTROLAIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL

HIGH STATIC FAN MOTOR

AIR FLOW

TYPE CENTRIFUGAL FANQUANTITYMATERIAL GALVANIZED STEELDRIVE DIRECTDIAMETER 160 / 6.30LENGTH 202 / 7.95

FAN MOTOR

COIL

AIRQUALITY

CASING

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) NAINSULATION GRADE E BPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTPOLES 4

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

kg/lb 0.80 / 1.76 0.83 / 1.83REFRIGERANT CHARGE

mm/in 261 / 10.3mm/in 765 / 30.1 905 / 35.6mm/in 411 / 16.2mm/in 376 / 14.8mm/in 951 / 37.4 1091 / 43.0mm/in 541 / 21.3kg/lb 18 / 40 22 / 49

UNIT DIMENSION

HEIGHTWIDTHDEPTH

PACKING DIMENSION

HEIGHTWIDTHDEPTH

UNIT WEIGHT

FAN

IND

OO

R U

NIT

mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4

mm/inmm/in

mm/inm2/ft2 0.115 / 1.238 0.143 / 1.542

TUBEMATERIAL COPPERDIAMETER 7.00 / 0.276THICKNESS 0.28 / 0.011

FIN

MATERIAL ALUMINIUM (CORR. FIN)THICKNESS 0.11 / 0.0043FACE AREAROW 3FIN PER INCH 18

pcLENGTH mm/in 560 / 22.05 700 / 27.56WIDTH mm/in 195 / 7.68THICKNESS mm/in

AIRFILTER

TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 1

SIZE5 / 0.20

COLOUR WITHOUT POWDER PAINT

Specification (R-410A)Ceiling Concealed Type - FDMN-C Series

Page 19: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

17

TM-F

DB

M-0

515-

C

FDMN10CV1M

RN10FV1

FDMN15CV1M

RN15FV1

mm/in 7.00 / 0.276mm/in 0.2 / 0.0079

ALUMINUMmm/inm2/ft2 0.33 / 3.55 0.32 / 3.44

2118

MODELINDOOR UNIT

OUTDOOR UNIT

OU

TD

OO

R U

NIT

TUBEMATERIAL COPPERDIAMETERTHICKNESS

FIN

MATERIALTHICKNESS 0.1 / 0.0039FACE AREAROWFIN PER INCH

COLOUR IVORY WHITE

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

l/s / CFM 438 / 927 390 / 827AIR FLOW

dBA 46 48SOUND PRESSURE LEVEL

mm/inmm/inmm/in

mm/inmm/inmm/inkg/lb

UNIT DIMENSION

HEIGHT 550 / 21.7WIDTH 658 / 25.9DEPTH 273 / 10.7

PACKING DIMENSION

HEIGHT 580 / 22.8WIDTH 775 / 30.5DEPTH 355 / 14.0

UNIT WEIGHT 28 / 61.7 29 / 63.9

mm/in 6.35 / 1/4mm/in 9.52 / 3/8 12.7 / 1/2

PIPECONNECTION

FAN

FAN MOTOR

COMPRESSOR

COIL

CASING

TYPE FLARE

SIZELIQUID

GAS

mm/in

TYPE PROPELLER

QUANTITY 1

MATERIAL ASG 20

DRIVE DIRECTDIAMETER 370 / 14.6

V/Ph/Hz

W 50 51

A 0.22 0.23

W 20

RPM 930 920

TYPE INDUCTION

QUANTITY 1

INDEX OF PROTECTION (IP) IP23

INSULATION GRADE B

POWER SOURCE 220-240 / 1 / 50

RATED INPUT POWER

RATED RUNNING CURRENT

MOTOR OUTPUT

MOTOR SPEED

POLES 6

TYPEOIL TYPE

OIL AMOUNT cm3 / fl.oz. 330 / 11.2HAF68D1

320 / 10.8NMOCZe-Gles RB68EP

INSULATION GRADEPOWER SOURCE V/Ph/HzCAPACITOR µF 35

RATED INPUT POWER W 859 1272

RATED RUNNING CURRENT A 3.86 5.7

LOCKED ROTOR AMP. A 18.0 24.5

ROTARY

E220-240 / 1 / 50

Specification (R-410A)Ceiling Concealed Type - FDMN-C Series(CONT’D)

Page 20: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

18

TM-F

DB

M-0

515-

C

FDMN20CV1MRN20CV1

FDMN25CV1MRN25CV1

Btu/h 18,000 21,000W 5,275 6,155W 1,870 2,150A 8.26 9.56

V/Ph/Hz

S. HIGH l/s / CFM - -HIGH l/s / CFM 269 / 570 326 / 690MEDIUM l/s / CFMLOW l/s / CFM

ESP (H/M/L) Pa (in.wg.) 29 / 20 / 10 (0.11 / 0.08 / 0.04)

mm/inmm/in

V/Ph/HzW 133 164A 0.61 0.74W 80 100

4

MODELINDOOR UNITOUTDOOR UNIT

TOTAL COOLING CAPACITY

TOTAL INPUT POWERTOTAL RUNNING CURRENT - 1Ø [3Ø]POWER SOURCE 220-240 / 1 / 50REFRIGERANT TYPEREFRIGERANT CHARGE

R-410A

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE

CONTROLAIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL

HIGH STATIC FAN MOTOR

AIR FLOW

TYPE CENTRIFUGAL FANQUANTITY 2MATERIAL GALVANIZED STEELDRIVE DIRECTDIAMETER 160 / 6.30LENGTH 202 / 7.95

B

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) NAINSULATION GRADE EPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTPOLES

311 / 660 253 / 536

263 / 558227 / 480

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

kg/lb 1.45 / 3.20 1.65 / 3.64

SOUND PRESSURE LEVEL (H/M/L) dBA 38 / 36 / 34 40 / 39 / 36mm/in 261 / 10.3mm/in 1065 / 41.9 1200 / 47.2mm/in 411 / 16.2mm/in 376 / 14.8mm/in 1251 / 49.3 1386 / 54.6mm/in 541 / 21.3kg/lb 24 / 53 26 / 57UNIT WEIGHT

FAN

FAN MOTOR

IND

OO

R U

NIT

COIL

UNIT DIMENSION

HEIGHTWIDTHDEPTH

PACKING DIMENSION

HEIGHTWIDTHDEPTH

mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4

mm/inmm/in

mm/inm2/ft2 0.176 / 1.892 0.203 / 2.187

3FIN PER INCH 18

7.00 / 0.276THICKNESS 0.28 / 0.011

FIN

MATERIAL ALUMINIUM (SLIT FIN)THICKNESS 0.11 / 0.0043FACE AREAROW

TUBEMATERIAL COPPERDIAMETER

pcLENGTH mm/in 860 / 33.86 995 / 39.17WIDTH mm/in 195 / 7.68THICKNESS mm/in 5 / 0.20

AIRFILTER

COLOURCASING

TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 1

SIZE

WITHOUT POWDER PAINT

Specification (R-410A)Ceiling Concealed Type - FDMN-C Series

Page 21: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

19

TM-F

DB

M-0

515-

C

mm/inmm/in

mm/in

m2/ft2 0.51 / 5.491

20

0.50 / 5.38

18

0.2 / 0.0079

FIN

COLOUR

MATERIAL ALUMINUMTHICKNESS 0.1 / 0.0039

IVORY WHITE

FACE AREAROW 2FIN PER INCH

OU

TD

OO

R U

NIT

TUBEMATERIAL COPPERDIAMETER 7.00 / 0.276THICKNESS

MODELINDOOR UNITOUTDOOR UNIT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

l/s / CFM 675 / 1430 755 / 1600AIR FLOWdBASOUND PRESSURE LEVEL 5249

mm/in 654 / 25.7mm/in 855 / 33.7mm/in 328 / 12.9mm/in 693 / 27.3mm/in 990 / 39.0mm/in 415 / 16.3kg/lb 43 / 94.8 47 / 103.6UNIT WEIGHT

UNIT DIMENSION

HEIGHTWIDTHDEPTH

PACKING DIMENSION

HEIGHTWIDTHDEPTH

mm/in 6.4 / 1/4mm/in 12.7 / 1/2 15.9 / 5/8

PIPECONNECTION

FAN

FAN MOTOR

COMPRESSOR

COIL

CASING

TYPE FLARE

SIZELIQUIDGAS

mm/in

TYPE PROPELLERQUANTITY 1MATERIAL ASG 20DRIVE DIRECTDIAMETER 455 / 17.9

V/Ph/HzW 78 121A 0.34

32710

0.53

WRPM

61

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) IP23INSULATION GRADE FPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTMOTOR SPEEDPOLES 6

840

cm3 / fl.oz. 670 / 22.7

V/Ph/HzµF 50W 1659 1865A 7.31 8.29A 32

POWER SOURCECAPACITORRATED INPUT POWERRATED RUNNING CURRENTLOCKED ROTOR AMP.

TYPE ROTARYOIL TYPE FV50SOIL AMOUNTINSULATION GRADE E

220-240 / 1 / 50

FDMN20CV1MRN20CV1

FDMN25CV1MRN25CV1

Specification (R-410A)Ceiling Concealed Type - FDMN-C Series(CONT’D)

Page 22: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

20

TM-F

DB

M-0

515-

C

Btu/hWWA

V/Ph/Hz

S.HIGH l/s / CFMHIGH l/s / CFMMEDIUM l/s / CFMLOW l/s / CFM

ESP (H/M/L) Pa (in.wg.)

mm/inmm/in

mm/in 19.1 / 3/4

GALVANIZED STEELDIRECT

185 / 7.28203 / 7.99

382 / 810363 / 770335 / 710

98 / 78 / 68 / 59 (0.39/0.31/0.28/0.24)CENTRIFUGAL FAN

2

220-240 / 1 / 50R-410A

OUTDOOR CAP. TUBE

DUCTEDWIRED REMOTE CONTROL

401 / 850

FDMN30CV1MRN28CV1

26,0007,6202,89212.8

INDOOR CONDENSATE DRAIN SIZE

FAN

FAN MOTOR

COIL

AIRQUALITY

CASING

IND

OO

R U

NIT

HIGH STATIC FAN MOTOR

AIRFLOW

TYPEQUANTITYMATERIALDRIVEDIAMETERLENGTH

POWER SOURCEREFRIGERANT TYPEREFRIGERANT CONTROL (EXPANSION DEVICE)

CONTROL AIR DISCHARGEOPERATION

MODELINDOOR UNITOUTDOOR UNIT

TOTAL COOLING CAPACITY

TOTAL INPUT POWERTOTAL RUNNING CURRENT - 1Ø [3Ø]

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

kg/lb 1.80 / 3.97REFRIGERANT CHARGE

SOUND PRESSURE LEVEL (H/M/L) dBA 44 / 41 / 38 / 34mm/inmm/inmm/inmm/inmm/inmm/inkg/lb

600 / 23.6343 / 13.51138 / 44.8690 / 27.2

40 / 88

285 / 11.2932 / 36.7

UNIT WEIGHT

UNIT DIMENSION

HEIGHTWIDTHDEPTH

PACKING DIMENSION

HEIGHTWIDTHDEPTH

WAW

2691.283204

INDUCTION1

IP20B

220-240 / 1 / 50

POLES

TYPEQUANTITYINDEX OF PROTECTION (IP)INSULATION GRADEPOWER SOURCERATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUT

mm/inmm/in

mm/inm2/ft2

ALUMINIUM (HYDROPHILIC FIN)0.11 / 0.00430.24 / 2.62

318

COPPER7.00 / 0.2760.28 / 0.011

FIN

MATERIALTHICKNESSFACE AREAROWFIN PER INCH

TUBEMATERIALDIAMETERTHICKNESS

pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in

456 / 17.95210 / 8.275 / 0.20

AIRFILTER

COLOUR

TYPEQUANTITY

SIZE

WASHABLE SARANET FILTER (OPTIONAL)2

WITHOUT POWDER PAINT

Specification (R-410A)Ceiling Concealed Type - FDMN-C Series

Page 23: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

21

TM-F

DB

M-0

515-

C

mm/inmm/in

mm/inm2/ft2

mm/inmm/inmm/inmm/inmm/inmm/inkg/lb

855 / 33.7328 / 12.9793 / 31.2990 / 39.0416 / 16.457 / 125.7

756 / 29.8

18

IVORY WHITE

7.00 / 0.2760.23 / 0.009ALUMINIUM0.11 / 0.00430.61 / 6.58

2

COPPER

UNIT WEIGHT

UNIT

DIMENSION

HEIGHTWIDTHDEPTH

PACKING DIMENSION

HEIGHTWIDTHDEPTH

FIN PER INCH

TUBEMATERIALDIAMETERTHICKNESS

FIN

COLOUR

MATERIALTHICKNESSFACE AREAROW

MODELINDOOR UNIT

OUTDOOR UNIT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

l/s / CFM 808 / 1712AIR FLOWdBA 54SOUND PRESSURE LEVEL

mm/inmm/in

FLARE VALVE9.52 / 3/815.88 / 5/8

PIPECONNECTION

FAN

OU

TD

OO

R U

NIT

FAN MOTOR

COMPRESSOR

COIL

CASING

TYPE

SIZELIQUIDGAS

mm/in

PROPELLER1

ASG 20

DIRECT455 / 17.9

TYPEQUANTITYMATERIALDRIVEDIAMETER

V/Ph/HzWAW

RPM

6

IP23F

220-240 / 1 / 501240.5466874

INDUCTION1

POLES

TYPEQUANTITYINDEX OF PROTECTION (IP)INSULATION GRADEPOWER SOURCERATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTMOTOR SPEED

cm3 / fl.oz.

V/Ph/HzµFWAA

220-240 / 1 / 5045

249910.98

63

SCROLL

FV50S

1130 / 38E

RATED RUNNING CURRENTLOCKED ROTOR AMP.

TYPEOIL TYPE

OIL AMOUNTINSULATION GRADEPOWER SOURCECAPACITORRATED INPUT POWER

FDMN30CV1M

RN28CV1

Specification (R-410A)Ceiling Concealed Type - FDMN-C Series (COND’T)

Page 24: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

22

TM-F

DB

M-0

515-

C

RN35DV1 RN40DY1Btu/h 32,000 39,000

W 9,379 11,430W 3,287 4,287A 15.2 [7.4]

V/Ph/Hz 220-240 / 1 / 50 380-415 / 3 / 50

S.HIGH l/s / CFMHIGH l/s / CFMMEDIUM l/s / CFMLOW l/s / CFM

ESP(H/M/L) Pa (in.wg.)

mm/inmm/in

V/Ph/HzWAW

kg/lb 2.00 / 4.41 2.32 / 5.11REFRIGERANT CHARGE

RATED RUNNING CURRENT 2.27MOTOR OUTPUT 470

POLES 4

IP21INSULATION GRADE BPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWER 503

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP)

DIAMETER 214 / 8.43LENGTH 203.2 / 8.00

CENTRIFUGAL FANQUANTITY 2MATERIAL GALVANIZED STEELDRIVE DIRECT

HIGH STATIC FAN MOTOR

AIR FLOW

604 / 1280547 / 1160496 / 1050434 / 920

118 / 96 / 78 / 61 (0.47 / 0.39 / 0.31 / 0.24)TYPE

REFRIGERANT TYPE R-410AREFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE

CONTROLAIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL

FDMN40CV1MOUTDOOR UNIT

TOTAL COOLING CAPACITY

TOTAL INPUT POWERTOTAL RUNNING CURRENT - 1Ø [3Ø]POWER SOURCE

MODELINDOOR UNIT

WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

SOUND PRESSURE LEVEL (H/M/L) dBA 52 / 49 / 47 / 45mm/inmm/inmm/inmm/inmm/inmm/inkg/lbUNIT WEIGHT

FAN

FAN MOTOR

IND

OO

R U

NIT

COIL

AIRQUALITY

CASING

49 / 108

638 / 25.1

PACKING DIMENSION

HEIGHT 355 / 14.0WIDTH 1461 / 57.5DEPTH 727 / 28.6

UNIT DIMENSION

HEIGHT 315 / 12.4WIDTH 1257 / 49.5DEPTH

mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4

mm/inmm/in

mm/inm2/ft2

ROW 3FIN PER INCH 18

MATERIAL ALUMINIUM (HYDROPHILIC FIN)THICKNESS 0.11 / 0.0043FACE AREA 0.34 / 3.61

TUBEMATERIAL COPPERDIAMETER 7.00 / 0.276THICKNESS 0.28 / 0.011

FIN

pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in

230 / 9.065 / 0.20

AIRFILTER

COLOUR

TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 2

SIZE608 / 23.94

Specification (R-410A)Ceiling Concealed Type - FDMN-C Series

Page 25: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

23

TM-F

DB

M-0

515-

C

mm/inmm/in

mm/inm2/ft2

cm3 / fl.oz. 1242 / 42 1951 / 66

V/Ph/Hz 220-240 / 1 / 50 380-415 / 3 / 50

µF 60 N/AW 2527 3527

A 11.83 [6.28]

A 97 [64]LOCKED ROTOR AMP. - 1Ø [3Ø]

INSULATION GRADE EPOWER SOURCECAPACITORRATED INPUT POWERRATED RUNNING CURRENT - 1Ø [3Ø]

2FIN PER INCH 18

IVORY WHITE

TYPE SCROLLOIL TYPE POE OILOIL AMOUNT

THICKNESS 0.23 / 0.009

FIN

COLOUR

MATERIAL ALUMINIUM (CORR. FIN)THICKNESS 0.11 / 0.0043

FACE AREA 0.85 / 9.15ROW

TUBE

MATERIAL COPPERDIAMETER 7.00 / 0.276

MODELINDOOR UNIT

OUTDOOR UNIT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

l/s / CFMAIR FLOW 1605 / 3400

dBA 58SOUND PRESSURE LEVELmm/inmm/inmm/inmm/inmm/inmm/inkg/lbUNIT WEIGHT 86 / 190

PACKING

DIMENSION

HEIGHT 1010 / 39.8WIDTH 1180 / 46.5DEPTH 514 / 20.2

UNIT

DIMENSION

HEIGHT 852 / 33.5WIDTH 1030 / 40.6DEPTH 400 / 15.7

95 / 209

mm/in

mm/inGAS 15.88 / 5/8

PIPECONNECTION

FAN

OU

TD

OO

R U

NIT

FAN MOTOR

COMPRESSOR

COIL

CASING

TYPE FLARE VALVE

SIZELIQUID 9.52 / 3/8

mm/inDIAMETER 610 / 24

QUANTITY 1

MATERIAL ASG 20

DRIVE DIRECT

TYPE PROPELLER

V/Ph/HzW

A

W

RPM

POLES 8

220-240 / 1 / 50

RATED INPUT POWER 257

RATED RUNNING CURRENT 1.10

MOTOR OUTPUT

MOTOR SPEED

145

625

TYPE INDUCTION

QUANTITY 1

INDEX OF PROTECTION (IP) IP54

INSULATION GRADE B F

POWER SOURCE

RN35DV1 RN40DY1

FDMN40CV1M

Specification (R-410A)Ceiling Concealed Type - FDMN-C Series (COND’T)

Page 26: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

24

TM-F

DB

M-0

515-

C

FDMN50CV1MRN50DY1

FDMN60CV1MRN61DY1

Btu/h 45,000 55,000W 13,189 16,120W 4,931 5,758A [8.5] [9.4]

V/Ph/Hz

S. HIGH l/s / CFM 675 / 1430 812 / 1720HIGH l/s / CFM 623 / 1320 732 / 1550MEDIUM l/s / CFM 580 / 1230 632 / 1340LOW l/s / CFM 533 / 1130 552 / 1170

ESP (H/M/L) Pa (in.wg.) 147 / 126 / 109 / 92 (0.59 / 0.50 / 0.44/ 0.37) 147 / 120 / 90 / 69 (0.59 / 0.48 / 0.36 /0.28)

mm/in

SOUND PRESSURE LEVEL (H/M/L) dBA 54 / 53 / 52 / 51 54 / 52 / 50 / 46

V/Ph/HzW 515 659A 2.32 2.91W 480 600

mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4

RATED RUNNING CURRENTMOTOR OUTPUTPOLES 4

IP20INSULATION GRADE BPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWER

TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP)

DIRECTDIAMETER 214 / 8.43LENGTH 203.2 / 8.00

IND

OO

R U

NIT

HIGH STATIC FAN MOTOR

AIRFLOW

TYPE CENTRIFUGAL FANQUANTITY 2MATERIAL GALVANIZED STEELDRIVE

CONTROLAIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL

POWER SOURCE 380-415 / 3 / 50REFRIGERANT TYPE R-410AREFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE & TXV

MODELINDOOR UNITOUTDOOR UNIT

TOTAL COOLING CAPACITY

TOTAL INPUT POWERTOTAL RUNNING CURRENT - 1Ø [3Ø]

mm/in

kg/lb 2.10 / 4.63 2.90 / 6.39REFRIGERANT CHARGE

mm/in 378 / 14.9mm/in 1299 / 51.1 1499 / 59.0mm/in 541 / 21.3mm/in 415 / 16.3mm/in 1497 / 59.0 1701 / 67.0mm/in 631 / 24.8kg/lb 50 / 110 56 / 123UNIT WEIGHT

FAN

FAN MOTOR

COIL

UNIT DIMENSION

HEIGHTWIDTHDEPTH

PACKING DIMENSION

HEIGHTWIDTHDEPTH

mm/inmm/in

mm/inm2/ft2 0.40 / 4.40 0.47 / 5.16

318 20FIN PER INCH

7.00 / 0.276THICKNESS 0.28 / 0.011

FIN

MATERIAL ALUMINIUM (HYDROPHILIC FIN)THICKNESS 0.11 / 0.0043FACE AREAROW

TUBEMATERIAL COPPERDIAMETER

pcLENGTH mm/in 634 / 24.96 734 / 28.90WIDTH mm/in 305 / 12.01THICKNESS mm/in

AIRFILTER

COLOUR

AIRQUALITY

CASING

TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 2

SIZE5 / 0.20

WITHOUT POWDER PAINT

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

Specification (R-410A)Ceiling Concealed Type - FDMN-C Series

Page 27: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

25

TM-F

DB

M-0

515-

C

mm/inmm/in

mm/in 0.10 / 0.004

m2/ft2 0.85 / 9.15 0.84 / 9.04

2 3

18

IVORY WHITE

mm/in 852 / 33.5mm/in 1030 / 40.6mm/in 400 / 15.7mm/in 1010 / 39.8mm/in 1180 / 46.5mm/in 514 / 20.2kg/lb 98 / 216UNIT WEIGHT

UNIT

DIMENSION

HEIGHTWIDTHDEPTH

PACKING

DIMENSION

HEIGHTWIDTHDEPTH

MATERIAL ALUMINIUM (CORR. FIN)THICKNESSFACE AREAROWFIN PER INCH

TUBE

MATERIAL INNER GROOVE COPPERDIAMETER 7.00 / 0.276THICKNESS 0.23 / 0.009

FIN

COLOUR

MODELINDOOR UNIT

OUTDOOR UNIT

OU

TD

OO

R U

NIT

105 / 231

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.

l/s / CFMAIR FLOW 1442 / 3056

dBA 60 65SOUND PRESSURE LEVEL

mm/in 9.52 / 3/8mm/in 15.88 / 5/8 19.05 / 3/4

PIPECONNECTION

FAN

FAN MOTOR

COMPRESSOR

COIL

CASING

TYPE FLARE VALVE

SIZELIQUID

GAS

mm/inDIAMETER 610 / 24

QUANTITY 1

MATERIAL ASG 20

DRIVE DIRECT

TYPE PROPELLER

F

V/Ph/Hz

W

A

W

RPM

RATED RUNNING CURRENT 1.34MOTOR OUTPUT

MOTOR SPEED

145

625

POLES 8

IP54

INSULATION GRADE

POWER SOURCE 220-240 / 1 / 50

RATED INPUT POWER 276

TYPE INDUCTION

QUANTITY 1

INDEX OF PROTECTION (IP)

cm3 / fl.oz. 1656 / 56 1591 / 56

V/Ph/HzµFW 4140 4823

A [7.28] [7.99]

A [74]

380-415 / 3 / 50CAPACITOR N/A

RATED INPUT POWERRATED RUNNING CURRENT - 1Ø [3Ø]LOCKED ROTOR AMP. - 1Ø [3Ø]

TYPE SCROLL

OIL TYPE COPELAND ULTRA 32-3 MAF

OIL AMOUNT

INSULATION GRADE EPOWER SOURCE

FDMN50CV1M

RN50DY1

FDMN60CV1M

RN61DY1

Specification (R-410A)Ceiling Concealed Type - FDMN-C Series(COND’T)

Page 28: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

26

TM-F

DB

M-0

515-

C

Safety Device - R-22 Series

OPEN kPa / psi

CLOSE kPa / psi

OPEN kPa / psi

CLOSE kPa / psi

°C / °F

OPEN kPa / psi

CLOSE kPa / psi

OPEN kPa / psi

CLOSE kPa / psi

°C / °F <130 / 266>

2413 / 350

NC

124 / 18

193 / 28

<YES>

<YES>

<130 / 266>

FDM60CV1M

FDB60CV1M

R61DY1

NC

2937 / 426

NC

2937 / 426

2413 / 350

NC

124 / 18

193 / 28

PHASE SEQUENCER, 1Ø <3Ø>

TYPE

PHASE SEQUENCER, 1Ø <3Ø>

MODEL

INDOOR UNIT

OUTDOOR UNIT

SAFETY DEVICE

HIGH PRESSURE SWITCH

TYPE

LOW PRESSURE SWITCH

TYPE

DISCHARGE THERMOSTAT SETTING

MODELINDOOR UNIT

OUTDOOR UNIT

SAFETY DEVICE

HIGH PRESSURE SWITCH

TYPE

LOW PRESSURE SWITCH

DISCHARGE THERMOSTAT SETTING

R35DV1 R40DY1

FDM50CV1M

FDB50CV1M

R50DY1

NC

OPEN kPa / psi 2937 / 426

CLOSE kPa / psi 2413 / 350

NC

OPEN kPa / psi 124 / 18

CLOSE kPa / psi 193 / 28

NA <YES>

°C / °F NA <130 / 266>

LOW PRESSURE SWITCH

TYPE

MODEL

INDOOR UNIT FDM40CV1M

FDB40CV1M

OUTDOOR UNIT

SAFETY DEVICE

HIGH PRESSURE SWITCH

TYPE

PHASE SEQUENCER, 1Ø <3Ø>

DISCHARGE THERMOSTAT SETTING

OPEN kPa / psi

CLOSE kPa / psi

OPEN kPa / psi

CLOSE kPa / psi

°C / °F

124 / 18

193 / 28

YES

125 / 257

FDM30CV1M

FDB30CV1M

R30CV1

NC

2937 / 426

2413 / 350

NC

LOW PRESSURE SWITCH

TYPE

PHASE SEQUENCER, 1Ø <3Ø>

DISCHARGE THERMOSTAT SETTING

MODELINDOOR UNIT

STANDARD STATIC PRESSURE

NON STANDARD STATIC PRESSURE

OUTDOOR UNIT

SAFETY DEVICE

HIGH PRESSURE SWITCH

TYPE

STANDARD STATIC PRESSURE

NON STANDARD STATIC PRESSURE

STANDARD STATIC PRESSURE

NON STANDARD STATIC PRESSURE

STANDARD STATIC PRESSURE

NON STANDARD STATIC PRESSURE

Page 29: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

27

TM-F

DB

M-0

515-

C

RN35DV1 RN40DY1

NC

OPEN kPa / psi 4137 / 600

CLOSE kPa / psi 3310 / 480

NC

OPEN kPa / psi 48 / 7

CLOSE kPa / psi 152 / 22

NA <YES>

°C / °F NA <130 / 266>

FDMN50CV1M

RN50DY1

FDMN60CV1M

RN61DY1

NC

OPEN kPa / psi 4137 / 600

CLOSE kPa / psi 3310 / 480

NC

OPEN kPa / psi 48 / 7

CLOSE kPa / psi 152 / 22

<YES>

°C / °F <130 / 266>

TYPE

LOW PRESSURE SWITCH

PHASE SEQUENCER, 1Ø <3Ø>

DISCHARGE THERMOSTAT SETTING

PHASE SEQUENCER, 1Ø <3Ø>

DISCHARGE THERMOSTAT SETTING

MODELINDOOR UNIT

OUTDOOR UNIT

SAFETY DEVICE

HIGH PRESSURE SWITCH

TYPE

LOW PRESSURE SWITCH

TYPE

MODELINDOOR UNIT FDMN40CV1M

OUTDOOR UNIT

SAFETY DEVICE

HIGH PRESSURE SWITCH

TYPE

Safety Device - R-410A Series

Page 30: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

28

TM-F

DB

M-0

515-

C

4.SelectionProcess

HIGHMEDLOW

4.00

5. 00

6.00

7.00

0.00

1.00

2.00

3.00

200.00 250.00 300.00 350.00 400.00 450.00

Fan Performance CurveFDM10CV1M

(High Static Blower)

Ex

tern

al S

tati

c P

res

su

re, (

mm

w.g

.)

Flowrate, (CFM)

Page 31: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

29

TM-F

DB

M-0

515-

C

Fan Performance CurveFDM15CV1M

(High Static Blower)

HIGHMEDLOW

4.00

5.00

6.00

7.00

0.00

1.00

2.00

3.00

300.00 350.00 400.00 450.00 500.00 550.00 600.00 650.00 700. 00 750.00 800.00

Ex

tern

al

Sta

tic

Pre

ss

ure

, (m

m w

.g.)

Flowrate, (CFM)

Page 32: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

30

TM-F

DB

M-0

515-

C

Fan Performance CurveFDM20CV1M

(High Static Motor)

HIGHMEDLOW

4.00

5.00

6.00

7.00

Ex

tern

al S

tati

c P

res

su

re, (

mm

w.g

.)

0.00

1.00

2.00

3.00

550.00 600.00 650.00 700.00 750.00 800.00 850.00 900.00 950. 00

Flowrate, (CFM)

Page 33: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

31

TM-F

DB

M-0

515-

C

Fan Performance CurveFDM25CV1M

(High Static Motor)

HIGHMEDLOW

4.00

5.00

6.00

7.00

0.00

1.00

2.00

3.00

400.00 450.00 500.00 550.00 600.00 650.00 700.00 750.00 800. 00 850.00 900.00

Flowrate, (CFM)

Ex

tern

al

Sta

tic

Pre

ss

ure

, (m

m w

.g.)

Page 34: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

32

TM-F

DB

M-0

515-

C

0

1

2

3

4

5

6

7

8

9

10

11

12

13

400 500 600 700 800 900 1000 1100 1200

Flowrate, (CFM)

To

tal S

tati

c P

ress

ure

, (m

m w

.g.)

Fan Performance CurveFDM30CV1M

(High Static Blower)

Page 35: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

33

TM-F

DB

M-0

515-

C

Fan Performance CurveFDM40CV1M

(High Static Blower)

0

1

2

3

4

5

6

7

8

9

10

11

12

13

400 500 600 700 800 900 1000 1100 1200 1300 1400

Flowrate, (CFM)

To

tal S

tati

c P

ress

ure

, (m

m w

.g.)

Page 36: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

34

TM-F

DB

M-0

515-

C

Fan Performance CurveFDM50CV1M

(High Static Blower)

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000

Flowrate, (CFM)

To

tal S

tati

c P

ress

ure

, (m

m w

.g.)

Page 37: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

35

TM-F

DB

M-0

515-

C

Fan Performance CurveFDM60CV1M

(High Static Blower)

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

1200 1300 1400 1500 1600 1700 1800 1900 2000

Flowrate, (CFM)

To

tal S

tati

c P

ress

ure

, (m

m w

.g.)

Page 38: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

36

TM-F

DB

M-0

515-

C

Fan Performance CurveFDB10CV1M

(Low Static Motor)

Flowrate, (CFM)

Ex

tern

al

Sta

tic

Pre

ss

ure

, (m

m w

.g.)

HIGHMEDLOW

2.50

3.00

3.50

4.00

4.50

5.00

0.00

0.50

1.00

1.50

2.00

100.00 150.00 200.00 250.00 300.00 350.00

Page 39: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

37

TM-F

DB

M-0

515-

C

Fan Performance CurveFDB15CV1M

(Low Static Motor)

Flowrate, (CFM)

Ex

tern

al

Sta

tic

Pre

ss

ure

, (m

m w

.g.)

HIGHMEDLOW

2.50

3.00

3.50

4.00

4.50

5.00

0.00

0.50

1.00

1.50

2.00

200.00 250.00 300.00 350.00 400.00 450.00 500.00 550.00 600. 00 650.00

Page 40: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

38

TM-F

DB

M-0

515-

C

Fan Performance CurveFDB20CV1M

(Low Static Motor)

Flowrate, (CFM)

Ex

tern

al

Sta

tic

Pre

ss

ure

, (m

m w

.g.)

HIGHMEDLOW

2.50

3.00

3.50

4.00

4.50

5.00

0.00

0.50

1.00

1.50

2.00

450.00 500.00 550.00 600.00 650.00 700.00 750.00 800.00

Page 41: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

39

TM-F

DB

M-0

515-

C

Fan Performance CurveFDB25CV1M

(Low Static Motor)

Flowrate, (CFM)

Ex

tern

al

Sta

tic

Pre

ss

ure

, (m

m w

.g.)

HIGHMEDLOW

2.50

3.00

3.50

4.00

4.50

5.00

0.00

0.50

1.00

1.50

2.00

450.00 500.00 550.00 600.00 650.00 700.00 750.00 800.00 850. 00

Page 42: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

40

TM-F

DB

M-0

515-

C

Fan Performance CurveFDB30CV1M

(Low Static Blower)

0

1

2

3

4

5

6

550 650 750 850 950 1050

Flowrate, (CFM)

To

tal S

tati

c P

ress

ure

, (m

m w

.g.)

Page 43: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

41

TM-F

DB

M-0

515-

C

Fan Performance CurveFDB40CV1M

(Low Static Blower)

0

1

2

3

4

5

850 950 1050 1150 1250 1350

Flowrate, (CFM)

To

tal S

tati

c P

ress

ure

, (m

m w

.g.)

Page 44: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

42

TM-F

DB

M-0

515-

C

Fan Performance CurveFDB50CV1M

(Low Static Blower)

0

1

2

3

4

5

6

1100 1200 1300 1400 1500 1600 1700

Flowrate, (CFM)

To

tal S

tati

c P

ress

ure

, (m

m w

.g.)

Page 45: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

43

TM-F

DB

M-0

515-

C

Fan Performance CurveFDB60CV1M

(Low Static Blower)

0

1

2

3

4

5

6

1400 1500 1600 1700 1800 1900

Flowrate, (CFM)

To

tal S

tati

c P

ress

ure

, (m

m w

.g.)

Page 46: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

44

TM-F

DB

M-0

515-

C0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

100 200 300 400

Ext

ern

al S

tati

c P

ress

ure

, (m

m w

.g.)

Flowrate, (CFM)

HM

L

Fan Performance CurveFDMN10CV1M

Page 47: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

45

TM-F

DB

M-0

515-

C 0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

300 350 400 450 500

Ext

ern

al S

tati

c P

ress

ure

, (m

m w

.g.)

Flowrate, (CFM)

HM

L

Fan Performance CurveFDMN15CV1M

Page 48: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

46

TM-F

DB

M-0

515-

C

Fan Performance CurveFDMN20CV1M

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

400 500 600 700

Ext

ern

al S

tati

c P

ress

ure

, (m

m w

.g.)

Flowrate, (CFM)

HM

L

Page 49: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

47

TM-F

DB

M-0

515-

C

Fan Performance CurveFDMN25CV1M

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

400 500 600 700 800

Ext

ern

al S

tati

c P

ress

ure

, (m

m w

.g.)

Flowrate, (CFM)

H

ML

Page 50: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

48

TM-F

DB

M-0

515-

C

Fan Performance CurveFDMN30CV1M

0

2

4

6

8

10

12

14

200.00 400.00 600.00 800.00 1000.00 1200.00

Ext

ern

al S

tati

c P

ress

ure

, (m

m w

.g.)

Flowrate, (CFM)

SH

H

ML

L

Page 51: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

49

TM-F

DB

M-0

515-

C

Fan Performance CurveFDMN40CV1M

0

5

10

15

600 800 1000 1200 1400 1600

To

tal S

tati

c P

ress

ure

, (m

m w

.g.)

Flowrate, (CFM)

SHH

M

L

Page 52: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

50

TM-F

DB

M-0

515-

C

Fan Performance CurveFDMN50CV1M

0

5

10

15

20

25

1000 1200 1400 1600 1800

To

tal S

tati

c P

ress

ure

, (m

m w

.g.)

Flowrate, (CFM)

SH

H

M

L

Page 53: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

51

TM-F

DB

M-0

515-

C

Fan Performance CurveFDMN60CV1M

0

5

10

15

20

25

1000 1200 1400 1600 1800 2000 2200

To

tal S

tati

c P

ress

ure

, (m

m w

.g.)

Flowrate, (CFM)

SHH

M

L

Page 54: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

52

TM-F

DB

M-0

515-

C

5.ApplicationInformation

Ensure the operating temperature is in allowable range.

Cooling Only

! Caution :

The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.

Out

door

tem

p. (°

CD

B)

Indoor temp. (°CWB)

-5

19

35

15

46

24

52

Standard point

High ambient unit

Low ambient kit

Note :

Standard operating range.

With High ambient unit. (Optional item) Please refer to local dealer for unit of this specification.

With Low ambient kit. (Optional item) Please refer to local dealer for unit of this specification.

Page 55: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

53

TM-F

DB

M-0

515-

C

Model : (Indoor) FDB10CV1M, FDM10CV1M, FDB15CV1M, FDM15CV1M, FDB20CV1M, FDM20CV1M, FDMN10CV1M, FDMN15CV1M, FDMN20CV1M, FDMN25CV1M (Outdoor) R10CV1, R15CV1, R20CV1, RN10FV1, RN15FV1, RN18CV1, RN20CV1, RN25CV1

Model : (Indoor) FDB25CV1M, FDM25CV1M, FDMN30CV1M (Outdoor) R20CV1, R25CV1, RN28CV1

Page 56: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

54

TM-F

DB

M-0

515-

C

Model : (Indoor) FDM30CV1M, FDB30CV1M; (Outdoor) R28CV1, R30CV1

Model : (Indoor) FDM40CV1M, FDB40CV1M, FDM50CV1M, FDB50CV1M, FDM60CV1M, FDB60CV1M; (Outdoor) R35DV1, R40DY1, R50DY1, R61DY1

Page 57: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

55

TM-F

DB

M-0

515-

C

Model : (Indoor) FDMN40CV1M, FDMN50CV1M, FDMN60CV1M; (Outdoor) RN35DV1, RN40DY1, RN50DY1, RN61DY1

Page 58: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

56

TM-F

DB

M-0

515-

C

Controller

DSLM8

Operating Guide

MODETURBO

TIMEROVERRIDE

TIMER

ON OFFTIMER

SWING QUIET

SLEEP

14

5

6

23

1011

8

97

1 MODE Button Press the MODE button to switch operation from COOL, AUTO*, DRY*, FAN. Check the display to

see in which mode the control is set. *AUTO and DRY are available for selected models only.

2 TURBO Fan Speed Press the Turbo key once to activate Turbo fan speed. Turbo symbol will be shown. To disable Turbo

fan speed and back to previous fan speed, press the Turbo key once again. For the unit that does not have TURBO fan speed it will show high fan speed.

3 SWING Function Press SWING button to activate the swing function. Press it again to deactivate it.

4 QUIET Fan Speed Press the Quiet key once to activate Quiet fan speed. Quiet symbol will be shown. To disable Quiet

fan speed and back to previous fan speed, press the Quiet key once again. For the unit that does not have QUIET fan speed it will show low fan speed.

5 “ ” or “ ” Set Temperature Button Press the temperature button and set the temperature of your choice by pressing “ ” or “ ” button

once, temperature changes by 1°C or 1°F. The default temperature setting range is from 16°C to 30°C (60°F to 86°F). When the Option 20 - 30ºC is set, the temperature range limit is set to 20ºC to 30ºC (68°F to 86°F). Pressing both keys simultaneously will toggle the temperature setting between ºC and ºF.

6 SLEEP Function Press the SLEEP button to activate the sleep mode. DRY MODE and FAN MODE are not valid

during sleep function.

Page 59: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

57

TM-F

DB

M-0

515-

C

7 “ON TIMER” and “OFF TIMER” The unit has 2-event timer, namely Timer 1 and Timer 2, each event has an ON TIMER and an OFF

TIMER. The key press activity for Timer ON and Timer OFF is shown on Table 1.1 Table 1.1: Timer ON and Timer OFF key press and event sequence.

All timers are event-triggered timers and can be overridden by the ON/OFF button and Override function.

Set Event 1 and Event 2 Timers

Process for Timer ON and Timer OFF is the same.1. Press and hold Timer ON/OFF key for 3 seconds to go into timer setting mode. (Icon ON 1 or OFF 1 will blink)2. Press UP or DOWN to select Timer 1 or Timer 2 to set. (‘1’ blinking indicate that Timer 1 is currently selected, ‘2’ blinking indicate that Timer 2 is currently selected)3. Press Timer ON/OFF key again to confirm. (Day will blink next)4. Press UP or DOWN to select the day.5. Press Timer ON/OFF key again to confirm the day. (Hour will blink next)4. Press UP or DOWN to change the hour.5. Press Timer ON/OFF key again to confirm the hour. (Minute will blink next)6. Press UP or DOWN to change the minute.7. Press Timer ON/OFF key again to confirm the minute.

Each timer (Timer 1 ON or Timer 1 OFF or Timer 2 ON or Timer 2 OFF) will only be set separately after all 7 steps, if there is no key operation for 5 seconds during setting the timer, it will automatically exits from setting mode and no changes will be made.

ON/OFF timer will be checked every 1 minute.It is not advisable to set ON TIMER and OFF TIMER to have same values. Shall these occur, the effective timer will be treated with priority as stated in Table 1.2.Example:ON TMR 2 settings: DAY – TUE, TIMER – 5.00pmOFF TMR 1 settings: DAY – TUE, TIMER – 5.00pmOutcome when RTC reaches 5.00pm on TUE: - when unit is on, no respond. - when unit is off, unit will trigger to on.

Table 1.2: Timer Priority

ON Timer 1 ON Timer 2 OFF Timer 1 OFF Timer 2 Deactivated Deactivated Deactivated Deactivated Activated Deactivated Activated Deactivated Deactivated Activated Deactivated Activated Activated Activated Activated Activated

TIMER ON KEY TIMER OFF KEY

Priority Timer

1 (Highest)

2

3

4 (Lowest)

ONTMR2

OFFTMR2

ONTMR1

OFFTMR1

Upon IR reception, IR wireless remote controller will override ON TIMER 2 and OFF TIMER 2 settings.

Page 60: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

58

TM-F

DB

M-0

515-

C

8 OVERRIDE Function Press the OVERRIDE key once will activate the override function for 1 hour. An indicator

“OVERRIDE 1” will show on the LCD. Press the same key again will increase the setting to 2 hours. An indicator “OVERRIDE 2” will be shown. Subsequent press will deactivate the override function. After the override timer is completed, the override function is deactivated and the logo is OFF. All other timers will be resumed.

9 FAN Speed Function Fan speed can be changed via pressing the FAN key: Low > Med > High > Auto > Low >

10 ON/OFF Button Starting Operation: - Press the ON/OFF button, the LCD will show full display and the unit is turned on. Stopping Operation: - Press the ON/OFF button, the LCD will show real time clock only and the unit is turn off.

11 Real-time Clock (RTC) Display RTC is shown on screen during the unit ON or OFF except for power failure or error code.

Set RTC Setting 1. Press RTC key one time will activate RTC setting mode. (Day will blink) 2. Press UP or DOWN to select the day. 3. Press RTC again to confi rm the day. (Hour will blink next) 4. Press UP or DOWN to change the hour. 5. Press RTC again to confi rm the hour. (Minute will blink next) 6. Press UP or DOWN to change the minute. 7. Press RTC again to confi rm the minute. RTC will only be set after all 7 steps, if there is no key operation for 5 seconds during setting the

RTC, it will automatically exits from setting mode and no changes will be made on the setting.

12 Hardware Setting The unit has 4 jumpers option to control the board function. Table 2.0: Summary of Hardware Settings

OPTION

Set Temp. Range

TURBO_QUIET

Reserved

Reserved

With Jumper

Set Temp. Range from 20˚C-30˚C

Reserved

Reserved

Without Jumper

Set Temp. Range from 16˚C-30˚C(Default)

Enable turbo and quiet fan speed

Reserved

Reserved

Disable turbo and quiet fan speed(Default)

Page 61: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

59

TM-F

DB

M-0

515-

C

Phase SequencerTheunitwithScrollCompressorcanonlyrotateinonedirection.Forthisreason,aprotectivedevice(phasesequencer)isfittedtopreventincorrectwiringoftheelectricalphases.Whenthethreephasesarenotconnectedcorrectly,thephasesequenceroperates,andtheunitwillnotstart.Thisdeviseislocatedinthecontrolboxoftheoutdoorunit.

ThefollowingtableshowstheLEDindicatorlightforphasesequencerundernormaloperationandfaultconditions.

Wired Remote Control (Universal Board)

Cooling

Error Code at 7 Segment Display Operation / Faulty Indication

Blink E1 Room sensor contact open / short Blink E2 Indoor coil sensor contact open Blink E3 Outdoor coil sensor contact open

Blink E4 Compressor overload/ Indoor coil sensor short/Outdoor coil sensor short

Blink E5 Gas leak

Blink E6 Pump faulty

Operating State And Fault Table

LED_PWR(Red)

LED_S (Yellow)

LED_T (Yellow)

Normal Operation

LEDs Error Indication

On

On On

On On

-On On

-

-

-

-

- -

-

On

-

Reverse Phase Blink Blink BlinkBlink

Blink

Blink

Blink

System OffBlink

Blink

Blink

T Phase Missing S Phase Missing R Phase Missing R Phase Missing (Main Power) Overload

Sensor Missing

High Pressure

Low Pressure

Notes: 1. “-” means LED off.2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 (Common) and 81(NO) will cut off.3. The unit will check the discharge sensor availability only during power up.4. All errors can only recover through manually reset.

Page 62: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

60

TM-F

DB

M-0

515-

C

6.Installations

Installation GuidelineSafety Precautions

WARNING

CAUTIONPlease take note of the following important points when installing.

If gas leaks and accumulates around the unit, it may cause fire ignition.

Ensure that drainage piping is connected properly.If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture.

Do not overcharge the unit.

This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.

Ensure that the unit’s panel is closed after service or installation.

Unsecured panels will cause the unit to operate noisily.

Sharp edges and coil surfaces are potential locations which may cause injury hazards.Avoid from being in contact with these places.

Before turning off the power supply, set the remote controller’s ON/OFF switch to the “OFF” positionto prevent the nuisance tripping of the unit. If this is not done, the unit’s fans will start turning automatically when power resumes, posing a hazard to service personnel or the user. Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt or deform as a result of the excessive heat.

Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively.

IMPORTANT : DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM.Do not use joined and twisted wires for incoming power supply.

Do not install the unit where leakage of flammable gas may occur. •

••

NOTICE

• Installation and maintenance should be performed by quali�ed persons who are familiar with local code and regulation, and experienced with this type of appliance.

• All field wiring must be installed in accordance with the national wiring regulation.• Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring

work according to the wiring diagram.• The unit must be GROUNDED to prevent possible hazard due to insulation failure.• All electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors.• Confirm that the unit has been switched OFF before installing or servicing the unit.• Disconnect from the main power supply before servicing the air conditioner unit.• DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which

may result in fire hazards.• Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static

may be heard even when more than 1m away}.

Disposal requirementsYour air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with unsorted household waste.Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil and of other parts must be done by a qualified installer in accordance with relevant local and national legislation. Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or local authority for more information.Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation.

Page 63: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

61

TM-F

DB

M-0

515-

C

Indoor Unit

Outdoor Unit

Air Intake

Air Intake

Air Discharge

Return Duct

Hanger

Supply Duct

Thermal Insulation

Wrap the insulated pipe withthe finishing tape from bottom to top

Drain Piping

Installation Diagram

Page 64: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

62

TM-F

DB

M-0

515-

C

W

See DetailInsulation material(field supply)

Air outlet side

Aluminium tape(Field supply) (Field supply)

Air inlet side

Field Supply

Washer for hanger bracket(Attached)

Tighten

Aluminium tape

Detail A

L

10m

m (0

.39”

)

Insulate securely

Do not leave in water

Bottom of the unit

Drain trap 100

100

or mo

re or

more

Slant

Unit: mm

300mmor more

Ceiling300mm* or more

2300mm or more

10m

m

Floor

The indoor unit must be installed such that there is no short circuit of the cool discharge. Respect the installation clearance. Do not put the indoor unit where there is direct sunlight on unit. The location is suitable for piping and drainage and it must have a large distance between a door and unit.

Ceiling Concealed Mounting• Use the hanger supplied with the unit.• Make sure that the ceiling is sufficiently strong

to withstand the weight.

Provide clearance for servicing ease and optimalair flow as shown in the diagram.

Center distance of axle (see drawing below)

Ceiling Concealed Drain Piping Work

• The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused by leaks and condensation.

• For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.• Ensure the drain pipe is securely insulated.• It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit

compared to the outside atmospheric pressure when the unit is operating. The drain trap is to avoid possibility of splashes or an odor.

• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.• Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is smooth.• In humid environments, use an extra drain pan to cover the entire area of the indoor unit.

Installation Of Indoor Unit

ModelFDB10CV1M, FDM10CV1M, FDMN10CV1MFDB15CV1M, FDM15CV1M, FDMN15CV1MFDB20CV1M, FDM20CV1M, FDMN20CV1MFDB25CV1M, FDM25CV1M, FDMN25CV1MFDMN30CV1MFDM30CV1M, FDB30CV1MFDMN40CV1MFDM40CV1M, FDB40CV1MFDM50CV1M, FDB50CV1M, FDMN50CV1MFDM60CV1M, FDB60CV1M, FDMN60CV1M

741 (29.2)881 (34.7)

1041 (41.0)1176 (46.3)959 (37.8)956 (37.6)

1264 (49.8)1076 (42.4)1326 (52.2)1526 (60.1)

225 (8.9)225 (8.9)225 (8.9)225 (8.9)

339 (13.3)256 (101)401 (15.8)256 (10.1)256 (10.1)256 (10.1)

W mm (inch)L mm (inch)

* Can be smaller than 300mm if ceiling is removable.

Page 65: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

63

TM-F

DB

M-0

515-

C

Installation Of The Outdoor Unit

As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum cooling capacity, the location selected for outdoor unit should fulfill the following requirements:

• Install the condensing (outdoor) unit in a way such that the hot air distributed by the outdoor condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the unit.

• Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air intake or discharge.

• The location must be well ventilated, so that the unit can draw in and distribute of air thus lowering the condensing temperature.

• A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.• A place protected from the direct sunlight. Otherwise use an awning for protection, if necessary.

• The location must not be susceptible to dust or oil mist.

Installation Clearances

Note: If there is any obstacle higher than 2m, or if there is any obstruction at the upper part of the unit, please allow more space than the figure indicated in the above table.

Dimension A B C D

Minimum Distance, mm (in)

300(11.8)

1000(39.4)

300(11.8)

500(19.7)

Ret

urn

air

Dis

char

ge a

ir

A

Obs

tacl

e

Obs

tacl

e

B

Obs

tacl

e

Ret

urn

air

Ser

vice

acc

ess

DC

Obs

tacl

e

Page 66: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

64

TM-F

DB

M-0

515-

C

Refrigerant PipingAllowable Pipe Length and ElevationIf the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to the flow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective. Always choose the shortest path and follow the recommendations as tabulated below:

For R22

Model

Max. allowable length, mMax. allowable elevation, m

Liquid pipe size, mm/(in)

Gas pipe size, mm/(in)

Indoor

Outdoor125

6.35(1/4”)9.52(3/8”)

125

6.35(1/4”)12.70(1/2”)

158

6.35(1/4”)15.88(5/8”)

158

9.52(3/8”)15.88(5/8”)

Model

Max. allowable length, mMax. allowable elevation, m

Liquid pipe size, mm/(in)

Gas pipe size, mm/(in)

Indoor

Outdoor R28CV1158

9.52(3/8”)15.88(5/8”)

R30CV1258

9.52(3/8”)15.88(5/8”)

R35DV14525

9.52(3/8”)19.05(3/4”)

R40DY14525

9.52(3/8”)19.05(3/4”)

R50DY14525

9.52(3/8”)19.05(3/4”)

R61DY13515

12.70(3/8”)19.05(3/4”)

FDM30CV1MFDB30CV1M

FDM40CV1MFDB40CV1M

FDM50CV1MFDB50CV1M

FDM60CV1MFDB60CV1M

For R410A

Model

Max. allowable length, mMax. allowable elevation, m

Liquid pipe size, mm/(in)

Gas pipe size, mm/(in)

IndoorOutdoor

FDMN10CV1M

RN10FV12010

6.35(1/4”)9.52(3/8”)

FDMN15CV1M

RN15FV12010

6.35(1/4”)12.70(1/2”)

FDMN20CV1M

RN20CV12010

6.35(1/4”)12.70(1/2”)

FDMN25CV1M

RN25CV12010

6.35(1/4”)15.88(5/8”)

Model

Max. allowable length, mMax. allowable elevation, m

Liquid pipe size, mm/(in)

Gas pipe size, mm/(in)

IndoorOutdoor

FDMN30CV1M

RN28CV1158

9.52(3/8”)15.88(5/8”)

RN35DV14525

9.52(3/8”)15.88(5/8”)

RN40DY14525

9.52(3/8”)15.88(5/8”)

FDMN50CV1M

RN50DY14525

9.52(3/8”)15.88(5/8”)

FDMN60CV1M

RN61DY13515

9.52(3/8”)19.05(3/4”)

FDMN40CV1M

Standard Static PressureNon-Standard Static Pressure

Standard Static PressureNon-Standard Static Pressure

FDB10CV1MFDM10CV1M

R10CV1

FDB15CV1MFDM15CV1M

R15CV1

FDB20CV1MFDM20CV1M

R20CV1

FDB25CV1MFDM25CV1M

R25CV1

Page 67: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

65

TM-F

DB

M-0

515-

C

Remove burr

Cutting copper tube

1/4t

Flared tubeFlare joint

Flare nutIndoor piping

Torque wrenchSpanar

Ø Tube, D A (mm)

Inch mm Imperial (Wing-nut Type)

Rigid (Clutch Type)

1/4" 6.35 1.3 0.7

3/8" 9.52 1.6 1.0

1/2" 12.70 1.9 1.3

5/8" 15.88 2.2 1.7

3/4" 19.05 2.5 2.0

Pipe Size (mm/in)

Torque (Nm/ft-lb)

6.35 (1/4") 18 (13.3)

9.52 (3/8") 42 (31.0)

12.70 (1/2") 55 (40.6)

15.88 (5/8") 65 (48.0)

19.05 (3/4") 78 (57.6)

Figure D

Figure A

Copper tubeSwaging block A

D

Figure B

Figure C

Piping Works And Flaring Technique• Do not use contaminated or damaged copper

tubing. If any piping, evaporator or condenser had been exposed or had been opened for 15 seconds or more, the system must be vacuumed. Generally do not remove plastic, rubber plugs and brass nuts from the valves, fittings, tubing and coils until it is ready to connect suction or liquid line into valves or fittings.

• If any brazing work is required, ensure that nitrogen gas is passed through coil and joints while the brazing work is being done. This will eliminate soot formation on the inside wall of copper tubings.

• Cut the pipe stages by stages, advancing the blade of pipe cutter slowly. Extra force and a deep cut will cause more distortion of pipe and therefore extra burr. See Figure A.

• Remove burrs from cut edges of the pipes with remover. See Figure B. Hold the pipe on top position and burr remover at lower position to prevent metal chips from entering the pipe. This will avoid unevenness on the flare faces which will cause gas leak.

• Insert the flare nuts, mounted on the connection parts of both the indoor unit and outdoor unit, into the copper pipes.

• The exact length of pipe protruding from the top surface of the swaging block is determined by the flaring tool. See Figure C.

• Fix the pipe firmly on the swaging block. Match the centers of both the swaging block and the flaring punch, then tighten the flaring punch fully.

Piping Connection To The Units

• Align the center of the piping and tighten the flare nut sufficiently with fingers. See Figure D.

• Finally, tighten the flare nut with torque wrench until the wrench clicks.

• When tightening the flare nut with the torque wrench, ensure that the tightening direction follows the arrow indicated on the wrench.

• The refrigerant pipe connection are insulated by closed cell polyurethane.

Page 68: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

66

TM-F

DB

M-0

515-

C

Vacuuming is necessary to eliminate all moisture and air from the system.

Refrigerant Piping

Outdoor Unit 3 ways valve

Allen key

Service Port

Flare nut

HIGH PRESSURE GAUGE

GAUGE MANIFOLD

LOW PRESSURE GAUGE

HANDLE HI (ALWAYS CLOSED)

CHARGE HOSE

-760mmHg

HANDLE LO

CHARGE HOSE VACUUM PUMP ADAPTER FOR

COUNTER FLOW PREVENTION

CHECK

VALVE

LIQUID

VALVE

HIGH PRESSURE GAUGELOW PRESSURE GAUGE

GAUGE MANIFOLD-760mmHg

HANDLE LO HANDLE HI (ALWAYS CLOSED)

CHARGE HOSECHARGE HOSE

CHECK

VALVE

LIQUID

VALVEGAS VALVE

(3-WAY)

CONFIGURATION OF AIR PURGE BY CHARGING

GAS VALVE (3-WAY)

CONFIGURATION OF AIR PURGE BY CHARGING

Vacuuming And Charging

Vacuuming The Piping And The Indoor UnitExcept for the outdoor unit which is pre-charged with refrigerant, the indoor unit and the refriger-ant connection pipes must be air-purged because the air containing moisture that remains in the refrigerant cycle may cause malfunction of the compressor.• Remove the caps from the valve and the

service port.• Connect the center of the charging gauge to

the vacuum pump.• Connect the charging gauge to the service port

of the 2-way valve.• Start the vacuum pump. Evacuate for approxi-

mately 30 minuted. The evacuation time varies with different vacuum pump capacity. Confirm that the charging gauge needle has moved towards - 760mmHg.

Caution• If the gauge needle does not move to

-760mmHg, be sure to check for gas leaks (using the refrigerant detector) at fl are type connection of the indoor and outdoor unit and repair the leak before proceeding to the next step.

• Close the valve of the changing gauge and stop the vacuum pump.

• On the outdoor unit, open the suction valve (3 way) and liquid valve (2 way) (in anti-clockwise

direction) with 4mm key for hexagon sacked screw.

Charge OperationThis operation must be done by using a gas cylinder and a precise weighing machine. The additional charge is topped-up into the outdoor unit using the suction valve via the service port.

• Remove the service port cap.• Connect the low pressure side of the charging

gauge to the suction service port center of the cylinder tank and close the high pressure side of the gauge. Purge the air from the service hose.

• Start the air conditioner unit.

• Open the gas cylinder and low pressure charging valve.

• When the required refrigerant quantity is pumped into the unit, close the low pressure side and the gas cylinder valve.

• Disconnect the service hose from service port. Put back the service port cap.

Page 69: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

67

TM-F

DB

M-0

515-

C

Additional Charge

For R22

For R410A

The refrigerant is pre-charge in the outdoor unit. If the piping length is less than 7.5m, then additional charge after vacuuming is not necessary. When the piping length is more than 7.5m, use the table below.

ModelIndoor

FDMN10CV1M

RN10FV1

FDMN15CV1M

RN15FV1

FDMN20CV1M

RN20CV1

FDMN25CV1M

RN25CV1

FDMN30CV1M

RN28CV1

FDMN40CV1M

RN35DV1 RN40DY1

FDMN50CV1M

RN50DY1

FDMN60CV1M

RN61DY1

18

23 26 23 32

18 20 20 33

16

545554 102

16 16

FDM30CV1M

FDB30CV1M

FDB25CV1M

FDM25CV1M

R25CV1

FDB20CV1M

FDM20CV1M

R20CV1

FDB15CV1M

FDM15CV1M

R15CV1

FDB10CV1M

FDM10CV1M

R10CV1

FDM40CV1M

FDB40CV1M

FDM50CV1M

FDB50CV1M

R50DY1

FDM60CV1M

FDB60CV1M

R61DY1R35DV1 R40DY1

R28CV1 R30CV1

39 41 55

Outdoor

Additional charge [g/m]

ModelIndoor

Outdoor

Additional charge [g/m]

ModelIndoor

Outdoor

Additional charge [g/m]

Model

Indoor

Outdoor

Additional charge [g/m]

Example:

FDB10CV1M / FDM10CV1M & R10CV1 with 13m piping length, additional piping length is 5.5m. Thus,Additional charge = 5.5[m] x 16[g/m] = 88[g]

Standard Static Pressure

Non-Standard Static Pressure

Standard Static Pressure

Non-Standard Static Pressure

Page 70: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

68

TM-F

DB

M-0

515-

C

Special Precaution When Charging Unit With Scroll CompressorTheseprecautionsareintendedforusewithScrollcompressorsonlywithR22andR410ArefrigerantsbutarenotappliedtootherscompetitiveScrollcompressors.Scrollcompressorshaveaveryhighvolumetricefficiencyandquicklypumpadeepvacuumif thereisinsufficientrefrigerantinthesystemorifrefrigerantisaddedtooslowly.Operationwithlowsuctionpressurewillquickly lead toveryhighdischarge temperatures.While thisprocess ishappening, thescrollsarenotbeingwelllubricated–scrollsdependontheoilmistintherefrigerantforlubrication.Alackof lubricationleadstohighfrictionbetweenthescrollflanksandtipsandgeneratesadditionalheat.Thecombinationofheatofcompressionandheat from increased friction isconcentrated inasmalllocalizeddischargeareawheretemperaturescanquicklyrisetomorethan300°C.TheseextremetemperaturesdamagetheScrollspiralsandtheorbitingScrollbearing.Thisdamagecanoccurinlessthanoneminuteespeciallyonlargercompressors.Failuremayoccurinthefirstfewhoursorthedamagedoneduringfieldchargingmayshowupsometimelater.Othertypicalfieldchargingproblemsincludeundercharging,overcharging,moistureorairinthesystemetc.Intimeeachoneoftheseproblemscancause compressor failure.Minimalequipmentisrequiredforfieldcharging.Theminimumequipmentrequiredtodoasatisfactoryjobis:- 1.Setofservicegauges 4.Vacuumgauge 2. Hoses 5. Scales 3. Vacuum pump 6. Thermometer The proper refrigerant charge should follow the volume as recommended by manufacturer andrecommendationshouldbefollowedbytheinstaller.

1. Charging procedures – Single phase compressors Evacuatethesystemto-760mmHg.Toreduceevacuationtime,useshort,largediameterhosesan

connecttounrestrictedserviceportsonthesystem.Qualityofvacuumcannotbedeterminedbytime–areliablevacuumgaugemustbeused.(etc.electronicvacuumgauge)

Turntherefrigerantcylinderupsidedown,purgethecharginghoseandcharge liquid throughtheliquidlinechargingportuntilrefrigerantnolongerflowsoruntilthecorrectchargehasbeenweighedin.Ifadditionalchargeisrequiredstartthesystemandslowlybleedliquidintothesuctionsideuntilthe system is full.

It recommends charging liquid in a CONTROLLED manner into the suction side until the system is full. Thisrecommendationdoesnotholdtrueforreciprocatingcompressorswhereliquid

chargingintothesuctionsidecouldcauseseveredamage. Carefullymonitorthesuctionanddischargepressures–ensurethatthesuctionpressuredoesnot

fallbelow25psig(1.7bar)atanytimeduringthechargingprocess.

Dip-pipeInvert cylinderwithout dip-pipe

Liquid withdrawal

CAUTION!

• Manifold Gauge will show cylinder pressure rather than suction pressure if the cylinder valve and Manifold valve “A” are both open.

Page 71: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

69

TM-F

DB

M-0

515-

C

Therearemanywaysof charging liquid ina “controlledmanner”intothesuctionside:-1. Use valveAonthemanifoldgaugeset2. Usethevalveontherefrigerantcylinder3. ChargethroughaShreddervalve4. UseahosewithaShreddervalvedepressor5. Chargeintothesuctionsideatsomedistance from the compressor6. Alloftheabove

2. Charging procedures – Three phase compressors The fundamentalprocedureisthesameasforsinglephasemodelsbutthecompressorcanrunin

thewrongdirectiononstarting.Ifthishappensreverseanytwophasesandstartagain.Shorttermreverserotationwillnotdamagethecompressor.

AllSpectercompressorshaveinternaldischargetemperatureprotectorswhichareveryeffectiveinpreventingdangerouslyhighdischargetemperaturesduringcharging.Theprotectionmodulewilltripandlockthecompressoroutfor30minutes.Itisnotnormallynecessarytowait30minutesforthemoduletoreset.Whenthecompressorhascooleddownthemodulecanberesetbybreakingthepowersupplytothecontrolcircuit.Veryoftentheservicemandoesnotunderstandwhythemoduletrippedandusesajumperwiretobypassit.Hecontinuestochargethesystemandremovesthejumperwhenchargingiscomplete.Thecompressormayormaynotrunwiththeprotectorbackinthecircuitbutitiscertainthatthecompressorhasbeendamagedandprematurefailureisinevitable.

A

Page 72: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

70

TM-F

DB

M-0

515-

C

Special Precautions When Dealing With Refrigerant R410A Unit

(1) What is New Refrigerant R410A?R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing is essential.

(2) ComponentsMixture weight composition R32(50%) and R125(50%)

(3) Characteristic• R410A liquid and vapour components have different compositions when the fluid

evaporates of condenses. Hence, when leak occurs and only vapor leaks out, the composition of the refrigerang mixture left in the system will change and subsequently affect the system performance. DO NOT add new refrigerant to leaked system. It is recommended that the system should be evacuated thoroughly before recharging with R410A.

• When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid phase. Hence when charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to make certain that only original composition of R410A is being charged into the system.

• POE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22 compressor. Extra precaution must be taken not to expose the R410A system too long to moist air.

(4) Check List Before Installation / Servicing• Tubing

Refrigerant R410A is more easily affected by dust of moisture compared with R22, make sure to temporarily cover the ends of the tubing prior to installation.

• Compressor oilNo additional charge of compressor oil is permitted.

• RefrigerantNo other refrigerant other that R410A

• Tools (size of service port is different from R22 system)Tools specifically for R410A only (must not be used for R22 or other refrigerant)i) Gauge manifold and charging hoseii) Gas leak detectoriii) Refrigerant cylinder/charging cylinderiv) Vacuum pump c/w adapterv) Flare toolsvi) Refrigerant recovery machine

(5) Handling and Installation GuildelinesLike R22 system, the handling and installation of R410A system are closely similar. All precautionary measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and thorough leak check and vacuuming are equally important requirements.However, due to it hydroscopic POE oil, additional precautions must be taken to ensure optimum and trouble free system operation.

(a) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to moist air. Residual POE oil in the piping and components can absorb moisture from the air.

(b) Ensure that the compressor is not exposed to open air for more than the recommended time specified by its manufacturer (typically less than 10 minutes). Removed the seal plugs only when the compressor is about to be brazed.

(c) The system should be thoroughly vacuumed to 1.0 Pa (700mmHg) or lower. This vacuuming level is more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.

Page 73: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

71

TM-F

DB

M-0

515-

C

d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to ensure that only the original composition of R410A is being delivered into the system. The liquidcomposition can be different from the vapor composition.

e) Normally, the R410A cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the bottom.

Dip-pipe Invert cylinderwithout dip-pipe

Liquidwithdrawal

Page 74: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

72

TM-F

DB

M-0

515-

C

7.WiringDiagrams

Indoor Unit

Outdoor UnitModel : R10CV1

Model : FDB10CV1M, FDM10CV1M

Page 75: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

73

TM-F

DB

M-0

515-

C

Indoor Unit

Outdoor UnitModel : RN10FV1

Model : FDMN10CV1M

Page 76: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

74

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDB15CV1M, FDM15CV1M

Outdoor UnitModel : R15CV1

Page 77: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

75

TM-F

DB

M-0

515-

C

Indoor Unit

Outdoor UnitModel : RN15FV1

Model : FDMN15CV1M

Page 78: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

76

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDB20/25CV1M, FDM20/25CV1M

Outdoor UnitModel : R18/20/25CV1

Page 79: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

77

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDMN20/25CV1M

Outdoor UnitModel : RN20/25CV1

Page 80: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

78

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDM30CV1M, FDB30CV1M

Outdoor UnitModel : R28CV1

Page 81: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

79

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDMN30CV1M

Outdoor UnitModel : RN28CV1

Page 82: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

80

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDM30CV1M, FDB30CV1M

Outdoor UnitModel : R30CV1

ENL

1 PHASE220~415VAC 50 Hz OR208~230VAC 60 Hz

Page 83: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

81

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDM40CV1M, FDB40CV1M

Outdoor UnitModel : R35DV1

ENL

1 PHASE220~415 VAC 50 Hz OR208~230 VAC 60 Hz

Page 84: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

82

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDMN40CV1M

Outdoor UnitModel : RN35DV1

Page 85: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

83

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDM40/50CV1M, FDB40/50CV1M

Outdoor UnitModel : R40/50DY1

ENTSR

380~415 V3PH 50Hz

Page 86: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

84

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDMN40/50CV1M

Outdoor UnitModel : RN40/50DY1

Page 87: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

85

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDM60CV1M, FDB60CV1M

Outdoor UnitModel : R61DY1

ENTSR

380~415 V3PH 50Hz

Page 88: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

86

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDMN60CV1M

Outdoor UnitModel : RN61DY1

Page 89: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

87

TM-F

DB

M-0

515-

C

8.ServicingandMaintenance

Warning: Disconnect from main supply before servicing the air conditioner

Components Maintenance Procedures Recommended Schedule Air Filter

(Indoor Unit) 1. Remove any dust adhering to the filter by using a

vacuum cleaner or wash in lukewarm water (below 40˚C) with a neutral cleaning detergent.

2. Rinse the filter well and dry before placing it back onto the unit.

3. Note: Never use gasoline, volatile substances or chemicals to clean the filter.

At least once every 2 weeks. More frequently if necessary.

Indoor Unit 1. Clean any dirt or dust on the grille or panel by wiping it with a soft cloth soaked in lukewarm water (below 40˚C) and a neutral detergent solution.

2. Note: Never use gasoline, volatile substances or chemicals to clean the indoor unit.

At least once every 2 weeks. More frequently if necessary.

Condense Drain Pan & Pipe

1. Check the cleanliness and clean it if necessary. 2. Check the condensate water flow.

Every 3 months.

Indoor Fan Check if there is any abnormal noise. If necessary. Indoor / Outdoor

Coil 1. Check and remove the dirt between the fins. 2. Check and remove any obstacles which hinder air flow

through the indoor or outdoor.

Every month.

Power Supply 1. Check the running current and voltage for indoor and outdoor unit.

2. Check the electrical wiring and tighten the wire onto the terminal block if necessary.

Every 2 months.

Every year.

Compressor No maintenance needed if refrigerant circuit remains sealed. However, check for refrigerant leak at joint and fitting.

Every 6 months.

Compressor Oil Oil is factory charged. Not necessary to add oil if circuit remains sealed.

No maintenance required.

Fan Motor Oil All motors are pre-lubricated and sealed at factory. No maintenance required.

Pre Start Up Maintenance(After Extended Shut Down)

- Inspect thoroughly and clean indoor and outdoor units.- Clean or replace air filters.- Clean condensates drain line.- Clean clogged indoor and outdoor coils.- Check fan imbalance before operation.- Tighten all wiring connections and panels.- Check for refrigerant leakage.

The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention.

Page 90: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

88

TM-F

DB

M-0

515-

C

9.Troubleshooting

When a malfunction of the air conditioner unit is detected, immediately switch off the main power supplybefore proceeding with the following troubleshooting procedures.The following are common fault conditions and simple troubleshooting tips. If any other fault conditions whichare not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.

snoitcaevitcerroc/sesuacelbissoPsnoitidnoctluaFoN

1 The air conditioner unit will not resume after power failure.

• The auto restart function is not functioning. Please turn on the unit with the wireless / wired controller.

2 The compressor does not operate 3 minutes after the air conditioner unit is started.

• Protection against frequent starting. • Wait for 3 or 4 minutes for the compressor to start

operating by it self.

3 The airflow is too slow or room cannot be cooled sufficiently.

• The air filter is dirty. • The doors and windows are opened. • The air suction and discharge of both indoor and

outdoor units are clogged or blocked. • The regulated temperature or temperature setting

is not low enough.

4 Discharge airflow has bad odor. • Cigarettes, smoke particles, perfume and others,which might have adhered onto the coil, maycause odor.

• Contact your nearest dealer.

5 Condensation on the front air grille of the indoor unit.

• This is caused by air humidity after an extended period of operation.

• The set temperature is too low. Increase the temperature setting and operate the unit at high fan speed.

6 Water flowing out from the air conditioner. • Switch off the unit and contact your nearest dealer. This might be due to tilted installation.

7 Hissing airflow sound from the air conditioner unit during operation.

• Liquid refrigerant flowing into the evaporator coil.

8 The wireless controller display is dim. • The batteries are discharged. • The batteries are not correctly inserted. • The assembly is not good.

9 Compressor operates continuously. • Dirty air filter. Clean the air filter. • Temperature setting too low (cooling). Use higher

temperature setting.

10 No cool air comes out during cooling cycle. • Temperature setting too high (cooling). Use lower temperature setting.

Page 91: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

89

TM-F

DB

M-0

515-

C

Pressure

Data

Circuit

Too

low

A li

ttle

low

Nor

mal

A li

ttle

high

Too

high

Probable cause

High side Low side

●●

1. Overcharged with refrigerant. 2. Non-condensable gases in refrigerant circuit (e.g. air) 3. Obstructed air-intake / discharge. 4. Hot air short circuiting in outdoor unit.

High side Low side

●1. Poor compression / no compression (compressor

defective) 2. Reversing valve leaking.

High side Low side ●

● 1. Undercharged with refrigerant. 2. Refrigerant leakage. 3. Air filter clogged / dirty (indoor unit). 4. Indoor fan locked / seized.

High side Low side ●

● 1. Outdoor fan blocked (cooling). 2. Outdoor coil dirty (cooling). 3. Non-condensable gases in refrigerant circuit (e.g. air)

High side Low side

●●

1. Air intake temperature of indoor unit too high.

Diagnostic Guidelines

By means of pressure reading :

Page 92: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

90

TM-F

DB

M-0

515-

CThe most common causes of air conditioner failure to “start” are :a) Voltage not within ±10% of rated voltage.b) Power supply interrupted.c) Improper control settings.d) Air conditioner is disconnected from main power source.e) Fuse blown or circuit breaker off.

By Means Of Diagnostic Flow Chart :Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling. “Starting failure” is caused by electrical defect while improper application or defects in refrigerant circuit causes “Insufficient cooling.

i) Diagnosis of Electric Circuit

Page 93: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

91

TM-F

DB

M-0

515-

C

Satisfactory operation with temperature difference of air intake & discharge of indoor unit8°C to 13°C. *( * value is for reference only )

ii ) Diagnosis of Refrigerant Circuit / ApplicationThere might be some causes where the unit starts running but does not perform satisfactorily, i.e. insufficient cooling. Judgement could be made by measuring temperature difference of indoor unit’s intake and discharge air as well as running current

Page 94: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

92

TM-F

DB

M-0

515-

C

10.DimensionalData

Model : FDB10CV1M, FDM10CV1M, FDMN10CV1M

Indoor UnitModel : FDB15/20/25CV1M, FDM15/20/25CV1M, FDMN15/20/25CV1M

All Dimensions are in mm

Indoor Unit

All Dimensions are in mm

881.0 225.0 842.0 802.0 261.0 411.0 351.0 905.0

1041.0 225.0 1002.0 962.0 261.0 411.0 351.0 1065.0

1176.0 225.0 1137.0 1097.0 261.0 411.0 351.0 1200.0

DimensionModelFDB15CV1M, FDM15CV1MFDMN15CV1M

A B C D F G HE

FDB20CV1M, FDM20CV1MFDMN20CV1MFDB25CV1M, FDM25CV1MFDMN25CV1M

Page 95: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

93

TM-F

DB

M-0

515-

C

Indoor UnitFDMN30CV1M

Page 96: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

94

TM-F

DB

M-0

515-

C

Indoor UnitModel : FDMN40CV1M

Page 97: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

95

TM-F

DB

M-0

515-

C

Indoor Unit

FDM30/40/50/60CV1M, FDB30/40/50/60CV1M, FDMN50/60CV1M

All dimension are in mm

A B C D E F G H I Dimension

ModelFDM30CV1MFDB30CV1M

FDM40CV1MFDB40CV1M

FDM50CV1MFDB50CV1MFDMN50CV1M

FDM60CV1MFDB60CV1MFDMN60CV1M

929.0 999.0 956.0 917.0 408.5 105.0 85.5 187.5 70.5

1045.0 1115.0 1072.0 1033.0 466.5 105.0 85.5 187.5 128.5

1299.0 1369.0 1326.0 1287.0 593.5 105.0 90.5 182.5 255.5

1499.0 1569.0 1526.0 1487.0 693.5 100.0 90.5 187.5 355.5

Page 98: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

96

TM-F

DB

M-0

515-

C

Outdoor UnitModel: R10/15CV1

R10/15CV1

A B C D E F G H I J K L M N O

700 521 250 485 175 36 95 93 86 68 441 130 111 15 18

Note : All Dimension in mm

K

B

LL

CN

N

M30

A

DO

319

6580

C

G H

I J

EF

Dimension

All dimensions are in mm

Outdoor UnitModel: RN10/15FV1

DimensionModel A B C D E F G H I J K L M N O P

RN10/15FV1 550 658 51 11 273 16 14 470 96 299 94 60 14 133 8 8

H

NJ

G

B CDE F

A

MK

L

P

O

I

Page 99: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

97

TM-F

DB

M-0

515-

C

Model: R35DV1, R40/50/61DY1RN35DV1, RN40/50/61DY1

Note : All Dimension in mm

A B C D E F G H I J K L M N O P Q R S T

R18/20CV1RN20/25CV1

R25/28/30CV1RN28CV1

855 628 328 520 179 46 93 149 101 113 603 126 164 15 34 32 3 23 73 75

855 730 328 520 179 46 93 149 101 113 603 126 164 15 34 32 3 23 73 75

Note : All Dimension in mm

Model: R18/20/25/28/30CV1 RN20/25/28CV1

142 746 142

2222

448

60

40.090.0

MODEL

Page 100: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

98

TM-F

DB

M-0

515-

C

11.ExplodedView&PartList

6

7

2

5

4

3

1

Model: FDB10CV1M, FDM10CV1M, FDMN10CV1M

NO. PARTS DESCRIPTION

TOP SIDE PANEL

FAN DECK

COIL

PRIMARY DRAIN PAN

SECONDARY DRAIN PAN

HANGER

CONTROL BOX

1

2

3

4

5

6

7

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

Page 101: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

99

TM-F

DB

M-0

515-

C

1 TOP SIDE PANEL

2 FAN DECK

3 COIL

4 PRIMARY DRAIN PAN

5 SECONDARY DRAIN PAN

6 HANGER

7 CONTROL BOX

Model: FDB15/20/25CV1M, FDM15/20/25CV1M, FDMN15/20/25CV1M

6

4

2

FRONT VIEW

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

NO. PARTS DESCRIPTION

Page 102: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

100

TM-F

DB

M-0

515-

C 1 ASSY. PANEL TOP

2 ASSY. TERMINAL BOX

3 ASSY. COIL TUBING

4 ASSY. DRAIN PAN SMALL

5 ASSY. DRAIN PAN BIG

6 ASSY. BLOWER

7 PANEL BLOWER

8 FLANGE BLOWER

9 FILTER RAIL

10 FILTER RAIL, COVER

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

Model: FDM30CV1M, FDB30CV1M, FDMN30CV1M

NO. PARTS DESCRIPTION

Page 103: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

101

TM-F

DB

M-0

515-

C

1 ASSY.PANEL TOP

2 ASSY. TERMINAL BOX

3 ASSY. COIL TUBING

4 ASSY. DRAIN PAN SMALL

5 ASSY. DRAIN PAN BIG

6 ASSY. BLOWER

7 PANEL BLOWER

8 FLANGE BLOWER

9 ASSY. RAIL FILTER

10 ASSY. INS. COVER FILTER L/R

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

Model: FDM40CV1M, FDB40CV1M, FDMN40CV1M

NO. PARTS DESCRIPTION

Page 104: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

102

TM-F

DB

M-0

515-

C

ASSY. PANEL TOP 1

2

3

4

5

6

7

8

9

10

PARTS DESCRIPTIONNO.

ASSY. TERMINAL BOX

ASSY. COIL TUBING

ASSY. DRAIN PAN SMALL

ASSY. DRAIN PAN BIG

ASSY. BLOWER

PANEL BLOWER

FLANGE BLOWER

ASSY., RAIL FILTER

ASSY., COVER FILTER L/R

Model: FDM50CV1M, FDB50CV1M, FDMN50CV1M

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

Page 105: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

103

TM-F

DB

M-0

515-

C

ASSY. PANEL TOP

PARTS DESCRIPTIONNO.

1

2

3

4

5

6

7

8

9

10

ASSY. TERMINAL BOX

ASSY. COIL TUBING

ASSY. DRAIN PAN SMALL

ASSY. DRAIN PAN BIG

ASSY. BLOWER

PANEL BLOWER

FLANGE BLOWER

ASSY., RAIL FILTER

ASSY., COVER FILTER L/R

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

Model: FDM60CV1M, FDB60CV1M, FDMN60CV1M

Page 106: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

104

TM-F

DB

M-0

515-

C1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., OUTDOOR COIL3 VALVE BRACKET

RIGHT PANEL

4 COMPRESSORASSY., FRONT PANEL

5 ASSY., PARTITION15

13

ASSY., CONTROL PANEL

6 SUCTION PIPE 7 DISCHARGE PIPE 8 ASSY., CAP TUBE 9 BRACKET, FAN MOTOR10

16

14

ASSY., VALVE COVER

Model : R10/15CV1

FAN MOTOR

17 ASSY., FRONT GRILLE 18 PLASTIC HANDLE 19 INSULATION PARTS NOT IN THE DIAGRAMS CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR11 FAN BLADE

12 LEFT PANEL

Page 107: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

105

TM-F

DB

M-0

515-

C

Model : RN10/15FV1

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY. OUTDOOR COIL

12 SUCTION PIPE2 TOP PANEL

13 ASSY. CAP TUBE3 FAN MOTOR BRACKET

14 VALVE BRACKET4 ASSY PARTITION

15 ASSY. VALVE COVER16 ASSY. CONTROL PANEL17 RIGHT PANEL

5 FAN MOTOR6 FAN BLADE7 ASSY. FRONT GRILLE8 ASSY FRONT PANEL9 ASSY BASE PAN

10 COMPRESSOR11 DISCHARGE PIPE

* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.

17

16

15

1413121110987

6

5

4

3

2 1

Page 108: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

106

TM-F

DB

M-0

515-

C1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., OUTDOOR COIL3 MOTOR BRACKET

13 TERMINAL COVER PANEL

4 FAN MOTOR

14 DISCHARGE PIPE

5 FAN BLADE

15 SUCTION PIPE

6 VALVE BRACKET 7 PARTITION 8 COMPRESSOR 9 BACK PANEL, RIGHT10

16 ASSY., CAP TUBE

Model : R18/20CV1, RN20/25CV1

17 ASSY., VALVE COVER 18 ASSY., FRONT GRILLE 19 PLASTIC HANDLE 20 SERVICE PANELPARTS NOT IN THE DIAGRAMS CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR

FRONT PANEL, LEFT11 TOP PANEL12 ASSY., CONTROL PANEL

Page 109: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

107

TM-F

DB

M-0

515-

C

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., OUTDOOR COIL3 MOTOR BRACKET

13 ASSY., CONTROL PANEL

4 FAN MOTOR

14 TERMINAL COVER PANEL

5 FAN BLADE15 ASSY., VALVE COVER

6 VALVE BRACKET 7 PARTITION 8 COMPRESSOR 9 BACK PANEL, RIGHT10

16 ASSY., FRONT GRILLE

Model : R25/28/30CV1, RN28CV1

17 PLASTIC HANDLE, SIDE 18 DISCHARGE PIPE 19 SUCTION PIPE 20 ASSY., CAP TUBE PARTS NOT IN THE DIAGRAMS CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR

SERVICE PANEL11 FRONT PANEL LEFT

12 TOP PANEL

Page 110: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

108

TM-F

DB

M-0

515-

C

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., COIL3 PALTE, FLARE VALVE4 FLARE VALVE 3/8”5 FLARE VALVE 5/8”

16 MOTOR BRACKET17 FAN MOTOR18 ASSY., FRONT PANEL19 ASSY., CONTROL PANEL20 SERVICE PANEL21 FAN BLADE22 TOP PANEL23 PLASTIC HANDLE

6 PARTITION 7 COMPRESSOR 8 ACCUMULATOR 9 ASSY., CAPILLARY TUBE10 SUCTION PIPE11 TUBE ACCUMULATOR TO SUCTION12 DISCHARGE PIPE13 INSULATION14 BACK PANEL, RIGHT

15 SIDE PANEL, LEFT

PARTS NOT IN THE DIAGRAMS

Model : R35DV1, R40/50/61DY1, RN35DV1, RN40/50/61DY1

PHASE SEQUENCER HIGH PRESSURE SWITCH LOW PRESSURE SWITCH CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR TXV

Page 111: Ceiling Concealed - Daikin Malaysia · FDM : Ceiling Concealed (Higher Static Pressure) Series C : C Series Power Supply V1 : Single Phase, 220-240V, 50Hz Controller M : Wired Controller

Branches: • Penang Tel: 04-331 1670 • Johor Tel: 07-557 7788 • Pahang Tel: 09-567 6778 • Perak Tel: 05-548 2307 • Melaka Tel: 06-288 1133 • Sabah Tel: 088-722 194 • Sarawak Tel: 082-333 299 • Negeri Sembilan Tel: 06-768 8969 • Kedah Tel: 04-733 0235 • Kelantan Tel: 09-747 4678

GROUP ASSOCIATED (C&L) SDN BHD (109719-M)

Head Office: Tel: 03-7953 8388 Fax: 03-7956 4371Email: [email protected], [email protected]

www.da i k i n . com.my