Ceiling Concealed
TM-FDBM-0515-CTECHNICAL MANUAL
1. Model Name .......................................................................................................... 1 2. Features ................................................................................................................ 3
3. Specifications ........................................................................................................ 4 GeneralData .............................................................................................. 4 SafetyDevices .......................................................................................... 26
4. SelectionProcess ................................................................................................ 28 FanPerformanceCurve ........................................................................... 28
5. ApplicationInformation ........................................................................................ 52 OperatingRange ...................................................................................... 52 RefrigerantDiagram ................................................................................. 53 Controllers ................................................................................................ 56
6. Installation ........................................................................................................... 60
7.WiringDiagram .................................................................................................... 72
8. Servicing&Maintenance .................................................................................... 87
9. Troubleshooting .................................................................................................. 88
10.DimensionalData ................................................................................................ 92
11.ExplodedView&PartList ................................................................................... 98
Note:Installationandmaintenancearetobeperformedonlybyqualifiedpersonnelwhoare familiarwithlocalcodesandregulations,andexperiencedwiththistypeofequipment.
Caution:Sharpedgesandcoilsurfacesareapotentialinjuryhazard.Avoidcontactwiththem.
Warning:Movingmachineryandelectricalpowerhazard.Maycauseseverepersonnel injuryordeath.Disconnectandlockoffpowerbeforeservicingequipment.
TableofContents
1
TM-F
DB
M-0
515-
C
1. Model Name
Indoor
FDB 10 C V1 M
Type of Air Conditioner
FDB : Ceiling Concealed (Lower Static Pressure)FDM : Ceiling Concealed (Higher Static Pressure)
Series
C : C Series
Power Supply
V1 : Single Phase, 220-240V, 50Hz
Controller
M : Wired Controller
Refrigerant
Blank : R22N : R410A
Capacity Index
10 : Based on Btu/hr
2
TM-F
DB
M-0
515-
C
Outdoor
R 10 C V1
Type of Air Conditioner
R : Single Split Condensing Unit
Series
C : C seriesD : D seriesF : F series
Power Supply
V1 : Single Phase, 220-240V, 50HzY1 : Three Phase, 380-415V, 50Hz
Refrigerant
Blank : R22N : R410A
Capacity Index
10 : Based on Btu/hr
3
TM-F
DB
M-0
515-
C
2. Features
Space Saving, Elegance and PrestigeThe unit is installed above the ceiling with only the supply and return air grille exposed to view. This ceiling concealed type of design has made it an “Evergreen” model without sacrificing the precious floor space. The air-conditioned space will appear as elegant and prestigious as centralized air-conditioned area but with only a fraction of the cost. This model is ideal for small offices, hotel rooms, hospitals and restaurant applications.
Double Protection Drainage SystemHigh humidity inside the ceiling area is always the main cause of water leaking. By introducing “Built In” double drain pans solution, i.e. primary drain pan and secondary drain pan, water leaking will not be a problem anymore. The high quality Polystyrene (PS) primary drain pan come with a layer of thermal forming High Impact Polystyrene (HIPS) coating. The primary drain pan is specially designed, with mould in gradient, for better condensate water drainage. Furthermore, the drain pan is made of PS, which is a very good insulation material to prevent sweating. The secondary drain pan will act as a drip pan to block any water that might be dripped down thus offering an additional protection to the ceiling. In such a case, additional drain pan will not be necessary during installation which means more cost saving. A drain socket is supplied to connect both drain pans to the drainage pipe.
Easy and Flexible InstallationThe physical height of the unit is only 378mm or less depends on the model, it is therefore offering greatest flexibility in selecting installation location. With its special designed installation accessories, the installation job become easy and better air distribution can be achieved without extra spending on duct works.
Easy MaintenanceThe simple design concept has a friendly maintenance and servicing in mind. Just loosening a few screws, remove secondary drain pan and drain guide, you can access to all the internal parts from the bottom of the unit. No water will splash down when removing the secondary drain pan makes the servicing work never easier before.
Medium Static Pressure with a Low Noise LevelThis series has a static pressure between 0 to 15 mmAq depend on duct work installation. The casing is well insulated internally to reduce the noise level.
4
TM-F
DB
M-0
515-
C
3.Specifications
Specification (R22)Ceiling Concealed Type - FDBM-C Series
FDB10CV1MFDM10CV1M
R10CV1
FDB15CV1MFDM15CV1M
R15CV1Btu/h 10,000 13,000
W 2,930 3,809
HIGH ESP 924 1,331LOW ESP 903 1,277
HIGH ESP 4.1 6.0LOW ESP 4.0 5.7
V/Ph/Hz
HIGH l/s / CFM
142 / 300 241 / 510
MEDIUM l/s / CFM
135 / 285 231 / 490
LOW l/s / CFM
123 / 260 189 / 400
ESP (H/M/L) Pa (in.wg.)
49 / 44 / 36 (0.20 / 0.18 / 0.15) 49 / 42 / 28 (0.20 / 0.17 / 0.11)
HIGH l/s / CFM
142 / 300 241 / 540
MEDIUM l/s / CFM
135 / 275 231 / 500
LOW l/s / CFM
123 / 225 189 / 380
ESP (H/M/L) Pa (in.wg.)
10 / 8 / 5 (0.04 / 0.03 / 0.02) 10 / 8 / 5 (0.04 / 0.03 / 0.02)
1 2
mm/inmm/in
HIGH ESP 36 / 35 / 33 40 / 38 / 33LOW ESP 33 / 30 / 25 36 / 33 / 28
V/Ph/Hz
HIGH ESP 89 160LOW ESP 68 106
HIGH ESP 0.40 0.78LOW ESP 0.30 0.47
HIGH ESP 38 72LOW ESP 20 40
POLES 4
220-240 / 1 / 50
RATED INPUT POWER W
RATED RUNNING CURRENT
A
MOTOR OUTPUT W
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) 20INSULATION GRADE BPOWER SOURCE
SOUND PRESSURE LEVEL (H/M/L) dBA
GALVANIZED STEELDRIVE DIRECTDIAMETER 164 / 6.46LENGTH 202 / 7.95
FAN
IND
OO
R U
NIT
HIGH STATIC FAN MOTOR*
AIR FLOWLOW STATIC FAN MOTOR
AIR FLOW
TYPE CENTRIFUGAL FANQUANTITYMATERIAL
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
CONTROLAIR DISCHARGE DUCTED
OPERATION WIRED REMOTE CONTROL
TOTAL RUNNING CURRENT - 1Ø [3Ø] A
POWER SOURCE 220-240 / 1 / 50REFRIGERANT TYPE R-22
MODEL INDOOR UNITSTANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE
OUTDOOR UNIT
TOTAL COOLING CAPACITY
TOTAL INPUT POWER W
FANMOTOR
COIL
AIRQUALITY
UNITDIMENSION
kg/lb 0.63 / 1.39 0.60 / 1.32REFRIGERANT CHARGE
mm/inmm/in
mm/inm2/ft2 0.115 / 1.238 0.143 / 1.542
12 14FIN PER INCH
ALUMINIUMTHICKNESS 0.11 / 0.004FACE AREAROW 3
TUBEMATERIAL COPPERDIAMETER 9.52 / 3/8THICKNESS 0.28 / 0.011
FIN
MATERIAL
pc
LENGTH mm/in 560 / 22.05 700 / 27.56WIDTH mm/in 195 / 7.68THICKNESS mm/in
AIRFILTER
TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 1
SIZE5 / 0.20
mm/in 261 / 10.3mm/in 765 / 30.1 905 / 35.6mm/in 411 / 16.2
HEIGHTWIDTHDEPTH
mm/in 376 / 14.8mm/in 951 / 37.4 1091 / 43.0mm/in 541 / 21.3
PACKINGDIMENSION
CASING
HEIGHTWIDTHDEPTH
kg/lb 18 / 39.7 22 / 48.5UNIT WEIGHT
COLOUR WITHOUT POWDER PAINT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4
5
TM-F
DB
M-0
515-
C
Specification (R-22)Ceiling Concealed Type - FDBM-C Series (CONT’D)
mm/in 7.00 / 0.276mm/in 0.28 / 0.011
ALUMINUM (RAISE LANCE)mm/in
m2/ft2 0.43 / 4.62120
TYPE
OIL TYPE
OIL AMOUNT cm3 / fl.oz. 320 / 11.3 350 / 11.8
INSULATION GRADE
POWER SOURCE V/Ph/Hz
CAPACITOR µF 30
RATED INPUT POWER W 783 1112
RATED RUNNING CURRENT A 3.5 5.0
LOCKED ROTOR AMP. A 19 21
mm/in
mm/in
mm/inmm/in
mm/in
mm/in
kg/lb 30 / 66 32 / 71
COLOUR IVORY WHITE
UNIT WEIGHT
CASING
HEIGHT 620 / 24.4WIDTH 810 / 31.9
DEPTH 330 / 13.0
UNITDIMENSION
HEIGHT 540 / 21.3
WIDTH 700 / 27.6
DEPTH 250 / 9.8
PACKING DIMENSION
0.11 / 0.004
FACE AREA
ROW
FIN PER INCH
COMPRESSOR
ROTARY
ATMOS NM56M or SUNISO 4GDID
E
220-240 / 1 / 50
TUBE
MATERIAL SEAMLESS INNER GROOVE COPPER
DIAMETER
THICKNESS
FIN
MATERIAL
THICKNESS
MODELINDOOR UNIT
OUTDOOR UNIT
l/s / CFM 453 / 960
mm/in
dBA 46 49
DRIVE DIRECTDIAMETER 401 / 15.8
SOUND PRESSURE LEVEL
AIR FLOW
TYPE PROPELLERQUANTITY 1MATERIAL ASG20
mm/in 6.35 / 1/4mm/in 9.52 / 3/8 12.7 / 1/2GAS
PIPE
FAN
FAN MOTOR
CONNECTION
COIL
TYPE FLARE
SIZELIQUID
V/Ph/HzW 52 74A 0.23
190.33
W 30RPM 730 860MOTOR SPEED
POLES 6
BPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUT
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) IP23INSULATION GRADE
OU
TD
OO
R U
NIT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
FDB10CV1M
FDM10CV1M
R10CV1
FDB15CV1M
FDM15CV1M
R15CV1
STANDARD STATIC PRESSURE
NON-STANDARD STATIC PRESSURE
6
TM-F
DB
M-0
515-
C
Specification (R-22)Ceiling Concealed Type - FDBM-C Series
R18CV1 R20CV1Btu/h 18,000 20,000
W 5,274 5,860
HIGH ESP 1,945 1,930LOW ESP 1,907 1,892
HIGH ESP 8.5LOW ESP 8.5 8.3
V/Ph/Hz
HIGH l/s / CFMMEDIUM l/s / CFMLOW l/s / CFM
ESP (H/M/L) Pa (in.wg.)HIGH l/s / CFMMEDIUM l/s / CFMLOW l/s / CFM
ESP (H/M/L) Pa (in.wg.)
mm/inmm/in
HIGH ESPLOW ESP
V/Ph/Hz
HIGH ESPLOW ESP
HIGH ESPLOW ESP
HIGH ESPLOW ESP
mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4
MOTOR OUTPUT W8060
POLES 4
220-240 / 1 / 50RATED INPUTPOWER W 170
132
RATED RUNNING CURRENT A 0.79
0.54
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) 20INSULATION GRADE BPOWER SOURCE
181
0.820.58
DIAMETER 164 / 6.46LENGTH 202 / 7.95
SOUND PRESSURE LEVEL(H/M/L) dBA
42 / 41 / 4038 / 37 / 35
QUANTITY 2MATERIAL GALVANIZED STEELDRIVE DIRECT
330 / 703319 / 675302 / 640
20 / 19 / 15 (0.08 / 0.07 / 0.06)
TYPE CENTRIFUGAL FAN
HIGH STATIC FAN MOTOR*
AIR FLOW
330 / 700319 / 675302 / 640
49 / 45 / 41 (0.20 / 0.18 / 0.17)
LOW STATIC FAN MOTOR
AIR FLOW
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
CONTROL AIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL
TOTAL RUNNING CURRENT - 1Ø [3Ø] A
POWER SOURCE 220-240 / 1 / 50REFRIGERANT TYPE R-22
MODEL INDOOR UNIT FDB20CV1MFDM20CV1M
OUTDOOR UNIT
TOTAL COOLING CAPACITY
TOTAL INPUT POWER W
kg/lb 0.90 / 1.98 0.83 / 1.83REFRIGERANT CHARGE
mm/inmm/inmm/inmm/inmm/inmm/inkg/lbUNIT WEIGHT
FAN
IND
OO
R U
NIT
FAN MOTOR
COIL
24 / 53
PACKINGDIMENSION
HEIGHT 376 / 14.8WIDTH 1251 / 49.3DEPTH 541 / 21.3
UNITDIMENSION
HEIGHT 261 / 10.3WIDTH 1065 / 41.9DEPTH 411 / 16.2
mm/inmm/in
mm/inm2/ft2
ROW 3FIN PER INCH 12
MATERIAL ALUMINIUMTHICKNESS 0.11 / 0.004FACE AREA 0.176 / 1.892
TUBEMATERIAL COPPERDIAMETER 9.52 / 3/8THICKNESS 0.28 / 0.011
FIN
pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in 5 / 0.20
AIRFILTER
CASING
TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 1
SIZE860 / 33.86195 / 7.68
COLOUR WITHOUT POWDER PAINT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
STANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE
7
TM-F
DB
M-0
515-
C
mm/in 7.00 / 0.276mm/in 0.23 / 0.009
ALUMINUMmm/inm2/ft2
IVORY WHITE
COMPRESSOR
FIN
COLOUR
MATERIALTHICKNESS 0.11 / 0.004FACE AREA 0.51 / 5.49
120
ROWFIN PER INCH
TUBEMATERIAL SEAMLESS INNER GROOVE COPPERDIAMETERTHICKNESS
COIL
CASING
MODEL INDOOR UNIT
OUTDOOR UNIT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
dBASOUND PRESSURE LEVEL 5152mm/inmm/inmm/inmm/inmm/inmm/inkg/lb 43 / 94.8UNIT WEIGHT
PACKING DIMENSION
HEIGHT 693 / 27.3WIDTH 990 / 39.0DEPTH 415 / 16.3
UNIT DIMENSION
HEIGHT 654 / 25.7WIDTH 855 / 33.7DEPTH 328 / 12.9
mm/in 6.35 / 1/4mm/in 15.88 / 5/8
PIPE CONNECTION
FAN
FAN MOTOR
OU
TD
OO
R U
NIT
TYPE
SIZELIQUIDGAS
FLARE
mm/inDIAMETER 457 / 17.9
TYPE PROPELLERQUANTITY 1MATERIAL ASG 20DRIVE DIRECT
l/s / CFMAIR FLOW 614 / 1300
V/Ph/HzWAW
RPMPOLES 68
220-240 / 1 / 50RATED INPUT POWER 77RATED RUNNING CURRENT 0.34MOTOR OUTPUTMOTOR SPEED
32680
TYPE INDUCTION
QUANTITY 1INDEX OF PROTECTION (IP) IP23INSULATION GRADE FPOWER SOURCE
cm3 / fl.oz.
V/Ph/HzµF 40 35
16727.3441
W 1698A 7.37
36A
POWER SOURCE 220-240 / 1 / 50CAPACITORRATED INPUT POWERRATED RUNNING CURRENTLOCKED ROTOR AMP.
TYPE ROTARYOIL TYPE SUNISO-4GSI/FREOL-K56OIL AMOUNT 600 / 20.3INSULATION GRADE E
FDB20CV1M
FDM20CV1M
STANDARD STATIC PRESSURE
NON-STANDARD STATIC PRESSURE
R18CV1 R20CV1
Specification (R-22)Ceiling Concealed Type - FDBM-C Series (CONT’D)
8
TM-F
DB
M-0
515-
C
Specification (R-22)Ceiling Concealed Type - FDBM-C Series
R20CV1 R25CV1Btu/h 22,000 25,000
W 6,446 7,325
HIGH ESP 1,941 2,625LOW ESP 1,921 2,625
HIGH ESP 8.6 11.7LOW ESP 8.4 11.6
V/Ph/Hz
HIGH l/s / CFMMEDIUM l/s / CFMLOW l/s / CFM
ESP (H/M/L) Pa (in.wg.)HIGH l/s / CFMMEDIUM l/s / CFMLOW l/s / CFM
ESP (H/M/L) Pa (in.wg.)
mm/inmm/in
HIGH ESPLOW ESP
V/Ph/Hz
HIGH ESPLOW ESP
HIGH ESPLOW ESP
HIGH ESPLOW ESP
POLES 4
RATED RUNNING CURRENT A
0.820.70
MOTOR OUTPUT W9080
20INSULATION GRADE BPOWER SOURCE 220-240 / 1 / 50
RATED INPUT POWER W 181161
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP)
DIAMETER 164 / 6.46LENGTH 202 / 7.95
SOUND PRESSURE LEVEL (H/M/L) dBA41 / 40 / 3640 / 39 / 35
QUANTITY 2MATERIAL GALVANIZED STEELDRIVE DIRECT
345 / 730311 / 660270 / 580
20 / 18 / 11 (0.08 / 0.07 / 0.04)
TYPE CENTRIFUGAL FAN
FAN
FAN MOTOR
COIL
IND
OO
R U
NIT
HIGH STATIC FAN MOTOR*
AIR FLOW
345 / 730311 / 660274 / 580
49 / 43 / 30 (0.20 / 0.17 / 0.12)
LOW STATIC FAN MOTOR
AIR FLOW
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
CONTROL AIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL
TOTAL RUNNING CURRENT - 1Ø [3Ø] A
POWER SOURCE 220-240 / 1 / 50REFRIGERANT TYPE R-22
MODEL INDOOR UNIT FDB25CV1MFDM25CV1M
OUTDOOR UNIT
TOTAL COOLING CAPACITY
TOTAL INPUT POWER W
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
kg/lb 1.40 / 3.08 1.10 / 2.43REFRIGERANT CHARGE
mm/inmm/inmm/inmm/inmm/inmm/inkg/lbUNIT WEIGHT 26 / 57.3
HEIGHT 376 / 14.8WIDTH 1386 / 54.6DEPTH 541 / 21.3
UNIT DIMENSION
HEIGHT 261 / 10.3WIDTH 1200 / 47.2DEPTH 411 / 16.2
PACKING DIMENSION
mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4
mm/inmm/in
mm/inm2/ft2
ROW 3FIN PER INCH 12
MATERIAL ALUMINIUMTHICKNESS 0.11 / 0.004FACE AREA 0.203 / 2.187
TUBEMATERIAL COPPERDIAMETER 9.52 / 3/8THICKNESS 0.28 / 0.011
FIN
pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in
AIR FILTER
CASING
TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 1
SIZE995 / 39.17195 / 7.685 / 0.20
WITHOUT POWDER PAINTCOLOUR
STANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE
9
TM-F
DB
M-0
515-
C
mm/inmm/in
mm/inm2/ft2 0.51 / 5.49 0.61 / 6.58
120
cm3 / fl.oz. 600 / 20.3 700 / 24.6
V/Ph/HzµF 35 50W 1683 2323A 7.44 10.35A 41 56
220-240 / 1 / 50CAPACITORRATED INPUT POWERRATED RUNNING CURRENTLOCKED ROTOR AMP.
TYPE ROTARYOIL TYPE SUNISO 4GSI /FREAOL-K56 ATMOS NM56M OR SUNISO 4GDIDOIL AMOUNTINSULATION GRADE EPOWER SOURCE
THICKNESS 0.23 / 0.009
FIN
MATERIAL ALUMINUM (RAISE LANCE)THICKNESS 0.11 / 0.004FACE AREAROWFIN PER INCH
TUBEMATERIAL SEAMLESS INNER GROOVE COPPERDIAMETER 7.00 / 0.276
MODELINDOOR UNIT
OUTDOOR UNIT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
l/s / CFM 755 / 1600AIR FLOW 614 / 1300
dBA 51 52SOUND PRESSURE LEVELmm/in 654 / 25.7 756 / 29.8mm/in 855 / 33.7mm/in 328 / 12.9mm/in 693 / 27.3 793 / 31.2
mm/in 990 / 39.0
mm/in 415 / 16.3kg/lb 43 / 94.8 50 / 110
DEPTHUNIT WEIGHT
UNIT DIMENSION
HEIGHTWIDTHDEPTH
PACKING DIMENSION
HEIGHTWIDTH
mm/in 6.35 / 1/4 9.52 / 3/8mm/in 15.88 / 5/8
PIPE CONNECTION
FAN
FAN MOTOR
COMPRESSOR
OU
TDO
OR
UN
IT
COIL
CASING
TYPE
SIZELIQUIDGAS
FLARE
mm/inDIAMETER 455 / 17.9
TYPE PROPELLERQUANTITY 1
MATERIAL ASG 20DRIVE DIRECT
V/Ph/HzW 77
0.3432
680
1210.5360
840
AW
RPMPOLES 6
FPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTMOTOR SPEED
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) IP23INSULATION GRADE
COLOUR IVORY WHITE
R20CV1 R25CV1
FDB25CV1M
FDM25CV1M
STANDARD STATIC PRESSURE
NON-STANDARD STATIC PRESSURE
Specification (R-22)Ceiling Concealed Type - FDBM- C Series (CONT’D)
10
TM-F
DB
M-0
515-
C
R28CV1 R30CV1Btu/h 28,000 30,000
W 8,204 8,790HIGH ESP 3,104 3,410LOW ESP 3,015 3,321HIGH ESP 15.5 14.6LOW ESP 15.5 14.2
V/Ph/Hz
HIGHSUPER HIGH
SUPER HIGH
l/s / CFMl/s / CFM
MEDIUM l/s / CFMLOW l/s / CFM
ESP (SH/H/M/L) Pa (in.wg.)
HIGH l/s / CFMl/s / CFM
MEDIUM l/s / CFMLOW l/s / CFM
ESP (SH/H/M/L) Pa (in.wg.)
mm/inmm/in
DIAMETER 214 / 8.43LENGTH 203 / 8.00
QUANTITY 2MATERIAL GALVANIZED STEELDRIVE DIRECT
392 / 830359 / 760335 / 710
49 / 39 / 29 / 20 (0.2 / 0.16 / 0.12 / 0.08)TYPE CENTRIFUGAL FAN
FAN
FAN MOTOR
COIL
AIRQUALITY
CASING
IND
OO
R U
NIT
HIGH STATIC FAN MOTOR
AIR FLOW 392 / 830425 / 900
425 / 900
359 / 760335 / 710
206 / 167 / 127 / 880.8 / 0.7 / 0.5 / 0.4)
LOW STATIC FAN MOTOR*
AIR FLOW
REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR CAP. TUBE
CONTROL AIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL
TOTAL RUNNING CURRENT - 1Ø [3Ø] A
POWER SOURCEREFRIGERANT TYPE R-22
MODEL INDOOR UNITFDM30CV1MFDB30CV1M
OUTDOOR UNITTOTAL COOLING CAPACITY
TOTAL INPUT POWER W
220-240 / 1 / 50
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
kg/lb 1.75 / 3.86 2.00 / 4.41REFRIGERANT CHARGE
HIGH ESPLOW ESP
SOUND PRESSURE LEVEL (H/M/L) dBA 46 / 44 / 42
41 / 40 / 39 / 36mm/inmm/inmm/inmm/inmm/inmm/inkg/lbUNIT WEIGHT 42 / 92.6
PACKING DIMENSION
HEIGHT 415 / 16.3WIDTH 1126 / 44.3DEPTH 631 / 24.8
UNIT DIMENSION
HEIGHT 378 / 14.9WIDTH 929 / 36.6DEPTH 541 / 21.3
mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4
V/Ph/HzHIGH ESPLOW ESPHIGH ESPLOW ESPHIGH ESPLOW ESP
POLES 4
RATED RUNNINGCURRENT A 1.36
0.95
MOTOR OUTPUT W 15085
INSULATION GRADE BPOWER SOURCE 220-240 / 1 / 50RATED INPUTPOWER W 306
217
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) 20
mm/inmm/in
mm/inm2/ft2
FIN PER INCH 12
ALUMINIUM (CORR. BARE FIN)THICKNESS 0.11 / 0.004FACE AREA 0.28 / 3.01ROW 3
TUBEMATERIAL COPPERDIAMETER 9.52 / 3/8THICKNESS 0.28 / 0.011
FIN
MATERIAL
pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in 5 / 0.20
AIR FILTER
COLOUR
TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 2
SIZE449 / 17.68305 / 12.01
WITHOUT POWDER PAINT
STANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE
Specification (R-22)Ceiling Concealed Type - FDBM-C Series
11
TM-F
DB
M-0
515-
C
mm/inmm/in
mm/inm2/ft2
mm/in 756 / 29.8mm/in 855 / 33.7mm/in 328 / 12.9mm/in 793 / 31.2mm/in 990 / 39.0mm/in 416 / 16.4kg/lb 57 / 126
COLOUR IVORY WHITE
DEPTHUNIT WEIGHT
UNIT DIMENSION
HEIGHTWIDTHDEPTH
PACKING DIMENSION
HEIGHTWIDTH
18
FIN
MATERIAL ALUMINIUM (RAISE LANCE)THICKNESS 0.10 / 0.004FACE AREA 0.61 / 6.58ROW 2FIN PER INCH
TUBEMATERIAL INNER GROOVE COPPERDIAMETER 7.00 / 0.276THICKNESS 0.23 / 0.009
MODELINDOOR UNIT
OUTDOOR UNIT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
l/s / CFM 808 / 1712AIR FLOWdBA 54 56SOUND PRESSURE LEVEL
mm/inmm/in
PIPE CONNECTION
FAN
FAN MOTOR
COMPRESSOR
OU
TD
OO
R U
NIT
COIL
CASING
TYPE FLARE VALVE
SIZELIQUID 9.52 / 3/8GAS 15.88 / 5/8
mm/in 455 / 18DIAMETER
TYPE PROPELLERQUANTITY 1MATERIAL ASG 20DRIVE DIRECT
IP23
V/Ph/HzW 124A 0.54W
RPM66874
6 6
POWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTMOTOR SPEEDPOLES
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP)INSULATION GRADE F
cm3 / fl.oz. 1050 / 36 900 / 30
V/Ph/HzµF 60
W 2674 2980
A 13.6 12.7A 62 66
POWER SOURCE 220-240 / 1 / 50CAPACITORRATED INPUT POWERRATED RUNNING CURRENTLOCKED ROTOR AMP.
TYPE ROTARY TWIN ROTARY
OIL TYPE ATMOS NM32A1SUNISO 4GSIOIL AMOUNTINSULATION GRADE E
R28CV1 R30CV1
FDM30CV1MFDB30CV1M
STANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE
Specification (R-22)Ceiling Concealed Type - FDBM-C Series (CONT’D)
12
TM-F
DB
M-0
515-
C
R35DV1 R40DY1Btu/h 35,000 40,000
W 10,255 11,720HIGH ESP 3,341 3,441LOW ESP 3,293 3,393HIGH ESP 16.2 [5.8]LOW ESP 15.91 [7.41]
220-240 / 1 / 50 380-415 / 3 / 50
HIGHSUPER HIGH
SUPER HIGH
l/s / CFMl/s / CFM
MEDIUM l/s / CFMLOW l/s / CFM
ESP (SH/H/M/L) Pa (in.wg.)
HIGH l/s / CFMl/s / CFM
MEDIUM l/s / CFMLOW l/s / CFM
ESP (SH/H/M/L) Pa (in.wg.)
mm/inmm/in
HIGH ESPLOW ESP
V/Ph/HzHIGH ESPLOW ESPHIGH ESPLOW ESPHIGH ESPLOW ESP
MOTOR OUTPUT W 180120
POLES 4
RATED INPUTPOWER W 384
336RATED RUNNING CURRENT A 1.75
1.46
INDEX OF PROTECTION (IP) 20INSULATION GRADE BPOWER SOURCE 220-240 / 1 / 50
IND
OO
R U
NIT
TYPE INDUCTIONQUANTITY 1
LENGTH 203 / 8.00
SOUND PRESSURE LEVEL(H/M/L)
dBA 51 / 49 / 45 / 4143 / 41 / 40 / 38
MATERIAL GALVANIZED STEELDRIVE DIRECTDIAMETER 214 / 8.43
467 / 990425 / 900
49 / 39 / 29 /20 (0.20 / 0.16 / 0.12 / 0.08)TYPE CENTRIFUGAL FANQUANTITY 2
HIGHSTATICFANMOTOR
AIR FLOW 500 / 1060519 / 1110
519 / 1110
467 / 990425 / 900
206 / 176 / 127 / 93 (0.8 / 0.7 / 0.5 / 0.4)
LOW STATIC FAN MOTOR*
AIR FLOW 500 / 1060
CONTROL AIR DISCHARGE DUCTEDWIRED REMOTE CONTROLOPERATION
FAN
FAN MOTOR
COIL
CASING
TOTAL RUNNING CURRENT - 1Ø [3Ø] A
POWER SOURCEREFRIGERANT TYPE R-22REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR CAP. TUBE
MODEL INDOOR UNITFDM40CV1MFDB40CV1M
OUTDOOR UNIT
TOTAL COOLING CAPACITY
TOTAL INPUT POWER W
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
kg/lb 1.90 / 4.19 2.50 / 5.51REFRIGERANT CHARGE
mm/inmm/inmm/inmm/inmm/inmm/inkg/lbUNIT WEIGHT 44 / 97
1045 / 41.1DEPTH 541 / 21.3
PACKING DIMENSION
HEIGHT 415 / 16.3WIDTH 1245 / 49.0DEPTH 631 / 24.8
UNIT DIMENSION
HEIGHT 378 / 14.9WIDTH
mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4
mm/inmm/in
mm/inm2/ft2
ROW 3FIN PER INCH 14
MATERIAL ALUMINIUM (CORR. BARE FIN)THICKNESS 0.11 / 0.004FACE AREA 0.31 / 3.34
TUBEMATERIAL SEAMLESS INNER SMOOTH COPPERDIAMETER 9.52 / 3/8THICKNESS 0.28 / 0.011
FIN
COLOUR WITHOUT POWDER PAINT
pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in
SIZE507 / 19.96305 / 12.01
5 / 0.20
AIR FILTER
AIR QUALITY
TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 2
STANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE
Specification (R-22)Ceiling Concealed Type - FDBM-C Series
13
TM-F
DB
M-0
515-
C
mm/in 9.52 / 3/8 7.00 / 0.2760.23 / 0.009mm/in 0.28 / 0.011
ALUMINIUM (CORRUGATED)mm/in 0.11 / 0.004m2/ft2 0.87 / 9.36 0.85 / 9.15
1 216 18
COLOUR IVORY WHITE
COMPRESSOR
FIN
MATERIALTHICKNESSFACE AREAROWFIN PER INCH
TUBEMATERIAL INNER GROOVE COPPERDIAMETERTHICKNESS
COIL
CASING
MODEL INDOOR UNIT
OUTDOOR UNIT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
l/s / CFMAIR FLOW 1605 / 3400dBA 58SOUND PRESSURE LEVEL
mm/inmm/inmm/inmm/inmm/inmm/inkg/lb 78 / 172 85 / 187UNIT WEIGHT
PACKING
DIMENSION
HEIGHT 1010 / 39.8WIDTH 1180 / 46.5DEPTH 514 / 20.2
UNIT
DIMENSION
HEIGHT 852 / 33.5WIDTH 1030 / 40.6DEPTH 400 / 15.7
mm/inmm/inGAS 19.05 / 3/4
PIPE CONNECTION
FAN
FAN MOTOR
OU
TD
OO
R U
NIT
TYPE FLARE VALVE
SIZELIQUID 9.52 / 3/8
mm/inDIRECT
DIAMETER 610 / 24
TYPE PROPELLERQUANTITY 1MATERIAL ASG 20DRIVE
IP54
V/Ph/HzWAW
RPMPOLES 8
RATED INPUT POWER 257RATED RUNNING CURRENT 1.10MOTOR OUTPUTMOTOR SPEED
145625
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP)INSULATION GRADE BPOWER SOURCE 220-240 / 1 / 50
SUNISO 3GS MINERAL OILcm3 / fl.oz. 1242 / 42
B1400 / 47
FV/Ph/Hz 220-240 / 1 / 50 380-415 / 3 / 50
N/AµF 60
W 2700 2800A 13.35 [4.85]A 97 [48]
RATED INPUT POWERRATED RUNNING CURRENT - 1Ø [3Ø]LOCKED ROTOR AMP. - 1Ø [3Ø]
TYPE SCROLLOIL TYPEOIL AMOUNTINSULATION GRADEPOWER SOURCECAPACITOR
R35DV1 R40DY1
FDM40CV1M
FDB40CV1MSTANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE
Specification (R-22)Ceiling Concealed Type - FDBM-C Series (CONT’D)
14
TM-F
DB
M-0
515-
C
FDM50CV1MFDB50CV1M
R50DY1
FDM60CV1MFDB60CV1M
R61DY1Btu/h 50,000 60,000
W 14,650 17,580HIGH ESP 5,067 7,010LOW ESP 4,984 7,005HIGH ESP [8.7] [11.5]LOW ESP [10.77] [14.14]
V/Ph/Hz
V/Ph/HzHIGH ESP 603 610LOW ESP 520 605HIGH ESP 2.60 2.68LOW ESP 2.20 2.68HIGH ESP 400 500LOW ESP 210 320MOTOR OUTPUT W
POLES 4
POWER SOURCE 220-240 / 1 / 50RATED INPUTPOWER W
RATED RUNNING CURRENT A
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) 20INSULATION GRADE B
FAN
FAN MOTOR
COIL
AIRQUALITY
CASING
INDOOR CAP. TUBE
CONTROLAIR DISCHARGE DUCTEDOPERATION
IND
OO
R U
NIT
WIRED REMOTE CONTROL
TOTAL RUNNING CURRENT - 1Ø [3Ø] A
POWER SOURCE 380-415 / 3 / 50REFRIGERANT TYPEREFRIGERANT CONTROL (EXPANSION DEVICE)REFRIGERANT CHARGE
R-22
MODEL INDOOR UNIT
OUTDOOR UNIT
TOTAL COOLING CAPACITY
TOTAL INPUT POWER W
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
COLOUR WITHOUT POWDER PAINT
kg/lb 2.45 / 5.40 4.80 / 10.58
HIGH ESP 53 / 52 / 50 / 47 55 / 53 / 50 / 47LOW ESP 46 / 44 / 43 / 42 48 / 47 / 46 / 45
SOUND PRESSURE LEVEL(H/M/L) dBA
mm/in 378 / 14.9mm/in 1299 / 51.1 1499 / 59.0mm/in 541 / 21.3mm/in 415 / 16.3mm/in 1497 / 59.0 1701 / 67.0mm/in 631 / 24.8kg/lb 50 / 110 56 / 123
HEIGHTWIDTHDEPTH
UNIT WEIGHT
UNIT DIMENSION
HEIGHTWIDTHDEPTH
PACKING DIMENSION
mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4
HIGH l/s / CFM
651 / 1380 722 / 1530
MEDIUM l/s / CFM
604 / 1280 675 / 1430
LOW l/s / CFM
571 / 1210 609 / 1290
ESP (SH/H/M/L) Pa (in.wg.)
78 / 59 / 39 / 20 (0.31 / 0.24 / 0.16 / 0.08) 69 / 49 / 29 / 20 (0.28 / 0.20 / 0.12 / 0.08)
mm/inmm/inLENGTH 203 / 8.00
MATERIAL GALVANIZED STEELDRIVE DIRECTDIAMETER 214 / 8.43
HIGHSUPER HIGH
SUPER HIGH
l/s / CFMl/s / CFM
651 / 1380
750 / 1590
722 / 1530
779 / 1650
750 / 1590 779 / 1650
MEDIUM l/s / CFM
604 / 1280 675 / 1430
LOW l/s / CFM
571 / 1210 609 / 1290
ESP (SH/H/M/L) Pa (in.wg.)
176 / 157 / 137 / 108 (0.7 / 0.6 / 0.6 / 0/4) 176 / 157 / 137 / 98 (0.7 . 0.6 / 0.6 / 0.4)
HIGH STATIC FAN MOTOR
AIR FLOWLOW STATIC FAN MOTOR*
AIR FLOW
TYPE CENTRIFUGAL FANQUANTITY 2
mm/inmm/in
mm/inm2/ft2 0.40 / 4.31 0.47 / 5.06
3FIN PER INCH 14
9.52 / 3/8THICKNESS 0.28 / 0.011
FIN
MATERIAL ALUMINIUMTHICKNESS 0.11 / 0.004FACE AREAROW
TUBEMATERIAL COPPERDIAMETER
pcLENGTH mm/in 634 / 24.96 734 / 28.90WIDTH mm/in 305 / 12.01THICKNESS mm/in
2
SIZE5 / 0.20
AIR FILTER
TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY
STANDARD STATIC PRESSURENON-STANDARD STATIC PRESSURE
Specification (R-22)Ceiling Concealed Type - FDBM-C Series
15
TM-F
DB
M-0
515-
C
mm/in 7.00 / 0.276 9.52 / 3/8mm/in 0.23 / 0.009
ALUMINIUM (COPRRUGATED)mm/in 0.11 / 0.004m2/ft2 0.85 / 9.15 0.87 / 9.36
2 318 16
MINERAL OIL (SONITEX 200LT)cm3 / fl.oz. 1400 / 47
F1705 / 57.7
V/Ph/HzµFW 4207 6128A [7.47] [10.18]A [59] [74]
COLOUR IVORY WHITE
N/ARATED INPUT POWERRATED RUNNING CURRENT - 1Ø [3Ø]LOCKED ROTOR AMP. - 1Ø [3Ø]
TYPE SCROLL
OIL TYPEOIL AMOUNTINSULATION GRADE -POWER SOURCECOMPRESSOR 380-415 / 3 / 50CAPACITOR
MATERIALTHICKNESSFACE AREAROWFIN PER INCH
TUBEMATERIAL INNER GROOVE COPPERDIAMETERTHICKNESS
FIN
COIL
CASING
MODEL
OU
TD
OO
R U
NIT
INDOOR UNIT
OUTDOOR UNIT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
l/s / CFM 1605 / 3400 1793 / 3800AIR FLOWdBA 58 61SOUND PRESSURE LEVEL
mm/in 852 / 33.5mm/in 1030 / 40.6mm/in 400 / 15.7mm/in 1010 / 39.8mm/in 1180 / 46.5mm/in 514 / 20.2kg/lb 88 / 194
HEIGHTWIDTHDEPTH
UNIT WEIGHT
UNIT DIMENSION
HEIGHTWIDTHDEPTH
PACKING DIMENSION
105 / 231
mm/in 9.52 / 3/8 12.7 / 1/2mm/in
PIPE CONNECTION
FAN
FAN MOTOR
TYPE FLARE VALVE
SIZE LIQUIDGAS 19.05 / 3/4
mm/in 610 / 24
MATERIAL ASG 20DRIVE DIRECTDIAMETER
TYPE PROPELLERQUANTITY 1
IP54F
V/Ph/HzW 257 272A 1.10 1.28W
RPM145625
8POLES
INSULATION GRADEPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTMOTOR SPEED
TYPE INDUCTION
QUANTITY 1INDEX OF PROTECTION (IP)
FDM50CV1MFDB50CV1M
R50DY1
FDM60CV1MFDB60CV1M
R61DY1
STANDARD STATIC PRESSURE
NON-STANDARD STATIC PRESSURE
Specification (R-22)Ceiling Concealed Type - FDBM-C Series (CONT’D)
16
TM-F
DB
M-0
515-
C
FDMN10CV1MRN10FV1
FDMN15CV1MRN15FV1
Btu/h 9,000 12,000W 2,638 3,517W 970 1,430A 4.35 6.41
V/Ph/Hz
S. HIGH l/s / CFM - -HIGH l/s / CFM 118 / 250 193 / 410MEDIUM l/s / CFM 111 / 235 174 / 370LOW l/s / CFM 99 / 210 118 / 250
ESP (H/M/L) Pa (in.wg.) 29 / 20 / 10 (0.11 / 0.08 / 0.04)
1 2
mm/inmm/in
SOUND PRESSURE LEVEL (H/M/L) dBA 33 / 30 / 26 37 / 34 / 29
V/Ph/HzW 61 107A 0.27 0.48W 30 50
MODELINDOOR UNITOUTDOOR UNIT
TOTAL COOLING CAPACITY
TOTAL INPUT POWERTOTAL RUNNING CURRENT - 1Ø [3Ø]POWER SOURCE 220-240 / 1 / 50REFRIGERANT TYPE R-410AREFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
CONTROLAIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL
HIGH STATIC FAN MOTOR
AIR FLOW
TYPE CENTRIFUGAL FANQUANTITYMATERIAL GALVANIZED STEELDRIVE DIRECTDIAMETER 160 / 6.30LENGTH 202 / 7.95
FAN MOTOR
COIL
AIRQUALITY
CASING
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) NAINSULATION GRADE E BPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTPOLES 4
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
kg/lb 0.80 / 1.76 0.83 / 1.83REFRIGERANT CHARGE
mm/in 261 / 10.3mm/in 765 / 30.1 905 / 35.6mm/in 411 / 16.2mm/in 376 / 14.8mm/in 951 / 37.4 1091 / 43.0mm/in 541 / 21.3kg/lb 18 / 40 22 / 49
UNIT DIMENSION
HEIGHTWIDTHDEPTH
PACKING DIMENSION
HEIGHTWIDTHDEPTH
UNIT WEIGHT
FAN
IND
OO
R U
NIT
mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4
mm/inmm/in
mm/inm2/ft2 0.115 / 1.238 0.143 / 1.542
TUBEMATERIAL COPPERDIAMETER 7.00 / 0.276THICKNESS 0.28 / 0.011
FIN
MATERIAL ALUMINIUM (CORR. FIN)THICKNESS 0.11 / 0.0043FACE AREAROW 3FIN PER INCH 18
pcLENGTH mm/in 560 / 22.05 700 / 27.56WIDTH mm/in 195 / 7.68THICKNESS mm/in
AIRFILTER
TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 1
SIZE5 / 0.20
COLOUR WITHOUT POWDER PAINT
Specification (R-410A)Ceiling Concealed Type - FDMN-C Series
17
TM-F
DB
M-0
515-
C
FDMN10CV1M
RN10FV1
FDMN15CV1M
RN15FV1
mm/in 7.00 / 0.276mm/in 0.2 / 0.0079
ALUMINUMmm/inm2/ft2 0.33 / 3.55 0.32 / 3.44
2118
MODELINDOOR UNIT
OUTDOOR UNIT
OU
TD
OO
R U
NIT
TUBEMATERIAL COPPERDIAMETERTHICKNESS
FIN
MATERIALTHICKNESS 0.1 / 0.0039FACE AREAROWFIN PER INCH
COLOUR IVORY WHITE
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
l/s / CFM 438 / 927 390 / 827AIR FLOW
dBA 46 48SOUND PRESSURE LEVEL
mm/inmm/inmm/in
mm/inmm/inmm/inkg/lb
UNIT DIMENSION
HEIGHT 550 / 21.7WIDTH 658 / 25.9DEPTH 273 / 10.7
PACKING DIMENSION
HEIGHT 580 / 22.8WIDTH 775 / 30.5DEPTH 355 / 14.0
UNIT WEIGHT 28 / 61.7 29 / 63.9
mm/in 6.35 / 1/4mm/in 9.52 / 3/8 12.7 / 1/2
PIPECONNECTION
FAN
FAN MOTOR
COMPRESSOR
COIL
CASING
TYPE FLARE
SIZELIQUID
GAS
mm/in
TYPE PROPELLER
QUANTITY 1
MATERIAL ASG 20
DRIVE DIRECTDIAMETER 370 / 14.6
V/Ph/Hz
W 50 51
A 0.22 0.23
W 20
RPM 930 920
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) IP23
INSULATION GRADE B
POWER SOURCE 220-240 / 1 / 50
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
MOTOR SPEED
POLES 6
TYPEOIL TYPE
OIL AMOUNT cm3 / fl.oz. 330 / 11.2HAF68D1
320 / 10.8NMOCZe-Gles RB68EP
INSULATION GRADEPOWER SOURCE V/Ph/HzCAPACITOR µF 35
RATED INPUT POWER W 859 1272
RATED RUNNING CURRENT A 3.86 5.7
LOCKED ROTOR AMP. A 18.0 24.5
ROTARY
E220-240 / 1 / 50
Specification (R-410A)Ceiling Concealed Type - FDMN-C Series(CONT’D)
18
TM-F
DB
M-0
515-
C
FDMN20CV1MRN20CV1
FDMN25CV1MRN25CV1
Btu/h 18,000 21,000W 5,275 6,155W 1,870 2,150A 8.26 9.56
V/Ph/Hz
S. HIGH l/s / CFM - -HIGH l/s / CFM 269 / 570 326 / 690MEDIUM l/s / CFMLOW l/s / CFM
ESP (H/M/L) Pa (in.wg.) 29 / 20 / 10 (0.11 / 0.08 / 0.04)
mm/inmm/in
V/Ph/HzW 133 164A 0.61 0.74W 80 100
4
MODELINDOOR UNITOUTDOOR UNIT
TOTAL COOLING CAPACITY
TOTAL INPUT POWERTOTAL RUNNING CURRENT - 1Ø [3Ø]POWER SOURCE 220-240 / 1 / 50REFRIGERANT TYPEREFRIGERANT CHARGE
R-410A
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
CONTROLAIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL
HIGH STATIC FAN MOTOR
AIR FLOW
TYPE CENTRIFUGAL FANQUANTITY 2MATERIAL GALVANIZED STEELDRIVE DIRECTDIAMETER 160 / 6.30LENGTH 202 / 7.95
B
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) NAINSULATION GRADE EPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTPOLES
311 / 660 253 / 536
263 / 558227 / 480
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
kg/lb 1.45 / 3.20 1.65 / 3.64
SOUND PRESSURE LEVEL (H/M/L) dBA 38 / 36 / 34 40 / 39 / 36mm/in 261 / 10.3mm/in 1065 / 41.9 1200 / 47.2mm/in 411 / 16.2mm/in 376 / 14.8mm/in 1251 / 49.3 1386 / 54.6mm/in 541 / 21.3kg/lb 24 / 53 26 / 57UNIT WEIGHT
FAN
FAN MOTOR
IND
OO
R U
NIT
COIL
UNIT DIMENSION
HEIGHTWIDTHDEPTH
PACKING DIMENSION
HEIGHTWIDTHDEPTH
mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4
mm/inmm/in
mm/inm2/ft2 0.176 / 1.892 0.203 / 2.187
3FIN PER INCH 18
7.00 / 0.276THICKNESS 0.28 / 0.011
FIN
MATERIAL ALUMINIUM (SLIT FIN)THICKNESS 0.11 / 0.0043FACE AREAROW
TUBEMATERIAL COPPERDIAMETER
pcLENGTH mm/in 860 / 33.86 995 / 39.17WIDTH mm/in 195 / 7.68THICKNESS mm/in 5 / 0.20
AIRFILTER
COLOURCASING
TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 1
SIZE
WITHOUT POWDER PAINT
Specification (R-410A)Ceiling Concealed Type - FDMN-C Series
19
TM-F
DB
M-0
515-
C
mm/inmm/in
mm/in
m2/ft2 0.51 / 5.491
20
0.50 / 5.38
18
0.2 / 0.0079
FIN
COLOUR
MATERIAL ALUMINUMTHICKNESS 0.1 / 0.0039
IVORY WHITE
FACE AREAROW 2FIN PER INCH
OU
TD
OO
R U
NIT
TUBEMATERIAL COPPERDIAMETER 7.00 / 0.276THICKNESS
MODELINDOOR UNITOUTDOOR UNIT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
l/s / CFM 675 / 1430 755 / 1600AIR FLOWdBASOUND PRESSURE LEVEL 5249
mm/in 654 / 25.7mm/in 855 / 33.7mm/in 328 / 12.9mm/in 693 / 27.3mm/in 990 / 39.0mm/in 415 / 16.3kg/lb 43 / 94.8 47 / 103.6UNIT WEIGHT
UNIT DIMENSION
HEIGHTWIDTHDEPTH
PACKING DIMENSION
HEIGHTWIDTHDEPTH
mm/in 6.4 / 1/4mm/in 12.7 / 1/2 15.9 / 5/8
PIPECONNECTION
FAN
FAN MOTOR
COMPRESSOR
COIL
CASING
TYPE FLARE
SIZELIQUIDGAS
mm/in
TYPE PROPELLERQUANTITY 1MATERIAL ASG 20DRIVE DIRECTDIAMETER 455 / 17.9
V/Ph/HzW 78 121A 0.34
32710
0.53
WRPM
61
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP) IP23INSULATION GRADE FPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTMOTOR SPEEDPOLES 6
840
cm3 / fl.oz. 670 / 22.7
V/Ph/HzµF 50W 1659 1865A 7.31 8.29A 32
POWER SOURCECAPACITORRATED INPUT POWERRATED RUNNING CURRENTLOCKED ROTOR AMP.
TYPE ROTARYOIL TYPE FV50SOIL AMOUNTINSULATION GRADE E
220-240 / 1 / 50
FDMN20CV1MRN20CV1
FDMN25CV1MRN25CV1
Specification (R-410A)Ceiling Concealed Type - FDMN-C Series(CONT’D)
20
TM-F
DB
M-0
515-
C
Btu/hWWA
V/Ph/Hz
S.HIGH l/s / CFMHIGH l/s / CFMMEDIUM l/s / CFMLOW l/s / CFM
ESP (H/M/L) Pa (in.wg.)
mm/inmm/in
mm/in 19.1 / 3/4
GALVANIZED STEELDIRECT
185 / 7.28203 / 7.99
382 / 810363 / 770335 / 710
98 / 78 / 68 / 59 (0.39/0.31/0.28/0.24)CENTRIFUGAL FAN
2
220-240 / 1 / 50R-410A
OUTDOOR CAP. TUBE
DUCTEDWIRED REMOTE CONTROL
401 / 850
FDMN30CV1MRN28CV1
26,0007,6202,89212.8
INDOOR CONDENSATE DRAIN SIZE
FAN
FAN MOTOR
COIL
AIRQUALITY
CASING
IND
OO
R U
NIT
HIGH STATIC FAN MOTOR
AIRFLOW
TYPEQUANTITYMATERIALDRIVEDIAMETERLENGTH
POWER SOURCEREFRIGERANT TYPEREFRIGERANT CONTROL (EXPANSION DEVICE)
CONTROL AIR DISCHARGEOPERATION
MODELINDOOR UNITOUTDOOR UNIT
TOTAL COOLING CAPACITY
TOTAL INPUT POWERTOTAL RUNNING CURRENT - 1Ø [3Ø]
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
kg/lb 1.80 / 3.97REFRIGERANT CHARGE
SOUND PRESSURE LEVEL (H/M/L) dBA 44 / 41 / 38 / 34mm/inmm/inmm/inmm/inmm/inmm/inkg/lb
600 / 23.6343 / 13.51138 / 44.8690 / 27.2
40 / 88
285 / 11.2932 / 36.7
UNIT WEIGHT
UNIT DIMENSION
HEIGHTWIDTHDEPTH
PACKING DIMENSION
HEIGHTWIDTHDEPTH
WAW
2691.283204
INDUCTION1
IP20B
220-240 / 1 / 50
POLES
TYPEQUANTITYINDEX OF PROTECTION (IP)INSULATION GRADEPOWER SOURCERATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUT
mm/inmm/in
mm/inm2/ft2
ALUMINIUM (HYDROPHILIC FIN)0.11 / 0.00430.24 / 2.62
318
COPPER7.00 / 0.2760.28 / 0.011
FIN
MATERIALTHICKNESSFACE AREAROWFIN PER INCH
TUBEMATERIALDIAMETERTHICKNESS
pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in
456 / 17.95210 / 8.275 / 0.20
AIRFILTER
COLOUR
TYPEQUANTITY
SIZE
WASHABLE SARANET FILTER (OPTIONAL)2
WITHOUT POWDER PAINT
Specification (R-410A)Ceiling Concealed Type - FDMN-C Series
21
TM-F
DB
M-0
515-
C
mm/inmm/in
mm/inm2/ft2
mm/inmm/inmm/inmm/inmm/inmm/inkg/lb
855 / 33.7328 / 12.9793 / 31.2990 / 39.0416 / 16.457 / 125.7
756 / 29.8
18
IVORY WHITE
7.00 / 0.2760.23 / 0.009ALUMINIUM0.11 / 0.00430.61 / 6.58
2
COPPER
UNIT WEIGHT
UNIT
DIMENSION
HEIGHTWIDTHDEPTH
PACKING DIMENSION
HEIGHTWIDTHDEPTH
FIN PER INCH
TUBEMATERIALDIAMETERTHICKNESS
FIN
COLOUR
MATERIALTHICKNESSFACE AREAROW
MODELINDOOR UNIT
OUTDOOR UNIT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
l/s / CFM 808 / 1712AIR FLOWdBA 54SOUND PRESSURE LEVEL
mm/inmm/in
FLARE VALVE9.52 / 3/815.88 / 5/8
PIPECONNECTION
FAN
OU
TD
OO
R U
NIT
FAN MOTOR
COMPRESSOR
COIL
CASING
TYPE
SIZELIQUIDGAS
mm/in
PROPELLER1
ASG 20
DIRECT455 / 17.9
TYPEQUANTITYMATERIALDRIVEDIAMETER
V/Ph/HzWAW
RPM
6
IP23F
220-240 / 1 / 501240.5466874
INDUCTION1
POLES
TYPEQUANTITYINDEX OF PROTECTION (IP)INSULATION GRADEPOWER SOURCERATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUTMOTOR SPEED
cm3 / fl.oz.
V/Ph/HzµFWAA
220-240 / 1 / 5045
249910.98
63
SCROLL
FV50S
1130 / 38E
RATED RUNNING CURRENTLOCKED ROTOR AMP.
TYPEOIL TYPE
OIL AMOUNTINSULATION GRADEPOWER SOURCECAPACITORRATED INPUT POWER
FDMN30CV1M
RN28CV1
Specification (R-410A)Ceiling Concealed Type - FDMN-C Series (COND’T)
22
TM-F
DB
M-0
515-
C
RN35DV1 RN40DY1Btu/h 32,000 39,000
W 9,379 11,430W 3,287 4,287A 15.2 [7.4]
V/Ph/Hz 220-240 / 1 / 50 380-415 / 3 / 50
S.HIGH l/s / CFMHIGH l/s / CFMMEDIUM l/s / CFMLOW l/s / CFM
ESP(H/M/L) Pa (in.wg.)
mm/inmm/in
V/Ph/HzWAW
kg/lb 2.00 / 4.41 2.32 / 5.11REFRIGERANT CHARGE
RATED RUNNING CURRENT 2.27MOTOR OUTPUT 470
POLES 4
IP21INSULATION GRADE BPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWER 503
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP)
DIAMETER 214 / 8.43LENGTH 203.2 / 8.00
CENTRIFUGAL FANQUANTITY 2MATERIAL GALVANIZED STEELDRIVE DIRECT
HIGH STATIC FAN MOTOR
AIR FLOW
604 / 1280547 / 1160496 / 1050434 / 920
118 / 96 / 78 / 61 (0.47 / 0.39 / 0.31 / 0.24)TYPE
REFRIGERANT TYPE R-410AREFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
CONTROLAIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL
FDMN40CV1MOUTDOOR UNIT
TOTAL COOLING CAPACITY
TOTAL INPUT POWERTOTAL RUNNING CURRENT - 1Ø [3Ø]POWER SOURCE
MODELINDOOR UNIT
WITHOUT POWDER PAINT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
SOUND PRESSURE LEVEL (H/M/L) dBA 52 / 49 / 47 / 45mm/inmm/inmm/inmm/inmm/inmm/inkg/lbUNIT WEIGHT
FAN
FAN MOTOR
IND
OO
R U
NIT
COIL
AIRQUALITY
CASING
49 / 108
638 / 25.1
PACKING DIMENSION
HEIGHT 355 / 14.0WIDTH 1461 / 57.5DEPTH 727 / 28.6
UNIT DIMENSION
HEIGHT 315 / 12.4WIDTH 1257 / 49.5DEPTH
mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4
mm/inmm/in
mm/inm2/ft2
ROW 3FIN PER INCH 18
MATERIAL ALUMINIUM (HYDROPHILIC FIN)THICKNESS 0.11 / 0.0043FACE AREA 0.34 / 3.61
TUBEMATERIAL COPPERDIAMETER 7.00 / 0.276THICKNESS 0.28 / 0.011
FIN
pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in
230 / 9.065 / 0.20
AIRFILTER
COLOUR
TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 2
SIZE608 / 23.94
Specification (R-410A)Ceiling Concealed Type - FDMN-C Series
23
TM-F
DB
M-0
515-
C
mm/inmm/in
mm/inm2/ft2
cm3 / fl.oz. 1242 / 42 1951 / 66
V/Ph/Hz 220-240 / 1 / 50 380-415 / 3 / 50
µF 60 N/AW 2527 3527
A 11.83 [6.28]
A 97 [64]LOCKED ROTOR AMP. - 1Ø [3Ø]
INSULATION GRADE EPOWER SOURCECAPACITORRATED INPUT POWERRATED RUNNING CURRENT - 1Ø [3Ø]
2FIN PER INCH 18
IVORY WHITE
TYPE SCROLLOIL TYPE POE OILOIL AMOUNT
THICKNESS 0.23 / 0.009
FIN
COLOUR
MATERIAL ALUMINIUM (CORR. FIN)THICKNESS 0.11 / 0.0043
FACE AREA 0.85 / 9.15ROW
TUBE
MATERIAL COPPERDIAMETER 7.00 / 0.276
MODELINDOOR UNIT
OUTDOOR UNIT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
l/s / CFMAIR FLOW 1605 / 3400
dBA 58SOUND PRESSURE LEVELmm/inmm/inmm/inmm/inmm/inmm/inkg/lbUNIT WEIGHT 86 / 190
PACKING
DIMENSION
HEIGHT 1010 / 39.8WIDTH 1180 / 46.5DEPTH 514 / 20.2
UNIT
DIMENSION
HEIGHT 852 / 33.5WIDTH 1030 / 40.6DEPTH 400 / 15.7
95 / 209
mm/in
mm/inGAS 15.88 / 5/8
PIPECONNECTION
FAN
OU
TD
OO
R U
NIT
FAN MOTOR
COMPRESSOR
COIL
CASING
TYPE FLARE VALVE
SIZELIQUID 9.52 / 3/8
mm/inDIAMETER 610 / 24
QUANTITY 1
MATERIAL ASG 20
DRIVE DIRECT
TYPE PROPELLER
V/Ph/HzW
A
W
RPM
POLES 8
220-240 / 1 / 50
RATED INPUT POWER 257
RATED RUNNING CURRENT 1.10
MOTOR OUTPUT
MOTOR SPEED
145
625
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) IP54
INSULATION GRADE B F
POWER SOURCE
RN35DV1 RN40DY1
FDMN40CV1M
Specification (R-410A)Ceiling Concealed Type - FDMN-C Series (COND’T)
24
TM-F
DB
M-0
515-
C
FDMN50CV1MRN50DY1
FDMN60CV1MRN61DY1
Btu/h 45,000 55,000W 13,189 16,120W 4,931 5,758A [8.5] [9.4]
V/Ph/Hz
S. HIGH l/s / CFM 675 / 1430 812 / 1720HIGH l/s / CFM 623 / 1320 732 / 1550MEDIUM l/s / CFM 580 / 1230 632 / 1340LOW l/s / CFM 533 / 1130 552 / 1170
ESP (H/M/L) Pa (in.wg.) 147 / 126 / 109 / 92 (0.59 / 0.50 / 0.44/ 0.37) 147 / 120 / 90 / 69 (0.59 / 0.48 / 0.36 /0.28)
mm/in
SOUND PRESSURE LEVEL (H/M/L) dBA 54 / 53 / 52 / 51 54 / 52 / 50 / 46
V/Ph/HzW 515 659A 2.32 2.91W 480 600
mm/inINDOOR CONDENSATE DRAIN SIZE 19.1 / 3/4
RATED RUNNING CURRENTMOTOR OUTPUTPOLES 4
IP20INSULATION GRADE BPOWER SOURCE 220-240 / 1 / 50RATED INPUT POWER
TYPE INDUCTIONQUANTITY 1INDEX OF PROTECTION (IP)
DIRECTDIAMETER 214 / 8.43LENGTH 203.2 / 8.00
IND
OO
R U
NIT
HIGH STATIC FAN MOTOR
AIRFLOW
TYPE CENTRIFUGAL FANQUANTITY 2MATERIAL GALVANIZED STEELDRIVE
CONTROLAIR DISCHARGE DUCTEDOPERATION WIRED REMOTE CONTROL
POWER SOURCE 380-415 / 3 / 50REFRIGERANT TYPE R-410AREFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE & TXV
MODELINDOOR UNITOUTDOOR UNIT
TOTAL COOLING CAPACITY
TOTAL INPUT POWERTOTAL RUNNING CURRENT - 1Ø [3Ø]
mm/in
kg/lb 2.10 / 4.63 2.90 / 6.39REFRIGERANT CHARGE
mm/in 378 / 14.9mm/in 1299 / 51.1 1499 / 59.0mm/in 541 / 21.3mm/in 415 / 16.3mm/in 1497 / 59.0 1701 / 67.0mm/in 631 / 24.8kg/lb 50 / 110 56 / 123UNIT WEIGHT
FAN
FAN MOTOR
COIL
UNIT DIMENSION
HEIGHTWIDTHDEPTH
PACKING DIMENSION
HEIGHTWIDTHDEPTH
mm/inmm/in
mm/inm2/ft2 0.40 / 4.40 0.47 / 5.16
318 20FIN PER INCH
7.00 / 0.276THICKNESS 0.28 / 0.011
FIN
MATERIAL ALUMINIUM (HYDROPHILIC FIN)THICKNESS 0.11 / 0.0043FACE AREAROW
TUBEMATERIAL COPPERDIAMETER
pcLENGTH mm/in 634 / 24.96 734 / 28.90WIDTH mm/in 305 / 12.01THICKNESS mm/in
AIRFILTER
COLOUR
AIRQUALITY
CASING
TYPE WASHABLE SARANET FILTER (OPTIONAL)QUANTITY 2
SIZE5 / 0.20
WITHOUT POWDER PAINT
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
Specification (R-410A)Ceiling Concealed Type - FDMN-C Series
25
TM-F
DB
M-0
515-
C
mm/inmm/in
mm/in 0.10 / 0.004
m2/ft2 0.85 / 9.15 0.84 / 9.04
2 3
18
IVORY WHITE
mm/in 852 / 33.5mm/in 1030 / 40.6mm/in 400 / 15.7mm/in 1010 / 39.8mm/in 1180 / 46.5mm/in 514 / 20.2kg/lb 98 / 216UNIT WEIGHT
UNIT
DIMENSION
HEIGHTWIDTHDEPTH
PACKING
DIMENSION
HEIGHTWIDTHDEPTH
MATERIAL ALUMINIUM (CORR. FIN)THICKNESSFACE AREAROWFIN PER INCH
TUBE
MATERIAL INNER GROOVE COPPERDIAMETER 7.00 / 0.276THICKNESS 0.23 / 0.009
FIN
COLOUR
MODELINDOOR UNIT
OUTDOOR UNIT
OU
TD
OO
R U
NIT
105 / 231
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR 4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION5) *NON-STANDARD MODEL, DELIVERY UPON REQUEST.
l/s / CFMAIR FLOW 1442 / 3056
dBA 60 65SOUND PRESSURE LEVEL
mm/in 9.52 / 3/8mm/in 15.88 / 5/8 19.05 / 3/4
PIPECONNECTION
FAN
FAN MOTOR
COMPRESSOR
COIL
CASING
TYPE FLARE VALVE
SIZELIQUID
GAS
mm/inDIAMETER 610 / 24
QUANTITY 1
MATERIAL ASG 20
DRIVE DIRECT
TYPE PROPELLER
F
V/Ph/Hz
W
A
W
RPM
RATED RUNNING CURRENT 1.34MOTOR OUTPUT
MOTOR SPEED
145
625
POLES 8
IP54
INSULATION GRADE
POWER SOURCE 220-240 / 1 / 50
RATED INPUT POWER 276
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP)
cm3 / fl.oz. 1656 / 56 1591 / 56
V/Ph/HzµFW 4140 4823
A [7.28] [7.99]
A [74]
380-415 / 3 / 50CAPACITOR N/A
RATED INPUT POWERRATED RUNNING CURRENT - 1Ø [3Ø]LOCKED ROTOR AMP. - 1Ø [3Ø]
TYPE SCROLL
OIL TYPE COPELAND ULTRA 32-3 MAF
OIL AMOUNT
INSULATION GRADE EPOWER SOURCE
FDMN50CV1M
RN50DY1
FDMN60CV1M
RN61DY1
Specification (R-410A)Ceiling Concealed Type - FDMN-C Series(COND’T)
26
TM-F
DB
M-0
515-
C
Safety Device - R-22 Series
OPEN kPa / psi
CLOSE kPa / psi
OPEN kPa / psi
CLOSE kPa / psi
°C / °F
OPEN kPa / psi
CLOSE kPa / psi
OPEN kPa / psi
CLOSE kPa / psi
°C / °F <130 / 266>
2413 / 350
NC
124 / 18
193 / 28
<YES>
<YES>
<130 / 266>
FDM60CV1M
FDB60CV1M
R61DY1
NC
2937 / 426
NC
2937 / 426
2413 / 350
NC
124 / 18
193 / 28
PHASE SEQUENCER, 1Ø <3Ø>
TYPE
PHASE SEQUENCER, 1Ø <3Ø>
MODEL
INDOOR UNIT
OUTDOOR UNIT
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
LOW PRESSURE SWITCH
TYPE
DISCHARGE THERMOSTAT SETTING
MODELINDOOR UNIT
OUTDOOR UNIT
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
LOW PRESSURE SWITCH
DISCHARGE THERMOSTAT SETTING
R35DV1 R40DY1
FDM50CV1M
FDB50CV1M
R50DY1
NC
OPEN kPa / psi 2937 / 426
CLOSE kPa / psi 2413 / 350
NC
OPEN kPa / psi 124 / 18
CLOSE kPa / psi 193 / 28
NA <YES>
°C / °F NA <130 / 266>
LOW PRESSURE SWITCH
TYPE
MODEL
INDOOR UNIT FDM40CV1M
FDB40CV1M
OUTDOOR UNIT
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
PHASE SEQUENCER, 1Ø <3Ø>
DISCHARGE THERMOSTAT SETTING
OPEN kPa / psi
CLOSE kPa / psi
OPEN kPa / psi
CLOSE kPa / psi
°C / °F
124 / 18
193 / 28
YES
125 / 257
FDM30CV1M
FDB30CV1M
R30CV1
NC
2937 / 426
2413 / 350
NC
LOW PRESSURE SWITCH
TYPE
PHASE SEQUENCER, 1Ø <3Ø>
DISCHARGE THERMOSTAT SETTING
MODELINDOOR UNIT
STANDARD STATIC PRESSURE
NON STANDARD STATIC PRESSURE
OUTDOOR UNIT
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
STANDARD STATIC PRESSURE
NON STANDARD STATIC PRESSURE
STANDARD STATIC PRESSURE
NON STANDARD STATIC PRESSURE
STANDARD STATIC PRESSURE
NON STANDARD STATIC PRESSURE
27
TM-F
DB
M-0
515-
C
RN35DV1 RN40DY1
NC
OPEN kPa / psi 4137 / 600
CLOSE kPa / psi 3310 / 480
NC
OPEN kPa / psi 48 / 7
CLOSE kPa / psi 152 / 22
NA <YES>
°C / °F NA <130 / 266>
FDMN50CV1M
RN50DY1
FDMN60CV1M
RN61DY1
NC
OPEN kPa / psi 4137 / 600
CLOSE kPa / psi 3310 / 480
NC
OPEN kPa / psi 48 / 7
CLOSE kPa / psi 152 / 22
<YES>
°C / °F <130 / 266>
TYPE
LOW PRESSURE SWITCH
PHASE SEQUENCER, 1Ø <3Ø>
DISCHARGE THERMOSTAT SETTING
PHASE SEQUENCER, 1Ø <3Ø>
DISCHARGE THERMOSTAT SETTING
MODELINDOOR UNIT
OUTDOOR UNIT
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
LOW PRESSURE SWITCH
TYPE
MODELINDOOR UNIT FDMN40CV1M
OUTDOOR UNIT
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
Safety Device - R-410A Series
28
TM-F
DB
M-0
515-
C
4.SelectionProcess
HIGHMEDLOW
4.00
5. 00
6.00
7.00
0.00
1.00
2.00
3.00
200.00 250.00 300.00 350.00 400.00 450.00
Fan Performance CurveFDM10CV1M
(High Static Blower)
Ex
tern
al S
tati
c P
res
su
re, (
mm
w.g
.)
Flowrate, (CFM)
29
TM-F
DB
M-0
515-
C
Fan Performance CurveFDM15CV1M
(High Static Blower)
HIGHMEDLOW
4.00
5.00
6.00
7.00
0.00
1.00
2.00
3.00
300.00 350.00 400.00 450.00 500.00 550.00 600.00 650.00 700. 00 750.00 800.00
Ex
tern
al
Sta
tic
Pre
ss
ure
, (m
m w
.g.)
Flowrate, (CFM)
30
TM-F
DB
M-0
515-
C
Fan Performance CurveFDM20CV1M
(High Static Motor)
HIGHMEDLOW
4.00
5.00
6.00
7.00
Ex
tern
al S
tati
c P
res
su
re, (
mm
w.g
.)
0.00
1.00
2.00
3.00
550.00 600.00 650.00 700.00 750.00 800.00 850.00 900.00 950. 00
Flowrate, (CFM)
31
TM-F
DB
M-0
515-
C
Fan Performance CurveFDM25CV1M
(High Static Motor)
HIGHMEDLOW
4.00
5.00
6.00
7.00
0.00
1.00
2.00
3.00
400.00 450.00 500.00 550.00 600.00 650.00 700.00 750.00 800. 00 850.00 900.00
Flowrate, (CFM)
Ex
tern
al
Sta
tic
Pre
ss
ure
, (m
m w
.g.)
32
TM-F
DB
M-0
515-
C
0
1
2
3
4
5
6
7
8
9
10
11
12
13
400 500 600 700 800 900 1000 1100 1200
Flowrate, (CFM)
To
tal S
tati
c P
ress
ure
, (m
m w
.g.)
Fan Performance CurveFDM30CV1M
(High Static Blower)
33
TM-F
DB
M-0
515-
C
Fan Performance CurveFDM40CV1M
(High Static Blower)
0
1
2
3
4
5
6
7
8
9
10
11
12
13
400 500 600 700 800 900 1000 1100 1200 1300 1400
Flowrate, (CFM)
To
tal S
tati
c P
ress
ure
, (m
m w
.g.)
34
TM-F
DB
M-0
515-
C
Fan Performance CurveFDM50CV1M
(High Static Blower)
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
Flowrate, (CFM)
To
tal S
tati
c P
ress
ure
, (m
m w
.g.)
35
TM-F
DB
M-0
515-
C
Fan Performance CurveFDM60CV1M
(High Static Blower)
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1200 1300 1400 1500 1600 1700 1800 1900 2000
Flowrate, (CFM)
To
tal S
tati
c P
ress
ure
, (m
m w
.g.)
36
TM-F
DB
M-0
515-
C
Fan Performance CurveFDB10CV1M
(Low Static Motor)
Flowrate, (CFM)
Ex
tern
al
Sta
tic
Pre
ss
ure
, (m
m w
.g.)
HIGHMEDLOW
2.50
3.00
3.50
4.00
4.50
5.00
0.00
0.50
1.00
1.50
2.00
100.00 150.00 200.00 250.00 300.00 350.00
37
TM-F
DB
M-0
515-
C
Fan Performance CurveFDB15CV1M
(Low Static Motor)
Flowrate, (CFM)
Ex
tern
al
Sta
tic
Pre
ss
ure
, (m
m w
.g.)
HIGHMEDLOW
2.50
3.00
3.50
4.00
4.50
5.00
0.00
0.50
1.00
1.50
2.00
200.00 250.00 300.00 350.00 400.00 450.00 500.00 550.00 600. 00 650.00
38
TM-F
DB
M-0
515-
C
Fan Performance CurveFDB20CV1M
(Low Static Motor)
Flowrate, (CFM)
Ex
tern
al
Sta
tic
Pre
ss
ure
, (m
m w
.g.)
HIGHMEDLOW
2.50
3.00
3.50
4.00
4.50
5.00
0.00
0.50
1.00
1.50
2.00
450.00 500.00 550.00 600.00 650.00 700.00 750.00 800.00
39
TM-F
DB
M-0
515-
C
Fan Performance CurveFDB25CV1M
(Low Static Motor)
Flowrate, (CFM)
Ex
tern
al
Sta
tic
Pre
ss
ure
, (m
m w
.g.)
HIGHMEDLOW
2.50
3.00
3.50
4.00
4.50
5.00
0.00
0.50
1.00
1.50
2.00
450.00 500.00 550.00 600.00 650.00 700.00 750.00 800.00 850. 00
40
TM-F
DB
M-0
515-
C
Fan Performance CurveFDB30CV1M
(Low Static Blower)
0
1
2
3
4
5
6
550 650 750 850 950 1050
Flowrate, (CFM)
To
tal S
tati
c P
ress
ure
, (m
m w
.g.)
41
TM-F
DB
M-0
515-
C
Fan Performance CurveFDB40CV1M
(Low Static Blower)
0
1
2
3
4
5
850 950 1050 1150 1250 1350
Flowrate, (CFM)
To
tal S
tati
c P
ress
ure
, (m
m w
.g.)
42
TM-F
DB
M-0
515-
C
Fan Performance CurveFDB50CV1M
(Low Static Blower)
0
1
2
3
4
5
6
1100 1200 1300 1400 1500 1600 1700
Flowrate, (CFM)
To
tal S
tati
c P
ress
ure
, (m
m w
.g.)
43
TM-F
DB
M-0
515-
C
Fan Performance CurveFDB60CV1M
(Low Static Blower)
0
1
2
3
4
5
6
1400 1500 1600 1700 1800 1900
Flowrate, (CFM)
To
tal S
tati
c P
ress
ure
, (m
m w
.g.)
44
TM-F
DB
M-0
515-
C0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
100 200 300 400
Ext
ern
al S
tati
c P
ress
ure
, (m
m w
.g.)
Flowrate, (CFM)
HM
L
Fan Performance CurveFDMN10CV1M
45
TM-F
DB
M-0
515-
C 0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
300 350 400 450 500
Ext
ern
al S
tati
c P
ress
ure
, (m
m w
.g.)
Flowrate, (CFM)
HM
L
Fan Performance CurveFDMN15CV1M
46
TM-F
DB
M-0
515-
C
Fan Performance CurveFDMN20CV1M
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
400 500 600 700
Ext
ern
al S
tati
c P
ress
ure
, (m
m w
.g.)
Flowrate, (CFM)
HM
L
47
TM-F
DB
M-0
515-
C
Fan Performance CurveFDMN25CV1M
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
400 500 600 700 800
Ext
ern
al S
tati
c P
ress
ure
, (m
m w
.g.)
Flowrate, (CFM)
H
ML
48
TM-F
DB
M-0
515-
C
Fan Performance CurveFDMN30CV1M
0
2
4
6
8
10
12
14
200.00 400.00 600.00 800.00 1000.00 1200.00
Ext
ern
al S
tati
c P
ress
ure
, (m
m w
.g.)
Flowrate, (CFM)
SH
H
ML
L
49
TM-F
DB
M-0
515-
C
Fan Performance CurveFDMN40CV1M
0
5
10
15
600 800 1000 1200 1400 1600
To
tal S
tati
c P
ress
ure
, (m
m w
.g.)
Flowrate, (CFM)
SHH
M
L
50
TM-F
DB
M-0
515-
C
Fan Performance CurveFDMN50CV1M
0
5
10
15
20
25
1000 1200 1400 1600 1800
To
tal S
tati
c P
ress
ure
, (m
m w
.g.)
Flowrate, (CFM)
SH
H
M
L
51
TM-F
DB
M-0
515-
C
Fan Performance CurveFDMN60CV1M
0
5
10
15
20
25
1000 1200 1400 1600 1800 2000 2200
To
tal S
tati
c P
ress
ure
, (m
m w
.g.)
Flowrate, (CFM)
SHH
M
L
52
TM-F
DB
M-0
515-
C
5.ApplicationInformation
Ensure the operating temperature is in allowable range.
Cooling Only
! Caution :
The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.
Out
door
tem
p. (°
CD
B)
Indoor temp. (°CWB)
-5
19
35
15
46
24
52
Standard point
High ambient unit
Low ambient kit
Note :
Standard operating range.
With High ambient unit. (Optional item) Please refer to local dealer for unit of this specification.
With Low ambient kit. (Optional item) Please refer to local dealer for unit of this specification.
53
TM-F
DB
M-0
515-
C
Model : (Indoor) FDB10CV1M, FDM10CV1M, FDB15CV1M, FDM15CV1M, FDB20CV1M, FDM20CV1M, FDMN10CV1M, FDMN15CV1M, FDMN20CV1M, FDMN25CV1M (Outdoor) R10CV1, R15CV1, R20CV1, RN10FV1, RN15FV1, RN18CV1, RN20CV1, RN25CV1
Model : (Indoor) FDB25CV1M, FDM25CV1M, FDMN30CV1M (Outdoor) R20CV1, R25CV1, RN28CV1
54
TM-F
DB
M-0
515-
C
Model : (Indoor) FDM30CV1M, FDB30CV1M; (Outdoor) R28CV1, R30CV1
Model : (Indoor) FDM40CV1M, FDB40CV1M, FDM50CV1M, FDB50CV1M, FDM60CV1M, FDB60CV1M; (Outdoor) R35DV1, R40DY1, R50DY1, R61DY1
55
TM-F
DB
M-0
515-
C
Model : (Indoor) FDMN40CV1M, FDMN50CV1M, FDMN60CV1M; (Outdoor) RN35DV1, RN40DY1, RN50DY1, RN61DY1
56
TM-F
DB
M-0
515-
C
Controller
DSLM8
Operating Guide
MODETURBO
TIMEROVERRIDE
TIMER
ON OFFTIMER
SWING QUIET
SLEEP
14
5
6
23
1011
8
97
1 MODE Button Press the MODE button to switch operation from COOL, AUTO*, DRY*, FAN. Check the display to
see in which mode the control is set. *AUTO and DRY are available for selected models only.
2 TURBO Fan Speed Press the Turbo key once to activate Turbo fan speed. Turbo symbol will be shown. To disable Turbo
fan speed and back to previous fan speed, press the Turbo key once again. For the unit that does not have TURBO fan speed it will show high fan speed.
3 SWING Function Press SWING button to activate the swing function. Press it again to deactivate it.
4 QUIET Fan Speed Press the Quiet key once to activate Quiet fan speed. Quiet symbol will be shown. To disable Quiet
fan speed and back to previous fan speed, press the Quiet key once again. For the unit that does not have QUIET fan speed it will show low fan speed.
5 “ ” or “ ” Set Temperature Button Press the temperature button and set the temperature of your choice by pressing “ ” or “ ” button
once, temperature changes by 1°C or 1°F. The default temperature setting range is from 16°C to 30°C (60°F to 86°F). When the Option 20 - 30ºC is set, the temperature range limit is set to 20ºC to 30ºC (68°F to 86°F). Pressing both keys simultaneously will toggle the temperature setting between ºC and ºF.
6 SLEEP Function Press the SLEEP button to activate the sleep mode. DRY MODE and FAN MODE are not valid
during sleep function.
57
TM-F
DB
M-0
515-
C
7 “ON TIMER” and “OFF TIMER” The unit has 2-event timer, namely Timer 1 and Timer 2, each event has an ON TIMER and an OFF
TIMER. The key press activity for Timer ON and Timer OFF is shown on Table 1.1 Table 1.1: Timer ON and Timer OFF key press and event sequence.
All timers are event-triggered timers and can be overridden by the ON/OFF button and Override function.
Set Event 1 and Event 2 Timers
Process for Timer ON and Timer OFF is the same.1. Press and hold Timer ON/OFF key for 3 seconds to go into timer setting mode. (Icon ON 1 or OFF 1 will blink)2. Press UP or DOWN to select Timer 1 or Timer 2 to set. (‘1’ blinking indicate that Timer 1 is currently selected, ‘2’ blinking indicate that Timer 2 is currently selected)3. Press Timer ON/OFF key again to confirm. (Day will blink next)4. Press UP or DOWN to select the day.5. Press Timer ON/OFF key again to confirm the day. (Hour will blink next)4. Press UP or DOWN to change the hour.5. Press Timer ON/OFF key again to confirm the hour. (Minute will blink next)6. Press UP or DOWN to change the minute.7. Press Timer ON/OFF key again to confirm the minute.
Each timer (Timer 1 ON or Timer 1 OFF or Timer 2 ON or Timer 2 OFF) will only be set separately after all 7 steps, if there is no key operation for 5 seconds during setting the timer, it will automatically exits from setting mode and no changes will be made.
ON/OFF timer will be checked every 1 minute.It is not advisable to set ON TIMER and OFF TIMER to have same values. Shall these occur, the effective timer will be treated with priority as stated in Table 1.2.Example:ON TMR 2 settings: DAY – TUE, TIMER – 5.00pmOFF TMR 1 settings: DAY – TUE, TIMER – 5.00pmOutcome when RTC reaches 5.00pm on TUE: - when unit is on, no respond. - when unit is off, unit will trigger to on.
Table 1.2: Timer Priority
ON Timer 1 ON Timer 2 OFF Timer 1 OFF Timer 2 Deactivated Deactivated Deactivated Deactivated Activated Deactivated Activated Deactivated Deactivated Activated Deactivated Activated Activated Activated Activated Activated
TIMER ON KEY TIMER OFF KEY
Priority Timer
1 (Highest)
2
3
4 (Lowest)
ONTMR2
OFFTMR2
ONTMR1
OFFTMR1
Upon IR reception, IR wireless remote controller will override ON TIMER 2 and OFF TIMER 2 settings.
58
TM-F
DB
M-0
515-
C
8 OVERRIDE Function Press the OVERRIDE key once will activate the override function for 1 hour. An indicator
“OVERRIDE 1” will show on the LCD. Press the same key again will increase the setting to 2 hours. An indicator “OVERRIDE 2” will be shown. Subsequent press will deactivate the override function. After the override timer is completed, the override function is deactivated and the logo is OFF. All other timers will be resumed.
9 FAN Speed Function Fan speed can be changed via pressing the FAN key: Low > Med > High > Auto > Low >
10 ON/OFF Button Starting Operation: - Press the ON/OFF button, the LCD will show full display and the unit is turned on. Stopping Operation: - Press the ON/OFF button, the LCD will show real time clock only and the unit is turn off.
11 Real-time Clock (RTC) Display RTC is shown on screen during the unit ON or OFF except for power failure or error code.
Set RTC Setting 1. Press RTC key one time will activate RTC setting mode. (Day will blink) 2. Press UP or DOWN to select the day. 3. Press RTC again to confi rm the day. (Hour will blink next) 4. Press UP or DOWN to change the hour. 5. Press RTC again to confi rm the hour. (Minute will blink next) 6. Press UP or DOWN to change the minute. 7. Press RTC again to confi rm the minute. RTC will only be set after all 7 steps, if there is no key operation for 5 seconds during setting the
RTC, it will automatically exits from setting mode and no changes will be made on the setting.
12 Hardware Setting The unit has 4 jumpers option to control the board function. Table 2.0: Summary of Hardware Settings
OPTION
Set Temp. Range
TURBO_QUIET
Reserved
Reserved
With Jumper
Set Temp. Range from 20˚C-30˚C
Reserved
Reserved
Without Jumper
Set Temp. Range from 16˚C-30˚C(Default)
Enable turbo and quiet fan speed
Reserved
Reserved
Disable turbo and quiet fan speed(Default)
59
TM-F
DB
M-0
515-
C
Phase SequencerTheunitwithScrollCompressorcanonlyrotateinonedirection.Forthisreason,aprotectivedevice(phasesequencer)isfittedtopreventincorrectwiringoftheelectricalphases.Whenthethreephasesarenotconnectedcorrectly,thephasesequenceroperates,andtheunitwillnotstart.Thisdeviseislocatedinthecontrolboxoftheoutdoorunit.
ThefollowingtableshowstheLEDindicatorlightforphasesequencerundernormaloperationandfaultconditions.
Wired Remote Control (Universal Board)
Cooling
Error Code at 7 Segment Display Operation / Faulty Indication
Blink E1 Room sensor contact open / short Blink E2 Indoor coil sensor contact open Blink E3 Outdoor coil sensor contact open
Blink E4 Compressor overload/ Indoor coil sensor short/Outdoor coil sensor short
Blink E5 Gas leak
Blink E6 Pump faulty
Operating State And Fault Table
LED_PWR(Red)
LED_S (Yellow)
LED_T (Yellow)
Normal Operation
LEDs Error Indication
On
On On
On On
-On On
-
-
-
-
- -
-
On
-
Reverse Phase Blink Blink BlinkBlink
Blink
Blink
Blink
System OffBlink
Blink
Blink
T Phase Missing S Phase Missing R Phase Missing R Phase Missing (Main Power) Overload
Sensor Missing
High Pressure
Low Pressure
Notes: 1. “-” means LED off.2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 (Common) and 81(NO) will cut off.3. The unit will check the discharge sensor availability only during power up.4. All errors can only recover through manually reset.
60
TM-F
DB
M-0
515-
C
6.Installations
Installation GuidelineSafety Precautions
WARNING
CAUTIONPlease take note of the following important points when installing.
If gas leaks and accumulates around the unit, it may cause fire ignition.
Ensure that drainage piping is connected properly.If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture.
Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.
Ensure that the unit’s panel is closed after service or installation.
Unsecured panels will cause the unit to operate noisily.
Sharp edges and coil surfaces are potential locations which may cause injury hazards.Avoid from being in contact with these places.
Before turning off the power supply, set the remote controller’s ON/OFF switch to the “OFF” positionto prevent the nuisance tripping of the unit. If this is not done, the unit’s fans will start turning automatically when power resumes, posing a hazard to service personnel or the user. Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt or deform as a result of the excessive heat.
Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively.
IMPORTANT : DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM.Do not use joined and twisted wires for incoming power supply.
Do not install the unit where leakage of flammable gas may occur. •
•
•
•
•
•
•
•
••
NOTICE
• Installation and maintenance should be performed by quali�ed persons who are familiar with local code and regulation, and experienced with this type of appliance.
• All field wiring must be installed in accordance with the national wiring regulation.• Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring
work according to the wiring diagram.• The unit must be GROUNDED to prevent possible hazard due to insulation failure.• All electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors.• Confirm that the unit has been switched OFF before installing or servicing the unit.• Disconnect from the main power supply before servicing the air conditioner unit.• DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which
may result in fire hazards.• Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static
may be heard even when more than 1m away}.
Disposal requirementsYour air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with unsorted household waste.Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil and of other parts must be done by a qualified installer in accordance with relevant local and national legislation. Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or local authority for more information.Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation.
61
TM-F
DB
M-0
515-
C
Indoor Unit
Outdoor Unit
Air Intake
Air Intake
Air Discharge
Return Duct
Hanger
Supply Duct
Thermal Insulation
Wrap the insulated pipe withthe finishing tape from bottom to top
Drain Piping
Installation Diagram
62
TM-F
DB
M-0
515-
C
W
See DetailInsulation material(field supply)
Air outlet side
Aluminium tape(Field supply) (Field supply)
Air inlet side
Field Supply
Washer for hanger bracket(Attached)
Tighten
Aluminium tape
Detail A
L
10m
m (0
.39”
)
Insulate securely
Do not leave in water
Bottom of the unit
Drain trap 100
100
or mo
re or
more
Slant
Unit: mm
300mmor more
Ceiling300mm* or more
2300mm or more
10m
m
Floor
The indoor unit must be installed such that there is no short circuit of the cool discharge. Respect the installation clearance. Do not put the indoor unit where there is direct sunlight on unit. The location is suitable for piping and drainage and it must have a large distance between a door and unit.
Ceiling Concealed Mounting• Use the hanger supplied with the unit.• Make sure that the ceiling is sufficiently strong
to withstand the weight.
Provide clearance for servicing ease and optimalair flow as shown in the diagram.
Center distance of axle (see drawing below)
Ceiling Concealed Drain Piping Work
• The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused by leaks and condensation.
• For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.• Ensure the drain pipe is securely insulated.• It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit
compared to the outside atmospheric pressure when the unit is operating. The drain trap is to avoid possibility of splashes or an odor.
• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.• Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is smooth.• In humid environments, use an extra drain pan to cover the entire area of the indoor unit.
Installation Of Indoor Unit
ModelFDB10CV1M, FDM10CV1M, FDMN10CV1MFDB15CV1M, FDM15CV1M, FDMN15CV1MFDB20CV1M, FDM20CV1M, FDMN20CV1MFDB25CV1M, FDM25CV1M, FDMN25CV1MFDMN30CV1MFDM30CV1M, FDB30CV1MFDMN40CV1MFDM40CV1M, FDB40CV1MFDM50CV1M, FDB50CV1M, FDMN50CV1MFDM60CV1M, FDB60CV1M, FDMN60CV1M
741 (29.2)881 (34.7)
1041 (41.0)1176 (46.3)959 (37.8)956 (37.6)
1264 (49.8)1076 (42.4)1326 (52.2)1526 (60.1)
225 (8.9)225 (8.9)225 (8.9)225 (8.9)
339 (13.3)256 (101)401 (15.8)256 (10.1)256 (10.1)256 (10.1)
W mm (inch)L mm (inch)
* Can be smaller than 300mm if ceiling is removable.
63
TM-F
DB
M-0
515-
C
Installation Of The Outdoor Unit
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum cooling capacity, the location selected for outdoor unit should fulfill the following requirements:
• Install the condensing (outdoor) unit in a way such that the hot air distributed by the outdoor condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the unit.
• Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air intake or discharge.
• The location must be well ventilated, so that the unit can draw in and distribute of air thus lowering the condensing temperature.
• A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.• A place protected from the direct sunlight. Otherwise use an awning for protection, if necessary.
• The location must not be susceptible to dust or oil mist.
Installation Clearances
Note: If there is any obstacle higher than 2m, or if there is any obstruction at the upper part of the unit, please allow more space than the figure indicated in the above table.
Dimension A B C D
Minimum Distance, mm (in)
300(11.8)
1000(39.4)
300(11.8)
500(19.7)
Ret
urn
air
Dis
char
ge a
ir
A
Obs
tacl
e
Obs
tacl
e
B
Obs
tacl
e
Ret
urn
air
Ser
vice
acc
ess
DC
Obs
tacl
e
64
TM-F
DB
M-0
515-
C
Refrigerant PipingAllowable Pipe Length and ElevationIf the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to the flow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective. Always choose the shortest path and follow the recommendations as tabulated below:
For R22
Model
Max. allowable length, mMax. allowable elevation, m
Liquid pipe size, mm/(in)
Gas pipe size, mm/(in)
Indoor
Outdoor125
6.35(1/4”)9.52(3/8”)
125
6.35(1/4”)12.70(1/2”)
158
6.35(1/4”)15.88(5/8”)
158
9.52(3/8”)15.88(5/8”)
Model
Max. allowable length, mMax. allowable elevation, m
Liquid pipe size, mm/(in)
Gas pipe size, mm/(in)
Indoor
Outdoor R28CV1158
9.52(3/8”)15.88(5/8”)
R30CV1258
9.52(3/8”)15.88(5/8”)
R35DV14525
9.52(3/8”)19.05(3/4”)
R40DY14525
9.52(3/8”)19.05(3/4”)
R50DY14525
9.52(3/8”)19.05(3/4”)
R61DY13515
12.70(3/8”)19.05(3/4”)
FDM30CV1MFDB30CV1M
FDM40CV1MFDB40CV1M
FDM50CV1MFDB50CV1M
FDM60CV1MFDB60CV1M
For R410A
Model
Max. allowable length, mMax. allowable elevation, m
Liquid pipe size, mm/(in)
Gas pipe size, mm/(in)
IndoorOutdoor
FDMN10CV1M
RN10FV12010
6.35(1/4”)9.52(3/8”)
FDMN15CV1M
RN15FV12010
6.35(1/4”)12.70(1/2”)
FDMN20CV1M
RN20CV12010
6.35(1/4”)12.70(1/2”)
FDMN25CV1M
RN25CV12010
6.35(1/4”)15.88(5/8”)
Model
Max. allowable length, mMax. allowable elevation, m
Liquid pipe size, mm/(in)
Gas pipe size, mm/(in)
IndoorOutdoor
FDMN30CV1M
RN28CV1158
9.52(3/8”)15.88(5/8”)
RN35DV14525
9.52(3/8”)15.88(5/8”)
RN40DY14525
9.52(3/8”)15.88(5/8”)
FDMN50CV1M
RN50DY14525
9.52(3/8”)15.88(5/8”)
FDMN60CV1M
RN61DY13515
9.52(3/8”)19.05(3/4”)
FDMN40CV1M
Standard Static PressureNon-Standard Static Pressure
Standard Static PressureNon-Standard Static Pressure
FDB10CV1MFDM10CV1M
R10CV1
FDB15CV1MFDM15CV1M
R15CV1
FDB20CV1MFDM20CV1M
R20CV1
FDB25CV1MFDM25CV1M
R25CV1
65
TM-F
DB
M-0
515-
C
Remove burr
Cutting copper tube
1/4t
Flared tubeFlare joint
Flare nutIndoor piping
Torque wrenchSpanar
Ø Tube, D A (mm)
Inch mm Imperial (Wing-nut Type)
Rigid (Clutch Type)
1/4" 6.35 1.3 0.7
3/8" 9.52 1.6 1.0
1/2" 12.70 1.9 1.3
5/8" 15.88 2.2 1.7
3/4" 19.05 2.5 2.0
Pipe Size (mm/in)
Torque (Nm/ft-lb)
6.35 (1/4") 18 (13.3)
9.52 (3/8") 42 (31.0)
12.70 (1/2") 55 (40.6)
15.88 (5/8") 65 (48.0)
19.05 (3/4") 78 (57.6)
Figure D
Figure A
Copper tubeSwaging block A
D
Figure B
Figure C
Piping Works And Flaring Technique• Do not use contaminated or damaged copper
tubing. If any piping, evaporator or condenser had been exposed or had been opened for 15 seconds or more, the system must be vacuumed. Generally do not remove plastic, rubber plugs and brass nuts from the valves, fittings, tubing and coils until it is ready to connect suction or liquid line into valves or fittings.
• If any brazing work is required, ensure that nitrogen gas is passed through coil and joints while the brazing work is being done. This will eliminate soot formation on the inside wall of copper tubings.
• Cut the pipe stages by stages, advancing the blade of pipe cutter slowly. Extra force and a deep cut will cause more distortion of pipe and therefore extra burr. See Figure A.
• Remove burrs from cut edges of the pipes with remover. See Figure B. Hold the pipe on top position and burr remover at lower position to prevent metal chips from entering the pipe. This will avoid unevenness on the flare faces which will cause gas leak.
• Insert the flare nuts, mounted on the connection parts of both the indoor unit and outdoor unit, into the copper pipes.
• The exact length of pipe protruding from the top surface of the swaging block is determined by the flaring tool. See Figure C.
• Fix the pipe firmly on the swaging block. Match the centers of both the swaging block and the flaring punch, then tighten the flaring punch fully.
Piping Connection To The Units
• Align the center of the piping and tighten the flare nut sufficiently with fingers. See Figure D.
• Finally, tighten the flare nut with torque wrench until the wrench clicks.
• When tightening the flare nut with the torque wrench, ensure that the tightening direction follows the arrow indicated on the wrench.
• The refrigerant pipe connection are insulated by closed cell polyurethane.
66
TM-F
DB
M-0
515-
C
Vacuuming is necessary to eliminate all moisture and air from the system.
Refrigerant Piping
Outdoor Unit 3 ways valve
Allen key
Service Port
Flare nut
HIGH PRESSURE GAUGE
GAUGE MANIFOLD
LOW PRESSURE GAUGE
HANDLE HI (ALWAYS CLOSED)
CHARGE HOSE
-760mmHg
HANDLE LO
CHARGE HOSE VACUUM PUMP ADAPTER FOR
COUNTER FLOW PREVENTION
CHECK
VALVE
LIQUID
VALVE
HIGH PRESSURE GAUGELOW PRESSURE GAUGE
GAUGE MANIFOLD-760mmHg
HANDLE LO HANDLE HI (ALWAYS CLOSED)
CHARGE HOSECHARGE HOSE
CHECK
VALVE
LIQUID
VALVEGAS VALVE
(3-WAY)
CONFIGURATION OF AIR PURGE BY CHARGING
GAS VALVE (3-WAY)
CONFIGURATION OF AIR PURGE BY CHARGING
Vacuuming And Charging
Vacuuming The Piping And The Indoor UnitExcept for the outdoor unit which is pre-charged with refrigerant, the indoor unit and the refriger-ant connection pipes must be air-purged because the air containing moisture that remains in the refrigerant cycle may cause malfunction of the compressor.• Remove the caps from the valve and the
service port.• Connect the center of the charging gauge to
the vacuum pump.• Connect the charging gauge to the service port
of the 2-way valve.• Start the vacuum pump. Evacuate for approxi-
mately 30 minuted. The evacuation time varies with different vacuum pump capacity. Confirm that the charging gauge needle has moved towards - 760mmHg.
Caution• If the gauge needle does not move to
-760mmHg, be sure to check for gas leaks (using the refrigerant detector) at fl are type connection of the indoor and outdoor unit and repair the leak before proceeding to the next step.
• Close the valve of the changing gauge and stop the vacuum pump.
• On the outdoor unit, open the suction valve (3 way) and liquid valve (2 way) (in anti-clockwise
direction) with 4mm key for hexagon sacked screw.
Charge OperationThis operation must be done by using a gas cylinder and a precise weighing machine. The additional charge is topped-up into the outdoor unit using the suction valve via the service port.
• Remove the service port cap.• Connect the low pressure side of the charging
gauge to the suction service port center of the cylinder tank and close the high pressure side of the gauge. Purge the air from the service hose.
• Start the air conditioner unit.
• Open the gas cylinder and low pressure charging valve.
• When the required refrigerant quantity is pumped into the unit, close the low pressure side and the gas cylinder valve.
• Disconnect the service hose from service port. Put back the service port cap.
67
TM-F
DB
M-0
515-
C
Additional Charge
For R22
For R410A
The refrigerant is pre-charge in the outdoor unit. If the piping length is less than 7.5m, then additional charge after vacuuming is not necessary. When the piping length is more than 7.5m, use the table below.
ModelIndoor
FDMN10CV1M
RN10FV1
FDMN15CV1M
RN15FV1
FDMN20CV1M
RN20CV1
FDMN25CV1M
RN25CV1
FDMN30CV1M
RN28CV1
FDMN40CV1M
RN35DV1 RN40DY1
FDMN50CV1M
RN50DY1
FDMN60CV1M
RN61DY1
18
23 26 23 32
18 20 20 33
16
545554 102
16 16
FDM30CV1M
FDB30CV1M
FDB25CV1M
FDM25CV1M
R25CV1
FDB20CV1M
FDM20CV1M
R20CV1
FDB15CV1M
FDM15CV1M
R15CV1
FDB10CV1M
FDM10CV1M
R10CV1
FDM40CV1M
FDB40CV1M
FDM50CV1M
FDB50CV1M
R50DY1
FDM60CV1M
FDB60CV1M
R61DY1R35DV1 R40DY1
R28CV1 R30CV1
39 41 55
Outdoor
Additional charge [g/m]
ModelIndoor
Outdoor
Additional charge [g/m]
ModelIndoor
Outdoor
Additional charge [g/m]
Model
Indoor
Outdoor
Additional charge [g/m]
Example:
FDB10CV1M / FDM10CV1M & R10CV1 with 13m piping length, additional piping length is 5.5m. Thus,Additional charge = 5.5[m] x 16[g/m] = 88[g]
Standard Static Pressure
Non-Standard Static Pressure
Standard Static Pressure
Non-Standard Static Pressure
68
TM-F
DB
M-0
515-
C
Special Precaution When Charging Unit With Scroll CompressorTheseprecautionsareintendedforusewithScrollcompressorsonlywithR22andR410ArefrigerantsbutarenotappliedtootherscompetitiveScrollcompressors.Scrollcompressorshaveaveryhighvolumetricefficiencyandquicklypumpadeepvacuumif thereisinsufficientrefrigerantinthesystemorifrefrigerantisaddedtooslowly.Operationwithlowsuctionpressurewillquickly lead toveryhighdischarge temperatures.While thisprocess ishappening, thescrollsarenotbeingwelllubricated–scrollsdependontheoilmistintherefrigerantforlubrication.Alackof lubricationleadstohighfrictionbetweenthescrollflanksandtipsandgeneratesadditionalheat.Thecombinationofheatofcompressionandheat from increased friction isconcentrated inasmalllocalizeddischargeareawheretemperaturescanquicklyrisetomorethan300°C.TheseextremetemperaturesdamagetheScrollspiralsandtheorbitingScrollbearing.Thisdamagecanoccurinlessthanoneminuteespeciallyonlargercompressors.Failuremayoccurinthefirstfewhoursorthedamagedoneduringfieldchargingmayshowupsometimelater.Othertypicalfieldchargingproblemsincludeundercharging,overcharging,moistureorairinthesystemetc.Intimeeachoneoftheseproblemscancause compressor failure.Minimalequipmentisrequiredforfieldcharging.Theminimumequipmentrequiredtodoasatisfactoryjobis:- 1.Setofservicegauges 4.Vacuumgauge 2. Hoses 5. Scales 3. Vacuum pump 6. Thermometer The proper refrigerant charge should follow the volume as recommended by manufacturer andrecommendationshouldbefollowedbytheinstaller.
1. Charging procedures – Single phase compressors Evacuatethesystemto-760mmHg.Toreduceevacuationtime,useshort,largediameterhosesan
connecttounrestrictedserviceportsonthesystem.Qualityofvacuumcannotbedeterminedbytime–areliablevacuumgaugemustbeused.(etc.electronicvacuumgauge)
Turntherefrigerantcylinderupsidedown,purgethecharginghoseandcharge liquid throughtheliquidlinechargingportuntilrefrigerantnolongerflowsoruntilthecorrectchargehasbeenweighedin.Ifadditionalchargeisrequiredstartthesystemandslowlybleedliquidintothesuctionsideuntilthe system is full.
It recommends charging liquid in a CONTROLLED manner into the suction side until the system is full. Thisrecommendationdoesnotholdtrueforreciprocatingcompressorswhereliquid
chargingintothesuctionsidecouldcauseseveredamage. Carefullymonitorthesuctionanddischargepressures–ensurethatthesuctionpressuredoesnot
fallbelow25psig(1.7bar)atanytimeduringthechargingprocess.
Dip-pipeInvert cylinderwithout dip-pipe
Liquid withdrawal
CAUTION!
• Manifold Gauge will show cylinder pressure rather than suction pressure if the cylinder valve and Manifold valve “A” are both open.
69
TM-F
DB
M-0
515-
C
Therearemanywaysof charging liquid ina “controlledmanner”intothesuctionside:-1. Use valveAonthemanifoldgaugeset2. Usethevalveontherefrigerantcylinder3. ChargethroughaShreddervalve4. UseahosewithaShreddervalvedepressor5. Chargeintothesuctionsideatsomedistance from the compressor6. Alloftheabove
2. Charging procedures – Three phase compressors The fundamentalprocedureisthesameasforsinglephasemodelsbutthecompressorcanrunin
thewrongdirectiononstarting.Ifthishappensreverseanytwophasesandstartagain.Shorttermreverserotationwillnotdamagethecompressor.
AllSpectercompressorshaveinternaldischargetemperatureprotectorswhichareveryeffectiveinpreventingdangerouslyhighdischargetemperaturesduringcharging.Theprotectionmodulewilltripandlockthecompressoroutfor30minutes.Itisnotnormallynecessarytowait30minutesforthemoduletoreset.Whenthecompressorhascooleddownthemodulecanberesetbybreakingthepowersupplytothecontrolcircuit.Veryoftentheservicemandoesnotunderstandwhythemoduletrippedandusesajumperwiretobypassit.Hecontinuestochargethesystemandremovesthejumperwhenchargingiscomplete.Thecompressormayormaynotrunwiththeprotectorbackinthecircuitbutitiscertainthatthecompressorhasbeendamagedandprematurefailureisinevitable.
A
70
TM-F
DB
M-0
515-
C
Special Precautions When Dealing With Refrigerant R410A Unit
(1) What is New Refrigerant R410A?R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing is essential.
(2) ComponentsMixture weight composition R32(50%) and R125(50%)
(3) Characteristic• R410A liquid and vapour components have different compositions when the fluid
evaporates of condenses. Hence, when leak occurs and only vapor leaks out, the composition of the refrigerang mixture left in the system will change and subsequently affect the system performance. DO NOT add new refrigerant to leaked system. It is recommended that the system should be evacuated thoroughly before recharging with R410A.
• When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid phase. Hence when charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to make certain that only original composition of R410A is being charged into the system.
• POE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22 compressor. Extra precaution must be taken not to expose the R410A system too long to moist air.
(4) Check List Before Installation / Servicing• Tubing
Refrigerant R410A is more easily affected by dust of moisture compared with R22, make sure to temporarily cover the ends of the tubing prior to installation.
• Compressor oilNo additional charge of compressor oil is permitted.
• RefrigerantNo other refrigerant other that R410A
• Tools (size of service port is different from R22 system)Tools specifically for R410A only (must not be used for R22 or other refrigerant)i) Gauge manifold and charging hoseii) Gas leak detectoriii) Refrigerant cylinder/charging cylinderiv) Vacuum pump c/w adapterv) Flare toolsvi) Refrigerant recovery machine
(5) Handling and Installation GuildelinesLike R22 system, the handling and installation of R410A system are closely similar. All precautionary measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and thorough leak check and vacuuming are equally important requirements.However, due to it hydroscopic POE oil, additional precautions must be taken to ensure optimum and trouble free system operation.
(a) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to moist air. Residual POE oil in the piping and components can absorb moisture from the air.
(b) Ensure that the compressor is not exposed to open air for more than the recommended time specified by its manufacturer (typically less than 10 minutes). Removed the seal plugs only when the compressor is about to be brazed.
(c) The system should be thoroughly vacuumed to 1.0 Pa (700mmHg) or lower. This vacuuming level is more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
71
TM-F
DB
M-0
515-
C
d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to ensure that only the original composition of R410A is being delivered into the system. The liquidcomposition can be different from the vapor composition.
e) Normally, the R410A cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the bottom.
Dip-pipe Invert cylinderwithout dip-pipe
Liquidwithdrawal
72
TM-F
DB
M-0
515-
C
7.WiringDiagrams
Indoor Unit
Outdoor UnitModel : R10CV1
Model : FDB10CV1M, FDM10CV1M
73
TM-F
DB
M-0
515-
C
Indoor Unit
Outdoor UnitModel : RN10FV1
Model : FDMN10CV1M
74
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDB15CV1M, FDM15CV1M
Outdoor UnitModel : R15CV1
75
TM-F
DB
M-0
515-
C
Indoor Unit
Outdoor UnitModel : RN15FV1
Model : FDMN15CV1M
76
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDB20/25CV1M, FDM20/25CV1M
Outdoor UnitModel : R18/20/25CV1
77
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDMN20/25CV1M
Outdoor UnitModel : RN20/25CV1
78
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDM30CV1M, FDB30CV1M
Outdoor UnitModel : R28CV1
79
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDMN30CV1M
Outdoor UnitModel : RN28CV1
80
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDM30CV1M, FDB30CV1M
Outdoor UnitModel : R30CV1
ENL
1 PHASE220~415VAC 50 Hz OR208~230VAC 60 Hz
81
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDM40CV1M, FDB40CV1M
Outdoor UnitModel : R35DV1
ENL
1 PHASE220~415 VAC 50 Hz OR208~230 VAC 60 Hz
82
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDMN40CV1M
Outdoor UnitModel : RN35DV1
83
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDM40/50CV1M, FDB40/50CV1M
Outdoor UnitModel : R40/50DY1
ENTSR
380~415 V3PH 50Hz
84
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDMN40/50CV1M
Outdoor UnitModel : RN40/50DY1
85
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDM60CV1M, FDB60CV1M
Outdoor UnitModel : R61DY1
ENTSR
380~415 V3PH 50Hz
86
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDMN60CV1M
Outdoor UnitModel : RN61DY1
87
TM-F
DB
M-0
515-
C
8.ServicingandMaintenance
Warning: Disconnect from main supply before servicing the air conditioner
Components Maintenance Procedures Recommended Schedule Air Filter
(Indoor Unit) 1. Remove any dust adhering to the filter by using a
vacuum cleaner or wash in lukewarm water (below 40˚C) with a neutral cleaning detergent.
2. Rinse the filter well and dry before placing it back onto the unit.
3. Note: Never use gasoline, volatile substances or chemicals to clean the filter.
At least once every 2 weeks. More frequently if necessary.
Indoor Unit 1. Clean any dirt or dust on the grille or panel by wiping it with a soft cloth soaked in lukewarm water (below 40˚C) and a neutral detergent solution.
2. Note: Never use gasoline, volatile substances or chemicals to clean the indoor unit.
At least once every 2 weeks. More frequently if necessary.
Condense Drain Pan & Pipe
1. Check the cleanliness and clean it if necessary. 2. Check the condensate water flow.
Every 3 months.
Indoor Fan Check if there is any abnormal noise. If necessary. Indoor / Outdoor
Coil 1. Check and remove the dirt between the fins. 2. Check and remove any obstacles which hinder air flow
through the indoor or outdoor.
Every month.
Power Supply 1. Check the running current and voltage for indoor and outdoor unit.
2. Check the electrical wiring and tighten the wire onto the terminal block if necessary.
Every 2 months.
Every year.
Compressor No maintenance needed if refrigerant circuit remains sealed. However, check for refrigerant leak at joint and fitting.
Every 6 months.
Compressor Oil Oil is factory charged. Not necessary to add oil if circuit remains sealed.
No maintenance required.
Fan Motor Oil All motors are pre-lubricated and sealed at factory. No maintenance required.
Pre Start Up Maintenance(After Extended Shut Down)
- Inspect thoroughly and clean indoor and outdoor units.- Clean or replace air filters.- Clean condensates drain line.- Clean clogged indoor and outdoor coils.- Check fan imbalance before operation.- Tighten all wiring connections and panels.- Check for refrigerant leakage.
The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention.
88
TM-F
DB
M-0
515-
C
9.Troubleshooting
When a malfunction of the air conditioner unit is detected, immediately switch off the main power supplybefore proceeding with the following troubleshooting procedures.The following are common fault conditions and simple troubleshooting tips. If any other fault conditions whichare not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.
snoitcaevitcerroc/sesuacelbissoPsnoitidnoctluaFoN
1 The air conditioner unit will not resume after power failure.
• The auto restart function is not functioning. Please turn on the unit with the wireless / wired controller.
2 The compressor does not operate 3 minutes after the air conditioner unit is started.
• Protection against frequent starting. • Wait for 3 or 4 minutes for the compressor to start
operating by it self.
3 The airflow is too slow or room cannot be cooled sufficiently.
• The air filter is dirty. • The doors and windows are opened. • The air suction and discharge of both indoor and
outdoor units are clogged or blocked. • The regulated temperature or temperature setting
is not low enough.
4 Discharge airflow has bad odor. • Cigarettes, smoke particles, perfume and others,which might have adhered onto the coil, maycause odor.
• Contact your nearest dealer.
5 Condensation on the front air grille of the indoor unit.
• This is caused by air humidity after an extended period of operation.
• The set temperature is too low. Increase the temperature setting and operate the unit at high fan speed.
6 Water flowing out from the air conditioner. • Switch off the unit and contact your nearest dealer. This might be due to tilted installation.
7 Hissing airflow sound from the air conditioner unit during operation.
• Liquid refrigerant flowing into the evaporator coil.
8 The wireless controller display is dim. • The batteries are discharged. • The batteries are not correctly inserted. • The assembly is not good.
9 Compressor operates continuously. • Dirty air filter. Clean the air filter. • Temperature setting too low (cooling). Use higher
temperature setting.
10 No cool air comes out during cooling cycle. • Temperature setting too high (cooling). Use lower temperature setting.
89
TM-F
DB
M-0
515-
C
Pressure
Data
Circuit
Too
low
A li
ttle
low
Nor
mal
A li
ttle
high
Too
high
Probable cause
High side Low side
●●
1. Overcharged with refrigerant. 2. Non-condensable gases in refrigerant circuit (e.g. air) 3. Obstructed air-intake / discharge. 4. Hot air short circuiting in outdoor unit.
High side Low side
●
●1. Poor compression / no compression (compressor
defective) 2. Reversing valve leaking.
High side Low side ●
● 1. Undercharged with refrigerant. 2. Refrigerant leakage. 3. Air filter clogged / dirty (indoor unit). 4. Indoor fan locked / seized.
High side Low side ●
● 1. Outdoor fan blocked (cooling). 2. Outdoor coil dirty (cooling). 3. Non-condensable gases in refrigerant circuit (e.g. air)
High side Low side
●●
1. Air intake temperature of indoor unit too high.
Diagnostic Guidelines
By means of pressure reading :
90
TM-F
DB
M-0
515-
CThe most common causes of air conditioner failure to “start” are :a) Voltage not within ±10% of rated voltage.b) Power supply interrupted.c) Improper control settings.d) Air conditioner is disconnected from main power source.e) Fuse blown or circuit breaker off.
By Means Of Diagnostic Flow Chart :Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling. “Starting failure” is caused by electrical defect while improper application or defects in refrigerant circuit causes “Insufficient cooling.
i) Diagnosis of Electric Circuit
91
TM-F
DB
M-0
515-
C
Satisfactory operation with temperature difference of air intake & discharge of indoor unit8°C to 13°C. *( * value is for reference only )
ii ) Diagnosis of Refrigerant Circuit / ApplicationThere might be some causes where the unit starts running but does not perform satisfactorily, i.e. insufficient cooling. Judgement could be made by measuring temperature difference of indoor unit’s intake and discharge air as well as running current
92
TM-F
DB
M-0
515-
C
10.DimensionalData
Model : FDB10CV1M, FDM10CV1M, FDMN10CV1M
Indoor UnitModel : FDB15/20/25CV1M, FDM15/20/25CV1M, FDMN15/20/25CV1M
All Dimensions are in mm
Indoor Unit
All Dimensions are in mm
881.0 225.0 842.0 802.0 261.0 411.0 351.0 905.0
1041.0 225.0 1002.0 962.0 261.0 411.0 351.0 1065.0
1176.0 225.0 1137.0 1097.0 261.0 411.0 351.0 1200.0
DimensionModelFDB15CV1M, FDM15CV1MFDMN15CV1M
A B C D F G HE
FDB20CV1M, FDM20CV1MFDMN20CV1MFDB25CV1M, FDM25CV1MFDMN25CV1M
93
TM-F
DB
M-0
515-
C
Indoor UnitFDMN30CV1M
94
TM-F
DB
M-0
515-
C
Indoor UnitModel : FDMN40CV1M
95
TM-F
DB
M-0
515-
C
Indoor Unit
FDM30/40/50/60CV1M, FDB30/40/50/60CV1M, FDMN50/60CV1M
All dimension are in mm
A B C D E F G H I Dimension
ModelFDM30CV1MFDB30CV1M
FDM40CV1MFDB40CV1M
FDM50CV1MFDB50CV1MFDMN50CV1M
FDM60CV1MFDB60CV1MFDMN60CV1M
929.0 999.0 956.0 917.0 408.5 105.0 85.5 187.5 70.5
1045.0 1115.0 1072.0 1033.0 466.5 105.0 85.5 187.5 128.5
1299.0 1369.0 1326.0 1287.0 593.5 105.0 90.5 182.5 255.5
1499.0 1569.0 1526.0 1487.0 693.5 100.0 90.5 187.5 355.5
96
TM-F
DB
M-0
515-
C
Outdoor UnitModel: R10/15CV1
R10/15CV1
A B C D E F G H I J K L M N O
700 521 250 485 175 36 95 93 86 68 441 130 111 15 18
Note : All Dimension in mm
K
B
LL
CN
N
M30
A
DO
319
6580
C
G H
I J
EF
Dimension
All dimensions are in mm
Outdoor UnitModel: RN10/15FV1
DimensionModel A B C D E F G H I J K L M N O P
RN10/15FV1 550 658 51 11 273 16 14 470 96 299 94 60 14 133 8 8
H
NJ
G
B CDE F
A
MK
L
P
O
I
97
TM-F
DB
M-0
515-
C
Model: R35DV1, R40/50/61DY1RN35DV1, RN40/50/61DY1
Note : All Dimension in mm
A B C D E F G H I J K L M N O P Q R S T
R18/20CV1RN20/25CV1
R25/28/30CV1RN28CV1
855 628 328 520 179 46 93 149 101 113 603 126 164 15 34 32 3 23 73 75
855 730 328 520 179 46 93 149 101 113 603 126 164 15 34 32 3 23 73 75
Note : All Dimension in mm
Model: R18/20/25/28/30CV1 RN20/25/28CV1
142 746 142
2222
448
60
40.090.0
MODEL
98
TM-F
DB
M-0
515-
C
11.ExplodedView&PartList
6
7
2
5
4
3
1
Model: FDB10CV1M, FDM10CV1M, FDMN10CV1M
NO. PARTS DESCRIPTION
TOP SIDE PANEL
FAN DECK
COIL
PRIMARY DRAIN PAN
SECONDARY DRAIN PAN
HANGER
CONTROL BOX
1
2
3
4
5
6
7
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
99
TM-F
DB
M-0
515-
C
1 TOP SIDE PANEL
2 FAN DECK
3 COIL
4 PRIMARY DRAIN PAN
5 SECONDARY DRAIN PAN
6 HANGER
7 CONTROL BOX
Model: FDB15/20/25CV1M, FDM15/20/25CV1M, FDMN15/20/25CV1M
6
4
2
FRONT VIEW
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
NO. PARTS DESCRIPTION
100
TM-F
DB
M-0
515-
C 1 ASSY. PANEL TOP
2 ASSY. TERMINAL BOX
3 ASSY. COIL TUBING
4 ASSY. DRAIN PAN SMALL
5 ASSY. DRAIN PAN BIG
6 ASSY. BLOWER
7 PANEL BLOWER
8 FLANGE BLOWER
9 FILTER RAIL
10 FILTER RAIL, COVER
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
Model: FDM30CV1M, FDB30CV1M, FDMN30CV1M
NO. PARTS DESCRIPTION
101
TM-F
DB
M-0
515-
C
1 ASSY.PANEL TOP
2 ASSY. TERMINAL BOX
3 ASSY. COIL TUBING
4 ASSY. DRAIN PAN SMALL
5 ASSY. DRAIN PAN BIG
6 ASSY. BLOWER
7 PANEL BLOWER
8 FLANGE BLOWER
9 ASSY. RAIL FILTER
10 ASSY. INS. COVER FILTER L/R
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
Model: FDM40CV1M, FDB40CV1M, FDMN40CV1M
NO. PARTS DESCRIPTION
102
TM-F
DB
M-0
515-
C
ASSY. PANEL TOP 1
2
3
4
5
6
7
8
9
10
PARTS DESCRIPTIONNO.
ASSY. TERMINAL BOX
ASSY. COIL TUBING
ASSY. DRAIN PAN SMALL
ASSY. DRAIN PAN BIG
ASSY. BLOWER
PANEL BLOWER
FLANGE BLOWER
ASSY., RAIL FILTER
ASSY., COVER FILTER L/R
Model: FDM50CV1M, FDB50CV1M, FDMN50CV1M
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
103
TM-F
DB
M-0
515-
C
ASSY. PANEL TOP
PARTS DESCRIPTIONNO.
1
2
3
4
5
6
7
8
9
10
ASSY. TERMINAL BOX
ASSY. COIL TUBING
ASSY. DRAIN PAN SMALL
ASSY. DRAIN PAN BIG
ASSY. BLOWER
PANEL BLOWER
FLANGE BLOWER
ASSY., RAIL FILTER
ASSY., COVER FILTER L/R
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
Model: FDM60CV1M, FDB60CV1M, FDMN60CV1M
104
TM-F
DB
M-0
515-
C1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., OUTDOOR COIL3 VALVE BRACKET
RIGHT PANEL
4 COMPRESSORASSY., FRONT PANEL
5 ASSY., PARTITION15
13
ASSY., CONTROL PANEL
6 SUCTION PIPE 7 DISCHARGE PIPE 8 ASSY., CAP TUBE 9 BRACKET, FAN MOTOR10
16
14
ASSY., VALVE COVER
Model : R10/15CV1
FAN MOTOR
17 ASSY., FRONT GRILLE 18 PLASTIC HANDLE 19 INSULATION PARTS NOT IN THE DIAGRAMS CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR11 FAN BLADE
12 LEFT PANEL
105
TM-F
DB
M-0
515-
C
Model : RN10/15FV1
NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY. OUTDOOR COIL
12 SUCTION PIPE2 TOP PANEL
13 ASSY. CAP TUBE3 FAN MOTOR BRACKET
14 VALVE BRACKET4 ASSY PARTITION
15 ASSY. VALVE COVER16 ASSY. CONTROL PANEL17 RIGHT PANEL
5 FAN MOTOR6 FAN BLADE7 ASSY. FRONT GRILLE8 ASSY FRONT PANEL9 ASSY BASE PAN
10 COMPRESSOR11 DISCHARGE PIPE
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
17
16
15
1413121110987
6
5
4
3
2 1
106
TM-F
DB
M-0
515-
C1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., OUTDOOR COIL3 MOTOR BRACKET
13 TERMINAL COVER PANEL
4 FAN MOTOR
14 DISCHARGE PIPE
5 FAN BLADE
15 SUCTION PIPE
6 VALVE BRACKET 7 PARTITION 8 COMPRESSOR 9 BACK PANEL, RIGHT10
16 ASSY., CAP TUBE
Model : R18/20CV1, RN20/25CV1
17 ASSY., VALVE COVER 18 ASSY., FRONT GRILLE 19 PLASTIC HANDLE 20 SERVICE PANELPARTS NOT IN THE DIAGRAMS CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR
FRONT PANEL, LEFT11 TOP PANEL12 ASSY., CONTROL PANEL
107
TM-F
DB
M-0
515-
C
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., OUTDOOR COIL3 MOTOR BRACKET
13 ASSY., CONTROL PANEL
4 FAN MOTOR
14 TERMINAL COVER PANEL
5 FAN BLADE15 ASSY., VALVE COVER
6 VALVE BRACKET 7 PARTITION 8 COMPRESSOR 9 BACK PANEL, RIGHT10
16 ASSY., FRONT GRILLE
Model : R25/28/30CV1, RN28CV1
17 PLASTIC HANDLE, SIDE 18 DISCHARGE PIPE 19 SUCTION PIPE 20 ASSY., CAP TUBE PARTS NOT IN THE DIAGRAMS CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR
SERVICE PANEL11 FRONT PANEL LEFT
12 TOP PANEL
108
TM-F
DB
M-0
515-
C
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., COIL3 PALTE, FLARE VALVE4 FLARE VALVE 3/8”5 FLARE VALVE 5/8”
16 MOTOR BRACKET17 FAN MOTOR18 ASSY., FRONT PANEL19 ASSY., CONTROL PANEL20 SERVICE PANEL21 FAN BLADE22 TOP PANEL23 PLASTIC HANDLE
6 PARTITION 7 COMPRESSOR 8 ACCUMULATOR 9 ASSY., CAPILLARY TUBE10 SUCTION PIPE11 TUBE ACCUMULATOR TO SUCTION12 DISCHARGE PIPE13 INSULATION14 BACK PANEL, RIGHT
15 SIDE PANEL, LEFT
PARTS NOT IN THE DIAGRAMS
Model : R35DV1, R40/50/61DY1, RN35DV1, RN40/50/61DY1
PHASE SEQUENCER HIGH PRESSURE SWITCH LOW PRESSURE SWITCH CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR TXV
Branches: • Penang Tel: 04-331 1670 • Johor Tel: 07-557 7788 • Pahang Tel: 09-567 6778 • Perak Tel: 05-548 2307 • Melaka Tel: 06-288 1133 • Sabah Tel: 088-722 194 • Sarawak Tel: 082-333 299 • Negeri Sembilan Tel: 06-768 8969 • Kedah Tel: 04-733 0235 • Kelantan Tel: 09-747 4678
GROUP ASSOCIATED (C&L) SDN BHD (109719-M)
Head Office: Tel: 03-7953 8388 Fax: 03-7956 4371Email: [email protected], [email protected]