cc848894724_product manual i2 pms

Upload: narendra-kumar-soni

Post on 06-Apr-2018

235 views

Category:

Documents


10 download

TRANSCRIPT

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    1/93

    IPMS Product Manual annexureJune- 2010

    IPMS Product Manual annexure for

    SMPS

    Notice: The information, specifications, and

    procedures in this manual are subject to change

    without notice.

    Lineage Power assumes no responsibility for any

    errors that may appear in this document.

    All international rights reserved

    Printed in India

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    2/93

    IPMS Product Manual annexureJune- 2010

    Table of Contents

    1. INTRODUCTION ...................................................................................................................................................5

    OVERVIEW.........................................................................................................ERROR!BOOKMARK NOT DEFINED.GENERAL ASSEMBLY DRAWINGS ......................................................................ERROR!BOOKMARK NOT DEFINED.CUSTOMER SUPPORT .........................................................................................ERROR!BOOKMARK NOT DEFINED.

    Customer Training ...............................................................................................Error! Bookmark not defined.Customer Service .................................................................................................Error! Bookmark not defined.Technical Support ................................................................................................Error! Bookmark not defined.Product Repair and Return ..................................................................................Error! Bookmark not defined.Warranty Service..................................................................................................Error! Bookmark not defined.Downloads and Software ..................................................................................... Error! Bookmark not defined.

    SAFETY MANUAL ..............................................................................................ERROR!BOOKMARK NOT DEFINED.Safety Statements..................................................................................................Error! Bookmark not defined.Warning Statements and Safety Symbols .............................................................Error! Bookmark not defined.Precautions ..........................................................................................................Error! Bookmark not defined.Handling Batteries ............................................................................................... Error! Bookmark not defined.

    2. SYSTEM DESCRIPTION.....................................................................ERROR! BOOKMARK NOT DEFINED.

    SYSTEM BLOCK DIAGRAM.................................................................................ERROR!BOOKMARK NOT DEFINED.SYSTEM COMPONENTS ......................................................................................ERROR!BOOKMARK NOT DEFINED.

    SYSTEM CONFIGURATIONS........................................................................................................................................6SYSTEM ARCHITECTURE............................................................................................................................................9

    Single Line Diagram of EP48XXX Plant .............................................................................................................9SYSTEM SPECIFICATION...........................................................................................................................................11

    Key Features ......................................................................................................................................................15Key Specifications..............................................................................................................................................17

    3. ICOMBO CONTROLLER...................................................................................................................................18

    OVERVIEW...............................................................................................................................................................18GENERIC INTERFACE REQUIREMENTS .....................................................................................................................19KEY FEATURES........................................................................................................................................................19SPECIFICATIONS.......................................................................................................................................................19

    Analog Inputs .....................................................................................................................................................20 Digital Inputs .....................................................................................................................................................22

    COMMUNICATIONS ..................................................................................................................................................23GP Interface.......................................................................................................................................................23Programming Interface......................................................................................................................................24

    SYSTEM CONTROL INTERFACE ................................................................................................................................24Alarm Outputs ....................................................................................................................................................24 Front Panel Alarm LEDs..................................................................................................................................25Factory Default Assignments for Alarms & LEDs............................................................................................26

    USER INTERFACE GUIDE ..........................................................................................................................................26Front Panel Keypad ...........................................................................................................................................26System Status Indicators ....................................................................................................................................27Local and Remote Access Ports.........................................................................................................................28

    User Interface Menu Structure...........................................................................................................................28Personal Identification (PIN).............................................................................................................................29User Interface Menu Flow Map .......................................................................................................................31...........................................................................................................................................................................35CONFIGURATION-Continued in next page...................................................................................................35...........................................................................................................................................................................36CONFIGURATION-Continued in next page...................................................................................................36...........................................................................................................................................................................37

    STATUS....................................................................................................................................................................38

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    3/93

    IPMS Product Manual annexureJune- 2010

    Rectifiers............................................................................................................................................................38Batteries.............................................................................................................................................................38Shunt Currents ..................................................................................................................................................39

    Disconnect States ..............................................................................................................................................39Alarm Thresholds ..............................................................................................................................................39Enabled/Disabled Info ......................................................................................................................................39This section of the menu provides a location to determine the Enable/Disable status of most of the Icombo

    controller features..............................................................................................................................................39System Info ........................................................................................................................................................40

    CONTROL/OPERATIONS...........................................................................................................................................41History ...............................................................................................................................................................42

    CONFIGURATION.....................................................................................................................................................42Float Settings .....................................................................................................................................................42Shunt Monitors..................................................................................................................................................43

    Rectifiers............................................................................................................................................................44Batteries.............................................................................................................................................................44Contactors..........................................................................................................................................................46

    Disconnects........................................................................................................................................................46Boost ..................................................................................................................................................................47ACO ...................................................................................................................................................................48System Settings ..................................................................................................................................................49

    Communication Ports .......................................................................................................................................49OVERVIEW..............................................................................................................................................................54

    4. EP2500AC48 Shelf........................................................................................................................................55OVERVIEW...............................................................................................................................................................55

    A.Standalone Shelf for accommodating six rectifiers........................................................................................55SPECIFICATIONS.......................................................................................................................................................56CONFIGURATION REQUIREMENTS............................................................................................................................57

    B. Shelf-less Concept for accommodating 2, or 3 rectifiers...............................................................................58

    5. EP2500AC48 RECTIFIERS.................................................................................................................................60

    OVERVIEW...............................................................................................................................................................60SALIENT FEATURES .................................................................................................................................................61INPUT BEHAVIOUR...................................................................................................................................................62

    OUTPUT BEHAVIOUR ...............................................................................................................................................63USER INTERFACE (LEDINDICATIONS) ....................................................................................................................64

    6. EP3000AC48 RECTIFIERS.................................................................................................................................66

    OVERVIEW...............................................................................................................................................................66SALIENT FEATURES .................................................................................................................................................67INPUT BEHAVIOUR...................................................................................................................................................68OUTPUT BEHAVIOUR ...............................................................................................................................................69USER INTERFACE (LEDINDICATIONS) ....................................................................................................................70

    APPENDIX B THE T1.317 COMMAND LANGUAGE.....................................................................................72

    INITIALIZING THE IC091_ICOMBO CONTROLLER.....................................................................................................72RS-232TERMINAL ..................................................................................................................................................72

    T1.317C

    OMMANDL

    ANGUAGE................................................................................................................................73Objects and Attributes........................................................................................................................................73

    APPENDIX C EXPLANATION OF BATTERY MANAGEMENT FUNCTIONS .........................................84

    FLOAT MODE...........................................................................................................................................................84SLOPE THERMAL COMPENSATION ...........................................................................................................................84

    High Temperature Alarm...................................................................................................................................84 High Temperature Compensation ......................................................................................................................84 Low Temperature Compensation .......................................................................................................................85

    PLANT BATTERY TEST.............................................................................................................................................87

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    4/93

    IPMS Product Manual annexureJune- 2010

    BOOST MODE ..........................................................................................................................................................89Auto-Boost Charge.............................................................................................................................................89 Redundancy Loss Function ................................................................................................................................90 Battery Voltage Imbalance Detection ......... ........... .......... ........... .......... ........... ........... .......... ........... .......... ........90 Battery Recharge Current Limit.........................................................................................................................91 Battery Parameter Defaults .................................................................................Error! Bookmark not defined.

    APPENDIX D - FACTORY DEFAULTS FOR ALARMS & LEDS ...................................................................92

    ISSUE HISTORY......................................................................................................................................................93

    ISSUE 0.1 .................................................................................................................................................................93

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    5/93

    IPMS Product Manual annexureJune- 2010

    1. Introduction

    Overview

    Lineage Power developed the Galaxy Power System EP4803 / EP4806 / EP4812 to support -48volt telecommunications powering solutions for the Indian market. The EP48XXX combines

    fan-cooled, switchmode rectifiers, microprocessor control technologies, battery and load

    disconnect/reconnect options in a modular front-access design. This modularity ensures easyaccess, simplified installation and maintenance, and allows the system to expand in capacity and

    features as power needs grow.

    The power system accepts alternating current from the commercial utility or a standby ac power

    source and rectifies it to produce dc power for connected equipment. The systems control and

    alarm functions interact with the rectifiers and the office. In addition, the system provides

    overcurrent protection and charge, discharge, and distribution facilities. Battery reserveautomatically provides a source of dc power if the commercial or standby ac fails.

    With 1200-ampere maximum capacity, distribution flexibility, Energy Monitoring features forthe AC input as well as DC Loads, the EP48XXX supports switching, transmission, and wirelessapplications in central office locations and environmentally controlled remote sites.

    Figure 1-1: Open Door Front View

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    6/93

    IPMS Product Manual annexureJune- 2010

    System Configurations

    The EP 48XXX is available in two configurations:

    The half height cabinet, shown in Figure 1-1 (EP4803 & EP4806) mounts on top of a

    battery stand and can provide up to 600 amperes of dc power.

    The full height cabinet, shown in Figures 1-2 (EP4812) is a standalone unit suitablefor floor anchoring, and can provide up to 1,200 amperes of dc power.

    Figure 2-2 shows the electrical schematic for the Half Height Cabinets.

    Figure 2-3 shows the electrical schematic for the Full Height Cabinets.

    Each system contains ac distribution, dc distribution panels, a battery connection panel,

    rectifiers, termination points for load circuits, and a system controller.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    7/93

    IPMS Product Manual annexureJune- 2010

    Figure 2-2: Electrical schematic for the Half Height Cabinets.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    8/93

    IPMS Product Manual annexureJune- 2010

    Figure 2-3: Electrical schematic for the Full Height Cabinets.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    9/93

    IPMS Product Manual annexureJune- 2010

    System Architecture

    The architecture of the EP48XXX platform is based on the IC091_CB ICOMBO Controller,

    which works as a front end master controller in addition to providing the user interface for

    the plant.

    The ICOMBO Controller provides complete control functionality, Distribution Monitoring &

    Control. ICOMBO is a combination of features of Pulsar plus controllers family and add-on

    modules (IEPSO). This approach of design gives a more centralized control and operation of

    power system.

    The ICOMBO works along with power system components and provides all the necessary

    supervisory, measurement, monitoring and control functions as required by the India

    Market. The feature set of the ICOMBO has been optimally designed considering the India

    Market Requirements, with new and special features such as AC Energy Monitoring, DCEnergy Monitoring and Energy Efficiency.

    This section describes the basic architecture of the EP48XXX Power Systems designed

    around the use of the IC091_CB ICOMBO Controller.

    The key features and specifications of the IC091_CB ICOMBO Controller are described in

    the next chapter.

    Single Line Diagram of EP48XXX Plant

    Figure 2-4 shows the Single Line Diagram of a typical EP48XXX plant, highlighting the

    interconnections between the IC091_CB_ICOMBO Controller and the various other power

    system components.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    10/93

    IPMS Product Manual annexureJune- 2010

    Figure 2-4: Single Line Diagram of EP48XXX Plant

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    11/93

    IPMS Product Manual annexureJune- 2010

    System Components

    The unit is internally wired for AC distribution from the MCBs / TB to each of the

    individual rectifier modules, through backplane interconnects of each shelf.

    Rectifiers convert an ac source voltage into the dc voltage level required to charge and floatthe batteries and to power the using equipment. The rectifiers are installed in the EP48XXX

    shelf, with each shelf accepting a maximum of six rectifiers. Up to four shelves may be

    present. Blocks are labeled and wired to a correspondingly marked rectifier as shown.

    (Front View)

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    12/93

    IPMS Product Manual annexureJune- 2010

    The AC distribution for the ultimate capacity of 24 Rectifiers installed in the plant is as

    shown below (viewed from front of the shelf), with background color indicating the

    respective phase from which the rectifier draws its input power. For Systems with less

    number of rectifiers, the uninstalled rectifiers occupy slots within the rightmost side of the

    shelf.

    R- Phase: L1

    Y- Phase: L2

    B- Phase: L3

    G41 G42 G43 G44 G45 G46

    G31 G32 G33 G34 G35 G36

    G21 G22 G23 G24 G25 G26

    G11 G12 G13 G14 G15 G16

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    13/93

    IPMS Product Manual annexureJune- 2010

    ControllerControllerControllerController provides the local and remote control, monitoring, and diagnostic functions

    required to control and monitor the power system.

    BatteriesBatteriesBatteriesBatteries provide energy storage for an uninterrupted power feed to the using equipment

    during loss of ac input or rectifier failure.

    DC Distribution PanelDC Distribution PanelDC Distribution PanelDC Distribution Panel provides over current protection, connection points for the using

    equipment, and bus bars used to interconnect the rectifiers, batteries, and dc distribution.

    Distribution panels have DIN Circuit Breakers, or DIN Fuse modulesDistribution panels have DIN Circuit Breakers, or DIN Fuse modulesDistribution panels have DIN Circuit Breakers, or DIN Fuse modulesDistribution panels have DIN Circuit Breakers, or DIN Fuse modules

    DIN Style Breakers

    Ensure breakers are in the off position. Connect load cables to the load distribution

    return bus bar and the -48V outputs from the MCBs

    Verify wiring polarity at the input of the load equipment.

    Leave breaker switch in the OFF position until the load equipment is ready to be

    energized.

    DIN Style Fuses for Battery Connection

    Remove the fuses from the fuse base. Connect the negative cables of the battery to

    the fuse base and the positive cable from the battery to the +Ve return bus bar.

    Verify wiring polarity of the battery terminals.

    Do not install load fuse and alarm fuse until the load equipment is ready to be

    energized.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    14/93

    IPMS Product Manual annexureJune- 2010

    Battery ConnectionBattery ConnectionBattery ConnectionBattery Connection PanelPanelPanelPanel provides connection points for the battery strings through battery

    disconnect fuses or contactors and current monitoring shunts.

    Secure Battery Cable

    connections with

    appropriate hardware. If

    required by local code orpractice, treat with an

    oxidation inhibitor such as

    NO-OX.

    Secure COG connection

    with provided hardware:

    If required by local code or

    practice, treat with an

    oxidation inhibitor such as

    NO-OX.

    COG lead to be connected at the right most position of the DC return bus bar.

    Connect -Ve terminal Return

    Battery String #3 here

    Connect +Ve term

    Return Common o

    Battery Strings an

    Loads here

    Connect -Ve terminal Return

    Battery String #1 here

    Connect -Ve terminal Return

    Battery String #2 here

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    15/93

    IPMS Product Manual annexureJune- 2010

    System Specification

    Key Features

    Special Features Redundant Power Supply for controller from AC Input, Plant Bus and Battery Strings.

    Energy Efficiency Algorithms

    User Interface

    Front accessible 64x128 LCD with control pad and intuitive menu navigation system

    Available front panel PIN (password) access feature

    Standard or customer specific factory defaults supported.

    Support of more than one factory default.

    Display of both plant voltages and plant currents on front panel.

    Alarm severity sensitive display backlight.

    Three separate configurable and assignable LED indicators, to differentiate between

    AC, DC and Battery events, along with Tri-color capability to indicate the severity

    of any alarm/event.

    Alarms & Events Management Alarm management of 48V DC distribution depending on the Load MCB card that

    are used of upto maximum of 64 MCBs

    Audible alarm and test feature

    10 configurable alarm outputs with manual alarm test features 10 User definable alarm inputs.

    Emergency Power Off (EPO).

    Industry standard classification of all events, depending upon severity, into one of

    five categories namely Critical (PCR), Major (PMJ), Minor (PMN), Record Only

    (RO)

    Event History Log.

    Distribution and temperature Management

    Battery Fuse Fail Detection for upto 3 Fuses.

    DC distribution monitoring can monitor up to 8MCBs (in one card) * 8 nos. and

    more.

    Temperature monitoring upto 3 Thermal probes.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    16/93

    IPMS Product Manual annexureJune- 2010

    Battery Management

    Upto a maximum of three Battery Strings. Battery Reverse Polarity Detection for all three strings. Plant Battery Test

    Slope Compensation, for both low & high temp., with independent adjustable slopes. Battery recharge current limit feature Step function for Manual and automatic Boost. Remote test, and periodic discharge test capability Manual time threshold for pass/fail criteria Reserve time calculations with configurable threshold Monitoring of upto 3 Battery Temperatures using Probes Configurable mid string imbalance alarm.

    Disconnects

    Drive Capability for both Latching and Non-Latching Contactor types. Up to two groups of Disconnect Contactors can be controlled, one for load and second

    for battery. By default, upto four parallel contactors comprise the group for

    load contactors and up to two contactors form the group for battery contactors. Load disconnects operated by low voltage. Battery disconnect operated by voltage threshold, All contactors can be closed or open using the Local port interface.

    Plant Analog Measurements AC Energy Monitoring DC Energy Monitoring

    Upto 3 Battery Shunts and 4 Load Shunts Battery Mid string Voltage Measurements. Plant Bus Voltage

    Communications Supervision, measurement, monitoring and control functions through Easy View 2 PC

    interface software. Communication through command language based on the T1.317 standard.

    Maintenance & Serviceability

    Easily field replaceable controller card. Modular design & different packaging alternatives for the ICOMBO Controller.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    17/93

    IPMS Product Manual annexureJune- 2010

    Key Specifications

    Item Specification

    AC Input Voltage Range176~290Vrms per phase Full Power Voltage

    90~176Vrms per phase De-rated Power Voltage

    10 minutes withstand capability @ 500VAC per phase(for Battery Floated Application)

    No Damage Input Volts1Hr withstand capability @320VAC per phase

    (for non-battery floated applications)

    Plant Voltage Range -48 volts: from -36.5 volts to -60 volts

    Quiescent Power Consumption 20 Watts Maximum

    Input Power Connections Single Phase or Three Phase

    Front Panel LCD user interface 8-line by 40-character LCD;

    Three status LEDs;

    System Configuration Methods Front panel LCD display and menu keys;

    From ICOMBO Controller :-RS232 port: T1.317 or Easy View

    Temperature Monitoring Up to 3 thermal probes.

    Alarm Contact Ratings 60 VDC, 0.5A

    Plant Voltage Measurement

    Accuracy

    0 to 50C (0.05% of full scale + 1 count)

    -40 to 85C (0.1% of full scale + 1 count)

    Resolution

    48V Systems: 40 mV; 24V Systems 25 mV

    48V Systems: 70 mV; 24V Systems 40 mV

    0.01V

    Plant Current Measurement

    Accuracy

    0 to +50C-40 to +85C

    Resolution

    0.5% of full scale1.25% of full scale

    1A

    Temperature Measurement Accuracy

    One-Wire Serial probes-5 to +55C

    -40 to +85C

    Resolution

    1C

    3C

    0.1C

    Environmental

    Operating Temperature Range-5 to 50C

    With 2.5% per Deg. C power derating above 50 Deg. C.

    Humidity 10% to 95% non-condensingAudible Noise < 60 dBA

    Table 2-1: Key System Specifications

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    18/93

    IPMS Product Manual annexureJune- 2010

    3. ICOMBO Controller

    Overview

    This section describes the architecture and operation of the ICOMBO Controller. It alsoprovides detailed information about the features of the front panel keys, LEDs and Displays.

    Fig 3-1: The ICOMBO Controller showing control elements

    Fig shows the Front Panel user Interface and the display, identifying the control elements.

    For the EP48XXX plant, the available options at the front panel craft port presently includeonly the RS232 interface.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    19/93

    IPMS Product Manual annexureJune- 2010

    Generic Interface Requirements

    Fig 3.2 shows the typical interconnects and functionality of the various connectors available

    on the ICOMBO Board. For details on the specifications, functionality and interfacerequirements for each of the individual connectors, refer to the Advanced Features User

    Guide for the ICOMBO Controller.

    Fig 3-2: Generic Interface Requirements for the ICOMBO Board

    Key Features

    For the key features and comprehensive capabilities of the ICOMBO Controller, please refer

    to the Advanced Features User Guide for the ICOMBO Controller Family, comcode

    CC109152360.

    Specifications

    For detailed product specifications of the ICOMBO Controller, please refer to the Advanced

    Features User Guide for the ICOMBO Controller, comcode CC109152360.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    20/93

    IPMS Product Manual annexureJune- 2010

    Analog Inputs

    Power Supply Inputs

    The ICOMBO can be wired up to derive its power from one of several sources. These sources

    are either one of a maximum of three battery strings, or the plant bus voltage. A bridgerectifier internal to the board is used to derive the power supply from these multiple sources.

    Wire up the board as below:-

    Battery Shunts

    The controller by default assumes the positive terminal of any battery shunt, as the terminal

    that is more positive under battery discharge conditions. The shunts used in power plants

    need to be wired considering this assumption. Upto 3 Battery Shunts can be monitored.

    Connection as mentioned below:-

    Connector Pin To

    HDR-12 1 BATT 1-ve

    HDR-12 2 BAT T2 -ve

    HDR-12 3 BATT 3 -ve

    HDR-12 4 LOAD -ve

    HDR-12 5 BATT +ve

    HDR-12 6 NC

    Connector Pin To

    HDR-13 1 Battery shunt-1+ve

    HDR-13 2 Battery shunt-2+ve

    HDR-13 3 Battery shunt-3+ve

    HDR-13 4 BATT +ve BB

    HDR-13 5 LOAD -ve BB

    HDR-13 6 GND

    HDR-13 7 BUFF-3107 (common RTM 1,2&3)

    HDR-13 8 RTM-2

    HDR-13 9 Battery shunt-1-ve

    HDR-13 10 Battery shunt-2-veHDR-13 11 Battery shunt-3-ve

    HDR-13 12 BATT -ve BB

    HDR-13 13 LOAD +ve BB

    HDR-13 14 GND

    HDR-13 15 RTM-1

    HDR-13 16 RTM-3

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    21/93

    IPMS Product Manual annexureJune- 2010

    Load Shunts

    Up to 4 Load Shunts can be monitored. Connection as mentioned below:-

    Connector Pin To

    HDR-3 1 LOAD SHUNT-1+ve

    HDR-3 2 LOAD SHUNT-2+ve

    HDR-3 3 LOAD SHUNT-3+ve

    HDR-3 4 LOAD SHUNT-4+ve

    HDR-3 5 GND

    HDR-3 6 LOAD SHUNT-1-ve

    HDR-3 7 LOAD SHUNT-2-ve

    HDR-3 8 LOAD SHUNT-3-ve

    HDR-3 9 LOAD SHUNT-4-ve

    HDR-3 10 GND

    Battery Mid-stringUp to three Battery Mid-string Voltages can be monitored. Connection as mentioned below:-

    Connector Pin To

    HDR-11 1 VBT 1+ve

    HDR-11 2 VBT 2+ve

    HDR-11 3 VBT 3+ve

    HDR-11 4 Bus bar-ve

    HDR-11 5 VBT 1-ve

    HDR-11 6 VBT 2-ve

    HDR-11 7 VBT 3-ve

    HDR-11 8 Bus bar-ve

    Potential free outputs10 potential free contacts are available. Out of which first 3 are for severity and 7 are factory

    programmed alarms. Connection as mentioned below:-

    Connector Pin To

    HDR-10 1 PCR common

    HDR-10 2 PCR

    HDR-10 3 PMJ-C

    HDR-10 4 PMJHDR-10 5 PMN-C

    HDR-10 6 PMN

    HDR-10 7 UR1-C

    HDR-10 8 UR1

    HDR-10 9 UR2-C

    HDR-10 10 UR2

    HDR-10 11 PCR

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    22/93

    IPMS Product Manual annexureJune- 2010

    HDR-10 12 UR3

    HDR-10 13 UR4-C

    HDR-10 14 UR4

    HDR-10 15 UR5-C

    HDR-10 16 UR5

    HDR-10 17 UR6-CHDR-10 18 UR6

    HDR-10 19 UR7-C

    HDR-10 20 UR7

    Digital Inputs

    General Binary Inputs

    There are three general binary inputs available at HDR7 connector. Activation of these inputs

    takes place by pulling the lines to -48V.

    Connector Pin ToHDR-7 1 AC SPD

    HDR-7 2 DC SPD

    HDR-7 3 AMJ

    HDR-7 4 OS

    HDR-7 5 FAN FAIL

    HDR-7 6 TR

    HDR-7 7 AIR CONDITION

    HDR-7 8 DOOR OPEN

    HDR-7 9 HIGH TEMP

    HDR-7 10 HIGH PRESSURE

    Contactor Monitoring and Distribution Monitoring

    The ICOMBO can control / monitor upto two groups of contactors namely Battery and Load.Battery group can have upto maximum of two battery contactors in parallel, and Load group can

    have upto maximum of four load contactors in parallel. Controller monitors the presence/absence

    as well as whether or not the contactors are closed or open. This is done by wiring up both theNC and NO contacts of the contactors to the board.

    Load distribution is monitored by load MCB fail card. It can cater upto 8 Distribution MCBs in

    one card. No of loads that can be monitored by the controller can be increased by connecting thecards in daisy chain distribution.

    Connector Pin To

    HDR-5 1 GN-B1N1

    HDR-5 2 GN-B1N3

    HDR-5 3 LVD-NO-2

    HDR-5 4 LVD-NC-2

    HDR-5 5 NC

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    23/93

    IPMS Product Manual annexureJune- 2010

    HDR-5 6 MCB FAIL-IN

    HDR-5 7 GN-B1N-2

    HDR-5 8 LVD-NO-1

    HDR-5 9 LVD-NC-1

    HDR-5 10 GND

    HDR-5 11 3.3V outHDR-5 12 GND-out

    Battery Polarity Detection

    I-Combo controller prevents closure of LVBD when Battery is connected to the plant in reverse

    polarity. The EP48XXX plant has been typically wired up as given below, to provide this

    feature.

    Battery 1 VE => J1 Pin 21

    Return Bus bar +Ve => J1 Pin 22

    Battery 2 VE => J1 Pin 23

    Return Bus bar +Ve => J1 Pin 24Battery 3 VE => J1 Pin 25

    Return Bus bar +Ve => J1 Pin 26

    Contactor Drive

    The ICOMBO can drive either latching or non-latching contactors. If Latching contactors are

    used, the jumper designated HDR2 should be placed across pins 1&2, else it should be placed

    across pins 2&3. Interface requirements as below:-

    Connector Pin To

    HDR-9 1 coil +ve (LVBD)

    HDR-9 2 coil -ve (LVLD)

    HDR-9 3 V bus +ve

    HDR-9 4 coil -ve (LVBD)

    HDR-9 5 coil -ve (LVLD)

    HDR-9 6 V bus -ve

    CommunicationsGP InterfaceConnector P2 (RJ11 connector) is for the GP interface to the ICOMBO controller.

    Connector Pin To

    P2 1 R485 +

    P2 2 RS485 -

    P2 3 GND

    P2 4 NC

    P2 5 NC

    P2 6 NC

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    24/93

    IPMS Product Manual annexureJune- 2010

    Programming Interface

    SPI programming interface for the card available at six pin connector HDR1.

    System Control InterfaceAlarm Outputs

    There are a total of ten potential free relay outputs, which are wired up within the EP48XXX

    plant, from the output terminal block to the HDR10 connector of the ICOMBO Controller.

    All ten relays can be independently programmed to operate in normally open or normally

    closed condition, by appropriately configuring jumpers 1-10 located on the ICOMBO board.

    The configuration needs to be done as illustrated below:

    Figure 3-3: Alarm Relay Configuration Jumpers for the ICOMBO

    Figure 3-4: Configuring default active state for alarm Outputs

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    25/93

    IPMS Product Manual annexureJune- 2010

    Each jumper corresponds to one alarm relay and each relay output can be configured

    independently. The potential free contacts from the relay outputs are available at the

    HDR10 connector of the ICOMBO controller. Out of the ten alarm relays, seven provide the

    actual alarm condition, and three provide the severity associated with the alarm. The

    severity relays transmit Power Critical (PCR), Power Major (PMJ), or Power Minor (PMN).

    Each alarm is factory assigned a severity based on industry practices; however, they may be

    reassigned to PCR, MAJ, MIN, or RO (Record Only). An alarm condition with the RO

    severity results in the system controller transmitting the alarm without the severity but is

    stored in the history log. PCR, PMJ nor PMN are transmitted with the alarm.

    The seven selectable alarm relays are called User Alarm Relay 1 (R1) through User Alarm

    Relay 7 (R7). Each relay can operate under one or more events/conditions or even when a

    logical combination of certain events occur. Further, the active states for all the Relays are

    user definable (either normally open or closed). Table 3-1 indicates the interconnection

    between the I-combo Board and the user terminal blocks for the output relays. The factorydefault functionality for the relays is also indicated.

    From To ICOMBO

    TB- No Name Connection

    DefaultFunctionality

    DefaultAlarm State

    Alarm StateProgrammable?

    1 HDR 10:1

    2PCR

    HDR10:11Power Critical Alarm Close Yes

    3 HDR10:2

    4PMJ

    HDR10:12Power Major Alarm Close Yes

    5 HDR10:3

    6PMN

    HDR10:13Power Minor Alarm Close Yes

    7 HDR10:4

    8OP ALM1

    HDR10:14Battery on Discharge Close Yes

    9 HDR10:5

    10OP ALM2

    HDR10:15

    Multiple AC Fail /AC Fail

    Close Yes

    11 HDR10:6

    12OP ALM3

    HDR10:16

    Multiple Rectifier Fail /Rectifier Fail

    Close Yes

    13 HDR10:7

    14OP ALM4

    HDR10:17Very Low Voltage Close Yes

    15 HDR10:8

    16OP ALM5

    HDR10:18

    LVLD Fail / LVLD Open /Load MCB Trip

    Close Yes

    17 HDR10:9

    18OP ALM6

    HDR10:19High Voltage Close Yes

    19 HDR10:10

    20OP ALM7

    HDR10:20

    LVBD Fail / LVBD Open /Battery Fuse Fail

    Close Yes

    Table 3-1: User Terminal Block Default Assignments - Alarm Outputs

    Front Panel Alarm LEDs

    The ICOMBO Controller Front Panel has three tri-color LEDs namely AC, DC and BD, each

    of which can be independently assigned to glow under specific single events.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    26/93

    IPMS Product Manual annexureJune- 2010

    Factory Default Assignments for Alarms & LEDsUtilize the Easy View interface to reassign any of the alarm outputs to specific alarm events

    or to change the severity of the alarms. Refer To Appendix-E for a comprehensive list of the

    factory default assignments for the output alarm relays and the front panel LEDs against

    specific event(s)

    User Interface Guide

    Front Panel Keypad

    Refer to Fig 3-5, showing the User Interface of the controller.

    The ICOMBO controllers have six tactile buttons to use to navigate through a structured

    menu system. The buttons serve multiple purposes depending on the screen a user is at.

    These functions are summarized below.

    Figure 3-5: User Interface of controller

    Buttons Description

    Parameter Change When changing a system parameter, the buttons increase or

    decrease the value of the parameter.

    Direction Buttons In the Menus, the direction buttons navigate to make aselection. A black box highlighting a menu item indicates that the item

    has sub-menus.

    Enter Button Enters a sub-menu or confirms a parameter change. From the Home

    Page only, goes to the top level Main menu.

    ESC Button Goes up one menu level or exits a parameter change without saving.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    27/93

    IPMS Product Manual annexureJune- 2010

    System Status Indicators

    The ICOMBO controller provides three separate LED indicators to help assist in providing

    more specific indications of the system status. These LEDs are used to provide specific

    indication concerning the AC and DC system status as well as a separate indicator for aBattery on Discharge state. These LEDs have factory assigned defaults as indicated in the

    table below. However assignments can be customized in the field using the remote

    interfaces.

    LED Status Condition

    AC input to all rectifiers is in range.

    ACAC input to one rectifier is missing or out of range.

    AC input to two or more rectifiers is missing or out of range.

    DC output to all loads is normal.

    DCOne or more of the following alarms are present: Fuse Minor 48.

    One or more of the following alarms are present: Open String, LVBD

    Open, Fuse Major 48

    System under battery test (blinks)

    BD State not presently assigned.

    System equal to or below configured Battery on Discharge (BD) threshold.

    The ICOMBO has an audible alarm located in its display assembly. This alarm willsound when any Critical, Major, or Minor alarm is detected by the controller. The

    alarm can be cut-off temporary from control/operations menu.

    Once the audible cut-off is selected the alarms at present in the system can be

    observed in alarms shortcut in the main screen. An indicator on the default front

    panel screen is provided to inform that the audible alarm cutoff is active. The audiblealarm can also be turned-back on following similar procedures.

    The audible alarm may be disabled altogether through proper configuration at the

    front panel.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    28/93

    IPMS Product Manual annexureJune- 2010

    Local and Remote Access Ports

    The ICOMBO provides communication ports for local remote access. Access to these ports

    depends on the specific controller configuration. The ICOMBO used in the EP48XXX plant

    has a front panel local DB9 RS232 asynchronous serial port.

    Port Description

    Front Panel A laptop PC can be connected to standard DB9 connector to provide a ground-

    referenced RS-232 serial connection using Easy View for local access.

    User Interface Menu StructureFeature content is functionally divided at the Main Menu into following categories:

    Status, Control/Operations, History & Configuration

    Access to the main menu starts at the default front panel screen shown below.

    Front Panel Default Menu The front panel default screen displays the

    primary (Rectifier) system bus voltages

    along with total load.

    The larger font represents the rectifier

    output. Output voltages of rectifier outputs

    have two decimal points.

    The operating mode of the system is also

    displayed. Possible operating modes are:

    Float, Battery On Discharge, Boost, etc.

    Pressing the button accesses the main

    menu and the feature categories previously

    listed.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    29/93

    IPMS Product Manual annexureJune- 2010

    Main Menu

    Access to alarms, warnings, equipment

    status detail, basic control and operations

    for maintenance purposes, and system

    configuration can be obtained.

    Note: the ICOMBO has the ability to have a

    front Panel Password that limits

    configuration as well as some operations. A

    person with administrator level access can

    enable this feature through the remote

    interfaces. Standard ICOMBO controllers

    are shipped from the factory with this

    feature enabled.

    Personal Identification (PIN)

    The ICOMBO controller has the ability to restrict access from the front panel of the unit. It

    has the ability to enforce a four digit Personal Identification Number (PIN) requirement for

    users of the front panel for control/operations and configurable items. These

    control/operations and configurations are generally considered the items that should only be

    done during initial install or by specific personnel. This feature is shipped enabled from the

    factory in the standard ICOMBO controller. The factory default for the PIN is 1234. Each

    position of the password is configurable between 0~9. A sample screen like that following is

    required for PIN access.

    The up, down, left and right arrows are used to enter the appropriate password. Uponentering a correct PIN the following momentary screen shows up and then disappears

    leaving the user at the menu location prior to entering the PIN.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    30/93

    IPMS Product Manual annexureJune- 2010

    Once a user enters the PIN, total front panel access is allowed for as long as the user remains

    in menus other than the default menu and/or any one of the following :-

    a) The front panel access will remain open once the PIN has been entered till the time out

    value. The Icombo controller has a factory configured default of 120 minutes.

    b) An internal counter shall be kept and reset if the user leaves the default menu and returns

    to others menus before the timeout period is reached.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    31/93

    IPMS Product Manual annexureJune- 2010

    User Interface Menu Flow Map

    Detailed menu flow map for each primary category of the main menu is documented and listed in

    the following pages. This information is followed up with brief descriptions of each of the menuitems. Alarms are not hierarchal mapped and are presented in chronological order of occurrence

    when they are present. No Active Alarms will be displayed when there are no alarms detectedby the controller.

    Status Menu

    STATUS-Continued in next page

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    32/93

    IPMS Product Manual annexureJune- 2010

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    33/93

    IPMS Product Manual annexureJune- 2010

    Control/Operations

    History Menus

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    34/93

    IPMS Product Manual annexureJune- 2010

    Configuration Menu

    CONFIGURATION-Continued in next page

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    35/93

    IPMS Product Manual annexureJune- 2010

    CONFIGURATION-Continued in next page

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    36/93

    IPMS Product Manual annexureJune- 2010

    CONFIGURATION-Continued in next page

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    37/93

    IPMS Product Manual annexureJune- 2010

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    38/93

    IPMS Product Manual annexureJune- 2010

    StatusThe Status section of the menu system provides an overview of system components, threshold

    settings, and feature configuration. Configuration is not possible from the status portion of the

    menu system. Status items are also available through the remote port connections such as theweb interface or local craft port using Easy View.

    RectifiersInstalled Capacity Provides the total installed rectifier capacity in the system.

    On-line Capacity The total rectifier capacity of rectifiers On-line in the system and able toproduce power. Rectifiers that are running or in Standby are considered to be

    On-line. Rectifiers that are in RFA, ACF, etc. are not counted in the On-line

    capacity.

    Total Output

    Current

    The total output current drain of all rectifiers.

    Gmn () Each individual rectifiers DC output current, AC input current, and AC inputvoltage by rectifier number Gmn () is available. m represents the shelf

    number and n represents the rectifier position number in that shelf. Thestate of the rectifier is also identified in the () when current is not shown.These states could be

    OFF: Rectifier has been shutdown due to hardware failure (ex RFA,Temp, HV).

    STANDBY: User has inhibited the rectifier's output voltage. User mayuse remote interfaces or the ope command to place a rectifier into a

    standby condition or during execution of energy efficiency.

    MISSING: An acknowledged rectifier has been removed.

    VACANT: Rectifier has not been installed in that position.

    BatteriesInstalled Capacity Total installed battery capacity based upon the number of strings in the

    system and the Amp-Hour (AH) rating of the strings installed.

    Current (Chrg/Dchg) Measured value of the current charging or Discharging of the batteries

    Battery Strings The total number of battery strings installed in the system.

    Highest Temp Highest battery temperature being measured by the RCB thermal probes

    attached in the system.

    Temp Probes Total number of installed thermal probes. Up to three probes can bemonitored by the controller.

    Mid-Cell Volts Total number of installed Mid-String voltage measurement modules.

    Battery Test Result Shows whether the most recent battery test was completed, and the last

    calculated reserve time.

    Next Test The date of the next automatic battery discharge test. The automaticdischarge test feature must be enabled for this to work.

    Live reserve time Shows live calculated reserve time during battery discharge test.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    39/93

    IPMS Product Manual annexureJune- 2010

    Shunt CurrentsID1-8 Displays the individual shunt monitor currents. Distribution Up to eight

    values can be displayed. Factory default is

    ID1-3 Battery currents

    ID 4-7 load currents.

    Disconnect StatesLVBD Provides LVBD (Low Voltage Battery Disconnect) status.

    None-Displayed for each non-configured contactor.

    Closed-displayed when contactors are closed and battery isconnected.

    Open-If contactors are opened and disconnected the battery.

    LVLD(1-3) Provides status of the three LVLDs (Low Voltage Load Disconnects )

    None-Displayed for each non-configured contactor.

    Closed-displayed when contactors are closed and battery is

    connected.

    Open-If contactors are opened or disconnected each respectiveload.

    Alarm ThresholdsFloat Voltage

    Alarms

    Shows the configured settings for the Float Settings:

    Very High Major

    High Minor

    Battery discharge Major (BD)

    Very Low Voltage (VLV) alarms.

    Values are shown in (xx.xxV) format.

    Boost VoltageAlarms

    Shows the configured settings for the Boost Settings:

    Very High Major

    High Minor

    Values are shown in (xx.xxV) format.

    High Batt Temp Shows measured value of the highest battery temperature of all attached

    battery thermal probes.

    Reserve Low Shows configured value for the Low battery reserve time alarm.

    Real Time Reserve Shows configured value for the Low battery real reserve time alarm

    Enabled/Disabled InfoThis section of the menu provides a location to determine the Enable/Disable status of most of theIcombo controller features.

    Temp Comp Shows whether Battery Temperature Compensation is Enabled or Disabled.

    Low Temp Comp Shows if the Low Temperature compensation features is Enabled or Disabled.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    40/93

    IPMS Product Manual annexureJune- 2010

    Recharge I lim Shows if the Recharge Current Limit feature is Enabled or Disabled.

    Emrgncy Pwr Off Displays whether or not the Emergency Power Off (Remote EmergencyBattery Disconnect) feature is Enabled or Disabled. If Enabled, EPO is

    asserted when contact closure is applied to the EPO input. The controller will

    keep battery contactors open until this contact closure has been removed. The

    feature assumes that AC has been removed to the system.Auto Boost Shows if the automatic boost charge mode of operation is Enabled or

    Disabled.

    Auto Batt Test Shows if the automatic battery test feature is Enabled or Disabled.

    Rect Redundancy Shows if the Rectifier redundancy feature is Enabled or Disabled.

    Mid-Cell V Mon Shows if the Mid-String Voltage imbalance detection feature is Enabled or

    Disabled.

    Imminent Shutdn Shows if the Imminent system shutdown alarm (LVBD) feature is Enabled or

    Disabled.

    Local buzzer Shows if local buzzer is Enabled or Disabled.

    Eff management En Shows if the energy efficiency management feature is Enabled or Disabled.

    Disconnects Shows if the LVBD (Low Voltage Battery Disconnect) and LVLD1-3 (Low

    Voltage Load Disconnects) features are Enabled or Disabled.

    Local Write Whether or not the system can be configured through the local port.

    System InfoController Info Provides software versions running on the ICOMBO. These versions include

    the versions for the application code, the boot block, the display, the defaults

    file, and the web pages.

    Date Present Date of the ICOMBO on-board real-time clock using the configuredDate format.

    Time Present time of the ICOMBO on-board real-time clock using the configured

    time format.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    41/93

    IPMS Product Manual annexureJune- 2010

    Control/OperationsThe following are the system control and operation functions that can be performed from the

    front panel. These operations are generally used in post installation and maintenance modes.

    Alarm Cut-Off Temporarily cuts-off (Turns off) the on-bard audible alarm.

    Start Lamp Test Temporarily illuminates all status indicators of ICOMBO controller.Restart Devices Provides the ability to restart All system serial controlled rectifiers. Provides

    the ability to individually reset only rectifiers at a time. This operation doesnot affect rectifiers and other system devices that are already functioning.

    Clear Events Used to clear momentary events or alarms. It clears the following system

    alarms: Check Battery, Reserve Time Low, Battery Voltage Imbalance

    Uninstall

    Equipment

    Clears alarms related to the removal of a system component such as a

    rectifier, thermal probe etc. Running this command allows the system

    controller to retake inventory of using equipment.

    Clear History This area of the menus system can be used to clear the various items that the

    controller maintains history records. Once cleared the controller begins to

    keep history of new events.Alarm History: Clears only alarm event history.

    BD History: Clear only BD network access history.

    Boost History: Clears only Boost event history.

    Clear Statistics This area of the menus system can be used to clear the various items that the

    controller maintains statistical records. Once cleared the controller begins to

    keep new statistical data.

    Clear Basic Clears individually or as a group the Basic statistical data kept

    on Plant Load, the highest battery temperature, and ambient.

    Clear Trend Clears the trend data kept on the plant load.

    Clear BD Clears the Battery on Discharge (BD) statistics kept on the

    plant load and voltage during discharge.

    Alarm Relay Test Provides ability to initiate an alarm relay test on all output relays. Alarmrelays are asserted at the configured alarm interval.

    Alarm buzzer Test Provides ability to initiate a audio buzzer test.

    Reset reserve time Resets reserve time

    Start Battery Test Initiates the manual battery test feature. A stop battery test operation is

    displayed to interrupt the testing and return the unit to normal operation. The

    manual battery test utilizes the configured test duration and a system bus

    voltage threshold to represent the end of reserve.

    Start Boost Initiates the manual battery Boost feature. A stop battery Boost operation is

    displayed to interrupt the Boost operation mode and return the unit to normal

    operation.

    Disconnects Provides individual manual control (to open or close) of up to four Low

    Voltage Disconnects (LVBD, LVLD1-3) for maintenance purpose.

    Load Config

    Defaults

    This operation allows a user to bring back all factory defaults with a single

    operation. Factory defaults are also custom configuration defaults that are

    available. Custom configurations may support multiple factory defaults.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    42/93

    IPMS Product Manual annexureJune- 2010

    Caution should be used when applying this command. Previous configuration

    changes will be overwritten.

    Reset Admin

    Password

    Resets user, super-user and administrator passwords back to standard defaults.

    HistoryThis area of the menu system contains event history information. The controller works on a

    first record in first record out once the record size of a specific field is reached. The following

    system history logs are available:

    Alarm History Chronological view of the last 500 alarms and events that have occurred since

    the last time the history log was cleared.

    BD History Chronological view of the last16 battery on discharge (BD) events since the

    last time the history log was cleared.

    Boost History Chronological view of the last 16 times the system entered boost mode since

    the last time the history log was cleared.

    ConfigurationThe Configuration section of the menu system is where system operational parameters, system

    device information, and alarm thresholds are set-up and modified. Factory defaults are provided

    for the standard ICOMBO controller. Some defaults are dependent on the battery type. ConsultAppendix E for default settings of different battery. Valve-Regulated Lead Acid (VRLA)

    batteries and default settings defined for the Standard configuration are assumed in this section.

    Customer specific configurations may be different. When there is doubt, contact Lineage Powertechnical support.

    All items are field configurable. Modified settings are stored in non-volatile memory. TheICOMBO controllers require time to update sectors in flash memory for changes. Allowapproximately a minute for the controller to accept and store modifications in non-volatile

    memory before removing power to the unit.

    Float SettingsSet Point Parameter sets the value that primary (rectifier) DC bus will be set and

    regulated.

    Range: 42.00V to -56.50V

    factory default is -54.00V

    ISHVSD This is an Independent High Voltage Shutdown threshold during the Float

    mode of operation that is sent to and stored in the rectifiers that is used byeach rectifier for independent high voltage monitoring.

    Range: 42.00V to -56.50V

    factory default is -54.00V

    Voltage alarms Very High MajorThis alarm indicates an abnormally high output voltage on the secondary DC

    bus during Float mode. This is second and critical level of high voltage alarm.The alarm does not attempt to shut the offending unit down.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    43/93

    IPMS Product Manual annexureJune- 2010

    Range: -50.00V to -60.00V

    Factory default: -57.00

    High MinorThis alarm indicates an abnormally high output voltage on the secondary DC

    bus during Float mode. This is first level of high voltage alarm. The alarm

    does not attempt to shut the offending unit down.The threshold can be set from

    Range: -50.00V to -60.00V

    Factory default: -56.00

    BD (Battery on Discharge) MajorPrimary DC bus threshold setting that determines when the system is

    determined to be operating on battery reserve.

    Range: -46.00V to - 55.00V.

    Factory default: -51.00V.

    Very Low Voltage MajorPrimary DC bus alarm threshold used to indicate a very low output voltage

    (VLV).

    Range: -40.00V to- 51.00V.

    Factory default: -46.00V.

    Shunt Monitors

    The ICOMBO controller can manage 3 battery shunts and 4 battery shunts. Shunt sizes for each

    assigned battery or load type must also be configured. All shunts are assumed to have a voltage

    rating of 50mV. The current rating of each shunt is programmable between 0 to 9999A. Systemsshipped with the I-combo controllers are appropriately pre-configured in the factory for the right

    shunt values and assignments.

    ID1-7 The operation Type of each shunt monitoring must be assigned based uponactual system implementation.

    The operational Type may be: None (For no shunt), Battery (Monitoring

    battery currents), and Load (for load currents).

    ID1-7 Rating The current rating of each shunt being monitored by ICOMBO controller

    must be configured based upon actual system implementation. All shunts are

    assumed to be 50mV. The current rating may be from 0-9999 Amps.

    The factory default is 300A for battery and 200A for the load shunts.

    Defaults

    The ICOMBO controller is factory configured with:

    ID1 Type: Battery Shunt: 300A

    ID2 Type: Battery Shunt: 300AID3 Type: Battery Shunt: 300A

    ID4 Type: Load Shunt: 200A

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    44/93

    IPMS Product Manual annexureJune- 2010

    ID5 Type: Load Shunt: 200A

    ID6 Type: Load Shunt: 200AID7 Type: Load Shunt: 200A

    Front panel displays summation of load current for default ID type settings.

    Rectifiers

    Redundancy An alarm is automatically generated when the load on system is more than

    N-X for a On-line rectifier capacity of N+X based system. X is the desired

    number of rectifiers to check for redundancy.

    The factory default for this feature is Enabled and X=1.

    Efficiency

    management

    Provides the ability to disable or enable energy efficiency feature

    Eff Target The rectifier which takes current below this %age value will be eligible to

    enter into Energy efficiency standby mode. The current of that rectifier is then

    shared by other rectifiers. This process continues until a steady state isreached.

    Range: 20-95 %

    Eff Turn ON The rectifier which takes current above this %age value will turn ON. This

    process continues until a steady state is reached.

    Range: 25-100 %

    Eff Initial delay Time delay setting for the first rectifier to enter into energy efficiency mode.

    Range: 1-30 min

    Eff Delay Time delay setting for the next rectifier to enter into energy efficiency mode.

    Range: 1-30 min

    Batteries

    Battery Type

    The type of batteries used in the system can be selected from the following

    battery types loaded in the Standard controller: Generic VRLA (Valve Regulated Lead Acid)

    Generic FLOODED (flooded lead acid)

    Generic NiCd (Nickel Cadmium)

    Once selected the user has the opportunity to automatically accept the

    standard defaults for all battery Type related features. Parameters such as

    float voltage, float alarms, thermal compensation parameters, etc. are

    automatically adjusted if defaults are accepted.

    The system factory default is Valve-Reg.

    Installed Capacity Capacity of an individual battery string in the system which is used to

    derive the total installed system battery capacity. This value has to be

    entered for Generic battery types but is automatically configured for

    specific battery models. The value configured should be the rating to

    1.75V at an 8-hr discharge rate.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    45/93

    IPMS Product Manual annexureJune- 2010

    The available range is 0-30000 AH. The system factory default is 0 AH

    corresponding to the Generic Valve-Reg.

    Battery Strings The total number of battery string installed in the system entered by the

    user for inventory purposes and initial reserve time calculations.

    Range is 0-16

    End of Dchrg The user defined system bus voltage at which the batteries are considered

    to be at the end of their reserve capability for manual battery testing (End

    of Discharge). This end-of-discharge voltage is used for automatic andopportunistic reserve time calculations.

    Range: -36.00V to -48.00V

    Factory default of -44.44V for 48V

    Battery Temp

    Management*

    This section includes all the parameters required for thermal management

    of the batteries. Parameters include the ability to enable/disable thermal

    compensation for high and low temperatures and set the slope decrease

    and increase rates, respectively. There is also a High Temperature alarm

    threshold feature.

    Factory default Enabled

    Batt Test* This section includes all the parameters required for battery testing through

    manual or automatic means. Configuration for manual test duration and

    the system test end-voltage for manual battery test are here along with the

    interval, start date, start time, time from last battery on discharge BD, and

    enable/disable for periodic battery test. The rectifier voltage during battery

    discharge testing and system reserve time low alarm threshold are also

    available.

    Automatic battery testing is factory disabled.

    Recharge Amp Limit Enable or disable battery recharge limiting and set recharge current limit.

    When enabled, the controller will regulate the current into the batteries to

    be below the setting.

    Recharge current limit is factory Disabled. The current limit range is 5 to

    1000A and has a factory default of 50A for Valve-Reg batteries.

    Voltage Imbal User defined voltage threshold for a mid-string voltage imbalance alarm.

    Range 1.4 - 3.0 Volts. The factory default is 1.7V for Valve-Reg batteries.

    This alarm is only generated after batteries have been sitting on float for a

    minimum of 12 hours and the total battery current is less than 3A.

    *See Appendix C for detailed descriptions of the Thermal Compensation and Battery Test

    features and parameters.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    46/93

    IPMS Product Manual annexureJune- 2010

    Contactors

    The ICOMBO controller monitors and controls contactors. Contactor controlled by appropriately

    configuring a unique board ID and associating it to a specific contactor function at the controller.

    ID1-6 Associates the ID numbers set on the controller to one of four independentset of contactor controls.

    These contactor controls are:

    LVBD (Low Voltage Battery Disconnect),

    LVLD1 (Low Voltage Load Disconnect 1),

    LVLD2 (Low Voltage Load Disconnect 2), and

    LVLD3 (Low Voltage Load Disconnect 3).

    The ICOMBO has assigned each unique board ID number as follows:

    ID1 to LVBDID2 to LVLD1ID3 to LVLD2

    ID4 to LVLD3

    DisconnectsThis section of the configuration menu contains the parameters associated with the individual

    function assignments made in the previous section. Each LVD type (LVBD and LVLD1-3) canindividually be enabled or disabled. Only the LVBD and LVLD1 are enabled from the factory.

    The LVDs disconnect and reconnect method of operation used by the controller can be

    configured for each assignment. The method of disconnect or reconnect can be based on the

    traditional means of reaching a system bus voltage threshold (Voltage) or based on both reachingthe system bus voltage threshold and an elapsed time from once the system has been placed on

    discharge (BD) and at least two or more rectifiers are reporting AC failures (Voltage/Time). The

    same Voltage and Voltage/Time mode of operation can also be selected for reconnecting LVDs.In this case the elapsed time configured is the time from once the reconnect voltage threshold has

    been reached. Note: selecting None for a reconnect mode will require manual intervention to

    shut the contactor. Selecting None for the disconnect mode will not allow a LVD to open. TheICOMBO has factory defaults of the following:

    LVBD (Enabled) Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, None

    Disconnect Voltage (-42.0V); Range:-39.0 to -50.0V

    Time Delay (0 min); Range: 0-300minReconnect Mode (Voltage); Range: Voltage, Voltage/Time, None

    Reconnect Voltage (-48.0V); Range:-39.0 to -55.0V

    Time Delay (0 sec); Range: 0-300sec

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    47/93

    IPMS Product Manual annexureJune- 2010

    LVLD1 (Enabled) Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, None

    Disconnect Voltage (-42.0V); Range:-39.0 to -50.0V

    Time Delay (0 min); Range: 0-300minReconnect Mode (Voltage); Range: Voltage, Voltage/Time, None

    Reconnect Voltage (-44.0V); Range: 39.0 to -55.0V

    Time Delay (0 sec); Range: 0-300sec

    LVLD2 (Disabled) Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, NoneDisconnect Voltage (-42.0V); Range:-39.0 to -50.0V/+19.5 to +25.0V

    Time Delay (0 min); Range: 0-300min

    Reconnect Mode (Voltage/Time); Range: Voltage, Voltage/Time, None

    Reconnect Voltage (-44.0V); Range: 39.0 to -55.0V

    Time Delay (30 sec); Range: 0-300sec

    LVLD3 (Disabled) Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, None

    Disconnect Voltage (-42.0V); Range:-39.0 to -50.0VTime Delay (0 min); Range: 0-300min

    Reconnect Mode (Voltage); Range: Voltage, Voltage/Time, None

    Reconnect Voltage (-44.0V); Range: 39.0 to -55.0V

    Time Delay (0 sec); Range: 0-300sec

    Shutdown AlarmWhen enabled, the Imminent Shutdown Alarm is generated prior to

    opening the LVBD. Once the LVBD threshold has been reached, the alarm

    is generated. The alarm is issued 15 seconds prior to opening the contactor

    to provide an indication that system shutdown is imminent due to asystem battery disconnect. The alarm is based on the configured LVBD

    battery disconnect threshold.

    The factory default for this feature is Disabled.

    Remote Emergency

    Power Off (EPO)

    If enabled, the remote Emergency Power Off (EPO) feature allows the

    controller to detect the occurrence of a contact closure between J3.5 and

    J.10 and force open all battery contactors in the system. The battery

    contactor will open five seconds after the contact has been asserted. Oncethe contact is removed, the battery contactor will be re-asserted to itsprevious operational state.

    The factory default for this feature is Enabled.

    BoostThe Boost function allows battery charging to be expedited by raising the system voltage to

    boost level for a set time. The following boost mode parameters are set in this area of the menusystem:

    Set Point Primary DC bus voltage set-point during the Boost mode of operation.Boost (set point) is adjustable from -48.00V to -58.00V in 0.1Vincrements.

    Factory default setting is -55.20V.

    ISHVSD This is an Independent High Voltage Shutdown threshold during the

    Boost mode of operation that is sent to and stored in the rectifiers that is

    used by each rectifier for independent high voltage monitoring.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    48/93

    IPMS Product Manual annexureJune- 2010

    Range: -52.00V to -60.00V

    Factory default: -58.5.00

    Voltage Alarms Has the ability to set similar DC bus level alarms during Boost as foundwith the Float mode of operation. This includes Very High Major, High

    Minor, and BD.

    Very High MajorThis alarm indicates an abnormally high output voltage on the secondaryDC bus during Boost. This is second and critical level of high voltage

    alarm. The alarm does not attempt to shut the offending unit down.

    Range: -50.00V to -60.00V

    Factory default: -57.00

    High MinorThis alarm indicates an abnormally high output voltage on the secondary

    DC bus during Boost. This is first level of high voltage alarm. The alarm

    does not attempt to shut the offending unit down.The threshold can be set from

    Range: -50.00V to -60.00V

    Factory default: -56.00

    Max Duration Defines the maximum time duration the system can remain in the Boost

    mode of operation.

    Range: 1 to 80 hours.

    Factory default: 5 hours.

    Automatic Enables or Disables the automatic boost feature. Boost will end once the

    monitored battery current reaches less than 5A or Max duration is

    elapsed. Factory default: Enabled

    ACO

    Local buzzer Enables or Disables the Local buzzer.

    Factory default: Enabled

    Duration To set the alarm cutoff duration.

    Range:30-480 min

    Factory default: 60min

    Alarm Test

    Relay duration To set the relay test duration.

    Range:5-300 sec

    Factory default: 05 sec

    Buzzer Duration To set Local buzzer test duration setting

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    49/93

    IPMS Product Manual annexureJune- 2010

    Range:5-300 sec

    Factory default: 05 sec

    System Settings

    Date Allows setting system Date.

    Factory default format: Date - yyyy-mm-dd

    Time Allows setting system Time.

    Factory default format: Time - hh:mm:ss (24HR format).

    Daylight Savings Enable or disable daylight savings.

    Factory default: Enabled.

    Display T Units Allows setting of temperature in C or F.

    Factory default is C.

    Communication Ports

    Menus for configuring the following communication parameters:

    Port Type Sets the RS232 asynchronous serial communication port for either Local

    terminal or Modem application.

    Factory default: Local.

    Local Port

    Settings

    Provides the ability to Enable or Disable Write access to the controller, the

    ability to change system settings through the SNMP management or local port.

    Write Access, baud rate and flow control parameters for the port is

    configurable.

    Factory default:Write Access-Enabled

    Baud rate-Autoflow control-None

    Easy View PC User Interface

    The ICOMBO can be integrated to communicate to PC through RS232 communication port. It

    requires for the user to install EASY VIEW software in the system. EASY VIEW 2 is the latestupdated version of ICOMBO software that is factory shipped. The pages support the majority of

    the functionality that is performed through the controller front panel. Following are few sample

    screens. Note: web pages are continuously updated for functionality and aesthetics. Thus, someof the screens shown may be slightly different than those served up by your ICOMBO.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    50/93

    IPMS Product Manual annexureJune- 2010

    Using a standard browser, a login page similar to that depicted below should be served up by

    the ICOMBO controller. There are three levels of access through the port; Read-Only,

    Read/Write, and Read/Write with password management privileges. Passwords defaults forthe Craft port as well as other remote access means default as follows:

    Access Default Password

    User (Read-Only) lineageSuper-User (Read/Write) super-user

    Administrator (Read/Write/Password Administration) administrator

    Security Levels/Passwords

    The ICOMBO controller supports three levels of access: (User, Super-User, and Administrator).

    Password defaults can be changed only by a user of administrator privileges.

    User security level:

    Can view almost every parameter in the system Can change only a few parameters considered to be of standard maintenance practices

    Default password: lineage

    Super-User security level: Can do everything the user can do Can change any configuration parameter in the system (except passwords)

    Default password:super-user

    Administrator security level:

    Can do everything the super-user can do

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    51/93

    IPMS Product Manual annexureJune- 2010

    Can change passwords

    Can upgrade controller software Default password:administrator

    After the controller has granted access, the controller serves up a Home page similar to that

    shown below. Front panel access and capabilities are a super-set of the functions and features

    available through the Craft port. Configuration of individual parameters and features can beperformed by using the items located in the Settings tab or a general quick configuration of the

    system can be performed through the Installation tab. The Home Page has tabs that are

    partitioned as the following:

    Home

    After login in, main menu screen will show graphic of the power components which are: the number

    of shelves, rectifiers in place with their appropriate outputs, empty slots, and indicate which rectifiers

    are in alarm condition. High-level summary for the Batteries, Distribution, Alarms present, and

    controller summary are also shown. There are also quick link tabs that take you to specific features.

    These tabs are the Home, Reports, Maintenance, Settings, and Installation.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    52/93

    IPMS Product Manual annexureJune- 2010

    Reports

    The reports tab displays reports or history records of the system that is recorded in the

    controller. These reports include Inventory, Battery Discharge and Statistics. Individual history

    groups like Alarm History, Boost History and Trends also available.

    Maintenance

    Allows remote access to Control/Operation commands that are available through the front

    panel. These include restarting rectifiers, starting alarm or battery tests, asserting boost,

    clearing history and statistics, clearing latched events and missing equipment, placingrectifiers/converters in and out of Standby, cutting of the audible alarm. The T1.317 Terminal

    button provides a quick link to a Telnet session to the controller that allows the T1.317

    command interface to be utilized.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    53/93

    IPMS Product Manual annexureJune- 2010

    Note: The Load Defaults button under system loads the factory default settings assigned to a

    specific battery type as defined in the defaults configuration file. In the Standard controller this

    function will Standard configuration file. Custom configured controllers will utilize the specific

    custom configuration file defined for that particular configuration.

    Settings

    Items in this menu are used to configure all the individual system parameters, features, and

    thresholds. These fields are arranged by System, Reserve, Power, Communication and

    Programming.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    54/93

    IPMS Product Manual annexureJune- 2010

    Installation

    This tab provides access to quickly configure the primary items typically needed for a site.

    These configurations are the minimum for basic system operation. These items include

    selecting the battery type, date, time, and the site ID mentioned during the front panelconfiguration start-up section.

    OverviewBroadly, The ICOMBO is capable of the below:-

    GP Bus interface to system controller Control/monitoring of two contactors (latching/non-latching). System configuration can

    include either all contactors of latching type or all contactors of non-latching type. Hardwired Selectable contactor type (latching/non-latching). If Latching contactors are

    used, the jumper designated HDR2 should be placed across pins 1&2, else it should be

    placed across pins 2&3. 1 Bus Voltage Measurement

    3 Mid-String Voltage Measurement 4 Load Shunt Currents Measurement 3 Battery charge/discharge shunt Currents Measurement Configurable Shunt Size for each shunt. 3 Battery Reverse Polarity Connection sensing 3 configurable alarm inputs (3 General Binary Inputs) Monitors up to 64 load breakers/fuses

    Monitors 3 battery fuses Automatic input presence detection

    Configurable Alarm Input configurationo Polarityo Type

    3 Phase AC Parameter Measurement (RMS voltage, RMS current and frequency)(Achieved using a dedicated True RMS AC measurement chip, accuracy < 1%)

    Configurable CTR (current transformer ratio) for each AC current phase. 1 Tri-Color Status LED

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    55/93

    IPMS Product Manual annexureJune- 2010

    4. EP2500AC48 Shelf

    Overview

    A.Standalone Shelf for accommodating six rectifiers

    The shelf conforms to 23 standard and accommodates upto 6 rectifiers. The EP48XXX Plant

    can accommodate upto a maximum of 4 shelves.

    Figure 4-1: EP48XXX Plant Shelf & Rectifier Arrangement

    The AC distribution for the ultimate capacity of 24 Rectifiers installed in the plant is as shownbelow (viewed from front of the shelf), with background color indicating the respective phase

    from which the rectifier draws its input power. The EP48XXX plant is internally wired for ACdistribution from the MCBs / TB to each of the individual rectifier modules, through backplane

    interconnects of each shelf.

    R- Phase: L1Y- Phase: L2

    B- Phase: L3

    G41 G42 G43 G44 G45 G46

    G31 G32 G33 G34 G35 G36G21 G22 G23 G24 G25 G26

    G11 G12 G13 G14 G15 G16

    Figure 4-2: EP48XXX Plant Rectifiers AC Input Wire Mapping

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    56/93

    IPMS Product Manual annexureJune- 2010

    For Systems with less number of rectifiers, the uninstalled rectifiers shall occupy slots within therightmost side of the shelf.

    Specifications

    Parameter Min Nom Max Unit Additional Information

    1 Input Voltage Full Power 176 230 290 V rms

    2 Derated Power 90 - 176 V rms

    3 No damage 0 - 500 V rms Continuous Rated

    1 Total Output Power - - 15000 Watts

    2 Output Voltage: Range -42 -52 -57 Vdc

    343 A

    3 Voltage Isolation Input / Chassis 1500 - - VAC For 1 minute.

    4 Output/Chassis 500 - - VAC For 1 minute.

    Storage -20 - 75 C

    -5 25 +55 C Full Power Rated. TemperatureOperating

    +55 +70 CAssumes 2.5%/ Deg. C power derating above 55Deg. C

    Humidity Storage 10 - 95 % Non condensing - no corrosion.

    Operating 5 - 95 %For 96 consecutive hours & no more than 15 days

    / year.

    Size Height - - 5.25 inches 3U Hieght with Rectifiers inserted inside shelf

    Width - - 19/23 inches Depends on whether 19 / 23 Shelf

    Depth - - 400 mm

    Ease of Use - - - - No tool is required to change a rectifer

    Addressing 2 Bit Addressing using piano switches

    Load Share

    All rectifiers installed have load share hardwired

    to backplane. Between shelves, two connectorsavailable for cascading load share cables from oneto another.

    Table 4-1: EP2500AC48 Shelf Specifications

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    57/93

    IPMS Product Manual annexureJune- 2010

    Configuration Requirements

    Table 4-2: EP2500AC48 Rear View Components Identification

    a. Shelf ID switch of bottommost shelf needs to be configured as 00b. Shelf ID switch of second shelf (from bottom) needs to be configured as 01c. Shelf ID switch of third shelf (from bottom) needs to be configured as 10d. Shelf ID switch of fourth shelf (from bottom) needs to be configured as 11

    Note:- Configuring the shelf ID switch (piano switch) as 0 means the switch should not bepressed.

    Shelf ID

    Switch

    Earth

    Line

    Neutral

    Load Share Conn.

    GP Interface Conn.

  • 8/3/2019 CC848894724_Product Manual I2 PMS

    58/93

    IPMS Product Manual annexureJune- 2010

    B. Shelf-less Concept for accommodating 2, or 3 rectifiers

    The shelf also comes in a variant called shelf-less, a concept introduced to reduce the overallsystem cost. Such shelves come with combinations of backplane PWBs that accommodate

    either 2 rectifiers or 3 rectifiers.

    Below is indica