caterpillar electronic technician 2012a v1.0 product ... · pdf filecaterpillar electronic...

56
Caterpillar Electronic Technician 2012A v1.0 Product Status Report 6/9/2013 2:59 PM Product Status Report EMCP 3.2 Logged Diagnostic Codes [Diagnostic Clock = Unavailable hours] - EMCP 3.2 Logged Event Codes [Diagnostic Clock = Unavailable hours] - EMCP 3.2 Parameter Value Engine Serial Number MJE00283 Equipment ID NOT PROGRAMMED Comments Parameter Value ECM Part Number 2275801-05 ECM Serial Number 2966B190HQ Software Group Part Number 3041337-00 Software Group Release Date OCT2006 Software Group Description L1_4_5_Standard -- English, 2.1 Prod, 26Oct2006 Code Description Occ. First Last 1383-11 Engine was Shut Down Hot : Other Failure Mode 1 3504 3504 Code Description Occ. First Last 110- 0 Engine Coolant Temperature : High - most severe (3) 4 3874 3874 110-15 Engine Coolant Temperature : High - least severe (1) 27 3874 3874 110-17 Engine Coolant Temperature : Low - least severe (1) 35 783 3883 168-15 Battery Potential / Power Input #1 : High - least severe (1) 99 6 1758 190- 1 Engine Speed : Low - most severe (3) 3 3087 3507 190-17 Engine Speed : Low - least severe (1) 10 2932 3507 970-31 Engine Auxiliary Engine Shutdown Switch 38 1025 4792 Page 1 of 56 6/9/2013 file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Upload: vandien

Post on 30-Jan-2018

404 views

Category:

Documents


14 download

TRANSCRIPT

Page 1: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Caterpillar Electronic Technician 2012A v1.0 Product Status Report

6/9/2013 2:59 PM

Product Status Report

EMCP 3.2

Logged Diagnostic Codes [Diagnostic Clock = Unavailable hours] - EMCP 3.2

Logged Event Codes [Diagnostic Clock = Unavailable hours] - EMCP 3.2

Parameter Value

Engine Serial Number MJE00283

Equipment ID NOT PROGRAMMED

Comments

Parameter Value

ECM Part Number 2275801-05

ECM Serial Number 2966B190HQ

Software Group Part Number 3041337-00

Software Group Release Date OCT2006

Software Group Description L1_4_5_Standard -- English, 2.1 Prod, 26Oct2006

Code Description Occ. First Last

1383-11 Engine was Shut Down Hot : Other Failure Mode 1 3504 3504

Code Description Occ. First Last

110- 0 Engine Coolant Temperature : High - most severe (3) 4 3874 3874

110-15 Engine Coolant Temperature : High - least severe (1) 27 3874 3874

110-17 Engine Coolant Temperature : Low - least severe (1) 35 783 3883

168-15 Battery Potential / Power Input #1 : High - least severe (1) 99 6 1758

190- 1 Engine Speed : Low - most severe (3) 3 3087 3507

190-17 Engine Speed : Low - least severe (1) 10 2932 3507

970-31 Engine Auxiliary Engine Shutdown Switch 38 1025 4792

Page 1 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 2: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Active Diagnostic Codes - EMCP 3.2

Active Event Codes - EMCP 3.2

Current Totals - EMCP 3.2

Configuration - EMCP 3.2

2436- 1 Generator Average AC Frequency : Low - most severe (3) 4 2932 3507

2436-17

Generator Average AC Frequency : Low - least severe (1) 99 2924 2933

2440- 1Generator Average Line-Line AC RMS Voltage : Low - most severe (3)

93 2925 3825

2440-17

Generator Average Line-Line AC RMS Voltage : Low - least severe (1)

99 2916 2931

2448- 0 Generator Average AC RMS Current : High - most severe (3) 1 3507 3507

2448-15

Generator Average AC RMS Current : High - least severe (1) 99 6 3272

2648-31

Maintenance Lamp 99 505 1181

4007-31

Generator Control not in Automatic 99 0 537

Code Description

No Active Codes

Code Description

2648-31 Maintenance Lamp

4007-31 Generator Control not in Automatic

Description Value Unit

Total Operating Hours Unavailable hours

Generator Total kW Hours Export Unavailable KW-hr

Description Value Unit

Engine Start Fault Protection Activation Delay Time 30 sec

Crank Duration 10 sec

Crank Cycle Rest Interval 10 sec

Page 2 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 3: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Engine Purge Cycle Time 0 sec

Maximum Number of Crank Cycles 5

Cooldown Duration 5 min

Start Aid Activation Time 0 sec

Crank Alert Activation Time 0 sec

Crank Terminate RPM 400 rpm

Engine Fuel Type Configuration Diesel

Fuel Shutoff Solenoid Type Configuration Energized to Run

Engine Type Configuration Electronic

Engine Controller J1939 Data Link Support Configuration Proprietary J1939 Support

Engine Cooldown Speed Configuration Rated Speed

Engine Operating State Input Configuration CAN Input

Fuel Priming Feature Enable Status Disabled

Engine Forced Idle Feature Enable Status Enabled

Maximum Generator Voltage Output Bias Percentage 5 %

Generator Nominal Output Voltage 480 Volts

High Battery Voltage Warning Event Threshold 29.4 Volts

High Battery Voltage Warning Event Notification Delay Time

30 sec

High Battery Voltage Shutdown Event Threshold 32.0 Volts

High Battery Voltage Shutdown Event Notification Delay Time

2 sec

Low Battery Voltage Warning Event Threshold 18.0 Volts

Low Battery Voltage Warning Event Notification Delay Time

10 sec

Low Battery Charging System Voltage Warning Event Threshold

24.5 Volts

Low Battery Charging System Voltage Warning Event Notification Delay Time

30 sec

Customer Password Security Level to Reset Crank/Start Counters

3-Factory, Single Use

SCADA Data Link Baud Rate 19200 baud

SCADA Data Link Parity None

SCADA Data Link Slave Address 1

SCADA Data Link Access Password 00000000

SCADA Data Link Connection Timeout Interval 30.0 sec

RS-485 Bias Resistor Enable Status Enabled

Digital Input #1 Active State Configuration High

Digital Input #2 Active State Configuration Low

Page 3 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 4: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Digital Input #3 Active State Configuration Low

Digital Input #4 Active State Configuration Low

Digital Input #5 Active State Configuration Low

Digital Input #6 Active State Configuration Low

Digital Input #7 Active State Configuration Low

Digital Input #8 Active State Configuration Low

Digital Output #1 Active State Configuration Low

Digital Selector #1 Source Configuration Input #2

Digital Selector #2 Source Configuration Input #4

Digital Selector #3 Source Configuration Input #4

Digital Selector #4 Source Configuration Input #6

Digital Selector #5 Source Configuration Input #5

Digital Selector #6 Source Configuration Input #5

Digital Selector #7 Source Configuration Input #1

Digital Selector #8 Source Configuration Disabled or Not Installed

Digital Selector #9 Source Configuration Disabled or Not Installed

Digital Selector #10 Source Configuration Disabled or Not Installed

Engine Coolant Temperature Sensor Configuration Data Link

High Engine Coolant Temperature Warning Event Threshold

216Deg F

High Engine Coolant Temperature Warning Event Notification Delay Time

2 sec

High Engine Coolant Temperature Shutdown Event Threshold

225Deg F

High Engine Coolant Temperature Shutdown Event Notification Delay Time

10 sec

Low Engine Coolant Temperature Warning Event Threshold

32Deg F

Low Engine Coolant Temperature Warning Event Notification Delay Time

30 sec

Engine Coolant Temperature Sensor Configuration Code Map #1

Engine Oil Pressure Sensor Configuration Data Link

Low Engine Oil Pressure Warning Event Threshold 35 psi

Low Idle Low Engine Oil Pressure Warning Event Threshold

15 psi

Low Engine Oil Pressure Warning Event Notification Delay Time

0 sec

Low Engine Oil Pressure Shutdown Event Threshold 30 psi

Low Idle Low Engine Oil Pressure Shutdown Event Threshold

10 psi

Page 4 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 5: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Low Engine Oil Pressure Shutdown Event Notification Delay Time

0 sec

Low Engine Oil Pressure Step Speed 1200 rpm

Engine Oil Pressure Sensor Configuration Code Map #1

Flywheel Teeth 136

Engine Overspeed Setpoint 2124 rpm

Engine Underspeed Warning Event Threshold 1548 rpm

Engine Underspeed Warning Event Notification Delay Time

2.0 sec

Engine Underspeed Shutdown Event Threshold 1476 rpm

Engine Underspeed Shutdown Event Notification Delay Time

2.0 sec

Engine Speed Sensor Configuration Sensor

Event Input Function #1 Suspect Parameter Number Earth Fault

Event Input Function #1 Failure Mode Identifier Condition Exists

Event Input Function #1 Event Notification Delay Time 10 sec

Event Input Function #1 Active State Configuration High

Event Input Function #2 Suspect Parameter Number Custom Event

Event Input Function #2 Failure Mode Identifier Condition Exists

Event Input Function #2 Event Notification Delay Time 0 sec

Event Input Function #2 Active State Configuration High

Event Input Function #3 Suspect Parameter Number Custom Event

Event Input Function #3 Failure Mode Identifier Condition Exists

Event Input Function #3 Event Notification Delay Time 0 sec

Event Input Function #3 Active State Configuration High

Event Input Function #4 Suspect Parameter Number Battery Charger Failure

Event Input Function #4 Failure Mode Identifier Condition Exists

Event Input Function #4 Event Notification Delay Time 0 sec

Event Input Function #4 Active State Configuration High

Event Input Function #5 Suspect Parameter Number Custom Event

Event Input Function #5 Failure Mode Identifier Condition Exists

Event Input Function #5 Event Notification Delay Time 0 sec

Event Input Function #5 Active State Configuration High

Event Input Function #6 Suspect Parameter Number Custom Event

Event Input Function #6 Failure Mode Identifier Condition Exists

Event Input Function #6 Event Notification Delay Time 0 sec

Event Input Function #6 Active State Configuration High

Event Input Function #7 Suspect Parameter Number Disabled or Not Installed

Event Input Function #7 Failure Mode Identifier Disabled or Not Installed

Page 5 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 6: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Event Input Function #7 Event Notification Delay Time Disabled or Not Installed sec

Event Input Function #7 Active State Configuration Disabled or Not Installed

Event Input Function #8 Suspect Parameter Number Disabled or Not Installed

Event Input Function #8 Failure Mode Identifier Disabled or Not Installed

Event Input Function #8 Event Notification Delay Time Disabled or Not Installed sec

Event Input Function #8 Active State Configuration Disabled or Not Installed

Event Output Function #1 Suspect Parameter Number Engine Oil Pressure

Event Output Function #1 Trigger Condition **Disabled

Event Output Function #2 Suspect Parameter Number Disabled or Not Installed

Event Output Function #2 Trigger Condition Disabled or Not Installed

Event Output Function #3 Suspect Parameter Number Disabled or Not Installed

Event Output Function #3 Trigger Condition Disabled or Not Installed

Event Output Function #4 Suspect Parameter Number Disabled or Not Installed

Event Output Function #4 Trigger Condition Disabled or Not Installed

Event Output Function #5 Suspect Parameter Number Disabled or Not Installed

Event Output Function #5 Trigger Condition Disabled or Not Installed

Event Output Function #6 Suspect Parameter Number Disabled or Not Installed

Event Output Function #6 Trigger Condition Disabled or Not Installed

Event Output Function #7 Suspect Parameter Number Disabled or Not Installed

Event Output Function #7 Trigger Condition Disabled or Not Installed

Event Output Function #8 Suspect Parameter Number Disabled or Not Installed

Event Output Function #8 Trigger Condition Disabled or Not Installed

Accessory Data Link Diagnostic Response Configuration Activate Warning Condition

Accessory Data Link Diagnostic Audible Alert Yes

Accessory Data Link Diagnostic Breaker #1 Trip No

Accessory Data Link Diagnostic Breaker #2 Trip No

Air Filter Differential Pressure Sensor Diagnostic Response Configuration

Activate Warning Condition

Air Filter Differential Pressure Sensor Diagnostic Audible Alert

No

Air Filter Differential Pressure Sensor Diagnostic Breaker #1 Trip

No

Air Filter Differential Pressure Sensor Diagnostic Breaker #2 Trip

No

Ambient Air Temperature Sensor Diagnostic Response Configuration

Activate Warning Condition

Ambient Air Temperature Sensor Diagnostic Audible Alert No

Ambient Air Temperature Sensor Diagnostic Breaker #1 Trip

No

Page 6 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 7: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Ambient Air Temperature Sensor Diagnostic Breaker #2 Trip

No

Digital Output #1 Diagnostic Response Configuration Activate Warning Condition

Digital Output #1 Diagnostic Audible Alert No

Digital Output #1 Diagnostic Breaker #1 Trip No

Digital Output #1 Diagnostic Breaker #2 Trip No

Engine Coolant Level Sensor Diagnostic Response Configuration

Activate Warning Condition

Engine Coolant Level Sensor Diagnostic Audible Alert No

Engine Coolant Level Sensor Diagnostic Breaker #1 Trip No

Engine Coolant Level Sensor Diagnostic Breaker #2 Trip No

Engine Coolant Temperature Sensor Diagnostic Response Configuration

Activate Warning Condition

Engine Coolant Temperature Sensor Diagnostic Audible Alert

No

Engine Coolant Temperature Sensor Diagnostic Breaker #1 Trip

No

Engine Coolant Temperature Sensor Diagnostic Breaker #2 Trip

No

Engine Oil Level Sensor Diagnostic Response Configuration

Activate Warning Condition

Engine Oil Level Sensor Diagnostic Audible Alert No

Engine Oil Level Sensor Diagnostic Breaker #1 Trip No

Engine Oil Level Sensor Diagnostic Breaker #2 Trip No

Engine Oil Pressure Sensor Diagnostic Response Configuration

Activate Warning Condition

Engine Oil Pressure Sensor Diagnostic Audible Alert No

Engine Oil Pressure Sensor Diagnostic Breaker #1 Trip No

Engine Oil Pressure Sensor Diagnostic Breaker #2 Trip No

Engine Oil Temperature Sensor Diagnostic Response Configuration

Activate Warning Condition

Engine Oil Temperature Sensor Diagnostic Audible Alert No

Engine Oil Temperature Sensor Diagnostic Breaker #1 Trip

No

Engine Oil Temperature Sensor Diagnostic Breaker #2 Trip

No

Engine Speed Sensor Diagnostic Response ConfigurationActivate Hard Shutdown Condition

Engine Speed Sensor Diagnostic Audible Alert Yes

Engine Speed Sensor Diagnostic Breaker #1 Trip No

Page 7 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 8: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Engine Speed Sensor Diagnostic Breaker #2 Trip No

Exhaust Temperature Sensor Diagnostic Response Configuration

Activate Warning Condition

Exhaust Temperature Sensor Diagnostic Audible Alert No

Exhaust Temperature Sensor Diagnostic Breaker #1 Trip No

Exhaust Temperature Sensor Diagnostic Breaker #2 Trip No

Right Exhaust Temperature Sensor Diagnostic Response Configuration

Activate Warning Condition

Right Exhaust Temperature Sensor Diagnostic Audible Alert

No

Right Exhaust Temperature Sensor Diagnostic Breaker #1 Trip

No

Right Exhaust Temperature Sensor Diagnostic Breaker #2 Trip

No

Left Exhaust Temperature Sensor Diagnostic Response Configuration

Activate Warning Condition

Left Exhaust Temperature Sensor Diagnostic Audible Alert

No

Left Exhaust Temperature Sensor Diagnostic Breaker #1 Trip

No

Left Exhaust Temperature Sensor Diagnostic Breaker #2 Trip

No

Fire Extinguisher Pressure Sensor Diagnostic Response Configuration

Activate Warning Condition

Fire Extinguisher Pressure Sensor Audible Alert No

Fire Extinguisher Pressure Sensor Breaker #1 Trip No

Fire Extinguisher Pressure Sensor Breaker #2 Trip No

Fuel Filter Differential Pressure Sensor Diagnostic Response Configuration

Activate Warning Condition

Fuel Filter Differential Pressure Sensor Diagnostic Audible Alert

No

Fuel Filter Differential Pressure Sensor Diagnostic Breaker #1 Trip

No

Fuel Filter Differential Pressure Sensor Diagnostic Breaker #2 Trip

No

Fuel Level Sensor Diagnostic Response Configuration Activate Warning Condition

Fuel Level Sensor Diagnostic Audible Alert No

Fuel Level Sensor Diagnostic Breaker #1 Trip No

Fuel Level Sensor Diagnostic Breaker #2 Trip No

External Tank Fuel Level Sensor Diagnostic Response Configuration

Activate Warning Condition

Page 8 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 9: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

External Tank Fuel Level Sensor Diagnostic Audible Alert No

External Tank Fuel Level Sensor Diagnostic Breaker #1 Trip

No

External Tank Fuel Level Sensor Diagnostic Breaker #2 Trip

No

Generator Bearing #1 Temperature Sensor Diagnostic Response Configuration

Activate Warning Condition

Generator Bearing #1 Temperature Sensor Diagnostic Audible Alert

No

Generator Bearing #1 Temperature Sensor Diagnostic Breaker #1 Trip

No

Generator Bearing #1 Temperature Sensor Diagnostic Breaker #2 Trip

No

Generator Output Sensing System Diagnostic Response Configuration

Activate Warning Condition

Generator Output Sensing System Diagnostic Audible Alert

Yes

Generator Output Sensing System Diagnostic Breaker #1 Trip

No

Generator Output Sensing System Diagnostic Breaker #2 Trip

No

Engine Oil Filter Differential Pressure Sensor Diagnostic Response Config

Activate Warning Condition

Engine Oil Filter Differential Pressure Sensor Diagnostic Audible Alert

No

Engine Oil Filter Differential Pressure Sensor Diagnostic Breaker #1 Trip

No

Engine Oil Filter Differential Pressure Sensor Diagnostic Breaker #2 Trip

No

Primary Data Link Diagnostic Response Configuration Activate Warning Condition

Primary Data Link Diagnostic Audible Alert No

Primary Data Link Diagnostic Breaker #1 Trip No

Primary Data Link Diagnostic Breaker #2 Trip No

SCADA Data Link Diagnostic Response Configuration Activate Warning Condition

SCADA Data Link Diagnostic Audible Alert No

SCADA Data Link Diagnostic Breaker #1 Trip No

SCADA Data Link Diagnostic Breaker #2 Trip No

SCADA Data Link Diagnostic Fault Protection Timer No

Starting Air Pressure Sensor Diagnostic Response Configuration

Activate Warning Condition

Starting Air Pressure Sensor Diagnostic Audible Alert No

Page 9 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 10: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Starting Air Pressure Sensor Diagnostic Breaker #1 Trip No

Starting Air Pressure Sensor Diagnostic Breaker #2 Trip No

Battery Charger Failure Diagnostic Response Configuration

Activate Warning Condition

Battery Charger Failure Diagnostic Audible Alert Yes

Engine Controller Not Responding Diagnostic Response Configuration

Activate Warning Condition

Engine Controller Not Responding Diagnostic Audible Alert

No

Engine Controller Not Responding Diagnostic Breaker #1 Trip

No

Engine Controller Not Responding Diagnostic Breaker #2 Trip

No

Air Damper Closed Event Response ConfigurationHard Shutdown & Active Only Condition

Air Damper Closed Event Audible Alert Yes

High Air Filter Differential Pressure Warning Event Response Configuration

Activate Warning Condition

High Air Filter Differential Pressure Warning Event Audible Alert

Yes

High Air Filter Differential Pressure Warning Event Breaker #1 Trip

No

High Air Filter Differential Pressure Warning Event Breaker #2 Trip

No

High Air Filter Differential Pressure Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Air Filter Differential Pressure Shutdown Event Audible Alert

Yes

High Air Filter Differential Pressure Shutdown Event Breaker #1 Trip

No

High Air Filter Differential Pressure Shutdown Event Breaker #2 Trip

No

Low Air Filter Differential Pressure Warning Event Response Configuration

Activate Warning Condition

Low Air Filter Differential Pressure Warning Event Audible Alert

Yes

Low Air Filter Differential Pressure Warning Event Breaker #1 Trip

No

Low Air Filter Differential Pressure Warning Event Breaker #2 Trip

No

Low Air Filter Differential Pressure Warning Event Fault Yes

Page 10 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 11: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Protection Timer

Low Air Filter Differential Pressure Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Low Air Filter Differential Pressure Shutdown Event Audible Alert

Yes

Low Air Filter Differential Pressure Shutdown Event Breaker #1 Trip

No

Low Air Filter Differential Pressure Shutdown Event Breaker #2 Trip

No

Low Air Filter Differential Pressure Shutdown Event Fault Protection Timer

Yes

Emergency Stop Activated Event Response ConfigurationActivate Hard Shutdown Condition

Emergency Stop Activated Event Audible Alert Yes

Emergency Stop Activated Event Breaker #1 Trip No

Emergency Stop Activated Event Breaker #2 Trip No

High Engine Coolant Level Warning Event Response Configuration

Activate Warning Condition

High Engine Coolant Level Warning Event Audible Alert Yes

High Engine Coolant Level Warning Event Breaker #1 Trip

No

High Engine Coolant Level Warning Event Breaker #2 Trip

No

High Engine Coolant Level Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Engine Coolant Level Shutdown Event Audible Alert Yes

High Engine Coolant Level Shutdown Event Breaker #1 Trip

No

High Engine Coolant Level Shutdown Event Breaker #2 Trip

No

Low Engine Coolant Level Warning Event Response Configuration

Activate Warning Condition

Low Engine Coolant Level Warning Event Audible Alert Yes

Low Engine Coolant Level Warning Event Breaker #1 Trip

No

Low Engine Coolant Level Warning Event Breaker #2 Trip

No

Low Engine Coolant Level Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Low Engine Coolant Level Shutdown Event Audible Alert Yes

Low Engine Coolant Level Shutdown Event Breaker #1 No

Page 11 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 12: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Trip

Low Engine Coolant Level Shutdown Event Breaker #2 Trip

No

High Engine Coolant Temperature Warning Event Response Configuration

Activate Warning Condition

High Engine Coolant Temperature Warning Event Audible Alert

Yes

High Engine Coolant Temperature Warning Event Breaker #1 Trip

No

High Engine Coolant Temperature Warning Event Breaker #2 Trip

No

High Engine Coolant Temperature Warning Event Fault Protection Timer

Yes

High Engine Coolant Temperature Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Engine Coolant Temperature Shutdown Event Audible Alert

Yes

High Engine Coolant Temperature Shutdown Event Breaker #1 Trip

No

High Engine Coolant Temperature Shutdown Event Breaker #2 Trip

No

High Engine Coolant Temperature Shutdown Event Fault Protection Timer

Yes

Low Engine Coolant Temperature Warning Event Response Configuration

Activate Warning Condition

Low Engine Coolant Temperature Warning Event Audible Alert

Yes

Low Engine Coolant Temperature Warning Event Breaker #1 Trip

No

Low Engine Coolant Temperature Warning Event Breaker #2 Trip

No

Low Engine Coolant Temperature Warning Event Fault Protection Timer

No

Engine Failure To Start Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Engine Failure To Start Shutdown Event Audible Alert Yes

Engine Failure To Start Shutdown Event Breaker #1 Trip No

Engine Failure To Start Shutdown Event Breaker #2 Trip No

High Engine Oil Level Warning Event Response Configuration

Activate Warning Condition

High Engine Oil Level Warning Event Audible Alert Yes

Page 12 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 13: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

High Engine Oil Level Warning Event Breaker #1 Trip No

High Engine Oil Level Warning Event Breaker #2 Trip No

High Engine Oil Level Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Engine Oil Level Shutdown Event Audible Alert Yes

High Engine Oil Level Shutdown Event Breaker #1 Trip No

High Engine Oil Level Shutdown Event Breaker #2 Trip No

Low Engine Oil Level Warning Event Response Configuration

Activate Warning Condition

Low Engine Oil Level Warning Event Audible Alert Yes

Low Engine Oil Level Warning Event Breaker #1 Trip No

Low Engine Oil Level Warning Event Breaker #2 Trip No

Low Engine Oil Level Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Low Engine Oil Level Shutdown Event Audible Alert Yes

Low Engine Oil Level Shutdown Event Breaker #1 Trip No

Low Engine Oil Level Shutdown Event Breaker #2 Trip No

Low Engine Oil Pressure Warning Event Response Configuration

Activate Warning Condition

Low Engine Oil Pressure Warning Event Audible Alert Yes

Low Engine Oil Pressure Warning Event Breaker #1 Trip No

Low Engine Oil Pressure Warning Event Breaker #2 Trip No

Low Engine Oil Pressure Warning Event Fault Protection Timer

Yes

Low Engine Oil Pressure Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Low Engine Oil Pressure Shutdown Event Audible Alert Yes

Low Engine Oil Pressure Shutdown Event Breaker #1 Trip

No

Low Engine Oil Pressure Shutdown Event Breaker #2 Trip

No

Low Engine Oil Pressure Shutdown Event Fault Protection Timer

Yes

High Engine Oil Temperature Warning Event Response Configuration

Activate Warning Condition

High Engine Oil Temperature Warning Event Audible Alert

Yes

High Engine Oil Temperature Warning Event Breaker #1 Trip

No

High Engine Oil Temperature Warning Event Breaker #2 Trip

No

Page 13 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 14: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

High Engine Oil Temperature Warning Event Fault Protection Timer

No

High Engine Oil Temperature Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Engine Oil Temperature Shutdown Event Audible Alert

Yes

High Engine Oil Temperature Shutdown Event Breaker #1 Trip

No

High Engine Oil Temperature Shutdown Event Breaker #2 Trip

No

High Engine Oil Temperature Shutdown Event Fault Protection Timer

No

Low Engine Oil Temperature Warning Event Response Configuration

Activate Warning Condition

Low Engine Oil Temperature Warning Event Audible Alert

Yes

Low Engine Oil Temperature Warning Event Breaker #1 Trip

No

Low Engine Oil Temperature Warning Event Breaker #2 Trip

No

Low Engine Oil Temperature Warning Event Fault Protection Timer

Yes

Low Engine Oil Temperature Shutdown Event Response Configuration

Disable Condition

Low Engine Oil Temperature Shutdown Event Audible Alert

No

Low Engine Oil Temperature Shutdown Event Breaker #1 Trip

No

Low Engine Oil Temperature Shutdown Event Breaker #2 Trip

No

Low Engine Oil Temperature Shutdown Event Fault Protection Timer

No

Unexpected Engine Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Unexpected Engine Shutdown Event Audible Alert Yes

Unexpected Engine Shutdown Event Breaker #1 Trip No

Unexpected Engine Shutdown Event Breaker #2 Trip No

Engine Overspeed Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Engine Overspeed Shutdown Event Audible Alert Yes

Engine Overspeed Shutdown Event Breaker #1 Trip No

Page 14 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 15: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Engine Overspeed Shutdown Event Breaker #2 Trip No

Engine Underspeed Warning Event Response Configuration

Disable Condition

Engine Underspeed Warning Event Audible Alert Yes

Engine Underspeed Warning Event Breaker #1 Trip No

Engine Underspeed Warning Event Breaker #2 Trip No

Engine Underspeed Warning Event Fault Protection Timer

Yes

Engine Underspeed Shutdown Event Response Configuration

Disable Condition

Engine Underspeed Shutdown Event Audible Alert Yes

Engine Underspeed Shutdown Event Breaker #1 Trip No

Engine Underspeed Shutdown Event Breaker #2 Trip No

Engine Underspeed Shutdown Event Fault Protection Timer

Yes

High Exhaust Temperature Warning Event Response Configuration

Activate Warning Condition

High Exhaust Temperature Warning Event Audible Alert Yes

High Exhaust Temperature Warning Event Breaker #1 Trip

No

High Exhaust Temperature Warning Event Breaker #2 Trip

No

High Exhaust Temperature Warning Event Fault Protection Timer

No

High Exhaust Temperature Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Exhaust Temperature Shutdown Event Audible Alert Yes

High Exhaust Temperature Shutdown Event Breaker #1 Trip

No

High Exhaust Temperature Shutdown Event Breaker #2 Trip

No

High Exhaust Temperature Shutdown Event Fault Protection Timer

No

Low Exhaust Temperature Warning Event Response Configuration

Activate Warning Condition

Low Exhaust Temperature Warning Event Audible Alert Yes

Low Exhaust Temperature Warning Event Breaker #1 Trip

No

Low Exhaust Temperature Warning Event Breaker #2 Trip

No

Low Exhaust Temperature Warning Event Fault

Page 15 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 16: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Protection Timer Yes

Low Exhaust Temperature Shutdown Event Response Configuration

Disable Condition

Low Exhaust Temperature Shutdown Event Audible Alert No

Low Exhaust Temperature Shutdown Event Breaker #1 Trip

No

Low Exhaust Temperature Shutdown Event Breaker #2 Trip

No

Low Exhaust Temperature Shutdown Event Fault Protection Timer

Yes

High Right Exhaust Temperature Warning Event Response Configuration

Activate Warning Condition

High Right Exhaust Temperature Warning Event Audible Alert

Yes

High Right Exhaust Temperature Warning Event Breaker #1 Trip

No

High Right Exhaust Temperature Warning Event Breaker #2 Trip

No

High Right Exhaust Temperature Warning Event Fault Protection Timer

No

High Right Exhaust Temperature Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Right Exhaust Temperature Shutdown Event Audible Alert

Yes

High Right Exhaust Temperature Shutdown Event Breaker #1 Trip

No

High Right Exhaust Temperature Shutdown Event Breaker #2 Trip

No

High Right Exhaust Temperature Shutdown Event Fault Protection Timer

No

Low Right Exhaust Temperature Warning Event Response Configuration

Activate Warning Condition

Low Right Exhaust Temperature Warning Event Audible Alert

Yes

Low Right Exhaust Temperature Warning Event Breaker #1 Trip

No

Low Right Exhaust Temperature Warning Event Breaker #2 Trip

No

Low Right Exhaust Temperature Warning Event Fault Protection Timer

Yes

Low Right Exhaust Temperature Shutdown Event Response Configuration

Disable Condition

Page 16 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 17: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Low Right Exhaust Temperature Shutdown Event Audible Alert

No

Low Right Exhaust Temperature Shutdown Event Breaker #1 Trip

No

Low Right Exhaust Temperature Shutdown Event Breaker #2 Trip

No

Low Right Exhaust Temperature Shutdown Event Fault Protection Timer

No

High Left Exhaust Temperature Warning Event Response Configuration

Activate Warning Condition

High Left Exhaust Temperature Warning Event Audible Alert

Yes

High Left Exhaust Temperature Warning Event Breaker #1 Trip

No

High Left Exhaust Temperature Warning Event Breaker #2 Trip

No

High Left Exhaust Temperature Warning Event Fault Protection Timer

No

High Left Exhaust Temperature Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Left Exhaust Temperature Shutdown Event Audible Alert

Yes

High Left Exhaust Temperature Shutdown Event Breaker #1 Trip

No

High Left Exhaust Temperature Shutdown Event Breaker #2 Trip

No

High Left Exhaust Temperature Shutdown Event Fault Protection Timer

No

Low Left Exhaust Temperature Warning Event Response Configuration

Activate Warning Condition

Low Left Exhaust Temperature Warning Event Audible Alert

Yes

Low Left Exhaust Temperature Warning Event Breaker #1 Trip

No

Low Left Exhaust Temperature Warning Event Breaker #2 Trip

No

Low Left Exhaust Temperature Warning Event Fault Protection Timer

Yes

Low Left Exhaust Temperature Shutdown Event Response Configuration

Disable Condition

Low Left Exhaust Temperature Shutdown Event Audible Alert

No

Page 17 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 18: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Low Left Exhaust Temperature Shutdown Event Breaker #1 Trip

No

Low Left Exhaust Temperature Shutdown Event Breaker #2 Trip

No

Low Left Exhaust Temperature Shutdown Event Fault Protection Timer

No

High Fuel Filter Differential Pressure Warning Event Response Configuration

Activate Warning Condition

High Fuel Filter Differential Pressure Warning Event Audible Alert

Yes

High Fuel Filter Differential Pressure Warning Event Breaker #1 Trip

No

High Fuel Filter Differential Pressure Warning Event Breaker #2 Trip

No

High Fuel Filter Differential Pressure Shutdown Event Response Config

Activate Hard Shutdown Condition

High Fuel Filter Differential Pressure Shutdown Event Audible Alert

Yes

High Fuel Filter Differential Pressure Shutdown Event Breaker #1 Trip

No

High Fuel Filter Differential Pressure Shutdown Event Breaker #2 Trip

No

Low Fuel Filter Differential Pressure Warning Event Response Configuration

Activate Warning Condition

Low Fuel Filter Differential Pressure Warning Event Audible Alert

Yes

Low Fuel Filter Differential Pressure Warning Event Breaker #1 Trip

No

Low Fuel Filter Differential Pressure Warning Event Breaker #2 Trip

No

Low Fuel Filter Differential Pressure Warning Event Fault Protection Timer

Yes

Low Fuel Filter Differential Pressure Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Low Fuel Filter Differential Pressure Shutdown Event Audible Alert

Yes

Low Fuel Filter Differential Pressure Shutdown Event Breaker #1 Trip

No

Low Fuel Filter Differential Pressure Shutdown Event Breaker #2 Trip

No

Low Fuel Filter Differential Pressure Shutdown Event Fault Protection Timer

Yes

Page 18 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 19: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

High Fuel Level Warning Event Response Configuration Activate Warning Condition

High Fuel Level Warning Event Audible Alert Yes

High Fuel Level Warning Event Breaker #1 Trip No

High Fuel Level Warning Event Breaker #2 Trip No

High Fuel Level Shutdown Event Response ConfigurationActivate Hard Shutdown Condition

High Fuel Level Shutdown Event Audible Alert Yes

High Fuel Level Shutdown Event Breaker #1 Trip No

High Fuel Level Shutdown Event Breaker #2 Trip No

Low Fuel Level Warning Event Response Configuration Activate Warning Condition

Low Fuel Level Warning Event Audible Alert Yes

Low Fuel Level Warning Event Breaker #1 Trip No

Low Fuel Level Warning Event Breaker #2 Trip No

Low Fuel Level Shutdown Event Response ConfigurationActivate Hard Shutdown Condition

Low Fuel Level Shutdown Event Audible Alert Yes

Low Fuel Level Shutdown Event Breaker #1 Trip No

Low Fuel Level Shutdown Event Breaker #2 Trip No

External Tank High Fuel Level Warning Event Response Configuration

Activate Warning Condition

External Tank High Fuel Level Warning Event Audible Alert

Yes

External Tank High Fuel Level Warning Event Breaker #1 Trip

No

External Tank High Fuel Level Warning Event Breaker #2 Trip

No

External Tank High Fuel Level Shutdown Event Response Configuration

Activate Hard Shutdown Condition

External Tank High Fuel Level Shutdown Event Audible Alert

Yes

External Tank High Fuel Level Shutdown Event Breaker #1 Trip

No

External Tank High Fuel Level Shutdown Event Breaker #2 Trip

No

External Tank Low Fuel Level Warning Event Response Configuration

Activate Warning Condition

External Tank Low Fuel Level Warning Event Audible Alert

Yes

External Tank Low Fuel Level Warning Event Breaker #1 Trip

No

External Tank Low Fuel Level Warning Event Breaker #2

Page 19 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 20: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Trip No

External Tank Low Fuel Level Shutdown Event Response Configuration

Activate Hard Shutdown Condition

External Tank Low Fuel Level Shutdown Event Audible Alert

Yes

External Tank Low Fuel Level Shutdown Event Breaker #1 Trip

No

External Tank Low Fuel Level Shutdown Event Breaker #2 Trip

No

Fuel Leak Event Response Configuration Activate Warning Condition

Fuel Leak Event Audible Alert Yes

Fuel Leak Event Breaker #1 Trip No

Fuel Leak Event Breaker #2 Trip No

High Engine Oil Filter Differential Pressure Warning Event Response Config

Activate Warning Condition

High Engine Oil Filter Differential Pressure Warning Event Audible Alert

Yes

High Engine Oil Filter Differential Pressure Warning Event Breaker #1 Trip

No

High Engine Oil Filter Differential Pressure Warning Event Breaker #2 Trip

No

High Engine Oil Filter Differential Pressure Shutdown Event Response Config

Activate Hard Shutdown Condition

High Engine Oil Filter Differential Pressure Shutdown Event Audible Alert

Yes

High Engine Oil Filter Differential Pressure Shutdown Event Breaker #1 Trip

No

High Engine Oil Filter Differential Pressure Shutdown Event Breaker #2 Trip

No

Low Engine Oil Filter Differential Pressure Warning Event Response Config

Activate Warning Condition

Low Engine Oil Filter Differential Pressure Warning Event Audible Alert

Yes

Low Engine Oil Filter Differential Pressure Warning Event Breaker #1 Trip

No

Low Engine Oil Filter Differential Pressure Warning Event Breaker #2 Trip

No

Low Engine Oil Filter Differential Pressure Warning Fault Protection Timer

Yes

Low Engine Oil Filter Differential Pressure Shutdown Event Response Config

Activate Hard Shutdown Condition

Page 20 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 21: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Low Engine Oil Filter Differential Pressure Shutdown Event Audible Alert

Yes

Low Engine Oil Filter Differential Pressure Shutdown Event Breaker #1 Trip

No

Low Engine Oil Filter Differential Pressure Shutdown Event Breaker #2 Trip

No

Low Engine Oil Filter Differential Pressure Shutdown Fault Protection Timer

Yes

Service Maintenance Interval Warning Event Response Configuration

Activate Warning Condition

Service Maintenance Interval Warning Event Audible Alert

No

High Starting Air Pressure Warning Event Response Configuration

Activate Warning Condition

High Starting Air Pressure Warning Event Audible Alert Yes

High Starting Air Pressure Warning Event Breaker #1 Trip

No

High Starting Air Pressure Warning Event Breaker #2 Trip

No

High Starting Air Pressure Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Starting Air Pressure Shutdown Event Audible Alert Yes

High Starting Air Pressure Shutdown Event Breaker #1 Trip

No

High Starting Air Pressure Shutdown Event Breaker #2 Trip

No

Low Starting Air Pressure Warning Event Response Configuration

Activate Warning Condition

Low Starting Air Pressure Warning Event Audible Alert Yes

Low Starting Air Pressure Warning Event Breaker #1 Trip

No

Low Starting Air Pressure Warning Event Breaker #2 Trip

No

Low Starting Air Pressure Warning Event Fault Protection Timer

Yes

Low Starting Air Pressure Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Low Starting Air Pressure Shutdown Event Audible Alert Yes

Low Starting Air Pressure Shutdown Event Breaker #1 Trip

No

Low Starting Air Pressure Shutdown Event Breaker #2 Trip

No

Page 21 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 22: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Low Starting Air Pressure Shutdown Event Fault Protection Timer

Yes

High Gas Pressure Warning Event Response Configuration

Activate Warning Condition

High Gas Pressure Warning Event Audible Alert Yes

High Gas Pressure Warning Event Breaker #1 Trip No

High Gas Pressure Warning Event Breaker #2 Trip No

High Gas Pressure Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Gas Pressure Shutdown Event Audible Alert Yes

High Gas Pressure Shutdown Event Breaker #1 Trip No

High Gas Pressure Shutdown Event Breaker #2 Trip No

Low Gas Pressure Warning Event Response Configuration

Activate Warning Condition

Low Gas Pressure Warning Event Audible Alert Yes

Low Gas Pressure Warning Event Breaker #1 Trip No

Low Gas Pressure Warning Event Breaker #2 Trip No

Low Gas Pressure Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Low Gas Pressure Shutdown Event Audible Alert Yes

Low Gas Pressure Shutdown Event Breaker #1 Trip No

Low Gas Pressure Shutdown Event Breaker #2 Trip No

Engine Intake Manifold Charge Combustion Event Response Configuration

Activate Hard Shutdown Condition

Engine Intake Manifold Charge Combustion Event Audible Alert

Yes

Engine Intake Manifold Charge Combustion Event Loss of Utility

No

Engine Intake Manifold Charge Combustion Event Breaker #1 Trip

No

Engine Intake Manifold Charge Combustion Event Breaker #2 Trip

No

Engine Intake Manifold Charge Combustion Event Fault Protection Timer

No

High Generator Bearing #1 Temperature Warning Event Response Configuration

Activate Warning Condition

High Generator Bearing #1 Temperature Warning Event Audible Alert

Yes

High Generator Bearing #1 Temperature Warning Event Breaker #1 Trip

No

High Generator Bearing #1 Temperature Warning Event

Page 22 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 23: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Breaker #2 Trip No

High Generator Bearing #1 Temperature Warning Event Fault Protection Timer

No

High Generator Bearing #1 Temperature Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Generator Bearing #1 Temperature Shutdown Event Audible Alert

Yes

High Generator Bearing #1 Temperature Shutdown Event Breaker #1 Trip

No

High Generator Bearing #1 Temperature Shutdown Event Breaker #2 Trip

No

High Generator Bearing #1 Temperature Shutdown Event Fault Protection Timer

No

Low Generator Bearing #1 Temperature Warning Event Response Configuration

Activate Warning Condition

Low Generator Bearing #1 Temperature Warning Event Audible Alert

Yes

Low Generator Bearing #1 Temperature Warning Event Breaker #1 Trip

No

Low Generator Bearing #1 Temperature Warning Event Breaker #2 Trip

No

Low Generator Bearing #1 Temperature Warning Event Fault Protection Timer

Yes

Low Generator Bearing #1 Temperature Shutdown Event Response Configuration

Disable Condition

Low Generator Bearing #1 Temperature Shutdown Event Audible Alert

No

Low Generator Bearing #1 Temperature Shutdown Event Breaker #1 Trip

No

Low Generator Bearing #1 Temperature Shutdown Event Breaker #2 Trip

No

Low Generator Bearing #1 Temperature Shutdown Event Fault Protection Timer

No

Generator Overcurrent Warning Event Response Configuration

Activate Warning Condition

Generator Overcurrent Warning Event Audible Alert Yes

Generator Overcurrent Warning Event Breaker #1 Trip No

Generator Overcurrent Warning Event Breaker #2 Trip No

Generator Overcurrent Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Generator Overcurrent Shutdown Event Audible Alert Yes

Page 23 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 24: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Generator Overcurrent Shutdown Event Breaker #1 Trip No

Generator Overcurrent Shutdown Event Breaker #2 Trip No

Generator Over Frequency Warning Event Response Configuration

Activate Warning Condition

Generator Over Frequency Warning Event Audible Alert Yes

Generator Over Frequency Warning Event Breaker #1 Trip

No

Generator Over Frequency Warning Event Breaker #2 Trip

No

Generator Over Frequency Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Generator Over Frequency Shutdown Event Audible Alert Yes

Generator Over Frequency Shutdown Event Breaker #1 Trip

No

Generator Over Frequency Shutdown Event Breaker #2 Trip

No

Generator Under Frequency Warning Event Response Configuration

Disable Condition

Generator Under Frequency Warning Event Audible Alert Yes

Generator Under Frequency Warning Event Breaker #1 Trip

No

Generator Under Frequency Warning Event Breaker #2 Trip

No

Generator Under Frequency Warning Event Fault Protection Timer

Yes

Generator Under Frequency Shutdown Event Response Configuration

Disable Condition

Generator Under Frequency Shutdown Event Audible Alert

Yes

Generator Under Frequency Shutdown Event Breaker #1 Trip

No

Generator Under Frequency Shutdown Event Breaker #2 Trip

No

Generator Under Frequency Shutdown Event Fault Protection Timer

Yes

Generator Reverse Power Warning Event Response Configuration

Activate Warning Condition

Generator Reverse Power Warning Event Audible Alert Yes

Generator Reverse Power Warning Event Breaker #1 Trip

No

Generator Reverse Power Warning Event Breaker #2 No

Page 24 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 25: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Trip

Generator Reverse Power Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Generator Reverse Power Shutdown Event Audible Alert Yes

Generator Reverse Power Shutdown Event Breaker #1 Trip

No

Generator Reverse Power Shutdown Event Breaker #2 Trip

No

Generator Over Voltage Warning Event Response Configuration

Activate Warning Condition

Generator Over Voltage Warning Event Audible Alert Yes

Generator Over Voltage Warning Event Breaker #1 Trip No

Generator Over Voltage Warning Event Breaker #2 Trip No

Generator Over Voltage Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Generator Over Voltage Shutdown Event Audible Alert Yes

Generator Over Voltage Shutdown Event Breaker #1 Trip

No

Generator Over Voltage Shutdown Event Breaker #2 Trip

No

Generator Under Voltage Warning Event Response Configuration

Disable Condition

Generator Under Voltage Warning Event Audible Alert Yes

Generator Under Voltage Warning Event Breaker #1 Trip No

Generator Under Voltage Warning Event Breaker #2 Trip No

Generator Under Voltage Warning Event Fault Protection Timer

Yes

Generator Under Voltage Shutdown Event Response Configuration

Disable Condition

Generator Under Voltage Shutdown Event Audible Alert Yes

Generator Under Voltage Shutdown Event Breaker #1 Trip

No

Generator Under Voltage Shutdown Event Breaker #2 Trip

No

Generator Under Voltage Shutdown Event Fault Protection Timer

Yes

Earth Fault Event Response ConfigurationActivate Hard Shutdown Condition

Earth Fault Event Audible Alert Yes

Earth Fault Event Breaker #1 Trip No

Earth Fault Event Breaker #2 Trip No

Page 25 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 26: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Generator Winding #1 High Temperature Warning Event Response Configuration

Activate Warning Condition

Generator Winding #1 High Temperature Warning Event Audible Alert

Yes

Generator Winding #1 High Temperature Warning Event Breaker #1 Trip

No

Generator Winding #1 High Temperature Warning Event Breaker #2 Trip

No

Generator Winding #1 High Temperature Warning Event Fault Protection Timer

No

Generator Winding #2 High Temperature Warning Event Response Configuration

Activate Warning Condition

Generator Winding #2 High Temperature Warning Event Audible Alert

Yes

Generator Winding #2 High Temperature Warning Event Breaker #1 Trip

No

Generator Winding #2 High Temperature Warning Event Breaker #2 Trip

No

Generator Winding #2 High Temperature Warning Event Fault Protection Timer

No

Generator Winding #3 High Temperature Warning Event Response Configuration

Activate Warning Condition

Generator Winding #3 High Temperature Warning Event Audible Alert

Yes

Generator Winding #3 High Temperature Warning Event Breaker #1 Trip

No

Generator Winding #3 High Temperature Warning Event Breaker #2 Trip

No

Generator Winding #3 High Temperature Warning Event Fault Protection Timer

No

Generator Winding #1 High Temperature Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Generator Winding #1 High Temperature Shutdown Event Audible Alert

Yes

Generator Winding #1 High Temperature Shutdown Event Breaker #1 Trip

No

Generator Winding #1 High Temperature Shutdown Event Breaker #2 Trip

No

Generator Winding #1 High Temperature Shutdown Event Fault Protection Timer

No

Generator Winding #2 High Temperature Shutdown Event Response Configuration

Data Invalid

Page 26 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 27: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Generator Winding #2 High Temperature Shutdown Event Audible Alert

Yes

Generator Winding #2 High Temperature Shutdown Event Breaker #1 Trip

No

Generator Winding #2 High Temperature Shutdown Event Breaker #2 Trip

No

Generator Winding #2 High Temperature Shutdown Event Fault Protection Timer

No

Generator Winding #3 High Temperature Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Generator Winding #3 High Temperature Shutdown Event Audible Alert

Yes

Generator Winding #3 High Temperature Shutdown Event Breaker #1 Trip

No

Generator Winding #3 High Temperature Shutdown Event Breaker #2 Trip

No

Generator Winding #3 High Temperature Shutdown Event Fault Protection Timer

No

High Ambient Air Temperature Warning Event Response Configuration

Activate Warning Condition

High Ambient Air Temperature Warning Event Audible Alert

Yes

High Ambient Air Temperature Warning Event Breaker #1 Trip

No

High Ambient Air Temperature Warning Event Breaker #2 Trip

No

High Ambient Air Temperature Warning Event Fault Protection Timer

No

High Ambient Air Temperature Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Ambient Air Temperature Shutdown Event Audible Alert

Yes

High Ambient Air Temperature Shutdown Event Breaker #1 Trip

No

High Ambient Air Temperature Shutdown Event Breaker #2 Trip

No

High Ambient Air Temperature Shutdown Event Fault Protection Timer

No

Low Ambient Air Temperature Warning Event Response Configuration

Activate Warning Condition

Low Ambient Air Temperature Warning Event Audible Alert

Yes

Page 27 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 28: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Low Ambient Air Temperature Warning Event Breaker #1 Trip

No

Low Ambient Air Temperature Warning Event Breaker #2 Trip

No

Low Ambient Air Temperature Shutdown Event Response Configuration

Disable Condition

Low Ambient Air Temperature Shutdown Event Audible Alert

No

Low Ambient Air Temperature Shutdown Event Breaker #1 Trip

No

Low Ambient Air Temperature Shutdown Event Breaker #2 Trip

No

Automatic Transfer Switch In Normal Position Event Response Configuration

Active Only Condition

Automatic Transfer Switch In Normal Position Event Audible Alert

No

Automatic Transfer Switch In Emergency Position Event Response Config

Active Only Condition

Automatic Transfer Switch In Emergency Position Event Audible Alert

No

High Battery Voltage Warning Event Response Configuration

Activate Warning Condition

High Battery Voltage Warning Event Audible Alert Yes

High Battery Voltage Warning Event Breaker #1 Trip No

High Battery Voltage Warning Event Breaker #2 Trip No

High Battery Voltage Shutdown Event Response Configuration

Activate Soft Shutdown Condition

High Battery Voltage Shutdown Event Audible Alert Yes

High Battery Voltage Shutdown Event Breaker #1 Trip No

High Battery Voltage Shutdown Event Breaker #2 Trip No

Low Battery Voltage Warning Event Response Configuration

Activate Warning Condition

Low Battery Voltage Warning Event Audible Alert Yes

Low Battery Voltage Warning Event Breaker #1 Trip No

Low Battery Voltage Warning Event Breaker #2 Trip No

Low Battery Voltage Warning Event Fault Protection Timer

No

Low Battery Charging System Voltage Warning Event Response Configuration

Disable Condition

Low Battery Charging System Voltage Warning Event Audible Alert

No

Page 28 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 29: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Low Battery Charging System Voltage Warning Event Breaker #1 Trip

No

Low Battery Charging System Voltage Warning Event Breaker #2 Trip

No

Low Battery Charging System Voltage Warning Event Fault Protection Timer

No

Generator Breaker Failure To Open Event Response Configuration

Activate Warning Condition

Generator Breaker Failure To Open Event Audible Alert Yes

Generator Breaker Failure To Open Event Breaker #1 Trip

No

Generator Breaker Failure To Open Event Breaker #2 Trip

No

Generator Breaker Failure To Close Event Response Configuration

Activate Hard Shutdown Condition

Generator Breaker Failure To Close Event Audible Alert Yes

Generator Breaker Failure To Close Event Breaker #1 Trip

No

Generator Breaker Failure To Close Event Breaker #2 Trip

No

Generator Breaker Open Event Response Configuration Active Only Condition

Generator Breaker Open Event Audible Alert No

Generator Breaker Closed Event Response Configuration Active Only Condition

Generator Breaker Closed Event Audible Alert No

Utility Breaker Failure To Open Event Response Configuration

Activate Hard Shutdown Condition

Utility Breaker Failure To Open Event Audible Alert Yes

Utility Breaker Failure To Open Event Breaker #1 Trip No

Utility Breaker Failure To Open Event Breaker #2 Trip No

Utility Breaker Failure To Close Event Response Configuration

Activate Warning Condition

Utility Breaker Failure To Close Event Audible Alert Yes

Utility Breaker Failure To Close Event Breaker #1 Trip No

Utility Breaker Failure To Close Event Breaker #2 Trip No

Utility Breaker Open Event Response Configuration Active Only Condition

Utility Breaker Open Event Audible Alert No

Utility Breaker Closed Event Response Configuration Active Only Condition

Utility Breaker Closed Event Audible Alert No

Emergency Shutdown Override Mode Active Warning Event Response Config

Activate Warning Condition

Page 29 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 30: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Emergency Shutdown Override Mode Active Warning Event Audible Alert

No

Engine In Cooldown Event Response Configuration Active Only Condition

Engine In Cooldown Event Audible Alert No

Engine Speed-Generator Output Freq Mismatch Warning Event Response Config

Activate Warning Condition

Engine Speed-Generator Output Freq Mismatch Warning Event Audible Alert

Yes

Engine Speed-Generator Output Freq Mismatch Warning Event Breaker #1 Trip

No

Engine Speed-Generator Output Freq Mismatch Warning Event Breaker #2 Trip

No

High Fire Extinguisher Pressure Warning Event Response Configuration

Activate Warning Condition

High Fire Extinguisher Pressure Warning Event Audible Alert

Yes

High Fire Extinguisher Pressure Warning Event Breaker #1 Trip

No

High Fire Extinguisher Pressure Warning Event Breaker #2 Trip

No

High Fire Extinguisher Pressure Shutdown Event Response Configuration

Activate Hard Shutdown Condition

High Fire Extinguisher Pressure Shutdown Event Audible Alert

Yes

High Fire Extinguisher Pressure Shutdown Event Breaker #1 Trip

No

High Fire Extinguisher Pressure Shutdown Event Breaker #2 Trip

No

Low Fire Extinguisher Pressure Warning Event Response Configuration

Activate Warning Condition

Low Fire Extinguisher Pressure Warning Event Audible Alert

Yes

Low Fire Extinguisher Pressure Warning Event Breaker #1 Trip

No

Low Fire Extinguisher Pressure Warning Event Breaker #2 Trip

No

Low Fire Extinguisher Pressure Warning Event Fault Protection Timer

No

Low Fire Extinguisher Pressure Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Low Fire Extinguisher Pressure Shutdown Event Audible Alert

Yes

Page 30 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 31: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Low Fire Extinguisher Pressure Shutdown Event Breaker #1 Trip

No

Low Fire Extinguisher Pressure Shutdown Event Breaker #2 Trip

No

Low Fire Extinguisher Pressure Shutdown Event Fault Protection Timer

No

Generator Control Not in Automatic Warning Event Response Configuration

Activate Warning Condition

Generator Control Not in Automatic Warning Event Audible Alert

Yes

Generator Breaker Locked Out Warning Event Response Configuration

Warning & Active Only Condition

Generator Breaker Locked Out Warning Event Audible Alert

Yes

Generator Breaker Locked Out Warning Event Breaker #1 Trip

No

Generator Breaker Locked Out Warning Event Breaker #2 Trip

No

Utility Breaker Locked Out Warning Event Response Configuration

Disable Condition

Utility Breaker Locked Out Warning Event Audible Alert No

Utility Breaker Locked Out Warning Event Loss of Utility No

Utility Breaker Locked Out Warning Event Breaker #1 Trip

No

Utility Breaker Locked Out Warning Event Breaker #2 Trip

No

Loss of Utility Event Response ConfigurationWarning & Active Only Condition

Loss of Utility Event Audible Alert Yes

Utility to Generator Transfer Failure Warning Event Response Configuration

Activate Warning Condition

Utility to Generator Transfer Failure Warning Event Audible Alert

Yes

Utility to Generator Transfer Failure Warning Event Breaker #1 Trip

No

Utility to Generator Transfer Failure Warning Event Breaker #2 Trip

No

Utility to Generator Transfer Failure Shutdown Event Response Configuration

Data Invalid

Utility to Generator Transfer Failure Shutdown Event Audible Alert

Yes

Utility to Generator Transfer Failure Shutdown Event

Page 31 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 32: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Breaker #1 Trip Yes

Utility to Generator Transfer Failure Shutdown Event Breaker #2 Trip

No

Generator to Utility Transfer Failure Warning Event Response Configuration

Activate Warning Condition

Generator to Utility Transfer Failure Warning Event Audible Alert

Yes

Generator to Utility Transfer Failure Warning Event Breaker #1 Trip

No

Generator to Utility Transfer Failure Warning Event Breaker #2 Trip

No

Earth Leakage Event Response ConfigurationActivate Hard Shutdown Condition

Earth Leakage Event Audible Alert Yes

Earth Leakage Event Breaker #1 Trip No

Earth Leakage Event Breaker #2 Trip No

Utility Breaker System Fault Event Response Configuration

Disabled or Not Installed

Utility Breaker System Fault Event Audible Alert Disabled or Not Installed

Utility Breaker System Fault Event Breaker #1 Trip Disabled or Not Installed

Utility Breaker System Fault Event Breaker #2 Trip Disabled or Not Installed

Custom Event #1 High Warning Event Response Configuration

Activate Warning Condition

Custom Event #1 High Warning Event Audible Alert Yes

Custom Event #1 High Warning Event Breaker #1 Trip No

Custom Event #1 High Warning Event Breaker #2 Trip No

Custom Event #1 High Warning Event Fault Protection Timer

No

Custom Event #1 High Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #1 High Shutdown Event Audible Alert Yes

Custom Event #1 High Shutdown Event Breaker #1 Trip No

Custom Event #1 High Shutdown Event Breaker #2 Trip No

Custom Event #1 High Shutdown Event Fault Protection Timer

No

Custom Event #1 Low Warning Event Response Configuration

Activate Warning Condition

Custom Event #1 Low Warning Event Audible Alert Yes

Custom Event #1 Low Warning Event Breaker #1 Trip No

Custom Event #1 Low Warning Event Breaker #2 Trip No

Page 32 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 33: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Custom Event #1 Low Warning Event Fault Protection Timer

No

Custom Event #1 Low Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #1 Low Shutdown Event Audible Alert Yes

Custom Event #1 Low Shutdown Event Breaker #1 Trip No

Custom Event #1 Low Shutdown Event Breaker #2 Trip No

Custom Event #1 Low Shutdown Event Fault Protection Timer

No

Custom Event #1 Condition Exists Event Response Configuration

Active Only Condition

Custom Event #1 Condition Exists Event Audible Alert No

Custom Event #1 Condition Exists Event Loss of Utility No

Custom Event #1 Condition Exists Event Breaker #1 Trip No

Custom Event #1 Condition Exists Event Breaker #2 Trip No

Custom Event #1 Condition Exists Event Fault Protection Timer

No

Custom Event #2 High Warning Event Response Configuration

Activate Warning Condition

Custom Event #2 High Warning Event Audible Alert Yes

Custom Event #2 High Warning Event Breaker #1 Trip No

Custom Event #2 High Warning Event Breaker #2 Trip No

Custom Event #2 High Warning Event Fault Protection Timer

No

Custom Event #2 High Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #2 High Shutdown Audible Alert Yes

Custom Event #2 High Shutdown Breaker #1 Trip No

Custom Event #2 High Shutdown Breaker #2 Trip No

Custom Event #2 High Shutdown Fault Protection Timer No

Custom Event #2 Low Warning Event Response Configuration

Activate Warning Condition

Custom Event #2 Low Warning Audible Alert Yes

Custom Event #2 Low Warning Breaker #1 Trip No

Custom Event #2 Low Warning Breaker #2 Trip No

Custom Event #2 Low Warning Fault Protection Timer No

Custom Event #2 Low Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #2 Low Shutdown Event Audible Alert Yes

Custom Event #2 Low Shutdown Event Breaker #1 Trip No

Page 33 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 34: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Custom Event #2 Low Shutdown Event Breaker #2 Trip No

Custom Event #2 Low Shutdown Event Fault Protection Timer

No

Custom Event #2 Condition Exists Event Response Configuration

Active Only Condition

Custom Event #2 Condition Exists Event Audible Alert No

Custom Event #2 Condition Exists Event Loss of Utility No

Custom Event #2 Condition Exists Event Breaker #1 Trip No

Custom Event #2 Condition Exists Event Breaker #2 Trip No

Custom Event #2 Condition Exists Event Fault Protection Timer

No

Custom Event #3 High Warning Event Response Configuration

Activate Warning Condition

Custom Event #3 High Warning Event Audible Alert Yes

Custom Event #3 High Warning Event Breaker #1 Trip No

Custom Event #3 High Warning Event Breaker #2 Trip No

Custom Event #3 High Warning Event Fault Protection Timer

No

Custom Event #3 High Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #3 High Shutdown Event Audible Alert Yes

Custom Event #3 High Shutdown Event Breaker #1 Trip No

Custom Event #3 High Shutdown Event Breaker #2 Trip No

Custom Event #3 High Shutdown Event Fault Protection Timer

No

Custom Event #3 Low Warning Event Response Configuration

Activate Warning Condition

Custom Event #3 Low Warning Event Audible Alert Yes

Custom Event #3 Low Warning Event Breaker #1 Trip No

Custom Event #3 Low Warning Event Breaker #2 Trip No

Custom Event #3 Low Warning Event Fault Protection Timer

No

Custom Event #3 Low Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #3 Low Shutdown Event Audible Alert Yes

Custom Event #3 Low Shutdown Event Breaker #1 Trip No

Custom Event #3 Low Shutdown Event Breaker #2 Trip No

Custom Event #3 Low Shutdown Event Fault Protection Timer

No

Custom Event #3 Condition Exists Event Response Active Only Condition

Page 34 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 35: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Configuration

Custom Event #3 Condition Exists Event Audible Alert No

Custom Event #3 Condition Exists Event Loss of Utility No

Custom Event #3 Condition Exists Event Breaker #1 Trip No

Custom Event #3 Condition Exists Event Breaker #2 Trip No

Custom Event #3 Condition Exists Event Fault Protection Timer

No

Custom Event #4 High Warning Event Response Configuration

Activate Warning Condition

Custom Event #4 High Warning Event Audible Alert Yes

Custom Event #4 High Warning Event Breaker #1 Trip No

Custom Event #4 High Warning Event Breaker #2 Trip No

Custom Event #4 High Warning Event Fault Protection Timer

No

Custom Event #4 High Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #4 High Shutdown Event Audible Alert Yes

Custom Event #4 High Shutdown Event Breaker #1 Trip No

Custom Event #4 High Shutdown Event Breaker #2 Trip No

Custom Event #4 High Shutdown Event Fault Protection Timer

No

Custom Event #4 Low Warning Event Response Configuration

Activate Warning Condition

Custom Event #4 Low Warning Event Audible Alert Yes

Custom Event #4 Low Warning Event Breaker #1 Trip No

Custom Event #4 Low Warning Event Breaker #2 Trip No

Custom Event #4 Low Warning Event Fault Protection Timer

No

Custom Event #4 Low Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #4 Low Shutdown Event Audible Alert Yes

Custom Event #4 Low Shutdown Event Breaker #1 Trip No

Custom Event #4 Low Shutdown Event Breaker #2 Trip No

Custom Event #4 Low Shutdown Event Fault Protection Timer

No

Custom Event #4 Condition Exists Event Response Configuration

Active Only Condition

Custom Event #4 Condition Exists Event Audible Alert No

Custom Event #4 Condition Exists Event Loss of Utility No

Custom Event #4 Condition Exists Event Breaker #1 Trip No

Page 35 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 36: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Custom Event #4 Condition Exists Event Breaker #2 Trip No

Custom Event #4 Condition Exists Event Fault Protection Timer

No

Custom Event #5 High Warning Event Response Configuration

Activate Warning Condition

Custom Event #5 High Warning Event Audible Alert Yes

Custom Event #5 High Warning Event Breaker #1 Trip No

Custom Event #5 High Warning Event Breaker #2 Trip No

Custom Event #5 High Warning Event Fault Protection Timer

No

Custom Event #5 High Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #5 High Shutdown Event Audible Alert Yes

Custom Event #5 High Shutdown Event Breaker #1 Trip No

Custom Event #5 High Shutdown Event Breaker #2 Trip No

Custom Event #5 High Shutdown Event Fault Protection Timer

No

Custom Event #5 Low Warning Event Response Configuration

Activate Warning Condition

Custom Event #5 Low Warning Event Audible Alert Yes

Custom Event #5 Low Warning Event Breaker #1 Trip No

Custom Event #5 Low Warning Event Breaker #2 Trip No

Custom Event #5 Low Warning Event Fault Protection Timer

No

Custom Event #5 Low Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #5 Low Shutdown Event Audible Alert Yes

Custom Event #5 Low Shutdown Event Breaker #1 Trip No

Custom Event #5 Low Shutdown Event Breaker #2 Trip No

Custom Event #5 Low Shutdown Event Fault Protection Timer

No

Custom Event #5 Condition Exists Event Response Configuration

Active Only Condition

Custom Event #5 Condition Exists Event Audible Alert No

Custom Event #5 Condition Exists Event Loss of Utility No

Custom Event #5 Condition Exists Event Breaker #1 Trip No

Custom Event #5 Condition Exists Event Breaker #2 Trip No

Custom Event #5 Condition Exists Event Fault Protection Timer

No

Custom Event #6 High Warning Event Response Activate Warning Condition

Page 36 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 37: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Configuration

Custom Event #6 High Warning Event Audible Alert Yes

Custom Event #6 High Warning Event Breaker #1 Trip No

Custom Event #6 High Warning Event Breaker #2 Trip No

Custom Event #6 High Warning Event Fault Protection Timer

No

Custom Event #6 High Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #6 High Shutdown Event Audible Alert Yes

Custom Event #6 High Shutdown Event Breaker #1 Trip No

Custom Event #6 High Shutdown Event Breaker #2 Trip No

Custom Event #6 High Shutdown Event Fault Protection Timer

No

Custom Event #6 Low Warning Event Response Configuration

Activate Warning Condition

Custom Event #6 Low Warning Event Audible Alert Yes

Custom Event #6 Low Warning Event Breaker #1 Trip No

Custom Event #6 Low Warning Event Breaker #2 Trip No

Custom Event #6 Low Warning Event Fault Protection Timer

No

Custom Event #6 Low Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #6 Low Shutdown Event Audible Alert Yes

Custom Event #6 Low Shutdown Event Breaker #1 Trip No

Custom Event #6 Low Shutdown Event Breaker #2 Trip No

Custom Event #6 Low Shutdown Event Fault Protection Timer

No

Custom Event #6 Condition Exists Event Response Configuration

Active Only Condition

Custom Event #6 Condition Exists Event Audible Alert No

Custom Event #6 Condition Exists Event Loss of Utility No

Custom Event #6 Condition Exists Event Breaker #1 Trip No

Custom Event #6 Condition Exists Event Breaker #2 Trip No

Custom Event #6 Condition Exists Event Fault Protection Timer

No

Custom Event #7 High Warning Event Response Configuration

Activate Warning Condition

Custom Event #7 High Warning Event Audible Alert Yes

Custom Event #7 High Warning Event Breaker #1 Trip No

Custom Event #7 High Warning Event Breaker #2 Trip No

Page 37 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 38: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Custom Event #7 High Warning Event Fault Protection Timer

No

Custom Event #7 High Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #7 High Shutdown Event Audible Alert Yes

Custom Event #7 High Shutdown Event Breaker #1 Trip No

Custom Event #7 High Shutdown Event Breaker #2 Trip No

Custom Event #7 High Shutdown Event Fault Protection Timer

No

Custom Event #7 Low Warning Event Response Configuration

Activate Warning Condition

Custom Event #7 Low Warning Event Audible Alert Yes

Custom Event #7 Low Warning Event Breaker #1 Trip No

Custom Event #7 Low Warning Event Breaker #2 Trip No

Custom Event #7 Low Warning Event Fault Protection Timer

No

Custom Event #7 Low Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #7 Low Shutdown Event Audible Alert Yes

Custom Event #7 Low Shutdown Event Breaker #1 Trip No

Custom Event #7 Low Shutdown Event Breaker #2 Trip No

Custom Event #7 Low Shutdown Event Fault Protection Timer

No

Custom Event #7 Condition Exists Event Response Configuration

Active Only Condition

Custom Event #7 Condition Exists Event Audible Alert No

Custom Event #7 Condition Exists Event Loss of Utility No

Custom Event #7 Condition Exists Event Breaker #1 Trip No

Custom Event #7 Condition Exists Event Breaker #2 Trip No

Custom Event #7 Condition Exists Event Fault Protection Timer

No

Custom Event #8 High Warning Event Response Configuration

Activate Warning Condition

Custom Event #8 High Warning Event Audible Alert Yes

Custom Event #8 High Warning Event Breaker #1 Trip No

Custom Event #8 High Warning Event Breaker #2 Trip No

Custom Event #8 High Warning Event Fault Protection Timer

No

Custom Event #8 High Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Page 38 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 39: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Custom Event #8 High Shutdown Event Audible Alert Yes

Custom Event #8 High Shutdown Event Breaker #1 Trip No

Custom Event #8 High Shutdown Event Breaker #2 Trip No

Custom Event #8 High Shutdown Event Fault Protection Timer

No

Custom Event #8 Low Warning Event Response Configuration

Activate Warning Condition

Custom Event #8 Low Warning Event Audible Alert Yes

Custom Event #8 Low Warning Event Breaker #1 Trip No

Custom Event #8 Low Warning Event Breaker #2 Trip No

Custom Event #8 Low Warning Event Fault Protection Timer

No

Custom Event #8 Low Shutdown Event Response Configuration

Activate Hard Shutdown Condition

Custom Event #8 Low Shutdown Event Audible Alert Yes

Custom Event #8 Low Shutdown Event Breaker #1 Trip No

Custom Event #8 Low Shutdown Event Breaker #2 Trip No

Custom Event #8 Low Shutdown Event Fault Protection Timer

No

Custom Event #8 Condition Exists Event Response Configuration

Active Only Condition

Custom Event #8 Condition Exists Event Audible Alert No

Custom Event #8 Condition Exists Event Loss of Utility No

Custom Event #8 Condition Exists Event Breaker #1 Trip No

Custom Event #8 Condition Exists Event Breaker #2 Trip No

Custom Event #8 Condition Exists Event Fault Protection Timer

No

Event Warning Condition Response Auto Reset Enable Status

Enabled

Event Audible Alert Response Auto Reset Enable Status Enabled

Event Loss Of Utility Response Auto Reset Enable Status Enabled

Event Breaker #1 Trip Response Auto Reset Enable Status

Enabled

Event Breaker #2 Trip Response Auto Reset Enable Status

Enabled

Generator Connection Configuration Wye (or Star) Connection

Generator Potential Transformer Primary Winding Rating 1 Volts

Generator Potential Transformer Secondary Winding Rating

1 Volts

Generator Current Transformer Primary Winding Rating 1500 Amps

Page 39 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 40: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Generator Current Transformer Secondary Winding Rating

5 Amps

Number of Generator Poles 4 Poles

Generator Rated Frequency 60 Hz

Generator Rated Voltage 480 Volts

Generator Rated Power 800 kW

Generator Rated Apparent Power 1035 kVA

Customer Password Security Level to Reset Generator Energy Meters

3-Factory, Single Use

Generator Breaker Closing Pulse Active Time Disabled or Not Installed sec

Generator Breaker Closing Pulse Rest Interval Disabled or Not Installed sec

Generator Breaker Maximum Closing Time Disabled or Not Installed sec

Generator Breaker Maximum Opening Time Disabled or Not Installed sec

Generator Breaker Lockout Configuration Disabled or Not Installed

Generator Breaker Type Configuration Disabled or Not Installed

Automatic Generator Breaker Control Source Configuration

Disabled or Not Installed

Generator Definite Time Overcurrent Warning Event Percentage Threshold

110 %

Generator Inverse Time Overcurrent Shutdown Event Time Multiplier

0.27 sec

Generator Definite Time Overcurrent Shutdown Event Percentage Threshold

125 %

Generator Definite Time Overcurrent Shutdown Event Notification Delay Time

10.0 sec

Generator Over Frequency Warning Event Percentage Threshold

105.0 %

Generator Over Frequency Warning Event Notification Delay Time

10 sec

Generator Over Frequency Shutdown Event Percentage Threshold

110.0 %

Generator Over Frequency Shutdown Event Notification Delay Time

10 sec

Generator Under Frequency Warning Event Percentage Threshold

95.0 %

Generator Under Frequency Warning Event Notification Delay Time

10 sec

Generator Under Frequency Shutdown Event Percentage Threshold

90.0 %

Generator Under Frequency Shutdown Event Notification Delay Time

15 sec

Page 40 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 41: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Generator Over Voltage Warning Event Percentage Threshold

110 %

Generator Over Voltage Warning Event Notification Delay Time

10 sec

Generator Over Voltage Shutdown Event Percentage Threshold

110 %

Generator Over Voltage Shutdown Event Notification Delay Time

10 sec

Generator Under Voltage Warning Event Percentage Threshold

95 %

Generator Under Voltage Warning Event Notification Delay Time

10 sec

Generator Under Voltage Shutdown Event Percentage Threshold

90 %

Generator Under Voltage Shutdown Event Notification Delay Time

15 sec

Maximum Engine Speed Bias 400 rpm

Generator Nominal Output Frequency 60.0 Hz

Programmable Cycle Timer #1 Activation Day - Sunday Deactivate

Programmable Cycle Timer #1 Activation Day - Monday Deactivate

Programmable Cycle Timer #1 Activation Day - Tuesday Deactivate

Programmable Cycle Timer #1 Activation Day - Wednesday

Deactivate

Programmable Cycle Timer #1 Activation Day - Thursday Deactivate

Programmable Cycle Timer #1 Activation Day - Friday Deactivate

Programmable Cycle Timer #1 Activation Day - Saturday Deactivate

Programmable Cycle Timer #1 Activation Start Time 0 min

Programmable Cycle Timer #1 Active Time 1 min

Programmable Cycle Timer #1 Output #1 Activation Configuration

Inactive

Programmable Cycle Timer #1 Output #2 Activation Configuration

Inactive

Programmable Cycle Timer #2 Activation Day - Sunday Deactivate

Programmable Cycle Timer #2 Activation Day - Monday Deactivate

Programmable Cycle Timer #2 Activation Day - Tuesday Deactivate

Programmable Cycle Timer #2 Activation Day - Wednesday

Deactivate

Programmable Cycle Timer #2 Activation Day - Thursday Deactivate

Programmable Cycle Timer #2 Activation Day - Friday Deactivate

Programmable Cycle Timer #2 Activation Day - Saturday Deactivate

Page 41 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 42: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Programmable Cycle Timer #2 Activation Start Time 0 min

Programmable Cycle Timer #2 Active Time 1 min

Programmable Cycle Timer #2 Output #1 Activation Configuration

Inactive

Programmable Cycle Timer #2 Output #2 Activation Configuration

Inactive

Programmable Cycle Timer #3 Activation Day - Sunday Deactivate

Programmable Cycle Timer #3 Activation Day - Monday Deactivate

Programmable Cycle Timer #3 Activation Day - Tuesday Deactivate

Programmable Cycle Timer #3 Activation Day - Wednesday

Deactivate

Programmable Cycle Timer #3 Activation Day - Thursday Deactivate

Programmable Cycle Timer #3 Activation Day - Friday Deactivate

Programmable Cycle Timer #3 Activation Day - Saturday Deactivate

Programmable Cycle Timer #3 Activation Start Time 0 min

Programmable Cycle Timer #3 Active Time 1 min

Programmable Cycle Timer #3 Output #1 Activation Configuration

Inactive

Programmable Cycle Timer #3 Output #2 Activation Configuration

Inactive

Programmable Cycle Timer #4 Activation Day - Sunday Deactivate

Programmable Cycle Timer #4 Activation Day - Monday Deactivate

Programmable Cycle Timer #4 Activation Day - Tuesday Deactivate

Programmable Cycle Timer #4 Activation Day - Wednesday

Deactivate

Programmable Cycle Timer #4 Activation Day - Thursday Deactivate

Programmable Cycle Timer #4 Activation Day - Friday Deactivate

Programmable Cycle Timer #4 Activation Day - Saturday Deactivate

Programmable Cycle Timer #4 Activation Start Time 0 min

Programmable Cycle Timer #4 Active Time 1 min

Programmable Cycle Timer #4 Output #1 Activation Configuration

Inactive

Programmable Cycle Timer #4 Output #2 Activation Configuration

Inactive

Programmable Cycle Timer #5 Activation Day - Sunday Deactivate

Programmable Cycle Timer #5 Activation Day - Monday Deactivate

Programmable Cycle Timer #5 Activation Day - Tuesday Deactivate

Programmable Cycle Timer #5 Activation Day - Wednesday

Deactivate

Programmable Cycle Timer #5 Activation Day - Thursday Deactivate

Page 42 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 43: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Programmable Cycle Timer #5 Activation Day - Friday Deactivate

Programmable Cycle Timer #5 Activation Day - Saturday Deactivate

Programmable Cycle Timer #5 Activation Start Time 0 min

Programmable Cycle Timer #5 Active Time 1 min

Programmable Cycle Timer #5 Output #1 Activation Configuration

Inactive

Programmable Cycle Timer #5 Output #2 Activation Configuration

Inactive

Programmable Cycle Timer #6 Activation Day - Sunday Deactivate

Programmable Cycle Timer #6 Activation Day - Monday Deactivate

Programmable Cycle Timer #6 Activation Day - Tuesday Deactivate

Programmable Cycle Timer #6 Activation Day - Wednesday

Deactivate

Programmable Cycle Timer #6 Activation Day - Thursday Deactivate

Programmable Cycle Timer #6 Activation Day - Friday Deactivate

Programmable Cycle Timer #6 Activation Day - Saturday Deactivate

Programmable Cycle Timer #6 Activation Start Time 0 min

Programmable Cycle Timer #6 Active Time 1 min

Programmable Cycle Timer #6 Output #1 Activation Configuration

Inactive

Programmable Cycle Timer #6 Output #2 Activation Configuration

Inactive

Programmable Cycle Timer #7 Activation Day - Sunday Deactivate

Programmable Cycle Timer #7 Activation Day - Monday Deactivate

Programmable Cycle Timer #7 Activation Day - Tuesday Deactivate

Programmable Cycle Timer #7 Activation Day - Wednesday

Deactivate

Programmable Cycle Timer #7 Activation Day - Thursday Deactivate

Programmable Cycle Timer #7 Activation Day - Friday Deactivate

Programmable Cycle Timer #7 Activation Day - Saturday Deactivate

Programmable Cycle Timer #7 Activation Start Time 0 min

Programmable Cycle Timer #7 Active Time 1 min

Programmable Cycle Timer #7 Output #1 Activation Configuration

Inactive

Programmable Cycle Timer #7 Output #2 Activation Configuration

Inactive

Programmable Cycle Timer #8 Activation Day of Week Unavailable

Programmable Cycle Timer #8 Activation Start Time Unavailable min

Programmable Cycle Timer #8 Active Time Unavailable min

Programmable Cycle Timer #8 Output #1 Activation

Page 43 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 44: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Configuration Unavailable

Programmable Cycle Timer #8 Output #2 Activation Configuration

Unavailable

Programmable Cycle Timer #9 Activation Day of Week Unavailable

Programmable Cycle Timer #9 Activation Start Time Unavailable min

Programmable Cycle Timer #9 Active Time Unavailable min

Programmable Cycle Timer #9 Output #1 Activation Configuration

Unavailable

Programmable Cycle Timer #9 Output #2 Activation Configuration

Unavailable

Programmable Cycle Timer #10 Activation Day of Week Unavailable

Programmable Cycle Timer #10 Activation Start Time Unavailable min

Programmable Cycle Timer #10 Active Time Unavailable min

Programmable Cycle Timer #10 Output #1 Activation Configuration

Unavailable

Programmable Cycle Timer #10 Output #2 Activation Configuration

Unavailable

Programmable Cycle Timer #11 Activation Day of Week Unavailable

Programmable Cycle Timer #11 Activation Start Time Unavailable min

Programmable Cycle Timer #11 Active Time Unavailable min

Programmable Cycle Timer #11 Output #1 Activation Configuration

Unavailable

Programmable Cycle Timer #11 Output #2 Activation Configuration

Unavailable

Programmable Cycle Timer #12 Activation Day of Week Unavailable

Programmable Cycle Timer #12 Activation Start Time Unavailable min

Programmable Cycle Timer #12 Active Time Unavailable min

Programmable Cycle Timer #12 Output #1 Activation Configuration

Unavailable

Programmable Cycle Timer #12 Output #2 Activation Configuration

Unavailable

Programmable Cycle Timer #13 Activation Day of Week Unavailable

Programmable Cycle Timer #13 Activation Start Time Unavailable min

Programmable Cycle Timer #13 Active Time Unavailable min

Programmable Cycle Timer #13 Output #1 Activation Configuration

Unavailable

Programmable Cycle Timer #13 Output #2 Activation Configuration

Unavailable

Programmable Cycle Timer #14 Activation Day of Week Unavailable

Programmable Cycle Timer #14 Activation Start Time Unavailable min

Page 44 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 45: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Programmable Cycle Timer #14 Active Time Unavailable min

Programmable Cycle Timer #14 Output #1 Activation Configuration

Unavailable

Programmable Cycle Timer #14 Output #2 Activation Configuration

Unavailable

Electronic Control Module Reduced Power Mode Enable Status

Disabled

Electronic Control Module Reduced Power Mode Delay Time

30 min

Relay Output #1 Active State Configuration High

Relay Output #2 Active State Configuration High

Relay Output #3 Active State Configuration High

Relay Output #4 Active State Configuration High

Relay Output #5 Active State Configuration High

Relay Output #6 Active State Configuration High

Relay Output #7 Active State Configuration High

Relay Output #8 Active State Configuration High

Maintenance Level 1 Cycle Interval Hours 500 hours

Maintenance Level 1 Cycle Interval Days 180

Customer Password Security Level to Reset Service Maintenance Interval

0-No Security

Spare Analog Input Enable Status Disabled

Spare Analog Input Type Configuration Pressure

Spare Analog Input Suspect Parameter Number Engine Oil Temperature

Spare Analog Input High Warning Event Percentage Threshold

99 %

Spare Analog Input High Temperature Warning Event Threshold

230Deg F

Spare Analog Input High Pressure Warning Event Threshold

131 psi

Spare Analog Input High Warning Event Notification Delay Time

2 sec

Spare Analog Input High Shutdown Event Percentage Threshold

100 %

Spare Analog Input High Temperature Shutdown Event Threshold

239Deg F

Spare Analog Input High Pressure Shutdown Event Threshold

146 psi

Spare Analog Input High Shutdown Event Notification Delay Time

10 sec

Spare Analog Input Low Warning Event Percentage

Page 45 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 46: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Threshold 10 %

Spare Analog Input Low Temperature Warning Event Threshold

68Deg F

Spare Analog Input Low Pressure Warning Event Threshold

15 psi

Spare Analog Input Low Warning Event Notification Delay Time

15 sec

Spare Analog Input Low Shutdown Event Percentage Threshold

5 %

Spare Analog Input Low Temperature Shutdown Event Threshold

32Deg F

Spare Analog Input Low Pressure Shutdown Event Threshold

11 psi

Spare Analog Input Low Shutdown Event Notification Delay Time

30 sec

Spare Analog Input Sensor Configuration Code Map #1

Programmable Trip Point Function #1 Trigger Condition Trip Above Threshold

Programmable Trip Point Function #1 Percentage Threshold

90 %

Programmable Trip Point Function #1 Hysteresis Percentage

5 %

Programmable Trip Point Function #1 Trip Activation Delay Time

10 sec

Programmable Trip Point Function #1 Trip Deactivation Delay Time

1 sec

Programmable Trip Point Function #2 Trigger Condition Disabled or Not Installed

Programmable Trip Point Function #2 Percentage Threshold

-1 %

Programmable Trip Point Function #2 Hysteresis Percentage

Disabled or Not Installed %

Programmable Trip Point Function #2 Trip Activation Delay Time

Disabled or Not Installed sec

Programmable Trip Point Function #2 Trip Deactivation Delay Time

Disabled or Not Installed sec

Programmable Trip Point Function #3 Trigger Condition Disabled or Not Installed

Programmable Trip Point Function #3 Percentage Threshold

-1 %

Programmable Trip Point Function #3 Hysteresis Percentage

Disabled or Not Installed %

Programmable Trip Point Function #3 Trip Activation Delay Time

Disabled or Not Installed sec

Page 46 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 47: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

C27 Genset (MJE00283)

Programmable Trip Point Function #3 Trip Deactivation Delay Time

Disabled or Not Installed sec

Programmable Trip Point Function #4 Trigger Condition Disabled or Not Installed

Programmable Trip Point Function #4 Percentage Threshold

-1 %

Programmable Trip Point Function #4 Hysteresis Percentage

Disabled or Not Installed %

Programmable Trip Point Function #4 Trip Activation Delay Time

Disabled or Not Installed sec

Programmable Trip Point Function #4 Trip Deactivation Delay Time

Disabled or Not Installed sec

Generator/Utility Automatic Transfer Enable Status Disabled or Not Installed

Loss of Utility Event Notification Delay Time Disabled or Not Installed sec

Utility to Generator Transfer Delay Time Disabled or Not Installed sec

Generator to Utility Transfer Delay Time Disabled or Not Installed min

Generator to Utility Fast Transfer Delay Time Disabled or Not Installed sec

Utility to Generator Transfer Failure Warning Event Threshold

Disabled or Not Installed sec

Utility to Generator Transfer Failure Shutdown Event Threshold

Disabled or Not Installed sec

Generator to Utility Transfer Failure Warning Event Threshold

Disabled or Not Installed sec

Generator/Utility Automatic Transfer Unpowered Load Time

Disabled or Not Installed sec

Generator Ready to Load Threshold Percentage Disabled or Not Installed %

Generator Ready to Load Delay Time Disabled or Not Installed sec

Generator to Utility Transfer Mode Disabled or Not Installed

Utility Breaker Closing Pulse Active Time Disabled or Not Installed sec

Utility Breaker Closing Pulse Rest Interval Disabled or Not Installed sec

Utility Breaker Maximum Closing Time Disabled or Not Installed sec

Utility Breaker Maximum Opening Time Disabled or Not Installed sec

Utility Breaker Lockout Configuration Disabled or Not Installed

Engine Serial Number Not Programmed

Display Pressure Units Configuration psi

Display Temperature Units Configuration Degrees Farenheit

Display Volume Units Configuration liters

Parameter Value

Page 47 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 48: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Logged Diagnostic Codes [Diagnostic Clock = 4788.7388 hours] - C27 Genset (MJE00283)

Logged Event Codes [Diagnostic Clock = 4788.7388 hours] - C27 Genset (MJE00283)

Active Diagnostic Codes - C27 Genset (MJE00283)

Active Event Codes - C27 Genset (MJE00283)

Current Totals - C27 Genset (MJE00283)

Equipment ID NOT PROGRAMMED

Engine Serial Number MJE00283

ECM Serial Number 33566469JV

Software Group Part Number 3459194-00

Software Group Release Date MAY09

Software Group Description C27 MEUI ACERT A4

Code Description Occ. First Last

247- 9 SAE J1939 Data Link : Abnormal Update Rate 24 4713 4788

274- 3 Atmospheric Pressure Sensor : Voltage Above Normal 127 3871 4788

168- 1 Electrical System Voltage : Low 37 3953 4786

Code Description Occ. First Last

E390 (1) Fuel Filter Restriction 6 4768 4788

Code Description

274- 3 Atmospheric Pressure Sensor : Voltage Above Normal

Code Description

No Active Events

Description Value Unit

Total Fuel 86389 gal

Total Time 4788 hours

Engine Starts 795

Page 48 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 49: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Configuration - C27 Genset (MJE00283)

Average Fuel Rate Based Percent Engine Load Factor 31 %

Description Value Unit

Equipment ID NOT PROGRAMMED

Engine Serial Number MJE00283

ECM Serial Number 33566469JV

Software Group Part Number 3459194-00

Software Group Release Date MAY09

Software Group Description C27 MEUI ACERT A4

Rating Number 4

Rated Frequency 60 Hz

Rated Engine Speed 1800 rpm

Rated Real Genset Power 800 kW

Rated Apparent Genset PowerUnavailable Parameter

Rating Configuration Low Emissions

Test Spec 0K74900K7925

Engine Acceleration Rate 350 rpm/s

Low Idle Speed 1200 rpm

Engine Speed Droop 3.0 %

Engine State Control Input Configuration CAN Input

Remote Throttle Control Min Speed 125 rpm

Remote Throttle Control Max Speed 125 rpm

Cooldown Speed 1800 rpm

Cooldown Duration 5 min

Engine Pre-Lube Duration 0 sec

Crank Duration 30 sec

Maximum Number of Crank Cycles 5

Crank Terminate RPM 400 rpm

Droop Mode Selection Isochronous

Ether Control Disabled

Desired Speed Input Configuration CAN Input

Secondary Desired Speed Input Configuration CAN Input

Coolant Level Sensor Installed

Droop/Isochronous Switch Enable Disabled

Emergency Shutdown Override Switch Installation Status Not Installed

Page 49 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 50: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Lifetime: Time vs Engine Coolant Temperature - C27 Genset (MJE00283)

Lifetime: Time vs Inlet Air Temperature - C27 Genset (MJE00283)

Emergency Shutdown Override Input Configuration Switch to Ground

Remote Emergency Stop (E-Stop) Switch Input Type Configuration

Normally Open

Air Intake Shutoff Detection Installation Status Not Installed

Engine Oil Temperature Sensor Installation Status Installed

Governor Gain Factor #1 10000

Governor Minimum Stability Factor #1 600

Governor Maximum Stability Factor #1 3600

FLS 37

FTS -27

Total Tattletale 10

Engine Coolant Temperature( Deg F ) hours %

<122 55.70 1.17

122-130 12.90 0.27

131-139 14.05 0.29

140-148 16.10 0.34

149-157 17.25 0.36

158-166 19.50 0.41

167-175 1222.85 25.58

176-184 3422.00 71.58

185-193 0.05 0.00

194-202 0.05 0.00

203-211 0.15 0.00

212-220 0.20 0.00

221-229 0.00 0.00

230-238 0.00 0.00

239-247 0.00 0.00

>248 0.00 0.00

Inlet Air Temperature( Deg F ) hours %

<104 4.85 97.98

104-112 0.00 0.00

113-121 0.10 2.02

Page 50 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 51: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Lifetime: Time vs Boost Pressure - C27 Genset (MJE00283)

Lifetime: Total Occurrences vs Engine Speed - C27 Genset (MJE00283)

122-130 0.00 0.00

131-139 0.00 0.00

140-148 0.00 0.00

149-157 0.00 0.00

158-166 0.00 0.00

167-175 0.00 0.00

176-184 0.00 0.00

185-193 0.00 0.00

194-202 0.00 0.00

203-211 0.00 0.00

>212 0.00 0.00

Boost Pressure( psi ) hours %

<12 0.60 12.77

12-12 1.90 40.43

13-14 1.75 37.23

15-15 0.45 9.57

16-16 0.00 0.00

17-18 0.00 0.00

19-19 0.00 0.00

20-21 0.00 0.00

22-22 0.00 0.00

23-24 0.00 0.00

25-25 0.00 0.00

26-27 0.00 0.00

28-28 0.00 0.00

>29 0.00 0.00

Engine Speed( rpm ) %

<2500 0.00 0.00

2500-2599 0.00 0.00

2600-2699 0.00 0.00

2700-2799 0.00 0.00

2800-2899 0.00 0.00

Page 51 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 52: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Lifetime: Time vs Engine Speed And Engine Load Factor - C27 Genset (MJE00283)

Injector Trim Calibration - C27 Genset (MJE00283)

2900-2999 0.00 0.00

3000-3099 0.00 0.00

3100-3199 0.00 0.00

3200-3299 0.00 0.00

>3300 0.00 0.00

rpm <11001100-1299

1300-1499

1500-1699

1700-1899

1900-2099

2100-2299

>2300 Total

%

<50 0.04 0.06 0.01 0.00 98.81 0.00 0.00 0.00 98.92

50-60

0.00 0.00 0.00 0.00 0.92 0.00 0.00 0.00 0.92

60-70

0.00 0.00 0.00 0.00 0.02 0.00 0.00 0.00 0.02

70-80

0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

80-90

0.00 0.00 0.00 0.00 0.02 0.00 0.00 0.00 0.02

>90 0.00 0.00 0.00 0.04 0.07 0.00 0.00 0.00 0.11

Total 0.04 0.06 0.01 0.04 99.85 0.00 0.00 0.00 100.00

Injector Serial Number File Version

Injector1 000000005A5119357998 0

Injector2 000000005A51193574BB 0

Injector3 000000005A51193570A7 0

Injector4 000000005A51193567A7 0

Injector5 000000005A5119359849 0

Injector6 000000005A5119362863 0

Injector7 000000005A511936136D 0

Injector8 000000005A5119359764 0

Injector9 000000005A51193564AE 0

Injector10 000000005A5119361771 0

Injector11 000000005A51193561B5 0

Injector12 000000005A51193548A0 0

Page 52 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 53: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Monitoring System - C27 Genset (MJE00283)

Description State Trip Point Delay Time

Engine Overspeed

Least Severe (1) Always On 2200 rpm 0 sec

Most Severe (3) Always On 2300 rpm 0 sec

High Engine Coolant Temperature

Least Severe (1) Always On 221 Deg F 10 sec

Moderate Severity (2) Off 232 Deg F 10 sec

Most Severe (3) On 225 Deg F 10 sec

High Engine Inlet Air Temperature

Least Severe (1) Always On 167.0 Deg F 8 sec

Moderate Severity (2) Off 174.2 Deg F 8 sec

High Engine Oil Temperature

Least Severe (1) On 230 Deg F 15 sec

Moderate Severity (2) Off 239 Deg F 15 sec

Most Severe (3) Off 239 Deg F 15 sec

High Fuel Filter Pressure Restriction

Least Severe (1) On None 30 sec

Moderate Severity (2) Off None 28800 sec

Most Severe (3) Off None 28800 sec

High Fuel Pressure

Least Severe (1) On 127.6 psi 8 sec

Moderate Severity (2) Off 132.0 psi 10 sec

Most Severe (3) Off 133.4 psi 12 sec

High Fuel Temperature

Least Severe (1) Always On 194.0 Deg F 30 sec

Moderate Severity (2) Off 195.8 Deg F 10 sec

Most Severe (3) Off 197.6 Deg F 10 sec

Low Coolant Level

Least Severe (1) On None 10 sec

Moderate Severity (2) Off None 10 sec

Most Severe (3) Off None 10 sec

Low Engine Oil Pressure

Least Severe (1) Always On None 8 sec

Most Severe (3) Always On None 4 sec

Low Fuel Pressure

Least Severe (1) On 63 psi 10 sec

Page 53 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 54: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Digital Voltage Regulator

Logged Diagnostic Codes [Diagnostic Clock = Unavailable hours] - Digital Voltage Regulator

Logged Event Codes [Diagnostic Clock = Unavailable hours] - Digital Voltage Regulator

Active Diagnostic Codes - Digital Voltage Regulator

Active Event Codes - Digital Voltage Regulator

Configuration - Digital Voltage Regulator

Moderate Severity (2) Off 62 psi 10 sec

Most Severe (3) Off 60 psi 10 sec

Parameter Value

ECM Part Number 235-5725

ECM Serial Number 35366118GD

Software Group Part Number 2790916-00

Software Group Release Date Aug2005

Software Group Description Regulator Software

Code Description Occ. First Last

No Logged Diagnostic Codes

Code Description Occ. First Last

No Logged Events

Code Description

No Active Codes

Code Description

No Active Events

Description Value Unit

Page 54 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 55: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Voltage Regulator Power Input Frequency Configuration 240 Hz

Potential Transformer Primary Winding Rating 120 Volts

Potential Transformer Secondary Winding Rating 120 Volts

Current Transformer Primary Winding Rating 1500 Amps

Current Transformer Secondary Winding Rating 5 Amps

Generator Connection Configuration Three Phase

Generator Rated Frequency 60 Hz

Generator Rated Voltage 480 Volts

Generator Rated Current 1245 Amps

Voltage Regulator Loss of Sensing Shutdown Event Notification Delay Time

2.0 sec

Generator Rotating Diode Monitor Shutdown Event Current Threshold

2.0 Amps

Generator Reverse VAr Shutdown Event Percentage Threshold 40 %

Generator Reverse VAr Shutdown Event Notification Delay Time

0.5 sec

Generator Reverse VAr Shutdown Event Response Configuration

Activate Warning Condition

Generator Over Voltage Shutdown Event Percentage Threshold 135 %

Generator Over Voltage Shutdown Event Notification Delay Time

2 sec

Generator Over Voltage Shutdown Event Response Configuration

Activate Warning Condition

Generator Under Voltage Shutdown Event Percentage Threshold

60 %

Generator Under Voltage Shutdown Event Notification Delay Time

30 sec

Generator Under Voltage Shutdown Event Response Configuration

Activate Warning Condition

Voltage Regulator Over Excitation Shutdown Event Threshold 12.0 Amps

Voltage Regulator Over Excitation Shutdown Event Notification Delay Time

10.0 sec

Voltage Regulator Over Excitation Shutdown Event Notification Delay Type

Definite Time

Voltage Regulator Fault Reset Switch Diagnostic Response Configuration

Activate Warning Condition

Generator Nominal Output Voltage 480 Volts

Voltage Regulator Corner (Knee) Frequency 59.8 Hz

Voltage Regulator Deviation From Corner (Knee) Frequency 5.0 Hz

Voltage Regulator Volts/Hz Slope 1 2.0

Page 55 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...

Page 56: Caterpillar Electronic Technician 2012A v1.0 Product ... · PDF fileCaterpillar Electronic Technician 2012A v1.0 ... EMCP 3.2 2436- 1 Generator ... most severe (3) 1 35073507 2448-15

Voltage Regulator Volts/Hz Slope 2 2.0

Voltage Regulator Minimum Voltage Setpoint Percentage 50.0 %

Voltage Regulator Minimum Frequency Threshold 33.0 Hz

Voltage Regulator Maximum Droop Percentage 0.0 %

Voltage Regulator Voltage (IR) Compensation Percentage 0.0 %

Voltage Regulator Starting Time 5.0 sec

Voltage Regulator Starting Voltage Percent 10.0 %

Voltage Regulator Noise Filter Time Constant 0.00 sec

Voltage Regulation Proportional Gain Percentage 20.00 %

Voltage Regulation Integral Gain Percentage 60.00 %

Voltage Regulation Derivative Gain Percentage 3.00 %

Voltage Regulator Gain Setting Selection Number 7

Voltage Regulator Gain Setting Type Configuration User Defined

Voltage Regulator Loop Gain Percentage 5.00 %

Maximum Generator Voltage Output Bias Percentage Setpoint 15 %

Generator Nominal Output Power Factor 1.00

Voltage Regulator Nominal Reactive Power Percentage 0.0 %

Generator Power Factor Controller Loop Gain Percentage 0.30 %

Generator Power Factor Controller Integral Gain Percentage 0.50 %

Voltage Regulator Load Compensation Type Configuration Off

Voltage Regulator Power Factor/VAr Controller Mode Selection Reactive Power

Voltage Regulator Desired Power Factor Configuration Lagging

Generator VAr Controller Loop Gain Percentage 0.25 %

Generator VAr Controller Integral Gain Percentage 0.50 %

Page 56 of 56

6/9/2013file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici...