![Page 1: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/1.jpg)
I M
Catawba Nuclear Station
Polyethylene Piping Use forSafety Related Buried
Water PipingService
ATTACHMENT 2
![Page 2: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/2.jpg)
Agenda
* Meeting Purpose and Expectations* Polyethylene Piping Use by Catawba* Polyethylene Materials* Joining Polyethylene* Seismic Analysis* NDE Technique Evaluation* Relief Request* Overall Strategy for Service Water System* Questions (questions encouraged during
presentation)
![Page 3: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/3.jpg)
Meeting Purpose
*Nuclear service water systems havebeen designed using codes thatspecify only metallic materials.
*Polyethylene (HDPE) material hasdemonstrated superior corrosion andfouling resistance in non safety relatedcooling water system service.
![Page 4: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/4.jpg)
Meeting Purpose*Provide information on use ofPolyethylene Piping in non safetyrelated service water system atCatawba Nuclear Station
*Provide information on developmentof relief request for replacement ofsafety related piping with high densitypolyethylene (HDPE) in buried servicewater applications
![Page 5: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/5.jpg)
Meeting Expectations
Information presented in the 6-27-05meeting is expected to be useful forfuture review of Duke Relief Request.
*NRC comments and questions duringthe 6-27-05 meeting will be used tofocus efforts to develop and preparethe Duke Relief Request.
![Page 6: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/6.jpg)
Catawba Nuclear StationPolyethylene Pipe Use
* ', Iw-uItr
T
4
![Page 7: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/7.jpg)
Catawba Nuclear Station
* Located 19 miles southwest of Charlotte, NCon the shores of Lake Wylie
* Two Unit 1208 MW Westinghouse PWR
* Main condenser cooling provided by closedloop cooling tower system
* Commercial operation in 1985 &1986respectively
![Page 8: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/8.jpg)
Water Systems
* Nuclear Service Water System coonuclear safety related components.material: SAl 55, Class 1, KC 70 &plain carbon steels
ling toPiping
SAl 06 CS
* Low Pressure Service Water Systemsecondary cooling and cooling towermakeup. Piping material: A1 06 CS & AP15Lcarbon steel
* Both systems combined total approximately45,000-50,000 feet of piping
![Page 9: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/9.jpg)
LEGEND
LA s y tIE
* RC CONDENSER CIRCULATING WATER
RL CONVENTIONAL LOW PRESSURESERVICE WATER
* RN NUCLEAR SERVICE WATER ANDSTANDBY NUCLEAR SERVICE WATER
* RY EXTERIOR FIRE PROTECTIONSERVICE WATER
4
RI INtAKE'���:�ZZ7STRUITURE
.R1 WACE4TERW ') eJ[>.
0 M. ,.'.. ant: pv ... -I
PhDukae 41_VPowerB
CATAWBA NUCLEAR STATIONSERVICE WATER PROJECT
FIGURE D-1LbWG Li~ N ~RETumR N
SITE PLANFIGURE Q-1
,_ _,,._ _.,I
![Page 10: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/10.jpg)
~[Qp ertion
'ten'
![Page 11: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/11.jpg)
Service Water Problems
* Potential loss of adequate cooling due toflow restrictions
* Concern for Foreign Material Exclusion(FME) from the corrosion products,sedimentation, biological growth, andclams fouling components within thesystem
* Localized through wall pitting
![Page 12: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/12.jpg)
Problems Addressedby System Monitoring
* UT corrosion rate monitoring to addressstructural integrity issues
* Systems Engineers trend flows,temperatures, equipment performance,and set maintenance equipment PMfrequencies
![Page 13: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/13.jpg)
Problems Addressedby System Cleaning
* In 2000, CNS cleaned and inspected over 8,000feet of Nuclear Service Water System piping.
* The primary methods used for this operationwere "Pigging" and Hydrolazing (High PressureWash) with Turbo Vacuum Trucks to remove thedebris.
* Chemical treatment was added to the safetyrelated service water system after the cleaningto help control the biological growth. Currentlymonitoring actual results of treatment
![Page 14: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/14.jpg)
Polyethylene
* 1985 CNS began experimenting withPolyethylene piping materials as a replacementfor Polybutylene
* Further testing of the Polyethylene piping beganin 1991 -1 992
* The test proved conclusively that Polyethylenewas very compatible with the system designparameters and water chemistry
![Page 15: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/15.jpg)
Polyethylene Piping Replacement
* After six years of actual in service application,there was no corrosion or biological materialbuildup on the inside of the pipe walls
* In 1998, the existing A-1 06 carbon steel supplyand return piping to the Unit 2 generatorhydrogen coolers was replaced with 500-600feet of 6" & 8" HDPE, SDR-1 1, polyethylenepiping
* Inspection results and performance of this pipingsince installation have been flawless (Nodegradation and no measurable fouling)
![Page 16: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/16.jpg)
, jj. I-"'ImII-p1 Ii)
A 2
F-- �-----���
F.,
A--
I - I4iF -Qd-e j
*: -
"- - .-
-a-woto
$t , __ _ _ _ _ _ _ '_ X
~~~~n~~. j '.2a>A.,.,
4j* - - **
._
![Page 17: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/17.jpg)
�N¶I
t
![Page 18: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/18.jpg)
.. . - - -1 ' . s
- - I
.Nx-11
-. . . . .
S: i - - -I. ; ,, '.- - . I .. I
,: -
,;. _
I .,-, & -,R � --. ,
bilk<..'.! I
ir. : - t T .'
j, - - -1 i
.a,. z 11k - -=
i-I
/
4a� -�
S~~ . .; X .
*, ati. -;. -- h I'
- . ., .) nS x.Ify4-'.'
![Page 19: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/19.jpg)
(I'- 7�.lpt, I
X�MA�L
w: -. -kt t , ~
C t w - r t x x
-c*�2
- a
;Ž �.. c�xI 7
4'xIt-.
![Page 20: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/20.jpg)
I*.I *1r- 7Sin ai
, -: -4s v/
.:-" * ,
I.I ~. Ia~I'.
-:L
-, i l '
1.dI-
(E. Ki e -A - 4 .
11
-
K
F'� I
I ,Hire
![Page 21: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/21.jpg)
w 7 r
*.. r.I
I1
![Page 22: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/22.jpg)
K f 1 --- ���>
=&NW'M
'. - 41.W --
;MIOW7
-, r:
![Page 23: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/23.jpg)
W- ? .I hi
I ;i hb ,_
,. .. . .
. ..
.
.
..
. .
:
, . 4. , .I: , .,
:'I - - :
X of, S ''' as.,,'w 4-" ' ''.'9F ,
.- 4'11 11 11 1'1 L1
![Page 24: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/24.jpg)
Conclu USions - Non Safety RelatedService Water Piping Experience
HDPE Piping has not exhibited anycorrosion or degradation or significantfouling in over 1 0 years of service atCatawba Nuclear Station.
![Page 25: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/25.jpg)
HDPE USE by British Energy
* Coordinated efforts with British EnergySizewell B Plant to use HDPE Piping
* Monthly teleconference meetings* PE Training organized in September/2004* HDPE Piping installed by Sizewell B in
Spring 2005 in the ASME Section III Class3 emergency service water system.
![Page 26: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/26.jpg)
HDPE USE by British Energy__cKFsWTTTZ
![Page 27: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/27.jpg)
HDPE USE by British Energy
![Page 28: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/28.jpg)
Polyethylene Piping Materials
ASTM Material Specifications Used:* ASTM D-3350 Standard Specification for PE
Plastic Pipe & Fittings Material* ASTM D-3035 Standard Specification for PE
Plastic Pipe based on controlled outsidediameter
* ASTM D-2837 Standard Method for ObtainingHydrostatic Design Basis for ThermoplasticPipe Material or Pressure Design Basis forThermoplastic Pipe Products
![Page 29: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/29.jpg)
HDPE Butt Fusion
«.7
![Page 30: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/30.jpg)
HDPE Butt Fusion
Joints made by trained and qualifiedoperators in accordance with a qualifiedprocedures
Essential parameters by data logger as apermanent record
![Page 31: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/31.jpg)
HDPE Butt Fusion
2 H Minimum1/2 H Maximum
2-1/2 H Maximum
_ , H
Uniform Bead Size & Shape
Bead Rolled to Pipe Surface
PE Pipe (Cross Section View)
![Page 32: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/32.jpg)
McElroy Joint Report
. Nlt, Q , .. tz.- ,, ,- Xw, T
:' I, t: raot-~
4 :Car~fyll U!¢3
t r;Uchm ,Y [-t INi'dilme ,
t:I 0 .4, _f tJ ,
r 'pof kv,-r i^A~; t"F1*>
JM: f f
f . X, -. -~' t .. i~ .t
I.,9 t, ^''i; Ip-i,,
41 $ rA
r~ t4
;^ ,~~ 414 rA ii*e. tr!4. !.r* Prqax"uttQ, 4V PA4
SlS' ti, i:,v 4i: 1'l -
'1 . rntr -A it ;vsta . r
HDPE Butt Fusion , !;f 4 r ! fl,� !a! 11 f c� ,, � � �
1 114 � .
, 1, , �,I �.
I; 1 .4�
1 � �� '. " I
Data Logger Report Datat i. rAnutw
COz-
![Page 33: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/33.jpg)
f Polyethylene Replacement Pipe, Project
Seismic Analysis
Jack SpannerEPRI NDE CenterJune 27, 2005USNRC Offices-White Flint
![Page 34: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/34.jpg)
Objectives
This project will provide a seismic analysismethodology for the technical justification toaccompany the relief request and a Code Case toallow utilities to repair or replace safety relatedpiping with polyethylene
Contract deliverables.*Task 1-Develop a general methodology for buried
HDPE pipe*Task 2-Analyze a buried system at Catawba NPP
- Piping to diesel heat exchanger*Task 3-Prepare Code case for Section III/XI
![Page 35: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/35.jpg)
Status
*Seismic analysis scheduled for completion byAugust 1, 2005
*Obtained HDPE and seismic performance datafrom Gas Technology Institute
*Catawba staff will also provide informationnecessary for seismic analysis-soil type, groundaccelerations, drawings, etc.
*Contractor provided analysis for buried HDPEpipe at a DOE facility
![Page 36: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/36.jpg)
,.�
-�U
-� I
-� I
Polyethylene Replacement Pipex-A Project
NDE Technique Evaluation
Jack SpannerEPRI NDE CenterJune 27, 2005USNRC Offices-White Flint
![Page 37: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/37.jpg)
Objectives of EPRI PE Pipe Project
This project will develop a technical justification toaccompany a Code Case to allow utilities to repair orreplace safety related piping that has degraded, usuallydue to corrosion. It was decided to also evaluate NDEtechniques for qualifying joining procedures.
* Task 1 - Evaluate NDE techniques for HDPE joints.* Task 2-Develop and publish a technical report that
provides the technical justification for the Code case andRelief Request
* Task 3-Submit a Code case to the Code forimplementation.- Buried pipe Code case first- Above ground Code case later
![Page 38: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/38.jpg)
NDE Techniques to Evaluate
*Visual Inspection of joint and bead* Microwave Inspection-Evisive*Ultrasonic Phased Array* Ultrasonic Time of Flight Diffraction (TOFD)9 Radiography
![Page 39: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/39.jpg)
Microwave Inspection atCatawba NPP
Waveguide
Evisive Manual Scanner,IA
PScanner
![Page 40: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/40.jpg)
Microwave Inspection of EF Coupling JointRG&E Mockup
Evisive Microwave NDT FileSaturday, May 1, 2004 13:55:33
Right Circular Cylinder - Sample Rate (Hz): 240
Ca)
-a
N. 03 0315
~0406 3039
3432 0127
3 4022- 02
3302 02 1
030097335 W ires30 43 0 0473
03424 0 05243
033334 0 04348
_003302
32940 0
3282 -0-449Pipe End0327337 01633
032507 .02926
02407 4 04022
0323404 005237
02109
3 1307 31187 5 -N nonFusb
End
on
Nameplates
Wires
Coupler EndCircumference
C D3
![Page 41: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/41.jpg)
Phased Array UT of EFCoupling Joint
i* Assumed Signals in Linear Array Ultrasonic Inspection for PE Coupler Joining
UltrasonicArray Sensor \
K'-00- \A/irga
End Cold _ 1,Zone
Coupler Wall
Pipe Wall oPipe
Electro-Fusion JInterface Z Center Cold
C(C*
![Page 42: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/42.jpg)
Time of Flight Diffraction (TOFD) UTTechnique-Cold fusion in butt joint
* Stage 3 - correlation UT-TOFD vs.destructive examination* Lab test spools. Field welds
Field Sample &Scan"
* Results* Strong positive
correlation ofNDE indicationsto actual flaws
FLUOR.
coS5
![Page 43: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/43.jpg)
Status
*Evaluating NDE techniques* RG&E, Duke and EPRI mockups* Microwave system interfaced with UT pipe scanner
and used at Catawba and on mockups* Ultrasonic time of flight demonstrations in progress* Tried phosphor plate RT techniques-not successful
- NE Gas Assoc. had better success
*Collaborating with others like British Energy(Sizewell), NorthEast Gas Assoc., RG&E,etc.
![Page 44: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/44.jpg)
Relief Request - Scope
* Catawba Nuclear Service Water System -Buried Piping (ASME Section Ill
* Buried Supply Piping to the heatClass 3)
exchangers that reject heat for the mainemergency diesel generators
* Existing 10 inch Carbon Steel NPS Pipingto be replaced with HDPE
* Approximately 1700 feet of piping forCatawba Units 1 and 2
![Page 45: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/45.jpg)
Relief Request - Development
* EPRI Project for code case development beganin 2004.
* Code case concept introduced at ASME SectionXl Committee in February, 2004.
* Code case and relief request work complimentone another.
* Duke Power made decision to pursue reliefrequest since piping replacement will berequired before code case is approved.
* Target date to submit relief request is2Fall, 20052
![Page 46: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/46.jpg)
Relief Request - Development
* Relief Request will address:DesignInstallationI nspectionTestingProcurement
![Page 47: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/47.jpg)
Service Water PipingRefurbishment Plan
NSW Plan (2006-2010)
* Replace portions of auxiliary building piping* Install NSW pump house header crossover* Install NSW auxiliary building header crossover* Replace EDG cooling supply headers* Remove selective cooling loads from NSW* Move isolation valves to reduce lake water
exposure* Submit LAR for single header operation
12
![Page 48: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information](https://reader033.vdocuments.site/reader033/viewer/2022041822/5e5e7ac4d7b22d572c3bb0a5/html5/thumbnails/48.jpg)
Contacts:
Larry Rudy, Regulatory Compliance, [email protected], 803-831-3084Steve Lefler Engineering, [email protected], 704 382 0138Ernie McElroy, Engineering, ewmcelro~duke-enerqv.com, 803 831 4174Dave Ward, Engineering, [email protected]' 803 831 4190Mel Arey Engineering, miareyl @duke-energy.com, 704 382 8619Joel Reeves CNS Service Water Project, [email protected], 803 831 3835Terry Edwards CNS Service Water Project, [email protected] 803 831 4153Jack Spanner (EPRI), [email protected], 704 547 6065