    Ringmaster

    Medium Voltage Distribution

    Ring Main Unit

    Catalogue2009

  • 7/21/2019 Catalogue Ringmaster Part1

    2/70

    A new path for achieving your electrical installations

    A comprehensive offer

    The Ringmaster range is part of a comprehensive offer of products that are perfectlycoordinated to meet all medium and low voltage electrical distribution requirements.All of these products have been designed to work together: electrical, mechanicaland communication compatibility.The electrical installation is thus both optimised and has improved performance:@ better service continuity,@ increased personnel and equipment safety,@ guaranteed upgradeability,@ efficient monitoring and control.You therefore have all the advantages at hand in terms of know-how and creativityfor achieving optimised, safe, upgradeable and compliant installations.

    Tools for facilitating the design and installation

    With Schneider Electric, you have a complete range of tools to help you get to know andinstall the products whilst complying with current standards and good working practices.These tools, technical sheets and guides, design software, training courses, etc areregularly updated.

    For a real partnership with you

    A universal solution doesnt exist because each electrical installation is specific.The variety of combinations on offer allows you to truly customise the technical solutions.You are able to express your creativity and put your know-how to best advantagewhen designing, manufacturing and exploiting an electrical installation.

    Schneider Electric is associating itself with

    your know-how and your creativity to produce

    optimised, safe, upgradeable and compliant

    installations

  • 7/21/2019 Catalogue Ringmaster Part1

    3/701AMTED399086EN.indd

    Presentation 2

    Applications 2

    Switchgear description 3

    VIP protection relays 5

    Network remote control 6

    Ringmaster selection guide 8

    Section 1 9

    Ring main units 10 - 25

    Circuit breaker, metering and switches 26 - 65

    Remote control 66 - 68

    Section 2 69

    Installation drawings 70 - 80

    Schematic diagrams 81 - 112

    Section 3 113

    Accessories 114 - 119

    Section 4 121

    Schneider Electric, an overview and order form 122 - 128

    Ringmaster range General contents

  • 7/21/2019 Catalogue Ringmaster Part1

    4/702 AMTED399086EN.indd

    Ringmaster range

    PresentationApplications

    Ringmaster is the ideal choice for all your MV applications.

    From simple transformer protection, or sectionalising with remote

    control, to multi-panel metered consumer switchboards,the Ringmaster range from Schneider Electric offers a solution.

    Quality engineering for extreme climates enables Ringmaster

    to provide flexibility for any location.

    Covering a wide range of options with an indoor and outdoor IP54

    design and ratings up to 13.8 kV, 630 A and 21 kA, Ringmaster

    has proved successful in markets around the world.

    Product advantages

    Simple, clear operation combined with compact size,

    high functionality and reliability extends the applicationsof the Ringmaster range.

    Safety to personnel

    Fully certified internal arc design.

    Indoor/outdoor design

    No need for expensive switchrooms.

    Self powered protection

    Not reliant on costly battery chargers.

    Compact

    Reduced dimensions, gives reduced civil costs.

    Virtually maintenance free

    Low lifetime costs.

    Modular design

    Quick, simple & easy to install.

    Proven design

    Assured consistent quality.

    ISO 9001 quality certification.

    Environmental

    Manufactured to ISO 14001 environmental standards.PE40438

  • 7/21/2019 Catalogue Ringmaster Part1

    5/703AMTED399086EN.indd

    Ringmaster range

    PresentationSwitchgear description

    PE57061

    A variety of different panel types are available for each unit within

    the range, together with a number of optional accessories enabling

    Ringmaster to satisfy the most complex system specification.

    A multitude of configurations

    Free standing,

    non-extensible,

    cable connected

    ring main unit.

    Transformer mounted,

    non-extensible ring main unit,

    incorporated in a packaged

    substation.

    Free standing,

    extensible cable

    connected ring main unit

    Transformer mounted,

    extensible ring main unit,

    incorporated in a packaged

    substation.

    Free standing,

    non-extensible

    circuit breaker.

    Cable connected

    extensible switchboard.

    PE57064

    PE57062

    PE57065

    PE57063

    PE57066

  • 7/21/2019 Catalogue Ringmaster Part1

    6/704 AMTED399086EN.indd

    Ringmaster range

    PresentationSwitchgear description

    General characteristics

    b Gas pressure indicator as standard

    bAnti-reflex operating handle with facilities

    for electrical operation

    bInterlocked MV cable test access (no need to remove

    cable terminations or use loose earthing devices)

    bIntegral self-powered protection with TFL,

    adjustable curve & relay options

    bIP54 enclosure

    bSimple to follow mimic providing user-friendly operation

    bEarth screened cast-resin gas module

    bRange of dry type metering units

    bMechanical tripped on-fault indication

    bResin encapsulated busbars in air bus chamber

    for extensible version

    bDirect coupling to transformers or cable connection.

    Standard and quality assurance

    Manufactured to BS EN ISO 9001.

    Ringmaster meets the following standards and has obtained

    approval from the UK Electricity Association: IEC 56, IEC 60265,

    IEC 62271-200, BS EN 60265 and EATS 41-26.

    PE57067

  • 7/21/2019 Catalogue Ringmaster Part1

    7/705AMTED399086EN.indd

    Ringmaster range

    PresentationVIP protection relaysSelf-powered reliability

    PE57160

    VIP 300

    Pick-up current ranges: RN2c, RE2c, CN2, CE2Overcurrent: 20A-200A.Earth fault: 2A-160A.CE6 and RN6c Overcurrent: 80A-800A.Earth fault: 8A to 640A.Hardened electronics Certified EMC performance to IEC60255 and EN 50061, EN50082.

    Separate overcurrent and earth fault trip indication.

    Flashing LEDs indicate when the relay is operating underfault conditions.

    b

    b

    b

    PE57159

    VIP 35

    provides protection against phase-to-phase faultsand earth faults.

    PE56826

    VAP 6

    VIP 300 - the leading protection relay providing a wide range of

    selectivity and quality of supplyThe VIP 300 is a three phase overcurrent and earth fault protection device, providing

    protection for networks and equipment. Being an integral part of the highly successful

    Ringmaster range, its main function is to detect phase and earth faults within the

    network and to trip the circuit breaker.

    Flexibility

    The relay provides for a wide range of protection settings for most applications.

    The IDMT characteristics employed for both the overcurrent and earth fault elements

    can be easily adjusted to provide discrimination with upstream MV and downstream

    LV protective devices. Fast power-up of the VIP 300 also provides immediate

    protection and can detect faults instructing the CB to trip in less than 40ms.

    Reliability

    The relay has a self monitoring device and diagnostic routine that constantly checks

    the operation of the relay automatically.

    Self-powered reliability

    The VIP 300 protection relay is a self powered microprocessor based device which

    requires no external DC power source or batteries, making it the ideal solution for

    location in remote areas where auxiliary supplies are not readily available.

    Ease of use

    VIP 300 has improved operation and control with the relay settings being clearly

    displayed on the front panel. Manual reset flags show separate tripped on fault for

    either phase or earth fault conditions.

    Testing

    The VAP 6 hand held test unit, is available to provide a simple check of the integrity

    of the relay and can also be used to perform trip tests on the circuit breaker.

    The circuit breaker trip inhibit facility allows the relay to be tested without tripping

    the circuit breaker. Secondary injection can be carried out using conventional testequipment.

    The VIP 30 and VIP 35 are self-powered devices, requiring no external DC power

    source or batteries. They are designed for use in distribution networks providing

    protection for transformers.

  • 7/21/2019 Catalogue Ringmaster Part1

    8/706 AMTED399086EN.indd

    Ringmaster range

    PresentationNetwork remote controlT200E telecontrol

    Ringmaster and T200E

    Control your Ringmaster from a remote position

    The Schneider Electric Easergy T200E telecontrol cabinet, which

    links the Ringmaster to a control centres automation system,

    allows you to manage a secondary distribution network from

    a remote point. Network faults can be identified and isolated

    and the network reconfigured in seconds without manual

    intervention, which substantially improves the quality of supply.

    The small and compact Easergy T200E can be easily mounted

    directly onto the Ringmaster, saving installation costs and valuable

    floor space.

    Telecontrol equipment can be added any time after installation.

    This makes Ringmaster RMUs even more cost-effective to install,

    since a control system can be bought separately if needed at a later

    date. Other RTUs can also be integrated if required.

    PE57069

    PE57071

    Internal viewof Easergy T200E

    Ringmaster C with Easergy T200E

  • 7/21/2019 Catalogue Ringmaster Part1

    9/707AMTED399086EN.indd

    Ringmaster range

    PresentationNetwork remote controlEasergy L500

    Continuity of service guaranteed by an overalltelecontrol offer

    Schneider Electric offers you a complete solution, including:the Easergy T200 E telecontrol interface,

    MT switchgear that is adapted for telecontrol.

    b

    b

    PE56312

    L500 network monitoring screen

    DE40901EN

    PE57073EN

    RN2C RN2C RN2C

    RN2CRN2C RN2C

    Network control centre

    HV/MV

    Communication network

    MV ring

    Easergy L500, a low cost solution

    to immediately improve your SAIDI ** SAIDI: system average interruption duration index

    Easergy L500 is a SCADA providing all the functions needed to operate

    the MV network in real time

    Pre-configured with Easergy range products:

    MV/LV substations equipped with T200 E or Flair 200C

    overhead line equipped with Flite 116/G200

    Broad range of transmission supports: Radio, GSM, GPRS, PSTN, LL, FO.

    Advantages

    Simple implementation:

    one to two weeks only for 20 MV/LV substations

    configuration, training and handling within a few daysShort return on investment

    Simple and fast evolutions by operations managers

    Service quality and operations rapidly improved.

    b

    v

    v

    b

    b

    v

    v

    b

    b

    b

  • 7/21/2019 Catalogue Ringmaster Part1

    10/708 AMTED399086EN.indd

    Key to product references

    Ringmaster is available as standard panel types, allowing easy

    selection and specification. The product references are made up as

    follows:

    R Ring main unit 2 200 A

    C Circuit breaker 6 600 A

    S Switch 16 16 kA

    N Non-Extensible 21 21 kA

    E Extensible

    MU Metering unit

    Example: CN2-T1/16 = circuit breaker, non extensible, 200 A, 16 kA fault rating.

    The Ringmaster catalogue allows easy selection and specification,

    based on a broad range of worldwide applications.

    Included in this publication is:

    bpanel type specifications

    bdetails of optional accessories

    bschematic diagrams

    bInstallation drawings.

    Accessories

    Accessories for the Ringmaster range are supplied either fitted or

    loose, where stated enabling simple panel configuration on site.

    Details of accessories are contained within the panel type pages.

    General arrangement drawings

    General arrangement drawings are given for each panel type.This allows you to quickly size up switchrooms and calculate

    external connections at the pre-order stage.

    Need more information?

    If your requirements are not listed, please contact your local

    Schneider Electric representative, or contact us on:

    Tel: +44(0) 113 290 3500

    Email: [email protected]

    Electronic catalogue requests

    Electronic copies of this selection guide are available free of charge

    upon request. For this, and other MV literature, please email your

    full contact details to Email:

    [email protected]

    RN2c RE2c RN6c MU2 CN2 SN6 CE2 CE6 SE6

    200 Anon extensiblering main unit

    200 Aextensiblering main unit

    630 Anon extensiblering main unit

    200 Afeedermetering unit

    200 Anon extensiblecircuit breaker

    630 Anon extensibleswitch

    200 Aextensiblecircuit breaker

    630 Aextensiblecircuit breaker

    630 Aextensibleswitch

    PE57072

    Ringmaster range

    PresentationRingmaster selection guide

  • 7/21/2019 Catalogue Ringmaster Part1

    11/709AMTED399086EN.indd

    Ringmaster range

    Section 1Contents

    Ring main units

    Non-extensible ring main unit 200A

    RN2c-T1, RN2c-T2, RN2c-T3, RN2c-T4, RN2c-T5 10 -17Non-extensible ring main unit 630A

    RN6c-T1 18

    Extensible ring main unit 200A

    RE2c-T1, RE2c-T2, RE2c-T3, RE2c-T4 19 - 25

    Circuit breaker, metering and switches

    Non-extensible circuit breaker - 200A

    CN2-T1, CN2-T6 26 - 29

    Non-extensible Switch 630A

    SN6-S1, SN6-S2 30 - 33

    Non-extensible metering unit - 200A

    MU2-M1, MU2-M2, MU2-M3 34 - 38

    Extensible circuit breaker - 200A

    CE2-T2, CE2-T7, CE2-T*, CE2-T12, CE2-T**,

    CE2-T13, CE2-T15, CE2-T16 39 - 49

    Extensible circuit breaker - 630A

    CE6-T4, CE6-T*, CE6-T8, CE6-T** 50 - 55

    Extensible switch - 630A

    SE6-S1, SE6-S2, SE6-E1 56 - 60

    Extensible bus section - 630A

    SE6-B1, CE6-B3, CE6-B5 61 - 65

    Remote controlTelecontrol unit

    Easergy T200-E01M, Easergy T200-E04M 66 - 68

  • 7/21/2019 Catalogue Ringmaster Part1

    12/7010 AMTED399086EN.indd

    Ringmaster range

    Section 1Ring main units non-extensibleSpecification

    RN2c-T1

    TFL

    RN2c-T2

    VIP 300

    RN2c-T3

    VIP 30

    RN2c-T4

    VIP 35

    RN2c-T5

    Glass TFL

    RN6c-T1

    VIP 300

    Environment

    Indoor / outdoor b b b b b b

    IP54 b b b b b b

    Transformer mounted b b b b b

    Freestanding O O O O O b

    Ratings

    Busbars 630A b b b b b b

    Circuit breaker normal rated current 200A b b b b b

    Circuit breaker normal rated current 630A b

    Switch normal rated current 630A b b b b b b

    12kV 16kA 3 seconds 75kV BIL b b b b b b

    13.8kV 21kA 3 seconds 95kV BIL O O O O O O

    Ring switch cable earth switch 16kA 3 seconds b b b b b b

    Ring switch cable earth switch 21kA 3 seconds O O O O O O

    Circuit breaker earth switch 3.15kA b b b b b b

    MechanismIndependent manual b b b b b b

    Provision for motorised mechanism LH ring switch b b b b b b

    Provision for motorised mechanism RH ring switch b b b b b b

    Provision for motorised mechanism circuit breaker O O O O O O

    Protection & control - circuit breaker

    CTs dual ratio - 100/50/5A class X b b

    CTs ratio - 200/1A class X b

    CTs ratio - 500/200/1A class X b b

    CTs ratio - 800/400/1A class X b

    Overcurrent & earth fault CT operated trip coils - TFL b

    Overcurrent & earth fault CT operated trip coils - glass TFL b

    Overcurrent relay - VIP 30 b

    Overcurrent & earth fault relay - VIP 35 b

    IDMT overcurrent & earth fault relay - VIP 300 b b

    Multi voltage shunt trip coil (see accessories page 11) O O O O O O

    Indication

    Mechanical ON/OFF b b b b b b

    Mechanical EARTH/MAIN b b b b b b

    Neon indication 3.3 - 13.8kV O O O O O O

    Gas pressure indicator (-25C to +55C) b b b b b b

    RSW aux contacts 1NO & 1NC O O O O O O

    Test facility

    Integral ring cable test facility b b b b b b

    Integral circuit breaker test facility O O O O O b

    Standard features

    Operating handle b b b b b b

    Cable (see available cable kit accessories)

    Bottom entry up 1 x 3C 300mm2 b b b b b b

    Bottom entry up 3 x 1C 630mm2 b b b b b b

    Top entry cables (indoor only) O O O O O O

    Order codes

    12kV, 16kA, 75kV BIL, 0.35bG RN2c-T1/16 RN2c-T2/16 RN2c-T3/16 RN2c-T4/16 RN2c-T5/16 RN6c-T1/16

    13.8kV, 21kA, 95kV BIL, 0.8bG RN2c-T1/21 RN2c-T2/21 RN2c-T3/21 RN2c-T4/21 RN2c-T5/21 RN6c-T1/21

    General arrangement drawing - transformer mounted RMINST-06Page 77

    RMINST-06Page 77

    RMINST-06Page 77

    RMINST-06Page 77

    RMINST-06Page 77

    RMINST-06Page 77

    General arrangement drawing - freestanding RMINST-05Page 116

    RMINST-05Page 116

    RMINST-05Page 116

    RMINST-05Page 116

    RMINST-05Page 116

    RMINST-05Page 116

    Schematic diagram - TFL RMSCH-01Page 85

    RMSCH-01Page 85

    Schematic diagram - VIP 30 RMSCH-02Page 87

    Schematic diagram - VIP 35 RMSCH-15Page 88

    Schematic diagram - VIP 300 RMSCH-03Page 86

    RMSCH-42Page 89

    Key: bStandard feature OOptional feature

  • 7/21/2019 Catalogue Ringmaster Part1

    13/7011AMTED399086EN.indd

    Ringmaster range

    Section 1Ring main units non-extensibleAccessories

    RN2c-T1

    TFL

    RN2c-T2

    VIP 300

    RN2c-T3

    VIP 30

    RN2c-T4

    VIP 35

    RN2c-T5

    Glass TFL

    RN6c-T1

    VIP 300

    Kit no.

    Cable kits

    Circuit breaker cable box v v v v v RMR-A/F47

    Circuit breaker cable box with integral cable test facility v v v v v b RMR-F325

    Gland plate 1 x 3C O O O O O O RMR-A316

    Gland plate 3 x 1C O O O O O O RMR-A319

    Small gland plate 1 x 3c O O O O O O RMR-A322

    Blank aluminium gland plate O O O O O O RMR-A320

    Brass wiping gland 1 x 3C O O O O O RMR-A10

    Brass wiping gland 3 x 1C O O O O O O RMR-A11

    Small brass wiping gland 1 x 3c O O O O O O RMR-A105

    Tubular gland 1 x 3C O O O O O O RMR-A12

    Tubular gland 3 x 1C O O O O O O RMR-A13

    Small tubular gland O O O O O O RMR-A106

    CES5 gland O O O O O O RMR-A120

    CES5 gland plate 1 x 3C O O O O O O RMR-A321

    CES5 gland adaptor O O O O O O RMR-A525

    6 x ECON cable termination kit O O O O O O RMR-A314

    3 x STD ECON end cap O O O O O O RMR-A370

    3 x ECON cable termination kit O O O O O O RMR-A315

    Top entry cables RH cable box (indoor only) v v v v v v RMR-F303

    Top entry cables LH cable box (indoor only) v v v v v v RMR-F302

    Rsw extension box for 2 x 3C cables (left hand) v v v v v v RMR-F523

    Rsw extension box for 2 x 3C (right hand) v v v v v v RMR-F522

    Angled gland plate 1 x 3C O O O O O O RMR-A317

    Split gland plate 1 x 3C O O O O O O RMR-A318

    Installation items

    Transformer mounting kit v v v v v v RMR-A/F323

    Extension trunking (to clear transformer radiators) O O O O O O RMR-A20

    Set of padlocks - 11 no O O O O O O RMR-A343

    Anti-vandal fixings, including tool O O O O O O RMR-A344

    Foundation bolts (not required for transformer mounting) O O O O O O RMR-A22Multicore pilot glands O O O O O O RMR-A342

    Time limit fuses (set of 2 - specify rating as table page 115) O O O O O O RMR-A17

    RN2c to MU2 installation kit v v v v v v RMR-A350

    Ariel mounting bracket O O O O O O RMR-A201

    Operational items

    Operating handle b b b b b b RMR-F345

    LH ring switch control auxiliary sw for motorisedmechanism provision

    v v v v v v RMR-F328

    LH ring switch termination block for motorisedmechanism provision (not Easergy)

    v v v v v v RMR-F363

    RH ring switch control auxiliary sw for motorisedmechanism provision

    v v v v v v RMR-F329

    RH ring switch termination block for motorisedmechanism provision (not Easergy)

    v v v v v v RMR-F364

    Provision for motorised mechanism circuit breaker v v v v v b RMR-F543

    Motorised mechanism - specify voltage v v v v v v RMR-F507

    CB Termination block for motorisedmechanism provision (not Easergy)

    v v v v v v RMR-F365

    Shunt trip coil (20-250V DC, 110-250V AC) TLF v v v v v v RMR-F581

    Shunt trip coil (20-250V DC, 110-250V AC) VIP v v v v v v RMR-F582

    Ring switch cable neon indication (11-13.8kV) v v v v v v RMR-F341

    Ring switch cable neon indication (3.3-7.2kV) v v v v v v RMR-F348

    Circuit breaker cable neon indication (11-13.8kV) v v v v v v RMR-F340

    Circuit breaker cable neon indication (3.3-7.2kV) v v v v v v RMR-F347

    Phase indication device O O O O O O RMR-A374

    VAP 6 test unit for VIP 300/30/35 O O O O O O RMR-A202

    Emergency trip push button v v v v v v RMR-F339

    Gas pressure switch for remote indication only v v v v v v RMR-F368

    Key: bStandard feature v Factory fitted accessory OLoose accessory, assembled on site

  • 7/21/2019 Catalogue Ringmaster Part1

    14/7012 AMTED399086EN.indd

    Ringmaster range

    Section 1Ring main units non-extensibleAccessories

    RN2c-T1

    TFL

    RN2c-T2

    VIP 300

    RN2c-T3

    VIP 30

    RN2c-T4

    VIP 35

    RN2c-T5

    Glass TFL

    RN6c-T1

    VIP 300

    Kit no.

    Mechanical interlocks

    Circuit breaker - key free, EARTH ON v v v v v v RMR-F337

    Circuit breaker - key free, MAIN OFF v v v v v v RMR-F338

    Switch - key free, SWITCH OFF LH v v v v v v RMR-F335

    Switch - key free, SWITCH OFF RH v v v v v v RMR-F336

    N. B. specify lock symbol at time of ordering ( 3 digits max) notavailable with motor mechanisms

    Earth fault passage indication (choose provision kit

    and an EFPI required if not using Easergy T200E)

    Phase & earth fault provision for Easergy T200E O O O O O O RMR-F310

    EFPI provision kit, inside cable box O O O O O O RMR-A304

    EFPI provision kit, CT outside cable box O O O O O O RMR-A305

    EFPI provision kit, inside cable box, top entry O O O O O O RMR-A308

    EFPI provision kit, outside cable box, top entry O O O O O O RMR-A309

    Bowden RR EFPI and CT O O O O O O RMR-A422

    Bowden STD EFPI type NB O O O O O O RMR-A277

    Bowden LV reset EFPI type NB1 O O O O O O RMR-A278

    Bowden LV reset & alarm type NB2 O O O O O O RMR-A279

    Fundamentals ER FIND EFPI and CT O O O O O O RMR-A57

    N. B. above CTs are ring type for split core - please consultSchneider Electric

    Key: v Factory fitted accessory OLoose accessory, assembled on site

  • 7/21/2019 Catalogue Ringmaster Part1

    15/7013AMTED399086EN.indd

    Ringmaster range

    Section 1Non-extensible ring main unit200 ARN2c-T1

    Transformer protection up to 1.6MVA at 11kV

    Protection & control - CB

    Overcurrent and earth fault protection using CT operated trip coils with provision for

    time fuse links

    Protection CTs - 100/50/5A class X

    Transformer ratings

    See table - page 119

    Documents

    Transformer mounted installation drawing ref: RMINST-06

    Freestanding installation drawing ref: RMINST-05

    Schematic drawing ref: RMSCH-01

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Busbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 630A/200ANormal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Ring cable earth switch, 16/21kA 3s

    Transformer earth switch, 3.15kA 3s

    Anti-reflex operating handle

    Provision for motorised mechanism LH/RH ring switch with plug interface

    Indication

    Mechanical tripped on fault flag indicator

    Mechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicatorCB auxiliary contacts 1NO 1NC

    CB earth position selected 1NO

    CB earth ON, 1NO

    Test facility

    Integral ring switch cable test facility

    Cable

    Bottom entry up to 1 x 3C 300mm2

    Bottom entry up to 3 x 1C 630mm2

    Accessories - see table, page 11

    CB, LH, RH motor kits

    LH, RH ring switch indication 1NO 1NC earth On 1NO

    Multi voltage shunt trip coil 20V DC - 250V AC

    Neon indication

    Inverted cable boxes (indoor only)

    Transformer mounting kitFreestanding tee-off cable box

    Order information

    Code Rating

    RN2c-T1/16 16kA, 12kV, 75kV BIL

    RN2c-T1/21 21kA, 13.8kV, 95kV BIL

    DE60180

    DE60181

  • 7/21/2019 Catalogue Ringmaster Part1

    16/7014 AMTED399086EN.indd

    Ringmaster range

    Section 1Non-extensible ring main unit200 ARN2c-T2

    Transformer protection up to 3.5MVA at 11kV

    Protection & control - CB

    Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

    IEC 60255 and BS142

    Protection CTs - 200/1A class X

    Setting range:

    Overcurrent: 20-200A

    Earth fault: 2-160A

    Transformer ratings

    See table - page 119

    Documents

    Transformer mounted installation drawing ref: RMINST-06

    Freestanding installation drawing ref: RMINST-05

    Schematic drawing ref: RMSCH-03

    Environment

    Indoor/outdoor

    IP54

    RatingsBusbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 630A/200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Ring cable earth switch, 16/21kA 3s

    Transformer earth switch, 3.15kA 3s

    Anti-reflex operating handle

    Provision for motorised mechanism LH/RH ring switch with plug interface

    Indication

    Mechanical tripped on fault flag indicatorMechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicator

    CB auxiliary contacts 1NO 1NC

    CB earth position selected 1NO

    CB earth ON, 1NO

    Test facility

    Integral ring switch cable test facility

    Cable

    Bottom entry up to 1 x 3C 300mm2

    Bottom entry up to 3 x 1C 630mm2

    Accessories - see table, page 11

    CB LH, RH motor kits

    LH, RH ring switch indication 1NO 1NC earth On 1NO

    Multi voltage shunt trip coil 20V DC - 250V ACNeon indication

    Inverted cable boxes (indoor only)

    Transformer mounting kit

    Freestanding tee-off cable box

    Order information

    Code Rating

    RN2c-T2/16 16kA, 12kV, 75kV BIL

    RN2c-T2/21 21kA, 13.8kV, 95kV BIL

    b

    v

    v

    DE60180

    DE60185

  • 7/21/2019 Catalogue Ringmaster Part1

    17/7015AMTED399086EN.indd

    MV transformer protection

    Protection & control - CB

    Self powered overcurrent relay, VIP 30.

    Protection CTs - 500/200/1A class X

    Setting range: 500/1A

    Overcurrent: 20-200A

    Setting range: 200/1A

    Overcurrent: 8-80A

    Transformer ratings

    See table - page 119

    Documents

    Transformer mounted installation drawing ref: RMINST-06

    Freestanding installation drawing ref: RMINST-05

    Schematic drawing ref: RMSCH-02

    Environment

    Indoor/outdoor

    IP54

    RatingsBusbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 630A/200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Ring cable earth switch, 16/21kA 3s

    Transformer earth switch, 3.15kA 3s

    Anti-reflex operating handle

    Provision for motorised mechanism LH/RH ring switch with plug interface

    Indication

    Mechanical tripped on fault flag indicatorMechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicator

    CB auxiliary contacts 1NO 1NC

    CB earth position selected 1NO

    CB earth ON, 1NO

    Test facility

    Integral ring switch cable test facility

    Cable

    Bottom entry up to 1 x 3C 300mm2

    Bottom entry up to 3 x 1C 630mm2

    Accessories - see table, page 11

    CB, LH, RH motor kit

    LH, RH ring switch indication 1NO 1NC earth On 1NO

    Multi voltage shunt trip coil 20V DC - 250V ACNeon indication

    Inverted cable box (indoor only)

    Transformer mounting kit

    Freestanding tee-off cable box

    Order information

    Code Rating

    RN2c-T3/16 16kA, 12kV, 75kV BIL

    RN2c-T3/21 21kA, 13.8kV, 95kV BIL

    b

    v

    b

    v

    Ringmaster range

    Section 1Non-extensible ring main unit200 ARN2c-T3

    DE60180

    DE60182

  • 7/21/2019 Catalogue Ringmaster Part1

    18/7016 AMTED399086EN.indd

    MV transformer protection

    Protection & control - CB

    Self powered overcurrent and earth fault relay, VIP 35.

    Protection CTs - 500/200/1A class X

    CH30 core balance CT

    Setting range: 500/1A

    Overcurrent: 20-200A

    Earth fault: 25-300A

    Setting range: 200/1A

    Overcurrent: 8-80A

    Earth fault: 10-120A

    Transformer ratings

    See table - page 119

    Documents

    Transformer mounted installation drawing ref: RMINST-06

    Freestanding installation drawing ref: RMINST-05

    Schematic drawing ref: RMSCH-15

    EnvironmentIndoor/outdoor

    IP54

    Ratings

    Busbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 630A/200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Ring cable earth switch, 16/21kA 3s

    Transformer earth switch, 3.15kA 3s

    Anti-reflex operating handle

    Provision for motorised mechanism LH/RH ring switch with plug interface

    Indication

    Mechanical tripped on fault flag indicator

    Mechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicator

    CB auxiliary contacts 1NO 1NC

    CB earth position selected 1NO

    CB earth ON, 1NO

    Test facility

    Integral ring switch cable test facility

    Cable

    Bottom entry up to 1 x 3C 300mm2

    Bottom entry up to 3 x 1C 630mm2

    Accessories - see table, page 11CB, LH, RH motor kits

    LH, RH ring switch indication 1NO 1NC earth On 1NO

    Multi voltage shunt trip coil 20V DC - 250V AC

    Neon indication

    Inverted cable boxes (indoor only)

    Transformer mounting kit

    Freestanding tee-off cable box

    Order information

    Code Rating

    RN2c-T4/16 16kA, 12kV, 75kV BIL

    RN2c-T4/21 21kA, 13.8kV, 95kV BIL

    b

    v

    v

    b

    v

    v

    Ringmaster range

    Section 1Non-extensible ring main unit200 ARN2c-T4

    DE60180

    DE60183

  • 7/21/2019 Catalogue Ringmaster Part1

    19/7017AMTED399086EN.indd

    Transformer protection up to 1.6MVA at 11kV

    Protection & control - CB

    Overcurrent and earth fault protection using CT operated trip coils with provision for

    time fuse links (glass fuse link)

    Protection CTs - 100/50/5A class X

    Transformer ratings

    See table - page 119

    Documents

    Transformer mounted installation drawing ref: RMINST-06

    Freestanding installation drawing ref: RMINST-05

    Schematic drawing ref: RMSCH-01

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Busbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 630A/200ANormal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Ring cable earth switch, 16/21kA 3s

    Transformer earth switch, 3.15kA 3s

    Anti-reflex operating handle

    Provision for motorised mechanism LH/RH ring switch with plug interface

    Indication

    Mechanical tripped on fault flag indicator

    Mechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicatorCB auxiliary contacts 1NO 1NC

    CB earth position selected 1NO

    CB earth ON, 1NO

    Test facility

    Integral ring switch cable test facility

    Cable

    Bottom entry up to 1 x 3C 300mm2

    Bottom entry up to 3 x 1C 630mm2

    Accessories - see table, page 11

    CB, LH, RH motor kits

    LH, RH ring switch indication 1NO 1NC earth On 1NO

    Multi voltage shunt trip coil 20V DC - 250V AC

    Neon indication

    Inverted cable boxes (indoor only)

    Transformer mounting kitFreestanding tee off cable box

    Order information

    Code Rating

    RN2c-T5/16 16kA, 12kV, 75kV BIL

    RN2c-T5/21 21kA, 13.8kV, 95kV BIL

    Ringmaster range

    Section 1Non-extensible ring main unit200 ARN2c-T5

    DE60180

    DE60184

  • 7/21/2019 Catalogue Ringmaster Part1

    20/7018 AMTED399086EN.indd

    Network sectionalising up to 12MVA 11kV

    Protection & control - CB

    Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

    IEC 60255 and BS142

    Protection CTs - 800/400/1A class X

    Setting range: 800/1A ratio

    Overcurrent: 80-800A

    Earth fault: 8-640A

    Setting range: 400/1A

    Overcurrent: 40-400A

    Earth fault: 4-320A

    Documents

    Freestanding installation drawing ref: RMINST-05

    Schematic drawing ref: RMSCH-42

    Environment

    Indoor/outdoor

    IP54

    RatingsBusbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 630A/630A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Circuit breaker earth switch 16/21kA

    Ring cable earth switch, 16/21kA 3s

    Anti-reflex operating handle

    Provision for motorised mechanism LH/RH ring switch and circuit breaker with plug

    interface

    Indication

    Mechanical tripped on fault flag indicatorMechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicator

    CB auxiliary contacts 1NO 1NC

    CB earth position selected 1NO

    CB earth ON, 1NO

    Test facility

    Integral ring switch and circuit breaker test facility

    Cable

    Bottom entry up to 1 x 3C 300mm2

    Bottom entry up to 3 x 1C 630mm2

    Accessories - see table, page 11

    CB, LH, RH motor kits

    LH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20V DC - 250V AC

    Neon indication

    Inverted cable boxes (indoor only)

    Freestanding

    Order information

    Code Rating

    RN6c-T1/16 16kA, 12kV, 75kV BIL

    RN6c-T1/21 21kA, 13.8kV, 95kV BIL

    b

    v

    v

    b

    v

    v

    Ringmaster range

    Section 1Non-extensible ring main unit200 ARN6c-T1

    DE60180

    DE60186

  • 7/21/2019 Catalogue Ringmaster Part1

    21/7019AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible ring main unitsSpecification

    RE2c-T1

    TFL

    RE2c-T2

    VIP 300

    RE2c-T3

    VIP 30

    RE2c-T4

    VIP 35

    Environment

    Indoor / outdoor b b b b

    IP54 b b b b

    Transformer mounted b b b b

    Freestanding b b b b

    Extensible (RHS) O O O O

    Ratings

    Busbars 630A b b b b

    Circuit breaker normal rated current 200A b b b b

    Circuit breaker normal rated current 630A

    Switch normal rated current 630A b b b b

    12kV 16kA 3 seconds 75kV BIL b b b b

    13.8kV 21kA 3 seconds 95kV BIL O O O O

    Ring switch cable earth switch 16kA 3 seconds b b b b

    Ring switch cable earth switch 21kA 3 seconds O O O O

    Circuit breaker earth switch 3.15kA b b b b

    Extensible rmu busbar chamber 630A O O O O

    Mechanism

    Independent manual b b b b

    Provision for motorised mechanism LH ring switch b b b b

    Provision for motorised mechanism RH ring switch b b b b

    Provision for motorised mechanism circuit breaker O O O O

    Protection & control - circuit breaker

    CTs dual ratio - 100/50/5A class X b

    CTs ratio - 200/1A class X b

    CTs ratio - 500/200/1A class X b b

    CTs ratio - 800/400/1A class X

    Overcurrent & earth fault CT operated trip coils - TFL b

    Overcurrent & earth fault CT operated trip coils - glass TFL

    Overcurrent relay - VIP 30 b

    Overcurrent & earth fault relay - VIP 35 bIDMT overcurrent & earth fault relay - VIP 300 b

    Multi voltage shunt trip coil (see accessories) O O O O

    Indication

    Mechanical ON/OFF b b b b

    Mechanical EARTH/MAIN b b b b

    Neon indication 3.3 - 13.8kV O O O O

    Gas pressure indicator (-25C to +55C) b b b b

    RSW aux contacts 1NO & 1NC O O O O

    Test facility

    Integral ring cable test facility b b b b

    Standard features

    Operating handle b b b b

    Cable (see available cable kit accessories)

    Bottom entry up 1 x 3C 300mm2 b b b b

    Bottom entry up 3 x 1C 630mm2 b b b b

    Top entry cables* (indoor only) (left hand side only) O O O O

    Order codes

    12kV, 16kA, 75kV BIL, 0.35bG RE2c-T1/16 RE2c-T2/16 RE2c-T3/16 RE2c-T4/16

    13.8kV, 21kA, 95kV BIL, 0.8bG RE2c-T1/21 RE2c-T2/21 RE2c-T3/21 RE2c-T4/21

    General arrangement drawing - freestanding RMINST-22, Page 75 RMINST-22, Page 75 RMINST-22, Page 75 RMINST-22, Page 75

    Schematic diagram - TFL RMSCH-01, Page 85

    Schematic diagram - VIP 30 RMSCH-02, Page 87

    Schematic diagram - VIP 35 RMSCH-15, Page 88

    Schematic diagram - VIP 300 RMSCH-03, Page 86

    Key: bStandard feature OOptional feature

  • 7/21/2019 Catalogue Ringmaster Part1

    22/7020 AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible ring main unitsAccessories

    RE2c-T1

    TFL

    RE2c-T2

    VIP 300

    RE2c-T3

    VIP 30

    RE2c-T4

    VIP 35

    Kit no.

    Cable kits

    Extensible ring main units v v v v RMR-A/F47

    Gland plate 1 x 3C O O O O RMR-A316

    Gland plate 3 x 1C O O O O RMR-A319

    Small gland plate 1 x 3C O O O O RMR-A322

    Blank aluminium gland plate O O O O RMR-A320

    Brass wiping gland 1 x 3C O O O O RMR-A10

    Brass wiping gland 3 x 1C O O O O RMR-A10

    Small brass wiping gland 1 x 3C O O O O RMR-A105

    Tubular gland 1 x 3C O O O O RMR-A12

    Tubular gland 3 x 1C O O O O RMR-A13

    Small tubular gland 1 x 3C O O O O RMR-A106

    CES5 gland O O O O RMR-A120

    CES5 gland plate 1 x 3C O O O O RMR-A321

    CES5 gland plate adaptor O O O O RMR-A525

    6 x ECON cable termination kit O O O O RMR-A314

    3 x STD ECON end cap O O O O RMR-A370

    3 x ECON cable termination kit O O O O RMR-A315

    3 x ECON end cap capacitors O O O O RMR-A371

    Top entry cables LH cable box (indoor only) v v v v RMR-F302

    Angled gland plate 1 x 3C O O O O RMR-A317

    Split gland plate 1 x 3C O O O O RMR-A318

    Installation items

    Transformer mounting kit v v v v RMR-A/F323

    Extension trunking (to clear radiators) O O O O RMR-A20

    Set of padlocks - 11 no O O O O RMR-A343

    Anti-vandal fixings, including tool O O O O RMR-A344

    Foundation bolts (not required for transformer mounting) O O O O RMR-A22

    Multicore pilot glands O O O O RMR-A342

    Time limit fuses (set of 2 - specify rating as table page 115) O O O O RMR-A17

    RE2c to MU2 installation kit v v v v RMR-A350Extensible busbar chamber 630A O O O O RMR-F369

    Ariel mounting bracket O O O O RMR-A201

    Operational items

    Operating handle b b b b RMR-F345

    LH ring switch control auxiliary sw for motorised mechanismprovision

    v v v v RMR-F328

    LH ring switch termination block for motorised mechanismprovision (not Easergy)

    v v v v RMR-F363

    RH ring switch control auxiliary sw for motorised mechanismprovision

    v v v v RMR-F329

    RH ring switch termination block for motorised mechanismprovision (not Easergy)

    v v v v RMR-F364

    Provision for motorised mechanism circuit breaker v v v v RMR-F543

    Motorised mechanism - specify voltage v v v v RMR-F507

    Shunt trip coil (20-250V DC, 110-250V AC) TLF v v v v RMR-F581

    Shunt trip coil (20-250V DC, 110-250V AC) VIP v v v v RMR-F582

    Ring switch cable neon indication (11-13.8kV) v v v v RMR-F341

    Ring switch cable neon indication (3.3-7.2kV) v v v v RMR-F348

    Circuit breaker neon indication (11-13.8kV) v v v v RMR-F340

    Circuit breaker neon indication (3.3-7.2kV) v v v v RMR-F347

    VAP 6 test unit for VIP 300/30/35 v v v v RMR-A202

    Emergency trip push button v v v v RMR-F339

    Gas pressure switch for remote indication only v v v v RMR-F368

    Key: bStandard feature vFactory fitted accessory OLoose accessory, assembled on site

  • 7/21/2019 Catalogue Ringmaster Part1

    23/7021AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible ring main unitsAccessories

    RE2c-T1

    TFL

    RE2c-T2

    VIP 300

    RE2c-T3

    VIP 30

    RE2c-T4

    VIP 35

    Kit no.

    Mechanical interlocks

    Circuit breaker - key free, earth on v v v v RMR-F337

    Circuit breaker - key free, main off v v v v RMR-F338

    Switch - key free, switch off LH v v v v RMR-F335

    Switch - key free, switch off RH v v v v RMR-F336

    N. B. specify lock symbol at time of ordering (3 digits max) notavailable with motor mechanisms

    Earth fault passage indication (choose provision kit

    and an EFPI required if not using Easergy T200E)

    Phase & earth fault provision for Easergy T200E O O O O RMR-F310

    EFPI provision kit, inside cable box O O O O RMR-A304

    EFPI provision kit, CT outside cable box O O O O RMR-A305

    EFPI provision kit, inside cable box, top entry O O O O RMR-A308

    EFPI provision kit, outside cable box, top entry O O O O RMR-A309

    Bowden RR EFPI and CT O O O O RMR-A422

    Bowden STD EFPI type NB O O O O RMR-A277

    Bowden LV reset EFPI type NB1 O O O O RMR-A278

    Bowden LV reset & alarm type NB O O O O RMR-A279

    Fundamentals ER FIND EFPI and CT O O O O RMR-A57

    N. B. above CTs are ring type for split core - please consultSchneider Electric

    Key: v Factory fitted accessory OLoose accessory, assembled on site

  • 7/21/2019 Catalogue Ringmaster Part1

    24/7022 AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible ring main unit 200 ARE2c-T1

    Multiple transformer feeders or network switching points

    Protection & control - CB

    Overcurrent and earth fault protection using CT operated trip coils with provision for

    time fuse links.

    Protection CTs - 100/50/5A class X

    Transformer ratings

    See table - page 119

    Documents

    Freestanding installation drawing ref: RMINST-22

    Schematic drawing ref: RMSCH-01

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Busbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 630A/200A

    Normal rated voltage 12/13.8kVNormal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Ring switch cable earth switch, 16/21kA 3s

    Transformer earth switch, 3.15kA 3s

    Anti-reflex operating handle

    Extensible (RHS)

    Provision for motorised mechanism LH/RH ring switch with plug interface

    Indication

    Mechanical tripped on fault flag indicator

    Mechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicatorCB auxiliary contacts 1NO 1NC

    CB earth position selected 1NO

    CB earth ON, 1NO

    Test facility

    Integral ring switch test facility

    Cable

    Bottom entry up to 1 x 3C 300mm2

    Bottom entry up to 3 x 1C 630mm2

    Accessories - see table, page 20

    CB, LH, RH motor kits

    LH, RH ring switch indication 1NO 1NC earth On 1NO

    Multi voltage shunt trip coil 20V DC - 250V AC

    Neon indication

    Integral circuit breaker test facility

    Inverted cable boxes LH, CB (indoor only)Transformer mounting kit

    Freestanding tee-off cable box

    Order information

    Code Rating

    RE2c-T1/16 16kA, 12kV, 75kV BIL

    RE2c-T1/21 21kA, 13.8kV, 95kV BIL

    DE60211

    DE60187

  • 7/21/2019 Catalogue Ringmaster Part1

    25/7023AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible ring main unit 200 ARE2c-T2

    Multiple transformer feeders or network switching points

    Protection & control - CB

    Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

    IEC 60255 and BS 142.

    Protection CTs - 200/1A class X

    Setting range:

    Overcurrent: 20-200A

    Earth fault: 2-160A

    Transformer ratings

    See table - page 119

    Documents

    Installation drawing ref: RMINST-22

    Schematic drawing ref: RMSCH-03

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Busbars 630AShort time withstand 16/21kA 3s

    Normal current rating 630A/200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Ring switch cable earth switch, 16/21kA 3s

    Transformer earth switch, 3.15kA 3s

    Anti-reflex operating handle

    Extensible (RHS)

    Provision for motorised mechanism LH/RH ring switch

    Indication

    Mechanical tripped on fault flag indicatorMechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicator

    CB auxiliary contacts 1NO 1NC

    CB earth position selected 1NO

    CB earth ON, 1NO

    Test facility

    Integral ring switch test facility

    Cable

    Bottom entry up to 1 x 3C 300mm2

    Bottom entry up to 3 x 1C 630mm2

    Accessories - see table, page 20

    CB, LH, RH motor kits

    LH, RH ring switch indication 1NO 1NC

    Multi voltage shunt trip coil 20V DC - 250V ACNeon indication

    Inverted cable box LH CB (indoor only)

    Transformer mounting kit

    Freestanding tee-off cable box

    Order information

    Code Rating

    RE2c-T2/16 16kA, 12kV, 75kV BIL

    RE2c-T2/21 21kA, 13.8kV, 95kV BIL

    b

    v

    v

    DE60211

    DE60188

  • 7/21/2019 Catalogue Ringmaster Part1

    26/7024 AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible ring main unit 200 ARE2c-T3

    MV transformer protection

    Protection & control - CB

    Self powered overcurrent relay, VIP 30.

    Protection CTs - 500/200/1A class X

    Setting range: 500/1A

    Overcurrent: 20-200A

    Setting range: 200/1A

    Overcurrent: 8-80A

    Transformer ratings

    See table - page 119

    Documents

    Installation drawing ref: RMINST-22

    Schematic drawing ref: RMSCH-02

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Busbars 630AShort time withstand 16/21kA 3s

    Normal current rating 630A/200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Ring switch cable earth switch, 16/21kA 3s

    Transformer earth switch, 3.15kA

    Anti-reflex operating handle

    Extensible (RHS)

    Provision for motorised mechanism LH/RH ring switch

    Indication

    Mechanical tripped on fault flag indicatorMechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicator

    CB auxiliary contacts 1NO 1NC

    CB earth position selected 1NO

    CB earth ON, 1NO

    Test facility

    Integral ring switch test facility

    Cable

    Bottom entry up to 1 x 3C 300mm2

    Bottom entry up to 3 x 1C 630mm2

    Accessories - see table, page 20

    CB, LH, RH motor kit

    LH, RH ring switch indication 1NO 1NC

    Multi voltage shunt trip coil 20V DC - 250V ACNeon indication

    Inverted cable boxes LH, CB (indoor only)

    Transformer mounting kit

    Freestanding tee-off cable box

    Order information

    Code Rating

    RE2c-T3/16 16kA, 12kV, 75kV BIL

    RE2c-T3/21 21kA, 13.8kV, 95kV BIL

    b

    v

    b

    v

    DE60211

    DE60189

  • 7/21/2019 Catalogue Ringmaster Part1

    27/7025AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible ring main unit 200 ARE2c-T4

    MV transformer protection

    Protection & control - CB

    Protection & control - CB

    Self powered overcurrent and earth fault relay, VIP 35.

    Protection CTs - 500/200/1A class with CH30 core balance CT

    Setting range: 500/1A

    Overcurrent: 20-200A

    Earth fault 25-300A

    Setting range: 200/1A

    Overcurrent: 8-80A

    Earth fault 10-120A

    Transformer ratings

    See table - page 119

    Documents

    Installation drawing ref: RMINST-22

    Schematic drawing ref: RMSCH-15

    Environment

    Indoor/outdoorIP54

    Ratings

    Busbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 630A/200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Ring switch cable earth switch, 16/21kA 3s

    Transformer earth switch, 3.15kA 3s

    Anti-reflex operating handle

    Extensible (RHS)

    Provision for motorised mechanism LH/RH ring switch

    Indication

    Mechanical tripped on fault indicator

    Mechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicator

    CB auxiliary contacts 1NO 1NC

    Earth position selected 1NO

    Earth ON, 1NO

    Test facility

    Integral ring switch test facility

    Cable

    Bottom entry up to 1 x 3C 300mm2

    Bottom entry up to 3 x 1C 630mm2

    Accessories - see table page 20CB, LH, RH motor kit

    LH, RH ring switch indication 1NO 1NC

    Multi voltage shunt trip coil

    Neon indication

    Inverted cable boxes LH, CB (indoor only)

    Transformer mounting

    Freestanding tee-off cable box

    Order information

    Code Rating

    RE2c-T4/16 16kA, 12kV, 75kV BIL

    RE2c-T4/21 21kA, 13.8kV, 95kV BIL

    b

    v

    v

    b

    v

    v

    DE60211

    DE60190

  • 7/21/2019 Catalogue Ringmaster Part1

    28/7026 AMTED399086EN.indd

    Ringmaster range

    Section 1Non-extensible circuit breakers200 ASpecification

    CN2-T1 CN2-T6

    Environment

    Indoor / outdoor b b

    IP54 b b

    Ratings

    Normal rated current 200A b b

    12kV 16kA 3 seconds 75kV BIL b b

    13.8kV 21kA 3 seconds 95kV BIL O O

    Cable earth switch 16kA 3 seconds b b

    Cable earth switch 21kA 3 seconds O O

    Transformer earth switch 3.15kA 3 seconds b b

    Mechanism

    Independent manual b b

    Protection & control - circuit breaker

    CTs dual ratio - 100/50/5A class X b

    CTs ratio - 200/1A class X b

    Overcurrent & earth fault CT operated trip coils b

    Time fuse Link O

    IDMT overcurrent & earth fault relay - VIP 300 b

    20V-250shunt trip coil b b

    Circuit breaker auxiliary switch 1NO 2NC b b

    Indication

    Mechanical ON/OFF b b

    Mechanical EARTH/MAIN b b

    Neon indication (6.6 - 13.8kV) O O

    Auxiliary switch contacts 1NO 2NC b b

    Gas pressure indicator b b

    Test facility

    Integral cable test facility b b

    Standard features

    Operating handle b b

    Transformer earth switch 3.15kA 3 seconds b b

    Cable (see available cable kit accessories)

    Bottom entry up 300mm21 x 3c b b

    Bottom entry up 630mm23 x 1c b b

    Key: bStandard feature OOptional feature

  • 7/21/2019 Catalogue Ringmaster Part1

    29/7027AMTED399086EN.indd

    Ringmaster range

    Section 1Non-extensible circuit breakers200 AAccessories

    CN2-T1 CN2-T6 Kit no.

    Cable kits

    Tee-off cable box v v

    RMR-F47Gland plate 1 x 3C O O RMR-A48

    Gland plate 3 x 1C O O RMR-A49

    Angled gland plates (RMR) O O RMR-A50 Blank

    Blank aluminium gland plate O O RMR-A52

    Brass wiping gland 1 x 3C O O RMR-A10

    Brass wiping gland 3 x 1C O O RMR-A11

    Tubular gland 1 x 3C O O RMR-A12

    Tubular gland 3 x 1C O O RMR-A13

    CES5 gland plate 1 x 3C O O RMR-A132

    Installation items

    Set of padlocks - 6 no O O RMR-A18/6

    Anti-vandal fixings, including tool O O RMR-A19

    Foundation bolts (not required for transformer mounting) O O RMR-A22

    Multicore pilot glands O O RMR-A16

    Time limit fuses (set of 2 - specify rating as table page 115) O RMR-A17Operational items

    Operating handle b b RMR-A23

    Neon indication (6.6-13.8kV) v v RMR-F108

    Neon lamp test unit (including lamp) O O RMR-A24

    Neon lamp O O RMR-A81

    VAP 6 test unit for VIP 300 O RMR-A202

    Mechanical interlocks

    Key free, earth on v v RMR-F85

    Key free, unit off v v RMR-F86

    Transformer earth switch, key free, earth on v v RMR-F110

    N. B. specify lock symbol at time of ordering (3 digits max) notavailable with motor mechanisms

    Order codes

    12kV, 16kA, 75kV BIL, 0.35bG CN2-T1/16 CN2-T6/16

    13.8kV, 21kA, 95kV BIL, 0.8bG CN2-T1/21 CN2-T6/21

    General arrangement drawing - transformer mounted RMINST-04 Page 76 RMINST-04 Page 76

    General arrangement drawing - freestanding RMINST-09 Page 117 RMINST-09 Page 117

    Schematic diagram RMSCH-26 Page 106 RMSCH-11 Page 96

    Key: bStandard feature v Factory fitted accessory OLoose accessory, assembled on site

  • 7/21/2019 Catalogue Ringmaster Part1

    30/7028 AMTED399086EN.indd

    Ringmaster range

    Section 1Non-extensible circuit breaker200 ACN2-T1

    Transformer protection up to 3.5MVA

    Protection & control - CB

    Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

    IEC 60255 and BS142

    Protection CTs - 200/1A class X

    Setting range:

    Overcurrent: 20-200A

    Earth fault: 2A-160A

    Shunt trip coil, 20V DC-250V AC

    Transformer ratings

    See table - page 119

    Documents

    Transformer mounted installation drawing ref: RMINST-04

    Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09

    Schematic drawing ref: RMSCH-26

    Environment

    Indoor/outdoor

    IP54Ratings

    Busbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Tee-off earth switch, 3.15kA 3s

    Cable earth switch, 16/21kA 3s

    Anti-reflex operating handle

    Indication

    Mechanical tripped on fault indicatorMechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicator

    CB auxiliary contacts 1NO 2 NC

    Test facility

    Integral cable test facilities

    Cable

    Bottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm23 x 1c

    Accessories

    Tee-off cable box

    Glands and plates

    Interlocks

    See page 27 for details

    Order information

    Code Rating

    CN2-T1/16 16kA, 12kV, 75kV BIL

    CN2-T1/21 21kA, 13.8kV, 95kV BIL

    b

    v

    v

    DE60250

  • 7/21/2019 Catalogue Ringmaster Part1

    31/7029AMTED399086EN.indd

    Ringmaster range

    Section 1Non-extensible circuit breaker200 ACN2-T6

    Transformer protection up to 1.5MVA

    Protection & control - CB

    Overcurrent and earth fault protection using CT operated trip coils with provision for

    time fuse links.

    Protection CTs - 100/50/5A class X

    Shunt trip coil, 20V DC-250V AC

    Transformer ratings

    See table - page 119

    Documents

    Transformer mounted installation drawing ref: RMINST-04

    Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09

    Schematic drawing ref: RMSCH-11

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Busbars 630A

    Short time withstand 16/21kA 3sNormal current rating 200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Transformer earth switch, 3.15kA 3s

    Cable earth switch, 16/21kA 3s

    Anti-reflex operating handle

    Indication

    Mechanical tripped on fault indicator

    Mechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicatorCB auxiliary contacts 1NO 2 NC

    Test facility

    Integral cable test facilities

    Cable

    Bottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm23 x 1c

    Accessories

    Tee-off cable box

    Glands and plates

    Interlocks

    See page 27 for details

    Order information

    Code Rating

    CN2-T6/16 16kA, 12kV, 75kV BILCN2-T6/21 21kA, 13.8kV, 95kV BIL

    DE60192

  • 7/21/2019 Catalogue Ringmaster Part1

    32/7030 AMTED399086EN.indd

    Ringmaster range

    Section 1Non-extensible switch 630 ASpecification

    SN6-S1 SN6-S2

    Environment

    Indoor / outdoor b b

    IP54 b b

    Ratings

    Normal rated current 630A b b

    13.8kV 21kA 3 seconds 95kV BIL b b

    Cable earth switch 21kA 3 seconds b b

    Transformer earth switch 3.15kA 3 seconds b b

    Mechanism

    Independent manual b b

    Provision for actuator 24V DC b

    Actuator 24V DC O

    Indication

    Mechanical ON/OFF b b

    Mechanical EARTH/MAIN b b

    Neon indication (6.6 - 13.8kV) O O

    Auxiliary switch contacts 1NO 2NC b

    Phase and earth fault detection CTs for Easergy 200E O

    Provision for EFPI O O

    Test facility

    Integral cable test facility b b

    Standard features

    Operating handle b b

    Transformer earth switch 3.15kA 3 seconds b b

    Cable (see available cable kit accessories)

    Bottom entry up 300mm21 x 3c b b

    Bottom entry up 630mm23 x 1c b b

    Key: bStandard feature OOptional feature

  • 7/21/2019 Catalogue Ringmaster Part1

    33/7031AMTED399086EN.indd

    Ringmaster range

    Section 1Non-extensible switch 630 AAccessories

    SN6-S1 SN6-S2 Kit no.

    Cable kits

    Tee-off cable box v v

    RMR-F47Gland plate 1 x 3C O O RMR-A48

    Gland plate 3 x 1C O O RMR-A49

    Angled gland plates (RMR) O O RMR-A50

    Blank aluminium gland plate O O RMR-A52

    Brass wiping gland 1 x 3C O O RMR-A10

    Brass wiping gland 3 x 1C O O RMR-A11

    Tubular gland 1 x 3C O O RMR-A12

    Tubular gland 3 x 1C O O RMR-A13

    CES5 gland plate 1 x 3C O O RMR-A132

    Installation items

    Set of padlocks - 6 no O O RMR-A18/6

    Anti-vandal fixings, including tool O O RMR-A19

    Foundation bolts (not required for transformer mounting) O O RMR-A22

    Multicore pilot glands O O RMR-A16

    Operational itemsOperating handle b b RMR-A23

    Neon indication (6.6-13.8kV) v v RMR-F108

    Neon lamp test unit (including lamp) O O RMR-A24

    Neon lamp O O RMR-A81

    Actuator 24V DC v RMR-F67

    Mechanical interlocks

    Key free, earth on v RMR-F85

    Key free, unit off v RMR-F86

    Transformer earth switch, key free, earth on v v RMR-F110

    N. B. specify lock symbol at time of ordering (3 digits max) notavailable with motor mechanisms

    Order codes

    13.8kV, 21kA, 95kVBIL, 0.8bG SN6-S1/21 SN6-S2/21

    General arrangement drawing - transformer mounted RMINST-04 Page 76 RMINST-04 Page 76

    General arrangement drawing - freestanding RMINST-09 Page 117 RMINST-09 Page 117

    Schematic diagram N/A RMSCH-28 Page 107

    Key: bStandard feature v Factory fitted accessory OLoose accessory, assembled on site

  • 7/21/2019 Catalogue Ringmaster Part1

    34/7032 AMTED399086EN.indd

    Switch disconnector

    Protection & control - CB

    Non-automatic

    Documents

    Installation drawing ref: RMINST-04

    Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09

    Schematic drawing ref: N/A

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Busbars 630A

    Short time withstand 21kA 3s

    Normal current rating 630A

    Normal rated voltage 13.8kV

    Normal rated BIL 95kV

    Operating mechanism

    Independent manual

    Standard features

    Transformer earth switch, 3.15kA 3s

    Cable earth switch, 21kA 3s

    Anti-reflex operating handle

    Indication

    Mechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicator

    Test facility

    Integral cable test facilities

    Cable

    Bottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm23 x 1c

    AccessoriesTee-off cable box

    Neon indication

    Glands and plates

    Interlocks

    See page 31 for details

    Order information

    Code Rating

    SN6-S1/21 21kA, 13.8kV, 95kV BIL

    Ringmaster range

    Section 1Non-extensible switch 630 ASN6-S1

    DE60193

  • 7/21/2019 Catalogue Ringmaster Part1

    35/7033AMTED399086EN.indd

    Switch disconnector

    Protection & control - CB

    Non-automatic

    Documents

    Installation drawing ref: RMINST-04

    Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09

    Schematic drawing ref: RMSCH-28

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Busbars 630A

    Short time withstand 21kA 3s

    Normal current rating 630A

    Normal rated voltage 13.8kV

    Normal rated BIL 95kV

    Operating mechanism

    Independent manualProvision for actuator, 24V DC

    Standard features

    Transformer earth switch, 3.15kA 3s

    Cable earth switch, 21kA 3s

    Anti-reflex operating handle

    Indication

    Mechanical ON/OFF indicator

    Mechanical earth/main indicator

    Gas pressure indicator

    Auxiliary contacts 1NO 2NC

    Earth selected auxiliary contact 1NO

    Test facility

    Integral cable test facilities

    CableBottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm23 x 1c

    Accessories

    Tee-off cable box

    Actuator, 24V DC

    Neon indication

    Glands and plates

    See page 31 for details

    Order information

    Code Rating

    SN6-S2/21 21kA, 13.8kV, 95kV BIL

    Ringmaster range

    Section 1Non-extensible switch 630 ASN6-S2

    DE60194

  • 7/21/2019 Catalogue Ringmaster Part1

    36/7034 AMTED399086EN.indd

    MU2-M1 MU2-M2 MU2-M3

    Environment

    Indoor / outdoor b b b

    IP54 b b b

    Ratings

    Normal rated current 200A b b b

    12kV 16kA 1 second 75kV BIL b b b

    Metering*

    CTs -50/25/5A 0.5s 7.5VA b

    CTs -100/50/5A 0.5s 10VA b

    CTs -200/100/5A 0.5s 10VA b

    VTs -11kV/110V 0.5 50VA b b b

    *CTs - 2 phases (R & B), VTs phase to phase. 6.6kV VTs areavailable - contact Schneider Electric

    Cable (see available cable kit accessories)

    Bottom entry up 300mm21 x 3c O O O

    Bottom entry up 630mm23 x 1c O O O

    Key: bStandard feature OOptional feature

    Ringmaster range

    Section 1Non-extensible metering unit200 ASpecification

  • 7/21/2019 Catalogue Ringmaster Part1

    37/7035AMTED399086EN.indd

    MU2-M1 MU2-M2 MU2-M3 Kit no.

    Cable kits

    Tee-off cable box v v v

    RMR-F47Gland plate 1 x 3C O O O RMR-A48

    Gland plate 3 x 1C O O O RMR-A49

    Angled gland plates (RMU) O O O RMR-A51 Blank

    Blank aluminium gland plate O O O RMR-A52

    Brass wiping gland 1 x 3C O O O RMR-A10

    Brass wiping gland 3 x 1C O O O RMR-A11

    Tubular gland 1 x 3C O O O RMR-A12

    Tubular gland 3 x 1C O O O RMR-A13

    CES5 gland plate 1 x 3C O O O RMR-A132

    Installation items

    Set of padlocks - XX no O O O RMR-A18/6

    Foundation bolts (not required for transformer mounting) O O O RMR-A22

    Multicore pilot glands O O O RMR-A16

    RMU - MU2 installation kit O O O RMR-A350

    Freestanding installation kit O O O RMR-A90Order codes

    12kV, 16kA, 75kV BIL, 0.35bG MU2-M1/16 MU2-M2/16 MU2-M3/16

    General arrangement drawing - t ransformer mounted RMINST-07/08Page 78 - 79

    RMINST-07/08Page 78 - 79

    RMINST-07/08Page 78 - 79

    Schematic diagram RMSCH-14 Page 97 RMSCH-14 Page 97 RMSCH-14 Page 97

    Key: v Factory fitted accessory OLoose accessory, assembled on site

    Ringmaster range

    Section 1Non-extensible metering unit200 AAccessories

  • 7/21/2019 Catalogue Ringmaster Part1

    38/7036 AMTED399086EN.indd

    Ringmaster range

    Section 1Non-extensible metering unit200 AMU2-M1

    Non-extensible metering unit

    Protection & control - CB

    N/A

    Metering transformers

    Metering CTs R & B phases

    50/25/5A

    7.5VA class 0.5s

    Metering VT ph - ph

    11kV/110V 50VA

    class 0.5

    Documents

    Installation drawing ref: RMINST-07/08

    Schematic drawing ref: RMSCH-14

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Short time withstand 16kA 1sNormal current rating 200A

    Normal rated voltage 12kV

    Normal rated BIL 75kV

    Standard features

    Direct coupling between RMU and transformer (optional freestanding cable

    connection)

    Cable connection

    Bottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm23 x 1c

    Accessories

    Cable box

    Glands and plates

    Installation kits

    See page 35 for detailsOrder information

    Code Rating

    MU2-M1/16 16kA, 12kV, 75kV BIL

    b

    v

    v

    b

    v

    v

    DE60210

  • 7/21/2019 Catalogue Ringmaster Part1

    39/7037AMTED399086EN.indd

    Ringmaster range

    Section 1Non-extensible metering unit200 AMU2-M2

    Non-extensible metering unit

    Protection & control - CB

    N/A

    Metering transformers

    Metering CTs R & B phases

    100/50/5A

    10VA class 0.5s

    Metering VT ph - ph

    11kV/110V 50VA

    class 0.5

    Documents

    Installation drawing ref: RMINST-07/08

    Schematic drawing ref: RMSCH-14

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Short time withstand 16kA 1sNormal current rating 200A

    Normal rated voltage 12kV

    Normal rated BIL 75kV

    Standard features

    Direct coupling between RMU and transformer (optional freestanding cable

    connection)

    Cable connection

    Bottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm23 x 1c

    Accessories

    Cable box

    Glands and plates

    Installation kits

    See page 35 for details

    Order information

    Code Rating

    MU2-M2/16 16kA, 12kV, 75kV BIL

    b

    v

    v

    b

    v

    v

    DE60210

  • 7/21/2019 Catalogue Ringmaster Part1

    40/7038 AMTED399086EN.indd

    Ringmaster range

    Section 1Non-extensible metering unit200 AMU2-M3

    Non-extensible metering unit

    Protection & control - CB

    N/A

    Metering transformers

    Metering CTs R & B phases

    200/100/5A

    10VA class 0.5s

    Metering VT ph - ph

    11kV/110V 50VA

    class 0.5

    Documents

    Installation drawing ref: RMINST-07/08

    Schematic drawing ref: RMSCH-14

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Short time withstand 16kA 1sNormal current rating 200A

    Normal rated voltage 12kV

    Normal rated BIL 75kV

    Standard features

    Direct coupling between RMU and transformer

    (optional freestanding cable connection)

    Cable connection

    Bottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm23 x 1c

    Accessories

    Cable box

    Glands and plates

    Installation kits

    See page 35 for detailsOrder information

    Code Rating

    MU2-M3/16 16kA, 12kV, 75kV BIL

    b

    v

    v

    b

    v

    v

    DE60210

  • 7/21/2019 Catalogue Ringmaster Part1

    41/7039AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible circuit breakers200 ASpecification

    CE2-

    T2

    CE2-

    T3

    CE2-

    T7

    CE2-

    T11

    CE2-

    T12

    CE2-

    T13

    CE2-

    T14

    CE2-

    T15

    CE2-

    T16

    CE2-

    T19

    CE2-

    T20

    CE2-

    T21

    Environment

    Indoor / outdoor b b b b b b b b b b b b

    IP54 b b b b b b b b b b b b

    Ratings

    Busbars 630A b b b b b b b b b b b b

    Circuit breaker normal rated current 200A b b b b b b b b b b b b

    12kV 16kA 3 seconds 75kV BIL b b b b b b b b b b b b

    13.8kV 21kA 3 seconds 95kV BIL O O O O O O O O O O O O

    Cable earth switch 16kA 3 seconds b b b b b b b b b b b b

    Cable earth switch 21kA 3 seconds O O O O O O O O O O O O

    Mechanism

    Independent manual b b b b b b b b b b b b

    Provision for actuator 24V DC b b b b

    Actuator 24V DC O O O O

    Operating handle b b b b b b b b b b b b

    Protection systemCTs dual ratio - 500/200/1A class x b b

    Overcurrent relay - VIP 30 b

    CTs dual ratio - 100/50/5A class X b

    CT ratio - 200/1A class X b b b b b b b b b

    Overcurrent & earth fault CT operated trip coils b

    Overcurrent & earth fault relay VIP 35 b

    Time fuse link O

    IDMT overcurrent & earth fault relay - VIP 300 b b b b b b b b b

    20V-250shunt trip coil b b b b b b b b b b b b

    Auxiliary switch 1NO 2NC b b b b b b b b b b b b

    Metering

    CTs -200/100/5A 0.5s 10VA b b b b b b b

    VTs -13.8kV/110V 0.5 10VA 13.8/110V/110V 0.5 50VA 3P 20VA b b

    VTs -11kV/110V 0.5 50VA b b b

    VTs -6.6kV/110V 0.5 50VA b b

    VTs phase - phase, CTs R & B b b b b

    VTs phase - earth, CTs RYB b b b

    Indication

    Mechanical ON/OFF b b b b b b b b b b b b

    Mechanical EARTH/MAIN b b b b b b b b b b b b

    Cable neon indication (6.6 - 13.8kV) O O O O O O O O O O O O

    Auxiliary switch contacts 1NO 2NC b b b b b b b b b b b b

    Earth selected auxiliary contacts 1NO b b b b

    Test facility

    Integral cable test facility b b b b b b b b b b b b

    Cable

    Bottom entry up to 300mm21 x 3c b b b b b b b b b b b b

    Bottom entry up to 630mm23 x 1c b b b b b b b b b b b b

    Top entry cables O O O O O O O O O O O O

    Key: bStandard feature OOptional feature

  • 7/21/2019 Catalogue Ringmaster Part1

    42/7040 AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible circuit breakers200 AAccessories

    CE2-

    T2

    CE2-

    T3

    CE2-

    T7

    CE2-

    T11

    CE2-

    T12

    CE2-

    T13

    CE2-

    T14

    CE2-

    T15

    CE2-

    T16

    CE2-

    T19

    CE2-

    T20

    CE2-

    T21

    Kit no.

    Cable kits

    Gland plate 1 x 3C O O O O O O O O O O O O RMR-A48

    Gland plate 3 x 1C O O O O O O O O O O O O RMR-A49

    Angled gland plates (RMR) O O O O O O O O O O O O RMR-A50

    Blank aluminium gland plate O O O O O O O O O O O O RMR-A52

    Brass wiping gland 1 x 3C O O O O O O O O O O O O RMR-A10

    Brass wiping gland 3 x 1C O O O O O O O O O O O O RMR-A11

    Tubular gland 1 x 3C O O O O O O O O O O O O RMR-A12

    Tubular gland 3 x 1C O O O O O O O O O O O O RMR-A13

    CES5 gland plate 1 x 3C O O O O O O O O O O O O RMR-A132

    Top entry cables standardpanels

    v v v v v RMR-F93

    Top entry cables MU6 only v v v v v v v RMR-F94

    Installation items

    3 phase busbars 630A O O O O O RMR-A14

    3 phase busbars 630A O O O O O O O RMR-A78

    Busbar end kit O O O O O O O O O O O O RMR-A15

    Set of padlocks - 6 no O O O O O O O O O O O O RMR-A18/6

    Foundation bolts (not requiredfor transformer mounting)

    b b b b b b b b b b b b RMR-A22

    Multicore pilot glands O O O O O O O O O O O O RMR-A16

    Time limit fuses (set of 2 - specifyrating as table page 115)

    O RMR-A17

    Operational items

    Operating handle b b b b b b b b b b b b RMR-A23

    Cable neon indication(6.6 - 13.8kV)

    v v v v v v v v v v v v RMR-F108

    Neon lamp test unit(including lamp)

    v v v v v v v v v v v v RMR-A24

    Neon lamp O O O O O O O O O O O RMR-A81

    VAP 6 test unit for VIP 300 O O O O O O O O O O O RMR-A202

    Actuator 24V DC v v v RMR-F67Polarity conversion kit** v v v RMR-F391

    Mechanical interlocks

    Key free, EARTH ON v v v v v v RMR-F85

    Key free, MAIN OFF v v v v v v RMR-F86

    N. B. specify lock symbol at timeof ordering (3 digits max)not available with motormechanisms

    Key: bStandard feature v Factory fitted accessory OLoose accessory, assembled on site**Only required when unit is used with RE2c ring main units and automation.

  • 7/21/2019 Catalogue Ringmaster Part1

    43/7041AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible circuit breakers200 AAccessories

    CE2-

    T2

    CE2-

    T3

    CE2-

    T7

    CE2-

    T11

    CE2-

    T12

    CE2-

    T13

    CE2-

    T14

    CE2-

    T15

    CE2-

    T16

    CE2-

    T19

    CE2-

    T20

    CE2-

    T21

    Kit no.

    Earth fault passage

    indication (choose

    provision kit and an EFPI

    required if not using

    Easergy 200E)

    EFPI provision kit, insidecable box

    O O O O O O O O O O O O RMR-F30

    Bowden STD EFPI type NB O O O O O O O O O O O O RMR-A277

    Bowden LV reset EFPI type NB1O O O O O O O O O O O O RMR-A278

    Bowden LV reset & alarmtype NB2

    O O O O O O O O O O O O RMR-A279

    Bowden RR EFPI and CT O O O O O O O O O O O O RMR-A56

    Fundamentals ER FINDEFPI and CT

    O O O O O O O O O O O O RMR-A57

    Ancillary items

    Tool box O O O O O O O O O O O O RMR-A80

    Order code12kV, 16kA, 75kV BIL, 0.35bG CE2-

    T2/16CE2-T3/16

    CE2-T7/16

    CE2-T11/16

    CE2-T12/16

    CE2-T13/16

    CE2-T14/16

    CE2-T15/16

    CE2-T16/16

    N/A CE2-T20/16

    N/A

    13.8kV, 21kA, 95kV BIL, 0.8bG CE2-T2/21

    CE2-T3/21

    CE2-T7/21

    CE2-T11/21

    CE2-T12/21

    CE2-T13/21

    CE2-T14/21

    CE2-T15/21

    CE2-T16/21

    CE2-T19/21

    N/A CE2-T21/21

    General arrangement drawing RMINST-03Page 74

    RMINST-02

    Page 73

    RMINST-03

    Page 74

    RMINST-02

    Page 73

    RMINST-03

    Page 74

    RMINST-02

    Page 73

    RMINST-02

    Page 73

    RMINST-03

    Page 74

    RMINST-03

    Page 74

    RMINST-02

    Page 73

    RMINST-02

    Page 73

    RMINST-02

    Page 73

    Schematic drawing RMSCH-07Page 92

    RMSCH-09

    Page 94

    RMSCH-06

    Page 91

    RMSCH-09

    Page 94

    RMSCH-19

    Page 100

    RMSCH-20

    Page 101

    RMSCH-20

    Page 101

    RMSCH-07

    Page 92

    RMSCH-07

    Page 92

    RMSCH-35

    Page 109

    RMSCH-35

    Page 109

    RMSCH-36

    Page 110

    Key: bStandard feature v Factory fitted accessory OLoose accessory, assembled on site**Only required when unit is used with RE2c ring main units and automation.

  • 7/21/2019 Catalogue Ringmaster Part1

    44/7042 AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible circuit breaker 200 ACE2-T2

    Feeder protection up to 3.5MVA at 11kV

    Protection & control - CB

    Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

    IEC 60255 and BS142.

    Protection CTs - 200/1A class X

    Shunt trip coil, 20V DC-250V AC

    Setting range:

    Overcurrent: 20-200A

    Earth fault: 2-160A

    Documents

    Installation drawing ref: RMINST-03

    Schematic drawing ref: RMSCH-07

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Busbars 630A

    Short time withstand 16/21kA 3sNormal current rating 200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Standard features

    Cable earth switch, 16/21kA 3s

    Anti-reflex operating handle

    Indication

    Mechanical tripped on fault flag indicator

    Mechanical ON/OFF indicator

    Mechanical earth/main indicator

    Auxiliary contacts,1NO 2NC

    Gas pressure indicator

    Test facility

    Integral cable test facilities

    Cable

    Bottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm23 x 1c

    Accessories

    Neon indication

    Glands and plates

    Interlocks

    Operating handle

    Busbar kit

    Top entry cables

    See page 40 for details

    Order information

    Code Rating

    CE2-T2/16 16kA, 12kV, 75kV BIL

    CE2-T2/21 21kA, 13.8kV, 95kV BIL

    b

    v

    v

    DE60251

  • 7/21/2019 Catalogue Ringmaster Part1

    45/7043AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible circuit breaker 200 ACE2-T7

    Transformer protection up to 1.5MVA at 11kV

    Protection & control - CB

    Overcurrent and earth fault protection using CT operated trip coils with provision

    for time fuse links.

    Protection CTs - 100/50/5A class X

    Shunt trip coil, 20V DC-250V AC

    Documents

    Installation drawing ref: RMINST-03

    Schematic drawing ref: RMSCH-06

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Busbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kVOperating mechanism

    Independent manual

    Standard features

    Cable earth switch, 16/21kA 3s

    Anti-reflex operating handle

    Indication

    Mechanical tripped on fault flag indicator

    Mechanical ON/OFF indicator

    Mechanical earth/main indicator

    Auxiliary contacts,1NO 2NC

    Gas pressure indicator

    Test facility

    Integral cable test facility

    CableBottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm23 x 1c

    Accessories

    Neon indication

    Glands and plates

    Interlocks

    Operating handle

    Busbar kit

    Top entry cables

    See page 40 for details

    Order information

    Code Rating

    CE2-T7/16 16kA, 12kV, 75kV BIL

    CE2-T7/21 21kA, 13.8kV, 95kV BIL

    DE60196

  • 7/21/2019 Catalogue Ringmaster Part1

    46/7044 AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible circuit breaker 200 ACE2-T*

    Feeder protection up to 3.5MVA at 11kV

    Protection & control - CB

    Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

    IEC 60255 and BS142.

    Protection CTs - 200/1A class X

    Shunt trip coil, 20V DC-250V AC

    Setting range:

    Overcurrent: 20-200A

    Earth fault: 2-160A

    Metering transformers

    Metering CTs R & B phases

    200/100/5A

    10VA class 0.5s

    Metering VT

    see below

    Environment

    Indoor/outdoor

    IP54Ratings

    Busbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Anti-reflex operating handle

    Standard features

    Cable earth switch, 16/21kA 3s

    Indication

    Mechanical tripped on fault flag indicator

    Mechanical ON/OFF indicator

    Mechanical earth/main indicatorAuxiliary contacts,1NO 2NC

    Gas pressure indicator

    Test facility

    Integral cable test facility

    Cable

    Bottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm23 x 1c

    Accessories

    Neon indication

    Glands and plates

    Interlocks

    Operating handle

    Busbar kit

    Top entry cablesSee page 40 for details

    Order code

    16kA, 12kV, 75kV BIL21kA, 13.8kV, 95kV BIL

    CE2-T3/16CE2-T3/21

    CE2-T11/16CE2-T11/21

    N/ACE2-T19/21

    CE2-T20/16N/A

    Metering VT information:Phase to phase

    b b

    Phase to earth b b

    6.6kV/110V b

    11kV/110V* b b

    13.8kV/110V b

    General arrangement drawing RMINST-02Page 73

    RMINST-02Page 73

    RMINST-02Page 73

    RMINST-02Page 73

    Schematic diagram RMSCH-09Page 94

    RMSCH-09Page 94

    RMSCH-35Page 109

    RMSCH-35Page 109

    *Please consult Schneider Electric when ordering units with 95kV BIL voltageTel: +44(0)113 290 3500

    b

    v

    v

    b

    v

    v

    b

    v

    DE60252

    (Select VT rating and switchgear rating from table below).

  • 7/21/2019 Catalogue Ringmaster Part1

    47/7045AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible circuit breaker 200 ACE2-T12

    Feeder protection up to 3.5MVA at 11kV

    Protection & control - CB

    Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

    IEC 60255 and BS142.

    Protection CTs - 200/1A class X

    Shunt trip coil, 20V DC-250V AC

    Setting range:

    Overcurrent: 20-200A

    Earth fault: 2-160A

    Documents

    Installation drawing ref: RMINST-03

    Schematic drawing ref: RMSCH-19

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Busbars 630A

    Short time withstand 16/21kA 3sNormal current rating 200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Provision for actuator, 24V DC

    Standard features

    Cable earth switch, 16/21kA 3s

    Anti-reflex operating handle

    Indication

    Mechanical tripped on fault flag indicator

    Mechanical ON/OFF indicator

    Mechanical earth/main indicator

    Auxiliary contacts,1NO 2 NC

    Earth selected auxiliary contact1NOGas pressure indicator

    Test facility

    Integral cable test facility

    Cable

    Bottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm2 3 x 1c

    Accessories

    Actuator, 24V DC

    Neon indication

    Glands and plates

    Interlocks

    Operating handle

    Busbar kit

    Top entry cablesSee page 40 for details

    Order information

    Code Rating

    CE2-T12/16 16kA, 12kV, 75kV BIL

    CE2-T12/21 21kA, 13.8kV, 95kV BIL

    b

    v

    v

    DE60253

  • 7/21/2019 Catalogue Ringmaster Part1

    48/7046 AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible circuit breaker 200 ACE2-T**

    Feeder protection up to 3.5MVA at 11kV

    Protection & control - CB

    Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

    IEC 60255 and BS142.

    Protection CTs - 200/1A class X

    Shunt trip coil, 20V DC-250V AC

    Setting range:

    Overcurrent: 20-200A

    Earth fault: 2-160A

    Metering transformers

    Metering CTs

    200/100/5A

    10VA class 0.5s

    Metering VT

    see below

    Environment

    Indoor/outdoor

    IP54Ratings

    Busbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Provision for actuator, 24V DC

    Standard features

    Cable earth switch, 16/21kA 3s

    Anti-reflex operating handle

    Indication

    Mechanical tripped on fault indicator

    Mechanical ON/OFF indicatorMechanical earth/main indicator

    Auxiliary contacts,1NO 2NC

    Earth selected auxiliary contact1NO

    Gas pressure indicator

    Test facility

    Integral cable test facility

    Cable

    Bottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm2 3 x 1c

    Accessories

    Actuator, 24V DC

    Neon indication

    Glands and plates

    InterlocksOperating handle

    Busbar kit

    Top entry cables

    See page 40 for details

    Order code

    16kA, 12kV, 75kV BIL21kA, 13.8kV, 95kV BIL

    CE2-T14/16CE2-T14/21

    N/ACE2-T21/21

    Metering VT information:Phase to phase

    b

    Phase to earth b

    6.6kV/110V b

    11kV/110V*

    13.8kV/110V b

    General arrangement drawing RMINST-02

    Page 73

    RMINST-02

    Page 73Schematic diagram RMSCH-20

    Page 101RMSCH-36Page 110

    *Please consult Schneider Electric when ordering units with 95kV BIL voltageTel: +44(0)113 290 3500

    b

    v

    v

    b

    v

    v

    b

    v

    DE60254

    (Select VT rating and switchgear rating from table below).

  • 7/21/2019 Catalogue Ringmaster Part1

    49/7047AMTED399086EN.indd

    Ringmaster range

    Section 1Extensible circuit breaker 200 ACE2-T13

    Feeder protection up to 3.5MVA at 11kV

    Protection & control - CB

    Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

    IEC 60255 and BS142.

    Protection CTs - 200/1A class X

    Shunt trip coil, 20V DC-250V AC

    Setting range:

    Overcurrent: 20-200A

    Earth fault: 2-160A

    Metering transformers

    Metering CTs

    200/100/5A

    10VA class 0.5s

    Metering VT ph - ph

    11kV/110V 50VA

    class 0.5

    Documents

    Installation drawing ref: RMINST-02Schematic drawing ref: RMSCH-20

    Environment

    Indoor/outdoor

    IP54

    Ratings

    Busbars 630A

    Short time withstand 16/21kA 3s

    Normal current rating 200A

    Normal rated voltage 12/13.8kV

    Normal rated BIL 75/95kV

    Operating mechanism

    Independent manual

    Actuator, 24V DC

    Standard features

    Cable earth switch, 16/21kA 3sAnti-reflex operating handle

    Indication

    Mechanical tripped on fault indicator

    Mechanical ON/OFF indicator

    Mechanical earth/main indicator

    Auxiliary contacts,1NO 2NC

    Earth selected auxiliary contact1NO

    Gas pressure indicator

    Test facility

    Integral cable test facility

    Cable

    Bottom entry up to 300mm21 x 3c

    Bottom entry up to 630mm23 x 1c

    AccessoriesNeon indication

    Glands and plates

    Interlocks

    Operating handle

    Busbar kit

    Top entry cables

    See page 40 for details

    Order information

    Code Rating

    CE2-T13/16 16kA, 12kV, 75kV BIL

    CE2-T13/21 21kA, 13.8kV, 95kV BIL

    b

    v

    v

    b

    v