catalogue 2012...200%-300% higher than normal blue fin*. *salt-spary testing result is from inventor...

68
CATALOGUE 2012 DC Inverter VRF Air Conditioning Systems VRF

Upload: others

Post on 09-Feb-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

  • C A T A L O G U E 2 0 1 2

    DC Inverter VRF Air Conditioning Systems VRF

  • 22

    YOUR CONDITIONS!

    Since 1916, pioneers in the US market, by designing and manufacturing innovative air conditioning and

    heat pump units. The company’s primary competitive advantage is the use of its know-how expertise gained in the past,

    to build air conditioning systems of the future.

    The key to units' success is that they are specifically designed to enable the modern individual invent his

    own custom made living and working conditions. Regulating effectively the natural environment,

    units can create silently the perfect indoor conditions; your conditions!

    All units carry a2-year Warranty for the compressor and for all parts of the unit.

    units can be found all across Europe in a

    continuously growing selected network of air conditioning

    professionals!

    Their excellent quality and operational efficiency has been

    awarded by the European Union with the highest standard

    certificates.

    Furthermore, the use of the environmental friendly refrigerants

    (freon) do not contribute to the increase of the global warming

    environment.

  • 33

    INV

    Features Pages

    Higher Efficiency 4-5Better Comfort 6-7Higher Reliability 8-9Better Versatility 10-11Easy Installation & Maintenance 12-13

    INV Mini 14-15

    Outdoor Units Pages

    Line up 16-17

    Specifications 18-21

    Indoor Units Pages

    Line up 22-23

    Duct Type 24-27Slim Duct Type 28-29Four-way Cassette Type 30-33One-way Cassette Type 34Floor Standing Type 35Wall Mounted Type 36-37Floor Ceiling Type 38-40Concole Type 41

    Treated Fresh Air Duct Type 42-43

    Control System Pages

    Control Network Sketch 44-45Controllers Comparison 46Comments of Control Functions 47Wired Remote Controller 48-49Wireless Remote Controller 50-51Group Controller 52Smart Zone Controller 53Centralized Controller 54IR Receiver & Key-card Control Board 55Communication Module 56Commissioning Program 57RS-422/485 Repeater 58RS-232 to RS-422/485 Converter 59INVENTOR Eudemon 2009 PC SUIT 60-61

    Piping Design Program 62-63

    Energy Recovery Ventilation 64-66

    Connection Branches 67

    index

  • 4

    ) Significantly improved EER/COP Significantly greater efficiency is realized by the use of DC Inverter Hermetic Scroll Compressors with high-pressure chamber design, improved DC inverter driving technology and large heat exchanger.

    ✍• EER is the efficiency rate= cooling capacity (kW) ÷ cooling power input (kW)

    COP is the coefficient of performance = heating capacity (kW) ÷ heating power input.

    • EER/COP values are based on INVENTOR laboratory testing method The data refers to a 8HP outdoor unit

    2.5

    3.0

    3.5

    4.0

    3.2

    4.07

    2.5

    3.0

    3.5

    3.7

    4.37

    4.0

    HIGHER EFFICIENCY

    Heat Exchanger

    Fan Motor

    Compressor

    ) High efficiency compressorHigh pressure chamber design

    What’s high pressure chamber? The compressed gas that is discharged from the fix scroll, fulfills the whole hermetic chamber of the compressor. Then, when the whole compressor shell has high temperature and there is high pressure inside the compressor, the gas goes out from the exhaust.

    What’s the Benefit of High Pressure Chamber? Direct suction in high pressure chamber compressor. No loss from overheat suction. Increased compressor efficiency up to 3-5%.

    High Pressure

    Fixed Scroll

    Orbiting Scroll

    Intermediate Pressure

    Low Pressure

    Intermediate Pressure Chamber

    Motor in high Pressure

    Suction

    Discharge

    New DC motor (concentrated winding) raises the low frequency performance

    HP chamber structure can raise the high and middle frequency performance

    27% increase of EER

    18% increase of COP

    Formermodel INV

    Formermodel INV

  • 5

    3%

    7%

    Former model INV

    Former model

    Air

    flow

    vol

    ume

    Air

    flow

    vol

    ume

    ) DC Fan motorCompared with the former model, airflow volume is increased 3% with the same single fan and 7% with the new dual fan, but the power consumption is decreased by 5% with the DC inverter motor.

    › 8HP/10HP Models

    › 12HP/14HP Models

    ) Heat Exchanger› The bigger condenser increases

    the heat-exchange area, improving the efficiency.

    Former model:

    2098x38.1x1156

    INV:

    2248x38.1x1190

    INV

    › Compared with the normal fin, the heat exchange efficiency of the louver is increased by 5%.

    Former model:

    Normal flat fin

    INV:

    Louver fin with golden coated

    › Special thickened inner groove copper tube enhances heat exchanging performance.

    › Comparing with normal compressor, the DC Inverter Scroll compressor can save up to 40% of energy consumption in a year.

    › Improved DC inverter motor Low frequency performance is highly raised thanks to the concentrated winding.

    › With stepless power regulating technology, the DC inverter compressor achieves stepless output regulation between 20Hz-120Hz

    0 20

    Com

    pres

    sor

    effic

    ienc

    y

    Distributed winding Concentrated winding

    Rotating speed (/rps)

    7%

    Formermodel INV

    Formermodel INV

  • 6

    ) Quiet Operation› Quiet operation during night time

    The Intelligent adjustment of the outdoor fan control can minimize the operation noise during night time.

    It can be reduced up to 8dB(A). So the operating noise at night is lower, at 50dB(A).

    › Low noise design

    OUTDOOR UNIT

    • HP chamber compressor has lower exhaust pressure fluctuation, so the noise is lower.

    INDOOR UNIT

    › Low noise indoor unit

    BETTER COMFORT

    • The optimized design of the condensing fan blade reduces the air flow turbulence among blades. So, the noise is lower.

    58dB(A) 50dB(A)

    Average 2dB(A) down

    Capacity Operating sound

    Heat load Capacity Operating sound

    Optimized

    Original design New design with higher performance &lower noise 4dB(A) less!

    37dB(A)Office

    Duct Type with High ESP

    37dB(A)Hotel

    Slim Duct Type

    28dB(A)Bedroom

    Wall Mounted Type

    37dB(A)Reception

    Four-way Cassette Type

    Qui

    et c

    ompr

    esso

    r

  • 7

    ) Comfortable› Precise temperature control

    The EXV (Electronic Expansion Valve) of each Indoor unit responds to the loading changes of indoor environment, so it continually adjusts the flow rate of refrigerant.

    Meanwhile, the outdoor unit with DC inverter compressor provides the capacity with certain amount of refrigerant exactly according to the total demands of the indoor units.

    With this Variable Refrigerant Flow (VRF) technol-ogy, we can quickly get a nearly constant room temperature. The typical temperature fluctuation that occurs with a conventional ON/OFF control system is eliminated.

    › Intelligent defrost technology

    Traditional defrost program

    • Simply executes defrosting according to a certain time.

    • The defrost function may still start even if there is no such (defrosting) demand.

    Intelligent defrost program

    • Humanized technology which considers the maxi-mization of energy saving.

    • Defrosting program that is designed under the consideration of heating efficiency and operation reliability.

    • Precise defrosting timing, which is intelligent indeed.

    • It’s an optimized defrosting program, which will be performed only when the system’s pressure is too low. This can obviously lengthen the time gap between two defrost operations and reduce the times of defrosting.

    • Heating capacity loss has been decreased by 75% with highly comfortable heating operation.

    › Individual control

    The set temperature of each room may vary by the individual thermostat control of each indoor unit.

    Cooler Uncomfortable

    Comfortable

    Less Cool Uncomfortable

    Temperature fluctuation of th

    e room

    Non VRF INV

    Hea

    ting

    Cap

    acit

    yH

    eati

    ng C

    apac

    ity

    Heating

    Heating

    Defrosting Defrosting

    Hea

    t Lo

    ss

    10mins 50mins 10mins 10mins50mins

    Time

    Defrosting

    Time

    Defrosting starts if the unit detects frost Defrosting stops after completion

    OFF

    200C

    240C 270C220C

    260C

  • 8

    ) Modular operating› The operating priority sequence of the outdoor unit

    modules will be changed without restart when the system accumulatively operates for 12 hours. This can maximize the service life of the system.

    HIGHER RELIABILITY› Emergency operation

    Each module is an independent sub-system. The whole system won’t fail down even if partial malfunction occurs. If a malfunction occurs at any module, there can be performed an emergency operation. This can simply be achieved by setting up manually the outdoor PCB switches.

    12hours Rotation

    12hours Rotation

    12hours Rotation

    12hours Rotation

    Operating

    Malfunction Emergency Operation

    ) Continuous operation of indoor unitsEach indoor unit is controlled individually on the system network. This allows all indoor units to continue operating even if an error occurs at any indoor unit on the VRF system.

    Failure

    ) Wide voltage range operationThe unit can safely operate within 342V-456V

    ) Power supply securityWith power supply security, the outdoor unit will start auto-protection if the power voltage or the current is out of the normal range. Protection will be relived automatically if the power condition resumes normal.342V 456V

    Safe operation range

  • 9

    ) PCB protection designWith unique high efficiency radiating air-dust design, the outdoor electric box is designed as water-proof, dust-proof, damp-proof and well –ventilated. This can ensure the required condition for the electric elements even in tropi-cal conditions. Also, it improves the system’s reliability and service life.

    ) Anti-corrosionThe primary material of Golden Fin is Al-Mn (Aluminum-Manga-nese) anti-rust alloy, which is coated with the Golden Protection Layer (Components: Epoxy Resin & Modified Acrylic, Silicon free). The anti-corrosive performance in salt-spray testing is 200%-300% higher than normal Blue Fin*.

    *Salt-spary testing result is from INVENTOR materials chemistry testing laboratory

    ) New generation of oil return controlThe pressure control achieves an optimized oil return of the system. As a result, the operating life of the compressor is greatly improved.

    Electric Box

    Baffle

    Electric Box Cover

    Guide louver

    Positive pressure

    Air inlet

    Front pane

    Air outlet

    Negative pressure

    Hydrophilic Layer

    Golden Protection Layer (Epoxy resin & Modified Acrylic)

    Al-Mn-corrosive alloy

    ) High efficiency oil-balanced technologyHigh-pressure chamber compressor with oil-balanced pipe can automatically drain out the excess oil. This can prevent an oil-unbalance between the compressors.

    › New patented oil separator allows the oil separating efficiency up to 99%.

    › Oil equalizing pipe connection designed at the outside of the module allows high reliability.

    Before Oil Balanced After Oil Balanced

    Backflow

    Suction pipe

    Discharge pipe

    Auto-oil pipe

    Compressors

    Oil storage tank

    Oil equalizing pipe Oil equalizing pipe

  • 10

    ) Long piping design› Maximum total piping length --- 500m

    › Maximum actual piping length --- 150m

    › Maximum equivalent piping length --- 175m

    › Maximum height difference between indoor units --- 15m

    › Maximum height difference between outdoor and indoor units --- 50m*

    › Maximum piping length from first indoor branch to the farthest indoor unit --- 40m

    * This value is based on the case that the outdoor unit is located above the indoor unit. If the outdoor unit is located underneath the indoor unit, the value is 40m.

    ) Wide operation rangeThe unit can operates in wide range, greatly reducing the ambient temperature limitation.

    ✍• If the required capacity of indoor units is 50% higher than the outdoor unit,

    the cooling range may be lower up to –150C

    • If the required capacity of indoor units is 50% lower than the outdoor unit, the cooling range may be up to –50C.

    BETTER VERSATILITY) Higher Static pressure

    of outdoor unitThe maximum external static pressure (ESP) of the outdoor fan can reach up to 75Pa*.

    The outdoor unit can be installed in the equipments room of high buildings.

    * Default ESP of the product is 40Pa. If higher ESP is required, please contact us.

    Heating

    Cooling

    15

    0m

    40

    m

    50

    m1

    5m

  • 11

    ) Compact DesignCompact size has been achieved by significantly reducing the width of the outdoor units compared to previous models.

    Former model (8HP) INV (8HP)

    Former model (8HP + 8HP) INV (16HP)

    ) Modular outdoor unit design› Various combinations from 8HP to 64HP with 2HP increments.

    › Max capacity of outdoor unit is 180kW (4 x modules)

    ) Various combinations

    › Up to 110 sets of indoor units can be connected**For the standard model that 4 models connect in parallel, up to 64 indoor units can be connected. If more indoor units are required to be connected please contact us.

    › 12 types and 69 models.

    › Maximum diversity is 135%

    17

    72

    mm

    880mm990mm

    16

    70

    mm

    770mm930mm

    17

    72

    mm

    880mm(990+990)mm

    16

    70

    mm

    770mm1340mm

    17%reduction

    41%reduction

    Floor area: 0,87m2 Floor area: 0,72m2

    Floor area: 1,74m2 Floor area: 1,03m2

  • 12

    ) Easier maintainability › Special-designed elecric box.

    The electric box can be opened by inverting downwards, for easy maintenance.

    › Error display & Self-diagnostics system.

    Any malfunction can be judged by the LED display that is on the main board (different combinations of ON/OFF or BLINK).

    • Self diagnostics • LED display on the • LED display on the system display connection board connection board

    EASY INSTALATION & MAINTENANCE

  • 13

    ) Easier transportation & installations› Light weight

    Former model (8HP+8HP): INV (16HP):

    240x2=480kg 370kg

    › Transportation by forklift

    › Compact design

    With compact design, the outdoor unit can be carried to the roof of a building through elevator. No crane is needed.

    Traditional Central Air Conditioner

    › Optimized base frame

    Optimized base frame. The locating and fixing of the outdoor unit during installation is more convenient and reliable.

    › Five-Way piping connection

    • Piping and wiring are available to the front and back, left and right, bottom.

    • The five-way piping connection reduces installation difficulty and cost. Improves the installation efficiently.

    INV

  • 14

    ) Flexible Design › Long piping design

    • Maximum total piping length --- 150m

    • Maximum actual piping length --- 70m

    • Maximum equivalent piping length --- 80m

    • Maximum height difference between indoor units --- 10m

    • Maximum height difference between outdoor and indoor units --- 30m*

    • Maximum piping length from first indoor branch and the farthest indoor unit --- 25m

    * This value is based on the outdoor unit to be located above the indoor unit. If the outdoor unit is located underneath the indoor unit, the value is 25m.

    › Compact Design

    Compact size has been achieved by significantly reducing the width of the outdoor units compared to previous models.

    Former Model INV

    ) Wide voltage range operationThe unit can safely operate within the power supply voltage of 185V to 264V.

    INV MINI

    70

    m

    25

    m

    30

    m1

    0m

    12

    50

    mm

    1100mm 340mm

    12

    50

    mm

    950mm340mm

    Floor area: 0,374m2 Floor area: 0,323m2

    14%reduction

    185V 264V

    Safe operation range

    70

    m

    25

    m

    30

    m

    12

    50

    mm

    950mmmmmm

  • 15

    ) High efficiencyDC inverter rotary compressor

    ) Easy InstallationWhen total piping length is less than 50m [(A+B+C+D+a+b+c+d) ≤ 50m], no additional refrigerant is required.

    ) Powerful heating in low temperatureWhen outdoor ambient temperature is low, the system can automatically increase the heating effect according to its judgment on parameters. Heating performance is improved by 15%, which brings great comfort.

    ) Capacity

    ) ComfortAuto quiet operation

    The unit is ensured to operate with the lowest noise due to the ultra-low fan speed and auto adjustment according to system parameters. The operation noise of the unit is reduced by 3dB(A) at lower loading.

    3dB(A)

    Ope

    rati

    on n

    oise

    MODEL INV-Pd100W/NaB-K INV-Pd120W/NaB-K INV-Pd140W/NaB-K INV-Pd160W/NaB-K

    CapacityHP 3.5 4.0 5.0 6.0kW 10 12 14 16

    Power Supply 1Phase, 220-240V, 50Hz

  • 16

    OUTDOOR UNITS LINEUPMODEL INV-Pdm224W/NaB-M (8HP)

    INV-Pdm280W/NaB-M (10HP)

    INV-Pdm335W/NaB-M (12HP)

    INV-Pdm400W/NaB-M (14HP)

    INV-Pdm450W/NaB-M (16HP)

    INV-Pdm224W/NaB-M (8HP)

    INV-Pdm228W/NaB-M (10HP)

    INV-Pdm335W/NaB-M (12HP)

    INV-Pdm400W/NaB-M (14HP)

    INV-Pdm450W/NaB-M (16HP)

    INV-Pdm504W2/NaB-M (18HP)

    INV-Pdm560W2/NaB-M (20HP)

    INV-Pdm615W2/NaB-M (22HP)

    INV-Pdm670W2/NaB-M (24HP)

    INV-Pdm730W2/NaB-M (26HP)

    INV-Pdm785W2/NaB-M (28HP)

    INV-Pdm850W2/NaB-M (30HP)

    INV-Pdm900W2/NaB-M (32HP)

  • 17

    MODEL INV-Pdm224W/NaB-M (8HP)INV-Pdm280W/NaB-M (10HP)

    INV-Pdm335W/NaB-M (12HP)

    INV-Pdm400W/NaB-M (14HP)

    INV-Pdm450W/NaB-M (16HP)

    INV-Pdm950W3/NaB-M (34HP)

    INV-Pdm1008W3/NaB-M (36HP)

    INV-Pdm1605W3/NaB-M (38HP)

    INV-Pdm1130W3/NaB-M (40HP)

    INV-Pdm1180W3/NaB-M (42HP)

    INV-Pd-m11253W3/NaB-

    M (44HP)

    INV-Pdm1300W3/NaB-M (46HP)

    INV-Pd-m11350W3/NaB-

    M (48HP)

    INV-Pdm1405W4/NaB-M (50HP)

    INV-Pdm1456W4/NaB-M (52HP)

    INV-Pdm1512W4/NaB-M (54HP)

    INV-Pdm1570W4/NaB-M (56HP)

    INV-Pdm1650W4/NaB-M (58HP)

    INV-Pdm1700W4/NaB-M (60HP)

    INV-Pdm1750W4/NaB-M (62HP)

    INV-Pdm1800W4/NaB-M (64HP)

  • 18

    SPECIFICATIONSINV Mini

    RATING CAPACITY HP 3.5 4 5 6

    MODEL INV-Pd 100W/NaB-K INV-Pd 120W/NaB-K INV-Pd 140W/NaB-K INV-Pd 160W/NaB-K

    Combination units - - - -

    Connectable indoor unit

    Maximum 6 7 8 9Cooling Capacity (kW) 5.0-13.5 6.0-16.2 7.0-18.9 8.0-21.6

    Power supply 1-Phase, 220-240V, 50Hz

    CapacityCooling (kW) 10.0 12.0 14.0 16.0Heating (kW) 11.0 14.0 15.4 17.6

    Power consumptionCooling (kW) 2.86 3.50 4.36 4.98Heating (kW) 2.60 3.40 4.05 4.85

    Compressor Type DC inverter dual-rotor type compressor x 1

    Airflow ratem3/h 6200 6200 6000 6400CFM 3642 3642 3525 3759

    Sound pressure level (dB(A)) 58 58 58 58Dimensions WxDxH (mm) 950x340x1250 950x340x1250 950x340x1250 950x340x1250Net weight

    kg111 111 111 115

    Refrigerant charge 7.5 7.5 7.5 7.5

    Operation range°C Cooling: 10 to 48, Heating: -20 to 27°F Cooling: 18 to 118.4, Heating: -4 to 81

    Connection pipe diameter

    Gasinch

    5/8 5/8 5/8 3/4

    Liquid 3/8 3/8 3/8 3/8

    Basic ModuleRATING CAPACITY HP 8 10 12 14 16

    MODEL INV-Pdm 224W/NaB-MINV-Pdm 280W/

    NaB-MINV-Pdm 335W/

    NaB-MINV-Pdm 400W/

    NaB-MINV-Pdm 450W/

    NaB-M

    Combination units -

    Connectable indoor unit

    Maximum 14 14 16 16 16Cooling Capacity (kW) 11.2 - 30.2 14.0 - 37.8 16.8 - 45.2 20.0 - 54.0 22.5 - 60.8

    Power supply 3-Phase, 380-415V, 50Hz

    CapacityCooling (kW) 22.4 28.0 33.5 40.0 45.0Heating (kW) 25.0 31.5 37.5 45.0 50.0

    Power consumptionCooling (kW) 5.52 7.52 9.23 12.45 14.32Heating (kW) 5.82 7.70 9.38 11.2 13.90

    Compressor Configration* DCx1+Cx1 DCx1+Cx2

    Airflow ratem3/h 10000 10000 13000 13000 13000CFM 5874 5874 7636 7636 7636

    Sound pressure level (dB(A)) 58 58 60 61 61Dimensions WxDxH mm 930x770x1670 1340x770x1670Net weight

    kg255 255 350 350 370

    Operating range 275 275 380 380 400Refrigerant charge 12 13 15 16 17

    Operation range°C Cooling: -5 to 48, Heating: -20 to 27 °F Cooling: 23 to 118.4, Heating: -4 to 81

    Connection pipe diameter

    Gasinch

    7/8 7/8 9/8 9/8 9/8

    Liquid 3/8 3/8 1/2 1/2 1/2

    *DC: DC inverter scroll compressor C: Constant speed scroll compressor

  • 19

    Combination ModulesRATING CAPACITY HP 18 20 22 24 26

    MODEL INV-Pdm 504W2/NaB-MINV-Pdm 560W2/

    NaB-MINV-Pdm 615W2/

    NaB-MINV-Pdm 670W2/

    NaB-MINV-Pdm 730W2/

    NaB-M

    Combination units

    INV-Pdm 224W/NaB-M

    INV-Pdm 280W/NaB-M

    INV-Pdm 280W/NaB-M

    INV-Pdm 280W/NaB-M

    INV-Pdm 280W/NaB-M

    INV-Pdm 335W/NaB-M

    INV-Pdm 280W/NaB-M

    INV-Pdm 400W/NaB-M

    INV-Pdm 280W/NaB-M

    INV-Pdm 450W/NaB-M

    Connectable indoor unit

    Maximum 30 32 32 32 32Cooling Capacity (kW) 25.2-68 28.0-75.6 30.8-83.0 33.5-90.5 36.5-98.6

    Power supply 3-Phase, 380-415V, 50Hz

    CapacityCooling (kW) 50.4 56.0 61.5 68.0 73.0Heating (kW) 56.5 63.0 69.0 76.5 81.5

    Power consumptionCooling (kW) 13.04 15.04 16.75 19.97 21.84Heating (kW) 13.52 15.40 17.08 18.90 21.60

    Compressor Configration* (DCx1+Cx1)x2 (DCx1+Cx1)+(DCx1+Cx2)

    Airflow rate m3/h 10000x2 10000+13000 CFM 5874x2 5874+7636

    Sound pressure level (dB(A)) 62 62 62 62 63Dimensions WxDxH mm (930x770x1670)+(930x770x1670) (930x770x1670)+(1340x770x1670)Net weight

    kg255+255 255+255 255+350 255+350 255+370

    Refrigerant charge 13+13 13+15 13+15 13+16 13+17

    Operation range°C Cooling: -5 to 48, Heating: -20 to 27 °F Cooling: 23 to 118.4, Heating: -4 to 81

    Connection pipe diameter

    GasInch

    9/8 9/8 9/8 9/8 11/8

    Liquid 5/8 5/8 5/8 3/4 3/4

    RATING CAPACITY HP 28 30 32 34 36

    MODEL INV-Pdm 785W2/NaB-MINV-Pdm 850W2/

    NaB-MINV-Pdm 900W2/

    NaB-MINV-Pdm 950W3/

    NaB-MINV-Pdm 1008W3/

    NaB-M

    Combination units

    INV-Pdm 335W/NaB-M

    INV-Pdm 450W/NaB-M

    INV-Pdm 400W/NaB-M

    INV-Pdm 450W/NaB-M

    INV-Pdm 450W/NaB-M

    INV-Pdm 450W/NaB-M

    INV-Pdm 280W/NaB-M

    INV-Pdm 280W/NaB-M

    INV-Pdm 400W/NaB-M

    INV-Pdm 280W/NaB-M

    INV-Pdm 280W/NaB-M

    INV-Pdm 450W/NaB-M

    Connectable indoor unit

    Maximum 32 32 32 48 48Cooling Capacity (kW) 39.3-106.0 42.5-114.8 45.0-121.5 47.5-128.3 50.4-136.1

    Power supply 3-Phase, 380-415V, 50Hz

    CapacityCooling (kW) 78.5 85.0 90.0 96.0 101.0Heating (kW) 87.5 95.0 100.0 108.0 113.0

    Power consumptionCooling (kW) 23.55 26.77 28.64 27.49 29.36Heating (kW) 23.28 25.10 27.8 26.60 29.30

    Compressor Configration* (DCx1+Cx2)x2 [(DCx1+Cx1)x2]+(DCx1+Cx2)

    Airflow rate m3/h 13000x2 10000x2+13000 CFM 7636x2 5874x2+7636

    Sound pressure level (dB(A)) 63 63 63 64 64Dimensions WxDxH mm (1340X770X1670)+(1340X770X1670) (930x770x1670)+(930x770x1670)+(1340x770x1670)Net weight

    kg350+370 350+370 370+370 255+255+350 255+255+370

    Refrigerant charge 15+16 18+17 17+17 13+13+16 13+13+17

    Operation range°C Cooling: -5 to 48, Heating: -20 to 27 °F Cooling: 23 to 118.4, Heating: -4 to 81

    Connection pipe diameter

    GasInch

    11/8 11/8 11/8 11/8 11/8

    Liquid 3/4 3/4 3/4 3/4 3/4

    *DC: DC inverter scroll compressor C: Constant speed scroll compressor

  • 20

    RATING CAPACITY HP 50 52 54 56 58

    MODEL INV-Pdm1405W4/NaB-MINV-Pdm1456W4/

    NaB-MINV-Pdm1512W4/

    NaB-MINV-Pdm1570W4/

    NaB-MINV-Pdm1650W4/

    NaB-M

    Combination units

    INV-Pdm280W/ NaB-M

    INV-Pdm280W/ NaB-M

    INV-Pdm400W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm280W/ NaB-M

    INV-Pdm280W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm280W/ NaB-M

    INV-Pdm335W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm280W/ NaB-M

    INV-Pdm400W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm280W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    Connectable indoor unit

    Maximum 64 64 64 64 64Cooling Capacity (kW) 70.3-189.7 72.8-196.6 75.6-204.1 78.5-212.0 82.5-222.8

    Power supply 3-Phase, 380-415V, 50Hz

    CapacityCooling (kW) 141.0 146.0 151.5 155.0 163.0Heating (kW) 158.0 163.0 169.0 176.5 181.5

    Power consumption

    Cooling (kW) 41.84 43.68 45.39 48.61 50.48Heating (kW) 40.05 43.20 44.88 46.70 49.90

    Compressor Configration* [(DCx1+Cx1) x2]+[(DCx1+Cx2)x2] (DCx1+Cx1)+[(DCx1+Cx2) x3]

    Airflow rate m³/h 10.000x2+13.000x2 10.000+13.000x3 CFM 5.874x2+7.636x2 5.874+7.636x3

    Sound pressure level (dB(A)) 65 65 65 65 65

    Dimensions WxDxH mm (930x770x1.670)+(930x770x1.670)+ +(1.340X770X1670)+(1.340X770X1.670)

    (930x770x1.670)+(1.340x770x1.670)+ +(1.340x770x1670)+(1.340x770x1.670)

    Net weightkg

    255+255+350+370 255+255+350+370 255+350+370+370 255+350+370+370 255+370+370+370

    Refrigerant charge 13+13+16+17 13+13+17+17 13+15+17+17 13+16+17+17 13+17+17+17

    Operation range°C Cooling: -5 to 48, Heating: -20 to 27°F Cooling: 23 to 118.4, Heating: -4 to 81

    Connection pipe diameter

    GasInch

    1” 3/4 1” 3/4 7/4 2” 1/8 2” 1/8

    Liquid 7/8 7/8 7/8 1 1

    *DC: DC inverter scroll compressor C: Constant speed scroll compressor

    Combination ModulesRATING CAPACITY HP 38 40 42 44 46 48

    MODEL INV-Pdm 1065W3/NaB-M

    INV-Pdm 1130W3/NaB-M

    INV-Pdm 1180W3/NaB-M

    INV-Pdm 1235W3/NaB-M

    INV-Pdm 1300W3/NaB-M

    INV-Pdm 1350W3/NaB-M

    Combination units

    INV-Pdm280W/NaB-M

    INV-Pdm335W/NaB-M

    INV-Pdm450W/NaB-M

    INV-Pdm280W/NaB-M

    INV-Pdm400W/NaB-M

    INV-Pdm450W/NaB-M

    INV-Pdm280W/NaB-M

    INV-Pdm450W/NaB-M

    INV-Pdm450W/NaB-M

    INV-Pdm335W/NaB-M

    INV-Pdm450W/NaB-M

    INV-Pdm450W/NaB-M

    INV-Pdm400W/NaB-M

    INV-Pdm450W/NaB-M

    INV-Pdm450W/NaB-M

    INV-Pdm450W/NaB-M

    INV-Pdm450W/NaB-M

    INV-Pdm450W/NaB-M

    Connectable indoor unit

    Maximum 48 48 48 48 48 48Cooling Capacity (kW) 53.3-143.8 56.5-152.6 59.0-159.3 61.81-166.7 65.0-175.5 67.5-182.3

    Power supply 3-Phase, 380-415V, 50Hz

    CapacityCooling (kW) 106.5 113.0 118.0 123.5 130.0 135.0Heating (kW) 119.0 126.5 131.5 137.5 145.0 150.0

    Power consumption

    Cooling (kW) 31.07 34.29 36.16 37.87 41.09 42.96Heating (kW) 30.98 32.80 35.50 37.18 39.00 41.70

    Compressor Configration* (DCx1+Cx1)+[(DCX1+Cx2)x2] (DCx1+Cx2)x3

    Airflow rate m3/h 10000+13000x2 13000X3 CFM 5874+7636x2 7636x3

    Sound pressure level (dB(A)) 64 64 64 65 65 65Dimensions WxDxH mm (930x770x1670)+(1340x770x1670)+(1340x770x1670) (1340x770x1670)+(1340x770x1670)+(1340x770x1670)Net weight

    kg255+350+370 350+370+370 350+370+370 370+370+370

    Refrigerant charge 13+15+17 13+16+17 13+17+17 15+17+17 16+17+17 17+17+17

    Operation range°C Cooling: -5 to 48, Heating: -20 to 27°F Cooling: 23 to 118.4, Heating: -4 to 81

    Connection pipe diameter

    GasInch

    1” 5/8 1” 5/8 1” 5/8 1” 5/8 1” 5/8 1” 5/8

    Liquid 3/4 3/4 3/4 3/4 3/4 3/4

  • 21

    Combination ModulesRATING CAPACITY HP 60 62 64MODEL INV-Pdm1700W4/NaB-M INV-Pdm1750W4/NaB-M INV-Pdm1800W4/NaB-M

    Combination units

    INV-Pdm335W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm400W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    INV-Pdm450W/ NaB-M

    Connectable indoor unit

    Maximum 64 64 64Cooling Capacity (kW) 85.0-230.0 87.5-236.3 80.0-243.0

    Power supply 3-Phase, 380-415V, 50Hz

    CapacityCooling (kW) 168.0 175.0 180.0Heating (kW) 187.5 195.0 200.0

    Power consumption

    Cooling (kW) 52.19 55.41 57.21Heating (kW) 51.80 52.90 55.60

    Compressor Configration* (DCx1+Cx2) x4

    Airflow rate m3/h 13000x4 CFM 7636x4

    Sound pressure level (dB(A)) 66 66 66Dimensions WxDxH mm (1340x770x1670)+(1340x770x1670)+(1340x770x1670)+(1340x770x1670)Net weight

    kg350+370+370+370

    Refrigerant charge 15+17+17+17 16+17+17+17 17+17+17+17

    Operation range°C Cooling: -5 to 48, Heating: -20 to 27°F Cooling: 23 to 118.4, Heating: -4 to 81

    Connection pipe diameter

    GasInch

    2” 1/8 2” 1/8 2” 1/8

    Liquid 1 1 1

    *DC: DC inverter scroll compressor C: Constant speed scroll compressor

  • 22

    INDOOR UNITS LINEUP

    CAPACITY INDEX (kW) 2.2 2.8 3.6 4.5 5.0 5.6 6.3

    Duct Type(EXV Integrated)

    Slim Duct Type(EXV Integrated)

    Four-way Cassette Type(EXV Integrated)

    Compact Four-wayCassette Type(EXV Separated)

    One-way Cassette Type(EXV Separated)

    Floor Standing Type

    Concole Type

    Floor Ceiling Type(EXV Integrated)

    Wall Mounted Type(EXV Separated)

    Wall Mounted Type(EXV Integrated)

    Treated Fresh AirDuct Type

  • 23

    7.1 8.0 9.0 10.0 11.2 12.5 14.0 22.4 28.0

  • 24

    ) Highly flexible installation› Highly flexible installation is possible to satisfy various needs

    Installation examples

    › Flexible and easy to install in type-L, type-U and in large rooms

    ) Fresh air function option for 5.6kW and above units

    DUCT TYPE

    Supply air duct Indoor unit

    Canvas air duct

    Long life filter

    Supply air duct

    Return air inlet

    Long life filterIndoor unit

    Maintenance access

    eeds

  • 25

    ) Drain pump lift reaches 1000mmOnly available for INV(L)-R*PS/NaB-K

    ) Easy maintenance› Long life and washable filter with buckles can be easily disassembled from each direction.

    › Compact size has been achieved by significantly reducing the width of the outdoor units compared to previous models.

    Former structure: push pull type New structure: with buckles

    The former structure is not easy to disassembly. The new structure makes the disassembly convenient.

    ) HIGHER ESP & lower noiseThe ESP is obviously upgraded while the noise is almost at the same level as before.

    Former model Low ESP of new model Former model New model (In low ESP)

    High ESP of new model

    ) Key-card control

    ES

    P (P

    a)

    Sou

    nd le

    vel (

    dB(A

    ))

    Model (kW) Model (kW)

  • 26

    Duct Type (With drain water pump)MODEL INV-R22PS/NaB-K INV-R28PS/NaB-K INV-R36PS/NaB-K INV-R45PS/NaB-K

    Power supply 1-Phase, 220-240V, 50Hz

    CapacityCooling (kW) 2.2 2.8 3.6 4.5Heating (kW) 2.5 3.2 4.0 5.0

    Power consumption (W) 75 80 80 140

    Airflow rate m3/h 450 570 570 700 CFM 265 335 336 412

    Sound pressure level (H/M/L) (dB(A)) 37/35/33 39/37/35 39/37/35 40/38/36Standard Esp (H/L) (Pa) 50/20 50/20 50/20 50/20Dimensions (WxDxH) (mm) 880x665x250 980x721x266Net weight (Kg) 28.5 30.5 30.5 36

    Connection pipe

    Gas (Flare)Inch 3/8 3/8 1/2 1/2mm φ9.52 φ9.52 φ12.7 φ12.7

    Liquid (Flare)Inch 1/4 1/4 1/4 1/4mm φ6.35 φ6.35 φ6.35 φ6.35

    Drain PipeExternal dia. mm φ20 φ20 φ20 φ30Thickness mm 1.5 1.5 1.5 1.5

    MODEL INV-R56PS/NaB-KINV-R71PS/

    NaB-KINV-R90PS/

    NaB-KINV-R112PS/

    NaB-KINV-R140PS/

    NaB-K

    Power supply 1-Phase, 220-240V, 50Hz

    CapacityCooling (kW) 5.6 7.1 9.0 11.2 14.0Heating (kW) 6.3 8.0 10.0 12.5 15.0

    Power consumption (W) 240 240 360 360 500

    Airflow rate m3/h 1.000 1.100 1.700 1.700 2.000 CFM 589 647 1.000 1.000 1.177

    Sound pressure level (H/M/L) (dB(A)) 44/42/40 45/43/41 48/46/44 48/46/44 50/48/46Standard Esp (H/L) (Pa) 60/30 60/30 80/40 80/40 100/50Dimensions (WxDxH) (mm) 1155x756x300 1425x736x300Net weight (Kg) 51 51 64 64 65.5

    Connection pipe

    Gas (Flare)Inch 5/8 5/8 5/8 5/8 5/8mm φ15.9 φ15.9 φ15.9 φ15.9 φ15.9

    Liquid (Flare)Inch 3/8 3/8 3/8 3/8 3/8mm φ9.52 φ9.52 φ9.52 φ9.52 φ9.52

    Drain PipeExternal dia. mm φ30 φ30 φ30 φ30 φ30Thickness mm 1.5 1.5 1.5 1.5 1.5

  • 27

    Duct Type (Without drain water pump)MODEL IN-R22P/NaB-K

    INV-R28P/NaB-K

    INV-R36PS/NaB-K

    INV-R45P/NaB-K

    INV-R56P/NaB-K

    INV-R71P/NaB-K

    Power supply 1-Phase, 220-240V, 50Hz

    CapacityCooling (kW) 2.2 2.8 3.6 4.5 5.6 7.1Heating (kW) 2.5 3.2 4.0 5.0 6.3 8.0

    Power consumption (W) 75 80 80 140 240 240

    Airflow rate m3/h 450 570 570 700 1.000 1.100 CFM 265 335 336 412 589 647

    Sound pressure level (H/M/L) (dB(A)) 37/35/33 39/37/35 39/37/35 40/38/36 44/42/40 45/43/41Standard Esp (H/L) (Pa) 50/20 50/20 50/20 50/20 60/30 60/30Dimensions (WxDxH) (mm) 880x665x250 980x721x266 1155x756x300Net weight (Kg) 27 28.5 28.5 34 49 49

    Connection pipe

    Gas (Flare)Inch 3/8 3/8 1/2 1/2 5/8 5/8mm φ9.52 φ9.52 φ12.7 φ12.7 φ15.9 φ15.9

    Liquid (Flare)Inch 1/4 1/4 1/4 1/4 3/8 3/8mm φ6.35 φ6.35 φ6.35 φ6.35 φ9.52 φ9.52

    Drain PipeExternal dia. mm φ20 φ20 φ20 φ30 φ30 φ30Thickness mm 1.5 1.5 1.5 1.5 1.5 1.5

    MODEL INV-R90P/NaB-KINV-R112P/

    NaB-KINV-R140P/

    NaB-KINV-R224P/

    NaB-MINV-R280P/

    NaB-M

    Power supply 1-Phase, 220-240V, 50Hz 3-Phase, 380-450V, 50Hz

    CapacityCooling (kW) 9.0 11.2 14.0 22.4 28.0Heating (kW) 10.0 12.5 15.0 25.0 31.0

    Power consumption (W) 360 360 500 1.600 1.600

    Airflow rate m3/h 1.700 1.700 2.000 4.000 4.800 CFM 1.000 1.000 1177 2.381 2.857

    Sound pressure level (H/M/L) (dB(A)) 48/46/44 48/46/44 50/48/46 56(H) 57(H)Standard Esp (H/L) (Pa) 80/40 80/40 100/50 200 220Dimensions (WxDxH) (mm) 1425x736x300 1463x799x389 1628x869x454Net weight (Kg) 62 62 63.5 88 113

    Connection pipe

    Gas (Flare)Inch 5/8 5/8 5/8 5/8 5/8mm φ15.9 φ15.9 φ15.9 φ15.9 φ15.9

    Liquid (Flare)Inch 3/8 3/8 3/8 3/8 3/8mm φ9.52 φ9.52 φ9.52 φ9.52 φ9.52

    Drain PipeExternal dia. mm φ30 φ30 φ30 φ25.4 φ25.4Thickness mm 1.5 1.5 1.5 1.5 1.5

  • 28

    ) Compact Design › 2.2kW, 2.8kW, 3.6Kw

    Only 700mm in width, 200mm in height and 22kg in weight*, which is perfect to install in limited spaces like drop ceiling in hotel.

    ✍• Note: the weight is 23kg for the unit of 3.6kW.

    › 4.5kW, 5.6kW

    Only 200mm in height, which can be installed in rooms with little depth as 240mm depth between the drop ceiling and ceiling slab.

    ✍ • Note: to be obtained locally

    ) Highly flexible installationHighly flexible installation is possible to satisfy various needs.

    Installation examples

    Example 1 Example 2

    SLIM DUCT TYPE

    700mm

    200mm

    200mm

    900mm

    Suspension bolt Suction duct*

    Discharge grille Air filter Suction grille

    AIR

    AIR

    Supply air duct Indoor unit

    Canvas air duct

    Long-life filter

    Supply air duct

    Long-life filter

    Return air inlet

    Indoor unit

    Maintenance access

  • 29

    ) Lower noisePlastic propeller housing, fan blade and intelligent-designed air-channel ensure air flow volume with lower operation noise.

    For example the normal unit of 2.8kW has noise level up to 40dB(A), but the new unit of 2.8kW reduces the noise up to only 37dB(A).

    ) Drain pump lift reaches 1000mm

    MODEL INV-R22P/NaE-KINV-R28P/

    NaE-KINV-R36P/

    NaE-KINV-R45P/

    NaE-KINV-R56P/

    NaE-KINV-R71P/

    NaE-K

    Power supply 1-Phase, 220-240V, 50HZ

    CapacityCooling (kW) 2.2 2.8 3.6 4.5 5.6 7.1Heating (kW) 2.5 3.2 4.0 5.0 6.3 8.0

    Power consumption (W) 64 64 70 91 91 100

    Airflow rate m3/h 450 450 550 700 700 1000 CFM 265 265 324 412 412 589

    Sound pressure level (H/M/L) (dB(A)) 37/35/33 37/35/33 39/37/35 40/38/36 41/39/37 42/40/38Standard Esp (Pa) 20 20 20 20 20 20Dimensions (WxDxH) (mm) 700x615x200 900x615x200 1100x615x200Net weight (Kg) 21 21 21 26 26 30

    Connection pipe

    Gas (Flare)Inch 3/8 3/8 1/2 1/2 5/8 5/8mm φ9.52 φ9.52 φ12.7 φ12.7 φ15.9 φ15.9

    Liquid (Flare)Inch 1/4 1/4 1/4 1/4 3/8 3/8mm φ6.35 φ6.35 φ6.35 φ6.35 φ9.52 φ9.52

    Drain PipeExternal dia. mm φ20 φ20 φ20 φ30 φ30 φ30Thickness mm 1.5 1.5 1.5 1.5 1.5 1.5

  • 30

    ) Four-way Cassette Type› Compact, light weight and square panel in the same size for

    easy installation.

    › A slim unit below 5.0kW is only 190mm in thickness. It can be installed in a narrow ceiling space of at least 210mm.

    › Drain pump fitted as standard with increased lift of 1100mm.

    Compact Four-way Cassette Type› Compact size of 650mm x 650mm for 2.8kW – 5.6kW

    › Only 230mm in thickness that can be installed in a ceiling space of at least 250mm.

    › Drain pump fitted as standard with increased lift of 500mm.

    FOUR WAY CASSETTE TYPE

    650mm

    650mm

    960mm

    960mm

    ) Four way Cassette Type) act Four way CCassette

  • 31

    Common characteristics› Low noise with 3 – dimensional blade.

    › The full-automatic operation, the 4-way air supply, the 3-speed fan setting and the strong circulating air flow volume, make the cooled or heated air to reach directly every corner of the room. This can be succeded even if the ceiling is higher than standard height.

    • The units below 7.1kW are applicable to • The units below 8kW are applicable to height below 3m. height below 4.5m.

    › Air supply in different directions with 30-60 degree sweep for even better temperature distribution*

    ✍Note: the guide louver defaults to min. position of 30° during cooling, dry and fan operation, or maximum position of 60° during heating operation.

    › Designed with fresh air baffle for fresh air introduction. › Long life and washable filter.

    Diffuser

    3-dimensional blade

  • 32

    Four-Way Cassette TypeMODEL INV-R28T/Na-K INV-R36T/Na-K INV-R45T/Na-K INV-R50T/Na-KPower supply 1-Phase, 220-240V, 50HZ

    CapacityCooling (kW) 2.8 3.6 4.5 5.0Heating (kW) 3.2 4.0 5.0 5.8

    Power consumption (W) 65 65 65 65

    Aiflow ratem3/h 680 680 680 680CFM 400 400 400 400

    Sound pressure level (H/M/L) (dB(A)) 37/35/33 37/35/33 37/35/33 37/35/33

    Connection pipe

    Gas (Flare)Inch 3/8 1/2 1/2 1/2mm φ9.52 φ12.7 φ12.7 φ12.7

    Liquid (Flare)Inch 1/4 1/4 1/4 1/4mm φ6.35 φ6.35 φ6.35 φ6.35

    Drain PipeExternal dia. (mm) φ30 φ30 φ30 φ30Thickness (mm) 1.5 1.5 1.5 1.5

    Main bodyDimensons (WxDxH) (mm) 840x840x190Net Weight (kg) 25 25 25 25

    PanelDimensons (WxDxH) (mm) 950x950x60Net Weight (kg) 6.5 6.5 6.5 6.5

    MODEL INV-R56T/Na-K INV-R63T/Na-K INV-R80T/Na-K INV-R90T/Na-KPower supply 1-Phase, 220-240V, 50HZ

    CapacityCooling (kW) 5.6 6.3 8.0 9.0Heating (kW) 6.3 7.1 8.8 10.0

    Power consumption (W) 83 83 83 133

    Aiflow ratem3/h 1.180 1.180 1.180 1.860CFM 694 694 694 1.095

    Sound pressure level (H/M/L) (dB(A)) 39/37/35 39/37/35 39/37/35 40/38/36

    Connection pipe

    Gas (Flare)Inch 5/8 5/8 5/8 5/8mm φ15.9 φ15.9 φ15.9 φ15.9

    Liquid (Flare)Inch 3/8 3/8 3/8 3/8mm φ9.52 φ9.52 φ9.52 φ9.52

    Drain PipeExternal dia. (mm) φ30 φ30 φ30 φ30Thickness (mm) 1.5 1.5 2.5 3.5

    Main bodyDimensons (WxDxH) (mm) 840x840x240 840x840x320

    Net Weight (kg) 30 30 30 38

    PanelDimensons (WxDxH) (mm) 950x950x60Net Weight (kg) 6.5 6.5 6.5 6.5

  • 33

    Compact Four-Way Cassette TypeMODEL INV-R22T/NaA-K INV-R28T/NaA-K INV-R36T/NaA-K INV-R45T/NaA-KPower supply 1-Phase, 220-240V, 50HZ

    CapacityCooling (kW) 2.2 2.8 3.6 4.5Heating (kW) 2.5 3.2 4.0 5.0

    Power consumption (W) 12 12 12 12

    Aiflow ratem3/h 600 600 600 600CFM 353 353 353 353

    Sound pressure level (H/M/L) (dB(A)) 47/44/41 47/44/41 47/44/41 47/44/41

    Connection pipe

    Gas (Flare)Inch 3/8 3/8 1/2 1/2mm φ9.52 φ9.52 φ12.7 φ12.7

    Liquid (Flare)Inch 1/4 1/4 1/4 1/4mm φ6.35 φ6.35 φ6.35 φ6.35

    Drain PipeExternal dia. (mm) φ30 φ30 φ30 φ30Thickness (mm) 1.5 1.5 1.5 1.5

    Main bodyDimensons (WxDxH) (mm) 570x570x230Net Weight (kg) 20 20 20 20

    PanelDimensons (WxDxH) (mm) 650x650x50Net Weight (kg) 2.5 2.5 2.5 2.5

    Four-Way Cassette TypeMODEL INV-R100T/Na-K INV-R112T/Na-K INV-R125T/Na-K INV-R140T/Na-KPower supply 1-Phase, 220-240V, 50HZ

    CapacityCooling (kW) 10.0 11.2 12.5 14.0Heating (kW) 11.0 12.5 13.5 14.5

    Power consumption (W) 133 133 133 133

    Aiflow ratem3/h 1.860 1.860 1.860 1.860CFM 1.095 1.095 1.095 1.095

    Sound pressure level (H/M/L) (dB(A)) 40/38/36 40/38/36 40/38/36 40/38/36

    Connection pipe

    Gas (Flare)Inch 5/8 5/8 5/8 5/8mm φ15.9 φ15.9 φ15.9 φ15.9

    Liquid (Flare)Inch 3/8 3/8 3/8 3/8mm φ9.53 φ9.52 φ9.52 φ9.52

    Drain PipeExternal dia. (mm) φ30 φ30 φ30 φ30Thickness (mm) 1.5 1.5 1.5 1.5

    Main bodyDimensons (WxDxH) (mm) 840x840x320Net Weight (kg) 38 38 38 38

    PanelDimensons (WxDxH) (mm) 950x950x60Net Weight (kg) 6.5 6.5 6.5 6.5

  • 34

    ONE-WAY CASSETTE TYPE) High flexible› Highly flexible installations for various needs.

    ) The unit is applicable to height below 3.5m

    ) Ultra quiet operationLow noise cross flow fan reduces vortex flow in the duct thus reducing the noise.

    ) Long life and washable filter

    ) Drain pump lift› Drain pump flitted as standard with increased lift of 700mm.

    ) Detachable and washable grille

    ) ComfortableThe equal and gentle air supply design and the advanced air flow controlling design make the room temperature equal and bal-anced. So, the people inside the room feel more comfortable.

    MODEL INV-R22Td/NaA-K INV-R28Td/NaA-K INV-R36Td/NaA-KPower supply 1-Phase, 220-240V, 50HZ

    CapacityCooling (kW) 2.2 2.8 3.6Heating (kW) 2.5 3.2 4.0

    Power consumption (W) 42 42 42

    Aiflow ratem3/h 450 500 500CFM 265 294 294

    Sound pressure level (dB(A)) 45/43/41 45/43/41 45/43/41

    Connection pipe

    Gas (Flare)Inch 3/8 3/8 1/2mm φ9.52 φ9.52 φ12.7

    Liquid (Flare)Inch 1/4 1/4 1/4mm φ6.35 φ6.35 φ6.35

    Drain PipeExternal dia. (mm) φ30 φ30 φ30Thickness (mm) 1.5 1.5 1.5

    Main bodyDimensons (WxDxH) (mm) 920x360x185Net Weight (kg) 16 16 16

    PanelDimensons (WxDxH) (mm) 1180χ430χ30Net Weight (kg) 3 3 3

    ) D i lift

  • 35

    Model / Heat pump INV-R71L/Na-K INV-R100L/Na-K INV-R140L/Na-K

    CapacityCooling kW 7.00 10.00 14.00 Heating kW 8.00 11.00 15.00

    Power supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50Motor power input W 160 185 200

    Air flow volumem3/h 1100/1000/920 1600/1500/1300 1700/1600/1400 CFM 655/595/548 952/893/774 1012/952/833

    Sound pressure level dB(A) 48/45/42 51/49/47 52/50/48

    Connecting pipeGas inch 5/8 5/8 5/8Liquid inch 3/8 3/8 3/8

    Drain pipeExternal dia. mm 31 31 31 Thickness mm 4.5 4.5 4.5

    Dimensions WxDxH mm 502x316x1756 556x381x1896 556x381x1896 Net Weight Body kg 39.0 53 57

    • Auto diagnosis

    • Fashionable and novel appearance

    • Quiet operation

    • Intelligent drainage device

    • Long life filter

    • Wider air supply and swing angle

    • Dynamic color display

    • Horizontal and vertical swing

    FLOOR STANDING TYPE

    FCU Wired remote controller WK-010PA-K

    Wireless

  • 36

    WALL MOUNTED TYPE

    ) Anti cool air designWhen heating in winter, intelligent anti cool air function is started.The unit blows only when the unit is pre-heated inside, to prevent it from blowing out cool air.

    ) Auto clean (under COOL & DRY mode)After the unit is turned off, the indoor fan will still operate in low speed in order to dry the inner components and parts. This way mould and odor are prevented from growing.

    ) Vertical auto swingWhen cooling, the cool air is directed across the room and then it sinks. When heating, the warm air is directed across the floor and then it rises.

    Cooling Heating

    ) Low noise designThe advanced irregular-distance mixed flow fan, the unique duct design and the multi-grill auxiliary duct, make the operation highly efficient and the noise lower.

    ) Streamlined design for spaces without ceiling

    ) Ternary filtersTernary air filters with anti-mildew, static electric dust capture and anti-bacterial function.

    Ternary filter

    ) Washable grilleThe front grille can be easily removed for washing.

  • 37

    MODEL INV-R50G/NaG-KINV-R56G/

    NaG-KINV-R71G/

    NaG-KINV-R71G/

    NaB-KINV-R80G/

    NaB-K

    Power supply 1-Phase, 220-240V, 50HZ

    CapacityCooling (kW) 5.0 5.6 7.1 7.1 8.0Heating (kW) 5.8 6.3 8.0 8.0 9.0

    Power consumption (W) 60 70 70 63 65

    Aiflow ratem3/h 630 800 800 1.200 1.200CFM 371 471 471 706 706

    Sound pressure level (H/M/L) (dB(A)) 44/41/38 44/41/38 44/41/38 49/45/42 49/45/42Dimensions (WxDxH)(mm) 940x200x298 1008x221x319 1178x227x326Net weight (kg) 13 15 15 17.5 17.5

    Connection pipe Gas (Flare)

    Inch 1/2 5/8 5/8 5/8 5/8mm φ12.7 φ15.9 φ15.9 φ15.9 φ15.9

    Liquid (Flare)Inch 1/4 3/8 3/8 3/8 3/8mm φ6.35 φ9.52 φ9.52 φ9.52 φ9.52

    Drain PipeExternal dia. (mm) φ28 φ28 φ28 φ30 φ30Thickness (mm) 4 4 4 1.5 1.5

    EXV Position Integrated External

    MODEL INV-R22G/NaG-KINV-R28G/

    NaG-KINV-R36G/

    NaG-KINV-R45G/

    NaG-K

    Power supply 1-Phase, 220-240V, 50HZ

    CapacityCooling (kW) 2.2 2.8 3.6 4.5Heating (kW) 2.5 3.2 4.0 5.0

    Power consumption (W) 50 50 60 60

    Aiflow ratem3/h 500 500 630 630CFM 294 294 371 371

    Sound pressure level (H/M/L) (dB(A)) 38/36/34 38/36/34 44/41/38 44/41/38Dimensions (WxDxH)(mm) 843x180x275 940x200x298Net weight (kg) 10.5 10.5 13 13

    Connection pipe Gas (Flare)

    Inch 3/8 3/8 1/2 1/2mm φ9.52 φ9.52 φ12.7 φ12.7

    Liquid (Flare)Inch 1/4 1/4 1/4 1/4mm φ6.35 φ6.35 φ6.35 φ6.35

    Drain PipeExternal dia. (mm) φ28 φ28 φ28 φ28Thickness (mm) 4 4 4 4

    EXV Position Intergrated

  • 38

    FLOOR CEILING TYPE) Compact and light weight

    Only 238mm in height

    ) Ultra quiet operation

    ) Long life, detachable and washable grille

    ) Easy to install and good looking, satisfies more requirements

  • 39

    ) Easy maintenanceConvenient disassembly and maintenance thanks to unique design.

    › Plastic filter with buckles › Grill buckle › Dismountable motor

    ) Wide discharge rangeWith cross-direction sweep. The air supply range is efficiently wider.

    ) Drain pump lift reaches 1100mm

  • 40

    Floor ceiling (EXV Integrated)MODEL INV-R28Zd/NaB-K INV-R36Zd/NaB-K INV-R50Zd/NaB-K INV-R71Zd/NaB-K

    Power supply 1-Phase, 220-240V, 50HZ

    CapacityCooling (kW) 2.8 3.6 5.0 7.1Heating (kW) 3.2 4.0 5.8 8.0

    Power consumption (W) 55 55 110 140

    Aiflow ratem3/h 650 650 950 1.400CFM 383 383 559 824

    Sound pressure level (dB(A)) 40 40 45 49Dimensions (WxDxH) (mm) 1.220x225x700 1420x245x700Net weight (kg) 40 40 40 52

    Connection pipe

    Gas (Flare)Inch 3/8 1/2 1/2 5/8mm φ9.52 φ12.7 φ12.7 φ15.9

    Liquid (Flare)Inch 1/4 1/4 1/4 3/8mm φ6.35 φ6.35 φ6.35 φ9.52

    Drain PipeExternal dia. (mm) φ17 φ17 φ17 φ17Thickness (mm) 1.75 1.75 1.75 1.75

    MODEL INV-R90Zd/NaB-K INV-R112Zd/NaB-K INV-R125Zd/NaB-K INV-R140Zd/NaB-K

    Power supply 1-Phase, 220-240V, 50HZ

    CapacityCooling (kW) 9.0 11.2 12.5 14.0Heating (kW) 10.0 12.5 13.5 16.0

    Power consumption (W) 180 250 250 250

    Aiflow ratem3/h 1.600 2.000 2.000 2.000CFM 942 1.777 1.777 1.777

    Sound pressure level (dB(A)) 51 55 55 55Dimensions (WxDxH) (mm) 1420x245x700 1700x245x700Net weight (kg) 54 64 66 66

    Connection pipe

    Gas (Flare)Inch 5/8 5/8 5/8 5/8mm φ15.9 φ15.9 φ15.9 φ15.9

    Liquid (Flare)Inch 3/8 3/8 3/8 3/8mm φ9.52 φ9.52 φ9.52 φ9.52

    Drain PipeExternal dia. (mm) φ17 φ17 φ17 φ17Thickness (mm) 1.75 1.75 1.75 1.75

  • 41

    CONCOLE TYPE

    • Vertical swing

    • Anti-cold function

    • Quiet operation

    • Comprehensive protection

    • Auto restart

    • Compact design

    • Easier maintainability

    MODEL INV-R28-C/Na-K INV-R36-C/Na-K INV-R28-C/Na-K

    Power Supply 1-Phase, 220-240V,50Hz

    Capacity Cooling (kW) 2.8 3.6 5.0Heating (kW) 3.2 4.0 5.5

    Power consumption (W) 60 60 60

    Air flow ratem3/h 500-430/370/280 600-520/440/360 650-620/500/410CFM 294-253/218/165 353-306/259/212 383-365/294/241

    Sound pressure level (H/M/L) (db(A)) 38/33/26 40/37/32 46/41/35Dimenions (WxDxH) (mm) 700x215x600Net weight (kg) 16

    Connection pipeGas

    inch 3/8 3/8 1/2mm φ9.52 φ9.52 φ12.7

    Liquidinch 1/4 1/4 1/4mm φ6.35 φ6.35 φ6.35

  • 42

    TREATED FRESH AIR DUCT TYPE) Provide fresh air of temperature that is close to the indoor

    ambient, ensures fresh and comfortable indoor air. ✍Note: The capacity of fresh air ducted unit should be less than 30% of the capacity of outdoor unit.

    ) Comfortable› Makes you feel comfortable, like in the nature. It is introducing › Treated fresh air supplying temperature is close to

    the outdoor fresh air, after treatment, in to the room. the indoor temperature (factory setting at 22 Celsius),

    reducing the cooling load of other indoor units.

  • 43

    ) Easy control› Wired remote control › Wireless remote control › Centralized control

    › Long-distance monitoring › Sub-room switch › Memory function

    › Auto restart after power recover › Weekly timer

    ) Flexible application › The indoor unit with high static pressure can realize long-distance fresh air supply to all corners of the room. So, it is greatly

    applicable to places that there is high density of people.

    › The standard pressure is 200Pa and the optional range is 50-300Pa.

    MODEL INV-R140P/Na(X1.2)-KINV-R224P/Na(X2.0)-M

    INV-R280P/Na(X2.5)-M

    INV-R280P/Na(X3.0)-M

    Power supply 220V, 50Hz, 1 Phase 380V, 50Hz, 3 Phase 380V, 50Hz, 3 Phase 380V, 50Hz, 3 Phase

    Capacity (At rated ESP)

    Cooling (kW) 14 22.4 28 28Heating (kW) 10 16 20 20

    Power input1Cooling (kW) 0.5 1.1 1.1 1.1Heating (kW) 0.5 1.1 1.1 1.1

    Aiflow VolumeCFM 706 1177 1471 1766m3/h 1200 2000 2500 3000

    Sound pressure level (H/M/L) (dB(A)) 42 47 48 51

    External Static Pressure

    Rated (Pa) 150 200 200 200Range (Pa) 50~150 50~200 50~200 50~200

    Dimensions (WxDxH) (mm) 1463x756x300 1500x1000x500 1500x1000x500 1500x1000x500Weight (kg) 63.5 130 150 150

    Connection pipe

    Valve Connection Type Flare Connection Brazing Connection Brazing Connection Brazing ConnectionLength (m) 7.5 7.5 7.5 7.5Gas additional charge (g/m) 54 54 54 54Liquid Pipe (Inch) 3/8 3/8 3/8 3/8Gas pipe (Inch) 5/8 7/8 7/8 7/8

  • 44

    CONTROL NETWORK SKETCH

    System Air Conditioning Individual Control

    Group Controller

    ZJA011

    Wired Remote Controller

    Z63351F/Z63151F

    Z60351F/Z60151F

    Wired Remote Controller

    ZX60451

    Wireless Remote Controller

    YB1FA Y512

    Key-card Control Board Key-card

    MK03

    (Field supplied)

    IR Receiver Unit

    JS01

    Communication module

    ME30-00/E2

    Communication module

    ME30-00/E2

    RS-422/485

    Repeater

    ✍Note: • Control network sketch is for reference only,

    please refer to the equipment manuals for actual cable connection method.

  • 45

    Air ConditioningCentral Control

    BuildingManagement

    RS-232 to RS-422/485 Converter

    RS-232 to RS-422/485 Converter

    INVENTOR AC Eudemon 2009 (Monitoring Software)

    FE30-00/A(M)

    Internet

    Web Monitoring Client

    Communication module

    ME30-00/E2

    Centralized Controller CE51-24/E(M)

    Smart Zone Controller

    CE50-24/E

    BMS Interface (Modbus)

    ME30-00/E2

    Commissioning Program (Software)

    Text Parser

    Module link

    Transmission line (INV network)

    Group controller line

    Remote Controller line

    Modbus network

    IR receiver line

    Key-card control board line

    Key-card signal line

    Building Management System

    Web Monitoring Client

  • 46

    CONTROLLERS COMPARISON

    ITEM

    Wireless remote

    Controller Y512

    Wireless remote

    controller YB1FA

    Wired Remote

    Controller Z63351F/Z60351*

    Wired Remote

    Controller XK02

    Group Controller ZJA011

    Smart Zone

    Controller CE50-24/E

    Centralized Controller CE51-24/

    E(M)

    INVENTOR AC Eude-mon 2009

    BMS Interface (Modbus)

    Connections

    Max Nos. of Outdoor Units - - - - - - 64 n*255 n*255

    Max Nos. of Wired Controller 1 1 1 1 16 16 1024 n*255*16 n*255*16

    Max Nos. of Indoor Units 1 1 1 1 16 16 1024 n*255*16 n*255*16

    Control functions

    ON/OFF ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓

    Mode Setting ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓

    Fan Speed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓

    Vertical Swing ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓

    Energy Saving Mode ✓ ✓ ✓ ✓ ✓ ✓

    Drying ✓ ✓

    Turbo Mode ✓ ✓

    Sleeping Mode ✓ ✓ ✓ ✓ ✓ ✓

    Light ✓ ✓

    Display

    Errors ✓ ✓ ✓ ✓ ✓ ✓ ✓

    Clock ✓ ✓ ✓ ✓

    Week ✓ ✓ ✓

    Room Temp. ✓ ✓ ✓ ✓ ✓ ✓ ✓

    Lock ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓

    Indoor unit Address √ ✓ ✓ ✓ ✓ ✓ ✓ ✓

    Timer

    ON/OFF Timer ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓

    Minimum Timer Gap 0.5h 1min 0.5h 0.5h 0.5h 0.5h 1min 1sec

    Weekly Timer ✓ ✓ ✓ √

    Centralized Week Timer ✓ ✓

    Group Week Timer ✓

    Shielding

    Shielding ✓ ✓ ✓ ✓ ✓ ✓ ✓

    Centralized Shielding ✓ ✓ ✓

    Group Shielding ✓

    Centralized Control

    Centralized Control ✓ ✓ ✓ ✓ ✓

    Group Control ✓

    ✍Note: • n: Nos. of serial port

    • Control functions availability is based on the indoor units. Please refer to the user’s manual of indoor unit for details.

  • 47

    COMMENTS OF CONTROL FUNCTIONS) ON/OFF Timer FunctionUnder ON/OFF state, set the unit to be automatically turned on or turned off in 0.5h hours (1≤n

  • 48

    WIRED REMOTE CONTROLLERZ60351F/Z63351F (Heat pump)

    • ON/OFF

    • Temperature setting

    • Fan speed setting

    • Energy-saving function

    • Room temperature display

    • Sleep function

    • Infrared remote control function is available and the remote controller is optional

    Z60351F/Z63351F (Heat pump)

    Z60151F/Z63151F (Cooling only)

    • ON/OFF Timer

    • Operation mode setting

    • Vertical swing

    • Self-diagnosis function (Error code display)

    • Memory function

    • Child lock function

    Operating Mode Display (COOL, DRY, FAN, HEAT)

    Sleep Mode Display

    Room Temperature Display /Error Displa

    Fan Speed Display (HIGH, MID, LOW, AUTO)

    Set Temperature Display

    Defrosting Display

    Timer Display

    Signal Receiver (For Remote Controller)

    Mode Setting Button

    Temperature Setting Button

    Fan Speed Setting Button

    Sleep Mode Setting Button*

    Timer Setting Button

    ON/OFF button

    Model Name Z63351F / Z60351F Power Supply DC12V (Supplied by the indoor unit)Dimensions (HxWxD) (mm) 85x85x20Weight (g) 94

    * Z60351F is for duct type indoor unit, and swing function is unavailable; Z63351F is for other types of indoor unit, button ‘SLEEP’ changes to ‘SWING’, and sleep function is unavailable.

    51

    51

    111FFFF (HHHeaattt pupumpmpppmpppppmppppppppp))))))))

    111FFF F (CCCCCCCCCoooooooolilililingnggggngngngng ooooooooooo onlllnlnnnlnlnnly)yy)y)y)

  • 49

    WIRED REMOTE CONTROLLERZX60451

    • ON/OFF

    • Displayed as white characters on black background

    • Fan speed setting

    • Self-diagnosis function (Error code display)

    • Turbo cooling/heating function

    • Quiet function

    • Enquire and setting address of wired controller

    • ON/OFF Timer

    • Temperature setting

    • Vertical swing

    • Environmental temperature display

    • Evaporation function

    • Shield function

    • Infrared remote control function is available and the remote controller is optional

    • Touchable wired controller

    • Operating mode setting

    • Energy saving function

    • Sleep function

    • Memory function

    • Child lock function

    Operating Mode Display (COOL, DRY, FAN, HEAT)

    Sleep Mode Display

    Fan Speed Display (AUTO, TURBO, LOW, MID, HIGH)

    Temperature /Timer / Quiet Mode Setting button

    Defrosting Operation Display

    Enter / Cancel Button

    Functions Setting Button

    Key- card Display

    Timer Display

    Fan Speed Setting Button

    Operation Mode Setting Button

    On/Off Button

    Timer Setting Button

    Model Name ZX60451Power Supply DC12V (Supplied by the indoor unit)Dimensions (HxWxD) (mm) 92x92x24Weight (g) 116

    Swing Display Lock Display

    Set / Room Temprature Display

    Function Display Area

  • 50

    WIRELESS REMOTE CONTROLLERY512

    • ON/OFF

    • Temperature setting

    • Fan speed setting

    • Child lock function

    • ON/OFF Timer

    • Operation mode setting

    • Vertical swing

    • Sleep function

    Fan Speed setting button

    Swing Button

    Fan Speed Setting Display (HIGH, MID, LOW, AUTO)

    Operation Mode Display/ (AUTO, COOL, DRY, FAN, HEAT)

    Room Temperature/ Malfunction Display

    Sleep Mode Display

    Timer Display

    Sleep Button

    Light ON/OFF Button

    Temperature/Timer Setting Button

    Timer ON Setting Button

    Timer OFF Setting Button

    Mode Setting Button

    ON/OFF Button

    Model Name Y512Power Supply AAA 1.5Vx2Dimensions (HxWxD) (mm) 159x56x18Weight (g) 92

  • 51

    WIRELESS REMOTE CONTROLLERYB1FA

    • ON/OFF

    • Temperature setting

    • Fan speed setting

    • Energy-saving function

    • Room temperature display

    • Turbo cooling/heating function

    • Mute function

    • Child lock function

    • ON/OFF Timer

    • Operation mode setting

    • Vertical swing

    • Self-diagnosis function (Error code display)

    • Sleep function

    • Blow function

    • Memory function (Turbo, Energy save, Quiet, Evaporation, etc. )

    • Clock display

    Operating Mode Display (AUTO, COOL, DRY, FAN, HEAT)

    Model Name YB1FAPower Supply AAA 1.5Vx2Dimensions (HxWxD) (mm) 122x44x21Weight (g) 70

    Sleep Mode Display

    Temperature Type Display

    Swing Angle Display

    ON/OFF Button

    Temperature/ Timer Setting Button

    Fan Speed Setting Button

    Clock Setting Button

    Blow Function ON/OFF Button

    Turbo Mode Setting Button

    Fan Speed (HIGH, MID, LOW, AUTO)

    Room Temperature/Malfunction Display

    Timer Display

    Child Lock Display

    Light Displayer

    Mode Setting Button

    Swing Mode Setting Button

    Timer Setting Button

    Temperature Display Button

    Light ON/OFF Button

    Sleep Mode Setting Button

  • 52

    GROUP CONTROLLERZJA011

    ) Group monitoring control and group wired control are the two main control functions for group Controller.

    Group monitoring controller can monitor or control 16 indoor units of a group for inquiry and single or centralized control.

    Features:

    • For a region consisted of 1-16 indoor units both single and central control are available.

    • The wired controller buttons in a region of 16 indoor units can be shielded or locked.

    • It can time 16 indoor units in a region.

    • It has the function of power-off memory.

    ✍ Note: Wired controller must be reserved with the indoor unit that has been matched.

    Group wired controller could replace 1-16 selected wired controllers, in order to uniformly set or control the indoor units.

    Features:

    • It can uniform the time for the selected indoor units.

    • It can replace the wired controller, in order to control the selected indoor units in a region.

    • It has the function of power-off memory.

    ✍ Note: The wired controller that is matched with the indoor unit must be removed and the indoor unit must be re-energized after debugging.

    No. Of indoor Unit

    Model Name ZJA011Power Supply DC12V (Supplied by the indoor unit)Dimensions (HxWxD) (mm) 85x85x20Weight (g) 94

    Inquiry/Control Display

    Operating Mode Display/ (COOL, DRY, FAN, HEAT)

    Error display for indoor or outdoor unit

    Room temperature display/ Malfunction display

    Fan Speed Display (AUTO, HIGH, MID, LOW)

    Lock Display

    Swing Display

    Set Temperature/Timer Time Display

    ON/OFF Button

    Inquiry/Single or Central Control Setting Button

    Operating Mode Setting Button (COOL, DRY, FAN, HEAT)

    Long-Distance Shield Status Display

    Value Setting Button for Temperature/ Timer/Indoor Unit Number Selecting (Under INQUIRY Status)

    Forced Operation Display

    Fan Speed/ Swing Setting Button

    Defrosting Operating Display

    Timer Button (Under SINGLE / CENTRAL Status) ON/OFF Timer Inquiring of On-line Indoor Uni (Under INQUIRY Status)

    t ll thh t

  • 53

    SMART ZONE CONTROLLERCE50-24/E

    • When the indoor units are connected to 3 sets of INV outdoor units, the air duct type indoor unit can be also connected.

    • Directly controls 16 indoor units in the network without extra communication module.

    • If an indoor unit is being operated by its own control group, it can be inquired and displayed on the operation status.

    • Remote shield function.

    • Timer function.

    • Weekly Timer Function.

    Model Name CE50-24/EPower Supply 220V~240V, 50/60HzDimensions (HxWxD) (mm) 120x120x62Weight (g) 391

    Operating Mode Display (AUTO, COOL, DRY, FAN, HEAT)

    Fan Speed Display (HIGH, MID, LOW, AUTO)

    Error/Child Lock/Lock Display

    Environmental Temperature /COM # Display

    On-line or Selected Indoor Unit No. Display

    Operation Mode Setting Button (COOL, DRY, FAN, HEAT)

    Fan Speed/Swing Setting

    Set Temperature/Timer Setting Button

    On/Off Button

    Timer/Clock Setting Button

    Current Day of Week and Time Display

    Shield Status Display (From long distance)Setting Temperature / NO. of Indoor Unit Display

    Timer Display

    Indoor Unit NO. / Week Selecting

    Shield Setting Button

    Central Control Setting

    Max 16

    Serial 1 (multirequency)Serial 2 (multirequency)

    Serial 3 (multirequency)

    played

  • 54

    CENTRALIZED CONTROLLERCE51-24/E(M)

    • Clock setting.

    • Error alarm and error code display

    • Single/Group/Center Control (including weekly timer setting, shield setting, etc)

    • 64 communication modules can be connected and 1024 sets of indoor units can be controlled.

    Model Name CE51-24/E(M)Power Supply 220V~240V, 50/60HzDimensions (HxWxD) (mm) 185x131x68Weight (g) 557

    • Inquire and control the ON/OFF, operation mode, set temperature, fan speed, swing state, etc. of indoor unit.

    • Automatically detect and display the status of online “region” and indoor unit (including operation mode, set temperature, fan speed, swing, weekly timer, shield, etc).

    • Long distance shield function.

    • Up to 1km communication wires without repeaters.

    Error Display

    Current Region No. and Unit No. Display (for indoor unit)

    Group No. Display

    Online Region No. Display*

    Online Indoor Unit No. Display

    CENTER/GROUP Operating or Setting Display

    Day of Week and Time Display

    Weekly Timer Display

    Direction Key (UP/DOWN/LEFT/RIGHT)

    Function Setting Confirmation Button

    Grouping Information Setting Button

    Back to Superior Menu Button

    Center Control Setting Button

    Clock Setting Button

    Group Control/Setting Button

    Cancel Button

    All Indoor Units ON/OFF Button

    Operation Mode Display

    Fan Speed Display (HIGH, MID, LOW, AUTO)

    SWING Operation Display

    Control Command Sending Display

    Shield Status Display

    Weekly Timer Display

    Set Temperature Display

    Room Temperature Display

    Swing Operation Setting Button

    Temperature Setting Button

    Operation Mode Setting Button

    Shield Setting Button

    ON/OFF Button

    Timer Setting or Inquiring Button

    Fan Speed Setting Button

    Max 64

    Communication Module

    Communication Module

    Communication Module

    Max 16 Max 16 Max 16

    * All indoor units connected by one communication module are automatically distributed in one region.

  • 55

    IR RECEIVER & KEY-CARD CONTROL BOARDJS01 / MK03

    ) IR receiverJS01

    It is applicable to INV duct type indoor unit and equipped with LED lamp for status indication and infrared remote control function.

    ) Key-card Control BoardMK03

    • This direction control board is only suitable for INVENTOR multi-variable (INV) indoor unit with gate-control function.

    • The AC will operate after plugging in the gate-control card and stop operating after pulling out the card.

    • Upon pulling out the card in order to stop the unit, the running states of the unit will be memorized.

    • After plugging in the card, the unit will be under standby state or resume running according to settings.

    • The AC will operate when the customer plugs in the card and automatically stop when he pulls out the card. This ensures that the unit will turn off after people leave the room and that energy will be saved.

    Model Name MK03Power Supply 220V~240V, 50/60Hz or DC5V~24V (Supplied by the indoor unit)Dimensions (HxWxD) (mm) 73x73x36Weight (g) 65

    LED Lamp

    Signal Receiver: it is used for receiving command sent from remote controller

    Heating ON/OFF and Cooling ON/OFF

    Model Name JS01Power Supply DC5V (Supplied by the indoor unit)Dimensions (HxWxD) (mm) 120x70x58.5Weight (g) 172

  • 56

    COMMUNICATION MODULEME30-00/E2

    ) Functions• The communication module (ME30-00/E2) is used for transforming and transmitting

    signals of the computer and the air conditioning system. It acts as a communication controller.

    • Modbus protocol and RS485 interface are adopted so that the unit can be connected to user’s BMS system and other net-works.

    • Lots of monitoring nodes make possible to have as many as 255 units in the same network.

    • Control of setting parameter is available.

    • Monitoring of operation state is available.

    • Monitoring of malfunction state is available.

    Model Name ME30-00/E2Power Supply 220V~240V, 50/60Hz

    Dimensions (HxWxD) (mm) 185x131x68

    Weight (g) 557

    Unit

    9~12V DC 800mA

    POWER

    Power Indicator (Red)

    Communication Indicator (Green)

    PC or COM2 of Other Module

    RS485 Interface

  • 57

    COMMISSIONING PROGRAMText Parser

    ) Brief introduction• This software receives data from the INV system through local COM port or network (both internet and LAN are suitable) and

    then analyses these data according to communication protocol.

    • Running parameters of unit, after analysis, will be displayed and saved in real time. There are two kinds of displaying methods, the text displaying and the curve displaying. The analytic data can be saved in database. Technician and service person can use this software to do commissioning.

    Real-time parameter display Curves Analysis

    Operating System

    Microsoft® Windows® 2000 Professional (English version / Service pack 4 or later)

    Microsoft® Windows® XP PROFESSIONAL (English version / Service pack 2 or later)

    Microsoft® Windows Vista® Home premium / Business / Enterprise / Ultimate

    Microsoft® Windows® 7 Home premium / Business / Enterprise / Ultimate

    64-bit version of Windows® are not supported

    CPU Intel® Pentium® / Celeron®, AMD® Athlon™ / Duron™ 1Ghz or higher

    HDD 4 GB or more of free space

    Memory 512MB or more

  • 58

    RS-422/485 RREPEATER (ISOLATED)

    Power Supply Input AC 220V~50/60HZ Output 12~30 DC 800mADimensions (HxWxD) (mm) 96 x 100.6 x 25

    Weight (g) 277

    Operation Indication LEDs

    ) FunctionsRs-422/485 repeater (isolated) is used to amplify the communication signal when the quantity of communication modules in the network is more than 30, or communication distance is longer than 800m.

    Power

    RS-422/485

    RS-422/585

    Maximum 30 Nos. of module between two repeaters

    Maximum cable length between two repeaters is 800m

  • 59

    ) FunctionsRS232-RS485 opt electronic isolated converter is used for converting the signal between computer / BMS System (RS232) and INVENTOR Air Conditioning Systems (RS485).

    Power Supply Input AC 220V~50/60HZ Output 12~30 DC 800mADimensions (HxWxD) (mm) 96 x 100.6 x 25

    Weight (g) 263

    Operation Indication LEDs

    RS-422/485

    PowerRS-232

    RS-232 TO RS-422/485CONVERTER (ISOLATED)

  • 60

    INVENTOR AC EUDEMON2009 PC SUIT) Brief introduction of INVENTOR AC Eudemon 2009INVENTOR AC Eudemon 2009 is the latest solution for controlling, monitoring and management of INVENTOR central air condi-tioning systems with your PC.

    › Maximum Connectable Systems/ Outdoor Units: 255

    › Maximum Connectable Indoor Units (INV System): 4,000

    › Maximum Control Distance: 5,600m (Standard distance 800m & extendable to 5.6km)

    › Compatible Systems: INV System, Centrifugal Chiller, Water-cooled screw chiller, Air-Cooled screw chiller, Air-cooled scroll chiller, etc.

    ) System schematic planINVENTOR AC Eudemon 2009 Management System/BMS Network Schematic Plan

    ✍Note:

    • In a RS485 Network, different type of systems cannot be connected.

    • User can only choose either INVENTOR AC Eudemon 2009 or BMS (Modbus) to manage the Air-conditioner system.

    Personal Computer

    BMS SystemINVENTOR AC Eudemon 2009

    Serial Port

    Max 255

    Convertor

    RS485 Network Protocol (Modbus)

    More AC Units

    Max 255

    Communication Module n

    Communication Module 1

    Communication Module 255

    Max 16 Max 16 Max 16

    009009

  • 61

    ) Functions of INVENTOR AC Eudemon 2009 › Air Conditioning System running status / error information checking.

    › Air Conditioning System Operation Parameter setting.

    › Multi User Management with different authorized levels.

    › Intelligent Timer with simplified schedule management.

    › Multi Serial port and Multithreading Monitoring.

    › Automatic Detection enables quick monitoring even if the user is not familiar with the concept of equipments, protocol and models, etc.

    › Vivid network plan helps the easy understanding of the physical structure of the air conditioning system.

    › Vivid location plan helps easy management of the air conditioning system.

    ) Functions of INVENTOR AC Eudemon 2009

    ) Requirement of PC for INVENTOR AC Eudemon 2009

    Model name INVENTOR AC Eudemon 2009 FE30-00/A(M)

    ContentINVENTOR AC Eudemon 2009 CD-ROM x 1 PCS

    RS232-RS485 Opto electronic Isolated Convertor x 1 PCS

    Operating System

    Microsoft® Windows® XP PROFESSIONAL (English version / Service pack 2 or later)Microsoft® Windows Vista® Home premium / Business / Enterprise / UltimateMicrosoft® Windows® 7 Home premium / Business / Enterprise / Ultimate64-bit version of Windows® are not supported

    CPU Intel® Pentium® / Celeron®, AMD® Athlon™ / Duron™ 1Ghz or higher

    HDD 10 GB or more of free space

    Memory 1GB or more

    Software Environment

    Internet Explorer® 6.0 SpP1 or later (.NET Framework supported)

    Microsoft® . NET framework® 2.0

    Microsoft® SQL Server® 2005 Express

    Microsoft® Data Access Components (MDAC) 2.8 SP1 or later.

    Microsoft Visual C++® 2008 Redistributable SP1

  • 62

    PIPING DESIGN PROGRAMINV SELECTOR) BRIEF Introduction› INVENTOR INV Selector is a program for doing the piping design of INV VRF systems.

    › Interface of the main program.

  • 63

    ) The software provides two ways to output the design› Excel summary files: it consists of › AutoCAD drawings: Electrical & Communication

    the equipment summary, design condition, wiring design of the system. system details and remote monitor detail.

    Operating System

    Microsoft® Windows® 2000 Professional (English version / Service pack 4 or later)Microsoft® Windows® XP Professional (English version / Service pack 2 or later)Microsoft® Windows Vista® Home premium / Business / Enterprise / UltimateMicrosoft® Windows® 7 Home premium / Business / Enterprise / Ultimate64-bit version of Windows® are not supported

    CPU Intel® Pentium® / Celeron®, AMD® Athlon™ / Duron™ 1Ghz or higher

    HDD 4 GB or more of free space

    Memory 512MB or more

    Software Environment

    AutoDesk® AutoCAD® Excel 2004/2005/2008

    Microsoft Office® Excel 2000/2003/2007 Professional

    Microsoft Visual C++® 2008 Redistributable SP1

    › Download “VRF Selection Software” www.inventor.ac/tech_spec

  • 64

    ENERGY RECOVERY VENTILATION) Introducing outdoor fresh air and discharging indoor air.

    Makes you feel comfortable as in the nature.

    ) Energy saving› Internal heat exchanger performs cooling and heating

    exchange between the discharged air and fresh air.

    Energy-recovery rate above 70%, high energy saving.

    › Unique by-pass mode can reduce power consumption of fan motor, in order to prolong lifetime of the heat exchanger core.

    › By the combination of heat exchange mode and by pass mode, the unit load can be reduced about 26% in a year.

    0%

    20% 26%

    Pow

    er r

    educ

    tion

    rat

    io

    Direct fresh air introduction

    Independent heat exchange process

    Heat exchange combined with

    by-pass proccessDischarge airAir Supply

    Temp plate

    Heat exchange mode By-pass mode

    Outdoor air intake

    Exchange air

    Return air

    Supply air

    Outdoor air temperature sensor Air supply fan

    Air exchange fan Heat exchange elementRoom temperature

    sensor

    Outdoor air intake

    Exchange air

    Return air

    Supply air

    Outdoor air temperature sensor Air supply fan

    Air exchange fan Heat exchange elementIndoor air temperature

    sensor

    Shell

    Indoors air inlet

    Fresh air outlet

    Lug

    Indoor air outlet

    Fresh air outlet

    Electrical box

    Heat exchanger

    Air filter

    arging indoor air

  • 65

    › Exchanege of humidity (latent heat)

    The vapour on the side with high humidity is absorbed by hy-groscopic agent and discharged to the side with low humidity through capillary action of the fibber.

    › Through heat exchange between the indoor air and fresh air, the internal heat exchanger reduces the fluctuation of indoor temperature. At the same time it prevents from high temperature difference of the supply air, while reducing the operation load of the unit.

    Moisture absorption

    Move through capillary

    Moisture release

    › Flexible control

    • LED display

    • Energy saving mode

    • 24h timer

    • Centralized controller

    • Weekly timer

    • Long-distance Monitoring Control (optional)

    › Low-noise Design

    Build-in low noise ventilation fan.

    Fresh air inlet

    Insulation material

    Indoor air outlet Fresh air Supply

    Room air inlet

    Fresh air outletIndoor air return

    Discharge air duct

    Fresh air duct

    ) High efficiency heat exchangeThe ERV can exchange the latent heat and sensible heat simultaneously, which can adjust temperature and humidity at the same time. It can be widely applied where there is big humidity difference between indoor and outdoor.

    › Heat exchange (sensible heat) inside the core

    Heat is exchanged between discharged air and fresh air, so that the fresh air temperature to come down and be close to the indoor temperature. The feeling of uncomfortable is avoided and meanwhile the load of air conditioning is effectively decreased.

    › Air Filtration and purification Function

    • Internal air filter keeps the fresh air introduced into room pure and dustless.

    • The efficient isolation between fresh air duct and discharge air duct ensures pure air supply.

    • With antibacterial and anti-mildew materials, the heat exchange core is suiting for healthy.

    › Wide range of models

    7 models in a range of 350~3000m3/h, which can fit for different spaces and reduce the waste of power. Wide range from 350 to 3000 m3/h, matching with buildings of various structures.

    › Reliability and easy maintenance

    • The complete unit with non-moving parts except the fan motor can reliably operate for a long period of time, without frequent maintenance.

    • Filter and heat exchange core can be easily taken out from the access door for cleaning.

    › Compact design and easy installation

    With a minimum height of 360mm, the unit is space saving. It can be installed inside limited ceiling spaces.

    ) Installation example

  • 66

    SPECIFICATIONS) ERV

    MODEL HRVQ-D3.5-K HRVQ-D5-K HRVQ-D8-K HRVQ-D10-K Power supply 220 240V, 1Ph, 50Hz Power Input (W) 165 262 400 440

    Airflow rate H/M/L m3/h 360/260/210 500/380/300 800/600/480 1000/750/600CFM 212/153/124 294/224/176 471/353/282 588/441/353

    Sound pressure level (dB(A)) 37 39 45 46 External static pressure H/M/L Pa 100/80/60 100/80/60 110/85/65 110/85/65 Temperature exchange efficiently H/M/L

    % 71/73/75 68/70/72 70/72/74 75/77/79

    Enthalpy exchange efficiency Heating (H/M/L) 65/67/68 62/64/65 63/65/67 66/68/70 Cooling (H/M/L) 61/63/65 57/59/61 60/62/64 62/64/65

    Dimension (WxDxH) (mm) 800x879x306 800x879x306 832x1016x380 832x1016x380 Net weight (Kg) 45 45 57 57

    MODEL HRVQ-D15-M HRVQ-D20-M HRVQ-D30-M Power supply 380~415V 3N~50Hz Power Input (W) 600 950 2800

    Airflow rate m3/h 1500 2000 3000CFM 882 1176 1176

    Sound pressure level (dB(A)) 48 50 54 External static pressure Pa 150 150 220 Temperature exchange efficiently

    %73 71 70

    Enthalpy exchange efficiency Heating 65 62 62 Cooling 60 58 58

    Dimension (WxDxH) (mm) 1210x1215x452 1210x1215x452 1340x1550x572 Net weight (Kg) 100 100 240

  • 67

    CONNECTION BRANCHES) Modular Outdoor ) Indoor Unit Y-Type

    Unit Branch Joint Branch Joint

    Gas Pipe Gas Pipe

    Liquid Pipe Liquid Pipe

    Modular Outdoor Unit Branch Joint

    Configuration

    Indoor Unit Y-Type Branch Joint

    Model Name Configuration

    ML01R 22.4 ≤ X ≤ 96ML02R 96 < X

    Model Name Configuration

    FQ01A/A X ≤ 20.0FQ01B/A 20.0 < X ≤ 30.0FQ02/A 30.0 < X ≤ 70.0FQ03/A 70.0 < X ≤ 135.0FQ04/A 135.0 < XFQ01Na/A X ≤ 5.6FQ02Na/A 5.6 < X ≤ 22FQ03Na/A 22 < X ≤ 30FQ04Na/A 30 < X ≤ 68FQ05Na/A 68 < X ≤ 96FQ06Na/A 96 < X ≤ 135FQ07Na/A 135 < X

  • For more technical information download the technical files

    www.inventor.ac/tech_spec

    No 1

    www.inventor.ac

    for the compressor and for all parts of the unit

    ec

    ecal informmamamaatititiononon dd dowownlnnlnlnloaoaoaao ddd the te

    .inventor.ac/tech_spe

    ALL UNITS ARE AVAILABLE FROM OUR SELECTED NETWORK

    OF AIR CONDITIONING PROFESSIONALS