catálogo geral ls

36
Electric Equipment MCB / MS / Mini-MC / EMPR / DMPR / MMS / MCCB / ACB / VCB Low Voltage Circuit Breakers & Contactors

Upload: rafael-da-costa

Post on 17-Mar-2016

242 views

Category:

Documents


3 download

DESCRIPTION

Catálogo geral LS, contactores, disjuntores, disjuntores motores, MCCB, ACB

TRANSCRIPT

Page 1: Catálogo Geral LS

Electric Equipment

MCB / MS / Mini-MC / EMPR / DMPR / MMS / MCCB / ACB / VCB

Low Voltage Circuit Breakers & Contactors

Page 2: Catálogo Geral LS

●1, 2, 3 and 4 pole series up to 125AF●B, C and D Characteristics

●2 and 4 pole series up to 63AF●Sensitivity up to 300mA●Overcurrent protection type available

Metasol/Meta-MEC series●3 and 4 pole series up to 800AF Mini-contactors available●AC/DC common use coil from 100AF●Thermal (Bimetallic) and electronic type overload relays are available●CE marked and UL approved

Page 4

Page 6

Page 8

Page 18

Page 3: Catálogo Geral LS

Susol /Meta-MEC series● 2, 3 and 4 pole series up to 1600AF ●Rated ambient temperature at 40℃ calibrated for 50℃ available●CE marked according to IEC standard and UL approved MCCBs

are also available.

Susol/Metasol series●65, 85 and 150kA breaking capacity●High functional digital trip relays ●CE marked and Marine classiflcation

Susol series

Page 20

Page 26

Page 32

Page 4: Catálogo Geral LS

4

Miniature circuit breakers1, 2, 3 and 4 pole series up to 125AF

3kA at 230VAC

6kA at 400VAC

6kA at 230/400VAC

1 changeover contact

6A at 240VAC, 3A at 415VAC

2A at 48VDC, 1A at 125VDC

Lug terminal

cable capacity 2.5㎟

9mm wide

Type BKP BKN

1A

2A

3A

4A

6A

10A

16A

20A

25A

32A

40A

50A

63A

80A

100A

125A

Auxiliary switch, AXOptional

Dimension See drawing 1 See drawing 2

Characteristic curve See curve 1 See curve 1

Protection Overload and short circuit Overload and short circuit

Rated current 3,6,10,16,20,25,32A 1,2,3,4,6,10,16,20,25,32,40,50,63A

Characteristic B, C, D curve B, C, D curve

Number of poles 1p+N 1p, 1p+N, 2p, 3p, 3p+N, 4p

Breaking capacity 1 pole 2~4 pole

Standard IEC 60898 IEC 60898

Type of trip Thermal magnetic release Thermal magnetic release Thermal magnetic release

Electrical endurance 20000 operations 6000 operations

Mount On 35mm DIN rail On 35mm DIN rail

Width 9mm per pole 17.8mm per pole

Terminal Lug type(cable up to 10㎟) Lug type(cable up to 25㎟)

Drawing 1 : Type BKP

17.8

8.9

60 82

60

37

455

45

68

(22)

(22)

(17)

Drawing 2 : Type BKN

5

37

4560

(14)

45

17.8

63

68

82

Page 5: Catálogo Geral LS

5

10kA at 400VAC

10kA at400VAC

10kA at 230/400VAC

10kA at 400VAC

BKN-b BKH

See drawing 3 See drawing 4

See curve 1 See curve 1

Overload and short circuit Overload and short circuit

1,2,3,4,6,10,20,25,32,40,50,63A 63, 80, 100, 125A

B, C, D curve C, D curve

1p, 1p+N, 2p, 3p, 3p+N, 4p 1p, 1p+N, 2p, 3p, 3p+N, 4p

1 pole 2~4 pole 1 pole 2~4 pole

IEC 60898 IEC 60947-2

Thermal magnetic release

8000 operations 6000 operations

On 35mm DIN rail On 35mm DIN rail

17.8mm per pole 27mm per pole

Lug type(cable up to 25㎟) Lug type(cable up to 50㎟)

Drawing 3 : Type BKN-b

17.8

(33)

(19)

4537

5 43.8

6860

65 82

Drawing 4 : Type BKH

Curve 1 : Type BKP, BKN, BKN-b, BKH, RKP

Page 6: Catálogo Geral LS

6

Residual current circuit breakers 2 and 4 pole series up to 63AF

Drawing 1 : Type RKP

35.6

8.9

8260

45

60

5

(22)

68

37

(22)

(17)

45

70

Drawing 2 : Type RKN

561

74

(13)45

36 45

22

72

68 82

36

68 82

1 3 5 N

2

1

24 6 N

N

N

Drawing 3 : Type KGR Drawing 4 : Type BKD

37

5

60

70

45

(10)

45

60

17.8

82

Drawing 5 : Type RKS

5523

18

18

Type RKP RKS RKN

Protection Ground fault and overcurrent Ground fault and overcurrent Ground fault Ground fault

Rated current, In 3(C,D),6,10,16,20,25,32A(B,C,D curve) 6, 10, 16, 20, 25, 32A (B, C curve) 25, 32, 40, 63A

Rated residual current

Operating, I△n 30, 100, 300mA(non-adjustable) 30, 100mA (non-adjustable) 30, 100, 300mA(non-adjustable)

Non-operating, I△no 0.5I△n 0.5I△n 0.5I△n

Number of poles 1P+N 1P+N 2, 4 pole

Rated voltage 230VAC 230VAC 230VAC(2p), 230/400VAC(4p)

Residual current off-time ≤ 0.1 sec. ≤ 0.3 sec. ≤ 0.1 sec.

Standard IEC 61009 IEC 61009 IEC 61008

Type of trip

Ground fault Electro-magnetic Electro-magnetic Electro-magnetic

Overcurrent Thermal-magnetic Thermal-magnetic N.A

Breaking capacity 4.5kA 10kA

Conditional short circuit capacity 6kA for In=25, 32, 40, 63A

Electrical endurance 20000 operations ≤ 4000 operations 6000 operations

Mount On 35mm DIN rail On 35mm DIN rail On 35mm DIN rail

Width 9mm per pole 9mm per pole 18mm per pole

Terminal Lug type(cable up to 10㎟) Lug type(cable up to 10㎟) Lug type(cable up to 35㎟)

Dimension See drawing 1 See drawing 5 See drawing 2

Characteristic curve See page 5 (curve 1)

Page 7: Catálogo Geral LS

7

Type BKDRated current, In 40, 50, 63, 80, 100, 125A

Number of poles 1p, 2p, 3p, 4p

Rated voltage 230/400VAC

Standard IEC 60947-3

Electrical 40, 50, 63A 20000 operationsendurance 80, 100, 125A 10000 operations

Mount On 35mm DIN rail

Width 17.8mm per pole

Terminal Lug type(cable up to 50㎟)

Dimension See drawing 4

32KGRb32KGRa

Curve 1 : Type 32KGRa, 32KGRb

Ground fault and overcurrent

15, 20, 30A

15, 30mA(non-adjustable)

0.5I△n

2 pole

110/220VAC

≤ 0.03 sec.

KS, JIS *(IEC61009)

Electronic

Bimetallic

1.5kA 2.5kA

6000 operations

On 35mm DIN rail

35mm

Screw clamp type(cable up to 25㎟)

See drawing 3

See curve 1

Note) * IEC61009 standard is applicable for 32KGRa only.

Page 8: Catálogo Geral LS

8

Contactors & Overload relaysMetasol MC 18 to 100A

MC type

Thermal Overload RelaysMT type

Magnetic Contactors

* The safety cover of magnetic contactor and thermal overload relay is optional.

MT-12/�

690V

690V

6kV

10A, 20

0.1~18A

0.17

45×73.2×63.7

Type

Screws clamp terminals

Rated operational voltage, Ue

Rated insulation voltage, Ui

Rated impulse withstand voltage, Uimp

Trip class

Setting range

Size Weight kg

and

weightSize(W×H×D) mm

WD

H

MC-6a MC-9a MC-12a MC-18a

● ● ● ●

3pole

690V

690V

50/60Hz

6kV

1800 operations per hour

15 mil. operations

2.5 mil. operations

25 25 25 32

2.5 2.5 3.5 4.5

9 11 13 18

3 4 5.5 7.5

7 9 12 18

3 4 7.5 7.5

6 7 12 13

3 4 7.5 7.5

4 6 9 9

1.5 1.5 2.2 3.7

7 8 11 16

2.2 2.2 4 4

5 6 9 11

0.33

45×73.5×82

0.47

45×83×113.7

1a or 1b

UA-1

AU-2, AU-4

18AF

Note) Minimum conduct current of Auxiliary contactor is DC 17V 5mA.

Type

screws clamp terminals

Number of poles

Rated operational voltage, Ue

Rated insulation voltage, Ui

Rated frequency

Rated impulse withstand voltage, Uimp

Maximum operating rate in operating cycles per hour(AC3)

Durability Mechanical

Electrical

Current AC-1, Thermal current A

and AC-3 200/240V kW

power A

380/440V kW

A

500/550V kW

A

690V kW

A

AC-4 200/240V kW

A

380/440V kW

A

Size AC Weight kg

and control Size(W×H×D) mm

weight DC Weight kg

control Size(W×H×D) mm

Auxiliary(standard)

Auxiliary Side mount

Front mount

Frame size

WD

H

MT-32/�

690V

690V

6kV

10A, 20

0.1~40A

0.17

45×75×90

MC-9b MC-12b MC-18b MC-22b*

● ● ● ●

3pole

690V

690V

50/60Hz

6kV

1800 operations per hour

15 mil. operations

2.5 mil. operations

25 25 32 40

2.5 3.5 4.5 5.5

11 13 18 22

4 5.5 7.5 11

9 12 18 22

4 7.5 7.5 15

7 12 13 20

4 7.5 7.5 15

6 9 9 18

1.5 2.2 3.7 3.7

8 11 16 18

2.2 4 4 5.5

6 9 11 13

0.46

45×73.5×86

0.47

45×73.5×117.7

1a1b

UA-1

AU-2, AU-4

22AF

Page 9: Catálogo Geral LS

9

MT-95/�

690V

690V

6kV

10A, 20

7~100A

0.48/0.5

70×97×110

MT-63/�

690V

690V

6kV

10A, 20

4~65A

0.31/0.33

55×81×100

100AF

MC-50a MC-65a

● ●

3pole

690V

1000V

50/60Hz

8kV

1800 operations per hour

12 mil. operations

2 mil. operations

70 100

15 18.5

55 65

22 30

50 65

30 33

43 60

30 33

28 35

7.5 11

35 50

15 22

32 47

1.05

79×106×122

1.3

79×106×149

2a2b

UA-1

AU-2, AU-4

65AF

MT-32/�

690V

690V

6kV

10A, 20

0.1~40A

0.17

45×75×90

MC-32a MC-40a

● ●

3pole

690V

1000V

50/60Hz

8kV

1800 operations per hour

12 mil. operations

2 mil. operations

50 60

7.5 11

32 40

15 18.5

32 40

18.5 22

28 32

18.5 22

20 23

4.5 5.5

20 25

7.5 11

17 24

0.55

69×83×93

0.77

69×83×120

2a2b

UA-1

AU-2, AU-4

40AF

MC-75a MC-85a MC-100a

● ● ●

3pole

690V

1000V

50/60Hz

8kV

1800 operations per hour

12 mil. operations

2 mil. operations

110 135 160

22 25 30

75 85 105

37 45 55

75 85 105

37 45 55

64 75 85

37 45 45

42 45 65

13 15 19

55 65 80

25 30 37

52 62 75

1.93

94×140×137

2.8

94×140×174

2a2b

UA-1

AU-2, AU-4

Page 10: Catálogo Geral LS

10

Contactors & Overload relaysMetasol MC 150 to 800A

MC type

Thermal Overload RelaysMT type

Magnetic Contactors

MT-150/�

690V

690V

6kV

10A, 20

34~150A

0.67

95×109×113

Type

Screws clamp terminals

Rated operational voltage, Ue

Rated insulation voltage, Ui

Rated impulse withstand voltage, Uimp

Trip class

Setting range

Size Weight kg

and

weightSize(W×H×D) mm

WD

H

MC-130a MC-150a

● ●

3pole

690V

1000V

50/60Hz

8kV

1200 operations per hour

5 mil. operations

1 mil. operations

160 210

37 45

130 150

60 75

120 150

60 75

90 100

55 55

60 60

22 30

93 120

45 55

90 110

2.1

95×158×132

2.1

95×158×132

UA-1

AU-2, AU-4

150AF

Type

screws clamp terminals

Number of poles

Rated operational voltage, Ue

Rated insulation voltage, Ui

Rated frequency

Rated impulse withstand voltage, Uimp

Maximum operating rate in operating cycles per hour(AC3)

Durability Mechanical

Electrical

Current AC-1, Thermal current A

and AC-3 200/240V kW

power A

380/440V kW

A

500/550V kW

A

690V kW

A

AC-4 200/240V kW

A

380/440V kW

A

Size AC Weight kg

and control Size(W×H×D) mm

weight DC Weight kg

control Size(W×H×D) mm

Auxiliary(standard)

Auxiliary Side mount

Front mount

Frame size

WD

H

MT-225/�

690V

690V

6kV

10A, 20

65~240A

2.5

147×141×184

MC-185a MC-225a

● ●

3pole

690V

1000V

50/60Hz

8kV

1200 operations per hour

5 mil. operations

1 mil. operations

230 275

55 75

185 225

90 110

185 225

110 132

180 200

110 140

120 150

37 45

150 180

75 90

150 180

5.4

138×203×181

AU-100 (Max.4NO4NC)

225AF

Page 11: Catálogo Geral LS

11

MT-400/�

690V

690V

6kV

10A, 20

85~400A

2.6

151×171×198

400AF

MC-265a MC-330a MC-400a

● ● ●

3pole

690V

1000V

50/60Hz

8kV

1200 operations per hour

5 mil. operations 2.5 mil. operations

1 mil. operations 0.5 mil. operations

300 350 450

80 90 125

265 330 400

132 150 200

265 330 400

140 160 200

225 280 350

160 200 250

185 225 300

50 55 75

200 220 300

102 110 150

200 220 300

9.2

163×243×198

AU-100 (Max.4NO4NC)

MT-800/�

690V

690V

6kV

10A, 20

200~800A

11.5

360×530×212

800AF

MC-500a MC-630a MC-800a

● ● ●

3pole

690V

1000V

50/60Hz

8kV

1200 operations per hour

2.5 mil. operations

0.5 mil. operations

580 660 900

147 190 220

500 630 800

250 300 400

500 630 800

250 300 400

400 500 720

300 400 500

380 420 630

90 110 160

350 400 630

176 200 300

350 400 630

22.4

285×312×242

AU-100 (Max.4NO4NC)

Page 12: Catálogo Geral LS

12

Contactors & Overload relays9 to 85A

2-poleSide mount

4-poleFront mount

2-poleFront mount

Types AC coil GMC-9 GMC-12 GMC-18 GMC-22

DC coil GMD-9 GMD-12 GMD-18 GMD-22

Ratings / IEC60947-4 kW A kW A kW A kW A

AC1 25 25 40 40AC3 200/240V 2.5 11 3.5 13 4.5 18 5.5 22

380/440V 4 9 5.5 12 7.5 18 11 22500/550V 4 7 7.5 12 7.5 13 15 22

690V 4 5 7.5 9 7.5 9 15 18

Ratings / UL508 hp A hp A hp A hp A

continuous current 20 25 30 32

single phase 115V 0.5 0.5 1 2

230V 1 2 3 3

three phase 200V 2 3 5 7

230V 2 3 5 7.5

460V 5 7.5 10 10575V 7.5 10 15 15

NEMA size 00 00 0 0

Types AC coil GMC-9/4 GMC-12/4 GMC-18/4 GMC-22/4

DC coil GMD-9/4 GMD-12/4 GMD-18/4 GMD-22/4

AC1(A) 20 20 25 32

Additional auxiliary contacts

3-pole Contactors

9A 12A 18A 22AFrame size

4-pole Contactors

Overload Relays

Bimetallic styleType GT

Base for separate mount

Settingranges (A)

Differential

Class10A Non-differential (3-heater)

Non-differential (2-heater)

Class 20 Differential

GTK-22GTH-22/3GTH-22

GTK-22/L

0.1 - 0.160.16 - 0.250.25 - 0.40.4 - 0.63

0.63 - 11 - 1.6

1.6 - 2.52.5 - 4

4 - 65 - 86 - 97 - 109 - 13

12 - 1616 - 22

Electronic styleType GMP

Class 1�30 adjustableSeparate mount type

GMP22

Setting ranges (A)

0.1 - 1.51 - 5

4.4 - 22

GT-22

Page 13: Catálogo Geral LS

13

Base for separate mount

Setting ranges(A) : 16 ~ 80A

Separate mountWiring by screw

GMP80

Setting ranges(A) : 5 ~ 60A

Separate mountWiring by CT tunnelGMP60

Setting ranges (A)4 - 20

8 - 40

GMC-32 GMC-40 GMC-50 GMC-65 GMC-75 GMC-85

GMD-32 GMD-40 GMD-50 GMD-65 GMD-75 GMD-85

kW A kW A kW A kW A kW A kW A

50 60 80 100 110 1357.5 32 11 40 15 55 18.5 65 22 75 25 85

15 32 18.5 40 22 50 30 65 37 75 45 8518.5 28 22 32 30 43 33 60 37 64 45 75

18.5 20 22 23 30 28 33 35 37 42 45 45

hp A hp A hp A hp A hp A hp A

45 50 70 80 90 100

2 3 3 5 5 7.5

5 5 7.5 10 15 15

7.5 10 10 15 20 25

10 10 15 20 25 30

20 25 30 40 50 5020 25 30 40 50 50

1 1 2 2 2 3

GMC-32/4 GMC-40/4 GMC-50/4 GMC-65/4 GMC-75/4 GMC-85/4

GMD-32/4 GMD-40/4 GMD-50/4 GMD-65/4 GMD-75/4 GMD-85/4

50 60 80 100 110 135

32A 40A 50A 65A 75A 85A

Base for separate mountGT-85

Setting ranges (A)

GTK-40

GTH-40/3

GTH-40

GTK-40/L

GTK-85

GTH-85/3

GTH-85

GTK-85/L

7 - 109 - 13

12 -1816 - 2218 - 2624 - 36

28 - 4034 -5045 - 6554 - 7563 - 85

GT-40

Setting ranges (A)

4 - 65 - 86 - 97 - 109 - 13

12 -1816 - 2218 - 2624 - 3628 - 40

separate mount

GMP40

2-poleSide mount

4-poleFront mount

2-poleFront mount

Page 14: Catálogo Geral LS

14

Contactors & Overload relays100 to 800A

Types AC/DC GMC-100 GMC-125 GMC-150 common coil

Ratings / IEC60947-4 kW A kW A kW A

AC1 160 160 210

AC3 200/240V 30 105 37 125 45 150

380/440V 55 105 60 120 75 150

500/550V 55 85 60 90 90 140

690V 55 65 60 70 90 100

Ratings / UL508 hp A hp A hp A

continuous current 160 160 210

single phase 115V 7.5 10 15

230V 15 20 25

three phase 200V 30 40 40

230V 30 40 50

460V 60 75 100

575V 60 75 100

NEMA size 3 3 4

Types AC/DC GMC-100/4 GMC-125/4 GMC-150/4common coil

AC1(A) 160 160 210

Additional auxiliary contacts

3-pole Contactors

100A 125A 150AFrame size

4-pole Contactors

Overload Relays

Bimetallic styleType GT

GT- 100

Setting ranges (A)

Differential

Class10A Non-differential (3-heater)

Non-differential (2-heater)

Class 20 Differential

GTK-100

GTH-100/3

GTH-100

GTK-100/L

GTK-150

GTH-150/3

GTH-150

GTK-150/L

34 - 50

39 - 57

43 - 65

54 - 80

65 - 100

85 - 125GT- 150

Setting ranges (A)

34 - 50

39 - 57

43 - 65

54 - 80

65 - 100

85 - 125

100 - 150

AU-1001NO+1NC, Side mount

Page 15: Catálogo Geral LS

15

GTK-220

GTH-220/3

GTH-220

GTK-220/L

GTK-400

GTH-400/3

GTH-400

GTK-400/L

GTK-600

GTH-600/3

GTH-600

GTK-600/L

GMC-180 GMC-220 GMC-300 GMC-400 GMC-600 GMC-800

kW A kW A kW A kW A kW A kW A

230 275 350 450 660 900

55 180 75 250 90 300 125 400 190 630 220 800

90 180 132 250 160 300 220 400 330 630 440 800

110 180 132 200 160 250 225 350 330 500 550 720

110 120 132 150 200 220 250 300 330 420 500 630

hp A hp A hp A hp A hp A hp A

230 275 350 450 660 900

15 15

30 40

60 60 100 125 150 250

60 75 100 150 200 300

125 150 200 300 400 600

125 150 200 300 400 600

4 4 5 5 6 7

GMC-180/4 GMC-220/4 GMC-300/4 GMC-400/4 GMC-600/4 GMC-800/4

230 275 350 450 660 900

180A 220A 300A 400A 600A 800A

GT- 220

Setting ranges (A)

65 - 100

85 - 125

100 - 150

120 - 180

160 - 240GT- 400

Setting ranges (A)

85 - 125

100 - 150

120 - 180

160 - 240

220 - 300

260 - 400

Setting ranges (A)

220 - 300

260 - 400

400 - 600

520 - 800

GT- 800

AU-1001NO+1NC, Side mount

Page 16: Catálogo Geral LS

16

Mini contactors6 to 16A

3NO main contacts

1 auxiliary contactsScrew clamp type Fast-on type Cage clamp type Solder pin type

Mini contactors

Overload Relays

Bimetallic styleType GT

Screw clamp type AC coil GMC-6M GMC-9M GMC-12M GMC-16M

DC coil GMD-6M GMD-9M GMD-12M GMD-16M

Fast-on type AC coil GMC-6MF GMC-9MF GMC-12MF GMC-16MF

DC coil GMD-6MF GMD-9MF GMD-12MF GMD-16MF

Cage clamp type AC coil GMC-6MC GMC-9MC GMC-12MC GMC-16MC

DC coil GMD-6MC GMD-9MC GMD-12MC GMD-16MC

Solder pin type AC coil GMC-6MP GMC-9MP GMC-12MP GMC-16MP

DC coil GMD-6MP GMD-9MP GMD-12MP GMD-16MP

Ratings / IEC60947-4 kW A kW A kW A kW A

AC1 20 20 20 20

AC3 200/240V 1.5 7 2.2 9 3 12 4 15

380/440V 2.2 6 4 9 5.5 12 7.5 16

500/550V 3 5 3.7 6 4 7 5.5 9

690V 3 4 4 5 4 5 4 5

Ratings / UL508 hp A hp A hp A hp A

continuous current Ith = 20A (maximum for cage clamp type is 10A)

single phase 120V 1/2 1/2 1 * -

230V/240V 1 1.5 2 * * -

three phase 240V 1.5 3 3 -

480V 3 5 7.5 * * * -

600V 3 5 7.5 -

Wire Range : Copper, 75°C, Stranded, 18-12AWG

NEMA size 00 00 00 0

Base for separate mountGT-12M

Setting ranges (A)

Differential

Non-differential (3-heater)

Non-differential (2-heater)

GTK-12M

GTH-12M/3

GTH-12M

0.1 - 0.160.16 - 0.250.25 - 0.40.4 - 0.63

0.63 - 11 - 1.6

1.6 - 2.52.5 - 4

4 - 65 - 86 - 97 - 109 - 13

12 - 16

Frame size 6A 9A 12A 16A

AU-2M

AU-1M

AU-4M

AU-2MF

AU-1MF

AU-4MF

AU-2MC

AU-1MC

AU-4MC AU-1MP

Additional auxiliary contacts

Note) * = 1/2 for cage clamp type, ** = 1.5hp for cage clamp type, *** = 5hp for cage clamp type16AF : not approved from UL

2-pole, Front mount

4-pole, Front mount

2-pole, Side mount

Fast-on type Cage clamp type Solder pin typeScrew clamp type

Page 17: Catálogo Geral LS

17

Digital motor protection relay

Model No. DMP06-S/Sa DMP60-S/Sa DMP06-T/Ta DMP06-T/Ta

Wiring Screw type Tunnel type

Panel mount Unit or Extension Note1)

Operation time Select either reverse time characteristics or definite time characteristics

Protection Over current According to the setting time

Phase failure 3 sec.

Reverse phase Within 0.1 sec.

Asymmetry 5 sec.

Stall 5 sec.

Lock Within 0.5 sec.

Under current 3 sec.

Ground fault Within 0.05~1 sec. Selectable (0.05~1.0sec)

Short circuit Note2) Within 50ms

Alarm Variable (60~110% of the setting current)

Current setting range (A) 0.5~6 5~60 0.5~6 5~60

Motor capacity 220~240V 0.09~0.75 1.1~11 0.09~0.75 1.1~11

(kW) 380~440V 0.12~1.5 2.2~22 0.09~1.5 2.2~22

Time setting Definite Delay in starting 0~60sec

range (sec) time Delay in operating 0~30sec

Inverse time 0~60sec

Reset Manual reset

Tolerance Current ±5%

Time ±5% (or±0.5sec)

Operating power Voltage AC 190~250V

Note3) Frequency 60Hz (50Hz)

Aux. contact OL 2-SPST 3A/250Vac Resistive load

AL SPST 3A/250Vac Resistive load

Insulation resistance Over DC500V 100㏁

Surge impulse voltage(IEC1000-4-5) 1.2×50㎲ 6kV (Apply standard wave form)

Fast transient burst(IEC1000-4-4) 2.5kV/5min

Environment Temperature Operation -25~70℃

Storage -30~80℃

Humidity 30~90% RH (No freezing)

Display 7-Segment 3 phase current, cause of a fault

Bar-Graph 60~110% of real load current

Mounting type 35mm Din-rail/Panel

Note1) In extension type, the digital EMPR is calibrated with combining the display past and main body so, please cautious not to combine the display part and main body with different part No.

Note2) Instantaneous short circuit protection is optional Note3) Operational voltage of AC 110V and 50Hz is optional

DMP�-S/Sa DMP�-T/Ta

Page 18: Catálogo Geral LS

18

Manual motor startersQuick selection table ... IEC rating

220V 220V240V 415V 460V 525V 690V 240V 415V 460V 525V 690V

230V 400V 440V 500V 600V 230V 400V 440V 500V 600V

Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics

100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 3 3100 100 100 100 100 100 50 38 3 3100 100 100 100 50 38 15 11 3 3100 100 100 100 15 11 10 8 3 3100 100 100 100 15 11 10 8 3 3100 100 50 38 15 11 6 5 3 3100 100 50 38 10 8 6 5 3 350 38 20 15 10 8 6 5 3 340 30 15 11 8 6 6 5 3 340 30 15 11 8 6 6 5 3 330 22 15 11 6 4 5 4 3 3- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics

100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 8 8100 100 100 100 100 100 100 100 8 8100 100 100 100 100 100 100 100 6 6100 100 100 100 50 38 50 38 6 6100 100 100 100 50 38 50 38 6 6100 100 100 100 50 38 42 32 6 6100 100 50 38 20 15 10 8 4 4100 100 50 38 20 15 10 8 4 4100 100 50 38 20 15 10 8 4 4100 100 50 38 20 15 10 8 4 4- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

0.160.250.40.63

11.62.54681013172226324050637590100

TypeCurrent adjustable type MMS-32S MMS-32HInstantaneous type - MMS-32HIBreaking capacity Standard High breakingHandle Type Toggle Rotary

Number of poles 3 3Rated operational voltage (Ue) Up to 690V Up to 690VRated frequency 50/60 Hz 50/60 HzRated insulation voltage (Ui) 690V 690VRated impulse voltage (Uimp) 6kV 6kVUtilization category IEC 60 947-2 (Breaker) Cat. A Cat. A

IEC 60 947-4 (Motor starter) AC 3 AC 3Mechanical endurance (Operating) 100,000 100,000Electrical endurance (Cycles) 100,000 100,000Max operating frequency per hour (Ope./h) 25 25Temperature compensation (Operation) -20 ~ +60℃ -20 ~ +60℃Instantaneous short circuit release 13 × Ie max. 13 × Ie max.Overload protection � �

Phase failure function � �

Trip indicating function × ×

Test function � �

Weight (g) 320 360Rated Rated Thermal releasebreaking operational Adjustmentcapacity

current (Ie)range

(kA) (A)0.1~0.160.16~0.250.25~0.40.4~0.630.63~11~1.6

1.6~2.52.5~44~65~86~109~1311~1714~2218~2622~3228~4034~5045~6355~7570~9080~100

Frame 32AF

Page 19: Catálogo Geral LS

19

MMS-63S MMS-63H MMS-100S MMS-100H- MMS-63HI - MMS-100HI

Standard High breaking Standard High breakingRotary Rotary Rotary Rotary

3 3 3 3Up to 690V Up to 690V Up to 690V Up to 690V50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz1,000V 1,000V 1,000V 1,000V

8kV 8kV 8kV 8kVCat. A Cat. A Cat. A Cat. AAC 3 AC 3 AC 3 AC 3

50,000 50,000 50,000 50,00025,000 25,000 25,000 25,000

25 25 25 25-20 ~ +60℃ -20 ~ +60℃ -20 ~ +60℃ -20 ~ +60℃

13 × Ie max. 13 × Ie max. 13 × Ie max. 13 × Ie max.� � � �

� � � �

× × � �

� � � �

1,000 1,000 2,200 2,200

63AF 100AF

220V 220V240V 415V 460V 525V 690V 240V 415V 460V 525V 690V

230V 400V 440V 500V 600V 230V 400V 440V 500V 600V

220V 220V240V 415V 460V 525V 690V 240V 415V 460V 525V 690V

230V 400V 440V 500V 600V 230V 400V 440V 500V 600V

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

100 100 100 100 15 12 10 8 4 3100 100 50 38 10 8 6 5 4 3100 100 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 3

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

100100 100 100 50 38 50 38 6 5100100 100 100 50 38 42 32 6 5100100 50 50 50 38 12 9 5 5100100 50 50 50 38 12 9 5 5100100 50 50 35 27 12 9 5 5100100 50 50 35 27 10 8 5 5100100 50 50 35 27 10 8 5 5100100 50 50 35 27 10 8 5 5100100 50 50 35 27 10 8 5 5

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

100 100 50 38 40 30 25 19 10 8100 100 50 38 40 30 25 19 10 8100 100 50 38 40 30 25 19 10 8100 100 50 38 40 30 15 11 10 8100 100 50 38 40 30 15 11 6 5100 100 50 38 40 30 12 9 6 5100 100 50 38 40 30 12 9 6 5100 100 50 38 40 30 8 6 5 4100 100 50 38 40 30 8 6 5 4100 100 50 38 40 30 8 6 5 4

Icu Ics Icu Ics Icu Ics Icu Ics Icu IcsIcu Ics Icu Ics Icu Ics Icu Ics Icu IcsIcu Ics Icu Ics Icu Ics Icu Ics Icu IcsIcu Ics Icu Ics Icu Ics Icu Ics Icu Ics

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

100100 100 100 50 38 35 27 12 9100100 100 50 50 38 35 27 12 9100100 100 50 50 38 35 27 12 9100100 100 50 50 38 25 19 12 9100100 100 50 50 38 20 15 12 9100100 100 50 50 38 15 11 10 8100100 100 50 50 38 15 11 8 6100100 75 50 50 38 12 9 6 6100100 75 50 50 38 12 9 6 6100100 75 50 50 38 12 9 6 6

Page 20: Catálogo Geral LS

20

Mold case circuit breakersSusol MCCB Series

TD100 TD160 TS100

♣ Applicable to MCCBs equipped with FTU, FMU, ATU★ 2 pole MCCB in 3pole frame size ★★ 700A only available for TS800FTU

★★★ Available for 3pole circuit breakers ★★★★ Under development★★★★★ Not applicable to 1pole

Frame size [AF]

Rated current, In ♣ [A]

No. of poles

Rated operational AC [V]

voltage, Ue DC [V]

Rated impulse withstand voltage, Uimp [kV]

Rated insulation voltage, Ui [V]

Rated ultimate short-circuit breaking capacity, Icu

AC 50/60Hz 220/240V [kA]

380/415V [kA]

440/460V [kA]

480/500V [kA]

660/690V [kA]

DC 250V [kA]

500V(2poles in series) [kA]

Rated service breaking capacity, Ics [%Icu]

Rated short-circuit making capacity Icm

AC 50/60Hz 220/240V [kA]

380/415V [kA]

440/460V [kA]

480/500V [kA]

660/690V [kA]

Category of utilization

Isolation behavior

Trip unit (release)

Thermal-Magnetic

●fixed-thermal, fixed-magnetic FTU

●adjustable-thermal, fixed-magnetic FMU

●adjustable-thermal, adjustable-magnetic ATU

●magnetic only MTU ★★★

Electronic

●LSI ETS ★★★

●LSI ETM ★★★

Option Earth-fault protection, Ig

Zone selective interlocking, ZSI

Ammeter

Communication

Earth-leakage protection module ★★★★

Connection fixed front-connection

rear-connection

plug-in front-connection

rear-connection

Mechanical life [operations]

Electrical life @ 415 V AC [operations]

Basic dimensions, W×H×D 1-pole [mm]

(front connection) 3-pole [mm]

4-pole [mm]

Weight 1-pole [kg]

(front connection) 3-pole [kg]

4-pole [kg]

Reference standard

100 160 100

16, 20, 25, 32, 40, 1P: 16, 20, 25, 32, 40, 50,

50, 63, 80, 10063, 80, 100, 125, 160 40, 50, 63, 80, 100

2, 3P: 100, 125, 160

2★, 3, 4 1, 2★, 3, 4 2★, 3, 4

690 240(1P), 690 690

500 250(1P), 500 500

8 8 8

750 750 750

N H L N H L N H L

30(1P) 50(1P)85 100 200

85 100 200 100 120 200

50 85 150 50 85 150 50 85 150

50 70 130 50 70 130 50 70 130

30 50 65 30 50 65 42 65 85

5 8 10 5 8 10 10 15 20

16(1P) 25(1P)42 65 100

42 65 100 50 85 100

42 65 100 42 65 100 50 85 100

100% 100% 100% 100% 100% 100% 100% 100% 100%

105(1P) 105(1P)187 220 440

187 220 440 220 264 440

105 187 330 105 187 330 105 187 330

105 154 286 105 154 286 105 154 286

63 105 143 63 105 143 88 143 187

8 14 17 8 14 17 17 30 40

A A A

● ● ●

● ● ●

● ●★★★★★ ●

- - -

- - ●

- - ●

- - -

- - -

- - -

- - -

- - -

- - -

● ● ●

● ●★★★★★ ●

● ●★★★★★ ●

● ●★★★★★ ●

25000 25000 25000

10000 10000 10000

- 35×140×86 -

90×140×86 90×140×86 105×160×86

120×140×86 120×140×86 140×160×86

- 0.57 -

1.5 1.5 2

1.8 1.8 2.6

IEC60947-2 IEC60947-2 IEC60947-2

Page 21: Catálogo Geral LS

21

TS160 TS250 TS400 TS630

1. The breakers with electronic trip units are available only at 3-pole version. (Only for AC supply)※ The trip unit ATU is available from 125A

TS800

160 250 400 630 800

(100)※, 125, 160 125, 160, 200, 250 300, 400 500, 630 700★★, 800

2★, 3, 4 2★, 3, 4 2★, 3, 4 2★, 3, 4 2★, 3, 4

690 690 690 690 690

500 500 500 500 500

8 8 8 8 8

750 750 750 750 750

N H L N H L N H L N H L N H L

100 120 200 100 120 200 100 120 200 100 120 200 100 120 200

50 85 150 50 85 150 65 85 150 65 85 150 65 100 150

50 70 130 50 70 130 65 85 130 65 85 130 65 100 130

42 65 85 42 65 85 42 65 85 42 65 85 42 85 100

10 15 20 10 15 20 10 20 35 10 20 35 10 20 35

50 85 100 50 85 100 50 85 100 50 85 100 50 85 100

50 85 100 50 85 100 50 85 100 50 85 100 50 85 100

100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%

220 264 440 220 264 440 220 264 440 220 264 440 220 264 440

105 187 330 105 187 330 143 187 330 143 187 330 143 220 330

105 154 286 105 154 286 143 187 286 143 187 286 143 220 286

88 143 187 88 143 187 88 143 187 88 143 187 88 187 220

17 30 40 17 30 40 17 40 74 17 40 74 17 40 74

A A A A A

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

- - ● ● ●

- - ● ● ●

- - ● ● ●

- - ● ● ●

- - ● ● ●

- - ● ● ●

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

25000 25000 20000 20000 10000

10000 10000 6000 6000 3000

- - - - -

105×160×86 105×160×86 140×260×110 140×260×110 210×320×135

140×160×86 140×160×86 186.5×260×110 186.5×260×110 280×320×135

- - - - -

2 2 5.4 5.4 15.1

2.6 2.6 7.2 7.2 19.6

IEC60947-2 IEC60947-2 IEC60947-2 IEC60947-2 IEC60947-2

Page 22: Catálogo Geral LS

22

Molded case circuit breakersMeta-MEC 30AF to 225AF Series

Note): 1. ● applicable or available2. ▲ available as a separate breaker3. (3) Breaking capacity(at 415VAC) of ABS32b 3A

ABS33b 3A is 2.5kA

Table 1.

Frame Size(AF)Frame TypeBreaking capacity(kA), Icu at 415VACNumber of polesType 2 pole

3 pole4 pole

Rated current (A)

Technical data conforming to IEC/EN60947-2Rated operational voltage(V), Ue(50/60Hz)Rated operational voltage(V), Ue(DC)Rated insulation voltage(V), Ui(50/60Hz)Rated impulse withstand voltage(kV), UimpUltimate breaking capacity(kA), Icu

AC 50/60Hz 220/240V380V415V440/460V480/500V600V

DC 125V250V

Service breaking capacity(%Icu), IcsCategory of useEndurance Mechanical(Number of operations) ElectricalType of trip unitThermal-magnetic releaseElectronic releasePre-alarm via LED Hydraulic-magnetic releaseMagnetic release only without thermal tripEarth leakage protection for 3 pole AccessoriesElectrical auxiliaries Auxiliary switch

Alarm switchShunt tripUndervoltage trip

External accessories Direct rotary handleExtended rotary handleTerminal shieldInsulation barrierRear connection Mechanical interlockPlug-in deviceMotor operator

Dimensions (W×H×Dmm) 3 pole breakerWeight(kg) 2 pole

3 pole4 pole

Derating chart : See tables

Amb. Temp. -5℃ 0℃ 10℃ 20℃ 25℃ 30℃ 35℃ 40℃ 45℃ 50℃

Calibrated for 40℃ In=15 to 30A 111.9% 111.3% 110.0% 108.0% 106.6% 104.9% 102.7% 100.0% 96.8% 93.3%

In=40 to 100A 110.2% 109.8% 108.7% 107.0% 105.8% 104.3% 102.4% 100.0% 97.2% 94.0%

Calibrated for 50℃ In=15 to 30A 113.1% 112.5% 111.3% 110.0% 109.1% 108.0% 106.6% 104.9% 102.7% 100.0%

In=40 to 100A 111.2% 110.7% 109.8% 108.7% 108.0% 107.0% 105.8% 104.3% 102.4% 100.0%

ABS ABH ABE ABS ABH5 10 5 10 25

2, 3 2, 3 2, 3 2, 3, 4 2, 3, 4ABS32b ABH32b ABE52b ABS52b ABH52bABS33b ABH33b ABE53b ABS53b ABH53b

ABS54b(3), 5, 10, 15, 20, 30 5, 10, 15, 20, 30 5, 10, 15, 20, 30, 40, 50 15, 20, 30, 40, 50

600 600 600 600 600250 250 250 250 250690 690 690 690 6906 6 6 6 6

10 25 10 25 507.5 14 7.5 14 255 10 5 10 255 10 5 10 25

2.5 7.5 2.5 7.5 142.5 5 2.5 5 105 10 5 10 20

2.5 5 2.5 5 1450 50 50 50 50A A A A A

8500 8500 8500 8500 85001500 1500 1500 1500 1500

fixed.

fixed fixed fixed fixed

▲ ▲ ▲ ▲ ▲

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

● ● ● ● ●

- - - - -- - - - -- - - - -

0.45 0.45 0.45 0.45 0.70.65 0.65 0.65 0.65 1

- - - 0.85 1.2

30 50

See table 1

75×130×60 75×130×60 90×155×60

Page 23: Catálogo Geral LS

23

60 100 225

105×165×60

See table 2

Table 2.

Amb. Temp. -5℃ 0℃ 10℃ 20℃ 25℃ 30℃ 35℃ 40℃ 45℃ 50℃Calibrated for 40℃ In=100 to 225A 114.3% 113.2% 110.6% 107.5% 105.8% 140.0% 102.0% 100.0% 97.9% 95.6%Calibrated for 50℃ In=100 to 225A 116.3% 115.4% 113.2% 110.6% 109.1% 107.5% 105.8% 104.0% 102.0% 100.0%

ABE ABS ABE ABS ABH ABE ABS ABH5 10 10 25 35 18 25 35

2, 3 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4ABE62b ABS62b ABE102b ABS102b ABH102b ABE202b ABS202b ABH202bABE63b ABS63b ABE103b ABS103b ABH103b ABE203b ABS203b ABH203bABH54b ABS64b ABE104b ABS104b ABH104b ABE204b ABS204b ABH204b

60 5, 10, 15, 20, 30, 15, 20, 30, 40, 50 100, 125, 150, 175, 200, 22540, 50, 60, 60, 75, 100

75, 100

600 600 600 600 600 600 600 600250 250 250 250 250 250 250 250690 690 690 690 690 690 690 6906 6 6 6 6 6 6 6

10 25 25 50 65 35 50 657.5 14 14 25 35 18 25 355 10 10 25 35 18 25 355 10 10 25 35 18 25 35

2.5 7.5 7.5 14 25 10 14 252.5 5 5 10 18 7.5 10 185 10 10 20 25 15 20 25

2.5 5 5 14 18 10 14 1850 50 50 50 50 50 50 50A A A A A A A A

8500 8500 8500 8500 8500 7000 7000 70001500 1500 1500 1500 1500 1000 1000 1000

fixed fixed. fixed fixed. fixed

fixed fixed fixed

▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

- - - - - - - -- - - - - - - -- - - - - - - -

0.45 0.45 0.45 0.7 0.7 1.1 1.1 1.10.65 0.65 0.65 1.1 1.1 1.2 1.2 1.2

- 0.85 0.85 1.2 1.2 1.5 1.5 1.5

75×130×60 90×155×60

See table 1 See table 1

Page 24: Catálogo Geral LS

24

Mold case circuit breakersMeta-MEC 250AF to 1600AF Series

Note ;● applicable or available▲ available as a separate breaker

Table 3.Amb. Temp. -5℃ 0℃ 10℃ 20℃ 25℃ 30℃ 35℃ 40℃ 45℃ 50℃

Calibrated for 40℃ 110.0% 109.0% 107.0% 105.0% 104.0% 103.0% 101.5% 100.0% 98.5% 97.0%

Calibrated for 50℃ 113.0% 112.0% 110.0% 108.0% 107.0% 106.0% 104.5% 103.0% 101.5% 100.0%

Frame Size(AF) 400

Frame TypeBreaking capacity(kA), Icu at 415VACNumber of polesType 2 pole

3 pole4 pole

Rated current (A)

Technical data conforming to IEC/EN60947-2Rated operational voltage(V), Ue(50/60Hz)Rated operational voltage(V), Ue(DC)Rated insulation voltage(V), Ui(50/60Hz)Rated impulse withstand voltage(kV), UimpUltimate breaking capacity(kA), Icu

AC 50/60Hz 220/240V380V415V440/460V480/500V600V690V

DC 125V250V

Service breaking capacity(%Icu), IcsCategory of useEndurance Mechanical(Number of operations) ElectricalType of trip unitThermal-magnetic releaseElectronic releasePre-alarm via LED Hydraulic-magnetic releaseMagnetic release only without thermal tripEarth leakage protection for 3 pole AccessoriesElectrical auxiliaries Auxiliary switch

Alarm switchShunt tripUndervoltage trip

External accessories Direct rotary handleExtended rotary handleTerminal shieldInsulation barrierRear connection Mechanical interlockPlug-in deviceMotor operator

Dimensions (W×H×Dmm) 3 pole breakerWeight(kg) 2 pole

3 pole4 pole

Derating chart : See tables

250, 300, 350, 400Interchangeable via rating plug between

250 and 300350 and 400

See table 3

ABE ABS ABH ABL25 35 50 85

2,3,4 2,3,4 2,3,4 2, 3, 4ABE402b ABS402b ABH402b ABL402bABE403b ABS403b ABH403b ABL403bABE404b ABS404b ABH404b ABL404b

600 600 600 600250 250 250 250690 690 690 6906 6 6 6

35 50 85 12530 42 65 10025 35 50 85/50(Ics)25 35 50 8518 25 35 6518 22 25 30- - - -

20 30 50 6010 20 40 40100 100 50 50A A A A

4000 4000 4000 40001000 1000 1000 1000

fixed fixed fixed fixed

▲ ▲

▲ ▲ ▲ ▲

● ● ● ●

● ● ● ●

● ● ● ●

● ● ● ●

● ● ● ●

- - - -● ● ● ●

● ● ● ●

● ● ● ●

● ● ● ●

- - - -- - - -

140×257×1135.2 5.2 5.2 5.26.2 6.2 6.2 6.27.8 7.8 7.8 7.8

Page 25: Catálogo Geral LS

25

800 1200 1600

210×400×105 210×350×142.5

800Electronically adjustable :

(0.5-0.6-0.7-0.8-0.9-1.0)×InElectronically adjustable :

(0.5-0.6-0.7-0.8-0.9-1.0)×InSee table 3

ABE ABS ABL GBN(E) GBH(E) ABS ABS(electronic trip) GBN(E)35 50 85 35 50 65 65 65

2, 3, 4 2, 3, 4 2, 3, 4 3 3 3, 4 3 3ABE802b ABS802b ABL802bABE803b ABS803b ABL803b GBN803E GBH803E ABS1003 ABS1203 ABS1203E GBN1603EABE804b ABS804b ABL804b ABS1004 ABS1204

1000 1200 1200 1600

600 600 600 600 600 600 600 600250 250 250 - - 250 250 -690 690 690 690 690 690 690 6906 6 6 6 6 6 6 8

50 100 125 50 85 100 100 -42 65 100 35 50 65 65 -35 50 85/50(Ics) 35 50 65 65 6535 50 85 30 42 65 65 4525 45 65 22 35 50 50 2222 25 30 18 25 45 45 -- - - - - - - 20

30 50 60 - - - - -20 40 40 - - 40 - -100 50 50 50 50 50 50 50

A A A A A A A A2500 2500 2500 2500 2500 2500 2500 10000500 500 500 500 500 500 500 4000

fixed fixed fixed Adjustable-thermal, Fixed-magneticLSIA configuration LSIA configuration ●

● ● ● ●

▲ ▲ ▲ ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● - - ●

- - - - - - - ●

● ● ● ● ● - - ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● - - -- - - - - - - ●

- - - - - - - ●

140×257×113 210×280×11311 11 11 - - - -

11.5 11.5 11.5 11.5 19.4 19.4 2318.2 18.2 18.2 - 27 - -

500, 600, 630, 700, 800Interchangeable via rating plug between 500 and 600, 500 and 630, 700 and 800

Page 26: Catálogo Geral LS

26

Air circuit breakersSusol ACB Series

Type

Ampere frame (AF)

Rated current(A) (In max) at 40℃

Setting current (A) Control trip relay ( ... × In max)

Rated current of neutral pole (A)

Rated insulation voltage(V) (Ui)

Rated operating voltage(V) (Ue)

Rated impulse withstand voltage (kV) (Uimp)

Frequency(Hz)

Number of poles (P)

Rated breaking capacity (kA sym)IEC 60947-2

220V/230V/380V/415V

AC 50/60Hz (Icu)KS C 4620

460V/480V/500V

550V/600V/690V

Rated service breaking capacity (kA) (Ics) ... %×Icu

Rated making capacity (kA peak)IEC 60947-2

220V/230V/380V/415V

AC 50/60Hz (Icm) KS C 4620

460V/480V/500V

550V/600V/690V

Rated short-time 1sec

withstand current (kA) (Icw) 2 sec

3 sec

Operating time (ms) Maximum total breaking time

Maximum closing time

Life cycle (time) Mechanical Without maintenance

With maintenance

Electrical Without maintenance

With maintenance

Connections Draw-out / Fixed Horizontal connection

Vertical connection

Front connection

Mixed connection

Weight (kg) Draw-out type Main body Motor charging type

(3P/4P) (With cradle) Manual charging type

Cradle only

Fixed type Motor charging type

Manual charging type

External dimensions (mm) Draw-out 3P

(H×W×D) type 4P

Fixed type 3P

4P

Trip relay

Certificate & Approval

Marine classiflcation

* Refer to trip relay specification. ** �: Standard, �: Option

AH-06D AH-08D AH-10D AH-13D AH-16D AH-20D

630 800 1000 1250 1600 2000

200 400

400 630 1000 1250 1600 2000

630 800

(0.4 ~ 1.0) × In max

400400

630 1000 1250 1600 2000630

800

1000

690

12

50/60

3, 4

85

85

65

100%

187

187

143

65

60

50

40

80

20,000

30,000

5,000

10,000

� -

� �

� -

� -

63/74 70/85

61/72 68/83

29/32 33/40

34/44 38/47

32/42 36/45

430×334×375

430×419×375

300×300×295

300×385×295

N, A, P, S type

KS / KEMA / KERI / GOST

LR, ABS, DNV, KR, BV, GL, RINA, NK

H

WD

*

**

Page 27: Catálogo Geral LS

27

AH-06E AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E

630 800 1000 1250 1600 2000 2500 3200 4000

630 800 1000 1250 1600 2000 2500 3200 4000

(0.4 ~ 1.0) × In max

630 800 1000 1250 1600 2000 2500 3200 4000

1,000

690

12

50/60

3, 4

100

100

85

100%

220

220

187

85

75

65

40

80

15,000

20,000

5,000

10,000

� �

� �

� -

� -

87/103 104/147

85/101 102/145

44/55 58/70

44/55 63/100

42/53 61/98

430×412×375

430×527×375

300×378×295

300×493×295

N, A, P, S type

KS / KEMA / KERI / GOST

LR, ABS, DNV, KR, BV, GL, RINA, NK

AH-40G AH-50G AH-63G

4000 5000 6300

4000 5000 6300

(0.4 ~ 1.0) × In max

4000 5000 6300

1,000

690

12

50/60

3, 4

150

150

100

100%

330

330

220

100

100

100

40

80

10,000

15,000

2,000

5,000

-

-

181/223 186/230

179/221 184/228

97/117 102/124

98/123 103/130

96/121 101/128

460×785×375

460×1015×375

300×751×295

300×981×295

N, A, P, S type

KS / KEMA / KERI / GOST

LR, ABS, DNV, KR, BV, GL, RINA, NK

Page 28: Catálogo Geral LS

28

Air circuit breakersMetasol ACB Series

Type

Ampere frame (AF)

Rated current(A) (In max) at 40℃

Setting current (A) Control trip relay ( ... × In max)

Rated current of neutral pole (A)

Rated insulation voltage(V) (Ui)

Rated operating voltage(V) (Ue)

Rated impulse withstand voltage (kV) (Uimp)

Frequency (Hz)

Number of poles (P)

Rated breaking capacity (kA sym) (Icu) 220V/230V/380V/415V

AC 50/60Hz IEC 60947-2 460V/480V/500V

550V/600V/690V

Rated service breaking capacity (kA) (Ics) ... %×Icu

Rated making capacity (kA peak) (Icm) 220V/230V/380V/415V

AC 50/60Hz IEC 60947-2 460V/480V/500V

550V/600V/690V

Rated short-time 1 sec

withstand current (kA) (Icw) 2 sec

3 sec

Operating time (ms) Maximum total breaking time

Maximum closing time

Life cycle (time) Mechanical Without maintenance

With maintenance

Electrical Without maintenance

With maintenance

Connections Draw-out / Fixed Horizontal connection

Vertical connection

Front connection

Mixed connection

Weight (kg) Draw-out type Main body Motor charging type

(3P/4P) (With cradle) Manual charging type

Cradle only

Fixed type Motor charging type

Manual charging type

External dimensions (mm) Draw-out 3P

(H×W×D) type 4P

Fixed type 3P

4P

Trip relay

Certificate & Approval

Marine classiflcation

* Refer to trip relay specification. ** �: Standard, �: Option

H

WD

*

**

AN-06D AN-08D AN-10D AN-13D AN-16D AS-20D

630 800 1000 1250 1600 2000

200 400

400 630 1000 1250 1600 2000

630 800

(0.4 ~ 1.0) × In max

400400

630 1000 1250 1600 2000630

800

1000

690

12

50/60

3, 4

65 70

65 70

50 65

100% 100%

143 154

143 154

105 143

50 65

42 55

36 50

40

80

20,000

30,000

5,000

10,000

� -

� �

� -

� -

63/74 70/85

61/72 68/83

29/32 33/40

34/44 38/47

32/42 36/45

430×334×375

430×419×375

300×300×295

300×385×295

N, A, P type

KS / KEMA / KERI / GOST

LR, ABS, DNV, KR, BV, GL, RINA, NK

Page 29: Catálogo Geral LS

29

AS-20E AS-25E AS-32E AS-40E AS-50F AS-40G AS-50G AS-63G

2000 2500 3200 4000 4000 5000 4000 5000 6300

630, 800

1000, 1250 2500 3200 4000 4000 5000 4000 5000 6300

1600, 2000

(0.4 ~ 1.0) × In max (0.4 ~ 1.0) × In max (0.4 ~ 1.0) × In max

630, 800

1000, 1250 2500 3200 4000 4000 5000 4000 5000 6300

1600, 2000

1,000 1000 1,000

690 690 690

12 12 12

50/60 50/60 50/60

3, 4 3, 4 3, 4

85 100 120

85 100 120

85 85 100

100% 100% 100%

187 220 264

187 220 264

187 187 220

85 85 100

75 75 90

65 65 85

40 40 40

80 80 80

15,000 10,000 10,000

20,000 15,000 15,000

5,000 2,000 2,000

10,000 5,000 5,000

� � � �

� � � �

� - - -

� - - -

87/103 104/147 145/173 181/223 186/230

85/101 102/145 143/171 179/221 184/228

44/50 58/70 78/90 97/117 102/124

44/55 63/100 76/94 98/123 103/130

42/53 61/98 74/92 96/121 101/128

430×412×375 460×629×375 460×785×375

430×527×375 460×799×375 460×1015×375

300×378×295 300×597×295 300×751×295

300×493×295 300×767×295 300×981×295

N, A, P type N, A, P type N, A, P type

KS / KEMA / KERI / GOST KS / KEMA / KERI / GOST KS / KEMA / KERI / GOST

LR, ABS, DNV, KR, BV, GL, RINA, NK LR, ABS, DNV, KR, BV, GL, RINA, NK LR, ABS, DNV, KR, BV, GL, RINA, NK

Page 30: Catálogo Geral LS

The trip relay of Susol ACB provides the additional protection functions for voltage, frequency, unbalance, andothers in addition to main protection functions for over current, short-circuit, ground fault. It supports theadvanced measurement functions for voltage, current, power, electric energy, harmonics, communicationfunction, and others.Analog trip function interlocked with mechanism enhanced a durability of devices as well as the breakingcapacity of ACB.Zone selective interlocking function makes the protective coordination more simple and thermal memory canbe applied to various loads.

Trip relay(OCR)Trip relay(OCR)

Page 31: Catálogo Geral LS

31

Trip relay types

Classification N type A type P type S type

Externals

Current �L / S / I / G / Thermal �L / S / I / G / Thermal �L / S / I / G / Thermal(Continuous) �P type

protection �ZSI(Protective coordination) �ZSI(Protective coordination)

� Earth leakage (Option) �Earth leakage(Option) �P type

Other�Over/Under current

protection�Over/Under frequency

�Unbalance(Voltage/Current)

�Reverse power

�Current (R / S / T / N) �3 Phase Voltage/Current �3 Phase Voltage/Current

RMS/Vector RMS/Vector

�Power(P, Q, S), PF(3-Phase) �Power(P, Q, S), PF(3-Phase)

�Energy(Positive/Negative) �Energy(Positive/Negative)

Measurement �Frequency, Demand �Frequency, Demand

function �Voltage/Current harmonics

(1st~63th)

�3 Phase Waveforms

�THD, TDD, K-Factor

Fine adjustment�Fine adjustment for long/short �P type

time delay/instantaneous/ ground

�Overload protection relays �P type

Pre Trip Alarm: DO (Alarm)

(Ground fault is not available

when using Pre trip alarm)

Digital Output�3DO (Fixed) �3DO (Programmable) �P type

�L, S/I, G Alarm �Trip, Alarm, General

IDMTL setting�Compliance with IEC60255-3 �P type

SIT, VIT, EIT, DT

Communication�Modbus/RS-485 �Modbus / RS-485 �Modbus / RS-485

�Profibus-DP �Profibus-DP �Profibus-DP

�Self Power �Self Power �AC/DC 100~250V �AC/DC 100~250V

-Power source - Power source works �DC 24~60V �DC 24~60V

works over 20% of over 20% of load current.

Power supply load current. - External power source are

required for comm.

�AC/DC 100~250V

�DC 24~60V

RTC timer �Available �Available �Available �Available

LED for�Long time delay �N type �N type �N type

trip info.�Short time delay/Instantaneous

�Ground fault

�10records �256records �256records

Fault recording (Fault/Current/Date and Time) (Fault/Current/Date and Time) �Last fault wave

recording (3 Phase)

Event recording �256 records(Content, Status, Date) �P type

Operating �Reset button �Reset, Menu �A type �A type

button Up/Down, Left/Right, Enter

Basic protection function(L / S / I / G)

is still under normal operation

without control power.

-

-

-

-

-

-

-

- -

-

-

-

Page 32: Catálogo Geral LS

32

Vacuum Circuit BreakersSusol VCB Series

Rated voltage (kV) 7.2 12

Rated short-circuit breaking current (kA) 8 12.5 20 25 31.5 40 50 20 25 31.5 40 50

Rated current (A) 400 630 630 630 1250 1250 1250 630 630 1250 1250 1250

1250 1250 2000 2000 2000 1250 1250 2000 2000 2000

2000 2000 3150 3150 3150 2000 2000 3150 3150 3150

4000 4000 4000 4000

Rated frequency (Hz) 50/60 50/60

Rated short-circuit breaking capacity (MVA) 100 160 250 310 390 500 620

Rated short-time withstand current (kA/3sec) 8 12.5 20 25 31.5 40 50 20 25 31.5 40 50

Rated short-circuit making current (kA) 20 32.5 52 65 82 104 130 52 65 82 104 130

Rated breaking time (Cycle) 3 3

Rated opening time (sec) ≤0.04 ≤0.04

No-load closing time (sec) ≤0.06 ≤0.06

Rated withstand Power frequency (kV/min) 20 28(42)

voltage Impulse (kV/1.2x50㎲㎲) 60 75

Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO

Type test Mechanical M2 M2

Electrical E2 (List1) E2 (List1)

Capacitive current switching C2 C2

Lifetime Mechanical Without maintenance (time) 10000 10000

Maintenance (time) 20000 20000

Electrical Without maintenance (time) 10000 10000

Maintenance (time) 20000 20000

Installing Fixed ■■ ■■ ■■ ■■ ■■ ■■ - ■■ ■■ - - -

method Draw-out ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■

Applied standard IEC 62271-100. JIS C 4603/JEC 2300 IEC 62271-100

Rated voltage (kV) 17.5 24 36 40.5

Rated short-circuit breaking current (kA) 20 25 40 50 12.5 25 31.5 40 25 31.5 40 25 31.5

Rated current (A) 630 630 1250 1250 630 630 1250 1250 360 630 1250 1250 1250

1250 1250 2000* 2000 1250* 1250* 2000 2000 1250 1250 2000 2000 2000

2000 2000 3150* 3150 2000* 3150 3150 2000 3150 2500

2500* 2500

Rated frequency (Hz) 50/60 50/60 50/60 50/60

Rated short-circuit breaking capacity (MVA)

Rated short-time withstand current (kA/3sec) 20 25 40 50 12.5 25 31.5 40 25 31.5 40 25 31.5

Rated short-circuit making current (kA) 52 65 104 130 32.5 65 82 104 65 82 104 65 82

Rated breaking time (Cycle) 3 3 3 3

Rated opening time (sec) ≤0.04 ≤0.04 ≤0.04 ≤0.04

No-load closing time (sec) ≤0.06 ≤0.06 ≤0.06 ≤0.06

Rated withstand Power frequency (kV/min) 38 50(65) 70(95) 95

voltage Impulse (kV/1.2x50㎲㎲) 95 125 170 185

Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO

Type test Mechanical M2 M2 M2 M2

Electrical E2 (List1) E2 (List1) E2 (List1) E2 (List1)

Capacitive current switching C2 C2 C2 C2

Lifetime Mechanical Without maintenance (time) 10000 10000 10000 10000

Maintenance (time) 20000 20000 20000 20000

Electrical Without maintenance (time) 10000 10000 10000 10000

Maintenance (time) 20000 20000 20000 20000

Installing Fixed ■■ ■■ - - ■■ ■■ - - ■■ - - - -

method Draw-out ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■

Applied standard IEC 62271-100 IEC 62271-100. JEC 2300 IEC 62271-100. JEC 2300 GB11022

Page 33: Catálogo Geral LS

33

Dimensions Main Cradle

• Secondary trip coil • Mechanical position indicator• Under voltage trip release• Current trip coil• Position S/W• Keylock• Button padlock• Button cover• Mechanical position indicator

• Secondary trip coil • Earthing S/W• Under voltage trip release • Earthing with electromechanical interlock• Current trip coil • Earthing S/W with position S/W• Position S/W • Earthing S/W with keylock• Keylock • Door interlock• Button padlock • MOC• Button cover • TOC• Plug interlock • Shutter padlock• Mechanical position indicator • Emergency mechanical trip device

• Secondary trip coil • Earthing S/W• Under voltage trip release • Earthing with electromechanical interlock• Current trip coil • Earthing S/W with position S/W• Position S/W • Earthing S/W with keylock• Keylock • Door interlock• Button padlock • MOC• Button cover • TOC• Plug interlock • Shutter padlock• Mechanical position indicator • Emergency mechanical trip device

E type• No Shutter

• For MESG

F type• Insulation Shutter

• For MESG

G type• Bushing

• Insulation Shutter

• For MESG

H type• Bushing

• Metal Insulation Shutter

• Closed Compartment structure

• Earthing Switch & Interlock

• For MCSG

• Door Interlock

Accessories

Variouse type of Cradle

Page 34: Catálogo Geral LS

34

Memo

Page 35: Catálogo Geral LS
Page 36: Catálogo Geral LS

��For your safety, please read user's manual thoroughly before operating.

��Contact the nearest authorized service facility for examination, repair, or adjustment.

��Please contact qualified service technician when you need maintenance.Do not disassemble or repair by yourself!

��Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions

�LS Industrial Systems (Middle East) FZE ��Dubai, U.A.E. Address: P.O.Box-114216, API World Tower, 303B, Sheikhe Zayed Road, Dubai, U.A.E. Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: [email protected]

�Dalian LS Industrial Systems Co., Ltd. ��Dalian, ChinaAddress: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, ChinaTel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: [email protected]

�LS Industrial Systems (Wuxi) Co., Ltd. ��Wuxi, ChinaAddress: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu,214028, P.R.ChinaTel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: [email protected]

�LS-VINA Industrial Systems Co., Ltd. ��Hanoi, VietnamAddress: Nguyen Khe - Dong Anh - Ha Noi - Viet NamTel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: [email protected]

�LS-VINA Industrial Systems Co., Ltd. ��Hochiminh , VietnamAddress: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, VietnamTel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: [email protected]

�LS Industrial Systems Tokyo Office ��Tokyo, JapanAddress: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, JapanTel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: [email protected]

�LS Industrial Systems Shanghai Office ��Shanghai, ChinaAddress: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. ChinaTel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: [email protected]

�LS Industrial Systems Beijing Office ��Beijing, ChinaAddress: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,Beijing 100013, P.R. ChinaTel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: [email protected]

�LS Industrial Systems Guangzhou Office ��Guangzhou, ChinaAddress: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. ChinaTel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: [email protected]

�LS Industrial Systems Chengdu Office ��Chengdu, ChinaAddress: 12Floor, Guodong Building, No52 Jindun Road Chengdu, 610041, P.R. ChinaTel: 86-28-8612-9151 Fax: 86-28-8612-9236 e-mail: [email protected]

�LS Industrial Systems Qingdao Office ��Qingdao, ChinaAddress: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. ChinaTel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: [email protected]

Specifications in this catalog are subject to change without notice due to continuous product development and improvement.

�� HEAD OFFICELS Tower, 1026-6 Hokyeh 1dong, Dongan-gu, Anyang, Kyonggi-Do, 431-848, KoreaTel. (82-2)2034-4887, 4873, 4918, 4148Fax. (82-2)2034-4648

�� CHEONG-JU PLANTCheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,Cheong Ju, 361-720, Korea

��Global Network

www.lsis.biz

2009. 07 LOW VOLTAGE CIRCUIT BREAKERS & CONTACTORS(E) 2004. 02/(22) 2009. 07 Printed in Korea STAFF