catalog 1106-1 - daikin...
TRANSCRIPT
Model RWA
Daikin Rooftop Water Source Heat Pumps
Model RWA, RGA – Downflow Discharge and Return Model, RWC, RGC – Horizontal Discharge and Return
Unit Sizes 150 – 420 • R-410A Refrigerant
Catalog 1106-1
Contents
CAT 1106-1 • ROOFTOP WSHP 2 www.DaikinApplied.com
Features and Options . . . . . . . . . . . . . . . . . . . . . . . . . . 3Standard Features: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Optional Features: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Model Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Design Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Heavy Duty Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Paint Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Compressor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Separate Refrigeration Circuits. . . . . . . . . . . . . . . . . . . . . . . 4Indoor Air Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4The Coaxial Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Air and Water Proving Switches . . . . . . . . . . . . . . . . . . . . . . 4Evaporator Blower and Motor . . . . . . . . . . . . . . . . . . . . . . . . 5Refrigeration Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Electromechanical Controls . . . . . . . . . . . . . . . . . . . . . . . . . 5Terminal Board Connections. . . . . . . . . . . . . . . . . . . . . . . . . 5Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Sloped Stainless Steel IAQ Condensate Drain Pan . . . . . . . 5Power Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Multiple Refrigeration Circuit. . . . . . . . . . . . . . . . . . . . . . . . . 5Harsh Environment Construction . . . . . . . . . . . . . . . . . . . . . 6Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Humidity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Cupro-Nickel Coaxial Water Coil . . . . . . . . . . . . . . . . . . . . . 6Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Unit Location - General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Unit Location - Rooftop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation and Application . . . . . . . . . . . . . . . . . . . . . 7Unit Location - Slab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Ductwork. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Condensate Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Independent Power Source . . . . . . . . . . . . . . . . . . . . . . . . . 7Main Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Water Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Ground Loop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Sizes 150-200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Sizes 240-420. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Capacity Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Size 150 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Size 180 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Size 210 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Size 200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Size 240 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Size 300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Size 360 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Size 420 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Correction Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Cooling Correction Multipliers . . . . . . . . . . . . . . . . . . . . . . . 20
Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Sizes 150-200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Sizes 240-420. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Models RWA, RGA, RWC, RGC. . . . . . . . . . . . . . . . . . . . . 23
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Model RWA, RGA – Size 1 50-210 . . . . . . . . . . . . . . . . . . 24Model RWA, RGA – Size 200-420 . . . . . . . . . . . . . . . . . . . 25Model RWC, RGC – Size 150-210 . . . . . . . . . . . . . . . . . . . 26Model RWC, RGC – Size 200-420 . . . . . . . . . . . . . . . . . . . 2714" High Roof Curb – Size 150-210 . . . . . . . . . . . . . . . . . . 2824" High Roof Curb – Size 150-210 . . . . . . . . . . . . . . . . . . 2814" High Roof Curb – Size 200-420 . . . . . . . . . . . . . . . . . . 2924" High Roof Curb – Size 200-420 . . . . . . . . . . . . . . . . . . 29
Engineering Guide Specifications . . . . . . . . . . . . . . 30Model RWA, RGA – Downflow Discharge and Return & Model, RWC, RGC – Horizontal Discharge and Horizontal Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-31
Model RWA, RGA – Downflow Discharge and Return & Model RWC, RGC - Horizontal Discharge and Horizontal ReturnStandard Features:● Heavy duty cabinet construction ● Downflow and horizontal discharge arrangements● Supply fan with seismic spring vibration isolation● 12.5 to 35 ton (44 to 123 kW) capacity● Multiple fan motor sizes● Multiple access panels● Fully insulated – double-wall construction● Crankcase heaters● Electromechanical controls● Sloped stainless steel drain pan● Multiple refrigerant circuits● Factory tested● Certified UL/ANSI standards by ETL ● R-410A refrigerant
Features and Options
Optional Features:● Hot gas reheat● Cupro-nickel inner tube heat exchanger● Hot gas by-pass on the lead circuit● Water regulating valve (see Note 2)● Harsh environment corrosion protection● Full perimeter roof curb● Geothermal operation● Economizer • with enthalpy changeover control • 0-10 VDC modulating actuator for control by others● Factory wired 115 volt GFCI receptacle with 15 amp
breaker● Firestat located in the return air stream with manual
reset limit control● Integral power disconnect for applications up to 100
ampsNote: 1. If a barometric damper is required, the WRWC and
WRGC (with horizontal supply and return) unit must use a field-furnished and installed barometric damper. This is because the horizontal supply/return unit economizer covers up the barometric relief on the unit.
2. For entering water temperatures below 70°F (21°C), the optional water regulating valve must be selected as a factory installed option.
Model Nomenclature W RWA 2 150 E F Y
Product CategoryW = WSHP
Product IdentifierRWA = Rooftop Downflow Water Source Heat PumpRWC = Rooftop Horizontal Water Source Heat PumpRGA = Rooftop Downflow WSHP (Geothermal Unit)RGC = Rooftop Horizontal WSHP (Geothermal Unit)
Design Series1 = 1st Design2 = 2nd Design3 = 3rd Design4 = 4th Design
Nominal Capacity150 = 150,000 Btuh Nominal Cooling180 = 180,000 Btuh Nominal Cooling210 = 210,000 Btuh Nominal Cooling 200 = 200,000 Btuh Nominal Cooling240 = 240,000 Btuh Nominal Cooling300 = 300,000 Btuh Nominal Cooling360 = 360,000 Btuh Nominal Cooling420 = 420,000 Btuh Nominal Cooling
Cabinet HeightY = None
VoltageF = 208-230/60/3K = 460/60/3L = 575/60/3
ControlsE = Electromechanical
Note: For illustration purposes only. Not all options available with all models.
Please consult Daikin Sales Representative for specific availability.
CAT 1106-1 • ROOFTOP WSHP 3 www.DaikinApplied.com
Design Features
CAT 1106-1 • ROOFTOP WSHP 4 www.DaikinApplied.com
ApplicationPackaged curb-mounted vertical discharge or horizontal discharge and return water-to-air heat pump air condi-tioners are an excellent choice for a multitude of building applications ranging in unit sizes from 12.5 to 35 tons. Versatile for new building construction or retrofit projects from offices, schools, health care and retirement facili-ties to restaurants, hotels, motels, and industrial opera-tions. The RWA and RWC models are normally used with a water loop system utilizing a cooling tower and boiler, this unit is designed to operate with entering water temperatures between 55°F and 95°F. The RGA and RGC models are rated for ground loop heat exchanger application with entering fluid temperature between 30°F and 100°F.These outdoor roof mounted units are positioned on the roof curb, above the conditioned space, for minimal field ductwork. Roof curbs are available as a field-installed accessory. After assembly each unit is charged and run tested in both the heating and cooling cycles for reliable operation. Units are certified and conform to UL/ANSI Standards by ETL.
Model RWA Unit
Standard Design FeaturesHeavy Duty CabinetAll models are constructed of G-90 galvanized steel. Gasketed access doors are 20-gauge steel with 1", 4-pound density closed cell insulation and a 24-gauge galvanized steel liner. Standard outer panels are insu-lated with 1" 4-pound density closed cell foam insulation with a 24-gauge galvanized steel interior liner. Service access doors are mounted with stainless steel hinges and equipped with one-quarter turn cam operated adjustable compression type latches. The underside of the base panel is insulated with 3/8" closed cell foam insulation.
Paint FinishThe unit is constructed of hot dipped galvanized G-90 steel that is chemically treated with zinc phosphate, coated with 0.2 to 0.3 MIL polyurethane primer then finished with 0.7 to 0.8 MIL polyester top coating.
CompressorUnits equipped with scroll compressors selected for their reliability and high efficiency. Compressor mountings are designed to reduce vibration transmission to the unit structure and minimize piping stress.
Compressor ProtectionAll compressors have crankcase heaters and internal overheat protection.
Separate Refrigeration CircuitsMultiple refrigeration circuits are standard. Multi com-pressor models provide the added benefit of partial standby. Also, they provide two-stage operation with one compressor being activated from the first stage of the two-stage space thermostat on the cooling cycle. On the heating cycle, all compressors are activated by the first stage of the space thermostat.
Indoor Air CoilThe indoor air coils have aluminum fins formed on multiple rows of seamless copper tubing arranged in a staggered tube configuration. The tubes are mechani-cally expanded, firmly bonding the tube to the collar of each fin.
The Coaxial Water CoilThe Coaxial Water Coil consists of an enhanced surface inner copper tube with outer steel tube (tube-in-tube). Water connections are stubbed off inside the cabinet. Field piped return and supply water lines enter through individual sleeves in the compressor base pan section after passing through the roof curb. Units are shipped with water pressure taps and upper elbows for easy con-nection to the water source. RGA and RGC models are equipped with fully insulated refrigerant and water lines and an insulated coaxial water coil.
Air and Water Proving SwitchesAn air proving switch prevents system operation unless there is proof of blower operation. The water proving switch prevents system operation if there is no fluid flow through the coaxial heat exchanger.
Design Features
Evaporator Blower and MotorAll units are fitted with a DWDI forward curved fan as-sembly mounted on spring vibration isolation. A slide out deck allows for blower assembly removal from the cabinet to service or inspect. The shaft is belt driven with adjustable drive sheave connected to an open drip proof motor with sealed ball bearings. Adjustable V-belt drives provide a minimum rating of 140% of the motor name-plate brake horsepower when the adjustable pulley is at the minimum RPM. The bearings on both the blower shaft and motor are permanently lubricated.
Evaporator Access
Refrigeration CircuitThe refrigerant system(s) operate with R-410A refrig-erant and include the compressor, crankcase heater, copper-tube, aluminum finned condenser and evapora-tor coils. The refrigerant circuit includes filter/drier, high pressure safety control (manual-reset), low pressure control/loss of charge protector (auto-reset), dual gauge connections for high and low pressure readings and thermal expansion valve with adjustable superheat. The condensing section of the unit is integral to the unit.
Electromechanical ControlsUnit electrical power entry is through the curb. The starter/control panel includes a programmable logic con-troller and a complete modular, integrated motor control system mounted on din rails. All safety and operating controls shall be factory mounted. The system includes all relays, fan contactors, compressor contactors, and power distribution. The 24-volt control circuit includes a transformer and low voltage terminal strip for interface with a control system.
Terminal Board ConnectionsTerminal boards are furnished for 24-volt thermostat con-nections on units.
FiltersAll models are shipped with 2-inch thick disposable glass fiber media filters mounted in a factory installed flat filter rack on the return air opening. The standard filter rack is capable of using 2" filters, 4" filters or 2" pre-filters and 4" after filters.
Sloped Stainless Steel IAQ Condensate Drain PanThe condensate drain pan is double-sloped to comply with ASHRAE Standard 62-1089R and fabricated from stainless steel. The bottom is insulated with closed cell neoprene insulation. Condensation may be drained from a MPT drain fitting positioned at the exterior of the cabinet.
Power EntryA chase is installed in the curb, directly under the electri-calcontrol section to bring power wiring inside the curb, preventing a separate roof penetration. The sleeve must be sealed after wiring is completed with suitable mastic to prevent water from entering the space. Power enter-ing through the curb is standard in all models.
Multiple Refrigeration CircuitAll units use two separate refrigeration circuits. This de-sign offers two stages of cooling for load shedding when conditions allow.Multiple compressors on independent circuits also offer the added benefit of continuous operation in the event of a failure in one of the circuits.
CAT 1106-1 • ROOFTOP WSHP 5 www.DaikinApplied.com
Design Features
CAT 1106-1 • ROOFTOP WSHP 6 www.DaikinApplied.com
Optional FeaturesHarsh Environment ConstructionThermoguard® condenser coil coating with antimicrobial agent for unit cabinet, base pan, evaporator and con-denser coils
ElectricalClogged Filter Indicator (Filter Differential Gauge)Dirty or clogged filters are indicated when the preset pressure differential across the filters is reached. The indicator is factory installed and is manually reset. It includes contacts for remote indication.
FirestatThis control, mounted in the return air section, de-ener-gizes the unit when return air reaches 135°F. The firestat is a manual reset control.
115-Volt Ground Fault Circuit Interrupter (GFCI ReceptacleA 115-volt GFCI receptacle mounted in a 2" x 4" en-closure and is furnished with a 15 amp circuit breaker. Separate 115-volt power source and ground is required.
Humidity ControlHot Gas BypassHot gas bypass is a means of capacity control during lower ambient temperature conditions. The Hot Gas Bypass valve is an adjustable valve and should be set to open when the refrigerant suction pressure drops to 107-112 psig. It varies unit capacity by introducing discharge refrigerant into the evaporator circuit where it creates a false evaporator load. The hot gas is cooled prior to its return to the compressor as it passes through the evaporator.The Hot Gas Bypass Solenoid Valve is energized through the thermostat and routs discharge gas to the hot gas bypass valve. It is de-energized during the pump down cycle.
Hot Gas Reheat with Water Regulating Valve (WRV)Hot gas reheat (HGRH) helps to maintain specific hu-midity and temperature levels in a conditioned space by cooling, dehumidifying and then re-heating the air. The modulating HGRH provides superior temperature control compared to typical "on-off" HGRH.HGRH includes a water regulating valve to maintain head pressure by adjusting water flow.Hot gas reheat requires use of a conventional field sup-plied humidistat.
Cupro-Nickel Coaxial Water CoilCupro-nickel inner tube, steel outer tube water to refrig-erant heat exchanger
Economizer • With Enthalpy Changeover • 0-10 VDC Modulating Actuator (Controls by
others)
Installation and ApplicationDaikin WRWA/WRWC units are designed for rooftop or slab mounted installations.
Unit Location - General • Avoid locations next to exhaust fans or flues. • Select a location where external water drainage
cannot collect around the unit. • Locate the unit as near as possible to the center
of the area to be environmentally controlled. • Other considerations such as unit supports, roof
opening, roof curb flashing, drain requirements, and power supply locations should be checked and verified.
Unit Location - Rooftop • Structural members supporting the unit must be
sufficiently strong for the weight of the unit and mounting rails.
Transmission of sound into the building is sometimes a problem when the structure is not strong enough. • Units with vertical returns are available with a 14"
high solid bottom roof curb. Units with horizontal supply and return air duct connections are made with the use of a 24" high solid bottom roof curb. Rooftop curbs are sold separately as an option.
• Proper installation for the RTU requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prior to setting rooftop unit on curb.
• Inspect roof curb to insure that none of the utility services (electric, gas, drain lines) routed through the curb protrude above the curb.
• Duct connections should be made before unit is set on roof curb.
• Being a fully welded solid bottom curb, duct openings are to be sized and cut by the installing contractor.
• Tie down kits are required when the units are mounted on roof curbs and will be included with every unit. See installation instructions included with the tie down kit.
• Rooftop units also require the installation of an equipment support rail in addition to the roof curb.
Installation and Application
CAT 1106-1 • ROOFTOP WSHP 7 www.DaikinApplied.com
Unit Location - Slab • When installed at ground level, the unit should be
mounted on a level concrete slab which should extend at least 2" beyond the unit on all sides.
• The top of the slab should be 2" above the ground level. Where snowfall is anticipated, mount the unit above the maximum snow depth for the area.
• The depth of the slab below the ground level and its structural design is governed by the type of soil and climatic conditions.
• The slab must not be in contact with any part of the building wall or foundation. The space between the slab and building wall prevents the possibility of transmitting vibration to the building.
• The dimensions of the slab or roof mount should be checked and verified before the equipment arrives.
• Locate the unit so roof runoff water does not pour directly on the unit. Provide gutter or other shielding at roof level.
• Do not locate the unit under an overhang that will short circuit hot air to the coil intakes.
ClearancesA clearance of 24"- 36" must be allowed for service and maintenance access to the compressor and electrical panelSufficient clearance must be available for service, edge of roof, other units, or hazards.Adequate clearance around the unit must be kept for safety, accessibility, service and maintenance. 48 inches clearance is required on the control end of the unit. This clearance must also be maintained for compressor removal.A 48 inch clearance is also required on the (outside air) end of the unit for blower removal and for adequate out-side air accessibility. All combustible materials must be kept out of the area.Figure 1: Unit Clearance Area
24" - 36"
48"
Control Panel
Filter Access
Outside AirIntake Hood
CondensateDrain Pan
Supply Fan
48"
36"
DuctworkProperly sized and installed ductwork is critical to reli-able performance of the unit and system. All ductwork must be installed according to local codes, practices and requirements.All duct connections with the use of a curb are to be field sized and cut. Industry manuals should be used as a guide to size and design the duct system.Ducts passing through unconditioned spaces must be well insulated and include a vapor barrier to prevent condensation from forming.
Condensate PipingA condensate trap must be installed. Trap must be primed before operating unit. Units with high internal and external static pressure drops will require a deeper trap.If condensate is to be piped into the building drainage system, the drain line must penetrate the roof external to the unit. Refer to local codes for additional requirements.Drainage of condensate directly onto the roof is ac-ceptable if permitted by local codes. A small drip pad of either stone, tar, wood or metal should be provided to prevent any possible damage to the roof.
ElectricalWiring ConnectionsPower wiring should be connected to the main power terminal block located within the main control section.Power wiring connections on units with factory discon-nects should be made at the line side of the disconnect switch.Low voltage wiring connections are made to the remote mounted controller or time clock.
Independent Power SourceIt is recommended that an independent 115-volt power source be brought to the vicinity of the rooftop unit for portable lights and tools used by the service mechanic.
Main Power WiringThe units are factory wired for the voltage shown on the nameplate. Make sure main power wiring is sized for the minimum wire ampacity shown on the nameplate.An external weather-tight disconnect switch properly sized for the unit total load is required for each unit. Dis-connect must be installed in accordance with local and/or national electric codes.Power wiring may enter the unit through the base pan and roof curbs on all models. Install conduit connectors at the entrance locations. External connectors must be weatherproof.
Performance Data
Water LoopTable 1: Models RWA, RWC
Unit SizeAir Flow Water Flow
Voltage Cooling Heating
CFM L/s GPM L/s Btu/hr Watts EER Btu/hr Watts COP
150 5000 2360 31.3 1.97
208-60-3
164390 11033 14.9 198666 58175 5.3230-60-3
460-60-3
180 6000 2832 37.5 2.37
208-60-3
199072 13361 14.9 241608 70750 5.2230-60-3
460-60-3
210 6000 2832 43.8 2.76
208-60-3
222472 14541 15.3 265856 77851 5.5230-60-3
460-60-3
200 6000 2832 41.7 2.63
208-60-3
225066 14245 15.8 264276 77388 5.3230-60-3
460-60-3
240 8000 3776 50.0 3.15
208-60-3
263654 16076 16.4 298834 87508 5.6230-60-3
460-60-3
300 10000 4719 62.5 3.94
208-60-3
358174 25768 13.9 439652 128743 4.9230-60-3
460-60-3
360 12000 5663 75.0 4.73
208-60-3
414688 28999 14.3 497222 145602 4.9230-60-3
460-60-3
420 12000 5663 87.6 5.53
208-60-3
477606 32490 14.7 583648 170910 5.0230-60-3
460-60-3
Notes:EER = Energy Efficiency RatioCOP = Coefficient of Performance. 1 . Cooling capacity is based on 80.6°F (27°C) db, 66.2°F (19°C) wb entering air temperature and 86°F (30°C) entering, 95°F (35°C)
leaving water temperature. Heating capacity based on 68°F (20°C) db entering air temperature and 68°F (20°C) entering water temperature. Net capacities include fan motor heat.
CAT 1106-1 • ROOFTOP WSHP 8 www.DaikinApplied.com
Performance Data
Ground LoopTable 2: Models RGA, RGC
Unit SizeAir Flow Water Flow
Voltage Cooling Heating
CFM L/s GPM L/s Btu/hr Watts EER Btu/hr Watts COP
150 5000 2360 31.3 1.97
208-60-3
171048 11033 16.8 128646 37671 3.8230-60-3
460-60-3
180 6000 2832 37.5 2.37
208-60-3
206992 13361 16.7 155900 45652 4.0230-60-3
460-60-3
210 6000 2832 43.8 2.76
208-60-3
231598 14541 17.2 167484 49044 4.0230-60-3
460-60-3
200 6000 2832 41.7 2.63
208-60-3
234082 14245 17.7 167404 49021 4.0230-60-3
460-60-3
240 8000 3776 50.0 3.15
208-60-3
274346 16076 18.5 190026 55645 4.2230-60-3
460-60-3
300 10000 4719 62.5 3.94
208-60-3
372950 25768 15.6 285872 83712 3.8230-60-3
460-60-3
360 12000 5663 75.0 4.73
208-60-3
430604 28999 15.9 315926 92513 3.7230-60-3
460-60-3
420 12000 5663 75.0 4.73
208-60-3
496578 30096 16.5 373286 109309 3.8230-60-3
460-60-3
Notes:EER = Energy Efficiency RatioCOP = Coefficient of Performance. 1 . Cooling capacity is based on 80.6°F (27oC) db, 66.2°F (19°C) wb entering air temperature and 77°F (25°C) entering, 87°F (31°C)
leaving water temperature. Heating capacity based on 68°F (20°C) db entering air temperature and 32°F (0°C) entering water temperature. Net capacities include fan motor heat.
CAT 1106-1 • ROOFTOP WSHP 9 www.DaikinApplied.com
Electrical Data
Sizes 150-200Table 3: Models RWA, RGA, RWC, RGC, Sizes 150-200
UnitSize
Fan MotorHP
Power Compressor FanMotor FLA
Total UnitFLA
Min./Max.Volts
Min . Circuit Ampacity
Max. Fuse SizeVoltage/Hz/Phase Qty RLA (each) LRA (each)
150
3.0
208-60-3 2 22.5 149.0 9.0 54.0 187/220 59.6 80230-60-3 2 22.5 149.0 9.0 54.0 187/220 59.6 80460-60-3 2 10.6 75.0 4.1 25.3 414/506 28.0 35575-60-3 2 7.7 54.0 3.3 18.7 518/632 20.6 25
5.0
208-60-3 2 22.5 149.0 14.5 59.5 187/220 65.1 80230-60-3 2 22.5 149.0 14.5 59.5 187/220 65.1 80460-60-3 2 10.6 75.0 6.8 28.0 414/506 30.7 40575-60-3 2 7.7 54.0 5.2 20.6 518/632 22.5 30
7.5
208-60-3 2 22.5 149.0 22.3 67.3 187/220 72.9 90230-60-3 2 22.5 149.0 22.3 67.3 187/220 72.9 90460-60-3 2 10.6 75.0 10.0 31.2 414/506 33.9 40575-60-3 2 7.7 54.0 7.6 23.0 518/632 24.9 30
10.0
208-60-3 2 22.5 149.0 29.0 74.0 187/220 79.6 100230-60-3 2 22.5 149.0 29.0 74.0 187/220 79.6 100460-60-3 2 10.6 75.0 12.9 34.1 414/506 36.8 45575-60-3 2 7.7 54.0 10.1 25.5 518/632 27.4 35
180
5.0
208-60-3 2 25.0 164.0 14.5 64.5 187/220 70.8 90230-60-3 2 25.0 164.0 14.5 64.5 187/220 70.8 90460-60-3 2 12.2 100.0 6.8 31.2 414/506 34.3 45575-60-3 2 9.0 78.0 5.2 23.2 518/632 25.5 30
7.5
208-60-3 2 25.0 164.0 21.5 71.5 187/220 77.8 100230-60-3 2 25.0 164.0 21.5 71.5 187/220 77.8 100460-60-3 2 12.2 100.0 10.0 34.4 414/506 37.5 45575-60-3 2 9.0 78.0 7.6 25.6 518/632 27.9 35
10.0
208-60-3 2 25.0 164.0 29.0 79.0 187/220 85.3 110230-60-3 2 25.0 164.0 29.0 79.0 187/220 85.3 110460-60-3 2 12.2 75.0 12.9 37.3 414/506 40.4 50575-60-3 2 9.0 78.0 10.1 28.1 518/632 30.4 35
210
5.0
208-60-3 2 29.5 195.0 14.5 73.5 187/220 80.9 110230-60-3 2 29.5 195.0 14.5 73.5 187/220 80.9 110460-60-3 2 14.8 95.0 6.8 36.4 414/506 40.1 50575-60-3 2 12.2 80.0 5.2 29.6 518/632 32.7 45
7.5
208-60-3 2 29.5 195.0 21.5 80.5 187/220 87.9 110230-60-3 2 29.5 195.0 21.5 80.5 187/220 87.9 110460-60-3 2 14.8 95.0 10.0 39.6 414/506 43.3 50575-60-3 2 12.2 80.0 7.6 32.0 518/632 35.1 45
10.0
208-60-3 2 29.5 195.0 28.0 87.0 187/220 94.4 110230-60-3 2 29.5 195.0 28.0 87.0 187/220 94.4 110460-60-3 2 14.8 95.0 12.9 42.5 414/506 46.2 60575-60-3 2 12.2 80.0 10.1 34.5 518/632 37.6 50
200
3.0
208-60-3 2 29.5 195.0 9.0 68.0 187/220 75.4 100230-60-3 2 29.5 195.0 9.0 68.0 187/220 75.4 100460-60-3 2 14.8 95.0 4.1 33.7 414/506 37.4 50575-60-3 2 12.2 80.0 3.3 27.7 518/632 30.8 40
5.0
208-60-3 2 29.5 195.0 14.5 73.5 187/220 80.9 110230-60-3 2 29.5 195.0 14.5 73.5 187/220 80.9 110460-60-3 2 14.8 95.0 6.8 36.4 414/506 40.1 50575-60-3 2 12.2 80.0 5.2 29.6 518/632 32.7 45
7.5
208-60-3 2 29.5 195.0 21.5 80.5 187/220 87.9 110230-60-3 2 29.5 195.0 21.5 80.5 187/220 87.9 110460-60-3 2 14.8 95.0 10.0 39.6 414/506 43.3 50575-60-3 2 12.2 80.0 7.6 32.0 518/632 35.1 45
10.0
208-60-3 2 29.5 195.0 28.0 87.0 187/220 94.4 110230-60-3 2 29.5 195.0 28.0 87.0 187/220 94.4 110460-60-3 2 14.8 95.0 12.9 42.5 414/506 46.2 60575-60-3 2 12.2 80.0 10.1 34.5 518/632 37.6 50
CAT 1106-1 • ROOFTOP WSHP 10 www.DaikinApplied.com
Electrical Data
Sizes 240-420Table 4: Models RWA, RGA, RWC, RGC, Sizes 240-420
UnitSize
Fan MotorHP
Power Compressor FanMotor FLA
Total UnitFLA
Min./Max.Voltage
Min . Circuit Ampacity
Max. Fuse SizeVoltage/Hz/Phase Qty RLA (each) LRA (each)
240
5.0
208-60-3 2 30.2 225.0 14.5 74.9 187/220 82.5 110230-60-3 2 30.2 225.0 14.5 74.9 187/220 82.5 110460-60-3 2 16.7 114.0 6.8 40.2 414/506 44.4 60575-60-3 2 12.2 80.0 5.2 29.6 518/632 32.7 45
7.5
208-60-3 2 30.2 225.0 21.5 81.9 187/220 89.5 110230-60-3 2 30.2 225.0 21.5 81.9 187/220 89.5 110460-60-3 2 16.7 114.0 10.0 43.4 414/506 47.6 60575-60-3 2 12.2 80.0 7.6 32.0 518/632 35.1 45
10.0
208-60-3 2 30.2 225.0 28.0 88.4 187/220 96.0 125230-60-3 2 30.2 225.0 28.0 88.4 187/220 96.0 125460-60-3 2 16.7 114.0 12.9 46.3 414/506 50.5 60575-60-3 2 12.2 80.0 10.1 34.5 518/632 37.6 50
5.0
208-60-3 2 48.1 245.0 37.8 98.2 187/220 105.8 125230-60-3 2 48.1 245.0 37.8 98.2 187/220 105.8 125460-60-3 2 18.6 125.0 18.9 52.3 414/506 56.5 70575-60-3 2 14.7 100.0 15.1 39.5 518/632 42.6 55
300
7.5
208-60-3 2 48.1 245.0 14.5 110.7 187/220 122.7 150230-60-3 2 48.1 245.0 14.5 110.7 187/220 122.7 150460-60-3 2 18.6 125.0 6.8 44.0 414/506 48.7 60575-60-3 2 14.7 100.0 5.2 34.6 518/632 38.3 50
10.0
208-60-3 2 48.1 245.0 22.3 118.5 187/220 130.5 175230-60-3 2 48.1 245.0 22.3 118.5 187/220 130.5 175460-60-3 2 18.6 125.0 10.0 47.2 414/506 51.9 70575-60-3 2 14.7 100.0 7.6 37.0 518/632 40.7 55
15.0
208-60-3 2 48.1 245.0 29.0 125.2 187/220 137.2 175230-60-3 2 48.1 245.0 29.0 125.2 187/220 137.2 175460-60-3 2 18.6 125.0 12.9 50.1 414/506 54.8 70575-60-3 2 14.7 100.0 10.1 39.5 518/632 43.2 55
5.0
208-60-3 2 55.8 340.0 43.4 139.6 187/220 151.6 175230-60-3 2 55.8 340.0 43.4 139.6 187/220 151.6 175460-60-3 2 27.0 173.0 18.9 56.1 414/506 60.8 70575-60-3 2 23.3 148.0 15.1 44.5 518/632 48.2 60
360
7.5
208-60-3 2 55.8 340.0 22.3 133.9 187/220 147.9 200230-60-3 2 55.8 340.0 22.3 133.9 187/220 147.9 200460-60-3 2 27.0 173.0 10.0 64.0 414/506 70.8 90575-60-3 2 23.3 148.0 7.6 54.2 518/632 60.0 80
10.0
208-60-3 2 55.8 340.0 29.0 140.6 187/220 154.6 200230-60-3 2 55.8 340.0 29.0 140.6 187/220 154.6 200460-60-3 2 27.0 173.0 12.9 66.9 414/506 73.7 100575-60-3 2 23.3 148.0 10.1 56.7 518/632 62.5 80
15.0
208-60-3 2 55.8 340.0 43.4 155.0 187/220 169.0 200230-60-3 2 55.8 340.0 43.4 155.0 187/220 169.0 200460-60-3 2 27.0 173.0 18.9 72.9 414/506 79.7 100575-60-3 2 23.3 148.0 15.1 61.7 518/632 67.5 90
7.5
208-60-3 2 29.5 195.0 57.0 168.6 187/220 182.6 225230-60-3 2 29.5 195.0 57.0 168.6 187/220 182.6 225460-60-3 2 14.8 95.0 24.5 78.5 414/506 85.3 110575-60-3 2 23.3 148.0 19.6 66.2 518/632 72.0 90
420
10.0
208-60-3 4 29.5 195.0 29.0 147.0 187/220 124.9 150230-60-3 4 29.5 195.0 29.0 147.0 187/220 124.9 150460-60-3 4 14.8 95.0 12.9 72.1 414/506 61.0 70575-60-3 4 23.3 148.0 10.1 103.3 518/632 109.1 130
15.0
208-60-3 4 29.5 195.0 43.4 161.4 187/220 139.3 175230-60-3 4 29.5 195.0 43.4 161.4 187/220 139.3 175460-60-3 4 14.8 95.0 18.9 78.1 414/506 67.0 80575-60-3 4 23.3 148.0 15.1 108.3 518/632 114.1 130
20.0
208-60-3 4 29.5 195.0 57.0 175.0 187/220 152.9 200230-60-3 4 29.5 195.0 57.0 175.0 187/220 152.9 200460-60-3 4 14.8 95.0 24.5 83.7 414/506 72.6 90575-60-3 4 23.3 148.0 19.6 112.8 518/632 118.6 140
CAT 1106-1 • ROOFTOP WSHP 11 www.DaikinApplied.com
Capacity Data
Size 150
CAT 1106-1 • ROOFTOP WSHP 12 www.DaikinApplied.com
Table 5: Cooling
EWT(°F) GPM CFM
Total Capacity
Btu/hr
Sensible Capacity
Btu/hrWatts
Heat Rejected
Btu/hr
40
27.8
4500 195700 139300 7050 220800
5000 199300 146500 7050 224300
5500 202300 153500 7050 227300
49
4500 197400 140000 6890 222200
5000 201200 146900 6884 226000
5500 204200 153900 6880 229000
50
27.8
4500 188800 136300 7708 215100
5000 192100 143500 7712 218500
5500 195000 150000 7718 221300
49
4500 190400 137000 7546 216500
5000 193900 144200 7546 219900
5500 196900 150500 7550 222900
70
27.8
4500 174200 130000 9244 203600
5000 177300 136300 9262 206800
5500 179700 143300 9264 209200
49
4500 175600 130500 9082 204700
5000 178800 136800 9100 208000
5500 181300 143900 9100 210400
85
27.8
4500 163200 124400 10600 195700
5000 165800 131800 10600 198300
5500 168100 139100 10596 200600
49
4500 164300 125800 10424 196400
5000 167100 132900 10426 199100
5500 169600 139700 10428 201600
100
27.8
4500 151500 119200 12210 187800
5000 153900 126600 12204 190200
5500 156000 133300 12208 192300
49
4500 152500 119300 12086 188500
5000 154900 127400 12052 190800
5500 157200 132900 12082 193300
110
27.8
4500 143200 116200 13454 182600
5000 145500 123000 13456 185000
5500 147400 129700 13456 186900
49
4500 144000 116700 13324 183100
5000 146500 123200 13314 185600
5500 148400 129800 13312 187500
Table 6: Heating
EWT(°F) GPM CFM
Heating Capacity
Btu/hrWatts
Heat Absorpted
Btu/hr
30
27.8
4500 116800 9800 80100
5000 117100 9686 80900
5500 117400 9570 81700
49
4500 120300 9900 83400
5000 120600 9744 84400
5500 120900 9620 85100
40
27.8
4500 131400 10100 94300
5000 129000 9900 95400
5500 131400 9770 96200
49
4500 135800 10200 98600
5000 135500 9900 99800
5500 136000 9850 100700
50
27.8
4500 147000 10400 110100
5000 147500 10200 111300
5500 148000 10000 112320
49
4500 152500 10500 115500
5000 153200 10300 116800
5500 153700 10100 117800
60
27.8
4500 164800 10700 127300
5000 165500 10500 128800
5500 166100 10300 129900
49
4500 171500 10800 133800
5000 172400 10600 135400
5500 173100 10400 136700
70
27.8
4500 183800 11100 145500
5000 184700 10800 147300
5500 185400 10600 148700
49
4500 191600 11200 153100
5000 192700 10900 155200
5500 193700 10700 156800
80
27.8
4500 203500 11500 164500
5000 204700 11200 166700
5500 205700 10900 168500
49
4500 212600 11600 173200
5000 214000 11306 175700
5500 215200 11000 177800Notes:1. Cooling capacities shown are based on 80°F DBT / 67°F WBT entering air coil conditions.2. Cooling capacities shown are gross capacities. For net capacities, multiply blower BHP (Break Horse Power) required times 2,545 and subtract from total and sensible Btu/h in tables.3. Typical of all heating and cooling capacitiy tables. Apply the cooling correction factors found on page 20.
Capacity Data
Size 180
CAT 1106-1 • ROOFTOP WSHP 13 www.DaikinApplied.com
Table 7: Cooling
EWT(°F) GPM CFM
Total Capacity
Btu/hr
Sensible Capacity
Btu/hrWatts
Heat Rejected
Btu/hr
40
34
5500 231200 166000 9178 263300
6000 234400 172900 9232 266700
6500 237200 179600 9278 269600
60
5500 235300 167800 8770 266700
6000 238700 174700 8820 270300
6500 241600 181400 8864 273300
50
34
5500 223200 162500 9980 256800
6000 226200 169400 10032 260000
6500 228800 176000 10076 262600
60
5500 227200 164200 9580 260000
6000 230400 171100 8626 263300
6500 233100 177300 9668 266200
70
34
5500 207000 155600 11734 244000
6000 209700 162400 11774 246800
6500 211900 169000 11806 249200
60
5500 210400 156500 11350 246700
6000 213300 163900 11374 249600
6500 215700 170500 11402 252000
85
34
5500 194400 149600 13312 234900
6000 196800 156900 13340 237300
6500 199000 163300 13372 239700
60
5500 197500 151500 12892 237100
6000 200100 158300 12922 239700
6500 202300 167800 12948 242000
100
34
5500 181100 144600 15218 223100
6000 183400 151100 15252 228600
6500 185400 157500 15280 230600
60
5500 183900 145700 14790 227900
6000 186200 151700 14834 230400
6500 188400 158100 14856 232600
110
34
5500 171900 140600 16758 220800
6000 174000 147100 16788 223000
6500 175800 153500 16814 224700
60
5500 174400 141600 16322 222200
6000 176600 148200 16344 224500
6500 178500 153900 16386 226600
Table 8: Heating
EWT(°F) GPM CFM
Heating Capacity
Btu/hrWatts
Heat Absorpted
Btu/hr
30
34
5500 135240 11186 92750
6000 135390 11036 93364
6500 134490 10890 93976
60
5500 142704 11396 99758
6000 142940 11238 100496
6500 142176 11082 101230
40
34
5500 150276 11612 107858
6000 150502 11440 108622
6500 150700 11296 109268
60
5500 159782 11880 116668
6000 160078 11696 117598
6500 160382 11542 118388
50
34
5500 167920 12086 124334
6000 168218 11898 125226
6500 168478 11740 125976
60
5500 179648 12386 135352
6000 180114 12180 136470
6500 180516 12010 137410
60
34
5500 186970 12576 142226
6000 187382 12358 143338
6500 187742 12174 144272
60
5500 201054 12952 155412
6000 201692 12712 156816
6500 202242 12512 158002
70
34
5500 207136 13118 161098
6000 207688 12862 162462
6500 208166 12652 163610
60
5500 223766 13582 176592
6000 224612 13302 178336
6500 225342 13072 179806
80
34
5500 228282 13710 180792
6000 229000 13418 182444
6500 229620 13178 183834
60
5500 247628 14280 198716
6000 248724 13960 200848
6500 249666 13694 202646
Notes:1. Cooling capacities shown are based on 80°F DBT / 67°F WBT entering air coil conditions.2. Cooling capacities shown are gross capacities. For net capacities, multiply blower BHP (Break Horse Power) required times 2,545 and subtract from total and sensible Btu/h in tables.3. Typical of all heating and cooling capacitiy tables. Apply the cooling correction factors found on page 20.4. For entering water temperatures below 70°F (21°C), the optional water regulating valve must be selected as a factory installed option.
Capacity Data
Size 210
CAT 1106-1 • ROOFTOP WSHP 14 www.DaikinApplied.com
Table 9: Cooling
EWT(°F) GPM CFM
Total Capacity
Btu/hr
Sensible Capacity
Btu/hrWatts
Heat Rejected
Btu/hr
40
38
6000 260500 187600 9888 294600
6250 262400 191600 9912 296600
6500 265400 195500 9824 299400
66
6000 265100 189600 9394 298200
6250 267100 193600 9414 300300
6500 269000 197600 9432 302200
50
38
6000 254100 184800 10834 290100
6250 256100 188700 10854 292200
6500 259000 192500 10774 294900
66
6000 258500 186700 10380 293600
6250 260600 190700 10396 295700
6500 262600 194500 10410 297700
70
38
6000 235700 176800 12814 275800
6250 237400 180600 12830 277600
6500 239900 184300 12750 280000
66
6000 239700 178500 12366 278900
6250 241500 182400 12380 280700
6500 243100 185700 12400 282500
85
38
6000 220900 170000 14550 265000
6250 222400 173700 14566 266500
6500 224700 177800 14474 268700
66
6000 224600 171500 14096 267600
6250 226200 175900 14098 269200
6500 227700 179000 14120 270900
100
38
6000 205300 163300 16612 254400
6250 206700 167000 16628 255800
6500 208700 171000 16530 257600
66
6000 208600 164700 16150 256500
6250 210000 168400 16162 258000
6500 211400 172100 16170 259400
110
38
6000 194200 158600 18252 247500
6250 195400 162300 18264 248700
6500 197300 166300 18162 250400
66
6000 197300 159900 17784 249300
6250 198600 163600 17792 250600
6500 199700 167300 17800 251800
Table 10: Heating
EWT(°F) GPM CFM
Heating Capacity
Btu/hrWatts
Heat Absorpted
Btu/hr
30
38
6000 142284 11908 99068
6250 142376 11838 99374
6500 142462 11772 99658
66
6000 149806 12064 106232
6250 149930 11988 106588
6500 150046 11918 106916
40
38
6000 159792 12280 115704
6250 159902 12196 116074
6500 160006 12118 116416
66
6000 169652 12510 125002
6250 169816 12418 125450
6500 169970 12334 125864
50
38
6000 179480 12746 134254
6250 179630 12646 134714
6500 179768 12554 135138
66
6000 191902 13050 145924
6250 192146 12940 146490
6500 192360 12840 147016
60
38
6000 201020 13276 154474
6250 201228 13158 155050
6500 201422 13050 155578
66
6000 216160 13624 168736
6250 216474 13502 169434
6500 216764 13392 170074
70
38
6000 223994 13802 176144
6250 224276 13672 176834
6500 224536 13554 177466
66
6000 244602 14396 195136
6250 242352 14068 193962
6500 242768 13938 194790
80
38
6000 247994 14352 198820
6250 248388 14202 199688
6500 248754 14064 200484
66
6000 268732 14826 218390
6250 269342 14660 219552
6500 269922 14510 220610
Notes:1. Cooling capacities shown are based on 80°F DBT / 67°F WBT entering air coil conditions.2. Cooling capacities shown are gross capacities. For net capacities, multiply blower BHP (Break Horse Power) required times 2,545 and subtract from total and sensible Btu/h in tables.3. Typical of all heating and cooling capacitiy tables. Apply the cooling correction factors found on page 20.
Capacity Data
Size 200
CAT 1106-1 • ROOFTOP WSHP 15 www.DaikinApplied.com
Table 11: Cooling
EWT(°F) GPM CFM
Total Capacity
Btu/hr
Sensible Capacity
Btu/hrWatts
Heat Rejected
Btu/hr
40
38
6000 264200 188800 9810 298200
7000 271900 204000 9894 306200
8000 277900 219800 9952 312300
66
6000 268500 190700 9346 301700
7000 276900 206100 9414 310200
8000 283000 221000 9414 310200
50
38
6000 255700 185000 10698 291500
7000 263200 200300 10772 299100
8000 268800 215000 10826 304900
66
6000 260000 186900 10250 294900
7000 267900 202300 10310 302900
8000 273600 217000 10360 308800
70
38
6000 237400 177000 12644 277100
7000 243800 192100 12708 283700
8000 248900 206500 12758 288900
66
6000 241600 178900 12200 280400
7000 248200 193900 12254 287100
8000 253500 208500 12294 292500
85
38
6000 223000 171000 14336 266300
7000 228700 185900 14394 273800
8000 233100 199900 14444 276800
66
6000 226500 172300 13896 268900
7000 232700 187600 13934 275200
8000 237400 201600 13976 280000
100
38
6000 207400 164200 16358 255500
7000 212500 178800 16412 260800
8000 216400 193000 16452 264800
66
6000 210600 165500 15914 257700
7000 216000 180300 15952 263200
8000 220200 194600 15980 267400
110
38
6000 196500 159600 17954 248600
7000 201200 174100 18002 253400
8000 204700 188100 18038 257000
66
6000 199500 161200 17502 250400
7000 204300 175500 17546 255300
8000 207900 189800 17568 259000
Table 12: Heating
EWT(°F) GPM CFM
Heating Capacity
Btu/hrWatts
Heat Absorpted
Btu/hr
30
38
6000 148954 11972 104046
7000 148094 11684 105402
8000 148422 11496 106298
66
6000 157296 12144 112066
7000 156686 11836 113674
8000 157134 11632 114742
40
38
6000 166146 12334 121794
7000 166698 12022 123296
8000 167122 11796 124404
66
6000 177116 12576 132212
7000 177924 12238 136056
8000 178540 11992 135424
50
38
6000 186662 12792 141256
7000 187410 12426 143136
8000 187980 12158 144526
66
6000 200400 13114 154242
7000 201542 12712 156634
8000 202418 12418 158410
60
38
6000 208854 13318 162228
7000 209896 12886 164602
8000 210690 12574 166362
66
6000 225408 13720 177830
7000 227006 13250 180900
8000 228224 12908 183182
70
38
6000 232212 13886 184252
7000 233634 13390 187222
8000 234710 13030 189420
66
6000 251820 14332 202796
7000 253928 13810 206544
8000 255510 13426 209386
80
38
6000 256596 14440 207338
7000 258432 13896 210874
8000 259766 13506 213484
66
6000 279162 14946 228750
7000 282032 14346 233520
8000 284186 13914 237038
Notes:1. Cooling capacities shown are based on 80°F DBT / 67°F WBT entering air coil conditions.2. Cooling capacities shown are gross capacities. For net capacities, multiply blower BHP (Break Horse Power) required times 2,545 and subtract from total and sensible Btu/h in tables.3. Typical of all heating and cooling capacitiy tables. Apply the cooling correction factors found on page 20.4. For entering water temperatures below 70°F (21°C), the optional water regulating valve must be selected as a factory installed option.
Capacity Data
Size 240
CAT 1106-1 • ROOFTOP WSHP 16 www.DaikinApplied.com
Table 13: Cooling
EWT(°F) GPM CFM
Total Capacity
Btu/hr
Sensible Capacity
Btu/hrWatts
Heat Rejected
Btu/hr
40
44
7000 301300 216900 10878 338700
8000 308700 232200 10992 346400
9000 314300 246200 11092 352300
76
7000 306300 219400 10370 171335
8000 313900 234400 10482 350600
9000 319900 248800 10572 356900
50
44
7000 291900 213100 11866 331400
8000 298600 227500 11982 338400
9000 303900 241900 12072 344000
76
7000 296500 214800 11374 335000
8000 303900 230100 11470 342600
9000 308500 244500 11552 348500
70
44
7000 271400 204300 14108 315800
8000 277200 218500 14208 321900
9000 282100 232600 14286 327000
76
7000 275900 206200 13596 319100
8000 282200 221000 13680 325600
9000 287200 235200 13748 330800
85
44
7000 254900 196800 16128 304000
8000 260200 196800 16210 304000
9000 264600 225200 16282 314200
76
7000 259000 198600 15596 306900
8000 264600 213200 15666 312700
9000 269200 227200 15728 317500
100
44
7000 237500 189500 18564 292800
8000 242300 203700 18636 297800
9000 246100 217700 18694 301800
76
7000 241200 191000 18016 295000
8000 246200 205400 18074 300300
9000 250300 219300 18122 304500
110
44
7000 225300 185000 20500 285600
8000 229700 198500 20574 290300
9000 233200 213000 20610 293800
76
7000 228600 185700 19958 287500
8000 233300 200000 20006 292300
9000 237000 213800 20044 296200
Table 14: Heating
EWT(°F) GPM CFM
Heating Capacity
Btu/hrWatts
Heat Absorpted
Btu/hr
30
44
7000 167072 13076 118426
8000 166300 12782 119876
9000 166698 12580 120878
76
7000 174916 13254 127190
8000 175554 12968 128696
9000 176066 12750 129862
40
44
7000 186760 13520 138392
8000 187342 13202 139944
9000 187808 12962 141146
76
7000 198442 13786 149428
8000 199242 13442 151292
9000 199884 13180 152736
50
44
7000 209812 14052 160158
8000 210542 13674 162056
9000 211128 13388 163526
76
7000 224342 14404 173820
8000 225398 13994 176154
9000 226250 13682 177968
60
44
7000 234728 14660 183586
8000 235674 14220 185908
9000 236442 13886 187708
76
7000 252296 15102 200002
8000 253668 14628 202912
9000 254804 14266 205182
70
44
7000 261160 15312 208370
8000 262316 14830 211086
9000 263314 14448 213288
76
7000 282026 15826 227942
8000 283864 15302 231434
9000 285302 14910 234124
80
44
7000 288840 16000 234344
8000 290438 15446 237670
9000 291686 15042 240224
76
7000 313092 16650 256922
8000 315566 16054 261294
9000 317502 15606 264664
Notes:1. Cooling capacities shown are based on 80°F DBT / 67°F WBT entering air coil conditions.2. Cooling capacities shown are gross capacities. For net capacities, multiply blower BHP (Break Horse Power) required times 2,545 and subtract from total and sensible Btu/h in tables.3. Typical of all heating and cooling capacitiy tables. Apply the cooling correction factors found on page 20.
Capacity Data
Size 300
CAT 1106-1 • ROOFTOP WSHP 17 www.DaikinApplied.com
Table 15: Cooling
EWT(°F) GPM CFM
Total Capacity
Btu/hr
Sensible Capacity
Btu/hrWatts
Heat Rejected
Btu/hr
40
56
8000 374500 258400 16142 430500
9000 382800 273000 16268 439100
10000 389500 287200 16370 446000
98
8000 381100 261400 15574 436200
9000 389900 276100 15688 445200
10000 396900 290400 15782 452500
50
56
8000 361600 252700 17312 419700
9000 369500 266500 17428 428000
10000 376000 280500 17516 434700
98
8000 367800 255400 16736 424900
9000 376100 270100 16838 433500
10000 382900 284500 16910 440400
70
56
8000 335400 241400 20078 399200
9000 342300 255500 20176 406400
10000 347900 268300 20268 412400
98
8000 341000 242600 19450 403600
9000 248300 257200 19534 411100
10000 354200 271000 19606 417200
85
56
8000 314300 231200 22694 384300
9000 320500 246200 22776 390600
10000 325400 260000 22848 395700
98
8000 319600 233700 22006 387900
9000 326100 248500 22074 394600
10000 331300 261500 22154 400100
100
56
8000 292200 221200 25888 370100
9000 297700 235000 25974 375900
10000 302200 248900 26038 380600
98
8000 296700 223700 25182 372900
9000 302500 237500 25248 278800
10000 307300 251100 25304 383800
110
56
8000 276600 214100 28434 361200
9000 281500 228500 28502 366300
10000 285800 241500 28572 370800
98
8000 280700 216300 27718 363400
9000 285900 230400 27776 368800
10000 290400 243900 27826 373400
Table 16: Heating
EWT(°F) GPM CFM
Heating Capacity
Btu/hrWatts
Heat Absorpted
Btu/hr
30
56
8000 225002 19362 151174
9000 225396 18980 152994
10000 225932 18686 154452
98
8000 236140 19688 161804
9000 236956 19288 163894
10000 237638 18974 165572
40
56
8000 250636 20114 174676
9000 249792 19634 177656
10000 250410 19292 179336
98
8000 265120 20546 188796
9000 264640 20034 191524
10000 265480 19668 193516
50
56
8000 277864 20926 202122
9000 278664 20418 204604
10000 279404 20020 206598
98
8000 295976 21424 218988
9000 297192 20900 221874
10000 298210 20496 224164
60
56
8000 309142 21792 231218
9000 310216 21228 234094
10000 311120 20792 236374
98
8000 330806 22414 251306
9000 332426 21798 254904
10000 333772 21322 257764
70
56
8000 342174 22748 261816
9000 343600 22092 265338
10000 344768 21586 268126
98
8000 367506 23514 285180
9000 369666 22796 289660
10000 371460 22244 293224
80
56
8000 376576 23796 293520
9000 378438 23040 297824
10000 379988 22460 301228
98
8000 405622 24732 320130
9000 408492 23902 325898
10000 410862 23264 330122
Notes:1. Cooling capacities shown are based on 80°F DBT / 67°F WBT entering air coil conditions.2. Cooling capacities shown are gross capacities. For net capacities, multiply blower BHP (Break Horse Power) required times 2,545 and subtract from total and sensible Btu/h in tables.3. Typical of all heating and cooling capacitiy tables. Apply the cooling correction factors found on page 20.4. For entering water temperatures below 70°F (21°C), the optional water regulating valve must be selected as a factory installed option.
Capacity Data
Size 360
CAT 1106-1 • ROOFTOP WSHP 18 www.DaikinApplied.com
Table 17: Cooling
EWT(°F) GPM CFM
Total Capacity
Btu/hr
Sensible Capacity
Btu/hrWatts
Heat Rejected
Btu/hr
40
72
9000 454600 306600 22216 230600
10000 464800 321400 22486 541700
11000 473400 335800 22716 551000
124
9000 460600 308500 21992 536800
10000 471400 323400 22278 548400
11000 480400 338800 22516 558100
50
72
9000 441300 299400 22940 518000
10000 451100 315300 23166 528500
11000 459200 329500 23368 537200
124
9000 447600 303600 22556 523900
10000 457700 318200 22800 534700
11000 466200 332600 23008 543800
70
72
9000 412800 287400 25504 494300
10000 421400 300700 25696 503500
11000 428500 314700 25846 511100
124
9000 418700 288900 24876 498900
10000 427700 304800 25034 508300
11000 435100 319000 25182 516300
85
72
9000 389300 276800 28508 477900
10000 396900 291300 28648 486000
11000 403300 305300 28770 492700
124
9000 395000 279300 27716 481600
10000 402900 293900 27846 490000
11000 409600 308000 27958 497100
100
72
9000 364000 265700 32500 463000
10000 370900 278500 32642 470400
11000 376400 293900 32716 476100
124
9000 369200 267900 31620 465900
10000 376300 282300 31718 473300
11000 382200 296300 31804 479500
110
72
9000 345800 258100 35782 453800
10000 352100 272100 35888 460400
11000 357500 284200 36006 466300
124
9000 350700 260100 34864 456200
10000 357300 274200 34952 463000
11000 362800 286400 35066 469000
Table 18: Heating
EWT(°F) GPM CFM
Heating Capacity
Btu/hrWatts
Heat Absorpted
Btu/hr
30
72
9000 292600 12400 203600
10000 280400 25400 187000
11000 280800 24500 190300
124
9000 291600 25800 199500
10000 292100 25300 201800
11000 292600 24800 203600
40
72
9000 314140 26496 217864
10000 312688 25882 220502
11000 313052 25422 222432
124
9000 331300 27002 233650
10000 330344 26350 236846
11000 331090 25876 239106
50
72
9000 349542 27550 252454
10000 350334 26892 255370
11000 351020 26370 257732
124
9000 370954 28216 271962
10000 372282 27504 275596
11000 373412 26942 278546
60
72
9000 389968 28822 289120
10000 390976 28046 292828
11000 391994 27432 295830
124
9000 415490 29684 312350
10000 417428 28842 317030
11000 419076 28180 320830
70
72
9000 432268 30268 327506
10000 433964 29362 332156
11000 435416 28652 335918
124
9000 462520 31372 354556
10000 465238 30392 360490
11000 467544 29624 365314
80
72
9000 476646 31910 367178
10000 478976 30864 372936
11000 480968 30050 377588
124
9000 511634 33312 398052
10000 515320 32182 405468
11000 518446 31304 411492
Notes:1. Cooling capacities shown are based on 80°F DBT / 67°F WBT entering air coil conditions.2. Cooling capacities shown are gross capacities. For net capacities, multiply blower BHP (Break Horse Power) required times 2,545 and subtract from total and sensible Btu/h in tables.3. Typical of all heating and cooling capacitiy tables. Apply the cooling correction factors found on page 20.
Capacity Data
Size 420
CAT 1106-1 • ROOFTOP WSHP 19 www.DaikinApplied.com
Table 19: Cooling
EWT(°F) GPM CFM
Total Capacity
Btu/hr
Sensible Capacity
Btu/hrWatts
Heat Rejected
Btu/hr
40
80
10000 488100 337500 20036 567800
11000 498200 353700 20162 567800
12000 506700 369300 20268 576600
144
10000 495700 341000 19118 563400
11000 506500 355900 19234 574400
12000 515700 371200 19332 583900
50
80
10000 471800 328500 21970 545100
11000 281200 346200 22066 554600
12000 489600 360200 22164 563300
144
10000 479200 333500 21086 550600
11000 489000 349600 21188 550600
12000 497800 363400 21284 569800
70
80
10000 438400 315300 25932 519600
11000 446600 331200 26016 528000
12000 454000 344800 26112 535900
144
10000 445200 316700 25144 524900
11000 453700 334300 25182 533400
12000 461300 348000 25268 541400
85
80
10000 411500 303600 29396 500400
11000 419200 317400 29500 508500
12000 425700 332500 29570 515200
144
10000 417900 304600 28602 505100
11000 425600 320200 28664 513000
12000 432400 335400 28716 520000
100
80
10000 383200 289500 33634 489000
11000 389900 304700 33634 489000
12000 395500 319700 33696 494700
144
10000 388700 291800 32736 485500
11000 295600 313200 32790 492600
12000 401400 322200 32834 498600
110
80
10000 362900 280700 36860 470100
11000 369000 295800 36926 476400
12000 373900 310600 36980 481500
144
10000 367800 283100 36030 472900
11000 282900 298100 36076 479400
12000 379400 313000 36114 484700
Table 20: Heating
EWT(°F) GPM CFM
Heating Capacity
Btu/hrWatts
Heat Absorpted
Btu/hr
30
80
10000 316100 28200 213200
11000 316400 27700 215500
12000 316700 28500 217700
144
10000 333100 28800 228900
11000 333900 28200 231600
12000 334600 27700 233800
40
80
10000 353800 29500 247800
11000 352300 28800 250700
12000 352800 28200 252900
144
10000 373900 30100 268300
11000 374800 29500 271400
12000 375600 28900 274000
50
80
10000 394100 30780 286700
11000 399000 30400 292900
12000 395400 29400 292400
144
10000 421600 31600 311800
11000 422900 30800 315700
12000 424000 30100 318900
60
80
10000 440000 32200 328600
11000 440900 31300 332400
12000 441800 30600 335600
144
10000 473100 33300 358600
11000 480400 32700 367700
12000 476300 31500 367500
70
80
10000 488500 33800 372600
11000 489900 32800 377300
12000 491100 32300 385200
144
10000 527300 35700 407500
11000 529700 34000 413700
12000 531800 33100 418800
80
80
10000 539200 35600 418300
11000 541200 34400 424100
12000 542700 33400 429000
144
10000 583700 37300 458000
11000 587000 35900 465700
12000 589900 34800 472000
Notes:1. Cooling capacities shown are based on 80°F DBT / 67°F WBT entering air coil conditions.2. Cooling capacities shown are gross capacities. For net capacities, multiply blower BHP (Break Horse Power) required times 2,545 and subtract from total and sensible Btu/h in tables.3. Typical of all heating and cooling capacitiy tables. Apply the cooling correction factors found on page 20.4. For entering water temperatures below 70°F (21°C), the optional water regulating valve must be selected as a factory installed option.
Correction Factors
Cooling Correction MultipliersTable 21: Cooling Correction Multipliers
Unit Size
Condensing Water Flow Cooling Performance Correction Factors
Cooling Cycle Design Δ T GPM
Pressure Drop Total Capacity Btu/hr Watts Input Heat Rejection
Btu/hrSensible Capacity
Btu/hr EERpsi Ft . HD .
150
8 49.0 8.7 20.2 1.005 0.987 1.002 1.001 1.02
10 39.6 5.9 13.6 1.000 1.000 1.000 1.000 1.00
12 33.0 4.2 9.7 0.987 1.012 0.992 0.996 0.98
14 27.8 3.1 7.1 0.973 1.025 0.985 0.992 0.95
180
8 30.0 7.1 16.3 1.005 0.987 1.002 1.001 1.02
10 24.0 4.7 10.8 1.000 1.000 1.000 1.000 1.00
12 20.0 3.3 7.7 0.987 1.012 0.992 0.996 0.98
14 17.0 2.5 5.7 0.973 1.025 0.985 0.992 0.95
200
8 33.0 4.9 11.3 1.005 0.987 1.002 1.001 1.02
10 27.0 3.4 7.9 1.000 1.000 1.000 1.000 1.00
12 22.0 2.3 5.4 0.987 1.012 0.992 0.996 0.98
14 19.0 1.8 4.2 0.973 1.025 0.985 0.992 0.95
210
8 33.0 8.4 19.4 1.005 0.987 1.002 1.001 1.02
10 27.0 5.8 13.4 1.000 1.000 1.000 1.000 1.00
12 22.0 4.0 9.2 0.987 1.012 0.992 0.996 0.98
14 19.0 3.0 7.0 0.973 1.025 0.985 0.992 0.95
240
8 38.0 6.3 14.5 1.005 0.987 1.002 1.001 1.02
10 31.0 4.4 10.1 1.000 1.000 1.000 1.000 1.00
12 26.0 3.2 7.3 0.987 1.012 0.992 0.996 0.98
14 22.0 2.3 5.4 0.973 1.025 0.985 0.992 0.95
300
8 49.0 6.1 14.1 1.005 0.987 1.002 1.001 1.02
10 40.0 4.2 9.8 1.000 1.000 1.000 1.000 1.00
12 34.0 3.2 7.3 0.987 1.012 0.992 0.996 0.98
14 28.0 2.2 5.1 0.973 1.025 0.985 0.992 0.95
360
8 62.0 6.9 15.9 1.005 0.987 1.002 1.001 1.02
10 50.0 4.6 10.7 1.000 1.000 1.000 1.000 1.00
12 42.0 3.4 7.8 0.987 1.012 0.992 0.996 0.98
14 36.0 2.6 5.9 0.973 1.025 0.985 0.992 0.95
420
8 72.0 7.3 16.9 1.005 0.987 1.002 1.001 1.02
10 57.0 4.8 11.0 1.000 1.000 1.000 1.000 1.00
12 47.0 3.3 7.7 0.987 1.012 0.992 0.996 0.98
14 40.0 2.5 5.7 0.973 1.025 0.985 0.992 0.95
CAT 1106-1 • ROOFTOP WSHP 20 www.DaikinApplied.com
Fan Performance
Sizes 150-200Table 22: RWA, RGA, RWC, RGC Fan Performance
CAT 1106-1 • ROOFTOP WSHP 21 www.DaikinApplied.com
Unit Size
External Static Pressure
CFM
Internal Static Pressure
Total Static Pressure
BHP RPM Motor HP
150 15 x 15Blower Wheel Size
0.5
4500 .80 1.30 1.99 14713.00
5000 1.06 1.56 2.67 1624
5500 1.19 1.69 3.32 1745 5.00
1.0
4500 .80 1.80 2.49 1600 3.00
5000 1.06 2.06 3.22 1740
5.00
5500 1.19 2.19 3.91 1851
1.5
4500 .80 2.30 3.01 1723
5000 1.06 2.56 3.79 1853
5500 1.19 2.69 4.52 1955
2.0
4500 .80 2.80 3.54 1839
5000 1.06 3.06 4.37 1961
5500 1.19 3.19 4.93 2057 7.50
2.5
4500 .80 3.30 4.08 1949 5.00
5000 1.06 3.56 4.76 20647.50
5500 1.19 3.69 5.55 2155
3.0
4500 .80 3.80 4.63 2053 5.00
5000 1.06 4.06 5.33 2163
7.505500 1.19 4.19 6.16 2249
3.5
4500 .80 4.30 4.97 2152
5000 1.06 4.56 5.91 2257
5500 1.19 4.69 6.79 2340 10.00
180 15 x 15Blower Wheel Size
0.5
5500 1.19 1.69 3.32 17455.00
6000 1.25 1.75 3.97 1853
6500 1.49 1.99 4.74 1996 7.50
1.0
5500 1.19 2.19 3.91 18515.0
6000 1.25 2.25 4.60 1950
6500 1.49 2.49 5.39 2086 7.50
1.5
5500 1.19 2.69 4.52 1955 5.0
6000 1.25 2.75 5.03 2047
7.50
6500 1.49 2.99 6.06 2175
2.0
5500 1.19 3.19 4.93 2057
6000 1.25 3.25 5.68 2142
6500 1.49 3.49 6.75 2264
2.5
5500 1.19 3.69 5.55 2155
6000 1.25 3.75 6.33 2235
6500 1.49 3.99 7.44 2351 10.0
3.0
5500 1.19 4.19 6.16 2249 7.50
6000 1.25 4.25 6.99 2326
10.0
6500 1.49 4.49 7.09 2437
3.5
5500 1.19 4.69 6.79 2340
6000 1.25 4.75 7.66 2413
6500 1.49 4.99 8.86 2520
Unit Size
External Static Pressure
CFM
Internal Static Pressure
Total Static Pressure
BHP RPM Motor HP
210 15 x 15Blower Wheel Size
0.5
6000 1.25 1.75 3.97 18535.00
6250 1.38 1.88 4.46 1927
6500 1.49 1.99 4.74 1996 7.50
1.0
6000 1.25 2.25 4.60 1950 5.00
6250 1.38 2.38 4.90 2020
7.50
6500 1.49 2.49 5.39 2086
1.5
6000 1.25 2.75 5.03 2047
6250 1.38 2.88 5.54 2113
6500 1.49 2.99 6.06 2175
2.0
6000 1.25 3.25 5.68 2142
6250 1.38 3.38 6.21 2205
6500 1.49 3.49 6.75 2264
2.5
6000 1.25 3.75 6.33 2235
6250 1.38 3.88 6.89 2295
10.0
6500 1.49 3.99 7.44 2351
3.0
6000 1.25 4.25 6.99 2326
6250 1.38 4.38 7.57 2383
6500 1.49 4.49 7.09 2437
3.5
6000 1.25 4.75 7.66 2413
6250 1.38 4.88 8.26 2468
6500 1.49 4.99 8.86 2520
200 18 x 18Blower Wheel Size
0.5
6000 .83 1.33 2.47 1294 3.00
7000 .90 1.40 3.36 1435
5.008000 .98 1.48 4.49 1584
1.0
6000 .83 1.83 3.07 1399
7000 .90 1.90 4.03 1526
8000 .98 1.98 5.00 1664 7.50
1.5
6000 .83 2.33 3.70 1503 5.00
7000 .90 2.40 4.73 16167.50
8000 .98 2.48 5.74 1743
2.0
6000 .83 2.83 4.36 1603 5.00
7000 .90 2.90 5.23 1705
7.508000 .98 2.98 6.50 1823
2.5
6000 .83 3.33 4.82 1699
7000 .90 3.40 5.94 1793
8000 .98 3.48 7.28 1901 10.0
3.0
6000 .83 3.83 5.48 17927.50
7000 .90 3.90 6.67 1878
8000 .98 3.98 8.08 1979 10.0
3.5
6000 .83 4.33 6.15 1882 7.50
7000 .90 4.40 7.42 196110.0
8000 .98 4.48 8.89 2055
Fan Performance
Sizes 240-420Table 23: RWA, RGA, RWC, RGC Fan Performance
CAT 1106-1 • ROOFTOP WSHP 22 www.DaikinApplied.com
Unit Size
External Static Pressure
CFM
Internal Static Pressure
Total Static Pressure
BHP RPM Motor HP
240 18 x 18Blower Wheel Size
0.5
7000 .90 1.40 3.36 14355.00
8000 .98 1.48 4.49 1584
9000 1.24 1.74 5.90 1763 7.50
1.0
7000 .90 1.90 4.03 1526 5.00
8000 .98 1.98 5.00 1664 7.50
9000 1.24 2.24 6.67 1834 10.0
1.5
7000 .90 2.40 4.73 16167.50
8000 .98 2.48 5.74 1743
9000 1.24 2.74 7.48 1905 10.0
2.0
7000 .90 2.90 5.23 17057.50
8000 .98 2.98 6.50 1823
9000 1.24 3.24 8.31 1976 10.0
2.5
7000 .90 3.40 5.94 1793 7.50
8000 .98 3.48 7.28 1901 10.0
9000 1.24 3.74 9.16 2046 15.0
3.0
7000 .90 3.90 6.67 1878 7.50
8000 .98 3.98 8.08 1979 10.0
9000 1.24 4.24 10.03 2116 15.0
3.5
7000 .90 4.40 7.42 196110.0
8000 .98 4.48 8.89 2055
9000 1.24 4.74 10.91 2185 15.0
300 18 x 18Blower Wheel Size
0.5
8000 .98 1.48 4.49 1584 5.00
9000 1.24 1.74 5.90 1763 7.50
10000 1.38 1.88 7.62 1925 10.0
1.0
8000 .98 1.98 5.00 1664 7.50
9000 1.24 2.24 6.67 183410.0
10000 1.38 2.38 8.46 1989
1.5
8000 .98 2.48 5.74 1743 7.50
9000 1.24 2.74 7.48 1905 10.0
10000 1.38 2.88 9.32 2052 15.0
2.0
8000 .98 2.98 6.50 1823 7.50
9000 1.24 3.24 8.31 1976 10.0
10000 1.38 3.38 10.21 2116 15.0
2.5
8000 .98 3.48 7.28 1901 10.0
9000 1.24 3.74 9.16 204615.0
10000 1.38 3.88 11.13 2180
3.0
8000 .98 3.98 8.08 1979 10.0
9000 1.24 4.24 10.03 211615.0
10000 1.38 4.38 12.05 2244
3.5
8000 .98 4.48 8.89 2055 10.0
9000 1.24 4.74 10.91 218515.0
10000 1.38 4.88 13.00 2307
Unit Size
External Static Pressure
CFM
Internal Static Pressure
Total Static Pressure
BHP RPM Motor HP
360 18 x 18Blower Wheel Size
0.5
9000 1.24 1.74 5.90 1763 7.50
10000 1.38 1.88 7.62 1925 10.0
11000 1.56 2.06 9.72 2094 15.0
1.0
9000 1.24 2.24 6.67 183410.0
10000 1.38 2.38 8.46 1989
11000 1.56 2.56 10.62 2151 15.0
1.5
9000 1.24 2.74 7.48 1905 10.0
10000 1.38 2.88 9.32 205215.0
11000 1.56 3.06 11.55 2209
2.0
9000 1.24 3.24 8.31 1976 10.0
10000 1.38 3.38 10.21 2116
15.0
11000 1.56 3.56 12.49 2266
2.5
9000 1.24 3.74 9.16 2046
10000 1.38 3.88 11.13 2180
11000 1.56 4.06 13.46 2324
3.0
9000 1.24 4.24 10.03 2116
10000 1.38 4.38 12.05 2244
11000 1.56 4.56 14.74 2383 20.0
3.5
9000 1.24 4.74 10.91 218515.0
10000 1.38 4.88 13.00 2307
11000 1.56 5.06 15.09 2440 20.0
420 18 x 18Blower Wheel Size
0.5
10000 1.38 1.88 7.62 1925 10.0
11000 1.56 2.06 9.72 209415.0
12000 1.94 2.44 12.54 2283
1.0
10000 1.38 2.38 8.46 1989 10.0
11000 1.56 2.56 10.62 2151
15.012000 1.94 2.94 13.51 2335
1.5
10000 1.38 2.88 9.32 2052
11000 1.56 3.06 11.55 2209
12000 1.94 3.44 14.79 2388 20.0
2.0
10000 1.38 3.38 10.21 211615.0
11000 1.56 3.56 12.49 2266
12000 1.94 3.94 15.15 2441 20.0
2.5
10000 1.38 3.88 11.13 218015.0
11000 1.56 4.06 13.46 2324
12000 1.94 4.44 16.16 2494 20.0
3.0
10000 1.38 4.38 12.05 2244 15.0
11000 1.56 4.56 14.74 2383 20.0
12000 1.94 4.94 17.20 2547 20.0
3.5
10000 1.38 4.88 13.00 2307 15.0
11000 1.56 5.06 15.09 244020.0
12000 1.94 5.44 18.25 2600
Physical Data
Models RWA, RGA, RWC, RGCTable 24: Physical Data
DescriptionUnit Size
150 180 210 200
Fan Wheel - Diameter × Width (Inches) 15 × 15
Fan Quantity 1
Fan Motor Horse Power (HP)
3 ● n/a ●
5 ● ● ● ●
7-1/2 ● ● ● ●
10 ● ● ● ●
Coil Face Area (Sq Ft) 12 23
Coil Rows 4 6 4
Compressor Type (Quantity) Scroll (2)
Filter (Quantity) Size (4) 20 × 24 × 2(2) 20 × 24 × 2
(4) 24 × 24 × 2
Water Connections O .D . Sweat 1-5/8 2-1/8
Condensate Connection Size (MPT) (Quantity) 1-1/4 (1)
Operating Weight 1860 1900 1920 3150
Shipping Weight 1860 1900 1920 3150
Curb Weight + Unit Weight 14" 1865 1905 1925 3455
24" 1965 2005 2025 3575
DescriptionUnit Size
240 300 360 420
Fan Wheel - Diameter × Width (Inches) 18 × 18
Fan Quantity 1
Fan Motor Horse Power (HP)
5 ● ● n/a
7-1/2 ● ● ● n/a
10 ● ● ● ●
15 ● ● ● ●
20 n/a ● ●
Coil Face Area (Sq Ft) 23
Coil Rows 4 6
Compressor Type (Quantity) Scroll (2) Scroll (4)
Filter (Quantity) Size(4) 20 × 24 × 2
(4) 24 × 24 × 2
Water Connections O .D . Sweat 2-1/8
Condensate Connection Size (MPT) (Quantity) 1-1/4 (1)
Operating Weight 3200 3300 3380 3800
Shipping Weight 3200 3300 3380 3800
Curb Weight + Unit Weight14" 3505 3605 3685 4105
24" 3625 3725 3805 4225
CAT 1106-1 • ROOFTOP WSHP 23 www.DaikinApplied.com
Dimensional Data
Model RWA, RGA – Size 1 50-210Figure 2: Downflow Discharge & Return
Overall Unit DimensionsNote: Front of unit is determined by facing the control panel.
97"W (including intake hood) x 96"D x 62"H82½"W (not including intake hood) x 96"D x 62"H
Water Coil Connections (O.D. Sweat)Size 150, 180, 210 = 1-5/8"
Condensate Drain Connection (MPT)Size 150, 180, 210 = 1-1/4"
Refrigerant Charge R410A (pounds)Size 150 = 21.2Size 180 = 26.0Size 210 = 32.4
Notes: 1. All dimensions are in inches. 2. A minimum of 24" to 36" should be allowed on all sides of unit for service clearance. 3. Clearance of 48" should be allowed for the control panel side of the unit.
CAT 1106-1 • ROOFTOP WSHP 24 www.DaikinApplied.com
Dimensional Data
Model RWA, RGA – Size 200-420Figure 3: Downflow Discharge & Return
Overall Unit DimensionsNote: Front of unit is determined by facing the control panel.
130-3/4"W (including intake hood) x 96"D x 83"H112-9/16"W (not including intake hood) x 96"D x 83"H
Water Coil Connections (O.D. Sweat)Size 200, 240, 300, 360, 420 = 2-1/8"
Condensate Drain Connection (MPT)Size 200, 240, 300, 360, 420 = 1-1/4"
Refrigerant Charge R410A (pounds)Size 200 = 38.8Size 240 = 39.3Size 300 = 45.4Size 360 = 46.3Size 420 = 61.0
Notes: 1. All dimensions are in inches. 2. A minimum of 24" to 36" should be allowed on all sides of unit for service clearance. 3. Clearance of 48" should be allowed for the control panel side of the unit.
CAT 1106-1 • ROOFTOP WSHP 25 www.DaikinApplied.com
Dimensional Data
Model RWC, RGC – Size 150-210Figure 4: Horizontal Discharge & Return
Overall Unit DimensionsNote: Front of unit is determined by facing the control panel.
107-3/4"W (including intake hood) x 96"D x 62"H82-1/2"W (not including intake hood) x 96"D x 62"H
Water Coil Connections (O.D. Sweat)Size 150, 180, 210 = 1-5/8"
Condensate Drain Connection (MPT)Size 150, 180, 210 = 1-1/4"
Refrigerant Charge R410A (pounds)Size 150 = 21.2Size 180 = 26.0Size 210 = 32.4
Notes: 1. All dimensions are in inches. 2. A minimum of 24" to 36" should be allowed on all sides of unit for service clearance. 3. Clearance of 48" should be allowed for the control panel side of the unit.
CAT 1106-1 • ROOFTOP WSHP 26 www.DaikinApplied.com
Dimensional Data
Model RWC, RGC – Size 200-420Figure 5: Horizontal Discharge & Return
Overall Unit DimensionsNote: Front of unit is determined by facing the control panel.
146-5/8"W (including intake hood) x 96"D x 83"H112-1/2"W (not including intake hood) x 96"D x 83"H
Water Coil Connections (O.D. Sweat)Size 200, 240, 300, 360, 420 = 2-1/8"
Condensate Drain Connection (MPT)Size 200, 240, 300, 360, 420 = 1-1/4"
Refrigerant Charge R410A (pounds)Size 200 = 38.8Size 240 = 39.3Size 300 = 45.4Size 360 = 46.3Size 420 = 61.0
Notes: 1. All dimensions are in inches. 2. A minimum of 24" to 36" should be allowed on all sides of unit for service clearance. 3. Clearance of 48" should be allowed for the control panel side of the unit.
CAT 1106-1 • ROOFTOP WSHP 27 www.DaikinApplied.com
Dimensional Data
14" High Roof Curb – Size 150-210Figure 6: Roof Curb – Size 150-210
24" High Roof Curb – Size 150-210Figure 7: Roof Curb – Size 150-210
CAT 1106-1 • ROOFTOP WSHP 28 www.DaikinApplied.com
Dimensional Data
14" High Roof Curb – Size 200-420Figure 8: Roof Curb – Size 200-420
24" High Roof Curb – Size 200-420Figure 9: Roof Curb – Size 200-420
CAT 1106-1 • ROOFTOP WSHP 29 www.DaikinApplied.com
Engineering Guide Specifications
CAT 1106-1 • ROOFTOP WSHP 30 www.DaikinApplied.com
Model RWA, RGA – Downflow Discharge and Return & Model, RWC, RGC – Horizontal Discharge and Horizontal ReturnGeneralFurnish and install Daikin Model RWA/RGA Series B water source heat pump per plans and specifications. Capacity and Energy Efficiency shall not be less than scheduled. Unit shall be provided with factory installed options listed below.
ApprovalsUnit shall be design certified to conform to appropriate UL/ANSI Standards by ETL or other nationally recognized testing laboratory.
Base and CabinetThe unit shall be double wall construction with heavy duty 20-gauge G-90 galvanized steel. Gasketed ac-cess doors shall be 20- gauge steel with 1" 4# density closed cell insulation and a 24-gauge galvanized steel liner. Standard outer panels will be insulated with 1" 4# density closed cell foam insulation with a 24-gauge galvanized steel interior liner. Service access doors shall also be mounted with stainless steel hinges and equipped with 1/4 turn cam operated adjustable com-pression type latches. The underside of the base panel shall be insulated with 3/8" closed cell foam insulation. Each roof section shall be sloped for proper drainage. All openings through the base pan of the unit shall have upturned flanges of at least 1/2" in height. The design of the cabinet shall allow access to the compressor and electrical control panel without impairing unit opera-tion. The compressors shall be mounted on a platform under the sloped condensers for easy serviceability. The condensers shall have a vinyl coated wire coil guard to protect the condensers as well as the compressors. Cabinet shall be designed for vertical supply and return air or horizontal supply and vertical return air. Horizontal return through a roof curb shall be acceptable. The unit shall be equipped with a factory installed weatherproof, outside-air intake hood with bird screen. Adjustable manual damper is included which allows preset outside-air volume up to 30% of the nominal rated CFM.
IAQ (Indoor Air Quality) Condensate Drain PanThe condensate drain pan shall be double sloped to comply with ASHRAE Standard 62-1089R and shall be fabricated from heavy gauge stainless steel. The bot-tom of the condensate drain pan shall be insulated with closed cell neoprene insulation. The drain pan shall be furnished with an MPT drain fitting positioned at the exterior of the cabinet. The weight of the coil and other components shall not compress the insulation thus re-ducing its insulation value.
Paint Finish (Cabinet & Exterior)Constructed of hot dipped galvanized G-90 steel that is chemically treated with zinc phosphate, coated with 0.2 to 0.3 MIL polyurethane primer then finished with 0.7 to 0.8 MIL polyester top coating.
Refrigerant SystemThe refrigerant system(s) shall operate with R-410A refrigerant and shall include the compressor, crankcase heater, copper-tube, aluminum finned condenser and evaporator coils. Each refrigerant circuit shall include fil-ter/drier, high pressure safety control, air proving switch and water proving switch (manual-reset), low pressure control/loss of charge protector (auto-reset), dual gauge connections for high and low pressure readings and thermal expansion valve with adjustable superheat. The condensing section of the unit shall be integral to the unit and shall be manufactured by the air conditioning unit manufacturer.
Electrical ControlsThe unit shall be designed for electrical power entry through the curb. The starter/control panel shall include a programmable logic controller and a complete modu-lar, integrated motor control system mounted on din rails. All safety and operating controls shall be factory mount-ed. The system shall also include all relays, fan contac-tors, compressor contactors, and power distribution. The 24-volt control circuit shall include a transformer and low voltage terminal strip for interface with a control system.
Supply Fan SectionAll unit sizes shall be fitted with a DWDI forward curved fan assembly mounted on spring vibration isolation. The supply fan shall be on a slide out deck for removal from the cabinet to service or inspect. The shaft is belt driven with adjustable drive sheave connected to an open drip proof motor with sealed ball bearings. Adjustable V-belt drives shall be provided with a minimum rating of 140% of the motor nameplate brake horsepower when the adjustable pulley is at the minimum RPM. The bearings on both the blower shaft and motor are permanently lu-bricated. The supply fan shall be on a slide out deck for removal from the cabinet to service or inspect.
Supply Fan MotorThe motor shall be a high efficiency ODP Evaporator fan motor for 1 HP and larger and is externally protected (manual reset).
Air Filters and RackThe standard filter rack shall be capable of using either of 2" filters, 4" filters or 2" pre-filters and 4" after filters. Standard filters are 2" pleated.
CAT 1106-1 • ROOFTOP WSHP 31 www.DaikinApplied.com
Optional Corrosion ProtectionHarsh Environment Protection shall include the following features, where applicable, to provide extra protection against corrosive atmospheric conditions:■ Coated refrigerant to air evaporator with
Thermoguard®, rated for 10,000 hr. Salt Spray■ Coated refrigerant to air hot gas reheat coil with
Thermoguard®, rated for 10,000 hr. Salt Spray■ Coated refrigerant to air sub cooling coil with
Thermoguard®, rated for 10,000 hr. Salt Spray■ All interior (un-insulated) cabinet panels coated
with Thermoguard®, rated for 10,000 hr. Salt Spray.■ All exterior surfaces of the cabinet coated with
Thermoguard®, rated for 10,000 hr. Salt Spray
Evaporator CoilEvaporator coil shall be enhanced surface aluminum fins, formed on multiple rows of seamless rifled cop-per tubing, arranged in staggered tube configuration with galvanized steel header plates. These tubes are mechanically expanded, firmly bonding the tube to the shoulder of each fin.■ All compressors, accumulators, factory installed
receivers, control device covers and refrigerant piping coated with Thermoguard®, rated for 10,000 hr. Salt Spray.
Optional Cupro-nickel Coaxial Water CoilThe Coaxial Water Coil will be supplied with an en-hanced surface cupro-nickel inner water tube with outer steel tube shell (tube-in-tube)
Optional Hot Gas ReheatThe unit shall be equipped with optional factory installed one row liquid sub cooling coil for all refrigeration cir-cuits. Unit shall have an optional factory installed cycling hot gas reheat one row coil for both single or dual refrigera-tion circuits that include VARISPEED™ low ambient head pressure Control and water regulating valve.Reheat coils shall be coated with Thermoguard®, a metallic impregnated polymeric structure designed specifically to withstand a wide range of chemical sub-stances without affecting the heat transfer capabilities of the surface it is protecting. The coating shall provide corrosive environment protection (up to 10 ppm particu-late concentration) against inorganic acids, Alkalines, Amines, Halogenated Hydrocarbons, Esters and Ke-tones. The coating shall meet or exceed 10,000 hr. salt spray test conditions per ASTM B117, 1,200 cycles per Kesternich test conditions and shall contain no volatile organic chemicals.
Optional Hot Gas BypassUnit shall be equipped with an optional factory installed cycling, hot gas reheat one-row coil on the lead refriger-ation circuit that includes VARISPEED low ambient head pressure control and water regulating valve.
Optional Electrical ComponentsUnit shall be equipped with an optional manual reset fire-stat pre-set to open when return air temperature reaches 135°F, shall be factory mounted in the return air opening to the unit.Unit shall be equipped with an optional factory mounted and wired non-fused disconnect.Unit shall be equipped with an optional 115 Volt GFCI convenience outlet. Receptacle shall be factory installed and wired. It is furnished with a 15A circuit breaker and transformer for factory wiring.
Optional EconomizerThe unit shall be equipped with an optional factory installed fully modulating enthalpy economizer with a weatherproof, full-size, outside-air intake hood and bird screen. The economizer shall consist of actuator oper-ated outside and return air dampers. The dampers shall be constructed with 14-gauge galvanized steel frames and 16-gauge galvanized steel formed blades. The blades shall have parallel action. Each blade shall have vinyl edge seals and aluminum end seals for a maximum leakage rate of 6.25 cfm/sq. ft. Shafts shall be square, plated steel stubs in oil-impregnated bronze sleeves. Linkage shall be plated steel arms with stainless steel pivots and galvanized steel angles, located external to the damper blades. Stops shall be 16-gauge steel angles. A direct connected actuator shall be connected to extended shafts. Plastic gears are not acceptable. A gravity relief damper and discharge hood are also included.The unit shall be equipped with an optional factory installed fully modulating enthalpy economizer with a weatherproof, full-size, outside-air intake hood and bird screen. The economizer shall consist of 0-10VDC actuator (controls by others) operated outside and return air dampers. The dampers shall be constructed with 14-gauge galvanized steel frame and 16-gauge galva-nized steel formed blades. The blades shall have parallel action. Each blade shall have vinyl edge seals and aluminum end seals for a maximum leakage rate of 6.25 cfm/sq. ft. Shafts shall be square, plated steel stubs in oil-impregnated bronze sleeves. Linkage shall be plated steel arms with stainless steel pivots and galvanized steel angles, located external to the damper blades. Stops shall be 16-gauge steel angles. A direct connected actuator shall be connected to extended shafts. Plastic gears are not acceptable. A gravity relief damper and discharge hood are also included.
Engineering Guide Specifications
Daikin Applied Training and Development
Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. Refer to Form 933-430285Y. To find your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787). To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.DaikinApplied.com.
Products manufactured in an ISO Certified Facility.
CAT 1106-1 ©2016 Daikin Applied (11/16) | (800) 432–1342 | www.DaikinApplied.com