case study in commercial near net-zero leed design

19
Case Study in Commercial Near Net-Zero LEED Design Peter C. D’Antonio, LEED AP, PE President - PCD Engineering Services, Inc.

Upload: others

Post on 10-Jan-2022

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Case Study in Commercial Near Net-Zero LEED Design

Case Study in CommercialNear Net-Zero LEED Design

Peter C. D’Antonio, LEED AP, PE

President - PCD Engineering Services, Inc.

Page 2: Case Study in Commercial Near Net-Zero LEED Design

Mapleleaf Orthopedics

8,000 SF medical

office, completed Dec

2007

Construction cost

$220/SF

Southern Colorado’s

1st LEED Building –

LEED 2.2 Gold

CRES award winner

www.cres.orgFirst LEED project for

owner and A/E team

Page 3: Case Study in Commercial Near Net-Zero LEED Design

Project Team

Owner: Dr. Ken DanylchuckArchitect: HGF ArchitectsSustainability Consultants: Sustainable Building

Concepts & PCD EngineeringMechanical Engineer: AE AssociatesElectrical Engineer: Kohnert EngineeringEnergy Consultant: PCD EngineeringCommissioning Agent: PCD EngineeringGeneral Contractor: TL Printz Constructors

Page 4: Case Study in Commercial Near Net-Zero LEED Design

Project Goals

Design a ‘green’ facility

with a ‘healthy’ environment

Page 5: Case Study in Commercial Near Net-Zero LEED Design

Site & Water

Building oriented

South to harvest solar

Pervious paving

Low water landscaping

Generous open space

Low flow fixtures

Page 6: Case Study in Commercial Near Net-Zero LEED Design

Energy

30kW Photovoltaic (PV) system – meets 30% of energy needs

Ground source heat pumps (GSHP)

Energy recovery ventilator (ERV) reduces ventilation load by 75%

ERV

GSHP

Page 7: Case Study in Commercial Near Net-Zero LEED Design

Lighting

Dimming and

occupancy based

lighting controls

Page 8: Case Study in Commercial Near Net-Zero LEED Design

Energy Profile

Electric Usage and Demand

-

1,000

2,000

3,000

4,000

5,000

6,000M

ar-

08

Ap

r-0

8

Ma

y-0

8

Ju

n-0

8

Ju

l-0

8

Au

g-0

8

(kW

h)

-

5.00

10.00

15.00

20.00

25.00

30.00

35.00

(kW

)

Usage (kWh) Demand (kW)

Page 9: Case Study in Commercial Near Net-Zero LEED Design

Performance Metrics

Source: EIA CBECS 2003: Table C.12 Consumption and Gross Energy Intensity by Year Constructed for Sum of Major Fuels for Non-Mall Buildings, 2003

Period March 2008 - August 2008

kWh Used/Year 51360

kWh Produced/Year 12640

Net kWh Used/Year 38720

Energy Use Intensity (Btu/Square Foot/Year) 16.5

CBECS: Office US 1990-2003* 88.0

CBECS: West Mountain Region 1990-2003* 81.2

Mapleleaf Orthopedics Performs 80% Better Than a Typical Building

$/Year $ 5,187

$/SF/Yr $ 0.65

Page 10: Case Study in Commercial Near Net-Zero LEED Design

Materials & Indoor Environment

Healthy, low/no VOC carpet & flooring that is recyclable or biodegradable

No VOC paints & stains Wheat board cabinets Sustainable lumber Construction waste

recycling Recycled content products Regional materials

Page 11: Case Study in Commercial Near Net-Zero LEED Design

Exemplary Performance

Exceed % of building energy cost met by PV System

Exemplary lighting design – auxiliary lighting system

Exemplary plumbing design – 59% reduction in water use from baseline(29% above LEED requirement)

Vegetated open space exceeds local zoning requirements by 516%(491% above LEED requirement)

Page 12: Case Study in Commercial Near Net-Zero LEED Design

Lessons Learned – LEED

Set LEED goals early

Get team members on board early with respect to

LEED, and schedule progress meetings

Budget time for credit documentation and

compliance

Value experience

Seek out exemplary projects and lessons learned

Page 13: Case Study in Commercial Near Net-Zero LEED Design

Lessons Learned – High Performance Design

Well written Owner Requirements and Basis of Engineering Design are key

Best results are achieved when risk is shared by a committed team

A building is not a thing – It’s a collaboration – Be involved

Reduce loads – Harvest passive and renewable energy sources

Track VE efforts and changes back to Basis of Design and Owner Requirements. Resist temptation to peel-off efficiency add-alternates

Page 14: Case Study in Commercial Near Net-Zero LEED Design

Lessons Learned – Energy Modeling

Establish Measurable Goals and stick to

them

Use modeling to inform the design

Complete modeling throughout the

process = best value

Monitor Post-Occupancy

Page 15: Case Study in Commercial Near Net-Zero LEED Design

Lessons Learned - Design Cx

Follow through early on to end Need clear Owner Defined Requirements & Basis of Design

LEED Checklist actively maintained (even if LEED not a goal)

Be O&M advocate during design Access and Service, Controls and Operations, Training

Requirements (including LEED) appropriately

represented in Plans and Specs

High performance and LEED - breeds complexity

–O&M advocate to assure operational “sanity”

Page 16: Case Study in Commercial Near Net-Zero LEED Design

Lessons Learned - Construction Cx

Don’t believe anything until you see it

Frequent communications with team – facilitate

teamwork

Objective is not “filling out forms” – it is in the

value of the process

Cx raises subcontractor level of performance and

compliance

Maintain issues log and

follow through

Page 17: Case Study in Commercial Near Net-Zero LEED Design

Challenges and Keys

Focus on the Value Tasks

Establish reasonable expectations

Apply appropriate technologies for the facility

type

Get team “up the curve” on high performance

design requirements

Achieve goals within budget

Page 18: Case Study in Commercial Near Net-Zero LEED Design

Feedback

Owner is thrilled with utility cost and increased

exposure for the facility

Gold Rating exceeded team’s expectation

LEED not black and white

Page 19: Case Study in Commercial Near Net-Zero LEED Design

Thank you!

Peter C. D’Antonio, PE, LEED AP