Page 1: Caracteristicas PLC S7 200 CPU 212

A

A-6S7-200 Programmable Controller System Manual

C79000–G7076–C230–02

A.2 CPU 212 DC Power Supply, DC Inputs, DC Outputs

Order Number: 6ES7 212–1AA01–0XB0

General Features

Physical size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)

Weight 0.3 kg (0.7 lbs.)

Power dissipation 5 W at 1.75 A load

User program size/storage 512 words/EEPROM

User data size/storageData retention

512 words/RAM50 hr typical (8 hr minimum at 40° C)

Local I/O1 8 inputs/6 outputs

Maximum number ofexpansion modules

2

Digital I/O supported 64 inputs/64 outputs

Analog I/O supported 16 inputs/16 outputs

Boolean execution speed 1.2 µs/instruction

Internal memory bits 128

Timers 64 timers

Counters 64 counters

High-speed counters 1 software (2 KHz max.)

Analog adjustments 1

Standards compliance UL 508 CSA C22.2 142FM Class I, Division 2VDE 0160 compliantCE compliant

Output Points

Output type Sourcing transistor

Voltage range 20.4 VDC to 28.8 VDC

Maximum load currentPer single pointPer 2 adjacent pointsAll points total

0 to 40° C 55° C2

0.75 A 0.50 A1.00 A 0.75 A2.25 A 1.75 A

Inductive load clampingSingle pulse

Repetitive

(per common)2A L/R = 10 ms1A L/R = 100 ms1 W energy dissipation(1/2 Li2 x switch rate 1 W)

Leakage current 100 µA

Output Points (continued)

Switching delay 25 µs ON, 120 µs OFF

Surge current 4 A, 100 ms

Voltage drop 1.8 V maximum at maximumcurrent

Optical isolation 500 VAC, 1 min

Short circuit protection None

Input Points

Input type (IEC 1131–2) Type 1 sinking

ON state range 15–30 VDC, 4 mA minimum35 VDC, 500 ms surge

ON state nominal 24 VDC, 7 mA

OFF state maximum 5 VDC, 1 mA

Response time I0.0 to I0.7 0.3 ms maximum

Optical isolation 500 VAC, 1 min

Power Supply

Voltage range 20.4 to 28.8 VDC

Input current 60 mA typical, CPU only500 mA maximum load

UL/CSA rating 50 VA

Holdup time 10 ms minimum from 24 VDC

Inrush current 10 A peak at 28.8 VDC

Fusing (non-replaceable) 1 A, 125 V, slow blow

5 VDC current 260 mA for CPU340 mA for expansion I/O

Isolated No

DC Sensor Supply

Voltage range 16.4 to 28.8 VDC

Ripple/noise (<10MHz) Same as supplied voltage

24 VDC available currentShort-circuit current limit

180 mA< 600 mA

Isolated No

1 The CPU reserves 8 process-image input and 8 process-image output image register points for local I/O.2 Linear derate 40 to 55° C Vertical mount derate 10° C.

S7-200 Data Sheets

Page 2: Caracteristicas PLC S7 200 CPU 212

A

A-7S7-200 Programmable Controller System Manual C79000–G7076–C230–02

OUTPUTS M L+ 0.0 0.1 0.2 0.3 0.4 0.5 M L+ 24VDC

INPUTS1M 0.0 0.1 0.2 0.3 2M 0.4 0.5 M L+0.6

Inputs (15 VDC to 30 VDC)

24 VDC power for inputsensors or expansionmdules (180 mA)

+

Outputs (20.4 to 28.8 VDC)

+

0.7

++

3.3K Ω

470 Ω

DC 24V DCSENSORSUPPLY

Power supply

Note:1. Actual component values may vary.2. DC circuit grounds are optional.

DC 24V

36V

36V

Figure A-2 Connector Terminal Identification for CPU 212 DC/DC/DC

S7-200 Data Sheets

Page 3: Caracteristicas PLC S7 200 CPU 212

A

A-8S7-200 Programmable Controller System Manual

C79000–G7076–C230–02

A.3 CPU 212 AC Power Supply, DC Inputs, Relay Outputs

Order Number: 6ES7 212–1BA01–0XB0

General Features

Physical size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)

Weight 0.4 kg (0.9 lbs.)

Power dissipation 6 W

User program size/storage 512 words/EEPROM

User data size/storageData retention

512 words/RAM50 hr typical(8 hr minimum at 40° C)

Local I/O1 8 inputs/6 outputs

Maximum number ofexpansion modules

2

Digital I/O supported 64 inputs/64 outputs

Analog I/O supported 16 inputs/16 outputs

Boolean execution speed 1.2 µs/instruction

Internal memory bits 128

Timers 64 timers

Counters 64 counters

High-speed counters 1 software (2 KHz max.)

Analog adjustments 1

Standards compliance UL 508 CSA C22.2 142FM Class I, Division 2VDE 0160 compliantCE compliant

Output Points

Output type Relay, dry contact

Voltage range 5 to 30 VDC/250 VAC

Maximum load current 2 A/point, 6 A/common

Overcurrent surge 7 A with contacts closed

Isolation resistance 100 M minimum (new)

Switching delay 10 ms maximum

Lifetime 10,000,000 mechanical100,000 with rated load

Contact resistance 200 m maximum (new)

Isolationcoil to contactcontact to contact(between open contacts)

1500 VAC, 1 min750 VAC, 1 min

Short circuit protection None

Input Points

Input type (IEC 1131–2) Type 1 sinking

ON state range 15–30 VDC, 4 mA minimum35 VDC, 500 ms surge

ON state nominal 24 VDC, 7 mA

OFF state maximum 5 VDC, 1 mA

Response timeI0.0 to I0.7 0.3 ms maximum

Optical isolation 500 VAC, 1 min

Power Supply

Voltage/frequency range 85 to 264 VAC at 47 to 63 Hz

Input current 4 VA typical, CPU only50 VA maximum load

Holdup time 20 ms minimum from 110 VAC

Inrush current 20 A peak at 264 VAC

Fusing (non-replaceable) 2 A, 250 V, slow blow

5 VDC current 260 mA for CPU340 mA for expansion I/O

Isolated Yes. Transformer, 1500 VAC,1 min

DC Sensor Supply

Voltage range 20.4 to 28.8 VDC

Ripple/noise (<10MHz) 1 V peak-to-peak maximum

24 VDC available currentShort circuit current limit

180 mA< 600 mA

Isolated No

1 The CPU reserves 8 process-image input and 8 process-image output image register points for local I/O.

S7-200 Data Sheets

Page 4: Caracteristicas PLC S7 200 CPU 212

A

A-9S7-200 Programmable Controller System Manual C79000–G7076–C230–02

OUTPUTS 1L 0.0 0.1 0.2 2L 0.3 0.4 0.5 N L1 85–264VAC

INPUTS1M 0.0 0.1 0.2 0.3 0.4 0.5 0.6 M L+0.7

Outputs (30 VDC/250 VAC) Power supply

Inputs (15 VDC to 30 VDC)

24 VDC power for input sensorsor expansion modules (180 mA)

2M

+ +

RELAY

DCSENSORSUPPLY

DC 24V

3.3 KΩ

470 Ω

N (–)

L (+)

Note:1. Actual component values may vary.2. Connect AC line to the L terminal.3. DC circuit grounds are optional.

N (–)

L (+)

Figure A-3 Connector Terminal Identification for CPU 212 AC/DC/Relay

S7-200 Data Sheets

Page 5: Caracteristicas PLC S7 200 CPU 212

A

A-10S7-200 Programmable Controller System Manual

C79000–G7076–C230–02

A.4 CPU 212 24 VAC Power Supply, DC Inputs, Relay Outputs

Order Number: 6ES7 212–1FA01–0XB0

General Features

Physical size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)

Weight 0.4 kg (0.9 lbs.)

Power dissipation 6 W

User program size/storage 512 words/EEPROM

User data size/storageData retention

512 words/RAM50 hr typical(8 hr minimum at 40° C)

Local I/O1 8 inputs/6 outputs

Maximum number ofexpansion modules

2

Digital I/O supported 64 inputs/64 outputs

Analog I/O supported 16 inputs/16 outputs

Boolean execution speed 1.2 µs/instruction

Internal memory bits 128

Timers 64 timers

Counters 64 counters

High-speed counters 1 software (2 KHz max.)

Analog adjustments 1

Standards compliance UL 508 CSA C22.2 142FM Class I, Division 2VDE 0160 compliantCE compliant

Output Points

Output type Relay, dry contact

Voltage range 5 to 30 VDC/250 VAC

Maximum load current 2 A /point, 6 A /common

Overcurrent surge 7 A with contacts closed

Isolation resistance 100 M minimum (new)

Switching delay 10 ms maximum

Lifetime 10,000,000 mechanical100,000 with rated load

Contact resistance 200 m maximum (new)

Isolationcoil to contactcontact to contact(between open contacts)

1500 VAC, 1 min750 VAC, 1 min

Short circuit protection None

Input Points

Input type (IEC 1131–2) Type 1 sinking

ON state range 15–30 VDC, 4 mA minimum35 VDC, 500 ms surge

ON state nominal 24 VDC, 7 mA

OFF state maximum 5 VDC, 1 mA

Response timeI0.0 to I0.7 0.3 ms maximum

Optical isolation 500 VAC, 1 min

Power Supply

Voltage/frequency range 20 to 29 VAC at 47 to 63 Hz

Input current 4 VA typical, CPU only50 VA maximum load

Holdup time 20 ms minimum from 24 VAC

Inrush current 20 A peak at 29 VAC

Fusing (non-replaceable) 2 A, 250 V, slow blow

5 VDC current 260 mA for CPU340 mA for expansion I/O

Isolated Yes. Transformer, 500 VAC,1 min

DC Sensor Supply

Voltage range 20.4 to 28.8 VDC

Ripple/noise (<10MHz) 1 V peak-to-peak maximum

24 VDC available currentShort circuit current limit

180 mA< 600 mA

Isolated No

1 The CPU reserves 8 process-image input and 8 process-image output image register points for local I/O.

S7-200 Data Sheets

Page 6: Caracteristicas PLC S7 200 CPU 212

A

A-11S7-200 Programmable Controller System Manual C79000–G7076–C230–02

OUTPUTS 1L 0.0 0.1 0.2 2L 0.3 0.4 0.5 N L1 20–29VAC

INPUTS1M 0.0 0.1 0.2 0.3 0.4 0.5 0.6 M L+0.7

Outputs (30 VDC/250 VAC) Power supply

Inputs (15 VDC to 30 VDC)

24 VDC power for input sensorsor expansion modules (180 mA)

2M

+ +

RELAY

DCSENSORSUPPLY

DC 24V

3.3 KΩ

470 Ω

N (–)

L (+)

Note:1. Actual component values may vary.2. Connect AC line to the L terminal.3. DC circuit grounds are optional.

N (–)

L (+)

Figure A-4 Connector Terminal Identification for CPU 212 24 VAC/DC/Relay

S7-200 Data Sheets

Page 7: Caracteristicas PLC S7 200 CPU 212

A

A-12S7-200 Programmable Controller System Manual

C79000–G7076–C230–02

A.5 CPU 212 AC Power Supply, AC Inputs, AC Outputs

Order Number: 6ES7 212–1CA01–0XB0

General Features

Physical size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)

Weight 0.4 kg (0.9 lbs.)

Power dissipation 7 W at 2.5 A load

User program size/storage 512 words/EEPROM

User data size/storageData retention

512 words/RAM50 hr typical(8 hr minimum at 40° C)

Local I/O1 8 inputs/6 outputs

Maximum number ofexpansion modules

2

Digital I/O supported 64 inputs/64 outputs

Analog I/O supported 16 inputs/16 outputs

Boolean execution speed 1.2 µs/instruction

Internal memory bits 128

Timers 64 timers

Counters 64 counters

High-speed counters 1 software (50 Hz max.)

Analog adjustments 1

Standards compliance UL 508 CSA C22.2 142FM Class I, Division 2CE compliant

Output Points

Output type Triac, zero-crossing

Voltage/frequency range 20 to 264 VAC, 47 to 63 Hz

Load circuit power factor 0.3 to 1.0

Inductive load clamping MOV 275 V working voltage

Maximum load currentper single pointper 2 adjacent pointsall points total*

0 to 40° C 55° C2

1.20 A 1.00 A1.50 A 1.25 A3.50 A 2.50 A

Minimum load current 30 mA

Leakage current 1.5 mA, 120 VAC/2.0 mA,240 VAC

Output Points (continued)

Switching delay 1/2 cycle

Surge current 30 A peak, 1 cycle / 10 A peak, 5 cycle

Voltage drop 1.5 V maximum at maximumcurrent

Optical isolation 1500 VAC, 1 min

Short circuit protection None

Input Points

Input type (IEC 1131–2) Type 1 sinking

ON state range 79 to 135 VAC, 47 to 63 Hz, 4 mA minimum

ON state nominal 120 VAC, 60 Hz, 7 mA

OFF state maximum 20 VAC, 1 mA

Response time 10 ms typical, 15 ms max.

Optical isolation 1500 VAC, 1 min

Power Supply

Voltage/frequency range 85 to 264 VAC at 47 to 63 Hz

Input current 4 VA typical, CPU only50 VA maximum load

Holdup time 20 ms minimum from 110 VAC

Inrush current 20 A peak at 264 VAC

Fusing (non-replaceable) 2 A, 250 V, slow blow

5 VDC current 320 mA for CPU280 mA for expansion I/O

Isolated Yes. Transformer, 1500 VAC,1 min

DC Sensor Supply

Voltage range 20.4 to 28.8 VDC

Ripple/noise (<10MHz) 1 V peak-to-peak maximum

24 VDC available current 180 mA

Short circuit current limit < 600 mA

Isolated No

1 The CPU reserves 8 process-image input and 8 process-image output register points for local I/O.2 Linear derate 40 to 55° C. Vertical mount derate 10° C.

S7-200 Data Sheets

Page 8: Caracteristicas PLC S7 200 CPU 212

A

A-13S7-200 Programmable Controller System Manual C79000–G7076–C230–02

1L 0.0 0.1 0.2 2L 0.3 0.4 0.5 N L1 85–264VAC

N 0.0 0.1 0.2 0.3 0.4 0.5 0.6 M L+0.7

Outputs (20 VAC to 264 VAC) Power supply

Inputs (79 VAC to 135 VAC)

24 VDC power for input sensorsor expansion modules (180 mA)

10 Ω0.0068 µF

275V MOV

0.15 µF 470 KΩ

390 Ω

ACOUTPUTS

DCSENSORSUPPLY

AC 120V INPUTS

3.3 KΩNote: Actual component values may vary.

Figure A-5 Connector Terminal Identification for CPU 212 AC/AC/AC

S7-200 Data Sheets

Page 9: Caracteristicas PLC S7 200 CPU 212

A

A-14S7-200 Programmable Controller System Manual

C79000–G7076–C230–02

A.6 CPU 212 AC Power Supply, Sourcing DC Inputs, Relay Outputs

Order Number: 6ES7 212–1BA10–0XB0

General Features

Physical size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)

Weight 0.4 kg (0.9 lbs.)

Power dissipation 6 W

User program size/storage 512 words/EEPROM

User data size/storageData retention

512 words/RAM50 hr typical(8 hr minimum at 40° C)

Local I/O1 8 inputs/6 outputs

Maximum number ofexpansion modules

2

Digital I/O supported 64 inputs/64 outputs

Analog I/O supported 16 inputs/16 outputs

Boolean execution speed 1.2 µs/instruction

Internal memory bits 128

Timers 64 timers

Counters 64 counters

High-speed counters 1 software (2 KHz max.)

Analog adjustments 1

Standards compliance UL 508 CSA C22.2 142FM Class I, Division 2VDE 0160 compliantCE compliant

Output Points

Output type Relay, dry contact

Voltage range 5 to 30 VDC/250 VAC

Maximum load current 2 A /point, 6 A/common

Overcurrent surge 7 A with contacts closed

Isolation resistance 100 M minimum (new)

Switching delay 10 ms maximum

Lifetime 10,000,000 mechanical100,000 with rated load

Contact resistance 200 m maximum (new)

Isolationcoil to contactcontact to contact(between open contacts)

1500 VAC, 1 min750 VAC, 1 min

Short circuit protection None

Input Points

Type Sourcing

Input voltage range 15 to 30 VDC, 35 VDC for 500 ms

ON state 4 mA minimum

OFF state 1 mA maximum

Response timeI0.0 to I0.7 0.3 ms maximum

Optical isolation 500 VAC, 1 min

Power Supply

Voltage/frequency range 85 to 264 VAC at 47 to 63 Hz

Input current 4 VA typical, CPU only50 VA maximum load

Holdup time 20 ms minimum from 110 VAC

Inrush current 20 A peak at 264 VAC

Fusing (non-replaceable) 2 A, 250 V, slow blow

5 VDC available current 260 mA for CPU340 mA for expansion I/O

Isolated Yes. Transformer, 1500 VAC,1 min

DC Sensor Supply

Voltage range 20.4 to 28.8 VDC

Ripple/noise (<10MHz) 1 V peak-to-peak maximum

24 VDC available currentshort circuit current limit

180 mA< 600 mA

Isolated No

1 The CPU reserves 8 process-image input and 8 process-image output register points for local I/O.

S7-200 Data Sheets

Page 10: Caracteristicas PLC S7 200 CPU 212

A

A-15S7-200 Programmable Controller System Manual C79000–G7076–C230–02

1L 0.0 0.1 0.2 2L 0.3 0.4 0.5 N L1 85–264VAC

1L 0.0 0.1 0.2 0.3 0.4 0.5 0.6 M L+0.7

Outputs (30 VDC/250 VAC) Power supply

Inputs (15 VDC to 30 VDC)

24 VDC power for input sensorsor expansion modules (180 mA)

2L

+

RELAYOUTPUTS

DCSENSORSUPPLY

DC 24VINPUTS

3.3 KΩ470 Ω

N (–)

L (+)

Note: 1. Actual component values may vary.2. Connect AC line to the L terminal.3. Input circuit ground is optional.

N (–)

L (+)

+

Figure A-6 Connector Terminal Identification for CPU 212 AC/Sourcing DC/Relay

S7-200 Data Sheets

Page 11: Caracteristicas PLC S7 200 CPU 212

A

A-16S7-200 Programmable Controller System Manual

C79000–G7076–C230–02

A.7 CPU 212 AC Power Supply, 24 VAC Inputs, AC Outputs

Order Number: 6ES7 212–1DA01–0XB0

General Features

Physical size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)

Weight 0.4 kg (0.9 lbs.)

Power dissipation 7 W at 2.5 A load

User program size/storage 512 words/EEPROM

User sata size/storageData retention

512 words/RAM50 hr typical(8 hr minimum at 40° C)

Local I/O1 8 inputs/6 outputs

Maximum number ofexpansion modules

2

Digital I/O supported 64 inputs/64 outputs

Analog I/O supported 16 inputs/16 outputs

Boolean execution speed 1.2 µs/instruction

Internal memory bits 128

Timers 64 timers

Counters 64 counters

High-speed counters 1 software (50 Hz max.)

Analog adjustments 1

Standards compliance UL 508 CSA C22.2 142FM Class I, Division 2CE compliant

Output Points

Output type Triac, zero-crossing

Voltage/frequency range 20 to 264 VAC, 47 to 63 Hz

Load circuit power factor 0.3 to 1.0

Inductive load clamping MOV 275 V working voltage

Maximum load currentper single pointper 2 adjacent pointsall points total

0 to 40° C 55° C 2

1.20 A 1.00 A1.50 A 1.25 A3.50 A 2.50 A

Minimum load current 30 mA

Leakage current 1.5 mA, 120 VAC/2.0 mA,240 VAC

Output Points (continued)

Switching delay 1/2 cycle

Surge current 30 A peak, 1 cycle / 10 A peak, 5 cycle

Voltage drop 1.5 V maximum at maximumcurrent

Optical isolation 1500 VAC, 1 min

Short circuit protection None

Input Points

Input type (IEC 1131–2) Type 1 sinking

ON state range 15 to 30 VAC, 47 to 63 Hz, 4 mA minimum

ON state nominal 24 VAC, 60 Hz, 7 mA

OFF state maximum 5 VAC, 1 mA

Response time 10 ms typical, 15 ms max.

Optical isolation 1500 VAC, 1 min

Power Supply

Voltage/frequency range 85 to 264 VAC at 47 to 63 Hz

Input current 4 VA typical, CPU only50 VA maximum load

Holdup time 20 ms minimum from 110 VAC

Inrush current 20 A peak at 264 VAC

Fusing (non-replaceable) 2 A, 250 V, slow blow

5 VDC current 320 mA for CPU280 mA for expansion I/O

Isolated Yes. Transformer, 1500 VAC,1 min

DC Sensor Supply

Voltage range 20.4 to 28.8 VDC

Ripple/noise (<10MHz) 1 V peak-to-peak maximum

24 VDC available current 180 mA

Short circuit current limit < 600 mA

Isolated No

1 The CPU reserves 8 process-image input and 8 process-image output register points for local I/O.2 Linear derate 40 to 55° C. Vertical mount derate 10° C

S7-200 Data Sheets

Page 12: Caracteristicas PLC S7 200 CPU 212

A

A-17S7-200 Programmable Controller System Manual C79000–G7076–C230–02

1L 0.0 0.1 0.2 2L 0.3 0.4 0.5 N L1 85–264VAC

N 0.0 0.1 0.2 0.3 0.4 0.5 0.6 M L+0.7

Outputs (20 VAC to 264 VAC) Power supply

Inputs (15 VAC to 30 VAC)

24 VDC power for input sensorsor expansion modules (180 mA)

10 Ω0.0068 µF

275V MOV

390 Ω

ACOUTPUTS

DCSENSORSUPPLY

AC 24VINPUTS

3.3 KΩ

Note: Actual component values may vary.

Figure A-7 Connector Terminal Identification for CPU 212 AC/AC/AC

S7-200 Data Sheets

Page 13: Caracteristicas PLC S7 200 CPU 212

A

A-18S7-200 Programmable Controller System Manual

C79000–G7076–C230–02

A.8 CPU 212 AC Power Supply, AC Inputs, Relay Outputs

Order Number: 6ES7 212–1GA01–0XB0

General Features

Physical Size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)

Weight 0.4 kg (0.9 lbs.)

Power Dissipation 6 W

User program size/storage 512 Words / EEPROM

User data size/storageData retention

512 Words / RAM50 hr typical(8 hr minimum at 40° C)

Local I/O1 8 Inputs / 6 Outputs

Maximum Number ofExpansion Modules

2

Digital I/O Supported 64 Inputs / 64 Outputs

Analog I/O Supported 16 Inputs / 16 Outputs

Boolean Execution Speed 1.2 µs/instruction

Internal Memory Bits 128

Timers 64 Timers

Counters 64 Counters

High-speed counters 1 Software (2 KHz max.)

Analog Adjustments 1

Standards Compliance UL 508 CSA C22.2 142FM Class I, Division 2VDE 0160 compliantCE compliant

Output Points

Output Type Relay, dry contact

Voltage Range 5 to 30 VDC / 250 VAC

Maximum Load Current 2 A/point

Overcurrent Surge 7 A with contacts closed

Isolation Resistance 100 M minimum (new)

Switching Delay 10 ms maximum

Lifetime 10,000,000 Mechanical100,000 with Rated Load

Contact Resistance 200 m maximum (new)

IsolationCoil to ContactContact to Contact

1500 VAC, 1 minute1000 VAC, 1 minute

Short Circuit Protection None

Input Points

Input Type (IEC 1131–2) Type 1 Sinking

ON State Range 79 to 135 VAC, 47 to 63 Hz.4 mA minimum

ON State Nominal 120 VAC, 60 Hz, 7mA

OFF State Maximum 20 VAC, 1 mA

Response Time 10 ms typical, 15 ms max.

Optical Isolation 1500 VAC, 1 minute

Power Supply

Voltage/frequency Range 85 to 264 VAC at 47 to 63 Hz

Input Current 4 VA typical, CPU only50 VA maximum load

Hold Up Time 20 ms minimum from 110 VAC

Inrush Current 20 A peak at 264 VAC

Fusing (non-replaceable) 2 A, 250 V, Slow Blow

5 VDC Current 260 mA for CPU340 mA for expansion I/O

Isolated Yes. Transformer, 1500 VAC,1 minute

DC Sensor Supply

Voltage Range 20.4 to 28.8 VDC

Ripple/noise (<10Mhz) 1 V peak-to-peak maximum

24 VDC Available CurrentShort Circuit Current Limit

180 mA< 600 mA

Isolated No

1 The CPU reserves 8 input and 8 output image register points for local I/O.

S7-200 Data Sheets

Page 14: Caracteristicas PLC S7 200 CPU 212

A

A-19S7-200 Programmable Controller System Manual C79000–G7076–C230–02

OUTPUTS 1L 0.0 0.1 0.2 2L 0.3 0.4 0.5 N L1 85–264VAC

Outputs (30 VDC / 250 VAC) Power Supply

RELAY

N (–)

L (+)

Note:1. Actual component values may vary.2. Connect AC line to the L terminal.

N (–)

L (+)

N 0.0 0.1 0.2 0.3 0.4 0.5 0.6 M L+0.7

Inputs (79 to 135 VAC)

24 VDC Power for Input Sensorsor Expansion Modules (180 mA)

0.0068 µF

0.15 µF 470K ohms

390 ohms

DCSENSORSUPPLY

AC 120V INPUTS

3.3K ohms

Figure A-8 Connector Terminal Identification for CPU 212 AC/AC/Relay

S7-200 Data Sheets