caracteristicas plc s7 200 cpu 212
TRANSCRIPT
A
A-6S7-200 Programmable Controller System Manual
C79000–G7076–C230–02
A.2 CPU 212 DC Power Supply, DC Inputs, DC Outputs
Order Number: 6ES7 212–1AA01–0XB0
General Features
Physical size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)
Weight 0.3 kg (0.7 lbs.)
Power dissipation 5 W at 1.75 A load
User program size/storage 512 words/EEPROM
User data size/storageData retention
512 words/RAM50 hr typical (8 hr minimum at 40° C)
Local I/O1 8 inputs/6 outputs
Maximum number ofexpansion modules
2
Digital I/O supported 64 inputs/64 outputs
Analog I/O supported 16 inputs/16 outputs
Boolean execution speed 1.2 µs/instruction
Internal memory bits 128
Timers 64 timers
Counters 64 counters
High-speed counters 1 software (2 KHz max.)
Analog adjustments 1
Standards compliance UL 508 CSA C22.2 142FM Class I, Division 2VDE 0160 compliantCE compliant
Output Points
Output type Sourcing transistor
Voltage range 20.4 VDC to 28.8 VDC
Maximum load currentPer single pointPer 2 adjacent pointsAll points total
0 to 40° C 55° C2
0.75 A 0.50 A1.00 A 0.75 A2.25 A 1.75 A
Inductive load clampingSingle pulse
Repetitive
(per common)2A L/R = 10 ms1A L/R = 100 ms1 W energy dissipation(1/2 Li2 x switch rate 1 W)
Leakage current 100 µA
Output Points (continued)
Switching delay 25 µs ON, 120 µs OFF
Surge current 4 A, 100 ms
Voltage drop 1.8 V maximum at maximumcurrent
Optical isolation 500 VAC, 1 min
Short circuit protection None
Input Points
Input type (IEC 1131–2) Type 1 sinking
ON state range 15–30 VDC, 4 mA minimum35 VDC, 500 ms surge
ON state nominal 24 VDC, 7 mA
OFF state maximum 5 VDC, 1 mA
Response time I0.0 to I0.7 0.3 ms maximum
Optical isolation 500 VAC, 1 min
Power Supply
Voltage range 20.4 to 28.8 VDC
Input current 60 mA typical, CPU only500 mA maximum load
UL/CSA rating 50 VA
Holdup time 10 ms minimum from 24 VDC
Inrush current 10 A peak at 28.8 VDC
Fusing (non-replaceable) 1 A, 125 V, slow blow
5 VDC current 260 mA for CPU340 mA for expansion I/O
Isolated No
DC Sensor Supply
Voltage range 16.4 to 28.8 VDC
Ripple/noise (<10MHz) Same as supplied voltage
24 VDC available currentShort-circuit current limit
180 mA< 600 mA
Isolated No
1 The CPU reserves 8 process-image input and 8 process-image output image register points for local I/O.2 Linear derate 40 to 55° C Vertical mount derate 10° C.
S7-200 Data Sheets
A
A-7S7-200 Programmable Controller System Manual C79000–G7076–C230–02
OUTPUTS M L+ 0.0 0.1 0.2 0.3 0.4 0.5 M L+ 24VDC
INPUTS1M 0.0 0.1 0.2 0.3 2M 0.4 0.5 M L+0.6
Inputs (15 VDC to 30 VDC)
24 VDC power for inputsensors or expansionmdules (180 mA)
+
Outputs (20.4 to 28.8 VDC)
+
0.7
++
3.3K Ω
470 Ω
DC 24V DCSENSORSUPPLY
Power supply
Note:1. Actual component values may vary.2. DC circuit grounds are optional.
DC 24V
36V
36V
Figure A-2 Connector Terminal Identification for CPU 212 DC/DC/DC
S7-200 Data Sheets
A
A-8S7-200 Programmable Controller System Manual
C79000–G7076–C230–02
A.3 CPU 212 AC Power Supply, DC Inputs, Relay Outputs
Order Number: 6ES7 212–1BA01–0XB0
General Features
Physical size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)
Weight 0.4 kg (0.9 lbs.)
Power dissipation 6 W
User program size/storage 512 words/EEPROM
User data size/storageData retention
512 words/RAM50 hr typical(8 hr minimum at 40° C)
Local I/O1 8 inputs/6 outputs
Maximum number ofexpansion modules
2
Digital I/O supported 64 inputs/64 outputs
Analog I/O supported 16 inputs/16 outputs
Boolean execution speed 1.2 µs/instruction
Internal memory bits 128
Timers 64 timers
Counters 64 counters
High-speed counters 1 software (2 KHz max.)
Analog adjustments 1
Standards compliance UL 508 CSA C22.2 142FM Class I, Division 2VDE 0160 compliantCE compliant
Output Points
Output type Relay, dry contact
Voltage range 5 to 30 VDC/250 VAC
Maximum load current 2 A/point, 6 A/common
Overcurrent surge 7 A with contacts closed
Isolation resistance 100 M minimum (new)
Switching delay 10 ms maximum
Lifetime 10,000,000 mechanical100,000 with rated load
Contact resistance 200 m maximum (new)
Isolationcoil to contactcontact to contact(between open contacts)
1500 VAC, 1 min750 VAC, 1 min
Short circuit protection None
Input Points
Input type (IEC 1131–2) Type 1 sinking
ON state range 15–30 VDC, 4 mA minimum35 VDC, 500 ms surge
ON state nominal 24 VDC, 7 mA
OFF state maximum 5 VDC, 1 mA
Response timeI0.0 to I0.7 0.3 ms maximum
Optical isolation 500 VAC, 1 min
Power Supply
Voltage/frequency range 85 to 264 VAC at 47 to 63 Hz
Input current 4 VA typical, CPU only50 VA maximum load
Holdup time 20 ms minimum from 110 VAC
Inrush current 20 A peak at 264 VAC
Fusing (non-replaceable) 2 A, 250 V, slow blow
5 VDC current 260 mA for CPU340 mA for expansion I/O
Isolated Yes. Transformer, 1500 VAC,1 min
DC Sensor Supply
Voltage range 20.4 to 28.8 VDC
Ripple/noise (<10MHz) 1 V peak-to-peak maximum
24 VDC available currentShort circuit current limit
180 mA< 600 mA
Isolated No
1 The CPU reserves 8 process-image input and 8 process-image output image register points for local I/O.
S7-200 Data Sheets
A
A-9S7-200 Programmable Controller System Manual C79000–G7076–C230–02
OUTPUTS 1L 0.0 0.1 0.2 2L 0.3 0.4 0.5 N L1 85–264VAC
INPUTS1M 0.0 0.1 0.2 0.3 0.4 0.5 0.6 M L+0.7
Outputs (30 VDC/250 VAC) Power supply
Inputs (15 VDC to 30 VDC)
24 VDC power for input sensorsor expansion modules (180 mA)
2M
+ +
RELAY
DCSENSORSUPPLY
DC 24V
3.3 KΩ
470 Ω
N (–)
L (+)
Note:1. Actual component values may vary.2. Connect AC line to the L terminal.3. DC circuit grounds are optional.
N (–)
L (+)
Figure A-3 Connector Terminal Identification for CPU 212 AC/DC/Relay
S7-200 Data Sheets
A
A-10S7-200 Programmable Controller System Manual
C79000–G7076–C230–02
A.4 CPU 212 24 VAC Power Supply, DC Inputs, Relay Outputs
Order Number: 6ES7 212–1FA01–0XB0
General Features
Physical size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)
Weight 0.4 kg (0.9 lbs.)
Power dissipation 6 W
User program size/storage 512 words/EEPROM
User data size/storageData retention
512 words/RAM50 hr typical(8 hr minimum at 40° C)
Local I/O1 8 inputs/6 outputs
Maximum number ofexpansion modules
2
Digital I/O supported 64 inputs/64 outputs
Analog I/O supported 16 inputs/16 outputs
Boolean execution speed 1.2 µs/instruction
Internal memory bits 128
Timers 64 timers
Counters 64 counters
High-speed counters 1 software (2 KHz max.)
Analog adjustments 1
Standards compliance UL 508 CSA C22.2 142FM Class I, Division 2VDE 0160 compliantCE compliant
Output Points
Output type Relay, dry contact
Voltage range 5 to 30 VDC/250 VAC
Maximum load current 2 A /point, 6 A /common
Overcurrent surge 7 A with contacts closed
Isolation resistance 100 M minimum (new)
Switching delay 10 ms maximum
Lifetime 10,000,000 mechanical100,000 with rated load
Contact resistance 200 m maximum (new)
Isolationcoil to contactcontact to contact(between open contacts)
1500 VAC, 1 min750 VAC, 1 min
Short circuit protection None
Input Points
Input type (IEC 1131–2) Type 1 sinking
ON state range 15–30 VDC, 4 mA minimum35 VDC, 500 ms surge
ON state nominal 24 VDC, 7 mA
OFF state maximum 5 VDC, 1 mA
Response timeI0.0 to I0.7 0.3 ms maximum
Optical isolation 500 VAC, 1 min
Power Supply
Voltage/frequency range 20 to 29 VAC at 47 to 63 Hz
Input current 4 VA typical, CPU only50 VA maximum load
Holdup time 20 ms minimum from 24 VAC
Inrush current 20 A peak at 29 VAC
Fusing (non-replaceable) 2 A, 250 V, slow blow
5 VDC current 260 mA for CPU340 mA for expansion I/O
Isolated Yes. Transformer, 500 VAC,1 min
DC Sensor Supply
Voltage range 20.4 to 28.8 VDC
Ripple/noise (<10MHz) 1 V peak-to-peak maximum
24 VDC available currentShort circuit current limit
180 mA< 600 mA
Isolated No
1 The CPU reserves 8 process-image input and 8 process-image output image register points for local I/O.
S7-200 Data Sheets
A
A-11S7-200 Programmable Controller System Manual C79000–G7076–C230–02
OUTPUTS 1L 0.0 0.1 0.2 2L 0.3 0.4 0.5 N L1 20–29VAC
INPUTS1M 0.0 0.1 0.2 0.3 0.4 0.5 0.6 M L+0.7
Outputs (30 VDC/250 VAC) Power supply
Inputs (15 VDC to 30 VDC)
24 VDC power for input sensorsor expansion modules (180 mA)
2M
+ +
RELAY
DCSENSORSUPPLY
DC 24V
3.3 KΩ
470 Ω
N (–)
L (+)
Note:1. Actual component values may vary.2. Connect AC line to the L terminal.3. DC circuit grounds are optional.
N (–)
L (+)
Figure A-4 Connector Terminal Identification for CPU 212 24 VAC/DC/Relay
S7-200 Data Sheets
A
A-12S7-200 Programmable Controller System Manual
C79000–G7076–C230–02
A.5 CPU 212 AC Power Supply, AC Inputs, AC Outputs
Order Number: 6ES7 212–1CA01–0XB0
General Features
Physical size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)
Weight 0.4 kg (0.9 lbs.)
Power dissipation 7 W at 2.5 A load
User program size/storage 512 words/EEPROM
User data size/storageData retention
512 words/RAM50 hr typical(8 hr minimum at 40° C)
Local I/O1 8 inputs/6 outputs
Maximum number ofexpansion modules
2
Digital I/O supported 64 inputs/64 outputs
Analog I/O supported 16 inputs/16 outputs
Boolean execution speed 1.2 µs/instruction
Internal memory bits 128
Timers 64 timers
Counters 64 counters
High-speed counters 1 software (50 Hz max.)
Analog adjustments 1
Standards compliance UL 508 CSA C22.2 142FM Class I, Division 2CE compliant
Output Points
Output type Triac, zero-crossing
Voltage/frequency range 20 to 264 VAC, 47 to 63 Hz
Load circuit power factor 0.3 to 1.0
Inductive load clamping MOV 275 V working voltage
Maximum load currentper single pointper 2 adjacent pointsall points total*
0 to 40° C 55° C2
1.20 A 1.00 A1.50 A 1.25 A3.50 A 2.50 A
Minimum load current 30 mA
Leakage current 1.5 mA, 120 VAC/2.0 mA,240 VAC
Output Points (continued)
Switching delay 1/2 cycle
Surge current 30 A peak, 1 cycle / 10 A peak, 5 cycle
Voltage drop 1.5 V maximum at maximumcurrent
Optical isolation 1500 VAC, 1 min
Short circuit protection None
Input Points
Input type (IEC 1131–2) Type 1 sinking
ON state range 79 to 135 VAC, 47 to 63 Hz, 4 mA minimum
ON state nominal 120 VAC, 60 Hz, 7 mA
OFF state maximum 20 VAC, 1 mA
Response time 10 ms typical, 15 ms max.
Optical isolation 1500 VAC, 1 min
Power Supply
Voltage/frequency range 85 to 264 VAC at 47 to 63 Hz
Input current 4 VA typical, CPU only50 VA maximum load
Holdup time 20 ms minimum from 110 VAC
Inrush current 20 A peak at 264 VAC
Fusing (non-replaceable) 2 A, 250 V, slow blow
5 VDC current 320 mA for CPU280 mA for expansion I/O
Isolated Yes. Transformer, 1500 VAC,1 min
DC Sensor Supply
Voltage range 20.4 to 28.8 VDC
Ripple/noise (<10MHz) 1 V peak-to-peak maximum
24 VDC available current 180 mA
Short circuit current limit < 600 mA
Isolated No
1 The CPU reserves 8 process-image input and 8 process-image output register points for local I/O.2 Linear derate 40 to 55° C. Vertical mount derate 10° C.
S7-200 Data Sheets
A
A-13S7-200 Programmable Controller System Manual C79000–G7076–C230–02
1L 0.0 0.1 0.2 2L 0.3 0.4 0.5 N L1 85–264VAC
N 0.0 0.1 0.2 0.3 0.4 0.5 0.6 M L+0.7
Outputs (20 VAC to 264 VAC) Power supply
Inputs (79 VAC to 135 VAC)
24 VDC power for input sensorsor expansion modules (180 mA)
10 Ω0.0068 µF
275V MOV
0.15 µF 470 KΩ
390 Ω
ACOUTPUTS
DCSENSORSUPPLY
AC 120V INPUTS
3.3 KΩNote: Actual component values may vary.
Figure A-5 Connector Terminal Identification for CPU 212 AC/AC/AC
S7-200 Data Sheets
A
A-14S7-200 Programmable Controller System Manual
C79000–G7076–C230–02
A.6 CPU 212 AC Power Supply, Sourcing DC Inputs, Relay Outputs
Order Number: 6ES7 212–1BA10–0XB0
General Features
Physical size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)
Weight 0.4 kg (0.9 lbs.)
Power dissipation 6 W
User program size/storage 512 words/EEPROM
User data size/storageData retention
512 words/RAM50 hr typical(8 hr minimum at 40° C)
Local I/O1 8 inputs/6 outputs
Maximum number ofexpansion modules
2
Digital I/O supported 64 inputs/64 outputs
Analog I/O supported 16 inputs/16 outputs
Boolean execution speed 1.2 µs/instruction
Internal memory bits 128
Timers 64 timers
Counters 64 counters
High-speed counters 1 software (2 KHz max.)
Analog adjustments 1
Standards compliance UL 508 CSA C22.2 142FM Class I, Division 2VDE 0160 compliantCE compliant
Output Points
Output type Relay, dry contact
Voltage range 5 to 30 VDC/250 VAC
Maximum load current 2 A /point, 6 A/common
Overcurrent surge 7 A with contacts closed
Isolation resistance 100 M minimum (new)
Switching delay 10 ms maximum
Lifetime 10,000,000 mechanical100,000 with rated load
Contact resistance 200 m maximum (new)
Isolationcoil to contactcontact to contact(between open contacts)
1500 VAC, 1 min750 VAC, 1 min
Short circuit protection None
Input Points
Type Sourcing
Input voltage range 15 to 30 VDC, 35 VDC for 500 ms
ON state 4 mA minimum
OFF state 1 mA maximum
Response timeI0.0 to I0.7 0.3 ms maximum
Optical isolation 500 VAC, 1 min
Power Supply
Voltage/frequency range 85 to 264 VAC at 47 to 63 Hz
Input current 4 VA typical, CPU only50 VA maximum load
Holdup time 20 ms minimum from 110 VAC
Inrush current 20 A peak at 264 VAC
Fusing (non-replaceable) 2 A, 250 V, slow blow
5 VDC available current 260 mA for CPU340 mA for expansion I/O
Isolated Yes. Transformer, 1500 VAC,1 min
DC Sensor Supply
Voltage range 20.4 to 28.8 VDC
Ripple/noise (<10MHz) 1 V peak-to-peak maximum
24 VDC available currentshort circuit current limit
180 mA< 600 mA
Isolated No
1 The CPU reserves 8 process-image input and 8 process-image output register points for local I/O.
S7-200 Data Sheets
A
A-15S7-200 Programmable Controller System Manual C79000–G7076–C230–02
1L 0.0 0.1 0.2 2L 0.3 0.4 0.5 N L1 85–264VAC
1L 0.0 0.1 0.2 0.3 0.4 0.5 0.6 M L+0.7
Outputs (30 VDC/250 VAC) Power supply
Inputs (15 VDC to 30 VDC)
24 VDC power for input sensorsor expansion modules (180 mA)
2L
+
RELAYOUTPUTS
DCSENSORSUPPLY
DC 24VINPUTS
3.3 KΩ470 Ω
N (–)
L (+)
Note: 1. Actual component values may vary.2. Connect AC line to the L terminal.3. Input circuit ground is optional.
N (–)
L (+)
+
Figure A-6 Connector Terminal Identification for CPU 212 AC/Sourcing DC/Relay
S7-200 Data Sheets
A
A-16S7-200 Programmable Controller System Manual
C79000–G7076–C230–02
A.7 CPU 212 AC Power Supply, 24 VAC Inputs, AC Outputs
Order Number: 6ES7 212–1DA01–0XB0
General Features
Physical size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)
Weight 0.4 kg (0.9 lbs.)
Power dissipation 7 W at 2.5 A load
User program size/storage 512 words/EEPROM
User sata size/storageData retention
512 words/RAM50 hr typical(8 hr minimum at 40° C)
Local I/O1 8 inputs/6 outputs
Maximum number ofexpansion modules
2
Digital I/O supported 64 inputs/64 outputs
Analog I/O supported 16 inputs/16 outputs
Boolean execution speed 1.2 µs/instruction
Internal memory bits 128
Timers 64 timers
Counters 64 counters
High-speed counters 1 software (50 Hz max.)
Analog adjustments 1
Standards compliance UL 508 CSA C22.2 142FM Class I, Division 2CE compliant
Output Points
Output type Triac, zero-crossing
Voltage/frequency range 20 to 264 VAC, 47 to 63 Hz
Load circuit power factor 0.3 to 1.0
Inductive load clamping MOV 275 V working voltage
Maximum load currentper single pointper 2 adjacent pointsall points total
0 to 40° C 55° C 2
1.20 A 1.00 A1.50 A 1.25 A3.50 A 2.50 A
Minimum load current 30 mA
Leakage current 1.5 mA, 120 VAC/2.0 mA,240 VAC
Output Points (continued)
Switching delay 1/2 cycle
Surge current 30 A peak, 1 cycle / 10 A peak, 5 cycle
Voltage drop 1.5 V maximum at maximumcurrent
Optical isolation 1500 VAC, 1 min
Short circuit protection None
Input Points
Input type (IEC 1131–2) Type 1 sinking
ON state range 15 to 30 VAC, 47 to 63 Hz, 4 mA minimum
ON state nominal 24 VAC, 60 Hz, 7 mA
OFF state maximum 5 VAC, 1 mA
Response time 10 ms typical, 15 ms max.
Optical isolation 1500 VAC, 1 min
Power Supply
Voltage/frequency range 85 to 264 VAC at 47 to 63 Hz
Input current 4 VA typical, CPU only50 VA maximum load
Holdup time 20 ms minimum from 110 VAC
Inrush current 20 A peak at 264 VAC
Fusing (non-replaceable) 2 A, 250 V, slow blow
5 VDC current 320 mA for CPU280 mA for expansion I/O
Isolated Yes. Transformer, 1500 VAC,1 min
DC Sensor Supply
Voltage range 20.4 to 28.8 VDC
Ripple/noise (<10MHz) 1 V peak-to-peak maximum
24 VDC available current 180 mA
Short circuit current limit < 600 mA
Isolated No
1 The CPU reserves 8 process-image input and 8 process-image output register points for local I/O.2 Linear derate 40 to 55° C. Vertical mount derate 10° C
S7-200 Data Sheets
A
A-17S7-200 Programmable Controller System Manual C79000–G7076–C230–02
1L 0.0 0.1 0.2 2L 0.3 0.4 0.5 N L1 85–264VAC
N 0.0 0.1 0.2 0.3 0.4 0.5 0.6 M L+0.7
Outputs (20 VAC to 264 VAC) Power supply
Inputs (15 VAC to 30 VAC)
24 VDC power for input sensorsor expansion modules (180 mA)
10 Ω0.0068 µF
275V MOV
390 Ω
ACOUTPUTS
DCSENSORSUPPLY
AC 24VINPUTS
3.3 KΩ
Note: Actual component values may vary.
Figure A-7 Connector Terminal Identification for CPU 212 AC/AC/AC
S7-200 Data Sheets
A
A-18S7-200 Programmable Controller System Manual
C79000–G7076–C230–02
A.8 CPU 212 AC Power Supply, AC Inputs, Relay Outputs
Order Number: 6ES7 212–1GA01–0XB0
General Features
Physical Size (L x W x D) 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.)
Weight 0.4 kg (0.9 lbs.)
Power Dissipation 6 W
User program size/storage 512 Words / EEPROM
User data size/storageData retention
512 Words / RAM50 hr typical(8 hr minimum at 40° C)
Local I/O1 8 Inputs / 6 Outputs
Maximum Number ofExpansion Modules
2
Digital I/O Supported 64 Inputs / 64 Outputs
Analog I/O Supported 16 Inputs / 16 Outputs
Boolean Execution Speed 1.2 µs/instruction
Internal Memory Bits 128
Timers 64 Timers
Counters 64 Counters
High-speed counters 1 Software (2 KHz max.)
Analog Adjustments 1
Standards Compliance UL 508 CSA C22.2 142FM Class I, Division 2VDE 0160 compliantCE compliant
Output Points
Output Type Relay, dry contact
Voltage Range 5 to 30 VDC / 250 VAC
Maximum Load Current 2 A/point
Overcurrent Surge 7 A with contacts closed
Isolation Resistance 100 M minimum (new)
Switching Delay 10 ms maximum
Lifetime 10,000,000 Mechanical100,000 with Rated Load
Contact Resistance 200 m maximum (new)
IsolationCoil to ContactContact to Contact
1500 VAC, 1 minute1000 VAC, 1 minute
Short Circuit Protection None
Input Points
Input Type (IEC 1131–2) Type 1 Sinking
ON State Range 79 to 135 VAC, 47 to 63 Hz.4 mA minimum
ON State Nominal 120 VAC, 60 Hz, 7mA
OFF State Maximum 20 VAC, 1 mA
Response Time 10 ms typical, 15 ms max.
Optical Isolation 1500 VAC, 1 minute
Power Supply
Voltage/frequency Range 85 to 264 VAC at 47 to 63 Hz
Input Current 4 VA typical, CPU only50 VA maximum load
Hold Up Time 20 ms minimum from 110 VAC
Inrush Current 20 A peak at 264 VAC
Fusing (non-replaceable) 2 A, 250 V, Slow Blow
5 VDC Current 260 mA for CPU340 mA for expansion I/O
Isolated Yes. Transformer, 1500 VAC,1 minute
DC Sensor Supply
Voltage Range 20.4 to 28.8 VDC
Ripple/noise (<10Mhz) 1 V peak-to-peak maximum
24 VDC Available CurrentShort Circuit Current Limit
180 mA< 600 mA
Isolated No
1 The CPU reserves 8 input and 8 output image register points for local I/O.
S7-200 Data Sheets
A
A-19S7-200 Programmable Controller System Manual C79000–G7076–C230–02
OUTPUTS 1L 0.0 0.1 0.2 2L 0.3 0.4 0.5 N L1 85–264VAC
Outputs (30 VDC / 250 VAC) Power Supply
RELAY
N (–)
L (+)
Note:1. Actual component values may vary.2. Connect AC line to the L terminal.
N (–)
L (+)
N 0.0 0.1 0.2 0.3 0.4 0.5 0.6 M L+0.7
Inputs (79 to 135 VAC)
24 VDC Power for Input Sensorsor Expansion Modules (180 mA)
0.0068 µF
0.15 µF 470K ohms
390 ohms
DCSENSORSUPPLY
AC 120V INPUTS
3.3K ohms
Figure A-8 Connector Terminal Identification for CPU 212 AC/AC/Relay
S7-200 Data Sheets