SpecificationS
-
7/28/2019 Capital Gate_SPEC_APR2012.pdf
2/8
CAPITAL GATE CAPITAL GATE 3
Summary
Specification
STRUCTURAL
Design Loads Oce area superimposed Dead Load = 2.4kPa,
Live Load = 5.0kPa Cladding.
Fully unitised acade curtain walling system is made
up rom 2 storey height diamonds which make up
the ree orm acade comprising double glazed
actory sealed triangular glass units and steel
section rames.
Dimensional Inormation Floor to foor height: 4.00m (4,000mm).
Floor to ceiling height: 2.502.75m
(2,5002,750mm).
Ceiling to void average: 0.80m (800mm).
Raised foor height: 0.15m (150mm).
All dimensions are approximate
ELECTRICAL SERVICES
General All common area lighting, power, two escape
staircases and elevators are ed rom the landlords
distribution network. One passenger elevator is
backed up by standby generator power, or use incase o emergency. All lie saety systems and
essential services are backed up by the standby
generator. In addition, some o the lie saety
system and essential system outlets are backed up
by uninterrupted power supply (UPS) to ensure
availability o power at all times.
Power Supply The building is supplied at 11KV rom an Abu Dhabi
Distribution Company (ADDC) primary substation
and network to basement sub-station.
Power is transormed to the operating voltage o
415 volts by ve, 1,500KVA transormers installed in
the substation. Main distribution boards (MDBs) are
ed rom the transormers installed in the basement
low voltage (LV) switchgear room, adjacent to the
substation. MDBs distribute power to the
development, through cable routes, rising bus bars,
sub-main distribution boards (SMDBs) and
distribution boards (DBs).
Power Feed Oce Areas are provided with 63 Amp three phase
power supply or smaller units and 100 Amp three
phase power supply or larger units, locally or each
oce unit with a local Isolator (based on three
oces per foor). These are ed rom the sub main
distribution boards in the electrical room (each
foor), through a KWH meter provided in the meter
room. Each tenant will provide a distribution board
as per their load requirements and connect to the
local Isolator provided by the Landlord.
Tenant supplied distribution boards are as per
ADDC/Abu Dhabi Water and Electricity Authority
(ADWEA) regulations. Tenants will obtain the
necessary approvals rom the authorities or their
layouts and power distribution requirements. KWH
meters shall be provided by ADDC/ADWEA
Authorities ater tenant t-out completion and
inspections o the electrical installation are carried
out by ADDC/ADWEA.
No separate provision or power backed by standby
generator has been made or the tenant areas
except the emergency lighting.
MECHANICAL SERVICES
HVAC System
General Fresh air ventilation, an coil unit (FCU) systems,
resh air handling units (AHUs), smoke extract
ventilation system, variable volume air-conditioning
system, and chilled water (CW) system are provided.
The cooling requirement is served by TABREED
district chilled water network, acilitated by an
energy transer station at the basement and Level 1
o the building as the primary supply o chilled
water network consisting o two units o rated heat
exchangers. The resulting or secondary chilled water
lines will be metered as being conveyed by our
rated pumps serving AHUs and FCUs mounted
at all foors o the building.
Oce Areas The oce areas including basement, ground and
mezzanine are served by centralised AHUs (2 Nos.)
located at Level 1.
The oce areas are provided with the ollowing
service stub-outs, including supply and return air
ducts and metered chilled water supply and return
lines (provisions only inside the oce areas), that
are interaced with building management system
(BMS) control. FCUs or each oce area will be
provided by the tenant.
The cooling criteria is based on the ollowing data:
A) Average year round summer and winter design
conditions in oces are to be maintained at
23C and 21C 1C, with relative humidity set
at 50% 5% and; B) The outdoor ventilation rate
is 8.0 l/s/person with approx. 812 air changes per
hour (ACH).
PLUMBING AND DRAINAGE
General Sanitary wares, water tanks, domestic water
systems, soil/waste/vent and overfows, irrigation
system and rainwater system have been included.
The main source o the buildings potable water,
rom the ADWEA distribution line, is stored in a tank
at the basement foor, which undergoes a ltration
system. The concrete water tank is a double
compartment type, allocated or domestic water,
re protection system, and irrigation source.
Aside rom preliminary ltration, the domestic water
passes through a proven anti-legionella chemical
dosing system. Water tanks are provided at
basement, Level 1 and Level 17, with compliance
to ADDC requirements o minimum 2 days
consumption storage.
The plumbing system consists o metered cold
water (CW) network, lter cooled cold water supply
(FCCWS) and centralised hot water (HW)
distribution. The HW network or the oce toilets,
hotel and dining area is enhanced with heat tracing
system or ast acquisition o hot water and uniorm
water temperature supply o 55C.
The drainage system is laid at all areas where
water service is available and tapped to the main
drainage point.
Oce Area Separate toilets or male and emale are present
on each oce foor.
Each oce area is provided with: A) Cold water
stub-out with meter provision to be applied to
ADWEA when occupied and; B) Soil, waste,
and vent pipes or uture pantry or toilet provisions.
FIREFIGHTING
General Sprinkler installation, external hydrant system,
manual re protection system o re extinguishing,
gas re suppression system, re alarms, and re
detectors have been included.
The building consists o manual and automatic
reghting equipment or complete building
protection. The re sprinkler system is entirely
independent rom the hydrant network as required
by Abu Dhabi Civil Deense Authority (ADCDA).
All foors are provided with accepted zonal re
sprinkler suppression with individual zonal control
valve. Each foor has three re hose cabinets (FHC)
at the common area, which can accommodate up
to 30m standard radius o service. All electrical
rooms are supplied with either automatic re
extinguishers or FM 200 or oam type re
suppression systems.
Oce Area The oce areas are tted with the ollowing:
A) Upright sprinkler heads or reghting and;
B) Recessed sprinkler stub outs.
OTHER SERVICES
Fire Alarm and Public Address
Evacuation Systems Smoke detectors have been provided within each
oce area. Smoke detectors are provided with
approx. two metres o additional cable or lowering
in to the ceilings. Voice evacuation speakers
are provided within each oce space, or
announcements.
Emergency Lighting Sucient emergency lights are provided with
additional length o cable to lower in to the ceilings,
together with one wall mounted type exit light or
installing above the entrance/exit door or each
oce space. All the emergency and exit lights are
backed up by the central battery system, which is
backed up by the standby generator.
Telecommunication State-o-the-art passive connectivity solutions
allow tenants to deploy a ull range o
telecommunications services rom the UAEs
leading service providers.
Optical bre connections with up to 10G capacity
are available to tenants or connections to
service providers.
Tenants must install their own I.T. inrastructure in
their oce areas. Tenants will be required to:
Ins tall and maintain the structured cabling and
network inrastructure within their leased space.
Ins tall and manage server room/data centre as
required or their business.
Ins tall and manage their own back oce, voice
and application server systems.
Obtain services rom the telecommunications
service providers directly.
Additional services, including voice, data,
high speed data links, video and television access,
may be requested rom ADNEC, although tenants
are advised that these may be subject to leasing
agreements and availability.Security
Security system has been provided with 24 hour
physical security presence incorporating CCTV
surveillance o the main entrances, elevator lobbies
and external areas. Tenants will use security access
cards in conjunction with proximity readers to
access the security barriers and at each o the main
entrance points.
Elevators Passenger Three passenger elevators are provided or oce
foors, serving Ground foor to Level 16. Each
elevator is 1,600kg (21 person) capacity. One
elevator is backed up by generator power or use in
case o mains power ailure.
Elevators Service/Goods One oce foor service elevator o 1,600kg capacity
is provided.
Ceilings All suspended ceilings incorporating plasterboard
and/or ceiling tiles is by the tenant.
Floors Fully accessible raised access fooring (600 x 600
tiles) with an overall foor depth o 150mm allowing
110mm clear void may be provided. (Currently
under review).
Walls Unplastered block and steel columns with
cementitious reproong to be clad or paintedby the tenant.
Floor Power All power reticulation, foor boxes, general purpose
outlets and connections to DBs are by the tenant.
Lighting All lighting and connections to DBs are by
the tenant.
Toilet and Pantry High quality nishes including tiling to foor and
walls, ceilings, recessed lighting, ablution acilities
and marble vanity tops are provided.
hell and Core Commercial Ofce Space
evel 2 to 16)
-
7/28/2019 Capital Gate_SPEC_APR2012.pdf
3/8
5capitaL GatecapitaL Gate
ProfiteroleCaf
Lobby
Ground fLoor pLan
AreasLobby
Core Areas
Lits
ScheduLe of areaS
HyattHotel
oFFICe
-
7/28/2019 Capital Gate_SPEC_APR2012.pdf
4/8
CAPITAL GATE CAPITAL GATE 354
fLoor pLanS
eight
60m / 35 storeys
ncline
8 degrees
irection
Westward (East to West)
verhang o the tower
om the base
3m
he Cardinal acade is 51% more
cient than a standard typical
acade in restricting solar heat
o the building. This reduces the
nergy consumption by HVAC
ystem by 15%.
oundation piles
90
epth o piles
030m
tructural steel
n Capital Gate
3,200 tonnes
iagrid systems
external 1 internal
iagrid nodes
02 external 120 internal
riangular glass panes
n acade
2,500
iamond shaped sections
n acade
20
otal built up area
3,100 sq m
otal oce area
4,396 sq m
otal hotel area
5,050 sq m
key
conStruction
factS
ces available rom
531,056 sq m
rovision or 2.52.75 foor
o ceiling height
50mm raised foor
wo tted pantries
nd WCs per foor
ecure access to each foor
edicated covered parking
:40 sq m
key LeaSinG
factS
Level 12Floor area:
1,040 sq m 11,194 sq ft
Level 13Floor area:
1,047 sq m 11,269 sq ft
Level 14Floor area:
1,025 sq m 11,033 sq ft
Level 07Floor area:
1,033 sq m 11,119 sq ft
Level 08Floor area:
1,025 sq m 11,033 sq ft
Level 09Floor area:
1,040 sq m 11,194 sq ft
Level 03Floor area:
1,008 sq m 10,850 sq ft
Level 02Floor area:
994 sq m 10,699 sq ft
Level 04Floor area:
1,012 sq m 10,893 sq ft
Level 16Floor area:
353 sq m 3,800 sq ft
Level 15Floor area:
1,029 sq m 11,076 sq ft
Level 11Floor area:
1,056 sq m 11,366 sq ft
Level 10Floor area:
1,041 sq m 11,205 sq ft
Level 06Floor area:
1,024 sq m 11,022 sq ft
Level 05Floor area:
1,027 sq m 11,054 sq ft
-
7/28/2019 Capital Gate_SPEC_APR2012.pdf
5/8
CAPITAL GATE CAPITAL GATE 376
Tea/Coffee
Prive
Business Bar/Lounge
Meeting Room 4
Meeting Room 3
Meeting Room 2
Meeting Room 1
Footb
ridg
eaccess
toofcecarp
ark
fLoor pLan LeveL 02
reasyatt
ore Areas
ts
fLoor pLan meZZanine LeveL
Floor Area
994 SQ M
10,699 SQ FT
AreasOce Space
Core Areas
Utilities
Lits
-
7/28/2019 Capital Gate_SPEC_APR2012.pdf
6/8
CAPITAL GATE CAPITAL GATE 398
fLoor pLan LeveL 14fLoor pLan LeveL 07 SpLit
oor Area
033 SQ M
1,119 SQ FT
reasce Space
ore Areas
tilities
ts
Floor Area
1,025 SQ M
11,033 SQ FT
AreasOce Space
Core Areas
Utilities
Lits
-
7/28/2019 Capital Gate_SPEC_APR2012.pdf
7/8
CAPITAL GATE CAPITAL GATE 410
CEO
Manager 01
Manager 02
Manager 03
Workstations(34 PAX)
Workstations(6 PAX)
Workstations18 PAX
Meeting(6 PAX)
Boardroom(14 PAX)
ServerRoom
Fax/copyarea
Fax/copyarea
FoldablePartition
Pantry/Breakout
Seating
Reception/Waiting
Meeting(4 PAX)
PA (2 PAX)
Boardroom(18 PAX)
InformalMeeting
CEO
Manager 01
Manager 02
Manager 03
Workstations24 PAX
Workstations36 PAX
Workstations12 PAX
Meeting(4 PAX)
Server Room
Fax/copy
Fax/copyarea
Pantry/Breakout
StoreRoom
Reception/Waiting
Meeting(6 PAX)
LiftLobby
Space pLan LeveL 07 Space pLan LeveL 07
oor Area
033 SQ M
1,119 SQ FT
reasce Space
ore Areas
tilities
ts
Floor Area
1,033 SQ M
11,119 SQ FT
AreasOce Space
Core Areas
Utilities
Lits
-
7/28/2019 Capital Gate_SPEC_APR2012.pdf
8/8