calibracion_modulos analogicos plc

Upload: javucho26

Post on 05-Jul-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/16/2019 Calibracion_Modulos Analogicos PLC

    1/4

    This product is the latest output from Allen Bradley. Level can use to industrial medium and largescale. Even today Rockwell Automation has made equivalent PlantPA system is even a!le tocompete with the relia!ility "#$ using the #ontrolLogi% as the main constituent component.$oftware used to design& download& and upload programs that R$Logi%'(((. )t is !etter you knowhow to cali!rate the #ontrolLogi% Analog )*+ ,odules to ensure the !est performance controlsystem. This guidance as !elow-

    Calibrating an Input Module and an Output Module ProcessThere are two things you have to do for #ontrolLogi% cali!ration process&- the cali!ration module for analog input modules and output modules. The important difference of those cali!ration processare-

    • The cali!ration process input modules using the parameters of current& voltage& or ohmscali!rators.

    • The cali!ration process output module using the tools of digital multimeter ",,/ tomeasure the signal modules sent. The position signal is sent to the outside of the module. Thisprocess requires cali!ration instruments with specific ranges as recommended in the ta!le list thecali!ration module.

    How can we calibrate with Either Program or Run Mode?The cali!ration process can !e carried out outside the standard program R$Logi%'(((. 0ou can

    use other programs on the condition that you must connect online and using precision resistors.+ne of the recommended resistors is 1RL Electronics 2 '34A525R(T a (.(56 5.( +hm * 478 +hm'34A52478R(T a (.(56. "o not use components that are !elow standard& for e%ample 58'92):59module with a voltage cali!rator of greater than ;*2 5'(

  • 8/16/2019 Calibracion_Modulos Analogicos PLC

    2/4

    )nput cali!ration process module needs to !e done to ensure that the accuracy of data input can !eprocessed properly. The process is relatively comple% !ecause it includes three main parametersthat require specific cali!ration range. The process includes-

    • The process of cali!rating the 58'92):59 or 58'92):7 ,odules• The process of cali!rating the 58'92)R9) ,odules• The process of cali!rating the 58'92)T9) or 58'92)T9)> ,odules

    ,ore details- http-**literature.rockwellautomation.com*idc*groups*literature*documents*um*58'92um(([email protected]

    Calibrating the 175 !I"1 or 175 !I"# ModulesThe cali!ration process !egins with the 58'92):59 or 58'92):7 modules. This cali!ration is used inapplications requiring voltage or current !y using a four2parameter input voltage ranges-25( ... 5(=( ... '=( ... 5(=( ... >( mA

    $he calibration process the 175 !IR I Modules#ali!ration of the 58'92)R9) is not associated with voltage or current !ut used to cali!rate thechannels in ohms using two precision resistors. The first resistor used for low reference cali!rationand the other resistor is used for high reference cali!ration. This cali!ration using the data range 5..478.

  • 8/16/2019 Calibracion_Modulos Analogicos PLC

    3/4

    Process Calibrating the 175 !I$ I or 175 !I$ I% Modules#ali!rating the 58'92)T9) or 58'92)T9)> require input voltage in millivolts scale with a range of 25> ...; 3( m= range or 25> ... ; 87 m= range. )n normal conditions typically use an input voltage range of 25> ... ; 3( m=& whereas for certain conditions can use a higher voltage range again.

    $he calibration process Output Modules#ali!ration process aims to measure the signal from the module which includes two cali!rationprocess& namely-

    Current Meter CalibrationsThis cali!ration process is using R$Logi% '((( software. R$Logi% '((( is used to determinespecific levels of current. ,ake sure all the data output is well documented to avoid anyinaccuracies.

    &oltage Meter CalibrationsThe cali!ration process is in principle the same as the current meter cali!ration& using the 58'92+:4& 58'92+:7& and 58'92+:9=) modules. Also make sure the output data when the systemcali!ration process goes well documented.