CALCULO DE ALUMBRADO (OFICINA)DATOS
ANCHO (a) 3LARGO (b) 4ALTURA (h) 3TECHO BLANCOPARED BLANCOPISO CREMACOEFICIENTE DE MANTENIMIENTO (Mu) 0.7COEFICIENTE DE UTILIZACION (Mm) 0.49TIPO DE ILUMINACION DIRECTALUXES RECOMENDADOS € 110TIPO DE LUMINARIA FLUORESENTE (TUBO LONGITUDINAL)POTENCIA (w) 65ALIMENTACION (v) 127
1800FLUJO DE LUMINARIA (ϴL)
![Page 2: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/2.jpg)
CALCULO FORMULA RESULTADOINDICE DEL LOCAL (K) a*b/h(a+b) 0.571428571
a*b*E/Mu*Mm 3848.396501NUMERO DE LAMPARAS (NL) 2.137998056 3FLUJO TOTAL (ϴt)
ϴt/ϴL
![Page 3: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/3.jpg)
CALCULO DE ALUMBRADO (ALMACEN)DATOS
ANCHO (a) 3LARGO (b) 4ALTURA (h) 3TECHO BLANCOPARED BLANCOPISO CREMACOEFICIENTE DE MANTENIMIENTO (Mu) 0.7COEFICIENTE DE UTILIZACION (Mm) 0.49TIPO DE ILUMINACION DIRECTALUXES RECOMENDADOS € 32TIPO DE LUMINARIA FLUORESENTE (TUBO LONGITUDINAL)POTENCIA (w) 65ALIMENTACION (v) 127
1800FLUJO DE LUMINARIA (ϴL)
![Page 4: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/4.jpg)
CALCULO FORMULA RESULTADOINDICE DEL LOCAL (K) a*b/h(a+b) 0.57142857
a*b*E/Mu*Mm 1119.53353NUMERO DE LAMPARAS (NL) 0.62196307 1FLUJO TOTAL (ϴt)
ϴt/ϴL
![Page 5: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/5.jpg)
CALCULO DE ALUMBRADO (AREA DE PRUEBAS)DATOS
ANCHO (a) 3LARGO (b) 8ALTURA (h) 3TECHO BLANCOPARED BLANCOPISO CREMACOEFICIENTE DE MANTENIMIENTO (Mu) 0.7COEFICIENTE DE UTILIZACION (Mm) 0.49TIPO DE ILUMINACION DIRECTALUXES RECOMENDADOS € 110TIPO DE LUMINARIA FLUORESENTE (TUBO LONGITUDINAL)POTENCIA (w) 65ALIMENTACION (v) 127
1800FLUJO DE LUMINARIA (ϴL)
![Page 6: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/6.jpg)
CALCULO FORMULA RESULTADOINDICE DEL LOCAL (K) a*b/h(a+b) 0.72727273
a*b*E/Mu*Mm 7696.793NUMERO DE LAMPARAS (NL) 4.27599611 5FLUJO TOTAL (ϴt)
ϴt/ϴL
![Page 7: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/7.jpg)
CALCULO DE ALUMBRADO (AREA DE DESARMADO)DATOS
ANCHO (a) 3LARGO (b) 8ALTURA (h) 3TECHO GRISPARED GRISPISO CONCRETOCOEFICIENTE DE MANTENIMIENTO (Mu) 0.6COEFICIENTE DE UTILIZACION (Mm) 0.38TIPO DE ILUMINACION DIRECTALUXES RECOMENDADOS € 80TIPO DE LUMINARIA FLUORESENTE (TUBO LONGITUDINAL)POTENCIA (w) 65ALIMENTACION (v) 127
1800FLUJO DE LUMINARIA (ϴL)
![Page 8: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/8.jpg)
CALCULO FORMULA RESULTADOINDICE DEL LOCAL (K) a*b/h(a+b) 0.72727273
a*b*E/Mu*Mm 8421.05263NUMERO DE LAMPARAS (NL) 4.67836257 5FLUJO TOTAL (ϴt)
ϴt/ϴL
![Page 9: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/9.jpg)
CALCULO DE ALUMBRADO (AREA DE EMBOBINADO)DATOS
ANCHO (a) 6LARGO (b) 9ALTURA (h) 3TECHO GRISPARED GRISPISO CONCRETOCOEFICIENTE DE MANTENIMIENTO (Mu) 0.6COEFICIENTE DE UTILIZACION (Mm) 0.44TIPO DE ILUMINACION DIRECTALUXES RECOMENDADOS € 80TIPO DE LUMINARIA FLUORESENTE (TUBO LONGITUDINAL)POTENCIA (w) 65ALIMENTACION (v) 127
1800FLUJO DE LUMINARIA (ϴL)
![Page 10: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/10.jpg)
CALCULO FORMULA RESULTADOINDICE DEL LOCAL (K) a*b/h(a+b) 1.2
a*b*E/Mu*Mm 16363.63636NUMERO DE LAMPARAS (NL) 9.090909091 10FLUJO TOTAL (ϴt)
ϴt/ϴL
![Page 11: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/11.jpg)
CALCULO DE ALUMBRADO (AREA DE HORNOS)DATOS
ANCHO (a) 4LARGO (b) 8ALTURA (h) 3TECHO NEGRAPARED NEGRAPISO CONCRETOCOEFICIENTE DE MANTENIMIENTO (Mu) 0.6COEFICIENTE DE UTILIZACION (Mm) 0.31TIPO DE ILUMINACION DIRECTALUXES RECOMENDADOS € 180TIPO DE LUMINARIA FLUORESENTE (TUBO LONGITUDINAL)POTENCIA (w) 65ALIMENTACION (v) 127
1800FLUJO DE LUMINARIA (ϴL)
![Page 12: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/12.jpg)
CALCULO FORMULA RESULTADOINDICE DEL LOCAL (K) a*b/h(a+b) 0.88888889
a*b*E/Mu*Mm 30967.7419NUMERO DE LAMPARAS (NL) 17.2043011 18FLUJO TOTAL (ϴt)
ϴt/ϴL
![Page 13: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/13.jpg)
CALCULO DE ALUMBRADO (AREA DE TORNOS)DATOS
ANCHO (a) 5LARGO (b) 8ALTURA (h) 3TECHO GRISPARED GRISPISO CONCRETOCOEFICIENTE DE MANTENIMIENTO (Mu) 0.7COEFICIENTE DE UTILIZACION (Mm) 0.42TIPO DE ILUMINACION DIRECTALUXES RECOMENDADOS € 80TIPO DE LUMINARIA FLUORESENTE (TUBO LONGITUDINAL)POTENCIA (w) 65ALIMENTACION (v) 127
1800FLUJO DE LUMINARIA (ϴL)
![Page 14: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/14.jpg)
CALCULO FORMULA RESULTADOINDICE DEL LOCAL (K) a*b/h(a+b) 1.02564103
a*b*E/Mu*Mm 10884.3537NUMERO DE LAMPARAS (NL) 6.04686319 6FLUJO TOTAL (ϴt)
ϴt/ϴL
![Page 15: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/15.jpg)
CALCULO DE ALUMBRADO (AREA DE TORNOS)DATOS
ANCHO (a) 5LARGO (b) 5ALTURA (h) 3TECHO GRISPARED GRISPISO CONCRETOCOEFICIENTE DE MANTENIMIENTO (Mu) 0.7COEFICIENTE DE UTILIZACION (Mm) 0.36TIPO DE ILUMINACION DIRECTALUXES RECOMENDADOS € 80TIPO DE LUMINARIA FLUORESENTE (TUBO LONGITUDINAL)POTENCIA (w) 65ALIMENTACION (v) 127
1800FLUJO DE LUMINARIA (ϴL)
![Page 16: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/16.jpg)
CALCULO FORMULA RESULTADOINDICE DEL LOCAL (K) a*b/h(a+b) 0.83333333
a*b*E/Mu*Mm 7936.50794NUMERO DE LAMPARAS (NL) 4.40917108 5FLUJO TOTAL (ϴt)
ϴt/ϴL
![Page 17: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/17.jpg)
CALCULO DE ALUMBRADO (AREA PRODUCCION TERMINADA)DATOS
ANCHO (a) 4LARGO (b) 5ALTURA (h) 3TECHO BLANCOPARED BLANCOPISO PASTELCOEFICIENTE DE MANTENIMIENTO (Mu) 0.75COEFICIENTE DE UTILIZACION (Mm) 0.36TIPO DE ILUMINACION DIRECTALUXES RECOMENDADOS € 90TIPO DE LUMINARIA FLUORESENTE (TUBO LONGITUDINAL)POTENCIA (w) 65ALIMENTACION (v) 127
1800FLUJO DE LUMINARIA (ϴL)
![Page 18: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/18.jpg)
CALCULO FORMULA RESULTADOINDICE DEL LOCAL (K) a*b/h(a+b) 0.74074074
a*b*E/Mu*Mm 6666.66667NUMERO DE LAMPARAS (NL) 3.7037037 4FLUJO TOTAL (ϴt)
ϴt/ϴL
![Page 19: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/19.jpg)
CALCULO DE ALUMBRADO (ENTRADA PRINCIPAL)DATOS
ANCHO (a) 5LARGO (b) 9ALTURA (h) 3TECHO BLANCOPARED BLANCOPISO PASTELCOEFICIENTE DE MANTENIMIENTO (Mu) 0.8COEFICIENTE DE UTILIZACION (Mm) 0.49TIPO DE ILUMINACION DIRECTALUXES RECOMENDADOS € 90TIPO DE LUMINARIA FLUORESENTE (TUBO LONGITUDINAL)POTENCIA (w) 65ALIMENTACION (v) 127
1800FLUJO DE LUMINARIA (ϴL)
![Page 20: CALCULO DE ALUMBRADO](https://reader036.vdocuments.site/reader036/viewer/2022082318/53f78695dab5caf01c8b462d/html5/thumbnails/20.jpg)
CALCULO FORMULA RESULTADOINDICE DEL LOCAL (K) a*b/h(a+b) 1.07142857
a*b*E/Mu*Mm 10331.6327NUMERO DE LAMPARAS (NL) 5.73979592 6FLUJO TOTAL (ϴt)
ϴt/ϴL