    1 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    ...Your Best Solution

    for three methods of protection: Ex d/Ex e/Ex tb

    TECHNICAL DATA SHEETNEW PRODUCTRev. 3 05/2014

    New Cable Glands REV and REVD series

    for ATEX and IECEx world

  • 5/19/2018 Cable Glands REV and REVD Series

    2/20

    2 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    1. The symbol CE means "Conformit Europenne" and it shows that the item is complying the essentialrequirements of the Directives on safety, public health, consumer protection, ecc

    2. N of the registered body (CESI) responsible for production monitoring in accordance with Directive94/9/CE ATEX

    3. Denotes the equipment with explosion protection

    4. Group II (surface devices)5. Category 2 (suitable for zone 1 and 2 for gas and zone 21 and 22 for dust)6. Gas and Dust (this material can be installed both in presence of gas and dust)7. ATEX Certification number8. Protection method (Ex d: flame-proof, Ex e: increased safety, IIC: GAS group, Gb: Epl Equipment

    protection level, Ex tb: dusts protection, IIIC: dusts group)9. IP protection10. IECEx Certification number

    MARKING REVAND REVDSERIES CABLE GLANDS

    ZONES 1 - 21 - 2 - 22

    AMBIENT TEMPERATURE -40C +110C

    IP PROTECTION IP66/67

    ATEX CERTIFICATION CESI 13 ATEX019X (ELFIT)CESI 13 ATEX 032X (CORTEM)

    IECEx CERTIFICATION IECEx CES 13.0005X (ELFIT)IECEx CES 13.0011X (CORTEM)

    CONFORMITY TO STANDARDS

    ATEX 94/9/CEEN 60079-0:2012; EN60079-1:2007;EN 60079-7:2007; EN 60079-31:2009;EN 60529:1991IEC 60079-0:2011; IEC 60079-1:2007;IEC 60079-7:2006; IEC 60079-31:2008;IEC 60529:2001RoHS standard 2002/95/CE

    OTHER CERTIFICATIONS Russian certification GOST TR CU

    CERTIFICATE DATA AND CONFORMITY TO STANDARDS

    PRODUCT DESCRIPTION REVAND REVDCABLE GLANDS

    The new cable glands of REV and REVDseries are suitable for use in hazardous areas with danger of e-

    xplosion to enable direct insertion of non-armoured cables, REV series cable glands, and of armored ca-

    bles, REVD series cable glands, into explosion-proof junction boxes and/or lighting fixtures, plugs and so-ckets,etc...

  • 5/19/2018 Cable Glands REV and REVD Series

    3/20

    3 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    The new cable glands series has optimally exceeded all the tests currently requi-

    red for the certification of this product. The result is a cable gland of highest per-

    formance in terms of reliability and safety, able to cover a wide range of the main cables on the marked

    such as plaited armoured cables, flat or wire cables with armour thickness from 0 to 2,5 mm.

    REVand REVDseries is more competitive and, at the same time, more powerful than the cable glands of

    the previous series.

    The most important innovation is the use of one sealing ring on the inner and outer sheath of the cable

    and no longer a kit of sealing rings of different diameters. REVseries is constituted by a single sealing ring

    which tightens the incoming cable ensuring the 'Ex d' way of protection. REVDseries has a second sealing

    ring that tightens on the outer sheath of the cable to ensure the IP66/67 degree of protection avoiding the

    ingress of water, moisture, rain and dust. The cable range available for each cable gland is described in

    the following tables.

    A further advantage is the lighter weight and the smaller dimensions, an important detail when theres the

    need to install a large number of cable glands on explosion-proof enclosures.

    The new cable glands REV and REVD series have been designed to replace FL/FG e FAL/FGA series

    cable glands. They are realized in NICKEL-PLATED BRASS, STAINLESS STEEL and GALVANIZED

    STEELfrom 3/8" up to 2 and in NICKEL-PLATED BRASS andSTAINLESS STEELfrom 2 1/2 up to 4".

    This new series includes also REVL, REVDL series special version which can accommodate smaller cable

    diameters than the standard required for each measure. In this way, the use of reductions is avoids.

    The new cable glands of REVFand REVNseries are designed to replace the FGF series (female threaded

    entry) and the FGN series cable glands (male threaded entry) available from 3/8" to 2" sizes and made of

    NICKEL-PLATED BRASS, STAINLESS STEEL and GALVANIZED STEEL. Its also available a water-

    proof series: TEV series for non-armoured cables and TEVDfor armoured cables.

    They are provided with high-tech and high mechanical performance compression rings and gaskets

    with high-temperature resistance.

    Thanks to their structure, they are particularly suitable both in harsh application, such as marine one, and

    places subjected to stress and mechanical shock as often happens in all those places of the heavy in-

    dustry where safety is a top priority.

    The new series has three types of protection 'Ex d', 'Ex e' and 'Ex tb'. It can be also used in Ex i intrinsic

    safety circuits. In this case, the cable glands have a part painted light blue.

    The evolution of the marking has allowed us to create a transparent polyester label which has stood very

    well the various tests of salt corrosion, durability in harsh environments and high temperatures, impact resi-

    stance.

    In order to ensure a greater security and reliability of its cable glands, Elfit, in addition to mandatory certifi-

    cation tests, submits its products to further harsher tests. It evaluates the resistance of its cable glands to a

    traction test without fixing the cable armour and with much higher load values (up

    to an extra 50%) than required by the standard.

  • 5/19/2018 Cable Glands REV and REVD Series

    4/20

    4 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    DETAILS OF REV SERIES CABLE GLANDSFOR UNARMOURED CABLES FROM 3/8 TO2

    CABLE GLAND PARTS

    1. Body2. Sealing ring3. Compression ring in plastic material4. Nut

    1

    23

    4

    ASSEMBLING INSTRUCTIONS

    Step 1 Insert on the cable the nut 4and the compression ring 3

    Step 2 Assembly the body 1 and the sealing ring 2 with the equipment

    Step 3 After inserting the cable into the sealing ring 2 close by tightening the nut 4

    Cable gland properlyassembled

  • 5/19/2018 Cable Glands REV and REVD Series

    5/20

    5 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    MODELS, FEATURES AND DIMENSIONSREV SERIES CABLE GLANDS FOR UNARMOURED CABLES FROM3/8 TO2

    Code

    REV

    Nickel-platedbrass

    Code

    REV

    StainlessSteel

    Code

    REV

    GalvanizedSteel

    Dimensions mm Cable Range mm

    AC M C d min-max

    REV01B REV01S REV01G 3/8" ISO7/1 24 28 44 5 10

    REV1B REV1S REV1G 1/2" ISO7/1 24 28 47 7 12

    REV2B REV2S REV2G 3/4" ISO7/1 32 37 48,5 12 18

    REV3B REV3S REV3G 1" ISO7/1 40 47 59,5 18 24

    REV4B REV4S REV4G 1 1/4 ISO7/1 48 56 60 24 30

    REV5B REV5S REV5G 1 1/2 ISO7/1 53 62 64 30 35

    REV6B REV6S REV6G 2" ISO7/1 63 73 64 35 45REV01NB REV01NS REV01NG 3/8" NPT 24 28 45 5 10

    REV1NB REV1NS REV1NG 1/2" NPT 24 28 49 7 12

    REV2NB REV2NS REV2NG 3/4" NPT 32 37 50,5 12 18

    REV3NB REV3NS REV3NG 1" NPT 40 47 63,5 18 24

    REV4NB REV4NS REV4NG 1 1/4 NPT 48 56 64 24 30

    REV5NB REV5NS REV5NG 1 1/2 NPT 53 62 66 30 35

    REV6NB REV6NS REV6NG 2" NPT 63 73 67 35 45

    REV01IB REV01IS REV01IG *M16X1,5 24 28 45 5 10

    REV1IB REV1IS REV1IG *M20X1,5 24 28 45 7 12

    REV2IB REV2IS REV2IG *M25X1,5 32 37 46,5 12 18

    REV3IB REV3IS REV3IG *M32X1,5 40 47 53,5 18 24REV4IB REV4IS REV4IG *M40X1,5 48 56 54 24 30

    REV5IB REV5IS REV5IG *M50X1,5 53 62 56 30 35

    REV6IB REV6IS REV6IG *M63X1,5 63/65 73 58 35 45

    Thread*

    * The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

  • 5/19/2018 Cable Glands REV and REVD Series

    6/20

    6 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    MODELS, FEATURES AND DIMENSIONS REVL CABLE GLANDSSPECIAL VERSION FOR UNARMOURED CABLES FROM1/2 TO2

    * The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

    Code

    REVL

    Nickel-platedbrass

    Code

    REVL

    StainlessSteel

    Code

    REVL

    GalvanizedSteel

    Dimensions mm Cable Range mm

    AC1 AC2 M1

    C d min-max

    REVL1B REVL1S REVL1G 1/2" ISO7/1

    24

    24

    28

    47 5 10

    REVL2B REVL2S REVL2G 3/4" ISO7/1 32 24 37 47 7 12

    REVL3B REVL3S REVL3G 1" ISO7/1 40 32 47 52,5 12 18

    REVL4B REVL4S REVL4G 1 1/4 ISO7/1

    48

    40

    56

    59,5 18 24

    REVL5B REVL5S REVL5G 1 1/2 ISO7/1 53 48 62 62 24 30

    REVL6B

    REVL6S

    REVL6G

    2" ISO7/1

    63

    53

    73

    64 30 35

    REVL1NB

    REVL1NS

    REVL1NG

    1/2 NPT

    24

    24

    28

    49 5 10

    REVL2NB REVL2NS REVL2NG 3/4 NPT 32 24 37 49 7 12

    REVL3NB

    REVL3NS

    REVL3NG 1 NPT 40 32 47 56,5 12 18

    REVL4NB REVL4NS REVL4NG 1 1/4 NPT

    48

    40

    56

    63,5 18 24

    REVL5NB REVL5NS REVL5NG 1 1/2 NPT

    53

    48

    62

    64 24 30

    REVL6NB REVL6NS REVL6NG 2 NPT 63 53 73 67 30 35

    REVL1IB REVL1IS REVL1IG *M20X1,5 24 24 28 45 5 10

    REVL2IB

    REVL2IS

    REVL2IG *M25X1,5 32 24 37 45 7 12

    REVL3IB REVL3IS REVL3IG *M32X1,5 40

    32

    47

    46,5 12 18

    REVL4IB REVL4IS REVL4IG *M40X1,5 48 40 56 53,5 18 24

    REVL5IB

    REVL5IS

    REVL5IG *M50X1,5 53 48 62 54 24 30

    REVL6IB

    REVL6IS

    REVL6IG

    *M63X1,5

    63/65

    53

    73

    58 30 35

    Thread*

  • 5/19/2018 Cable Glands REV and REVD Series

    7/20

    7 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    MODELS, FEATURES AND DIMENSIONS REVF CABLE GLANDS VERSIONFOR UNARMOURED CABLES FROM3/8 TO 2 WITH A FEMALETHREADED ENTRY

    * The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

    CodeREVF(female)

    Nickel-plated brass

    CodeREVF(female)

    StainlessSteel

    CodeREVF(female)

    GalvanizedSteel

    Dimensions mm Cable Range mm

    AC M C d min-max

    REVF01B REVF01S REVF01G 3/8" ISO7/1 24 28 69,5 5 10

    REVF1B REVF1S REVF1G 1/2" ISO7/1 24 28 75,5 7 12

    REVF2B REVF2S REVF2G 3/4" ISO7/1 32 37 77 12 18

    REVF3B REVF3S REVF3G 1" ISO7/1 40 47 92 18 24

    REVF4B REVF4S REVF4G 1 1/4 ISO7/1 48 56 92,5 24 30

    REVF5B REVF5S REVF5G 1 1/2 ISO7/1 53 62 98,5 30 35REVF6B REVF6S REVF6G 2" ISO7/1 63 73 98,5 35 45

    REVF01NB REVF01NS REVF01NG 3/8" NPT 24 28 68,5 5 10

    REVF1NB REVF1NS REVF1NG 1/2" NPT 24 28 76,5 7 12

    REVF2NB REVF2NS REVF2NG 3/4" NPT 32 37 78 12 18

    REVF3NB REVF3NS REVF3NG 1" NPT 40 47 94 18 24

    REVF4NB REVF4NS REVF4NG 1 1/4 NPT 48 56 95,5 24 30

    REVF5NB REVF5NS REVF5NG 1 1/2 NPT 53 62 97,5 30 35

    REVF6NB REVF6NS REVF6NG 2" NPT 63 73 98,5 35 45

    REVF01IB REVF01IS REVF01IG *M16X1,5 24 28 70,5 5 10

    REVF1IB REVF1IS REVF1IG *M20X1,5 24 28 70,5 7 12

    REVF2IB REVF2IS REVF2IG *M25X1,5 32 37 72 12 18

    REVF3IB REVF3IS REVF3IG *M32X1,5 40 47 79 18 24

    REVF4IB REVF4IS REVF4IG *M40X1,5 48 56 79,5 24 30

    REVF5IB REVF5IS REVF5IG *M50X1,5 53 62 82,5 30 35

    REVF6IB REVF6IS REVF6IG *M63X1,5 63/65 73 84,5 35 45

    Thread*

  • 5/19/2018 Cable Glands REV and REVD Series

    8/20

    8 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    MODELS, FEATURES AND DIMENSIONS REVN CABLE GLANDS VERSIONFOR ARMOURED CABLES FROM3/8 TO2WITH A MALETHREADED ENTRY

    * The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

    CodeREVN(male)

    Nickel-platedbrass

    CodeREVN(male)

    StainlessSteel

    CodeREVN(male)

    GalvanizedSteel

    Dimensions mm Cable Range mm

    AC M C d min-max

    REVN01B REVN01S REVN01G 3/8" ISO7/1 24 28 69,5 5 10

    REVN1B REVN1S REVN1G 1/2" ISO7/1 24 28 75,5 7 12

    REVN2B REVN2S REVN2G 3/4" ISO7/1 32 37 77 12 18

    REVN3B REVN3S REVN3G 1" ISO7/1 40 47 92 18 24

    REVN4B REVN4S REVN4G 1 1/4 ISO7/1 48 56 92,5 24 30

    REVN5B REVN5S REVN5G 1 1/2 ISO7/1 53 62 98,5 30 35REVN6B REVN6S REVN6G 2" ISO7/1 63 73 98,5 35 45

    REVN01NB REVN01NS REVN01NG 3/8" NPT 24 28 71,5 5 10

    REVN1NB REVN1NS REVN1NG 1/2" NPT 24 28 79,5 7 12

    REVN2NB REVN2NS REVN2NG 3/4" NPT 32 37 81 12 18

    REVN3NB REVN3NS REVN3NG 1" NPT 40 47 100 18 24

    REVN4NB REVN4NS REVN4NG 1 1/4 NPT 48 56 100,5 24 30

    REVN5NB REVN5NS REVN5NG 1 1/2 NPT 53 62 102,5 30 35

    REVN6NB REVN6NS REVN6NG 2" NPT 63 73 104,5 35 45

    REVN01IB REVN01IS REVN01IG *M16X1,5 24 28 72,5 5 10

    REVN1IB REVN1IS REVN1IG *M20X1,5 24 28 66,5 7 12

    REVN2IB REVN2IS REVN2IG *M25X1,5 32 37 74 12 18

    REVN3IB REVN3IS REVN3IG *M32X1,5 40 47 82 18 24

    REVN4IB REVN4IS REVN4IG *M40X1,5 48 56 75,5 24 30

    REVN5IB REVN5IS REVN5IG *M50X1,5 53 62 77,5 30 35

    REVN6IB REVN6IS REVN6IG *M63X1,5 63/65 73 81,5 35 45

    Thread*

  • 5/19/2018 Cable Glands REV and REVD Series

    9/20

    9 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    DETAILS OF REV/REVS SERIES CABLE GLANDSFOR UNARMOURED CABLES FROM2 1/2 TO4

    CABLE GLAND PARTS

    1. Body2. Compression gasket3. Anti-friction ring4. Nut

    ASSEMBLING INSTRUCTIONS

    Step 1 Insert on the cable the nut 4and the ring 3

    Step 2 Assembly the body 1 and the compression gasket 2 on the electrical equipment

    Step 3 After having slipped the cable into the compression gasket 2 close by tightening the nut 4

    Cable gland properly assembled

  • 5/19/2018 Cable Glands REV and REVD Series

    10/20

    10 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    MODELS, FEATURES AND DIMENSIONSREV/REVS SERIES CABLE GLANDS FOR UNARMOURED CABLES FROM2 1/2 TO4

    Code

    REV/REVS

    Nickel-platedbrass

    Code

    REV/REVS

    StainlessSteel

    Thread* Dimensions mm Cable Range mm

    AC1 d min-max

    REV7B REV7S 2 1/2 ISO7/1 84 73 100 46 55

    REVS7B REVS7S 2 1/2 ISO7/1 90 84 100 55 62

    REV8B REV8S 3" ISO7/1 100 94 100 62 70

    REVS8B REVS8S 3" ISO7/1 105 98 100 70 78

    REV9B REV9S 3 1/2 ISO7/1 115 105 101 76 84REVS9B REVS9S 3 1/2 ISO7/1 120 112 101 84 92REV10B REV10S 4" ISO7/1 115 105 101,5 76 84

    REVS10B REVS10S 4 ISO7/1 120 112 101,5 84 92

    REV7NB REV7NS 2 1/2 NPT 84 73 110 46 55

    REVS7NB REVS7NS 2 1/2 NPT 90 84 110 55 62

    REV8NB REV8NS 3" NPT 100 94 112 62 70

    REVS8NB REVS8NS 3" NPT 105 98 112 70 78

    REV9NB REV9NS 3 1/2 NPT 115 105 114 76 84

    REVS9NB REVS9NS 3 1/2 NPT 120 112 114 84 92

    REV10NB REV10NS 4" NPT 115 105 115,5 76 84

    REVS10NB REVS10NS 4 NPT 120 112 115,5 84 92

    REV7IB REV7IS *M75X1,5 84 73 88 46 55

    REVS7IB REVS7IS *M75X1,5 90 84 88 55 62

    REV8IB REV8IS *M90X1,5 100 94 88 62 70REVS8IB REVS8IS *M90X1,5 105 98 88 70 78

    REV10IB REV10IS *M100X1,5 115 105 89,5 76 84

    REVS10IB REVS10IS *M100X1,5 120 112 89,5 84 92

    AC2 C

    * The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

  • 5/19/2018 Cable Glands REV and REVD Series

    11/20

    11 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    DETAILS OF REVD SERIES CABLE GLANDSFOR ARMOURED CABLES FROM3/8 TO2

    CABLE GLAND PARTS

    1. Body2. Sealing ring3. Conical metallic compression

    ring4. Metallic compression ring5. Intermediate Body6. IP sealing ring on the outer

    sheath of the cable7. Teflon washer8. Nut

    ASSEMBLING INSTRUCTIONS

    Step 1 Assembly the body 1complete with the sealing ring 2on the equipment.

    Step 2 Insert on the cable in sequence the details 8-7-6-5 and pre-assemble the wholeloosely.

    Step 3 Insert the compression ring 4on the cable armour.

    Step 4 Open the armour to connect the compression ring 3 withthe compression ring 4.

    Step 5 Once connected, no sticking out filaments of the armour should remain becausethey could interfere with the thread of the body 1. If you experience this problem,the filaments must be cut to avoid to compromise the final assembly between thebody 1 and the intermediate body 5.

    Step 6 Insert the internal sheath into the sealing ring 2 and the two compression ringspreviously assembled into the body 1, pulling the cable towards the interior of theequipment, so that the armour does not spill out by the two compression rings 3-4.

    Step 7 Complete the assembly by tightening the pre-assembled parts (Step 2) on thebody 1 and close the whole system.

    1

    234

    5

    6

    7

    8

    Cable gland properly assembled

  • 5/19/2018 Cable Glands REV and REVD Series

    12/20

    12 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    MODELS, FEATURES AND DIMENSIONSREVD SERIES CABLE GLANDS FOR ARMOURED CABLES FROM 3/8 TO2

    * The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

    Code

    REVD

    Nickel-plated brass

    Code

    REVD

    StainlessSteel

    Code

    REVD

    GalvanizedSteel

    Thread* Cable Range mm

    d min-max D min-max

    AC M C

    Internalsheath

    Outersheath of the

    cableREVD01B REVD01S REVD01G 3/8" ISO7/1 24 28 69 5 10 8 15

    REVD1B REVD1S REVD1G 1/2" ISO7/1 24 28 72 7 12 11 16

    REVD2B REVD2S REVD2G 3/4" ISO7/1 32 37 73,5 12 18 16 24

    REVD3B REVD3S REVD3G 1" ISO7/1 40 47 86,5 18 24 24 31

    REVD4B REVD4S REVD4G 1 1/4 ISO7/1 48 56 89 24 30 31 37

    REVD5B REVD5S REVD5G 1 1/2 ISO7/1 53 62 94 30 35 37 43

    REVD6B REVD6S REVD6G 2" ISO7/1 63 73 94 35 45 43 53REVD01NB REVD01NS REVD01NG 3/8" NPT 24 28 70 5 10 8 15

    REVD1NB REVD1NS REVD1NG 1/2" NPT 24 28 74 7 12 11 16

    REVD2NB REVD2NS REVD2NG 3/4" NPT 32 37 75,5 12 18 16 24

    REVD3NB REVD3NS REVD3NG 1" NPT 40 47 90,5 18 24 24 31REVD4NB REVD4NS REVD4NG 1 1/4 NPT 48 56 93 24 30 31 37

    REVD5NB REVD5NS REVD5NG 1 1/2 NPT 53 62 96 30 35 37 43

    REVD6NB REVD6NS REVD6NG 2" NPT 63 73 97 35 45 43 53

    REVD01IB REVD01IS REVD01IG *M16X1,5 24 28 70 5 10 8 15

    REVD1IB REVD1IS REVD1IG *M20X1,5 24 28 70 7 12 11 16

    REVD2IB REVD2IS REVD2IG *M25X1,5 32 37 71,5 12 18 16 24

    REVD3IB REVD3IS REVD3IG *M32X1,5 40 47 80,5 18 24 24 31

    REVD4IB REVD4IS REVD4IG *M40X1,5 48 56 83 24 30 31 37

    REVD5IB REVD5IS REVD5IG *M50X1,5 53 62 86 30 35 37 43

    REVD6IB REVD6IS REVD6IG *M63X1,5 63/65 73 88 35 45 43 53

    Dimensions mm

  • 5/19/2018 Cable Glands REV and REVD Series

    13/20

    13 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    MODELS, FEATURES AND DIMENSIONS REVDL CABLE GLANDSSPECIAL VERSION FOR ARMOURED CABLES FROM1/2 TO2

    * The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

    Code

    REVDL

    Nickel-platedbrass

    Code

    REVDL

    StainlessSteel

    Code

    REVDL

    GalvanizedSteel

    Dimensions mm Cable Range mm

    d min-max D min-max

    AC1 AC2

    M1 C

    Internalsheath

    Outersheath ofthe cable

    REVDL1B

    REVDL1S

    REVDL1G 1/2" ISO7/1

    24

    24

    28 72 5 10 8 15

    REVDL2B

    REVDL2S

    REVDL2G 3/4" ISO7/1

    32

    24

    37 72 7 12 11 16

    REVDL3B REVDL3S REVDL3G 1" ISO7/1 40 32 47 77,5 12 18 16 24

    REVDL4B

    REVDL4S

    REVDL4G 1 1/4 ISO7/1

    48

    40

    56 86,5 18 24 24 31

    REVDL5B

    REVDL5S

    REVDL5G 1 1/2 ISO7/1

    53

    48

    62

    9124 30

    31 37

    REVDL6B

    REVDL6S

    REVDL6G

    2" ISO7/1

    63

    53

    73

    94 30 35

    37 43

    REVDL1NB REVDL1NS REVDL1NG 1/2" NPT 24 24 28 74 5 10 8 15REVDL2NB

    REVDL2NS

    REVDL2NG 3/4" NPT

    32

    24

    37 74 7 12 11 16

    REVDL3NB REVDL3NS REVDL3NG 1" NPT 40 32 47 81,5 12 18 16 24

    REVDL4NB

    REVDL4NS

    REVDL4NG 1 1/4 NPT 48 40 56 90,5 18 24 24 31

    REVDL5NB

    REVDL5NS

    REVDL5NG 1 1/2 NPT

    53

    48

    62 93 24 30 31 37

    REVDL6NB REVDL6NS REVDL6NG 2" NPT

    63

    53

    73 97 30 35 37 43

    REVDL1IB

    REVDL1IS

    REVDL1IG *M20X1,5

    24

    24

    28 70 5 10 8 15

    REVDL2IB

    REVDL2IS

    REVDL2IG *M25X1,5

    32

    24

    37 70 7 12 11 16

    REVDL3IB REVDL3IS REVDL3IG *M32X1,5 40 32 47 71,5 12 18 16 24

    REVDL4IB

    REVDL4IS

    REVDL4IG *M40X1,5

    48

    40

    56 80,5 18 24 24 31

    REVDL5IB

    REVDL5IS

    REVDL5IG *M50X1,5

    53

    48

    62 83 24 30 31 37

    REVDL6IB REVDL6IS REVDL6IG *M63X1,5

    63/65

    53

    73 88 30 35 37 43

    Thread*

  • 5/19/2018 Cable Glands REV and REVD Series

    14/20

    14 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    DETAILS OF REVD/REVDS SERIES CABLE GLANDSFOR ARMOURED CABLES FROM 2 1/2 TO4

    CABLE GLAND PARTS

    1. Body2. Compression gasket3. Anti-friction ring4. Armour clamping body5. Ring nut6. Intermediate body7. IP gasket on the outer sheath of

    the cable8. Nut

    NOTE: REVDS series cable glandshas a special body (1) to accomo-date a wider cable range

    ASSEMBLING INSTRUCTIONS

    Step 1 Insert on the cable in sequence the details 8-7-6-5-4 and pre-assemble the whole loosely.

    Step 2 Fit the body 1complete with the compression gasket 2 and the anti-friction ring 3 on the equipment.

    Step 3 After having slipped the under armour sheath of the cable into compression gasket 2, tighten theassembly with the armour clamping body 4. Keep the cable pushed towards the inside of the equi-pment, so that the armour is always in contact with the conical part of the armour tightening section.

    Step 4 Push the ring nut 5on the armour and to the cone (armour clamping body 4). The over armour she-ath of the cable must have a maximum distance equal to 2mm from the ring nut 5. Once connected,no sticking out filaments of the armour should remain because they could interfere with the thread. Ifyou experience this problem, the filaments must be cut to avoid to compromise the final assemblybetween the armour clamping body 4 and the intermediate body 6.

    Step 5 Assemble the intermediate body 6 with the armour clamping body 4and the ring nut 5, while alwayskeeping the cable pusched towards the inside of the apparatus and ensuring that the armour doesnot move away from the locking system.

    Step 6 Complete the installation by tightening the upper gasket 7, which was previously inserted into theintermediate body 6and locked with nut 8.

    Cable gland properly assembled

  • 5/19/2018 Cable Glands REV and REVD Series

    15/20

    15 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    MODELS, FEATURES AND DIMENSIONSREVD/REVDS SERIES CABLE GLANDS FOR ARMOURED CABLES FROM 2 1/2 TO4

    * The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

    Code

    REVD/REVDS

    Nickel-platedBrass

    Code

    REVD/REVDS

    StainlessSteel

    Thread* Cable Range mm

    d min-max D min-max

    AC1 AC2 AC3 AC4Internalsheath

    Outersheath of the

    cableREVD7B REVD7S 2 1/2 ISO7/1 84 105 118 127 185 46 55 54 78

    REVDS7B REVDS7S 2 1/2 ISO7/1 90 105 118 127 185 55 62 54 78

    REVD8B REVD8S 3" ISO7/1 100 113 130 140 185 62 70 64 90

    REVDS8B REVDS8S 3" ISO7/1 105 113 130 140 185 70 78 64 90

    REVD9B REVD9S 3 1/2 ISO7/1 115 135 144 153 187 76 84 88 104

    REVDS9B REVDS9S 3 1/2 ISO7/1 120 135 144 153 187 84 92 88 104REVD10B REVD10S 4" ISO7/1 115 135 144 153 187,5 76 84 88 104

    REVDS10B REVDS10S 4 ISO7/1 120 135 144 153 187,5 84 92 88 104

    REVD7NB REVD7NS 2 1/2 NPT 84 105 118 127 195 46 55 54 78

    REVDS7NB REVDS7NS 2 1/2 NPT 90 105 118 127 195 55 62 54 78

    REVD8NB REVD8NS 3" NPT NPT 100 113 130 140 197 62 70 64 90

    REVDS8NB REVDS8NS 3" NPT 105 113 130 140 197 70 78 64 90

    REVD9NB REVD9NS 3 1/2 NPT 115 135 144 153 200 76 84 88 104

    REVDS9NB REVDS9NS 3 1/2 NPT 120 135 144 153 200 84 92 88 104

    REVD10NB REVD10NS 4" NPT 115 135 144 153 201,5 76 84 88 104

    REVDS10NB REVDS10NS 4 NPT 120 135 144 153 201,5 84 92 88 104

    REVD7IB REVD7IS *M75X1,5 84 105 118 127 173 46 55 54 78REVDS7IB REVDS7IS *M75X1,5 90 105 118 127 173 55 62 54 78REVD8IB REVD8IS *M90X1,5 100 113 130 140 173 62 70 64 90

    REVDS8IB REVDS8IS *M90X1,5 105 113 130 140 173 70 78 64 90

    REVD10IB REVD10IS *M100X1,5 115 135 144 153 175,5 76 84 88 104

    REVDS10IB REVDS10IS *M100X1,5 120 135 144 153 175,5 84 92 88 104

    Dimensions mm

    C

  • 5/19/2018 Cable Glands REV and REVD Series

    16/20

    16 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    TIGHTENING TORQUES TO ENSURE THE CLAMPING OF THE CABLE

    Size

    Tightening (Nm)

    01 20

    1 20

    2 45

    3 50

    4 60

    5 65

    6 65

    7 70

    8 80

    9 90

    10 90

    STANDARD ACCESSORIES UPON REQUEST

    Reducers and adaptorsRE series

    They allow the connectionbetween different threads ordifferent sizes.

    Plugs PLG... series

    They can be used to tem-porarly close not neces-sary entries.

    Lock nutsDL series

    They assure the fixing ofcable glands with parallelthread (isometric).

    Earthing ringsA series

    They are used to guaranteethe earthing of the cablegland and the installed e-quipment.

    PVC protectorsPGA... series

    PGA series protectors aremade in PVC and are usedto offer a further protectionto the cable glands fromthe entry of dusts and li-quids.

    Auto-binder tape

    Tape for the mechanicalprotection adaptable to allsizes of the cable glands.

    Serrated internal washer

    Serrated or shake-proof washers act as an anti-vibration device toprevent the cable gland from loosening. It can be also used as anearth enhancing devise on painted enclosures.

  • 5/19/2018 Cable Glands REV and REVD Series

    17/20

    17 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    TABLE OF ACCESSORIES UPON REQUEST

    MORE ACCESSORIES UPON REQUEST

    CABLEGLANDS

    SERIES

    CABLE GLAND CODEACCESSORIES

    CODE

    ACCESSORIES

    CODE

    ACCESSORIES

    CODEPROTECTORS BLACK PVC

    01 REV REVD REVL REVDL 01 PGA1F

    1 REV REVD REVL REVDL 1 PGA1F

    2 REV REVD 2 PGA2R

    L2 REVL REVDL 2 PGA1F

    3 REV REVD 3 PGA3

    L3 REVL REVDL 3 PGA2R

    4 REV REVD 4 PGA4

    L4 REVL REVDL 4 PGA3

    5 REV REVD 5 PGA5

    L5 REVL REVDL 5 PGA46 REV REVD 6 PGA6R

    L6 REVL REVDL 6 PGA5

    LOCK NUTS FOR METRIC CABLE GLANDS

    Nickel-plated

    brass Galvanized Steel Stainless steel

    01 REV REVD REVL REVDL REVF REVN 01I DL01IB DL01IG DL01IS

    1 REV REVD REVL REVDL REVF REVN 1I DL1IB DL1IG DL1IS

    2 REV REVD REVL REVDL REVF REVN 2I DL2IB DL2IG DL2IS

    3 REV REVD REVL REVDL REVF REVN 3I DL3IB DL3IG DL3IS

    4 REV REVD REVL REVDL REVF REVN 4I DL4IB DL4IG DL4IS

    5 REV REVD REVL REVDL REVF REVN 5I DL5IB DL5IG DL5IS

    6 REV REVD REVL REVDL REVF REVN 6I DL6IB DL6IG DL6IS

    EARTHING RINGS Thread ISO 261

    Nickel-plated

    brass Stainless steel

    01 REV REVD REVL REVDL REVF REVN 01I A0131B A0131S

    1 REV REVD REVL REVDL REVF REVN 1I A1311IB A1311IS

    2 REV REVD REVL REVDL REVF REVN 2I A2312IB A2312IS

    3 REV REVD REVL REVDL REVF REVN 3I A3313IB A3313IS

    4 REV REVD REVL REVDL REVF REVN 4I A4314IB A4314IS

    5 REV REVD REVL REVDL REVF REVN 5I A5315IB A5315IS

    6 REV REVD REVL REVDL REVF REVN 6I A6316IB A6316IS

    SERRATED INTERNAL WASHER Thread ISO 261 Stainless steel

    01 REV REVD REVL REVDL REVF REVN 01I RDI01IS/A4

    1 REV REVD REVL REVDL REVF REVN 1I RDI1IS/A4

    2 REV REVD REVL REVDL REVF REVN 2I RDI2IS/A4

    3 REV REVD REVL REVDL REVF REVN 3I RDI3IS/A4

    4 REV REVD REVL REVDL REVF REVN 4I RDI4IS/A4

    5 REV REVD REVL REVDL REVF REVN 5I RDI5IS/A4

    6 REV REVD REVL REVDL REVF REVN 6I RDI6IS/A4

  • 5/19/2018 Cable Glands REV and REVD Series

    18/20

    18 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    APPLICATION EXAMPLES

    Cortem aluminium junction box EJB-4 series complete with:

    Lighting fixtures FLFE-258 complete with:

    n2 REV5NB n 1 REVD6NB

    n. 4 PLG2NB

    n 7 REVD2NB

    n2 REV2IB

    Sealant for threads

    The Loctite 577 (or a product of equal orsuperior characteristics) must be used onthe threaded entry of NPT and ISO 7/1 ca-ble gland to ensure a better IP seal. Itshould be applied, covering at least 2 fullthreads, only on the tapered thread.

    OTHER ACCESSORIES RECOMMENDED

  • 5/19/2018 Cable Glands REV and REVD Series

    19/20

    19 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    APPLICATION

    Manufacturing plants and process facilities:chemical, petrochemical, refineries, pharma-ceutical, Gas treatment and transport

    Areas with risk of explosion and fire due to

    abnormal, unusual or accidental presence ofignitable concentration of gases/vapours anddusts, even simultaneously

    On-shore, off-shore, naval and harbour instal-lations

    Waste and or sewage treatment facilities

    Thermal plants

    Area with presence of combustible dusts suchas joineries, sugarhouses, food industries withtreatment and storage of wheat and deriva-tives

    Painting plants

    MARKET

    Industry Mechanical and electrical engineering

    Agribusiness

    Distillery

    Oil & Gas industries Pharmaceutical industries

    Energy

    Engineering and Contractors Project Design companies

    Electrical contractors

    Construction companies

    Electrical equipment distributors Shipyards / harbours

    Off-shore rig constructors

    On-shore treatment and refining plants

    ATEX REFERENCE STANDARDS

    EN 60079-0:2012 Electrical apparatus for explosive gas atmospheresPart 0: General Requiremets

    EN60079-1:2007 Electrical apparatus for explosive gas atmospheresPart 1: Flameproof enclosures d

    EN 60079-7:2007 Electrical apparatus for explosive gas atmospheresPart 7: Incresed safety e

    EN 60079-31:2009 Explosive atmospheresPart 31: Equipment dust ignition protection by enclosure "t"

    EN 60529:1991 Degrees of protection provided by enclosures (IP Code)

    ATEX 94/9/CE Equipment for explosive atmospheres

    IEC 60079-0:2011 Electrical apparatus for explosive gas atmospheresPart 0: General Requiremets

    IEC 60079-1:2007 Electrical apparatus for explosive gas atmospheresPart 1: Flameproof enclosures d

    IEC 60079-7:2006 Electrical apparatus for explosive gas atmospheresPart 7: Incresed safety e

    IEC 60079-31:2008

    Explosive atmospheres

    Part 31: Equipment dust ignition protection by enclosure "t"

    IEC 60529:2001 Degrees of protection provided by enclosures (IP Code)

    IECEX REFERENCE STANDARDS

  • 5/19/2018 Cable Glands REV and REVD Series

    20/20

    20 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

    ELFIT S.P.A.

    HEADQUARTERS AND FACTORYVia Aquileia 12, 34070 Villesse (GO), ITALY

    Tel +39 0481 964911

    Fax +39 0481 964999

    [email protected]

    [email protected]

    www.cortemgroup.com

    CORTEM S.P.A.

    HEADQUARTERS AND FACTORYVia Aquileia 10, 34070 Villesse (GO), ITALY

    Tel +39 0481 964911

    Fax +39 0481 964999

    [email protected]

    SALES OFFICESP.le Dateo 2, 20129 Milano ITALIA

    Tel +39 02 761100501

    Fax +39 02 70005471

    [email protected]

    www.cortemgroup.com