cable glands and bushingsaccessories for installation 7 for installation bag series explosion-proof...
TRANSCRIPT
Zones 1&2; 21&22
7
7/15
7
7/14
Accessories for Installation
BAG Series Explosion-proof Seal Bushings
Schematic diagram
BAG-Z(Vertical type M20 x 1.5~M32 x 1.5) BAG-Z(Vertical type M40 x 1.5~M63 x 1.5)
BAG-P(Drainage type M20 x 1.5~M32 x 1.5) BAG-P(Drainage type M40 x 1.5~M63 x 1.5)
BAG-H(Horizontal type)
Cable Glands and Bushings
Cable Glands
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Zone 21 and Zone 22
Class I, Zone 1 and Zone 2
Class I, Division 1, Groups A , B, C, D
Class I, Division 2, Groups A , B, C, D
Ex d and Ex e versions
Cable glands:
-Suitable for armored or unarmored cable
-Suitable for cable or steel pipe wiring
Explosion-proof cable glands include:
1) DQM-I (Ex e)
-Plastic, unarmored
-Metal, unarmored or armored
2) DQM-II (Ex d)
-Metal, unarmored, single seal
-Metal, armored, dual seal
3) DQM-III (Ex d)
-Metal, armored, compound barrier
http:// www.waromgroup.comGeneral Catalogue 01.01.2013http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Selection table
Gland
size
Standard
entry thread
A
Cable outer diameter B (mm)
20
25
32
40
50
63
75
M20 x 1.5
M25 x 1.5
M32 x 1.5
M40 x 1.5
M50 x 1.5
M63 x 1.5
M75 x 1.5
Min
5
10
14
18
22
32
44
Max
10
14
18
25
32
44
56
Minimum
thread length
C (mm)
15
15
17
17
17
17
17
Ordering
code
706001
706002
706003
706004
706005
706006
706007
Weight
(kg)
0.15
0.15
0.30
0.50
0.55
0.70
0.90
Across flats
D (mm)
33
33
37
40
40
53
53
Across corners
E (mm)
27
32
38
47
55
68
80
Nominal
protrusion length
F (mm)
30
35
41
50
60
72
85
Note: 1. Standard material is galvanized carbon steel. Nickel plated brass or stainless steel is optional. Weight above is based
upon galvanized carbon steel.
2. Supplied with locknut and seal gasket. 3. Earth lug and shroud on request. See P7/31.
ABD C
F
E
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Metal Unarmored
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Class I, Zone 1 and Zone 2
Class I, Division 2, Groups A , B, C, D
Ex e structure; available in stainless steel, nickel plated brass
or galvanized carbon steel.
Single seal, suitable for unarmored cable.
7
7/16
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Plastic Unarmored
http:// www.waromgroup.comGeneral Catalogue 01.01.2013
7
http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Plastic Unarmored
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Class I, Zone 1 and Zone 2
Class I, Division 2, Groups A , B, C, D
Ex e structure, made of plastic, black.
Single seal, suitable for unarmored cable.
Technical data
Explosion-proof cable glands DQM-I Ex e (plastic unarmored)
Explosion protection
Certificates
Conformity to standards
Gland material
Degree of protection
Ambient temperature
Connection thread
II 2 G Ex e II
PTB 04 ATEX 1087X; IECEx CQM 07.0009
EN 50014:1997+A1+A2, EN 50019:2000 IEC 60079-0:2004, IEC 60079-7:2001
Plastic, black
IP65
-20℃~+55℃
Metric thread is standard type; G thread is optional, but limited at G3/4″ ; NPT thread is not suitable
Without stopping rod
With stopping rod
AB
D C
F
E
Note: 1. Supplied with locknut (nickel plated brass) and seal gasket, without stopping rod. 2. Stopping rod on request. See P7/31.
Selection table
Ordering
code
705001
705002
705004
705005
705006
705007
Weight
(kg)
0.05
0.05
0.05
0.10
0.11
0.15
Gland
size
16
20
32
40
50
63
Standard
entry thread
A
Cable outer diameter B (mm)
5
6
10
17
23
32
8
12
18
25
32
44
MaxMin
9
12
13
16
Nominal
protrusion length
F (mm)
21
26
45
55
63
78
Across corners
E (mm)
19
24
41
50
57
70
Across flats
D (mm)
27
29
35
46
51
51
Minimum
thread length
C (mm)
15
15
15
14
14
15
25 M25 x 1.5
M16 x 1.5
M20 x 1.5
M32 x 1.5
M40 x 1.5
M50 x 1.5
M63 x 1.5
15 33 30 33 705003 0.05
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Metal Unarmored
Technical data
Explosion-proof cable glands DQM-I Ex e (metal unarmored)
Explosion protection
Certificates
Conformity to standards
Gland material
Degree of protection
Ambient temperature
Connection thread
II 2 G Ex e II
PTB 04 ATEX 1087X; IECEx CQM 07.0009
EN 50014:1997+A1+A2, EN 50019:2000 IEC 60079-0:2004, IEC 60079-7:2001
Stainless steel, nickel plated brass or galvanized carbon steel
IP65
-20℃~+55℃(-60℃~+100℃ optoonal)
Metric thread is standard type; G thread or NPT thread is optional
7/17
Selection table
Gland
size
Standard
entry thread
A
Cable outer diameter B (mm)
20
25
32
40
50
63
75
M20 x 1.5
M25 x 1.5
M32 x 1.5
M40 x 1.5
M50 x 1.5
M63 x 1.5
M75 x 1.5
Min
5
10
14
18
22
32
44
Max
10
14
18
25
32
44
56
Minimum
thread length
C (mm)
15
15
17
17
17
17
17
Ordering
code
706001
706002
706003
706004
706005
706006
706007
Weight
(kg)
0.15
0.15
0.30
0.50
0.55
0.70
0.90
Across flats
D (mm)
33
33
37
40
40
53
53
Across corners
E (mm)
27
32
38
47
55
68
80
Nominal
protrusion length
F (mm)
30
35
41
50
60
72
85
Note: 1. Standard material is galvanized carbon steel. Nickel plated brass or stainless steel is optional. Weight above is based
upon galvanized carbon steel.
2. Supplied with locknut and seal gasket. 3. Earth lug and shroud on request. See P7/31.
AB
D C
F
E
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Metal Unarmored
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Class I, Zone 1 and Zone 2
Class I, Division 2, Groups A , B, C, D
Ex e structure; available in stainless steel, nickel plated brass
or galvanized carbon steel.
Single seal, suitable for unarmored cable.
7
7/16
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Plastic Unarmored
http:// www.waromgroup.comGeneral Catalogue 01.01.2013
7
http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Plastic Unarmored
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Class I, Zone 1 and Zone 2
Class I, Division 2, Groups A , B, C, D
Ex e structure, made of plastic, black.
Single seal, suitable for unarmored cable.
Technical data
Explosion-proof cable glands DQM-I Ex e (plastic unarmored)
Explosion protection
Certificates
Conformity to standards
Gland material
Degree of protection
Ambient temperature
Connection thread
II 2 G Ex e II
PTB 04 ATEX 1087X; IECEx CQM 07.0009
EN 50014:1997+A1+A2, EN 50019:2000 IEC 60079-0:2004, IEC 60079-7:2001
Plastic, black
IP65
-20℃~+55℃
Metric thread is standard type; G thread is optional, but limited at G3/4″ ; NPT thread is not suitable
Without stopping rod
With stopping rod
AB
D C
F
E
Note: 1. Supplied with locknut (nickel plated brass) and seal gasket, without stopping rod. 2. Stopping rod on request. See P7/31.
Selection table
Ordering
code
705001
705002
705004
705005
705006
705007
Weight
(kg)
0.05
0.05
0.05
0.10
0.11
0.15
Gland
size
16
20
32
40
50
63
Standard
entry thread
A
Cable outer diameter B (mm)
5
6
10
17
23
32
8
12
18
25
32
44
MaxMin
9
12
13
16
Nominal
protrusion length
F (mm)
21
26
45
55
63
78
Across corners
E (mm)
19
24
41
50
57
70
Across flats
D (mm)
27
29
35
46
51
51
Minimum
thread length
C (mm)
15
15
15
14
14
15
25 M25 x 1.5
M16 x 1.5
M20 x 1.5
M32 x 1.5
M40 x 1.5
M50 x 1.5
M63 x 1.5
15 33 30 33 705003 0.05
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Metal Unarmored
Technical data
Explosion-proof cable glands DQM-I Ex e (metal unarmored)
Explosion protection
Certificates
Conformity to standards
Gland material
Degree of protection
Ambient temperature
Connection thread
II 2 G Ex e II
PTB 04 ATEX 1087X; IECEx CQM 07.0009
EN 50014:1997+A1+A2, EN 50019:2000 IEC 60079-0:2004, IEC 60079-7:2001
Stainless steel, nickel plated brass or galvanized carbon steel
IP65
-20℃~+55℃(-60℃~+100℃ optoonal)
Metric thread is standard type; G thread or NPT thread is optional
7/17
7
7/18
Technical data
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Metal Armored
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Metal Armored
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Class I, Zone 1 and Zone 2
Class I, Division 2, Groups A , B, C, D
Ex e structure; available in stainless steel, nickel plated brass
or galvanized carbon steel.
Single seal, suitable for both armored and unarmored cable.
Explosion-proof cable glands DQM-I Ex e (metal armored)
Explosion protection
Certificates
Conformity to standards
Gland material
Degree of protection
Ambient temperature
Connection thread
II 2 G Ex e II
PTB 04 ATEX 1087X; IECEx CQM 07.0009
EN 50014:1997+A1+A2, EN 50019:2000
IEC 60079-0:2004, IEC 60079-7:2001
Stainless steel, nickel plated brass or galvanized carbon steel
IP65
-20℃~+55℃(-60℃~+100℃ optoonal)
Metric thread is standard type; G thread or NPT thread is optional
7
7/19
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Metal Armored
http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Note: 1. Standard material is nickel plated brass. Stainless steel or galvanized carbon steel is optional. Weight above is based upon nickel plated brass. 2. Supplied with locknut and seal gasket. 3. Earth lug and shroud on request. See P7/31.
Gland
size
Standard
entry thread
A
Cable outer diameter B (mm)
Max
20S
20
25S
25
32S
32
40S
40
50S
50
63S
63
75S
75
90S
90
110S
110
M20 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110x 1.5
11
11
11
17
17
22
25
25
33
33
40
40
40
61
61
73
73
88
Cable outer diameter C (mm)
Min
6
9
9
14
14
19
24
27
29
34
38
44
44
47
47
55
55
62
Max
12
15
15
22
22
28
28
33
35
41
45
52
52
74
74
87
87
103
Minimum
thread length
D (mm)
15
15
15
15
17
17
19
19
19
19
19
19
19
19
19
19
19
19
Across flats
E (mm)
50
50
50
50
50
55
58
58
67
67
73
73
73
94
96
108
108
110
Across corners
F (mm)
27
27
27
34
34
41
41
50
50
60
60
75
72
100
400
115
115
128
Ordering
code
Weight
(kg)
707001
707002
707003
707004
707005
707006
707007
707008
707009
707010
707011
707012
707025
707026
707027
707028
707029
707030
Nominal
protrusion
length G (mm)
30
30
30
37
37
45
45
55
55
65
65
77
77
105
105
120
120
135
Ordering
code
Weight
(kg)
Nominal
protrusion
length G (mm)
30
30
30
37
37
45
45
55
55
65
65
77
77
105
105
120
120
135
707013
707014
707015
707016
707017
707018
707019
707020
707021
707022
707023
707024
707031
707032
707033
707034
707035
707036
Gland
size
Standard
entry thread
A
20S
20
25S
25
32S
32
40S
40
50S
50
63S
63
75S
75
90S
90
110S
110
M20 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110x 1.5
M125x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
M125 x 1.5
Cable outer diameter C (mm)
MaxMin
Cable outer diameter B (mm)
Max
11
11
11
17
17
22
25
25
33
33
42
42
42
61
61
73
73
88
6
9
14
14
19
19
24
27
29
34
38
44
44
47
47
55
55
62
12
15
22
22
28
28
28
33
35
41
45
52
52
74
74
87
87
103
Standard
entry thread
H
Minimum
thread length
D (mm)
15
15
15
15
17
17
19
19
19
19
19
19
19
19
19
19
19
19
Across flats
E (mm)
66
66
67
66
73
73
76
76
85
85
91
91
91
115
115
126
126
129
Across corners
F (mm)
27
27
27
34
34
41
41
50
50
60
60
72
72
100
100
115
115
128
Steel pipe wiring selection table
Cable wiring selection table
Cable wiring Steel pipe wiring
http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Cable wiring selection table
G
F
A
D
BC
E
E D F
Steel pipe wiring selection table
C
H
A
GB
0.19
0.18
0.23
0.22
0.26
0.24
0.32
0.29
0.39
0.36
0.48
0.45
3.00
2.85
4.05
3.95
5.05
4.95
0.14
0.13
0.18
0.17
0.21
0.19
0.27
0.24
0.34
0.31
0.43
0.40
2.80
2.70
3.90
3.80
4.80
4.70
7
7/18
Technical data
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Metal Armored
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Metal Armored
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Class I, Zone 1 and Zone 2
Class I, Division 2, Groups A , B, C, D
Ex e structure; available in stainless steel, nickel plated brass
or galvanized carbon steel.
Single seal, suitable for both armored and unarmored cable.
Explosion-proof cable glands DQM-I Ex e (metal armored)
Explosion protection
Certificates
Conformity to standards
Gland material
Degree of protection
Ambient temperature
Connection thread
II 2 G Ex e II
PTB 04 ATEX 1087X; IECEx CQM 07.0009
EN 50014:1997+A1+A2, EN 50019:2000
IEC 60079-0:2004, IEC 60079-7:2001
Stainless steel, nickel plated brass or galvanized carbon steel
IP65
-20℃~+55℃(-60℃~+100℃ optoonal)
Metric thread is standard type; G thread or NPT thread is optional
7
7/19
Cable Glands
DQM-I Series Explosion-proof Cable Glands (Ex e)
Metal Armored
http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Note: 1. Standard material is nickel plated brass. Stainless steel or galvanized carbon steel is optional. Weight above is based upon nickel plated brass. 2. Supplied with locknut and seal gasket. 3. Earth lug and shroud on request. See P7/31.
Gland
size
Standard
entry thread
A
Cable outer diameter B (mm)
Max
20S
20
25S
25
32S
32
40S
40
50S
50
63S
63
75S
75
90S
90
110S
110
M20 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110x 1.5
11
11
11
17
17
22
25
25
33
33
42424261
61
73
73
88
Cable outer diameter C (mm)
Min
6
9
9
14
14
19
24
27
29
34
38
44
44
47
47
55
55
62
Max
12
15
15
22
22
28
28
33
35
41
45
52
52
74
74
87
87
103
Minimum
thread length
D (mm)
15
15
15
15
17
17
19
19
19
19
19
19
19
19
19
19
19
19
Across flats
E (mm)
50
50
50
50
50
55
58
58
67
67
73
73
73
94
96
108
108
110
Across corners
F (mm)
27
27
27
34
34
41
41
50
50
60
60
75
72
100
100
115
115
128
Ordering
code
Weight
(kg)
707001
707002
707003
707004
707005
707006
707007
707008
707009
707010
707011
707012
707025
707026
707027
707028
707029
707030
Nominal
protrusion
length G (mm)
30
30
30
37
37
45
45
55
55
65
65
77
77
105
105
120
120
135
Ordering
code
Weight
(kg)
Nominal
protrusion
length G (mm)
30
30
30
37
37
45
45
55
55
65
65
77
77
105
105
120
120
135
707013
707014
707015
707016
707017
707018
707019
707020
707021
707022
707023
707024
707031
707032
707033
707034
707035
707036
Gland
size
Standard
entry thread
A
20S
20
25S
25
32S
32
40S
40
50S
50
63S
63
75S
75
90S
90
110S
110
M20 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110x 1.5
M110x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
M125 x 1.5
Cable outer diameter C (mm)
MaxMin
Cable outer diameter B (mm)
Max
11
11
11
17
17
22
25
25
33
33
42
42
42
61
61
73
73
88
6
9
914
1419
24
27
29
34
38
44
44
47
47
55
55
62
12
15
1522
2228
28
33
35
41
45
52
52
74
74
87
87
103
Standard
entry thread
H
Minimum
thread length
D (mm)
15
15
15
15
17
17
19
19
19
19
19
19
19
19
19
19
19
19
Across flats
E (mm)
66
66
67
66
73
73
76
76
85
85
91
91
91
115
115
126
126
129
Across corners
F (mm)
27
27
27
34
34
41
41
50
50
60
60
72
72
100
100
115
115
128
Steel pipe wiring selection table
Cable wiring selection table
Cable wiring Steel pipe wiring
http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Cable wiring selection table
G
F
A
D
BC
E
E D F
Steel pipe wiring selection table
C
H
A
GB
0.19
0.18
0.23
0.22
0.26
0.24
0.32
0.29
0.39
0.36
0.48
0.45
3.00
2.85
4.05
3.95
5.05
4.95
0.14
0.13
0.18
0.17
0.21
0.19
0.27
0.24
0.34
0.31
0.43
0.40
2.80
2.70
3.90
3.80
4.80
4.70
7
7/21
7
7/20 http:// www.waromgroup.comGeneral Catalogue 01.01.2013http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Cable Glands
DQM-II Series Explosion-proof Cable Glands (Ex d IIC)
Unarmored Single Seal
Cable Glands
DQM-II Series Explosion-proof Cable Glands
(Ex d IIC) Unarmored Single Seal
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Zone 21 and Zone 22
Class I, Zone 1 and Zone 2
Class I, Division 1, Groups A , B, C, D
Ex d structure; available in stainless steel, nickel plated brass
or galvanized carbon steel.
Single seal, suitable for unarmored cable.
Cable wiring
Steel pipe wiring
Cable Glands
DQM-II Series Explosion-proof Cable Glands (Ex d IIC)
Unarmored Single Seal
Note: 1. Standard material is galvanized carbon steel. Nickel plated brass or stainless steel is optional. Weight above is based upon galvanized carbon steel. 2. Supplied without locknut. 3. Earth lug and shroud on request. See P7/31.
Gland
size
Standard
entry thread
A
Cable outer diameter B (mm)
20
25
32
40
50
63
75
90
110
M20 x 1.5
M25 x 1.5
M32 x 1.5
M40 x 1.5
M50 x 1.5
M63 x 1.5
M75 x 1.5
M90 x 1.5
M110x 1.5
Min
6.5
10
11
14
20
25
38
55
48
Max
11
15
18
24
27
35
57
67
80
Minimum
thread length
C (mm)
16
16
16
16
16
16
17
17
17
Ordering
code
708001
708002
708003
708004
708005
708006
708013
708014
708015
Weight
(kg)
Across flats
D (mm)
37
40
40
45
50
57
65
85
105
Across corners
E (mm)
30
36
41
50
60
70
102
110
140
34
41
46
55
65
75
110
115
145
Nominal
protrusion
length F (mm)
Gland
size
20
25
32
40
50
63
75
90
110
Standard
entry thread
A
M20 x 1.5
M25 x 1.5
M32 x 1.5
M40 x 1.5
M50 x 1.5
M63 x 1.5
M75 x 1.5
M90 x 1.5
M110 x 1.5
Standard
entry thread
G
M20 x 1.5
M25 x 1.5
M32 x 1.5
M40 x 1.5
M50 x 1.5
M63 x 1.5
M75 x 1.5
M90 x 1.5
M110 x 1.5
Cable outer diameter B (mm)
MaxMin
10
12
15
18
26
30
38
55
48
14
17
23
30
37
47
57
67
80
Minimum
thread length
C (mm)
15
15
17
17
17
17
17
17
17
Ordering
code
708007
708008
708009
708010
708011
708012
708016
708017
708018
Weight
(kg)
Across flats
D (mm)
51
51
65
68
68
73
73
73
78
Across corners
E (mm)
36
41
50
60
70
78
102
110
140
41
46
55
63
75
85
110
115
145
Nominalprotrusion
length F (mm)
Steel pipe wiring selection table
Cable wiring selection table
A
D C
B
G
Steel pipe wiring selection table
AB
D C
F
E
Cable wiring selection table
F
E
0.20
0.25
0.40
0.60
0.75
1.15
1.50
1.80
3.50
0.15
0.25
0.40
0.55
0.65
0.90
1.10
1.30
1.60
Technical data
Explosion-proof cable glands DQM-II Ex d (unarmored single seal)
Explosion protection
Gas explosion protection
Dust explosion protection
Certificates
Conformity to standards
Gland material
Degree of protection
Ambient temperature
Connection thread
II 2 G Ex d IIC Gb II 2 G Ex e IIC Gb
II 2 D Ex tb IIIC Db IP65
LCIE 06 ATEX 6100; IECEx LCI 08.0011
EN 60079-0:2009, EN 60079-1:2007, EN 60079-7:2007, EN 60079-31:2009
IEC 60079-0:2011, IEC 60079-1:2007, IEC 60079-7:2006, IEC 60079-31:2008
Stainless steel, nickel plated brass or galvanized carbon steel
IP65
-20℃~+55℃(-60℃~+100℃ optoonal)
Metric thread is standard type; G thread or NPT thread is optional
7
7/21
7
7/20 http:// www.waromgroup.comGeneral Catalogue 01.01.2013http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Cable Glands
DQM-II Series Explosion-proof Cable Glands (Ex d IIC)
Unarmored Single Seal
Cable Glands
DQM-II Series Explosion-proof Cable Glands
(Ex d IIC) Unarmored Single Seal
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Zone 21 and Zone 22
Class I, Zone 1 and Zone 2
Class I, Division 1, Groups A , B, C, D
Ex d structure; available in stainless steel, nickel plated brass
or galvanized carbon steel.
Single seal, suitable for unarmored cable.
Cable wiring
Steel pipe wiring
Cable Glands
DQM-II Series Explosion-proof Cable Glands (Ex d IIC)
Unarmored Single Seal
Note: 1. Standard material is galvanized carbon steel. Nickel plated brass or stainless steel is optional. Weight above is based upon galvanized carbon steel. 2. Supplied without locknut. 3. Earth lug and shroud on request. See P7/31.
Gland
size
Standard
entry thread
A
Cable outer diameter B (mm)
20
25
32
40
50
63
75
90
110
M20 x 1.5
M25 x 1.5
M32 x 1.5
M40 x 1.5
M50 x 1.5
M63 x 1.5
M75 x 1.5
M90 x 1.5
M110x 1.5
Min
6.5
10
11
14
20
25
38
55
48
Max
11
15
18
24
27
35
57
67
80
Minimum
thread length
C (mm)
16
16
16
16
16
16
17
17
17
Ordering
code
708001
708002
708003
708004
708005
708006
708013
708014
708015
Weight
(kg)
Across flats
D (mm)
37
40
40
45
50
57
65
85
105
Across corners
E (mm)
30
36
41
50
60
70
102
110
140
34
41
46
55
65
75
110
115
145
Nominal
protrusion
length F (mm)
Gland
size
20
25
32
40
50
63
75
90
110
Standard
entry thread
A
M20 x 1.5
M25 x 1.5
M32 x 1.5
M40 x 1.5
M50 x 1.5
M63 x 1.5
M75 x 1.5
M90 x 1.5
M110 x 1.5
Standard
entry thread
G
M20 x 1.5
M25 x 1.5
M32 x 1.5
M40 x 1.5
M50 x 1.5
M63 x 1.5
M75 x 1.5
M90 x 1.5
M110 x 1.5
Cable outer diameter B (mm)
MaxMin
10
12
15
18
26
30
38
55
48
14
17
23
30
37
47
57
67
80
Minimum
thread length
C (mm)
15
15
17
17
17
17
17
17
17
Ordering
code
708007
708008
708009
708010
708011
708012
708016
708017
708018
Weight
(kg)
Across flats
D (mm)
51
51
65
68
68
73
73
73
78
Across corners
E (mm)
36
41
50
60
70
78
102
110
140
41
46
55
63
75
85
110
115
145
Nominalprotrusion
length F (mm)
Steel pipe wiring selection table
Cable wiring selection table
A
D C
B
G
Steel pipe wiring selection table
AB
D C
F
E
Cable wiring selection table
F
E
0.20
0.25
0.40
0.60
0.75
1.15
1.50
1.80
3.50
0.15
0.25
0.40
0.55
0.65
0.90
1.10
1.30
1.60
Technical data
Explosion-proof cable glands DQM-II Ex d (unarmored single seal)
Explosion protection
Gas explosion protection
Dust explosion protection
Certificates
Conformity to standards
Gland material
Degree of protection
Ambient temperature
Connection thread
II 2 G Ex d IIC Gb II 2 G Ex e IIC Gb
II 2 D Ex tb IIIC Db IP65
LCIE 06 ATEX 6100; IECEx LCI 08.0011
EN 60079-0:2009, EN 60079-1:2007, EN 60079-7:2007, EN 60079-31:2009
IEC 60079-0:2011, IEC 60079-1:2007, IEC 60079-7:2006, IEC 60079-31:2008
Stainless steel, nickel plated brass or galvanized carbon steel
IP65
-20℃~+55℃(-60℃~+100℃ optoonal)
Metric thread is standard type; G thread or NPT thread is optional
7
7/22
Cable Glands
DQM-II Series Explosion-proof Cable Glands (Ex d IIC)
Armored Dual Seal
Cable Glands
DQM-II Series Explosion-proof Cable Glands
(Ex d IIC) Armored Dual Seal
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Zone 21 and Zone 22
Class I, Zone 1 and Zone 2
Class I, Division 1, Groups A , B, C, D
Ex d structure; available in stainless steel, nickel plated brass
or galvanized carbon steel.
Dual seal, suitable for both armored and unarmored cable.
Technical data
Explosion-proof cable glands DQM-II Ex d (armored dual seal)
Explosion protection
Gas explosion protection
Dust explosion protection
Certificates
Conformity to standards
Gland material
Degree of protection
Ambient temperature
Connection thread
Note: 1. Standard material is nickel plated brass. Stainless steel or galvanized carbon steel is optional. Weight above is based upon nickel plated brass. 2. Supplied without locknut. 3. Earth lug and shroud on request. See P7/31.
7
7/23
Cable Glands
DQM-II Series Explosion-proof Cable Glands (Ex d IIC)
Armored Dual Seal
http:// www.waromgroup.comGeneral Catalogue 01.01.2013http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Steel pipe wiring selection table
Ordering
code
709013
709014
709015
709016
709017
709018
709019
709020
709021
709022
709023
709024
709031
709032
709033
709034
709035
709036
Weight
(kg)Gland
size
Standard
entry thread
A
Cable outer diameter B (mm)
MaxMin
Standard
entry thread
H
20S
20
25S
25
32S
32
40S
40
50S
50
63S
63
75S
75
90S
90
110S
110
M20 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
M125 x 1.5
4
7
11
11
15
15
19
19
22
27
30
36
36
30
30
38
38
48
9
11
17
17
22
22
25
25
27
32
36
41
41
50
50
57
57
80
6
9
14
14
19
19
24
27
29
34
38
44
44
47
47
55
55
62
12
15
22
22
28
28
28
33
35
41
45
52
52
74
74
87
87
103
Minimum thread length
D (mm)
15
15
15
15
17
17
19
19
19
19
19
19
19
19
19
19
19
19
MaxMin
Cable outer diameter C (mm)
Acrossflats
E (mm)
75
75
76
76
83
83
89
89
98
98
106
106
106
145
145
161
161
167
AcrosscornersF (mm)
27
27
27
34
34
41
41
50
50
60
60
72
72
100
100
115
115
128
30
30
30
37
37
45
45
55
55
65
65
77
77
105
105
120
120
135
Nominalprotrusion
length G (mm)
Cable wiring selection table
Gland
size
Standard
entry thread
A
20S
20
25S
25
32S
32
40S
40
50S
50
63S
63
75S
75
90S
90
110S
110
M20 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
Cable outer diameter B (mm)
Min
4
7
7
11
11
15
19
19
22
27
30
36
36
30
30
38
38
48
Max
9
11
11
17
17
22
25
25
27
32
36
41
41
50
50
57
57
80
Cable outer diameter C (mm)
Min
6
9
9
14
14
19
24
27
29
34
38
44
44
47
47
55
55
62
Max
12
15
15
22
22
28
28
33
35
41
45
52
52
74
74
87
87
103
Minimum
thread length
D (mm)
15
15
15
15
17
17
19
19
19
19
19
19
19
19
19
19
19
19
Ordering
code
709001
709002
709003
709004
709005
709006
709007
709008
709009
709010
709011
709012
709025
709026
709027
709028
709029
709030
Weight
(kg)
Across flats
E (mm)
59
59
59
60
60
65
71
71
80
80
88
88
88
124
126
143
143
148
Across corners
F (mm)
27
27
27
34
34
41
41
50
50
60
60
72
72
100
100
115
115
128
30
30
30
37
37
45
45
55
55
65
65
77
77
105
105
120
120
135
Nominalprotrusion
length G (mm)
Cable wiring selection table
G
F
A
D
BC
E
Steel pipe wiring selection table
E D F
CH A GB
0.20
0.19
0.24
0.23
0.27
0.25
0.33
0.30
0.40
0.37
0.49
0.46
2.90
2.80
3.80
3.70
5.00
4.90
0.15
0.14
0.19
0.18
0.22
0.20
0.28
0.25
0.35
0.32
0.44
0.41
3.10
3.00
4.00
3.90
5.20
5.10
II 2 G Ex d IIC Gb II 2 G Ex e IIC Gb
II 2 D Ex tb IIIC Db IP66
LCIE 06 ATEX 6100; IECEx LCI 08.0011
EN 60079-0:2009, EN 60079-1:2007, EN 60079-7:2007, EN 60079-31:2009
IEC 60079-0:2011, IEC 60079-1:2007, IEC 60079-7:2006, IEC 60079-31:2008
Stainless steel, nickel plated brass or galvanized carbon steel
IP66
-20℃~+55℃(-60℃~+100℃ optoonal)
Metric thread is standard type; G thread or NPT thread is optional.
Cable wiring
Steel pipe wiring
7
7/22
Cable Glands
DQM-II Series Explosion-proof Cable Glands (Ex d IIC)
Armored Dual Seal
Cable Glands
DQM-II Series Explosion-proof Cable Glands
(Ex d IIC) Armored Dual Seal
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Zone 21 and Zone 22
Class I, Zone 1 and Zone 2
Class I, Division 1, Groups A , B, C, D
Ex d structure; available in stainless steel, nickel plated brass
or galvanized carbon steel.
Dual seal, suitable for both armored and unarmored cable.
Technical data
Explosion-proof cable glands DQM-II Ex d (armored dual seal)
Explosion protection
Gas explosion protection
Dust explosion protection
Certificates
Conformity to standards
Gland material
Degree of protection
Ambient temperature
Connection thread
Note: 1. Standard material is nickel plated brass. Stainless steel or galvanized carbon steel is optional. Weight above is based upon nickel plated brass. 2. Supplied without locknut. 3. Earth lug and shroud on request. See P7/31.
7
7/23
Cable Glands
DQM-II Series Explosion-proof Cable Glands (Ex d IIC)
Armored Dual Seal
http:// www.waromgroup.comGeneral Catalogue 01.01.2013http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Steel pipe wiring selection table
Ordering
code
709013
709014
709015
709016
709017
709018
709019
709020
709021
709022
709023
709024
709031
709032
709033
709034
709035
709036
Weight
(kg)Gland
size
Standard
entry thread
A
Cable outer diameter B (mm)
MaxMin
Standard
entry thread
H
20S
20
25S
25
32S
32
40S
40
50S
50
63S
63
75S
75
90S
90
110S
110
M20 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
M125 x 1.5
4
7
711
1115
19
19
22
27
30
36
36
30
30
38
38
48
9
11
1117
1722
25
25
27
32
36
41
41
50
50
57
57
80
6
9
914
1419
24
27
29
34
38
44
44
47
47
55
55
62
12
15
1522
2228
28
33
35
41
45
52
52
74
74
87
87
103
Minimum thread length
D (mm)
15
15
15
15
17
17
19
19
19
19
19
19
19
19
19
19
19
19
MaxMin
Cable outer diameter C (mm)
Acrossflats
E (mm)
75
75
76
76
83
83
89
89
98
98
106
106
106
145
145
161
161
167
AcrosscornersF (mm)
27
27
27
34
34
41
41
50
50
60
60
72
72
100
100
115
115
128
30
30
30
37
37
45
45
55
55
65
65
77
77
105
105
120
120
135
Nominalprotrusion
length G (mm)
Cable wiring selection table
Gland
size
Standard
entry thread
A
20S
20
25S
25
32S
32
40S
40
50S
50
63S
63
75S
75
90S
90
110S
110
M20 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
Cable outer diameter B (mm)
Min
4
7
7
11
11
15
19
19
22
27
30
36
36
30
30
38
38
48
Max
9
11
11
17
17
22
25
25
27
32
36
41
41
50
50
57
57
80
Cable outer diameter C (mm)
Min
6
9
9
14
14
19
24
27
29
34
38
44
44
47
47
55
55
62
Max
12
15
15
22
22
28
28
33
35
41
45
52
52
74
74
87
87
103
Minimum
thread length
D (mm)
15
15
15
15
17
17
19
19
19
19
19
19
19
19
19
19
19
19
Ordering
code
709001
709002
709003
709004
709005
709006
709007
709008
709009
709010
709011
709012
709025
709026
709027
709028
709029
709030
Weight
(kg)
Across flats
E (mm)
59
59
59
60
60
65
71
71
80
80
88
88
88
124
126
143
143
148
Across corners
F (mm)
27
27
27
34
34
41
41
50
50
60
60
72
72
100
100
115
115
128
30
30
30
37
37
45
45
55
55
65
65
77
77
105
105
120
120
135
Nominalprotrusion
length G (mm)
Cable wiring selection table
G
F
A
D
BC
E
Steel pipe wiring selection table
E D F
CH A GB
0.20
0.19
0.24
0.23
0.27
0.25
0.33
0.30
0.40
0.37
0.49
0.46
2.90
2.80
3.80
3.70
5.00
4.90
0.15
0.14
0.19
0.18
0.22
0.20
0.28
0.25
0.35
0.32
0.44
0.41
3.10
3.00
4.00
3.90
5.20
5.10
II 2 G Ex d IIC Gb II 2 G Ex e IIC Gb
II 2 D Ex tb IIIC Db IP66
LCIE 06 ATEX 6100; IECEx LCI 08.0011
EN 60079-0:2009, EN 60079-1:2007, EN 60079-7:2007, EN 60079-31:2009
IEC 60079-0:2011, IEC 60079-1:2007, IEC 60079-7:2006, IEC 60079-31:2008
Stainless steel, nickel plated brass or galvanized carbon steel
IP66
-20℃~+55℃(-60℃~+100℃ optoonal)
Metric thread is standard type; G thread or NPT thread is optional.
Cable wiring
Steel pipe wiring
7
7/24
Cable Glands
DQM-III Series Explosion-proof Cable Glands (Ex d IIC)
Armored Compound Barrier
Cable Glands
DQM-III Series Explosion-proof Cable Glands
(Ex d IIC) Armored Compound Barrier
◆
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Zone 21 and Zone 22
Class I, Zone 1 and Zone 2
Class I, Division 1, Groups A , B, C, D
Ex d structure; available in stainless steel, nickel plated brass
or galvanized carbon steel.
With seal ring and sealing compound; suitable for armored
cable.
The compound consists of type A and type B; it can solidify
after mixing together.
Note: 1. Standard material is nickel plated brass. Stainless steel or galvanized carbon steel is optional. Weight above is based upon nickel plated brass. 2. Supplied without locknut. 3. Earth lug and shroud on request. See P7/31.
7
7/25
Cable Glands
DQM-III Series Explosion-proof Cable Glands (Ex d IIC)
Armored Compound Barrier
Steel pipe wiring selection table
Ordering
code
Weight
(kg)Gland
size
Standard
entry thread
A
Cable outer diameter B (mm)
Standard
entry thread
H
Minimum
thread length
D (mm)Max MaxMin
Cable outer diameter C (mm)
20S
20
25S
25
32S
32
40S
40
50S
50
63S
63
75S
75
90S
90
110S
110
M20 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
M125 x 1.5
11
11
11
16
16
22
25
25
33
33
42
42
42
50
50
57
57
80
6
9
14
14
19
19
24
27
29
34
38
44
44
47
147
55
55
62
12
15
22
22
28
28
28
33
35
41
45
52
52
74
74
87
87
103
15
15
15
15
17
17
19
19
19
19
19
19
19
19
19
19
19
19
710013
710014
710015
710016
710017
710018
710019
710020
710021
710022
710023
710024
710031
710032
710033
710034
710035
710036
http:// www.waromgroup.comGeneral Catalogue 01.01.2013http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Cable wiring selection table
Gland
size
Standard
entry thread
A
Cable outer diameterB (mm)
Max
Cable outer diameter C (mm)
MaxMin
20S
20
25S
25
32S
32
40S
40
50S
50
63S
63
75S
75
90S
90
110S
110
M20 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
11
11
11
16
16
22
25
25
33
33
42
42
42
50
50
57
57
80
6
9
9
14
14
19
24
27
29
34
38
44
44
47
47
55
55
62
12
15
15
22
22
28
28
33
35
41
45
52
52
74
74
87
87
103
Minimum
thread length
D (mm)
30
30
30
37
37
45
45
55
55
65
65
77
77
105
105
120
120
135
Ordering
code
710001
710002
710003
710004
710005
710006
710007
710008
710009
710010
710011
710012
710025
710026
710027
710028
710029
710030
Weight
(kg)
Acrossflats
E (mm)
15
15
15
15
17
17
19
19
19
19
19
19
19
19
19
19
19
19
AcrosscornersF (mm)
50
50
50
50
50
55
58
58
67
67
73
73
73
94
96
108
108
110
27
27
27
34
34
41
41
50
50
60
60
72
72
100
100
115
115
128
Nominalprotrusion
length G (mm)
Acrossflats
E (mm)
66
66
67
66
73
73
76
76
85
85
91
91
91
115
117
126
126
129
AcrosscornersF (mm)
27
27
27
34
34
41
41
50
50
60
60
72
72
100
100
115
115
128
30
30
30
37
37
45
45
55
55
65
65
77
77
105
105
120
120
135
Nominalprotrusion
length G (mm)
Cable wiring selection table
Steel pipe wiring selection table
E D F
CH A GB
G
F
A
D
BC
E
0.12
0.11
0.16
0.15
0.19
0.17
0.25
0.22
0.32
0.29
0.41
0.38
3.00
2.90
3.90
3.80
5.00
4.90
0.17
0.16
0.21
0.20
0.24
0.22
0.30
0.27
0.37
0.34
0.46
0.43
2.80
2.70
3.70
3.60
4.80
4.70
Technical data
Explosion-proof cable glands DQM-III Ex d (armored compound barrier)
Explosion protection
Gas explosion protection
Dust explosion protection
Certificates
Conformity to standards
Gland material
Degree of protection
Ambient temperature
Connection thread
II 2 G Ex d IIC Gb II 2 G Ex e IIC Gb
II 2 D Ex tb IIIC Db IP66
Nemko 10 ATEX 1005X; IECEx CQM 11.0028
EN 60079-0:2009, EN 60079-1:2007, EN 60079-7:2007, EN 60079-31:2009
IEC 60079-0:2011, IEC 60079-1:2007, IEC 60079-7:2006, IEC 60079-31:2008
Stainless steel, nickel plated brass or galvanized carbon steel
IP66
-20℃~+55℃(-60℃~+100℃ optoonal)
Metric thread is standard type; G thread or NPT thread is optional
Cable wiring
Steel pipe wiring
7
7/24
Cable Glands
DQM-III Series Explosion-proof Cable Glands (Ex d IIC)
Armored Compound Barrier
Cable Glands
DQM-III Series Explosion-proof Cable Glands
(Ex d IIC) Armored Compound Barrier
◆
◆
◆
◆
◆
Explosion protection to
-CENELEC
-IEC
-NEC
Can be used in
Zone 1 and Zone 2
Zone 21 and Zone 22
Class I, Zone 1 and Zone 2
Class I, Division 1, Groups A , B, C, D
Ex d structure; available in stainless steel, nickel plated brass
or galvanized carbon steel.
With seal ring and sealing compound; suitable for armored
cable.
The compound consists of type A and type B; it can solidify
after mixing together.
Note: 1. Standard material is nickel plated brass. Stainless steel or galvanized carbon steel is optional. Weight above is based upon nickel plated brass. 2. Supplied without locknut. 3. Earth lug and shroud on request. See P7/31.
7
7/25
Cable Glands
DQM-III Series Explosion-proof Cable Glands (Ex d IIC)
Armored Compound Barrier
Steel pipe wiring selection table
Ordering
code
Weight
(kg)Gland
size
Standard
entry thread
A
Cable outer diameter B (mm)
Standard
entry thread
H
Minimum
thread length
D (mm)Max MaxMin
Cable outer diameter C (mm)
20S
20
25S
25
32S
32
40S
40
50S
50
63S
63
75S
75
90S
90
110S
110
M20 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
M125 x 1.5
11
11
11
16
16
22
25
25
33
33
42
42
42
50
50
57
57
80
6
9
14
14
19
19
24
27
29
34
38
44
44
47
147
55
55
62
12
15
22
22
28
28
28
33
35
41
45
52
52
74
74
87
87
103
15
15
15
15
17
17
19
19
19
19
19
19
19
19
19
19
19
19
710013
710014
710015
710016
710017
710018
710019
710020
710021
710022
710023
710024
710031
710032
710033
710034
710035
710036
http:// www.waromgroup.comGeneral Catalogue 01.01.2013http:// www.waromgroup.comGeneral Catalogue 01.01.2013
Cable wiring selection table
Gland
size
Standard
entry thread
A
Cable outer diameterB (mm)
Max
Cable outer diameter C (mm)
MaxMin
20S
20
25S
25
32S
32
40S
40
50S
50
63S
63
75S
75
90S
90
110S
110
M20 x 1.5
M20 x 1.5
M25 x 1.5
M25 x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
M90 x 1.5
M90 x 1.5
M110 x 1.5
M110 x 1.5
11
11
11
16
16
22
25
25
33
33
42
42
42
50
50
57
57
80
6
9
9
14
14
19
24
27
29
34
38
44
44
47
47
55
55
62
12
15
15
22
22
28
28
33
35
41
45
52
52
74
74
87
87
103
Minimum
thread length
D (mm)
30
30
30
37
37
45
45
55
55
65
65
77
77
105
105
120
120
135
Ordering
code
710001
710002
710003
710004
710005
710006
710007
710008
710009
710010
710011
710012
710025
710026
710027
710028
710029
710030
Weight
(kg)
Acrossflats
E (mm)
15
15
15
15
17
17
19
19
19
19
19
19
19
19
19
19
19
19
AcrosscornersF (mm)
50
50
50
50
50
55
58
58
67
67
73
73
73
94
96
108
108
110
27
27
27
34
34
41
41
50
50
60
60
72
72
100
100
115
115
128
Nominalprotrusion
length G (mm)
Acrossflats
E (mm)
66
66
67
66
73
73
76
76
85
85
91
91
91
115
117
126
126
129
AcrosscornersF (mm)
27
27
27
34
34
41
41
50
50
60
60
72
72
100
100
115
115
128
30
30
30
37
37
45
45
55
55
65
65
77
77
105
105
120
120
135
Nominalprotrusion
length G (mm)
Cable wiring selection table
Steel pipe wiring selection table
E D F
CH A GB
G
F
A
D
BC
E
0.12
0.11
0.16
0.15
0.19
0.17
0.25
0.22
0.32
0.29
0.41
0.38
3.00
2.90
3.90
3.80
5.00
4.90
0.17
0.16
0.21
0.20
0.24
0.22
0.30
0.27
0.37
0.34
0.46
0.43
2.80
2.70
3.70
3.60
4.80
4.70
Technical data
Explosion-proof cable glands DQM-III Ex d (armored compound barrier)
Explosion protection
Gas explosion protection
Dust explosion protection
Certificates
Conformity to standards
Gland material
Degree of protection
Ambient temperature
Connection thread
II 2 G Ex d IIC Gb II 2 G Ex e IIC Gb
II 2 D Ex tb IIIC Db IP66
Nemko 10 ATEX 1005X; IECEx CQM 11.0028
EN 60079-0:2009, EN 60079-1:2007, EN 60079-7:2007, EN 60079-31:2009
IEC 60079-0:2011, IEC 60079-1:2007, IEC 60079-7:2006, IEC 60079-31:2008
Stainless steel, nickel plated brass or galvanized carbon steel
IP66
-20℃~+55℃(-60℃~+100℃ optoonal)
Metric thread is standard type; G thread or NPT thread is optional
Cable wiring
Steel pipe wiring