IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 29 NO. 1 JANUARYIFEBRUAKY 1993
Control of Parallel Connected Inverters
in Standalone ac Supply Systems
Mukul
C.
Chandorkar ,
Student Member IEEE
Deepakra j
M.
Divan, Member
IEEE
a nd R a mba bu Ada pa , Senior Member
IEEE
Abstract-A scheme for controlling parallel-connected invert-
ers in a standalone ac supply system is presented in this paper.
This scheme is suitable for control of inverters in distributed
source environments such as in isolated ac systems, large and
distributed uninterruptible power supply (UPS) systems, photo-
voltaic systems connected to ac grids, and low-voltage dc power
transmission meshes. A key featur e of the control scheme is that
it uses feedback of only those variables that can be measured
locally at the inverte r and does not need comm unication of control
signals between the inverters. This is essential for the operation
of large ac systems, where distances between inverters make
comm unication imprac tical. It is also important in high-reliability
UPS systems where system operation can be maintained in the
face of a communication breakdown. Real and reactive power
sharing between inverters can be achieved by controlling two
independent quantities-the power angle, and the fundamental
inverter voltage magn itude. Simulation results obtained with the
control scheme are also presented.
I. INTRODUCTION
S
DC
TO
AC pow er converters feeding power to ac sup-
A
ly systems become more numerous, the issues relating
to their control need to be addressed in greater detail. Inverters
connecting dc power supplies to ac systems occur in numerous
applications. Photovoltaic power plants and battery storage
installations are examples of such applications. In either case,
the inverter interfaces could be connected to a common ac
system. Distributed uninterruptible power supply (UPS) sys-
tems feeding power to a common ac system are also possible
examples. In addition, over the past several years, there has
been considerable interest in applying inverter technology to
low voltage dc (LVDC) meshed power transmission systems.
The feasibility from the control viewpoint
of
an LVDC mesh
has been demonstrated in
[l]
The transmission system could
typically consist of inverters connected at several points on
the LVDC mesh, providing power to ac systems that could
be interconnected as well. Multiple inverters connected to a
common ac system essentially operate in parallel and need to
be controlled in a manner that ensures stable operation and
prevents inverter overloads. Although inverter topologies used
Paper IPCSD 92-16, approved by the Industrial Power Converter Committee
of the IEEE Industry Applications Society for presentation at the 1991 Industry
Applications Society Annual Meeting, Dearborn, MI, September 28-October
4.
This
work was supported by
NSF
grant 8 818 339 and EPRI Agreement
RP7911-12. Manuscript released for publication April 25, 1992.
M. C. Chandorkar and D. M. Divan are with the Department of Electrical
and Computer Engineering, University of Wisconsin, Madison, WI 53706.
R. Adapa is with the Electric Power Research Institute, Palo Alto, CA
94303.
IEEE
Log
Number 9204199.
Jnvener
""f
Fig. 1. Inverter connected to stiff ac system.
for power transmission have traditionally been current sourced,
in recent years, voltage source inverters (VSI) have been
increasingly used for high-power applications like electric
traction and mill drives, photovoltaic power systems, and
battery storage systems. Control schemes for VSI's in power
system environments have formed the topic of recent work
[2]. Further, with inverter topologies like the neutral-point
clamped (NPC) inverter
[3],
it is possible to achieve substan-
tial harmonic reduction at reasonably low PWM switching
frequencies.
A standalone ac system may be described as one in which
the entire ac power is delivered to the system through inverters.
In a standalone ac system, there are no synchronous alternators
present in the system that would provide a reference for the
system frequency and voltage. All inverters in the system need
to be o perated to provide a stable frequency and voltage in the
presence of arbitrarily varying loads. This paper first develops
a control method for an inverter feeding real and reactive
power into a stiff ac system with a defined voltage, as shown
in Fig.
1.
This forms the basis of a control method suitable for
standalone operation. The inverter is a VSI with gate turn-off
(GTO) thyristor switches, operating from a dc power source,
and feeding into the ac system through a filter inductor. In
a standalone system, a filter capacitor is needed to suppress
the voltage harmonics of the inverter. The requirements for
controlling such an interface are described in the next section.
Later sections describe the development of an effective control
scheme to meet these requirements and present simulation
results obtained from the study of a power distribution system
with parallel-connected inverters.
11.
REQUIREMENTS
OF THE CONTROL SYSTEM
The control of inverters used to supply power to an ac
system in a distributed environment should be based on
information that is available locally at the inverter. In typical
power systems, large distances between inverters may make
communication of information between inverters impractical.
Comm unication of information may be used to enhance system
0093-9994/93 03.00
0
993 IEEE
-
8/10/2019 C1_Control of Parallel Connected Inverters...
2/8
CHANDORKAR er
al.:
CONTROL OF PARALLEL-CONNECTED INVERTERS
137
I
3 I 2
P=X L
sin6
w Lf
Q =*
=cos6
w
Lf w Lf
Fig. 2.
Real and
reactive power
flows.
performance but must not be cr itical for system opera tion. This
essentially implies that inverter control should be based on
terminal quantities.
It is well known that stable operation of a power system
needs good control of the real power flow P and the reactive
power flow Q. The
P
and Q flows in an ac system are
decoupled to a good extent [4].
P
depends predominantly on
the power angle, and
Q
depends predominantly on the voltage
magnitude. This is illustrated in Fig. 2.It is essential to have
good control of the pow er angle and the voltag e level by means
of the inverter. Control of frequency dynamically controls
the power angle and, thus, the real power flow. To avoid
overloading the inverters , it is im portant to ensure that cha nges
in load are taken up by the inverters in a predetermined manner
without communication. This is achieved in conventional
power systems with m ultiple generators by introducing a droop
in the frequency of each generator with the real power P
delivered by the generator [4]. This permits each generator to
take up changes in total load in a manner determined by its
frequency droop cha racteristics and es sentially utilizes the sys-
tem frequency as a comm unication link between the gene rator
control systems. In this paper, the sam e philosophy
is
used to
ensure reasonable distribution of total power betwee n parallel-
connected inverters in a standalone ac system. Similarly, a
droop in the voltage with reactive power is used to ensure
reactive power sharing.
An important aspect of the control methodology developed
here is that it is highly modular in nature. Thus, the basic
control scheme can be very easily adapted to mee t variations in
the configuration of the power system, as show n in Sections 111
and IV. This modularity is achieved by choosing the controlled
quantities of the slow, outer control loops to meet the d ictates
of the power system configuration while maintaining the same
fast, inner inverter control structure. The controller for an
inverter connected to a stiff ac system, which is detailed
in Section 111, is easily modified for the control of parallel-
connected inverters feeding a standalone ac system, which is
detailed in Section IV.
111. CONTROL OF SINGLE INVERTER
FEEDINGNTO A STIFF SYSTEM
The power schematic of Fig. 1shows a single inverter
connected to a stiff ac system through a filter inductor.
The inverter is assumed to be a six-pulse GTO VSI. This
section details the control of the inverter based on feedback
of quantities measured locally at the inverter. The real and
reactive power fed into the ac system are the two va riables that
are controlled by the inverter. Given set points for the real and
V
d
1 :
nverter
Voltage
Vwtor
0:e I
For Choice
of
Inverter
Voltage Vector
(a)
1 2 3 4
(b)
Fig.
3.
(a) Inverter output voltage vectors; (b) inverter switch positions.
reactive power
P
and
Q*,
the real and reactive power P and
Q fed by the inv erter into the ac system c an be c ontrolled by
a me thod that controls the time integral of the inverter output
voltage space vector. This concept has previously been applied
extensively to ac motor drives
[ 5 ] , [6].
The entire control
of
the inverter is performed in th e stationary d-q reference frame
and is essentially vector control. The transformation from the
physical a-b-c reference frame to the stationary d-q-n reference
frame is described by the following equations [7].
In these equations, the quantity generically denotes a
physical quantity, such as a voltage or a current. In the absence
of a neutral c onnection, the quantity f n is of no interest. For
a six-pulse VSI, the inverter output voltage space vector can
take any of seven positions in the plane specified by the d-q
coordinates. These are shown in Fig.
3
as the vectors
0-6.
The time integral of the inverter output voltage space vector
is called the inverter flux vector for short. The flux vector
does not have the same significance as in motor applications.
Rather, it is a fictitious quantity related to the volt-seconds in
the filter inductor. The
d
and
q
axis components of the inverter
-
8/10/2019 C1_Control of Parallel Connected Inverters...
3/8
138
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL.
29
NO. 1, JANUARY/FEBRUARY 1993
P I
Regulator
P' & Q*
:
Set Points for Real & Reactive Power
L o w
Pass
Filter
Fig. 4.
Inverter
control scheme-stiff ac system.
flux vector are defined as
t
d u
=
d d r (4)
--CO
t
,U
= / ( 5 )
CO
The magnitude of & is
The angle of
5
ith respect to the y axis is
6 = tan- 7 )
The d and
y
axis components of the ac system voltage flux
vector 5 ts magnitude, and angle are defined in a similar
manner. The angle between
(8)
and6 s defined as
6 = 6 Se.
Control of the flux vector has been shown
to
have good
dynamic and steady-state performance [ 5 ] , 6]. It also provides
a convenient means to define the power a ngle since the inverter
voltage vector switches position in the
d - y
plane, whereas
there is no discontinuity in the inverter flux vector. It is useful
to develop the power transfer relationships in terms of the
flux vectors. The basic real power transfer relationship for the
system of Fig. 1 in the d-q reference frame is
(9)
3
2
P
= - eq i ,
+ e d i d ) .
In (9), e , and e d are the q- and d-axis components, respec-
tively, of the ac system voltage vector
E .
n addition, i, and i d
are the components of the current vector
7.
When i , and
i d
are
expressed in terms of the fluxes, the equation is expressed as
Taking into account the spatial relationships between the
two flux vectors and assuming the ac system voltage to be
sinusoidal, (10) can be expressed as
w , , sin
6.
= -
3
2L.f
In this expression, and are the magnitudes of the ac
system and the inverter flux vectors, respectively, and 6
is
the
spatial angle between the two flux vectors.
w
is the frequency
of rotation of the two flux vectors. The expression for reactive
power transfer for Fig. 1can be derived in a similar manner.
This is
(12)
w
Q = - U , C O S
-
/ 5 3 .
2 L.f
Equations (11) and (12) indicate that P can be controlled
by controlling
S
which can be defined as the power angle,
and Q can be controlled by controlling &,. The cross coupling
between the control of
P
and
Q
is also apparent from these
equations.
The control system for the inverter is given in Fig. 4.The
two variables that are controlled directly by the inverter are
is controlled to have a specified
magnitude and a specified position relative to the ac system
flux vector6.his control forms the innermost control loop
and is very fast. It is noted that both the inverter and the
and
6.
The vector
-
8/10/2019 C1_Control of Parallel Connected Inverters...
4/8
CHANDORKAR
t al :
CONTROL OF PARALLEL-CONNECTED INVERTERS
139
TABLE
CHOICE
F
SWITCHINGVECTOR
Sector
No.
(Location
of z)
I
I I m r v v v 1
Increase
2 3 4 5 6 1
Decrease &
3
4 5 6 1 2
(The zero vector
is
chosen to decrease
4,
ac system voltage space vectors ,are obtained by me asuring
instantaneous voltage values that are available locally. The se t
points for the controller are
P
and
Q*,
and the set points for
the innermost control loop
:
and
6
are derived from these.
The a ctual values of P and Q calculated from the feedback are
compared with the se t values. The error drives a proportional-
integral (P-I) regulator, which generates the set points and
6
for the innermost control loop. The control of the inve rter
to generate the specified
,
and 6 is detailed in the next
subsection.
A. Control of and
6
The control of 4, and 6 forms the first level of control
and directly controls the inverter switching. The choice of
the inverter switching vector is made on the basis of the
deviations of ,, and 6 from the set values
:
and 6
and the position of the inverter flux vector in the
d-q
plane
give n by 6,. If the devia tion of 6 from 6 is more than
a specified limit, a zero switching vector is chosen. If this
deviation is less than a specified limit or if
,
deviates from
by more than a specified amount, a switching vector that
increases 6 and changes in the correct direction is chosen.
This is essentially accomplished by hysteresis comparators for
the set values and then using a look-up table to choose the
correct inverter output voltage vector. The c onsiderations for
developing the look-up table are de alt with in [ 5 ] .The choice
of
inverter switching vector is dictated by the value of
6,.
The d-q plane is divided into six sectors for 6 as shown in
Fig. 3(a), which also shows the inverter switching vectors.
The inverter switch positions for the vectors are show n in Fig.
3(b). The value of 6, determ ines the cho ice of two possible
inverter switching vectors apart from the zero vector. One
vector increases the magnitude
,,
and the other decreases
it, whereas both tend to increase 6,. Thus, to decreas e 6 the
zero switching vector is chosen. To correct the value of ,,,
one of the two active switching vectors is chosen, depending
on the sign of the correction required. Table I gives the ch oice
of active vectors for given positions of the inverter flux vector,
which is specifie d by 6,. In this man ner, and 6 are tightly
controlled to lie within specified hysteresis bands by means
of inverter switching. The tip of the inverter flux vector is
guided along
an
almost circular path. Control of and
6
in this manner results in a PWM voltage waveform at the
inverter output.
.ii
3 3
N
10
c
-
L I U 6 00
-2.011 2 00
6
00 In
h v VS
Fig.
5.
Inverter
flux
vector.
I
1.694
1l.727
1l.760 1'.794 1l.827
s
1'.860
T
*10-1
Fig.
6.
Inverter voltage and current waveforms.
the power system of Fig. 1are presented in Figs.
5-7.
The dc
bus voltage is taken to be 10 kV, and the line-to-line voltage
of the ac system is taken to be 3.3 kV rms. The inductor L
is 17 mH. Fig. 5gives the plot of the locus of the inverter
flux vector6.he locus is seen to be close to a circle since
the magnitude , is very tightly controlled. Fig. 6 shows the
inverter line-to-line voltage ? and the inverter line current u
for
P*
=
1
MW and Q* =
500
kvar.Fig.7shows the response
of the inverter
to
step changes in Q* and P*, uccessive ly. It
is noted that there is a disturbance in P when Q* is changed
and a disturba nce in
Q
when P* is changed. In eac h case, the
P-I regulators modify the set values of
6
and
4,:
to main
the P and the Q at the set values. In addition, the tight contro
of
P
and
Q
within limits is apparent from Fig.
7.
I v . CONTROL
OF INVERTERS
IN A
STANDALONE
SYSTEM
B. Simulation Results
The control of a single inverter feeding a stiff ac system
based only on instantaneous measurement of terminal quanti-imulation results of the c ontrol scheme of Fig. 4applied to
-
8/10/2019 C1_Control of Parallel Connected Inverters...
5/8
140
IEEE TRANSACTIONS ON INDUSTRY A PPLICATIONS,
VOL.
29, NO. 1, JANUARYFEBRUARY 1993
I I I I
I
o l
I
I
0 .02 0.06 0.11 0.15 0 .20 S 0 . 2 5
T
Fig.
7.
Inverter real and reactive power.
Fig. 8. Standalone ac system.
ties now forms the basis of the control scheme for multiple
inverters in standalone system environments. The essential
difference in the control scheme is that in the standalone
system, there is no ac side voltage available for reference. The
inverters themselves produce the ac system voltage, which is
fed back to control the inverters. There is thus a possibility
of contro lling the voltage and the frequency of the ac system
by inverter control. Fig.
8
shows two inverters feeding into
a standalone ac system. The inverters are interfaced to the ac
system through
LC
filters. The two inverters are connected by
a tie line, and each inverter has a local load. The dc power
source represents a 10-kV dc power transmission mesh. The
nominal voltage on the ac system is
3.6
kV rms line to line, and
the nominal frequency is 60 Hz.
Each inverter is a six-pulse
VSI made up of GTO switches.
Fig. 9 shows the block diagram of the control of inverters
in a standalone system.
As
in the sing le inverter case, the two
variables that are directly controlled are
and
6
for each
inverter. Middle control loops are then used to control the
magnitude and angular frequency of the ac system voltage
frequency of are obtained from the outermost loop, which
implements specified droop characteristics for the frequency
with
P
and magnitude with Q , as mentio ned in Section 11. The
entire control
is,
thus, a three-level structure. The innermost
control level controls and 6 and is the same as that
described in the previous section. The second level controls
the ac side frequency and the voltage at each inverter and
provides set points
6
and for the innermost level. The
third level computes the set points for frequency and voltage
for each inverter. The two outer control levels are described
below.
A . Control of Frequency and Voltage
The frequency co ntroller determines the setpoint
6
that
is
needed to attain the specified frequency. The structure of the
frequency controller is given in Fig.
10.
The frequency setting
w* is integrated to obtain a reference for the position 6:c of
the ac system voltage vector across the filter capacitor. This
is compared with the actual position Sa of
E .
The error is
used to drive a P-I regulator, which produces the setpoint
a which is given to the innermost control loop described
previously. This scheme achieves a very tight control
of
the
output frequency since the regulator attempts to control the
output voltage vector angle at every instant.
The voltage controller determines the setpoint that is
needed to attain the specified ac system voltage magnitude.
The voltage controller needs to take care of the filter dynamics
to determine the exact value of
:
The structu re of the voltage
controller is given in Fig.
11.
The controller command input
is
E*,
which is the specified value of the magnitude of
F .
The con troller consists of a com mand feedforward term and a
voltage magnitude feedback term. The command feedforward
term is given by
The command feedforward gives the value of needed to
achieve the specified E* with an unloaded filter and is intended
to speed up the voltage control loop. The voltage magnitude
feedback term is used to generate an error signal that actuates
a P-I controller. The resultant value of is used as a setpoint
for the innermost control loop described previously.
The ac system frequency
w
is computed six times
in
one
cycle. For this purpose, six axes are defined in the d-q plane.
The time taken by the vector
E
to cross from one axis to
the next consecutive axis is used to compute the frequency.
For parallel operation of multiple inverter units, the setpoints
w* and E* need to be chosen to ensure the correct
P
and
Q
sharing between the inverters in response to arbitrary load
changes. This has to be done without communication of the
setpoints between the two inverter systems. The next subsec-
tion describes the outermost control loop, which determines the
setpoints
w*
and
E*
for each inverter system independently
without any signal communication. This is done on the basis
vector
E .
The set points fo r the magnitude and angular
of the real and reac tive power loading of the inverter systems.
-
8/10/2019 C1_Control of Parallel Connected Inverters...
6/8
CHANDORKAR et al.: CONTROL OF PARALLEL-CONNECTED INVERTERS
141
Outer
hop:
Droop
Characteristics
Middle
Loop:
E and Innerbop:
vv
nd Sp
- 1
-- --- --T--
_--
_--
---
I - - - --- --- --
E
I
vv*
I
Droops
I
W V
Inverter nverter I
SYStelll E
Flux
Vector
o a n d ,
Vector
AC System I
Voltage J
Feedback
'
PandQ
E*=f(Q)
Voltage
Vector
Control Calc.
,
1
I
AC System
Voltage
Inverter
Voltage
Feedback
Feedback
E
V
Control
+Inverter
Switches
Fig. 9.
Inverter control scheme-standalone ac system.
*
0
sx I
From Filter
Output
Fig.10.
Frequency contro ller for standalone system.
Regulator
From Filter
Fig. 11 .
Voltage controller for standalone system.
B.
Computing
w*
and
E* for
Parallel Operation
The outermost loop determines the setpoints for w* and
E*
to
ensure correct real and reactive powe r sharing between
the parallel connected inverters. This action is similar to that
used in conventional power systems to ensure the corre ct load
sharing between generators feeding to a common ac system
[4]. or the frequency set point, a droop is defined for the P -
w characteristic of each inverter. The frequency set point is
thus made to dec rease with increasing real power supplied by
the inverter. The P-U* droop characteristic can be described
(13)
by
w t =
W O m,(Po; P,) = g, (P) .
In this expression, =
1
for inverter
1,
and
=
2 for
inverter
2
(Fig. 8). WO is the nominal operating frequency of
the ac system and is taken to be 377 rads
(60
Hz).
Po,
is the
power rating of the ith inve rter, and P, is its actual loading.
The slope of the droop characteristic is
m,
and is numerically
negative. The values of m; for different inverters determine
the relative power sharing between the inverters. In typical
systems, the P-w* characteristics are stiff, and the frequency
change from no load to full load is extremely small. If the
slopes
m,
for different inverters are chosen such that
mlPo2
=
maPo2
= ... =
mnPon
(14)
then for a total power
P ,
the load distribution between the
inverters satisfies the relationships
mlP1 = mzP2
=
...
=
m n P n
(15)
By choosing the slopes according to
(14),
it can be ensured
that load changes are taken up by the inverters in proportion
to their power ratings. The power-sharing mechanism can
be best understood by considering the two-inverter system
shown in Fig. 8. An increase in power drawn by the load
near Inverter 2 results in increased power from both inverters.
If the magnitude of m 2 is larger than that of m l ,
w;
would
tend to drop lower than w: . Hence, the vector
Fz
would lag
the vector
E l ,
and the power flow in the tieline from Inverter
1
to Inverter 2 would increase. Thus, Inverter
1
would take
up a larger proportion of the load. It is possible to define
a composite power-frequency curve for all the inverters in
the system. The composite load curve is likewise defined.
At the steady-state operating point on the composite load-
frequency curve, the total power delivered by the inverters
matches the power consum ed by the loads. Depending on the
stiffness of the com posite power-frequency curve, the steady-
state system frequency will change on changing loads. The
frequency may then be restored to its nominal value by a
slower outer loop. To restore the frequency, the value of Po;,
(13) has to be modified for the inverters. This is equivalen t to
shifting the power-frequency curve v ertically. The restoration
of the frequency may be done in a slow, coordinated manner
by a master controller, using a slow communication channel
between the inverters.
In a similar manner, the setpoints E,* for the ac system
voltages at the inverter systems ca n be determined from
drooping reactive power-voltage characteristics
(Q-E)
for
-
8/10/2019 C1_Control of Parallel Connected Inverters...
7/8
142
IEEE
TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 29, NO.
1
JANUARYIFEBRUARY 1993
the inverters. This droop ensures the desired reactive power
sharing between the inverter systems and is described by
Ef = Eo - n;(Qoi - Q;)
=
f ; (P ) .
(17)
In (17), EO s the nominal voltage on the ac system , Q o; s
the nominal reactive power supplied by the ith inverter, and
n;
is the slope of the droop characteristic.
The control system described above has been applied to the
standalone system of Fig. 8. The results of simulation studies
are presented below.
C. Simulation Results
systems are cha racterized by the following parameters:
For the simulation studies, the droops of the two inverter
Pol = 0.75 MW
Po = 0.6 MW
ml =
-1.4 x (radls)/W
mz = -1.75
x (radls)/W
Qol
=
0.2 Mvar
n1 = -1.0 x 10-4
V/VX
Qo2 = 0.1
M V U
n
=
- 2 .0 x V/var.
The nominal voltage is
3.6
kV rms line to line, and the
nominal frequency is
60
Hz. The filter components for the
two inverter systems are identical as are the initial load
components. The component values
are
typical for a low-
power ac system. With reference to Fig. 8, the component
values are
Fig. 12 shows the response of the inverters when the
resistance RE^ (Fig. 8) is decreased suddenly to half its value.
Fig. 12shows the real and reactive powers supplied by the two
inverter systems to the load. The figure shows that Inverter 1
carries a larger share of the real power since it has a stiffer
slope. Fig. 13shows the line-to-line voltage across the filter
capacitor of Inverter
1.
The plot for the reactive powers in
Fig. 12 shows oscillations. These oscillations are the result of
filter interactions and occur in the absence of active damping
of the loop formed by the two filter capacitors and the tie-line
inductance. These oscillations are not uncommon in power
systems and can be damped by the inverters, given sufficient
inverter bandwidth. One effective means of damping these
oscillations is the introduction of a series active filter
[8]
between the capa citor and the ac system bus. As mentioned in
[8],
this method presents a low resistance to the fundamental
and a high resistance to harmonics, thus effectively limiting
the harmonic current injection into the ac system. The series
active filter inverter is not expected to handle real pow er and
can have a reasonably low rating.
U.
24 0.28 U.32 U . 3 6 U .4U
T
3 I I I I I J
O.ZI1
11.24
0.28 0 . 3 2
0 . 3 6 s U . 4 0
Inverter real and reactive power (standalone system).
T
Fig. 12.
L
U.2U
U. 24 0 .28 0 . 32
0.36 S
0 .40
T
Fig.
13.
Voltage across Inverter 1 filter capacitor.
V.
CONCLUSIONS
This paper has described a method to effectively control
inverters in a standalone ac supply system without any form of
signal communication. The control m ethodology has a highly
modular structure. This feature enables easy modification of
the controls to meet the requirements of different ac system
structures. The simulation results presented indicate that the
scheme effectively achieves the goals of power sharing in
the presence of arbitrarily changing loads. Active damping in
the loop formed by the filter capacitors and the tieline would
enhance the performance further. The scheme described in this
paper uses
P-I
regulators to determine
the
set points for 6
-
8/10/2019 C1_Control of Parallel Connected Inverters...
8/8
CHANDORKAR
ef
al.:
CONTROL
OF
PARALLEL-CONNECTED INVERTERS
143
and
:.
However, the dynamic performance of the system can
be substantially improved if an observer structure is used to
determine the frequency . The position
of
the ac system voltage
vector can be determined very accurately at any time. This
information can be used to set up a frequency observer, the
output of which would be an estimated frequency. The time
integral of the estimated frequency can be compared with the
actual position of the voltage vector, and the estimated fre-
quency can be modified accordingly. Feedback
of
the observer
states results in a system w ith very good dynam ic response and
disturbance rejection properties.
In summary, this paper has
discussed control system requirements for inverters inter-
faced to an ac system, with emp hasis on a standalone ac
system
developed a modular control scheme that meets these
requirements without control signal communication be-
tween parallel-connected inverters
presented simulations for the control scheme as applied
to an inverter connected to a strong ac system and to two
inverters connected in parallel to a stan dalone ac system
briefly discussed the issue of filter interaction in the c ase
of
parallel-connected inverters and suggested a method
for minimizing these interactions.
REFERENCES
[ ]
B.
K. Johnson, R. H. Lasseter, and R. Adapa, Power control applica-
tions on a superconducting LVdc mesh, IEEE Trans. Power Delivery
vol. 6, no. 3, pp. 1282-1288, July 1991.
[2] L.
Angquist and
L.
Lindberg, Inner phase angle control of voltage
source converter in high power applications, in IEEE
PESC
Con
Rec.
[3]
A. Nabae, I. Takahashi, and H. Akagi, A neutral-point-clamped PWM
inverter, IEEE Trans. Industry Applicaitons vol. IA-17, pp. 518-523,
Sept./Oct. 1981.
[4]
A.
R.
Bergen,
Power System Analysis.
Englewood Cliffs, NJ: Prentice-
Hall, 1986.
[5]
I.
Takahashi and T. Noguchi, A new quick-response and high-efficiency
control strategy of an induction motor,
IEEE Trans. Industry Applica-
tions
vol. IA-22, pp. 820-827, Sept./Oct. 1986.
[6]
M.
Depenbrock, Direct self-control (DSC) of inverter-fed induction
machine,
IEEE Trans. Power Electron.
vol. 3, pp. 420-429, Oct 1988.
[7]
T. A. Lipo, Analysis of synchronous machines, course notes, Univ.
of Wisconsin-Madison, 1990.
[8]
S
Bhattacharya,
D.
M. Divan, and B. Banerjee, Synchronous frame
harmonic isolator using active series filter, in Proc. 4th Euro.
Con5
Power Electron. Applications
(Florence, Italy), 1991, vol.
3,
pp. 30-35.
1991, pp. 293-298.
Mukul
C. Chandorkar
(S90) received
the
B.Tech.
degree in electrical engineering from the Indian
Institute of Technology, Bombay, India, in 1 984 and
the
M.
Tech. degree in electrical engineering from
the Indian Institute of Technology, Madras, India, in
1987. Since 1989, he has
been
working on the Ph.
D. program in Electrical and Computer Engineering
at the University of Wisconsin, Madison
From 1984 to 1986, he was with Larsen and
Toubro Limited, Bombay, India, working
on
the
engineering of cement and chemical plants. He
Deepakraj
M.
Divan
(M83) received the B. Tech
degree in electrical engineering from the Indian
Institute of Technology, Kanpur, India, in 1975. He
also received the M.Sc and Ph.D degrees in elec-
trical engineering from the University
of
Calgary,
Canada.
He has worked for two years as a Development
Engineer with Philips India Ltd. After finishing
his
Masters program in 1979, he started his own con-
cem in Pune, India, providing product development
and manufacturing services in the power electronics
and instrumentation areas. In 1983, he joined the Depa&ent of Electrical
Engineering at the University of Alberta as an Assistant Professor. Since 1985,
he has been with the Department of Electrical and Computer Engineering at
the University of Wisconsin, Madison, where he is presently an Associate
Professor. He is also an Associate Director of the Wisconsin E lectric Machines
and Power Electronics Consortium (WEMPEC). His primary areas of interest
are in power electronic converter circuits and control techniques. He has over
30 papers in the area as well as many patents. He is also a consultant for
various industrial concems.
Dr.
Divan was a recepient of the Killam Scholarship while in the Ph.D
program and has won various prize papers including the IEEE-US Best Paper
Award for 1988-89, first prize paper for the Industrial Drives and Static Power
Converter Committee in 1989, third prize paper in the Power Semiconductor
Committee and the 1983 third prize paper award of the Static Power Converter
Committee of the IEEE Industry Applications Society. He has been the
Program Chairman for the 1988 and 1989 Static Power Converter Committee
of the IEEE-IAS, Program Chairman for PESC 91, and a Treasurer for PESC
89. He is also a Chairman of the Education Com mittee in the IEEE Pow er
Electronics Society.
Rambabu Adapa
(S81-M786-SM90) was bom
in Andhra Pradesh, India, on Sept. 2, 1956. He
received the B.S. degree in electrical engineering
from Jawaharlal Nehru Technological University,
Kakinada, India, in 1979. He received the
M.S.
degree in electrical engineering from the Indian
Institute of Technology, Kanpur, India, in 1981.
He
received the Ph.D. degree in electrical engineering
from the University of Waterloo, Canada, in 1986.
He joined the Power System Planning and Oper-
ations urogram of the Electrical Svstems Division
of the Electric Power Research I n & & (EPRI), Palo Ako, CA, in June
1989. Prior to joining EPRI, he was Staff Engineer in the Systems Engi-
neering department of McGraw-Edison Power Systems, Franksville,
WI.
At
McGraw-Edison, he was involved in several digital and analog
studies,
which
included transient, harmonic, and insulation coordination studies performed
for electric utilities. At EPRI, he manages the Electro-Magnetic Transients
Program (EMTP) development and maintenance project, commercialization
of the Harmonic Analysis Software
(HARMFLO)
endeavor, and several
other EPRUNSF-funded projects.
His
interests include EMTP, power system
planning and operations, HVDC transmission, harmonics, and expert systems.
Dr. Adapa is a Senior Member of the IEEE Power Engineering Society,
a member of the DC Transmission subcommittee of the Transmission and
Distribution Committee, a member of CIGRE and of the local IEEE Santa
Clara chapter. He is a Registered Professional Engineer in the State of
Wisconsin.
worked as a design engineer in the power electronics industry in India
during 1988-1989. His primary technical interests are in power electronics
applications to electric machines and to power systems.