Level measurement for high temperature, high pressure and low density Closed and robust stainless steel design with different material options IP68 local indicator, with different optional signal output
Bypass level indicator
Technical Datasheet
www.rehe-krohne.com 2
1. Description The BM 26A/BM26B/BM26G is a simple, rugged instrument designed to indicate level or interface of liquid. It is a totally metal design, with optional level transmitter and limit switch for alarming. It indicates level using a float magnetically coupled to an index or a column of rotating flaps. It is ideal for aggressive media stored in tanks when the PTFE lining option is used.
It is widely used in petrochemical, chemical, metal, power, food, pharmaceutical, paper industry for level
and interface measurement.
2. Operating principle The BM 26 operates on the principle of communicating tubes. The measuring tube is connected as a side vessel to the tank so that the same conditions are obtained in the tube as those in the tank.
The float is equipped with a system of permanent magnets to transmit measured value to the local indicator. The magnet system of the float activates the magnetic flaps according to the liquid level, or a movable follower magnet in the indicating section of the indicator. The column of reversed yellow magnetic flaps, or the vertical position of the follower magnet, is the indication of the liquid level.
Installation Diagram
1. Vent plug 2. Measuring tube 3. Triangle mark 4. Glass tube for indicator 5. Scale 6. Float 7. Liquid level 8. Display of indicator 9. Index indicator (option) 10. Zero point of measurement (centerline of lower connecting flange) 11. Scale zero 12. Lower stop ( KROHNE plate) 13. Drain plug or drain valve (option) 14. Instrument nameplate
www.rehe-krohne.com 3
3 Product features
• Most compact and robust construction design with reliable measurement.
• Magnetic flapper or index sealed in glass tube for indicator.
• Indicator and signal output are completely isolated from process (magnetically-coupled).
• Level transmitter and limit switch are optional.
• Material options: 304L, 316, 316L, Ti and Hastelloy® C.
• Different process connection and different installation
• Branch connection of measuring tube by cold forming enables the float move freely
• Spring as the float stopper to avoid damage of the float
3.1 BM26A features
• Operating pressure should be less than 5.0 MPa.
• Operating temperature should be less than 400 (for Ex requirement, less than 200).
• Min. operating temperature is -200.
• Density should be higher than 0.5 g/cm3.
• For interface measurement, the difference of density should be higher than 0.1 g/cm3.
• IP68 sealed glass tube with magnetic flapper or index inside.
• Suitable in corrosive, sandy and windy, rainy environment.
• PTFE liner and plastic material are optional.
• Easy to change indicator, optional heat jacket and isolation.
• Signal outputs are both intrinsically safe and explosive-proof proved.
3.2 BM26B features
• Best volume and pressure ratio.
• Optimized construction design with low weight.
3.3 BM26G features
• Nominal pressure up to 25 MPa.
• Operating temperature: -200…+400.
• Min. density: 0.4 g/cm3.
*These three figures can’t be obtained at one device.
4. BM26A/BM26B/BM26G
The BM26A/B/G consists of a measuring tube, which is connected as a side vessel to the tank with different material options, an indicator isolated totally from the process, some signal output like limit switch, current output.
BM26A Standard Magnetic Level Meter
BM26B Economical Magnetic Level Meter
BM26G High temperature, high pressure, low density Magnetic Level Meter
www.rehe-krohne.com 4
5. Installation
BM26A / BM26B / BM26G has multiple installation to meet the customer requirements, such as:
C Two side connections
D Two inline connections
E Top side connection and bottom inline connection
F Top inline connection and bottom side connection
H Top mounted (only for BM26A)
6. Process connection BM26A/BM26B / BM26G has different process connections to meet the demands of customer, such as:
Flange connection:DIN,ANSI,GB,HG etc.
Male thread connection:Metric, Imperial, NPT etc.
Female thread connection: Metric, Imperial, NPT etc.
Welded connection.
Welding type thread type Flange type
7. Vent and drain construction
7.1 Vent 7.2 Drain
8. Approval
Explosion protection: NEPSI, ExiaIICT3-T6,ExdIICT3-T6 Explosion protection: PTB,ATEX,L.C.I.E Protection category: IP68, according to NAMUR NE21/05/93 PTB explosion protection and overfill protection certification TUV, ZeFu type testing certificate AB Svensk type testing certificate
www.rehe-krohne.com 5
9. BM26A technical data
Product density ≥0.5kg/l Difference of density for interface measurement
≥0.1kg/l
Operating pressure ≤5.0MPa Viscosity ≤5000mPa.s Operating temperature Standard -20~+200 Option -200~+400 Measuring range 300~6000mm Accuracy ±10mm Indicator IP68 Magnetic flap
IP68 Magnetic index Measuring tube materials 304L,316L,Ti,HC,B,Ф72×2.3 Float Ф64×200mm,316L,Ti, 304L Vent and drain Plug cock M20×1.5 Process connection DIN,ANSI,GB flange Weight 14.5kg for 1000mm (additional
0.51kg/100mm) Option
level transmitter, MS15, MS40 and KS limit switch
BM26A/C two side connections
BM26A/D two inline connections BM26A/E top side and bottom inline connection
www.rehe-krohne.com 6
BM26A/F top inline and bottom side connection BM26A/H top mounted
BM26A/H top mounted Measuring range 300~3000mm Operating temperature -100~+300 Operating pressure 1.6 MPa Liquid density ≥0.65kg/l Material of measuring tube 304L、316L、Φ60×2
Float Ф140×1.0mm,316L Ф140×0.7mm,316L
Note: The measurement of dead zone is 185mm, H ≥ M +185 mm
9.2 BM26A PTFE-lined
Product density ≥0.65kg/l Difference of density for interface measurement
≥0.1kg/l
Operating pressure ≤1.6MPa Viscosity ≤5000mPa.s product temperature -20~+150 Measuring range 300~6000mm Accuracy ±10mm Indicator IP68 magnetic flap or index Measuring tube materials
304 or 316L,Ф63×2.5mm, PTFE lined
Float Materials PTFE Vent and drain Blind flange Process connection DIN,ANSI,GB Weight 20kg for 1000mm(additional
0.53kg/100m) Option
level transmitter, MS15、MS40 and KS limit switch
www.rehe-krohne.com 7
9.3 BM26A plastic measuring tube
Product density ≥0.85kg/l
Difference of density for interface measurement
≥0.1kg/l
Operating pressure ≤0.3MPa
Viscosity ≤5000mPa.s
Product temperature -20~+60Measuring range 300~4000mm
Accuracy ±10mm
Indicator IP68 magnetic flap or index
Measuring tube materials Ф63×4.7mm CPVC
Float Materials Ф50×178mm CPVC
Vent Blind flange
Drain Blind flange, Valve option
Process connection DIN,ANSI,GB flange
Weights 6.6kg for 1000mm ( additional 0.13kg/100mm)
Option
ER analog transmitter, MS15、MS40 switch,KS switch
9.4 BM26A Heating jacket for measuring tube Product density ≥0.5kg/l
Difference of density for interface measurement
≥0.1kg/l
Operating pressure ≤5.0MPa
Viscosity ≤5000mPa.s
Operating temperature Standard -20~+200 Option -200~+400
Measuring range 300~6000mm
Accuracy ±10mm
Indicator IP68 Magnetic flap or index
Measuring tube materials 304L,316L,Ti,HC,B,Ф72×2.3
Heating jacket Ф89×2.0/304 Float Ф64×200mm,316L,Ti
Vent and drain Plug cock M20×1.5, G1/2
Process connection DIN,ANSI,GB flange
Weight 20.6kg for 1000mm(additional 0.82kg/100mm)
Option level transmitter, MS15、MS40 and KS limit switch
1. Entry of jacket
2. Heating jacket
3. Measuring tube
Heating jacket for measuring tube
www.rehe-krohne.com 8
9.5 BM26A (Low temperature measurement)
IC/TR Low-temperature measurement structure
Liquid density ≥0.5kg/l
Difference of density for interface measurement
≥0.1kg/l
Operating pressure ≤5.0MPa
Viscosity ≤5000mPa.s
Product temperature AG ≥-40
IC/AG ≥-40
TR ≥-200
IC/TR ≥-200Measuring range 300~6000mm
Accuracy ±10mm
Indicator Magnetic flap or index
Measuring tube materials 304L ,316L ,Ti ,HC ,B ,Ф72×2.3
Float Materials Ф64×200mm,316L,Ti
Vent and drain Plug cock M20×1.5
Process connection DIN,ANSI,GB flange
Weight 14.5kg for 1000mm(additional 0.6kg/100mm)
Option AG Level transmitter, MS15、MS40 and KS limit switch
IC/AG Level transmitter
AG
1 Plexitherm glass
2 Scale
3 Glass tube for indicator
4 Measuring tube
TR
1 Measuring tube
2 Glass tube for indicator
3 Plexitherm glass
4 Scale
IC/TR
1 Measuring tube
2 Glass wool insulation
3 Glass tube for indicator
4 Plexitherm glass
5 Stainless steel cladding
www.rehe-krohne.com 9
9.6 BM26A (High temperature)
Product density ≥0.5kg/l
Difference of density for Interface measurement
≥0.1kg/l
Operating pressure ≤2.5MPa
Viscosity ≤5000mPa.s
Operating temperature HR +200~+300
IC/HR +200~+300
Measuring range 300~6000mm
Accuracy ±10mm
Indicator IP68 Magnetic float Indicator
Measuring tube materials 304L,316L,Ti,HC,B,Ф72×2.3
Float Materials Ф64×200mm,316L,Ti
Vent and drain Plug cock M20×1.5
Process connection DIN,ANSI,GB flange
Weights 15.5kg for 1000mm (additional 0.6kg/100mm)
IC/HR High temperature structure
1. Measuring tube
2. Insulation
3. Magnetic flap or index indicator
4. Stainless steel cladding
9.7 BM26A Selection of float type
No. BM26A float
Min. density
Max. allowable operating pressure at
20 100 200 300 Product temperature
Type Dimensions
in mm Material Kg/l MPa MPa MPa MPa min. max.
1 cylindrical Ф64×200×1.0 316L 0.82 5.5 4.1 3.7 3.2 -200 400
2 cylindrical Ф64×200×0.5 316L 0.55 1.6 1.2 1.0 0.9 -200 400
3 cylindrical Ф64×208×0.6 Ti 0.50 2.3 1.3 1.0 0.8 -200 300
4 cylindrical Ф64×208×1.0 Ti 0.60 5.5 3.1 2.4 1.9 -200 300
5 cylindrical Ф50×120×2.0 PVC 0.85 0.3 - - - -10 40
6 spherical Ф140×1.0 316L 0.85 4.0 - - - - -
7 spherical Ф140×0.7 316L 0.80 2.5 - - - - -
Float test pressure = 1.5 * max. allowable operating pressure at 20
www.rehe-krohne.com 10
10. BM26A float selection
The floats of BM26A consist of standard and special design.
10.1 Standard float
The indicator should be installed according to the X value
showed in below picture, which is the distance between
the magnet and center line of bottom flange.
Advantage:
The standard float can be used interchangeably. If the
density changed, adjust the indicator position according to X value.
Serial production with some inventory
Reliable and stable measurement
Note: compared with the special float, there is a difference between
the real level and the rotated flapper, but the indicated value is correct.
Suggest to choose the standard float. BM26A standard float
10.2 Special float
The zero position of indicator is exactly the same with centerline of the bottom flange, no difference between the
real level and the rotated flapper, as below picture. The special float is named as T type.
Advantage:
No difference between the real level and rotated flapper,
the same with glass level gauge.
Note:
Adjust the weight of the float to keep the real level the same
with the magnet. Different density with different float weight.
The float is not able to exchange, without serial production.
The liquid density must be accurate.
BM26A special float
www.rehe-krohne.com 11
11: BM26G Technical data
Type:BM26G/100 Pressure rating:PN10.0MPa/class 600Ibs
Liquid density ≥0.57kg/l Difference of density for Interface measurement
≥0.1kg/l
Operating pressure ≤10.0MPa Viscosity ≤5000mPa.s Operating temperature local indicator -196~+400
Level transmitter ≤+200 Measuring range 300~6000mm Accuracy ±10mm Indicator Magnetic flap Indicator Measuring tube materials 304L,316L,Ti,HC,B,Ф76×4 Float Materials Ф56,Titanium Vent and drain Variety Process connection DIN,ANSI,GB flange Weights 22.4kg for 1000mm( additional
0.65kg/100mm) Option Level transmitter, MS40 and KS limit
switch
PN10.0MPa Temperature - pressure curve BM26G Ti Float dimensions
Vent Drain
BM26G/100
www.rehe-krohne.com 12
12: BM26G Technical data
Type:BM26G/160 Pressure rating:PN16.0MPa/class 900Ibs
Liquid density ≥0.57kg/l Difference of density for Interface measurement
≥0.1kg/l
Operating pressure ≤16.0MPa Viscosity ≤5000mPa.s Operating temperature local indicator -196~+400
Level transmitter ≤+200 Measuring range 300~6000mm Accuracy ±10mm Indicator Magnetic flap Indicator Measuring tube materials 304L,316L,Ti,HC,B,Ф76×5 Float Materials Ф56,Titanium Vent and drain Variety Process connection DIN,ANSI,GB flange Weights 25.2kg for 1000mm(additional
0.85kg/100mm) Option Level transmitter, MS40 and
KS limit switch
BM26G/160
PN16.0Mpa Temperature - pressure curve
BM26G Ti Float dimensions
Vent Drain
www.rehe-krohne.com 13
13: BM26G Technical data
Type:BM26G/250 Pressure rating:PN25.0MPa/class 1500Ibs
Liquid density ≥0.51kg/l Difference of density for interface measurement
≥0.1kg/l
Operating pressure ≤25.0MPa Viscosity ≤5000mPa.s Operating temperature Local display -196~+400
Level transmitter ≤+200 Measuring range 300~6000mm Accuracy ±10mm Indicator Magnetic flap Indicator Measuring tube material 304L,316L,Ti,HC,B,Ф80×8.5 Float Materials Ф56,Titanium Vent and drain variety Process connection DIN,ANSI,GB flange Weights 32.5kg for 1000mm (additional
1.5kg/100mm) Option Level transmitter, MS40 and KS limit
switch
BM26G/250
PN25.0Mpa Temperature - pressure curve
BM26G Ti Float dimensions
Vent Drain
www.rehe-krohne.com 14
14: BM26B Technical data
Liquid density ≥0.54kg/l Difference of density for Interface measurement
≥0.1kg/l
Operating pressure ≤4.0Mpa Viscosity ≤5000mPas Product temperature -20~+300 Measuring range 300~6000mm Accuracy ±10mm Indicator IP rating IP68 Measuring tube and float material
304L,316L,Ti,Hastelloy® C φ42.4×2
Vent Plug cock M16×1.5 Drain Plug cock M16×1.5
ball valve(Female thread 1/2“NPT)Process connection DIN , ANSI , HG20592 , GB/T
flange, DN15~50,PN16/40
Option Level transmitter, Radar/TDR transmitter, MS40、KS limit switch
Weight 7.4kg for 500mm; (additional 0.3Kg/100mm)
Float data
Density Dimension mm
Material
0.54~0.69kg/l φ32×420 Ti 0.70~0.98kg/l φ32×240 Ti 0.99~2.0 kg/l φ32×185 316L
Vent plug or valve
Level transmitter
Level indication
Process connection Red flap means
float failure
Stainless steel optional switch Measuring tube
Drain plug or valve
BM26 B/C two side connections
Float Dimension
mm φ32×420 480 φ32×240 299 φ32×185 255
BM26 B/D two inline connection
Float Dimension
mm φ32×420 570 φ32×240 390 φ32×185 340
www.rehe-krohne.com 15
BM26 B/E top side and bottom inline connection
Float dimension
mm φ32×420 580 φ32×240 400 φ32×185 360
BM26 B/F top inline and bottom side connection
Float dimension
mm φ32×420 480 φ32×240 299 φ32×185 255
15. level transmitter
15.1 Principle In addition to the local indicator, the BM 26 can be equipped with the ER analog transmitter system. This transmitter consists of a tube that clamped onto the measuring tube and with reed and resistor chain inside, a housing with converter inside to provide the current output. The moveable float will activate different reeds when level changing, also provide different resistance value and then convert to 4…20mA current output.
For non-Ex application, ER transmitter provide 4…20 mA current output directly.
For Exd application, choose the explosive-proof transmitter housing with marking Ex d IIC T3-T6.
For Exi application, please connect suitable related apparatus to the transmitter. Ex marking :ExiaIICT3-T6.
ER analog transmitter principle
15.2 Technical data of ER analog transmitter
Measuring range 300-6000mm Accuracy ±10mm Output 4-20mA Power supply 14-36VDC Reverse Connection
Protection Load characteristic (U-12)/20 mA(max.500Ω) Electromagnetic compatibility
According to EN50081-1 and EN50082-2
Protection category IP65 Ambient temperature -20-+60 process temperature -40-+200
15.3 Electrical connection
Signal convertor
Cable entry: M20X1.5 Electric connection for Exi application
www.rehe-krohne.com 16
signal converter signal converter
Cable entry: M20X1.5 Cable entry: M20X1.5
Electric connection for Exd application Electric connection for non-Ex application
Installation note for intrinsically safe transmitter:
The BM26/…/ER/Exi has been approved by NEPSI(National Supervision and
Inspection Center for Explosion Protection and Safety of Instrumentation in
China) under Certification No.
GYB16.1206X
This level meter is designed with intrinsically safe type of protection with
protection level of Ex ia IIC T3-T6 and designed according to GB 3836.1-2010,
GB 3836.4-2010 and GB 3836.20-2010 standards. It must be equipped with
safety barrier to form intrinsically safe explosion protective system and applies to
fields exist explosive mixture gas under IIC grade.
Please comply with following notes when installation:
1. The level meter must be equipped with safety barrier approved by NEPSI,
then can be used in environment with explosive gas mixture. Please pay
attention to the cable connection which must be complied with the
instruction of both.
2. Safety barrier must be placed in secure location and complied with the
installation instruction.
3. Intrinsically safe data:
Ui=28V li=120mA Pi=0.84W Ci=22nF Li=0
The connection cable between level meter and safety barrier must be
shielded (with insulation sheath). The cross section area of each wire must
be higher than 0.5 mm2. The shielding layer must be grounded at safety
location. Please avoid the electromagnetic interference when cable
distribution. The level meter with safety barrier must be meet following
requirement:
Uo≤Ui, Io≤Ii, Po≤Pi, Co≥Ci+Cc, Lo≥Li+Lc
Uo, Io, Po, Co and Lo are intrinsically safe type output data and external
allowable data. Cc and Lc are respectively capacitance and inductance of
connection cable. The relation between temperature class and measuring
temperature is as bellowed.
Temperature class T3 T4 T5 T6
Max. operating temperature 190 125 95 80
4. Do not replace the components by yourselves, please contact with the
manufacture.
Installation note for explosive-proof transmitter:
The BM26/…/ER/Exd has been approved by NEPSI (National Supervision
and Inspection Center for Explosion Protection and Safety of
Instrumentation in China) under Certification No.
GYB16.1205X
This level meter is designed with explosive-proof type of protection with
protection level of Ex d IIC T3-T6 and designed according to GB 3836.1-
2010, GB 3836.2-2010 standards.
1. The level meter should be grounded.
2. Pay attention to the warning marking “open the transmitter
housing after power cutoff” when maintenance.
3. The outer diameter of the connecting cable must be within
the sealing range of the cable entry (8.5-10mm). please
fasten the gland nut to fasten cable sheath.
4. Sealing ring and cable sheath should be replace in time
when it is aged.
5. The voltage, current and power should be complied with
the specified value.
6. Maintenance must be carried out at secure location.
Please be sure that no hazardous gas around before
maintenance.
7. The surface temperature should complied with the
temperature class.
For both intrinsically safe and explosive-proof type of
protection, the level meter should be installed, operated
and repaired according to the technical datasheet of the
meter, part 15 of GB3836.15-2010 and GB50058-1992.
www.rehe-krohne.com 17
16.4 MS15/BRX reed switch
It is also a kind of reed switch which can be activated by the float magnet. The minimum distance between two switches
is 50mm. explosive proof housing is available.
Explosion protection: Exd IICT3-T6
Contact type: SPDT
16.5 Technical data of limit switch
Type MS15/MC MS40 MS40/NAMUR MS15/BRX
Contact SPDT SPDT SPDT SPDT
Switch type Micro switch reed reed reed
Switch capacity 4A, 250VAC, 1000VA 1A, 250VAC, 60VA NAMUR 19234 1.5A, 250VAC, 20VA
Apply to BM26A BM26A, BM26B, BM26G BM26A, BM26B, BM26G BM26A, BM26B
Ambient temperature -20~120 -40~120 -40~120 -20~60
Operating temperature <250 <250 <250 <200
Ingress protection IP65 IP65 IP65 IP65
Cable entry M20X1.5 M16X1.5 M16X1.5 M20X1.5
Housing material Plastic Aluminum Aluminum Aluminum
Explosion protection without Ex ia II CT3-T6 Ex ia II CT3-T6 Ex d II CT3-T6
weight 130g 200g 200g 200g
16: Limit switch In order to provide alarm for a specific level, the BM 26 magnetic level indicator can be equipped with various limit switches that are clamped to the measuring tube and thus adjustable over the whole measuring range. They are activated by the magnet system in the float. Depending on different operating conditions, various limit switches are available. 16.1 MS15/MC The MS15/MC limit switch is a micro switch that is activated by the magnet system in the float. The minimum distance between two switches is 30mm. Contact type: SPDT
16.2 MS40、MS40/NAMUR Reed Switch
MS40 is a bi-stable reed switch with minimum distance of 50mm. The output signal of MA40/NAMUR complies with NAMUR 1923 standard. Explosion Protection:ExiaIICT3-T6
Contact type:SPDT
16.3 KS Series Switch KS series limit switches consist of reed switch and micro switch.
It is a multi-function switch, suitable for all BM26 products. It is
activated by the float magnet, with the option of explosive proof
housing. The minimum distance between two switches is
100mm.
Explosion protection:ExdIICT3-T6
Contact type:SPDT、DPDT
MS15/MC KS seiral
MS40、MS40/NAMUR
www.rehe-krohne.com 18
Type KS1 KS2 KS3 KS4 KS5 KS6 KS7 KS8
Contact SPDT SPDT SPDT SPDT SPDT DPDT SPDT DPDT
Switch type reed reed reed reed Micro
switch
Micro
switch
Micro
switch
Micro
switch
Switch capacity 1A,
150VAC/DC,
20W/VA
1A,
250VAC/DC,
60W/VA
1A,
150VAC/DC,
20W/VA
1A,
250VAC/DC,
60W/VA
4A,
220VAC,
1000VA
4A,
220VAC,
1000VA
4A,
220VAC,
1000VA
4A,
220VAC,
1000VA
Apply to BM26A
BM26B
BM26A
BM26B
BM26G BM26G BM26A
BM26B
BM26A
BM26B
BM26G BM26G
Ambient temperature -20~120
Operating temperature <200
Ingress protection IP65
Cable entry M20X1.5 female
Housing material Aluminum
Explosion protection Exd II CT3-T6
Weight 650 g 690 g
www.rehe-krohne.com 19
17. Type Code
17.1 BM26B type code (φ42.4mm)
Indicator P Magnetic flap Indicator
Installation
C two side connections D two inline connections E top side and bottom inline connections F top inline and bottom side connections
Material RR 304L RRL 316L SM Other special material
Current Output
0 Without ER 4-20mA,Reed chain Transmitter EH 4-20mA+HART,Reed chain Transmitter MR 4-20mA+HART,Magnetostrictive Transmitter PA Profibus PA communication FF Foundation field bus communication
Number/ Limit Switches
0 Without Kn/MS40 MS40 Reed switch(SPDT,60VA/1A/250VAC,Exia ⅡCT3-T6) Kn/MS40/NUMAR MS40 NAMUR reed switch(SPDT,NUMAR, Exia ⅡCT3-T6) Kn/KS Explosive-proof switch(KS1~KS8) Kn/MS15/BRX Explosive-proof switch (SPDT,20VA/1.5A/250VAC,ExdⅡCT3-T6)
Explosion Protection N Without Exi Intrinsically safe, Ex ia ⅡCT3-T6 Exd Explosive-proof, ExdⅡCT3-T6
Temperature range
0 Standard B With heat jacket AG Low temperature (-40°C) IC/AG Low temperature (-40°C) with insulation HR High temperature (+300°C, max. 2.5Mpa)
Density /Float
L1 0.54 to 0.69g/cm3/Titanium L2 0.70 to 0.98g/cm3/Titanium L3 0.99 to 2.00g/cm3/316L T9 Special Float
Process connection
F Flange S1 Female thread S2 Male thread H welded connection
Vent
M Plug cock M16x1.5(standard) N Plug cock NPT 1/2" V Ball valve(DN15,NPT 1/2" female thread) F Flange DN15 SV Special vent
Drain
M Plug cock M16x1.5 (standard) N Plug cock NPT 1/2" V Ball valve(DN15,NPT 1/2" female thread) F Flange DN15 SD Special drain
Cable Entry M1 M20x1.5 female thread (standard) G1 G1/2” female thread N1 NPT1/2” female thread
Certificate
0 Without R1 Material certificate R2 Pressure test certificate R3 Inspection records R4 Cleaning report R5 X-ray inspection report R6 PMl R7 Nuclear R9 Other
BM26B
www.rehe-krohne.com 20
17.2 BM26A/BM26G type code (¢72mm, ¢76-90mm) :
Indicator
P Magnetic flap Indicator S Magnetic index Indicator M Metal magnetic flap Indicator(for BM26G) L Frost protection indicator UL Ultralow temperature indicator
Installation
C two side connections D two inline connections E top side and bottom inline connections F top inline and bottom side connections
H Top mounted (except for BM26G)
Material
RR 304L RRL 316L PTFE Lining PTFE(except for BM26G) PVC Engineering plastic (except for BM26G) TI Titanium alloy HC Hastelloy alloy SM Other special material
Current Output
0 without ER 4-20mA,Reed Chain Transmitter EH 4-20mA+HART,Reed Chain Transmitter MR 4-20mA+HART,Magnetostrictive Transmitter PA Profibus PA communication FF Foundation Field bus communication
Number/ Limit Switches
0 without Kn/MS15/MC Micro Switch (SPDT,1000VA/4A/250VAC,not for BM26G) Kn/MS40 Reed switch(SPDT,60VA/1A/250VAC,Exia ⅡCT3-T6) Kn/MS40/NUMAR NUMAR Reed switch(SPDT,NUMAR Exia ⅡCT3-T6) Kn/KS Explosive-proof switch(KS1~KS8)
Kn/MS15/BRX Explosive-proof switch (SPDT,20VA/1.5A/250VAC,ExdⅡCT3-T6)
Explosion
Protection
N non-Ex EXI Intrinsically safe, Ex ia II CT3-T6 EXD Explosive-proof, Ex d II CT3-T6
Temperature
range
0 Standard type B With heat jacket AG Low temperature (-40°C) IC/AG Low temperature (-40°C) with insulation TR Low temperature (-200°C) IC/TR Low temperature (-200°C) with Insulation HR High temperature (+300°C,max. 4.0Mpa) IC/HR High temperature (+300°C) with Insulation
Density /Float
1 Standard Float ≥ 0.82g/cm3 316L 1.0mm 2 Standard Float ≥ 0.55g/cm3 316L 0.5mm 3 Standard Float ≥ 0.5g/cm3 Ti 0.6mm 4 Standard Float ≥ 0.6g/cm3 Ti 1.0mm 5 Standard Float ≥ 0.85g/cm3 PVC 6 Top mounted Float ≥0.65g/cm3 316L 1.0mm 7 Equivalent Float ≥0.82g/cm3 316L 1.0mm
www.rehe-krohne.com 21
8 Equivalent Float ≥0.55g/cm3 316L 0.5mm T1 Interface ≥0.1g/cm3 316L 1.0mm T2 Interface ≥0.1g/cm3 Ti 1.0mm T9 Special Float
Pressure rating
040 4.0MPa 064 6.4 MPa 100 10.0 MPa/600LBS ( For BM26G) 160 16.0MPa/900LBS(For BM26G) 250 25.0MPa/1500LBS(For BM26G) 320 32.0MPa(For BM26G)
Process
connection
F Flange S1 Female thread S2 Male thread H Welded
Vent
M plug cock M20x1.5(standard) N plug cock NPT 1/2"(BM26G standard) V Ball valve(DN15,NPT 1/2") F Flange DN15 SD Special vent
Drain
M plug cock M20*1.5 (standard) N plug cock NPT 1/2"(BM26G standard) V Ball valve(DN15,NPT 1/2") F Flange DN15 SD Special drain
Cable entry M1 M20x1.5 Female thread G1 G1/2” Female thread N1 NPT1/2” Female thread
Certificate
0 without R1 Material certificate R2 Pressure test certificate R3 Inspection records R5 X-ray inspection report R6 PMl detection report R7 Nuclear power user files R9 Other
BM26A/G