Page 1: BY-CX series

Air Handling UnitsDirect Expansion

BY Series(Matching with CX series Condensing units)

BY03 thru BY252.5 TR thru 30 TR9 kW thru 105 kW

Page 2: BY-CX series

Company BusinessZamil Air Conditioners was founded in 1974 as one of the first air conditioning business to be established in Saudi Arabiaand today is a leading international manufacturer of air conditioning systems and is No. 1 in the Middle East.

Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55countries in the Middle East, Europe, Africa and Asia.

The company’s operations are structured into four Strategic Business Units (SBUs) supporting five in-house product andservice brands as well as a number of international brands under the OEM sales.

The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.

The four SBUs are:1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.2. Unitary & Applied Business Unit supporting Classic, Cooline, GE and OEM brands for commercial and industrial

customers.3. Zamil CoolCare providing engineering & project management services, HVAC maintenance, retrofit services and parts.4. Geoclima srl is an independent business supporting other SBUs for their requirement of Chillers & Double skin AHU’s.

The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare Service direct their businessoperations from the corporate headquarters at Dammam, Saudi Arabia.

Geoclima has its engineering & production departments located at Monfalcone, Italy and has a design center in Austria.

All the four SBUs, while operating independently, supplement each other’s activities in a way that makes synergy work atits best and achieve the corporate goals of maximizing customer satisfaction.

Factories and ProductionsZamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one speciality production facilityin Italy operated by Geoclima.

The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central AirConditioning systems per year.

Quality & Product CertificatesThe Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2000 certification.

Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabia’s Standard Organization)Certificate for Room Air Conditioners. ZAC's products are also certified with:1. CE (Council of European Community)2. UL (Underwriters Laboratory)3. Eurovent4. ASME5. ETL

Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammedbin Fahd Al Saud Award for Factory Safety.

Our ProductsIn addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditionersmanufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from the Con-cealed Units up to 5 tons, the Ducted Splits up to 30 tons, the Packaged Units up to 90 tons, the Single and Double SkinAir Handling Units up to 70,630 CFM and the Water Chillers up to 660 tons cooling capacity.

Page 3: BY-CX series

Contents Page

Outstanding features ................................................................................................................................ 2

Model decoding ........................................................................................................................................ 3

Blower drive options ................................................................................................................................. 4

Standard specifications ......................................................................................................................... 4-5

Options and accessories ....................................................................................................................... 5-6

Physical data ............................................................................................................................................ 7

Cooling capacities ............................................................................................................................... 8-15

Fan performance data ....................................................................................................................... 16-17

Electrical data .................................................................................................................................... 18-20

Dimensions, indoor units ................................................................................................................... 21-24

Dimensions, heater box .......................................................................................................................... 25

Dimensions, outdoor units ................................................................................................................. 26-30

Typical schematic wiring diagram ...................................................................................................... 31-34

Controls and sequence of operation ....................................................................................................... 35

Installation instructions ........................................................................................................................... 36

INDEX

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

1

Page 4: BY-CX series

* HIGH EER (ENERGY EFFICIENCY RATIO)

* INDEPENDENT HORIZONTAL OR VERTICAL AIR DISCHARGE UNITS

* LOW CEILING HEIGHT REQUIREMENTS

* MICROPROCESSOR BASED CONTROLS

* ONE SIDE TOTAL SERVICE ACCESSIBILITY

* SINGLE POINT POWER ENTRY

* UV FLOW™ LIGHT EMITTERS FOR ENHANCED IAQ (INDOOR AIR QUALITY)

* NUMBERED CODED WIRES

* INSULATED DRAIN PAN

* FACTORY INSTALLED OPTIONS UPON REQUEST

* SMALL FOOTPRINT

* LIGHT WEIGHT

* PRE-PAINTED CABINETS WITH FIBERGLASS INSULATION

* LARGE CHOICE OF HEATERS; FACTORY OR FIELD INSTALLATION

* STANDARD OR OPTIONAL MOTORS; FACTORY OR FIELD INSTALLATION

* ALUMINUM OR SYNTHETIC FILTERS

* UL LISTED MAJOR COMPONENTS

OUTSTANDING FEATURES

2

Page 5: BY-CX series

1& 2

BA

SIC

3 &

4FA

CE

AR

EA(S

Q. F

T.)

7R

EFR

IGER

ATIO

NC

IRC

UIT

6EL

ECTR

ICA

LSU

PPLY

(V-P

h-H

z)

9B

LOW

ERM

OTO

R

12EV

APO

RAT

OR

CO

IL

13FI

LTER

11H

EATE

RO

PTIO

NS

(kW

/STA

GE)

BY

AIR

HA

ND

LIN

GU

NIT

03 05

S :S

ING

LEC

:208

/230

-1-6

0

H:2

08/2

30-3

-60

M:3

80-3

-60

(

4 W

IRE

)

F :4

60-3

-60

A :A

LUM

INU

M

FIN

B :

CO

ATE

DA

LUM

INU

MFI

N

C :

CO

PP

ER

FIN

N:N

O H

EA

TER

A:5

/1

B:6

/1

C:7

.5 /1

**

MO

DEL

DEC

OD

ING

8M

OD

E

C:C

OO

L O

NLY

N :

DIR

EC

TD

RIV

E

10D

RIV

E O

PTIO

NS

5AR

RANG

EMEN

T

H:H

OR

IZO

NTA

L

V:V

ER

TIC

AL

N:N

O F

ILTE

R

E:1

/2" A

LUM

INU

M

F:1

/2"

SY

NTH

ETI

C

A:1

" ALU

MIN

UM

C:1

" S

YN

THE

TIC

NO

TES:

*–

Blo

wer

mot

or R

UN

& T

RIP

indi

catio

n.

**–

Hea

ter

capa

city

will

be

7kW

for

sing

le p

hase

pow

er s

uppl

y.

1& 2

BA

SIC

3 &

4FA

CE

AR

EA(S

Q. F

T.)

7R

EFR

IGER

ATIO

NC

IRC

UIT

6EL

ECTR

ICA

LSU

PPLY

(V-P

h-H

z)

9B

LOW

ERM

OTO

R

12EV

APO

RAT

OR

CO

IL

13FI

LTER

11H

EATE

RO

PTIO

NS

(kW

/STA

GE)

BY

AIR

HA

ND

LIN

GU

NIT

07 10 14 18 25

S :S

ING

LE

D :

DU

AL

H:2

08/2

30-3

-60

M:3

80-3

-60

(

4 W

IRE

)

F :4

60-3

-60

D: 2

HP

OD

P

E:3

HP

OD

P

D: 2

HP

OD

P

E:3

HP

OD

P

G:5

HP

OD

P

J:7

.5 H

P O

DP

J:7

.5 H

P O

DP

L:1

0 H

P O

DP

A :A

LUM

INU

M

FIN

B :

CO

ATE

DA

LUM

INU

MFI

N

C :

CO

PP

ER

FIN

FOR

BY07

-BY1

4

N:N

O H

EA

TER

A:5

/1B

:6/1

C:7

.5 /1

D:1

0 /2

E:1

2/2

F:1

5 /2

G:2

0 /2

H:2

5/2

J:3

0/2

FOR

BY18

-BY2

5N

:NO

HE

ATE

RE

:12/

2F

:15

/2G

:20

/2H

:25/

2J

:30/

2K

:35/

2L

:40/

2

8M

OD

E

C:C

OO

L O

NLY

J : A

LT. I

K :

ALT

. II

10D

RIV

E O

PTIO

NS

5AR

RANG

EMEN

T

H:H

OR

IZO

NTA

L

V:V

ER

TIC

AL

FOR

BY0

7N

:NO

FIL

TER

E:1

/2" A

LUM

INU

MF

:1/2

" S

YN

THE

TIC

A:1

" ALU

MIN

UM

C:1

" S

YN

THE

TIC

N:N

O F

ILTE

RA

:1" A

LUM

INU

MB

:2" A

LUM

INU

MC

:1"

SY

NTH

ETI

CD

:2"S

YN

THE

TIC

N:N

O F

ILTE

RB

:2" A

LUM

INU

MD

:2"S

YN

THE

TIC

BY0

3 - B

Y05

BY0

7 - B

Y25

FOR

BY0

7

FOR

BY1

0

FOR

BY1

4/18

FOR

BY2

5

NO

TE: *

–Blo

wer

mot

or R

UN

& T

RIP

indi

catio

n.

FOR

BY1

8 - B

Y25

FOR

BY0

7 - B

Y14

D :

DU

AL

U:0

.5 H

P O

DP

W: 0

.75

HP

OD

P

W: 0

.75

HP

OD

P

Y: 1

HP

OD

P

FOR

BY1

0, 1

4 &

18

FOR

BY2

5

3

14O

THER

OPT

ION

S

N :

NO

OP

TIO

N

V :V

OLT

FR

EE

CO

NTA

CTS

*

15TH

ERM

OST

ATO

PTIO

N

S:U

NIT

WIT

HTH

ER

MO

STA

T

D:U

NIT

WIT

HO

UT

THE

RM

OS

TAT

14O

THER

OPT

ION

S

N :

NO

OP

TIO

N

V :V

OLT

FR

EE

CO

NTA

CTS

*

15TH

ERM

OST

ATO

PTIO

N

S:U

NIT

WIT

HTH

ER

MO

STA

T

D:U

NIT

WIT

HO

UT

THE

RM

OS

TAT

Page 6: BY-CX series

STANDARD SPECIFICATIONSA. GeneralThese Zamil Air Handling Units are factory fabricated and assembled, consisting of forward-curved fan section withblower motor, DX coil, electric heaters (optional), filters & electrical control box and are suitable for indoor applications.The unit is ready to operate when piped to a suitable condensing unit, connected to power/controls and air ducts orplenums.

They should be ordered separately as horizontal air discharge or vertical air discharge units as per application require-ments.

B. Unit EnclosureCasing Panels are of heavy gauge (G-90) galvanized steel. Removable access panels are provided for inspection andaccess to all internal parts. These panels are insulated with 1/2" thick fiberglass insulation to prevent condensation fromforming on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against deterioration anderrosion from air currents. Steel sheet is zinc-coated, galvanized by the hot dip process of lock forming quality conform-ing to ASTM A 653 commercial weight G-90, followed by baked-on electrostatic polyester dry powder coat.

C. CoilsCoils are of the enhanced louvered fin-and-tube type, constructed of copper tubes, mechanically bonded to aluminumfins. As an option, corrugated copper or enhanced coated aluminum fins may be provided. End plates and tube supportsheets are 18 gauge galvanized steel, formed to provide structural strength. Each coil is pressure tested in the factory atnot less than 300 psi (2070 kPa) air pressure. Coils conform to ARI 410.

D. Drain PansDrain pans provided under cooling coil section are made of G-90 galvanized steel with mastic coated liner for additionalcorrosion protection. Drain outlets of 3/4" NPT is provided for field connection.

E. Evaporator FanEvaporator fan is of a centrifugal forward-curved blade design and sized to meet system airflow/pressure. Fan motor(except for BY03 & BY05, which have direct drive motors) is mounted on an adjustable base and secured by a lockingdevice. Fan drive is through adjustable motor pitch pulley and belt-driven. Fan shafts are designed to operate at less than2/3rds of the first critical speed when the unit comes up to rated revolutions per minute (RPM). Units have sealed,permanently lubricated ball or sleeve fan bearing and are statically / dynamically balanced in the fan housing during finalassembly. Fan motors are of the open drip-proof type (totally enclosed types are optional) and conform to NEMA MG-1 & MG-2. Motor starters are magnetic contactor, across-the-line type.

4

BLOWER DRIVE OPTIONSMODEL

NUMBER OPTION

MOTOR BLOWER APPROX. SPEEDCHANGE PER

PULLEYTURN (RPM)

PULLEYPITCH DIA.

(INCH)

SPEED RANGE (RPM)MINIMUM MAXIMUM

PULLEYPITCH DIA.

(INCH)HP RPM

BY07

BY10

BY14

BY18

BY25

ALT. IALT. IIALT. IALT. IIALT. IALT. IIALT. IALT. IIALT. IALT. II

23235

7.55

7.57.510

1750175017501750175017501750175017501750

2.7 - 3.72.7 - 3.73.1 - 4.13.1 - 4.13.7 - 4.74.3 - 5.53.7 - 4.74.3 - 5.54.3 - 5.54.3 - 5.5

893964733875809940809875685800

11561321970115710281203102811208801023

5.64.97.46.28.08.08.08.6119.4

62714047374437403844

Page 7: BY-CX series

5

F. Microprocessor controllerThese Air handling units are provided with a microprocessor control board incorporating the following features:

• BALANCE LOADING OF COMPRESSORS: The unit’s electronic control automatically operates lead/lag sequenceof compressors. This is to load the compressors evenly over long periods of operation. If required however, compres-sor-1 can also be set to always lead. In this case, compressor-1 always starts first and stops last. (Selectable throughdip switch setting on control board).

• PUMP DOWN FUNCTION: In units equipped with pump down system, the controller provides the time delay betweensolenoid’s opening and compressor starting to equalize the pressure in the system necessary for compressor to start-up. (Selectable through dip switch setting on control board).

• COMPRESSOR ANTI-RECYCLING PROTECTION: The controller has a built-in 3 minutes minimum off timer forcompressor. This is for compressor protection in case of accidental manual re-set or immediate re-cycling of thermo-stat due to load demand.

• COMPRESSOR LOCK-OUT FUNCTION: If any of the unit’s safety control trips due to abnormal conditions, theelectronic controls locks out the compressor after a pre-determined timing preventing a re-start unless attended by aqualified service technician. The unit can be re-started through thermostat re-set after ensuring safe system condi-tions.

• FAULT DIAGNOSTICS: In case of system fault, LED’s on the board emits a flashing signal indicating where the faultis. This is to guide the service technician in identifying the fault.

• DIGITAL I/O’s: The unit’s control board is compatible to operate with a DDC controller or any standard 24V a.c.thermostat commercially available.

• SEQUENTIAL CONTROL: With input signals from the thermostat, the motors in the equipment is started in sequen-tial order: supply fan – condenser fan – compressor; at a pre-determined timings.

G. Control PanelA complete factory-wired control panel is provided to ensure safe and proper operation.

OPTIONS AND ACCESSORIESA. Zone ControlTotal comfort zone control systems are available up to 19 zones and can provide a comfortable temperature to eachzone/room (field supplied).

B. Electric HeatersElectric heaters are of the resistance open coil type and conform to the requirements of UL 573 or equivalent. Electricalcharacteristics, kW capacities and number of stages are as indicated. Thermal cut-outs, fusible links and airflow switchesare provided to shut-off power to heaters in case of airflow failure.

C. FiltersFilters are easily accessible through the filter access panel. Filters may be synthetic or permanent washable aluminumtype (refer to model decoding for details). As an accessory, bag filter section can be provided for belt driven units.

D. Discharge Air Plenum & Return Air GrilleAs an accessory, discharge air plenum with return air grilles can be provided on vertical units.

E. UV Flow™ Light EmittersThe damp & dark environment inside the AHU is ideal for the growth and development of hazardous bacteria & fungi. TheUV flow concept uses emitters of Ultra Violet light to simulate the effect of healthy sun radiation. This will inhibit the growthof these microorganisms reducing in this manner mold related allergies and diseases. Breath safely with UV flow™.

To order the UV flow™ use the kit numbers in the table below:

MODEL NUMBER BY03 BY05 BY07 BY10 BY14 BY18 BY25

KIT PART NUMBER 700-391-16 700-391-17 700-391-18 700-391-19 700-391-20 700-391-21 700-391-22

Page 8: BY-CX series

6

F. Electronic ThermostatsGeneral information: Electronic thermostat shall control one or two stage heating and cooling applications. The thermo-stat normally displays room temperature and mode of operation.

The temperature can be set by up/down buttons for both cooling and heating cycles. The thermostat also allows you toselect continuous fan operation, or have the fan on intermittent operation with the equipment.

The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a partition wall (not an outside wall), andshould not be exposed to direct light from lamps, sun etc. It should be in return air stream, away from supply air registers/diffusers.

The recommended wire length between the controller and the thermostat should not be more than 50 meters.

• Single/dual stage - Cooling & heating.

• Low voltage control - 24 VAC (nominal).

• Room temperature display - in 0C or 0F.

• Mode of operation - FAN/COOL/HEAT/AUTO.

• Fan mode - ON: Continuous fan operation; AUTO: Fan operates ON/OFF with compressor.

• Heating & cooling setpoint is permissible.

• Temperature set button - Up for increasing & down for decreasing temperature.

• Built-in compressor fault & clogged filter indication led lights.

• Remote sensing function as an option. Duct sensor is provided with the thermostat.

800-652-61 1 & 2 1 & 2 OFF-HEAT/COOL ON - AUTO

TYPICAL THERMOSTAT

Part No. HeatingStages

CoolingStages

Selector Switch Positions

Mode Switch Fan Switch

Page 9: BY-CX series

MODEL NUMBER BY03 BY05 BY07 BY10 BY14 BY18 BY25

EVAPORATOR BLOWER Type Centrifugal

Nominal airflow CFM (L/S) 1200 (566) 2000 (944) 2800 (1321) 4600 (2171) 5500 (2596) 7000 (3303) 9000 (4247)

Motor HP (Std/Alt) 0.5/0.75 0.75/1 2/3 3/2 5/7.5 5/7.5 7.5/10

Drive type Direct Direct Belt Belt Belt Belt Belt

Blower size 10x10 10x10 12x12 15x15 15x15 15x12 18x18

Quantity 1 1 1 1 1 2 2

EVAPORATOR COIL Type

Tube dia. - Rows - FPI 3/8 - 3 - 14 3/8 - 3 - 14 3/8 - 3 - 14 3/8 - 4 - 14 3/8 - 4 - 14 3/8 - 4 - 14 3/8 - 4 - 14

Face area, Sq. ft. (Sq. m.) 3.2 (0.3) 4.6 (0.43) 7 (0.65) 10 (0.93) 14 (1.3) 17.4 (1.62) 25 (2.32)

REFRIGERANT LINES Suction line size O.D. (inch) 7/8 7/8 1-1/8 1-3/8 1-3/8 - -SINGLE COMPRESSOR

Liquid line size O.D. (inch) 3/8 3/8 5/8 5/8 5/8 - -

REFRIGERANT LINES Suction line size O.D. (inch) - - 7/8 7/8 1-1/8 1-3/8 1-3/8DUAL COMPRESSOR

Liquid line size O.D. (inch) - - 1/2 1/2 5/8 5/8 7/8

RETURN AIR FILTER Size (inch) 24 x 20 x 1/2 16 x 20 x 1/2 20 x 20 x 1/2 18 x 24 x 1 20 x 24 x 1 20 x 24 x 1 20 x 24 x 2

Quantity 1 1 3 3 3 3 3

SHIPPING WEIGHT kg. (approx.) 80 120 165 225 300 340 420

Corrugated Fin & Tube

PHYSICAL DATA

7

Page 10: BY-CX series

CONDENSERENTERING AIR

TEMP. (0F)

BY03 INDOOR UNIT WITH CX030 OUTDOOR UNIT

62 67 7230.42 33.25 36.3027.36 22.62 17.823.42 3.57 3.7128.82 31.58 34.5526.95 22.34 17.513.58 3.75 3.9226.82 29.49 32.3425.25 21.75 16.923.84 4.04 4.2425.13 27.64 30.3123.75 21.17 16.324.0 4.22 4.44

23.50 25.87 28.4722.17 20.49 15.714.18 4.41 4.66

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

EVAPORATOR AIRFLOW, CFM/DR1045/0.117

EVAPORATOR ENTERING AIR, WBE (0F)

COOLING CAPACITIES(Single compressor units)

CONDENSERENTERING AIR

TEMP. (0F)

BY03 INDOOR UNIT WITH CX036 OUTDOOR UNIT

62 67 7237.57 40.90 44.4335.55 29.51 23.354.05 4.26 4.4635.59 38.82 42.2534.63 28.64 22.544.31 4.55 4.7833.34 36.42 39.7132.67 27.68 21.634.56 4.81 5.0831.19 34.13 37.2730.57 26.80 20.794.73 5.0 5.329.05 31.78 34.7828.47 25.89 19.944.94 5.24 5.56

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

EVAPORATOR AIRFLOW, CFM/DR1230/0.138

EVAPORATOR ENTERING AIR, WBE (0F)

CONDENSERENTERING AIR

TEMP. (0F)

BY05 INDOOR UNIT WITH CX048 OUTDOOR UNIT

62 67 7246.12 50.69 55.6143.86 36.24 28.494.65 4.83 4.99

43.85 48.29 53.0841.76 35.42 27.694.86 5.07 5.28

40.85 45.08 49.6839.06 34.38 26.695.11 5.36 5.6

38.21 42.24 46.6336.56 33.40 25.735.34 5.6 5.88

35.65 39.48 43.6734.11 32.41 24.785.54 5.84 6.14

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

EVAPORATOR AIRFLOW, CFM/DR1680/0.130

EVAPORATOR ENTERING AIR, WBE (0F)

CONDENSERENTERING AIR

TEMP. (0F)

BY05 INDOOR UNIT WITH CX060 OUTDOOR UNIT

62 67 7258.04 63.40 69.1757.51 47.65 37.666.09 6.36 6.6154.80 60.01 65.5453.71 46.46 36.476.48 6.8 7.1150.87 55.74 61.0449.85 44.65 34.796.77 7.11 7.4747.64 52.27 57.3346.68 43.26 33.467.03 7.41 7.8144.75 49.22 54.0443.86 42.22 32.427.37 7.79 8.25

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

EVAPORATOR AIRFLOW, CFM/DR2000/0.153

EVAPORATOR ENTERING AIR, WBE (0F)

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].4. Total unit power input includes blower motor watts at nominal CFM & 0.15 ESP.

TC – Total Capacity (1000 Btuh) GrossSC – Sensible Heat Capacity (1000 Btuh) Gross

DBE – Dry Bulb Temp. (0F) of Air Entering CoilWBE – Wet Bulb Temp. (0F) of Air Entering Coil

DBL – Dry Bulb Temp. (0F) of Air Leaving CoilWBL – Wet Bulb Temp. (0F) of Air Leaving Coil

kW – Total unit power inputDR – Wet Bulb depression ratio

MODEL No.: BY03MULTIPLIERS FOR HIGHER/LOWER CFM

% of rated airflow 80% 90% 100% 110% 120%

TC 0.965 0.985 1 1.015 1.03

SC 0.89 0.945 1 1.05 1.1

kW 0.975 0.987 1 1.012 1.025

MODEL No.: BY05

8

% of rated airflow 70% 80% 90% 100% 110% 120%

TC 0.94 0.96 0.98 1 1.015 1.03

SC 0.82 0.88 0.94 1 1.05 1.1

kW 0.94 0.96 0.98 1 1.017 1.035

Page 11: BY-CX series

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

TC – Total Capacity (1000 Btuh) GrossSC – Sensible Heat Capacity (1000 Btuh) Gross

DBE – Dry Bulb Temp. (0F) of Air Entering CoilWBE – Wet Bulb Temp. (0F) of Air Entering Coil

DBL – Dry Bulb Temp. (0F) of Air Leaving CoilWBL – Wet Bulb Temp. (0F) of Air Leaving Coil

kW – Total unit power inputDR – Wet Bulb depression ratio

BY07 INDOOR UNIT WITH CX075 OUTDOOR UNIT

BY07 INDOOR UNIT WITH CX090 OUTDOOR UNIT

62 67 72 62 67 72 62 67 7267.89 74.05 80.67 71.22 77.83 84.83 73.67 80.46 87.8858.18 48.86 39.38 66.25 54.91 43.33 71.22 60.41 46.946.98 7.35 7.7 7.34 7.69 8.07 7.9 8.25 8.6465.32 71.33 77.72 68.39 74.81 81.72 70.64 77.32 84.5057.12 47.83 38.35 65.13 53.80 42.32 68.34 59.32 45.857.42 7.81 8.21 7.78 8.17 8.58 8.34 8.73 9.1662.26 68.04 74.36 65.15 71.27 78.00 67.10 73.67 80.6355.93 46.64 37.27 63.18 52.59 41.16 65.07 58.15 44.697.91 8.34 8.78 8.27 8.7 9.18 8.84 9.28 9.7759.28 64.83 70.84 61.91 67.84 74.28 63.81 70.03 76.7554.79 45.51 36.13 60.19 51.45 40.02 62.04 56.97 43.568.45 8.92 9.42 8.82 9.29 9.82 9.39 9.88 10.4356.05 61.37 67.07 58.56 64.09 70.24 60.27 66.13 72.6353.55 44.32 34.93 57.10 50.20 38.79 58.77 55.71 42.379.03 9.55 10.1 9.42 9.93 10.52 9.99 10.52 11.14

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR1900/0.102 2400/0.126 2900/0.148

EVAPORATOR ENTERING AIR, WBE (0F)

62 67 72 62 67 72 62 67 7276.47 83.50 90.97 79.79 87.16 94.98 82.18 89.75 98.0565.81 55.14 44.24 74.21 61.35 48.26 78.58 66.98 51.967.97 8.39 8.81 8.58 8.99 9.41 9.13 9.54 9.9873.04 79.79 86.99 76.01 83.15 90.76 78.24 85.69 93.5764.56 53.87 42.98 72.85 60.03 46.99 75.03 65.75 50.658.45 8.9 9.35 9.06 9.5 9.98 9.62 10.06 10.5567.55 73.84 80.59 70.27 76.84 84.12 72.25 79.15 86.6461.66 51.10 40.39 66.76 57.15 44.40 68.64 62.80 47.988.66 9.13 9.61 9.27 9.73 10.24 9.82 10.3 10.8262.84 68.77 75.06 65.27 71.50 78.33 67.15 73.63 80.7259.52 49.07 38.43 61.82 55.08 42.41 63.59 60.72 46.029.11 9.61 10.14 9.72 10.22 10.77 10.27 10.79 11.36

58.43 63.89 69.83 60.64 66.40 72.78 62.33 68.40 74.9455.37 47.30 36.73 57.46 53.30 40.67 59.06 58.97 44.259.53 10.05 10.62 10.14 10.67 11.27 10.7 11.25 11.87

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR2250/0.118 2800/0.144 3350/0.168

EVAPORATOR ENTERING AIR, WBE (0F)

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

COOLING CAPACITIES(Single compressor units)

BY10 INDOOR UNIT WITH CX100 OUTDOOR UNIT

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

62 67 72 62 67 72 62 67 7291.75 101.12 111.16 95.56 105.54 116.36 98.47 108.90 120.1785.49 71.22 56.66 91.80 79.36 62.08 94.60 87.13 67.089.69 10.09 10.51 9.98 10.38 10.83 10.41 10.81 11.2986.62 95.77 105.72 90.22 99.94 110.50 92.90 103.01 114.1484.18 69.95 55.41 87.68 78.17 60.81 90.28 85.95 65.8910.33 10.81 11.34 10.64 11.13 11.7 11.08 11.57 12.1881.99 90.80 100.41 85.33 94.63 104.93 87.67 97.46 108.2881.55 69.64 54.83 84.88 77.98 60.34 87.20 85.89 65.4810.78 11.32 11.93 11.1 11.67 12.33 11.54 12.13 12.8477.72 86.18 95.47 80.74 89.77 99.66 82.96 92.43 102.7677.44 67.95 53.19 80.45 76.26 58.65 82.66 84.18 63.7511.25 11.85 12.54 11.58 12.21 12.96 12.04 12.68 13.4872.47 80.48 89.19 75.26 83.72 93.06 77.39 86.18 96.0372.40 65.96 51.15 75.18 74.21 56.58 77.31 82.14 61.7511.52 12.17 12.92 11.86 12.55 13.36 12.32 13.03 13.9

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR2800/0.05 3400/0.066 4000/0.076

EVAPORATOR ENTERING AIR, WBE (0F)

9

Page 12: BY-CX series

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

TC – Total Capacity (1000 Btuh) GrossSC – Sensible Heat Capacity (1000 Btuh) Gross

DBE – Dry Bulb Temp. (0F) of Air Entering CoilWBE – Wet Bulb Temp. (0F) of Air Entering Coil

DBL – Dry Bulb Temp. (0F) of Air Leaving CoilWBL – Wet Bulb Temp. (0F) of Air Leaving Coil

kW – Total unit power inputDR – Wet Bulb depression ratio

BY10 INDOOR UNIT WITH CX120 OUTDOOR UNIT

BY10 INDOOR UNIT WITH CX150 OUTDOOR UNIT

62 67 72 62 67 72 62 67 72106.95 118.06 129.79 111.72 123.64 136.21 115.24 127.56 140.6997.88 81.82 65.34 107.05 92.32 72.23 110.42 102.11 78.5211.01 11.66 12.33 11.63 12.28 12.98 12.37 13.02 13.75

101.23 111.82 123.17 105.80 117.05 129.14 108.97 120.69 133.4595.51 79.44 63.08 101.43 89.92 69.92 104.48 99.68 76.2611.51 12.21 12.94 12.13 12.84 13.61 12.88 13.59 14.3995.37 105.57 116.41 99.69 110.46 121.90 102.69 113.83 126.0091.66 77.26 60.91 95.82 87.73 67.68 98.70 97.48 74.0711.96 12.71 13.49 12.6 13.35 14.19 13.35 14.12 14.9889.38 98.91 109.24 93.25 103.53 114.48 96.00 106.75 118.1486.00 74.80 58.54 89.73 85.31 65.37 92.38 95.15 71.6512.38 13.18 14.02 13.03 13.83 14.72 13.78 14.61 15.5483.10 92.12 101.79 86.62 96.24 106.55 89.10 99.26 109.8680.09 72.42 56.14 83.48 82.81 62.90 85.87 92.68 69.1312.77 13.61 14.51 13.42 14.28 15.24 14.18 15.06 16.05

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR3200/0.059 4000/0.076 4800/0.092

EVAPORATOR ENTERING AIR, WBE (0F)

62 67 72 62 67 72 62 67 72130.02 142.54 156.21 133.29 146.38 160.80 135.29 148.70 163.15114.45 95.14 75.62 122.16 102.29 80.37 123.99 107.02 83.2913.72 14.37 15.06 14.27 14.92 15.62 14.67 15.32 16.05

123.92 136.30 149.83 127.28 139.99 154.06 128.98 141.98 156.47111.86 92.79 73.48 116.60 99.99 78.16 118.16 104.56 81.1714.65 15.39 16.21 15.19 15.95 16.8 15.6 16.36 17.23117.82 129.71 142.76 120.66 133.21 146.72 122.44 135.04 149.14108.04 90.49 71.23 110.65 97.71 75.89 112.28 102.26 78.9715.65 16.5 17.45 16.21 17.08 18.08 16.63 17.51 18.52110.68 122.08 134.66 113.45 125.24 138.40 115.03 127.02 140.52101.47 87.73 68.62 104.01 94.86 73.29 105.46 99.47 76.2816.74 17.7 18.79 17.32 18.3 19.44 17.73 18.73 19.89

103.36 114.10 126.03 105.83 117.06 129.47 107.19 118.57 131.2594.76 84.93 65.88 97.03 92.08 70.52 98.27 96.57 73.4017.85 18.93 20.16 18.43 19.54 20.83 18.86 19.99 21.3

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR4000/0.076 4600/0.088 5000/0.095

EVAPORATOR ENTERING AIR, WBE (0F)

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

COOLING CAPACITIES(Single compressor units)

BY14 INDOOR UNIT WITH CX150 OUTDOOR UNIT

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

62 67 72 62 67 72 62 67 72140.31 154.16 169.31 145.78 160.44 176.69 150.62 166.21 183.50122.35 102.38 82.14 135.93 112.88 89.15 140.44 125.29 97.2714.42 15.11 15.88 15.05 15.75 16.57 16.03 16.77 17.65133.33 147.05 161.90 138.46 152.95 168.83 143.04 158.16 175.00119.56 99.83 79.72 129.30 110.33 86.69 133.58 122.59 94.6715.3 16.1 17.02 15.95 16.78 17.77 16.96 17.83 18.89

125.84 138.90 153.28 130.51 144.42 159.72 134.70 149.36 165.75116.35 96.63 76.70 121.75 107.09 83.60 125.66 119.40 91.6916.23 17.15 18.21 16.9 17.85 18.99 17.92 18.93 20.14118.17 130.58 144.31 122.35 135.68 150.21 126.36 140.31 155.75110.48 93.76 73.87 114.39 104.21 80.70 118.14 116.56 88.7417.2 18.23 19.42 17.89 18.96 20.25 18.93 20.07 21.44

109.46 121.21 134.14 113.36 125.90 139.66 116.76 130.00 144.50102.42 90.43 70.59 106.07 100.86 77.44 109.25 113.08 85.3018.17 19.31 20.66 18.88 20.08 21.52 19.94 21.2 22.74

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR4000/0.050 4800/0.062 5800/0.076

EVAPORATOR ENTERING AIR, WBE (0F)

10

Page 13: BY-CX series

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC= 1.08 x CFM (1 – DR) (DBE – 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

TC – Total Capacity (1000 Btuh) GrossSC – Sensible Heat Capacity (1000 Btuh) Gross

DBE – Dry Bulb Temp. (0F) of Air Entering CoilWBE – Wet Bulb Temp. (0F) of Air Entering Coil

DBL – Dry Bulb Temp. (0F) of Air Leaving CoilWBL – Wet Bulb Temp. (0F) of Air Leaving Coil

kW – Total unit power inputDR – Wet Bulb depression ratio

BY07 INDOOR UNIT WITH CX075 OUTDOOR UNIT

62 67 72 62 67 72 62 67 7269.05 75.04 81.49 72.47 78.76 85.55 74.93 81.47 88.5057.49 48.24 38.86 65.41 54.10 42.68 70.94 59.52 46.156.6 6.93 7.24 6.95 7.27 7.59 7.51 7.82 8.15

66.07 71.99 78.21 69.33 75.54 82.14 71.52 78.07 85.0056.31 47.15 37.77 64.27 53.02 41.61 67.83 58.43 45.127.0 7.37 7.73 7.36 7.72 8.09 7.92 8.27 8.66

61.26 66.88 72.81 64.21 70.13 76.45 66.21 72.42 79.0054.39 45.28 35.98 61.04 51.15 39.83 62.94 56.54 43.297.49 7.9 8.32 7.86 8.26 8.7 8.43 8.83 9.2857.46 62.77 68.47 60.13 65.76 71.90 62.04 67.89 74.2552.91 43.80 34.58 57.28 49.64 38.44 59.10 55.03 41.887.88 8.32 8.77 8.25 8.69 9.17 8.82 9.27 9.7653.32 58.40 63.80 55.84 61.18 66.93 57.62 63.11 69.1350.86 42.24 33.07 53.27 48.09 36.89 54.97 53.45 40.348.28 8.76 9.25 8.66 9.14 9.66 9.24 9.72 10.28

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR1900/0.102 2400/0.126 2900/0.148

EVAPORATOR ENTERING AIR, WBE (0F)

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

BY07 INDOOR UNIT WITH CX090 OUTDOOR UNIT

62 67 72 62 67 72 62 67 7280.29 88.08 96.40 84.06 92.25 101.14 86.85 95.42 104.6968.17 57.52 46.62 76.74 63.88 50.84 83.89 69.74 54.668.03 8.43 8.79 8.63 9.01 9.36 9.18 9.54 9.8975.98 83.50 91.55 79.42 87.40 95.95 82.03 90.33 99.3466.47 55.86 45.02 75.00 62.23 49.21 79.46 68.09 53.068.65 9.09 9.51 9.25 9.68 10.09 9.81 10.23 10.6469.61 76.57 84.18 72.71 80.12 88.10 75.03 82.78 91.1163.21 52.72 42.11 69.88 59.03 46.21 72.10 64.83 49.978.93 9.39 9.85 9.53 9.99 10.45 10.09 10.55 11.0164.31 70.82 77.88 67.10 74.05 81.59 69.19 76.39 84.3360.71 50.31 39.75 64.17 56.55 43.87 66.16 62.23 47.599.38 9.89 10.39 10 10.5 11.02 10.57 11.07 11.5959.41 65.55 72.16 61.98 68.46 75.55 63.93 70.73 77.9756.95 48.48 37.94 59.41 54.68 42.03 61.28 60.45 45.699.87 10.43 10.99 10.5 11.05 11.63 11.07 11.63 12.21

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR2250/0.118 2800/0.144 3350/0.168

EVAPORATOR ENTERING AIR, WBE (0F)

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

COOLING CAPACITIES(Dual compressor units)

BY10 INDOOR UNIT WITH CX100 OUTDOOR UNIT

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

62 67 72 62 67 72 62 67 7293.82 103.66 114.41 97.93 108.49 120.03 100.92 112.02 124.1486.39 72.19 57.80 94.06 80.46 63.31 96.93 88.23 68.389.48 9.99 10.54 9.82 10.34 10.93 10.26 10.8 11.4387.97 97.60 108.02 91.70 102.00 113.14 94.47 105.26 117.0784.01 69.97 55.66 88.23 78.16 61.08 90.89 85.89 66.1910.15 10.73 11.37 10.5 11.09 11.77 10.96 11.57 12.382.35 91.53 101.50 85.78 95.66 106.40 88.37 98.67 110.0079.53 67.89 53.60 82.84 76.11 59.08 85.34 83.84 64.1510.69 11.32 12.03 11.04 11.7 12.46 11.51 12.19 12.9976.98 85.70 95.22 80.15 89.47 99.66 82.61 92.25 103.1074.49 65.83 51.57 77.56 73.97 56.95 79.94 81.68 62.0611.18 11.85 12.62 11.53 12.25 13.08 12.01 12.75 13.6371.49 79.87 88.83 74.52 83.28 93.06 76.69 86.01 96.2169.23 63.72 49.45 72.16 71.76 54.86 74.26 79.61 59.9211.28 11.99 12.8 11.65 12.39 13.25 12.12 12.89 13.82

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR2800/0.05 3400/0.066 4000/0.076

EVAPORATOR ENTERING AIR, WBE (0F)

11

Page 14: BY-CX series

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

TC – Total Capacity (1000 Btuh) GrossSC – Sensible Heat Capacity (1000 Btuh) Gross

DBE – Dry Bulb Temp. (0F) of Air Entering CoilWBE – Wet Bulb Temp. (0F) of Air Entering Coil

DBL – Dry Bulb Temp. (0F) of Air Leaving CoilWBL – Wet Bulb Temp. (0F) of Air Leaving Coil

kW – Total unit power inputDR – Wet Bulb depression ratio

BY10 INDOOR UNIT WITH CX120 OUTDOOR UNIT

BY10 INDOOR UNIT WITH CX150 OUTDOOR UNIT

62 67 72 62 67 72 62 67 72111.55 122.64 134.62 116.78 128.50 141.38 120.47 132.76 146.4897.65 81.75 65.57 109.41 92.00 72.32 112.87 101.65 78.6611.71 12.34 12.99 12.32 12.95 13.64 13.05 13.69 14.41

105.13 115.70 127.17 109.98 121.21 133.62 113.36 125.27 138.2195.16 79.27 63.14 103.26 89.55 69.94 106.44 99.28 76.1812.39 13.09 13.82 13.02 13.72 14.51 13.75 14.48 15.398.86 108.90 119.86 103.36 114.10 125.86 106.46 117.78 130.1492.68 76.82 60.76 97.21 87.14 67.53 100.13 96.79 73.7712.95 13.72 14.54 13.6 14.38 15.26 14.34 15.15 16.0793.00 102.52 112.97 97.08 107.34 118.45 99.97 110.71 122.4887.66 74.61 58.58 91.51 84.91 65.27 94.23 94.52 71.5213.44 14.27 15.17 14.09 14.94 15.91 14.85 15.73 16.7486.87 95.72 105.52 90.63 100.23 110.69 93.28 103.21 114.4182.11 72.32 56.26 85.67 82.66 63.00 88.18 92.18 69.2414.03 14.94 15.92 14.7 15.63 16.69 15.47 16.43 17.55

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR3200/0.059 4000/0.076 4800/0.092

EVAPORATOR ENTERING AIR, WBE (0F)

62 67 72 62 67 72 62 67 72128.45 140.46 153.45 131.69 144.18 157.63 133.55 146.10 159.91115.13 95.48 75.58 122.08 102.74 80.25 123.81 107.29 83.2114.33 15.09 15.92 14.89 15.66 16.52 15.3 16.08 16.95122.88 134.74 147.41 126.07 138.20 151.48 127.67 140.03 153.66112.82 93.40 73.59 116.93 100.61 78.31 118.41 105.18 81.2815.24 16.07 17.01 15.8 16.66 17.63 16.21 17.08 18.08117.12 128.32 140.69 119.86 131.62 144.34 121.35 133.53 146.55108.58 90.98 71.35 111.12 98.21 75.96 112.50 102.92 79.0116.25 17.17 18.22 16.82 17.77 18.87 17.24 18.21 19.33111.20 121.91 133.62 113.65 124.84 137.21 115.25 126.59 139.22103.19 88.76 69.10 105.46 95.87 73.80 106.95 100.55 76.8117.36 18.38 19.55 17.95 18.99 20.22 18.37 19.43 20.7104.92 115.14 126.38 107.43 118.06 129.67 108.71 119.65 131.4797.31 86.27 66.74 99.64 93.51 71.39 100.83 98.16 74.3318.59 19.71 21.03 19.19 20.34 21.71 19.62 20.79 22.2

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR4000/0.076 4600/0.088 5000/0.095

EVAPORATOR ENTERING AIR, WBE (0F)

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

COOLING CAPACITIES(Dual compressor units)

BY14 INDOOR UNIT WITH CX150 OUTDOOR UNIT

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

62 67 72 62 67 72 62 67 72136.99 150.00 164.31 142.22 155.86 171.10 146.83 161.43 177.25121.60 101.32 80.87 133.34 111.79 87.77 137.67 124.34 95.7614.53 15.32 16.22 15.19 16.01 16.97 16.2 17.07 18.09130.54 143.24 157.07 135.32 148.79 163.45 139.50 153.63 169.25119.01 98.84 78.43 126.96 109.33 85.30 130.88 121.59 93.2815.44 16.32 17.34 16.11 17.03 18.13 17.13 18.11 19.29124.10 136.30 149.66 128.42 141.50 155.59 132.43 146.09 161.25116.46 96.34 76.01 120.63 106.82 82.82 124.40 119.11 90.9116.45 17.42 18.57 17.13 18.15 19.4 18.17 19.26 20.59117.65 129.36 142.07 121.73 134.01 147.72 125.35 138.29 152.75110.56 93.81 73.49 114.39 104.11 80.33 117.80 116.38 88.2317.56 18.64 19.92 18.26 19.39 20.78 19.31 20.52 22110.85 122.08 134.14 114.61 126.31 139.45 118.02 130.50 144.00104.28 91.25 70.95 107.82 101.46 77.78 111.02 113.91 85.5918.78 19.98 21.4 19.5 20.76 22.3 20.57 21.91 23.55

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR4000/0.05 4800/0.062 5800/0.076

EVAPORATOR ENTERING AIR, WBE (0F)

12

Page 15: BY-CX series

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

TC – Total Capacity (1000 Btuh) GrossSC – Sensible Heat Capacity (1000 Btuh) Gross

DBE – Dry Bulb Temp. (0F) of Air Entering CoilWBE – Wet Bulb Temp. (0F) of Air Entering Coil

DBL – Dry Bulb Temp. (0F) of Air Leaving CoilWBL – Wet Bulb Temp. (0F) of Air Leaving Coil

kW – Total unit power inputDR – Wet Bulb depression ratio

BY14 INDOOR UNIT WITH CX180 OUTDOOR UNIT

62 67 72 62 67 72 62 67 72166.22 180.64 196.10 173.51 188.84 205.30 178.59 194.57 211.94141.12 118.19 94.89 160.18 132.32 104.07 168.80 145.53 112.6016.4 16.76 17.09 17.29 17.61 17.96 18.53 18.86 19.25

159.90 173.97 188.90 166.80 181.69 197.72 171.69 187.13 203.97138.51 115.70 92.43 157.59 129.80 101.63 162.48 143.03 110.1317.75 18.13 18.48 18.62 18.97 19.36 19.87 20.21 20.66153.57 167.10 181.69 160.09 174.54 190.13 164.50 179.69 196.29135.99 113.15 90.02 151.71 127.31 99.23 155.88 140.54 107.8419.34 19.74 20.14 20.2 20.58 21.03 21.44 21.82 22.33147.05 160.42 174.67 153.14 167.38 182.54 157.59 172.25 188.33133.35 110.76 87.73 145.33 124.86 96.85 149.56 138.08 105.4121.11 21.54 21.99 21.96 22.38 22.89 23.2 23.62 24.2

140.34 152.98 166.90 145.95 159.52 174.48 150.12 164.24 179.79130.67 107.93 85.09 138.58 121.97 94.26 142.54 135.28 102.7223.05 23.52 24.03 23.89 24.35 24.95 25.12 25.6 26.27

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR4400/0.056 5500/0.073 6600/0.088

EVAPORATOR ENTERING AIR, WBE (0F)

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

COOLING CAPACITIES(Dual compressor units)

BY18 INDOOR UNIT WITH CX180 OUTDOOR UNIT

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

62 67 72 62 67 72 62 67 72173.83 189.16 205.70 180.90 197.19 215.07 185.87 203.26 221.94155.56 129.23 102.57 171.49 145.30 113.09 176.20 160.79 122.9917.45 17.8 18.19 18.14 18.48 18.94 19.05 19.42 19.94167.23 182.15 198.30 173.76 189.82 207.19 178.63 195.41 213.81152.70 126.49 99.97 164.66 142.57 110.45 169.27 157.92 120.3719.03 19.41 19.85 19.71 20.09 20.62 20.62 21.02 21.63160.63 175.14 191.12 167.18 182.72 199.59 171.73 187.88 205.67150.05 123.94 97.65 158.64 140.21 108.11 162.95 155.43 117.8920.47 20.87 21.37 21.13 21.56 22.15 22.04 22.49 23.17153.81 168.14 183.50 160.04 175.07 191.72 164.16 180.02 197.54146.19 121.55 95.22 152.11 137.63 105.75 156.03 152.91 115.5522.28 22.73 23.3 22.95 23.42 24.1 23.85 24.36 25.14146.77 160.48 175.66 152.63 167.15 183.30 156.59 171.84 188.75139.62 118.72 92.68 145.20 134.88 103.10 148.97 150.16 112.8624.28 24.78 25.43 24.94 25.47 26.25 25.84 26.41 27.31

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR5050/0.052 6300/0.067 7550/0.082

EVAPORATOR ENTERING AIR, WBE (0F)

BY18 INDOOR UNIT WITH CX220 OUTDOOR UNIT

62 67 72 62 67 72 62 67 72197.82 214.55 232.26 206.71 224.51 243.58 212.85 231.41 251.56166.78 139.90 112.50 188.92 156.33 123.30 202.67 171.70 133.2320.44 20.85 21.2 21.16 21.52 21.89 22.05 22.4 22.83190.34 206.67 223.98 198.75 216.04 234.62 204.95 222.90 242.45163.63 136.92 109.68 185.74 153.28 120.38 195.43 168.87 130.4322.18 22.62 23.01 22.89 23.28 23.71 23.77 24.16 24.64182.64 198.13 215.06 190.51 207.30 225.12 196.40 213.73 232.68160.49 133.65 106.63 181.90 150.20 117.29 187.53 165.74 127.3924.12 24.61 25.04 24.83 25.26 25.73 25.7 26.14 26.67174.49 189.59 205.70 182.00 198.01 215.34 187.52 204.24 222.59157.13 130.51 103.45 174.00 146.87 114.15 179.28 162.52 124.2826.28 26.82 27.3 26.98 27.47 28 27.87 28.34 28.93165.69 179.96 195.69 172.67 188.18 204.75 177.65 193.77 211.53153.59 126.92 100.13 165.34 143.49 110.80 170.11 158.93 120.8928.71 29.29 29.84 29.4 29.93 30.52 30.27 30.8 31.46

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR5050/0.054 6300/0.069 7550/0.085

EVAPORATOR ENTERING AIR, WBE (0F)

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

13

Page 16: BY-CX series

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

TC – Total Capacity (1000 Btuh) GrossSC – Sensible Heat Capacity (1000 Btuh) Gross

DBE – Dry Bulb Temp. (0F) of Air Entering CoilWBE – Wet Bulb Temp. (0F) of Air Entering Coil

DBL – Dry Bulb Temp. (0F) of Air Leaving CoilWBL – Wet Bulb Temp. (0F) of Air Leaving Coil

kW – Total unit power inputDR – Wet Bulb depression ratio

BY18 INDOOR UNIT WITH CX240 OUTDOOR UNIT

62 67 72 62 67 72 62 67 72222.29 241.32 261.17 232.72 252.49 273.66 240.10 260.74 282.78183.63 154.41 124.47 208.00 172.25 136.12 226.22 189.23 146.9822.9 23.47 23.9 23.84 24.32 24.73 24.99 25.42 25.86

214.73 233.31 252.72 224.49 243.99 264.61 231.32 251.64 273.00180.49 151.41 121.61 204.75 169.30 133.23 218.24 186.14 143.9324.89 25.48 25.93 25.81 26.32 26.77 26.95 27.41 27.9206.92 224.81 243.55 216.25 234.88 254.96 222.54 242.17 263.22177.42 148.30 118.54 201.78 166.14 130.20 210.34 183.02 141.0627.07 27.71 28.22 27.98 28.54 29.07 29.12 29.64 30.21198.14 215.34 233.66 206.80 224.87 244.40 213.02 231.97 252.00173.52 144.49 115.02 195.39 162.31 126.61 201.27 179.32 137.3329.48 30.18 30.76 30.38 31 31.61 31.51 32.1 32.76189.59 206.12 223.52 197.65 215.16 233.84 203.14 221.41 241.14170.28 141.24 111.69 187.09 159.11 123.36 192.28 175.79 134.1532.1 32.86 33.52 33 33.68 34.39 34.12 34.78 35.55

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR5600/0.061 7000/0.078 8400/0.094

EVAPORATOR ENTERING AIR, WBE (0F)

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

COOLING CAPACITIES(Dual compressor units)

62 67 72 62 67 72 62 67 72227.97 247.37 268.19 239.54 260.44 282.87 247.45 269.22 292.89192.01 160.52 128.63 219.15 180.87 142.09 230.75 199.71 154.3022.43 22.88 23.27 23.06 23.45 23.88 23.87 24.26 24.76219.87 238.79 259.14 230.72 251.01 272.84 238.43 259.47 282.80188.44 157.12 125.42 215.09 177.27 138.67 222.28 196.18 151.0724.41 24.88 25.31 25.01 25.44 25.94 25.81 26.24 26.83211.24 229.68 249.31 221.57 241.26 262.50 228.63 249.32 271.55184.82 153.70 122.06 206.63 173.78 135.34 213.21 192.72 147.4826.57 27.1 27.6 27.17 27.66 28.25 27.97 28.47 29.16202.35 220.32 239.22 212.09 231.18 251.83 218.82 238.79 260.30181.07 150.17 118.61 197.82 170.14 131.88 204.10 189.03 143.9428.94 29.53 30.12 29.54 30.09 30.8 30.33 30.91 31.72193.20 210.43 228.62 202.29 220.77 240.52 208.63 227.86 248.66177.56 146.67 115.20 188.99 166.69 128.41 194.91 185.51 140.5431.52 32.18 32.86 32.11 32.74 33.56 32.9 33.57 34.51

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR6000/0.041 7500/0.054 9000/0.067

EVAPORATOR ENTERING AIR, WBE (0F)

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

BY25 INDOOR UNIT WITH CX240 OUTDOOR UNIT

BY25 INDOOR UNIT WITH CX300 OUTDOOR UNIT

62 67 72 62 67 72 62 67 72285.80 309.95 335.79 299.22 325.01 352.24 308.71 335.24 364.03239.93 201.44 162.41 272.08 225.42 177.91 294.45 247.63 192.3028.62 29.3 29.89 29.59 30.2 30.82 30.92 31.51 32.18275.45 299.03 324.00 287.84 312.92 339.44 296.47 322.60 350.53235.48 197.21 158.24 267.39 220.91 173.62 282.98 243.14 187.9631.3 31.99 32.59 32.24 32.85 33.49 33.54 34.14 34.86

264.16 287.17 311.59 276.08 300.43 326.64 284.71 309.95 337.03230.76 192.72 154.01 262.81 216.44 169.56 272.21 238.93 183.8134.16 34.91 35.58 35.08 35.76 36.51 36.38 37.05 37.87252.24 274.68 298.55 263.53 287.17 312.67 271.53 296.38 322.60225.65 187.88 149.47 252.07 211.53 164.91 259.73 234.17 179.2137.31 38.12 38.89 38.22 38.97 39.83 39.5 40.26 41.2240.31 261.88 284.90 250.98 273.90 298.32 258.35 282.33 307.71221.07 183.26 144.95 240.54 207.10 160.42 247.61 229.56 174.7340.73 41.62 42.5 41.63 42.47 43.45 42.92 43.77 44.85

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR7200/0.052 9000/0.067 10800/0.082

EVAPORATOR ENTERING AIR, WBE (0F)

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SC` kW

14

Page 17: BY-CX series

COOLING CAPACITIES(Dual compressor units)

BY25 INDOOR UNIT WITH CX360 OUTDOOR UNIT

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

TC – Total Capacity (1000 Btuh) GrossSC – Sensible Heat Capacity (1000 Btuh) Gross

DBE – Dry Bulb Temp. (0F) of Air Entering CoilWBE – Wet Bulb Temp. (0F) of Air Entering Coil

DBL – Dry Bulb Temp. (0F) of Air Leaving CoilWBL – Wet Bulb Temp. (0F) of Air Leaving Coil

kW – Total unit power inputDR – Wet Bulb depression ratio

62 67 72 62 67 72 62 67 72323.14 350.38 379.01 333.07 360.98 390.58 340.39 369.36 399.83276.99 230.76 183.70 302.51 249.42 195.70 318.43 267.30 207.1234.57 35.42 36.11 35.73 36.5 37.18 37.02 37.75 38.44311.37 337.89 365.43 320.72 347.77 376.55 327.84 355.84 385.34271.78 225.84 178.88 297.22 244.36 190.91 306.52 262.30 202.3237.49 38.36 39.07 38.63 39.43 40.13 39.91 40.66 41.39298.82 324.23 351.47 307.45 333.66 361.62 314.25 341.27 370.34266.86 220.89 174.42 287.87 239.45 186.24 294.23 257.37 197.8540.71 41.65 42.44 41.84 42.7 43.5 43.11 43.93 44.76286.27 310.97 337.11 294.64 320.01 347.13 300.65 326.71 354.83261.76 216.06 169.66 276.04 234.70 181.68 281.67 252.24 192.9744.33 45.34 46.22 45.44 46.39 47.29 46.71 47.61 48.56273.33 296.92 321.98 280.92 305.44 331.29 286.54 311.62 338.79256.53 211.24 164.90 263.64 229.90 176.84 268.92 247.36 188.2748.3 49.39 50.38 49.39 50.43 51.46 50.66 51.65 52.74

CONDENSERENTERING AIR

TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR9000/0.065 10500/0.079 12000/0.092

EVAPORATOR ENTERING AIR, WBE (0F)

TC85 SC

kWTC

95 SCkWTC

105 SCkWTC

115 SCkWTC

125 SCkW

15

Page 18: BY-CX series

BLOWER MOTOR HP BLOWER MOTOR

SPEED 0.1 0.2 0.3 0.4 0.5 0.6HIGH 1350 1290 1220 1160 1070 990

0.5 MEDIUM 1260 1200 1125 1060 1000 900

LOW 1070 1020 960 900 830 740

HIGH 1660 1480 1300 1230 1140 10600.75 MEDIUM 1570 1375 1180 1120 1060 960

LOW 1500 1320 1130 940 870 780

MODEL No.: BY03

FAN PERFORMANCE DATADIRECT DRIVE MOTORS

CFM @ External Static Pressure (inch wg.)

BLOWER MOTOR HP BLOWER MOTOR

SPEED 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8HIGH 2010 1920 1820 1730 1620 1490 1350 1230

0.75 MEDIUM 1830 1740 1660 1570 1470 1360 1240 1100

LOW 1710 1650 1570 1490 1390 1300 1170 975

HIGH 2252 2215 2180 2140 2105 2065 2020 1950

1.0 MEDIUM 2021 1990 1950 1920 1880 1840 1795 1700

LOW 1820 1805 1790 1735 1700 1665 1630 1530

MODEL No.: BY05CFM @ External Static Pressure (inch wg.)

BELT DRIVEN MOTORSMODEL No.: BY07

NOTES (For BY07/BY10): 1. Values include losses for filters, unit casing and wet coils.2. 2 HP motor and alternative drive I to be used for the unshaded portion.3. 3 HP motor and alternative drive II to be used for the shaded portion.

2800 (1321)3000 (1416)3200 (1510)3400 (1605)3600 (1699)3800 (1793)4000 (1888)4200 (1982)4400 (2076)4600 (2170)4800 (2265)5000 (2360)

Airflow,CFM (L/S)

0.2RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP610 0.62 710 0.75 745 0.87 760 0.95 850 1.2625 0.69 720 0.80 760 0.95 810 1.12 865 1.25636 0.77 734 0.92 780 1.06 820 1.26 870 1.38660 0.88 746 1.01 805 1.18 833 1.34 881 1.5675 1.0 760 1.16 820 1.32 848 1.48 900 1.66700 1.13 778 1.3 840 1.43 868 1.63 913 1.8727 1.28 790 1.45 865 1.62 882 1.8 926 1.96772 1.41 843 1.62 880 1.78 921 1.96 968 2.16791 1.58 864 1.79 887 1.94 934 2.14 979 2.34840 1.79 890 1.96 931 2.2 975 2.38 1017 2.59

857 1.95 906 2.17 947 2.4 988 2.57 1035 2.76

876 2.15 920 2.38 961 2.6 1005 2.76

External Static Pressure (inch wg.)0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP905 1.32 965 1.5 1000 1.6 1054 1.8 1100 2.0915 1.4 970 1.6 1013 1.75 1065 2.0 1115 2.15925 1.51 978 1.73 1023 1.86 1073 2.1 1122 2.28939 1.67 983 1.84 1033 2.02 1083 2.25 1128 2.44950 1.82 995 1.98 1043 2.21 1090 2.41 1131 2.6966 2.0 1006 2.18 1056 2.39 1100 2.58 1143 2.78980 2.18 1023 2.4 1066 2.6 1108 2.771011 2.36 1054 2.56 1096 2.761024 2.54 1067 2.771058 2.77

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

MODEL No.: BY10

I

II

16

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

820* 0.62* 900 0.71 965 0.82 1020 0.88 1102 1.03

824* 0.7* 905 0.79 970 0.91 1026 1.0 1107 1.12

853 0.81 927 0.91 986 1.02 1041 1.13 1111 1.25

950 0.94 1004 1.05 1059 1.21 1132 1.27 1155 1.38

968 1.1 1032 1.22 1086 1.33 1150 1.45 1194 1.57

1054 1.4 1106 1.5 1160 1.61 1216 1.76 1261 1.88

1066 1.55 1133 1.7 1180 1.82 1234 1.94 1276 2.09

1091 1.75 1157 1.91 1202 2.02 1255 2.2 1307 2.33

1116 1.96 1171 2.1 1228 2.3 1276 2.45 1329 2.6

1800 (849)2000 (944)2200 (1038)2400 (1133)2600 (1227)2800 (1321)3000 (1416)3200 (1510)3400 (1605)

Airflow,CFM (L/S)

External Static Pressure (inch wg.)1.0 1.2 1.4

RPM BHP RPM BHP

1145 1.14 1220 1.26

1152 1.25 1225 1.35

1160 1.36 1237 1.48

1244 1.5 1297 1.65

1250 1.69 1305 1.82

1323 2.02 1380* 2.2*1334* 2.23* 1400* 2.3*1359* 2.47*1368* 2.73*

0.80.60.40.2

I

II

NOTE: 1. Values include losses for dry coil, filter & unit casing.2. Direct drive motors have single speed connection only. Thermostats are also single speed type only. Refer to the unit wiring diagram for connecting to other motor speeds.

Page 19: BY-CX series

BHP RPM BHP RPM BHP RPM BHP RPM BHP4.5 940 5.0 980 5.46 1010 6.0 1059* 6.6*4.73 942 5.23 981 5.71 1011 6.3 1060* 6.92*4.96 944 5.45 982 5.97 1013 6.6 1062* 7.22*5.2 945 5.68 983 6.23 1014 6.95 1063* 7.51*5.45 947 5.9 985 6.5 1016 7.25 1064* 7.78*5.65 948 6.12 986 6.8 1018 7.5 1065* 8.05*5.97 949 6.48 988 7.2 1019 7.8 1066* 8.35*6.3 951 6.8 990 7.6 1020 8.1 1067* 8.65*6.75 953 7.15 992 8.0 1021 8.45 1068* 9.0*7.1 955 7.6 994 8.35 1022 8.75 1069* 9.45*7.4 957 8.06 996 8.71 1023 9.25 1070* 9.8*7.85 965 8.4 1003 9.1 1034* 9.7*8.3 973 8.8 1009 9.58.7 981 9.25 1014 9.99.15 989 9.69.6 996 10.1

FAN PERFORMANCE DATA (BELT DRIVEN MOTORS)

4000 (1888)4200 (1982)4400 (2076)4600 (2170)4800 (2265)5000 (2360)5200 (2454)5400 (2548)5600 (2643)5800 (2737)6000 (2832)6200 (2926)6400 (3020)6600 (3115)

Airflow,CFM (L/S)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP694* 1.21* 743* 1.3* 797 1.52 845 1.66 890 1.83705* 1.33* 761* 1.45* 811 1.67 857 1.81 903 2.0719* 1.43* 774 1.6 823 1.8 869 1.97 918 2.17735* 1.57* 787 1.75 835 1.95 885 2.17 929 2.34748* 1.72* 800 1.92 846 2.09 897 2.35 935 2.52761* 1.87* 812 2.09 862 2.30 904 2.52 948 2.70778 2.06 823 2.27 873 2.48 917 2.70 959 2.91800 2.31 846 2.5 894 2.72 934 2.94 979 3.15808 2.46 858 2.7 903 2.90 945 3.12 987 3.38826 2.68 869 2.9 917 3.12 955 3.4 1000 3.65837 2.90 885 3.12 927 3.37 965 3.64 1009 3.9850 3.12 900 3.41 940 3.65 980 3.92 1021 4.17879 3.41 920 3.70 962 3.96 1000 4.2 1040 4.45894 3.76 933 4.0 973 4.24 1013 4.44 1050 4.68

0.2External Static Pressure (inch wg.)MODEL No.: BY14

0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP937 2.03 975 2.25 992 2.4 1075 2.64 1102 2.85951 2.19 992 2.43 1002 2.6 1080 2.82 1110 3.05963 2.33 1006 2.58 1010 2.78 1093 2.97 1133 3.2971 2.55 1013 2.75 1053 2.93 1100 3.17 1138 3.41979 2.72 1023 2.91 1065 3.14 1107 3.4 1144 3.62989 2.91 1032 3.11 1068 3.37 1113 3.6 1150 3.86

1001 3.11 1038 3.34 1070 3.59 1119 3.85 1159 4.081019 3.38 1056 3.64 1098 3.88 1133 4.10 1171 4.361028 3.65 1063 3.83 1106 4.14 1139 4.35 1176 4.571041 3.9 1078 4.13 1114 4.37 1150 4.6 1186 4.781047 4.13 1088 4.35 1123 4.59 1157 4.85 1194 5.051061 4.38 1100 4.66 1133 4.85 1167 5.1 1205 5.41078 4.69 1114 4.92 1150 5.2 1183 5.45 1218 5.761091 4.92 1125 5.2 1161 5.51 1194 5.8 1229 6.08

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP955 2.66 1005 2.96 1057 3.3 1104 3.6 1153* 3.88*961 2.83 1010 3.15 1060 3.46 1107 3.76 1155* 4.04*966 2.96 1012 3.23 1062 3.57 1109 3.88 1157* 4.27*968 3.07 1015 3.38 1065 3.73 1110 4.07 1158* 4.4*970 3.23 1020 3.53 1066 3.84 1113 4.18 1159* 4.59*980 3.4 1025 3.69 1070 4.0 1118 4.4 1162* 4.72*985 3.56 1030 3.84 1080 4.27 1120 4.63 1163* 4.95*990 3.72 1036 4.04 1082 4.45 1126 4.82 1165* 5.09*1000 3.88 1045 4.23 1083 4.6 1127 5 1170* 5.3*1004 4.14 1050 4.47 1090 4.83 1134 5.16 1175* 5.51*1012 4.28 1054 4.66 1095 5.04 1135 5.39 1179* 5.72*1017 4.47 1059 4.85 1100 5.19 1141* 5.58* 1183* 5.95*1021 4.68 1065 5.09 1108 5.47 1150* 5.8* 1185* 6.12*1026 4.85 1069 5.23 1112 5.66 1154* 6* 1193* 6.42*1041 5.14 1083 5.47 1125 5.9 1158* 6.36* 1200* 6.78*1046 5.33 1087 5.75 1128 6.12 1164* 6.6*1054 5.56 1100 6 1132 6.36 1172* 6.84*1066 5.85 1107 6.24 1140 6.72

5000 (2360)5200 (2454)5400 (2548)5600 (2643)5800 (2737)6000 (2832)6200 (2926)6400 (3020)6600 (3115)6800 (3209)7000 (3303)7200 (3398)7400 (3492)7600 (3587)7800 (3681)8000 (3775)8200 (3870)8400 (3964)

Airflow,CFM (L/S)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP715* 1.33* 731* 1.56* 787* 1.82* 850 2.07 902 2.4718* 1.42* 737* 1.68* 793* 1.96* 856 2.26 905 2.53721* 1.53* 750* 1.81* 802* 2.07* 860 2.35 911 2.66725* 1.68* 756* 1.92* 807 2.21 866 2.5 916 2.79729* 1.81* 762* 2.03* 816 2.35 872 2.64 921 2.9733* 1.9* 775* 2.14* 833 2.42 877 2.78 930 3.02738* 2.03* 788* 2.35* 839 2.57 888 2.92 935 3.24745* 2.15* 795* 2.5* 850 2.71 900 3.08 940 3.41753* 2.38* 800* 2.64* 855 2.92 905 3.25 950 3.58761* 2.5* 810 2.78 863 3.08 910 3.41 960 3.75772* 2.69* 820 2.92 875 3.33 918 3.58 967 3.95777* 2.84* 830 3.08 880 3.41 927 3.75 976 4.14794* 2.96* 845 3.3 890 3.62 936 3.95 985 4.4805 3.18 850 3.5 900 3.83 941 4.2 990 4.57820 3.36 870 3.69 909 4.1 954 4.5 1002 4.9830 3.59 880 3.86 922 4.25 963 4.65 1008 5.05867 3.77 890 4.1 936 4.5 972 4.9 1016 5.25890 4.05 904 4.42 945 4.75 986 5.1 1025 5.45

0.2External Static Pressure (inch wg.)MODEL No.: BY18

0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

NOTES (For BY14/BY18): 1. Values include losses for filters, unit casing and wet coils.2. Standard 5 HP motor and alternative drive I to be used for the unshaded portion.3. Alt. 7.5 HP motor and alternative drive II to be used for the shaded portion.* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

I II

I II

17

NOTES: 1. Values include losses for filters, unit casing and wet coils.2. Standard 7.5 HP motor to be used for the unshaded portion.3. Alt. 10 HP motor to be used for the shaded portion.

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

6000 (2832)6400 (3020)6800 (3209)7200 (3398)7600 (3587)8000 (3775)8400 (3964)8800 (4152)9200 (4341)9600 (4530)

10000 (4719)10400 (4907)10800 (5096)11200 (5286)11600 (5474)12000 (5663)

Airflow,CFM (L/S)

0.4External Static Pressure (inch wg.)

MODEL No.: BY25

0.6 0.8 1.0 1.2 1.4 2.01.81.6

I IIRPM BHP RPM BHP RPM BHP RPM BHP RPM700 2.6 762 3.12 812 3.6 847 4.0 870706 2.8 764 3.3 813 3.78 848 4.22 871716 3.05 766 3.5 814 4.0 849 4.42 872722 3.24 768 3.7 815 4.19 850 4.64 873732 3.4 770 3.82 816 4.35 851 4.88 874740 3.6 772 4.0 818 4.56 852 5.18 875751 3.9 778 4.35 821 4.85 853 5.5 876759 4.2 784 4.65 824 5.16 857 5.81 878770 4.5 790 5.0 828 5.5 862 6.14 880779 4.9 796 5.35 832 5.84 870 6.45 900790 5.2 806 5.67 838 6.15 878 6.7 915801 5.55 813 6.1 849 6.6 890 7.1 920809 5.9 825 6.5 870 7.0 898 7.5 928821 6.4 856 6.9 876 7.4 906 7.95 936852 6.8 872 7.3 885 7.9 914 8.45 944870 7.2 885 7.8 892 8.5 925 9.0 952

Page 20: BY-CX series

MIN. MAX. HP FLA kW FLA– – 2.3 155 21.7 29.4 30

0.50 1.8 6/7 26.1/30.4 34.9/40.3 40/4510*/12* 43.5/52.2 56.6/67.5 60/70

208/230-1-60 187 25314* 60.9 78.4 80– – 5.9 155 21.7 33 35

0.75 4.7 6/7 26.1/30.4 38.5/43.9 40/4510*/12* 43.5/52.2 60.3/71.1 70/80

14* 60.9 82 90– – 2.3 155 12.6 18 20

0.50 1.8 6/7.5 15.1/18.8 21.1/25.8 25/3010*/12* 25.1/30.1 33.6/39.9 35/40

208/230-3-60 187 25315* 37.7 49.4 50– – 5.9 155 12.6 21.6 25

0.75 4.7 6/7.5 15.1/18.8 24.8/29.4 30/3510*/12* 25.1/30.1 37.3/43.5 40/45

15* 37.7 53 60– – 2.3 155 7.6 11.8 15

0.50 1.8 6/7.5 9.1/11.4 13.6/16.5 15/2010*/12* 15.2/18.2 21.3/25 25/30

380-3-60 342 418 15* 22.8 30.8 35– – 5.9 155 7.6 15.4 20

0.75 4.7 6/7.5 9.1/11.4 17.3/20.1 20/2510*/12* 15.2/18.2 24.9/28.6 30/30

15* 22.8 34.4 35– – 1.3 155 6.3 9.1 15

0.50 1.0 6/7.5 7.5/9.4 10.6/13 15/2010*/12* 12.6/15.1 17/20.1 20/25

460-3-60 414 50615* 18.8 24.8 30– – 3.3 155 6.3 11.1 15

0.75 2.6 6/7.5 7.5/9.4 12.6/15 15/2010*/12* 12.6/15.1 19/22.1 20/25

15* 18.8 26.8 30

POWERSUPPLY(V-Ph-Hz)

VOLTAGERANGE

BLOWER

MOTOR** ELECTRIC HEATERMCA MOCP

ELECTRICAL DATAMODEL No.: BY03

MODEL No.: BY05

MIN. MAX. HP FLA kW FLA– – 5.9 155 21.7 33 40

0.75 4.7 6/7 26.1/30.4 38.5/43.9 45/5010*/12* 43.5/52.2 60.3/71.1 70/80

208/230-1-60 187 25314* 60.9 82 90– – 10.3 155 21.7 37.4 40

1.0 8.2 6/7 26.1/30.4 42.9/48.3 45/5010*/12* 43.5/52.2 64.6/75.5 70/80

14* 60.9 86.4 90– – 5.9 155 12.6 21.6 25

0.75 4.7 6/7.5 15.1/18.8 24.8/29.4 25/3010*/12* 25.1/30.1 37.3/43.5 40/45

208/230-3-60 187 25315* 37.7 53 60– – 10.3 155 12.6 26 30

1.0 8.2 6/7.5 15.1/18.8 29.1/33.8 30/3510*/12* 25.1/30.1 41.6/47.9 45/50

15* 37.7 57.4 60– – 5.9 155 7.6 15.4 20

0.75 4.7 6/7.5 9.1/11.4 17.3/20.1 20/2510*/12* 15.2/18.2 24.9/28.6 25/30

380-3-60 342 41815* 22.8 34.3 35– – 10.3 155 7.6 19.8 25

1.0 8.2 6/7.5 9.1/11.4 21.6/24.5 25/3010*/12* 15.2/18.2 29.3/33 30/35

15* 22.8 38.8 40– – 3.8 155 6.3 11.6 15

0.75 3.0 6/7.5 7.5/9.4 13.1/15.5 15/2010*/12* 12.6/15.1 19.5/22.6 20/25

460-3-60 414 50615* 18.8 27.3 30– – 5.5 155 6.3 13.4 15

1.0 4.4 6/7.5 7.5/9.4 14.9/17.3 20/2010*/12* 12.6/15.1 21.3/24.4 25/25

15* 18.8 29 30

POWERSUPPLY(V-Ph-Hz)

VOLTAGERANGE

BLOWERMOTOR** ELECTRIC HEATER

MCA MOCP

MIN. MAX. HP FLA kW FLA

– – 8.3 15

5 12.6 24 25

208/230-3-60 187 253

2 6.6 6/7.5 15.1/18.8 27.1/31.8 30/35

10*/12* 25.1/30.1 39.6/45.9 40/50

15*/20* 37.7/50.2 55.4/71 60/80

25*/30* 62.8/75.3 86.8/102.4 90/110

– – 11 20

5 12.6 26.8 30

3 8.8 6/7.5 15.1/18.8 29.9/34.5 35/35

10*/12* 25.1/30.1 42.4/48.6 45/50

15*/20* 37.7/50.2 58.1/73.8 60/80

25*/30* 62.8/75.3 89.5/105.1 90/110

– – 5 15

5 7.6 14.5 15

380-3-60 342 418

2 4 6/7.5 9.1/11.4 16.4/19.3 20/20

10*/12* 15.2/18.2 24/27.8 25/30

15*/20* 22.8/30.4 33.5/43 35/45

25*/30* 38/45.6 52.5/62 60/70

– – 6.4 15

5 7.6 15.9 20

3 5.14 6/7.5 9.1/11.4 17.8/20.7 20/25

10*/12* 15.2/18.2 25.4/29.2 30/30

15*/20* 22.8/30.4 34.9/44.4 40/45

25*/30* 38/45.6 53.9/63.4 60/70

– – 4.4 15

5 6.3 12.3 15

460-3-60 414 506

2 3.5 6/7.5 7.5/9.4 13.8/16.1 15/20

10*/12* 12.6/15.1 20.1/23.3 25/25

15*/20* 18.8/25.1 27.9/35.8 30/40

25*/30* 31.4/37.7 43.6/51.5 45/60

– – 5.1 15

5 6.3 13 15

3 4.1 6/7.5 7.5/9.4 14.5/16.9 15/20

10*/12* 12.6/15.1 20.9/24 25/25

15*/20* 18.8/25.1 28.6/36.5 30/40

25*/30* 31.4/37.7 44.4/52.3 45/60

POWERSUPPLY(V-Ph-Hz)

VOLTAGERANGE

BLOWERMOTOR ELECTRIC HEATER

MCA MOCP

MODEL No.: BY07

(4 WIRE)

(STD.)

(STD.)

(ALT.)

(ALT.)

LEGEND

FLA – Full Load Amps

HP – Horse Power

MCA – Minimum Circuit Amps

MOCP – Maximum Over Current Protection

* Combination of 2 heater modules

** Single phase motors(208/230V-1Ph-60Hz for 208/230V-3Ph-60Hz & 380V-3Ph-60Hz power supply.460V-1Ph-60Hz for 460V-3Ph-60Hz power supply).

(4 WIRE)

(STD.)

(4 WIRE)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(STD.)

(ALT.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

18

Page 21: BY-CX series

ELECTRICAL DATA

MIN. MAX. HP FLA kW FLA

– – 8.3 15

5 12.6 24 25

208/230-3-60 187 253

2 6.6 6/7.5 15.1/18.8 27.1/31.8 30/35

10*/12* 25.1/30.1 39.6/45.9 40/50

15*/20* 37.7/50.2 55.4/71 60/80

25*/30* 62.8/75.3 86.8/102.4 90/110

– – 11 20

5 12.6 26.8 30

3 8.8 6/7.5 15.1/18.8 29.9/34.5 35/35

10*/12* 25.1/30.1 42.4/48.6 45/50

15*/20* 37.7/50.2 58.1/73.8 60/80

25*/30* 62.8/75.3 89.5/105.1 90/110

– – 5 15

5 7.6 14.5 15

380-3-60 342 418

2 4 6/7.5 9.1/11.4 16.4/19.3 20/20

10*/12* 15.2/18.2 24/27.8 25/30

15*/20* 22.8/30.4 33.5/43 35/45

25*/30* 38/45.6 52.5/62 60/70

– – 6.4 15

5 7.6 15.9 20

3 5.14 6/7.5 9.1/11.4 17.8/20.7 20/25

10*/12* 15.2/18.2 25.4/29.2 30/30

15*/20* 22.8/30.4 34.9/44.4 40/45

25*/30* 38/45.6 53.9/63.4 60/70

– – 4.4 15

5 6.3 12.3 15

460-3-60 414 506

2 3.5 6/7.5 7.5/9.4 13.8/16.1 15/20

10*/12* 12.6/15.1 20.1/23.3 25/25

15*/20* 18.8/25.1 27.9/35.8 30/40

25*/30* 31.4/37.7 43.6/51.5 45/60

– – 5.1 15

5 6.3 13 15

3 4.1 6/7.5 7.5/9.4 14.5/16.9 15/20

10*/12* 12.6/15.1 20.9/24 25/25

15*/20* 18.8/25.1 28.6/36.5 30/40

25*/30* 31.4/37.7 44.4/52.3 45/60

POWERSUPPLY(V-Ph-Hz)

VOLTAGERANGE

BLOWERMOTOR ELECTRIC HEATER

MCA MOCP

MODEL No.: BY10

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(4 WIRE)

LEGEND

FLA – Full Load Amps

HP – Horse Power

MCA – Minimum Circuit Amps

MOCP – Maximum Over Current Protection

* Combination of 2 heater modules

MIN. MAX. HP FLA kW FLA

– – 17.3 30

5 12.6 33 40

208/230-3-60 187 253

5 13.8 6/7.5 15.1/18.8 36.1/40.8 45/45

10*/12* 25.1/30.1 48.6/54.9 50/60

15*/20* 37.7/50.2 64.4/80 70/90

25*/30* 62.8/75.3 95.8/111.4 100/125

– – 24.4 40

5 12.6 40.1 50

7.5 19.5 6/7.5 15.1/18.8 43.3/47.9 50/60

10*/12* 25.1/30.1 55.8/62 60/70

15*/20* 37.7/50.2 71.5/87.1 80/90

25*/30* 62.8/75.3 102.9/118.5 110/125

– – 11.3 20

5 7.6 20.8 25

380-3-60 342 418

5 9 6/7.5 9.1/11.4 22.6/25.5 25/30

10*/12* 15.2/18.2 30.3/34 35/35

15*/20* 22.8/30.4 39.8/49.3 45/50

25*/30* 38/45.6 58.8/68.3 60/70

– – 15.6 25

5 7.6 25.1 35

7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35

10*/12* 15.2/18.2 34.6/38.4 40/45

15*/20* 22.8/30.4 44.1/53.6 50/60

25*/30* 38/45.6 63.1/72.6 70/80

– – 8.6 15

5 6.3 16.5 20

460-3-60 414 506

5 6.9 6/7.5 7.5/9.4 18/20.4 20/25

10*/12* 12.6/15.1 24.4/27.5 30/30

15*/20* 18.8/25.1 32.1/40 35/45

25*/30* 31.4/37.7 47.9/55.8 50/60

– – 12.2 20

5 6.3 20.1 25

7.5 9.75 6/7.5 7.5/9.4 21.6/23.9 25/30

10*/12* 12.6/15.1 27.9/31.1 30/35

15*/20* 18.8/25.1 35.7/43.6 40/45

25*/30* 31.4/37.7 51.4/59.3 60/70

POWERSUPPLY(V-Ph-Hz)

VOLTAGERANGE

BLOWERMOTOR ELECTRIC HEATER

MCA MOCP

MODEL No.: BY14

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(4 WIRE)

19

Page 22: BY-CX series

ELECTRICAL DATA

LEGEND

FLA – Full Load Amps

HP – Horse Power

MCA – Minimum Circuit Amps

MOCP – Maximum Over Current Protection

* Combination of 2 heater modules

MIN. MAX. HP FLA kW FLA

– – 25.5 45

5 12.6 41.2 50

208/230-3-60 187 253

7.5 20.4 6/7.5 15.1/18.8 44.3/49 60/60

10*/12* 25.1/30.1 56.9/63.2 70/70

15*/20* 37.7/50.2 72.6/88.3 80/90

25*/30* 62.8/75.3 103.9/119.6 110/125

35*/40* 87.9/100.4 135.3/151 150/175

– – 32.6 50

5 12.6 48.3 70

10 26.1 6/7.5 15.1/18.8 51.5/56.2 70/70

10*/12* 25.1/30.1 64/70.3 80/80

15*/20* 37.7/50.2 79.7/95.4 90/100

25*/30* 62.8/75.3 111.1/126.8 125/150

35*/40* 87.9/100.4 142.4/158.1 150/175

– – 15.6 25

5 7.6 25.1 35

380-3-60 342 418

7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35

10*/12* 15.2/18.2 34.6/38.4 40/45

15*/20* 22.8/30.4 44.1/53.6 50/60

25*/30* 38/45.6 63.1/72.6 70/80

35*/40* 53.2/60.8 82.1/91.6 90/100

– – 20 35

5 7.6 29.5 40

10 16 6/7.5 9.1/11.4 31.4/34.2 45/45

10*/12* 15.2/18.2 39/42.8 50/50

15*/20* 22.8/30.4 48.5/58 50/60

25*/30* 38/45.6 67.5/77 70/80

35*/40* 53.2/60.8 86.5/96 90/100

– – 12.8 20

5 6.3 20.6 25

460-3-60 414 506

7.5 10.2 6/7.5 7.5/9.4 22.2/24.5 30/30

10*/12* 12.6/15.1 28.4/31.6 35/35

15*/20* 18.8/25.1 36.3/44.1 40/45

25*/30* 31.4/37.7 52/59.8 60/60

35*/40* 43.9/50.2 67.7/75.5 70/80

– – 16.3 25

5 6.3 24.1 35

10 13 6/7.5 7.5/9.4 25.7/28 35/35

10*/12* 12.6/15.1 31.9/35.1 40/40

15*/20* 18.8/25.1 39.8/47.6 45/50

25*/30* 31.4/37.7 55.5/63.3 60/70

35*/40* 43.9/50.2 71.2/79 80/80

POWERSUPPLY(V-Ph-Hz)

VOLTAGERANGE

BLOWERMOTOR ELECTRIC HEATER

MCA MOCP

MODEL No.: BY25

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(4 WIRE)

MIN. MAX. HP FLA kW FLA

– – 17.3 30

5 12.6 33 40

208/230-3-60 187 253

5 13.8 6/7.5 15.1/18.8 36.1/40.8 45/45

10*/12* 25.1/30.1 48.6/54.9 50/60

15*/20* 37.7/50.2 64.4/80 70/90

25*/30* 62.8/75.3 95.8/111.4 100/125

35*/40* 87.9/100.4 127.1/142.8 150/150

– – 24.4 40

5 12.6 40.1 50

7.5 19.5 6/7.5 15.1/18.8 43.3/47.9 50/60

10*/12* 25.1/30.1 55.8/62 60/70

15*/20* 37.7/50.2 71.5/87.1 80/90

25*/30* 62.8/75.3 102.9/118.5 110/125

35*/40* 87.9/100.4 134.3/149.9 150/175

– – 11.3 20

5 7.6 20.8 25

380-3-60 342 418

5 9 6/7.5 9.1/11.4 22.6/25.5 25/30

10*/12* 15.2/18.2 30.3/34 35/35

15*/20* 22.8/30.4 39.8/49.3 45/50

25*/30* 38/45.6 58.8/68.3 60/70

35*/40* 53.2/60.8 77.8/87.3 80/90

– – 15.6 25

5 7.6 25.1 35

7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35

10*/12* 15.2/18.2 34.6/38.4 40/45

15*/20* 22.8/30.4 44.1/53.6 50/60

25*/30* 38/45.6 63.1/72.6 70/80

35*/40* 53.2/60.8 82.1/91.6 90/100

– – 8.6 15

5 6.3 16.5 20

460-3-60 414 506

5 6.9 6/7.5 7.5/9.4 18/20.4 20/25

10*/12* 12.6/15.1 24.4/27.5 30/30

15*/20* 18.8/25.1 32.1/40 35/45

25*/30* 31.4/37.7 47.9/55.8 50/60

35*/40* 43.9/50.2 63.5/71.4 70/80

– – 12.2 20

5 6.3 20.1 25

7.5 9.75 6/7.5 7.5/9.4 21.6/23.9 25/30

10*/12* 12.6/15.1 27.9/31.1 30/35

15*/20* 18.8/25.1 35.7/43.6 40/45

25*/30* 31.4/37.7 51.4/59.3 60/70

35*/40* 43.9/50.2 67.1/74.9 70/80

POWERSUPPLY(V-Ph-Hz)

VOLTAGERANGE

BLOWERMOTOR ELECTRIC HEATER

MCA MOCP

MODEL No.: BY18

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(4 WIRE)

20

Page 23: BY-CX series

DIMENSIONSBY03 - BY14 (HORIZONTAL DISCHARGE)

A B C D E F G H J K L MBY03 1092(43) 648(25.5) 575(22.64) 483(19.02) 143(5.63) 406(15.98) 45(1.77) 542(21.34) 524(20.63) 297(11.69) 553(21.77) 151(5.94)

BY05 1092(43) 813(32) 600(23.62) 483(19.02) 224(8.82) 406(15.98) 45(1.77) 707(27.83) 550(21.65) 297(11.69) 553(21.77) 183(7.2)

BY07 1360(53.5) 1100(43.31) 600(23.62) 813(32) 182(7.16) 406(15.98) 66(2.6) 995(39.17) 550(21.65) 378(14.88) 721(28.38) 123(4.84)

BY10 1490(58.7) 1400(55.12) 675(26.57) 813(32) 332(13.1) 406(15.98) 42(1.65) 1295(51) 625(24.61) 378(14.88) 721(28.38) 198(7.8)

BY14 1625(64) 1600(63) 705(27.75) 1321(52) 187(7.36) 406(15.98) 55(2.16) 1495(58.86) 655(25.8) 471(18.54) 791(31.14) 153(6.02)

MODELDIMENSIONS

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

21

Page 24: BY-CX series

DIMENSIONSBY03 - BY14 (VERTICAL DISCHARGE)

A B C D E F G H J K L MBY03 1092(43) 648(25.5) 575(22.64) 483(19.02) 134(5.28) 406(15.98) 35(1.38) 543(21.38) 502(19.76) 285(11.22) 553(21.77) 154(6.06)

BY05 1092(43) 813(32) 600(23.62) 483(19.02) 229(9.02) 406(15.98) 32(1.26) 712(28.03) 502(19.76) 300(11.81) 553(21.77) 195(7.68)

BY07 1360(53.5) 1100(43.31) 600(23.62) 813(32) 213(8.4) 406(15.98) 85(3.34) 991(39) 504(19.83) 302(11.87) 697(27.53) 110(4.33)

BY10 1490(58.7) 1400(55.12) 675(26.57) 813(32) 365(14.38) 406(15.98) 35(1.38) 1299(51.15) 607(23.91) 338(13.29) 732(28.81) 123(4.84)

BY14 1625(64) 1600(63) 705(27.75) 1321(52) 224(8.82) 406(15.98) 49(1.92) 1497(58.95) 607(23.91) 370(14.59) 929(36.56) 110(4.33)

MODELDIMENSIONS

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

22

Page 25: BY-CX series

DIMENSIONSBY18 - BY25 (HORIZONTAL DISCHARGE)

A B C D E F G H J K L MBY18 1625(64) 2070(81.5) 705(27.75) 1575(62) 382(15.04) 483(19.02) 35(1.38) 1965(77.36) 655(25.79) 471(18.54) 791(31.14) 153(6.02)

BY25 1825(71.85) 2362(93) 840(33.1) 1575(62) 590(23.23) 483(19.02) 50(1.97) 2257(88.86) 790(31.1) 503(19.8) 913(35.94) 288(11.34)

MODELDIMENSIONS

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

23

Page 26: BY-CX series

DIMENSIONSBY18 - BY25 (VERTICAL DISCHARGE)

A B C D E F G H J K L MBY18 1625(64) 2070(81.5) 705(27.75) 1575(62) 422(16.61) 483(19.02) 46(1.81) 1969(77.52) 596(23.46) 354(13.94) 878(34.57) 110(4.33)

BY25 1825(71.85) 2362(93) 840(33.1) 1575(62) 625(24.61) 483(19.02) 74(2.91) 2217(87.28) 596(23.46) 704(27.72) 878(34.57) 110(4.33)

MODELDIMENSIONS

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

24

Page 27: BY-CX series

DIMENSIONS - HEATER BOX

25

415 (16.3")

205 (

8.1")

490 (19.3")

25.4 (1")

HEATER CONTROLS MTGCOVER

HEATER CONTROLS MTGPLATE

TYP

BY03 - BY0520

5 (8.1

")

412 (16.2")

25.4 (1") TYP

HEATER CONTROLS MTGCOVER

HEATER CONTROLS MTG

HEATER ACCESS COVER

PLATE

BY07 - BY14

ABY07 818 (32.2)

BY10 818 (32.2)

BY14 1326(52.2)

MODELDIMENSIONS

1581 (62.3")

205 (

8.1")

492 (19.4")

25.4 (1") TYP

HEATER CONTROLS MTGCOVER

HEATER CONTROLS MTG

HEATER ACCESS COVER

PLATE

(BOTH SIDES)

BY18 - BY25

NOTES: 1. All dimensions are in mm (dimensions in brackets are in inches).2. Heater box is an optional feature.

Page 28: BY-CX series

DIMENSIONSMATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CX030 - CX060

26

MODEL NUMBER A B C D E F G H

CX030 - CX036 711 610 708 596 440 175 86 57

CX042 - CX060 889 813 806 695 538 216 99 72

NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2.Allow 32" (812mm) clearance to service end of the unit,

12" (305mm) on remaining sides and 24" (610mm) be-tween units for proper airflow.

Page 29: BY-CX series

DIMENSIONSMATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CX075 - CX120

27

NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 32" (812 mm) clearance to service end of the unit, 24" (610 mm) on remaining sides and 48" (1219 mm) between units for

proper airflow.

Page 30: BY-CX series

DIMENSIONSMATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CX150 - CX220

28

NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 32" (812 mm) clearance to service end of the unit, 48" (1219 mm) on remaining sides for proper airflow.

Page 31: BY-CX series

DIMENSIONSMATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CX240 & CX300

NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 48" (1219 mm) clearance on all sides for proper airflow.

29

Page 32: BY-CX series

943[37.13"]

943[37.13"]

2032[80.0"]

73 [2.88"]

2197[86.50"]

2121[83.50"]

1550

[61.

0"]

203

[8.0

"]DIMENSIONS

MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CX360

NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 48" (1219 mm) clearance on all sides for proper airflow.

30

Page 33: BY-CX series

LUG

HVTB OR BMC

BM

L2

L3

L1

68 69

BMC

70

BM

CONNECTION APPLICABLE FOR 1PH BM

FACTORY SETTINGS OF DIP SWITCHES

ONDIP SWITCH #

OFF

S1 S2 S3 S4

S4

ON= TEST MODE ENABLE

ON= COMPRESSOR 1 LEAD

OFF=TEST MODE DISABLE

LOAD BALANCE S2

S1

(Comp1&2 Auto Lead Lag)OFF=

S3 OFF= WITHOUT PUMP DOWN ON= WITH PUMP DOWN OPTION

on-board programming function (always set to on)

LED INDICATORSGreen power on/off indicatorRed system lock-out due to system fault

Yellowsystem 1 fault diagnostic

blinking slow - LPS1 ckt fault blinking fast - HPS1 ckt fault

Orangesystem 2 fault diagnostic

blinking slow - LPS2 ckt fault blinking fast - HPS2 ckt fault

note:Set dip switch # 3 according to unit's option(pump down or no pump down)

ECB DIP SWITCH SETTINGS & LED INDICATORS DIP SWITCH FUCTIONS

SEC

PRI

ON

DIP SWITCH

J_PROG

POWER(GRN)

DIP

LOCK2(RED)

SYSTEM2(ORG)

FUSE

SYSTEM1(YEL)

P3_##

LOCK1(RED) ECB

BMC

TRAN

S

TO CONDENSING UNIT ATB

TO CONDENSING UNIT ATB

TO ATBSEE CONDENSING

UNIT DIAGRAM

30 29

230V

STG1 HEATINGSTG1 COOLINGBM CONTROL

24Vac

W2W1Y1

CG

R

THERMOSTAT / DDC CONTROLLER(by others)

W1W2 Y1 G RC

28HC1

HC2

CNC

NO

AFS

STG2 HEATING

TYPICAL SCHEMATIC WIRING DIAGRAM(Matching with single compressor units)

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.

31

REFER TO UNITNAMEPLATE FORPOWER SUPPLY

Page 34: BY-CX series

T1G

HEATER OPTION-3HEATER OPTION-1

HC2

HC1

T1G

71A

T1F

HEATER1

T3F

29

T2F

73A

72A

F11

F12

HC1

F13

71A

HEATER OPTION-2(SEE TABLE)

HC2

HEATER2

T3G

T2G

28

73B

72B

71B

F14

F15

F16

30

HEATER3

T1H

T2H

T3H

F17

74A

76A

75A

F18

F19

HC4

76B

HEATER4

28

T3I

T1I

HC3

T2I

74B

HC3

75B

F20

F21

29

HC4

F22

HEATER3

(SEE TABLE)F1

9

HC1

28

HEATER1

HC1

T3F

T1F

T2F

73A

72A

F11

F12

F13

T1H

30 HC3

T2H

T3H

74A

76A

75A

F18

F17

HC129

72A

HEATER1

T2F

28

T1F

HC3

71A

F11

T3F

HC1

73A

F12

F13

L1 L2 L3 L3

TO HVTB

L2L1 L3 L1 L2 L2L1 L3 L3

TO HVTB

L1 L2 L3 L2L1TO HVTBL1 L3L2

(SEE TABLE)

HC2

HC2

28 30

HEATER2

T3G

T2G

HEATER3

T3H

T2H

T1H

76A

74A

75A

F17

F18

F19

28

T2I

HEATER4

T1I

T3I

OPTIONS

TO HVTBL2L1 L3

1. ANTI ICE OPTION

NOTES: HTR-35 & 40KW IS APPLICABLE FOR

5 K.W

20 K.W

25 K.W

35 K.W

30 K.W

10 K.W

15 K.W

12 K.W

7.5 K.W

40 K.W

6 K.W

HTR

GECB

**

H2

2 1 6 K.W

7.5 K.W

12.5 K.W

2*10 K.W

7.5+10 K.W2*

BY 18 MODEL ONLY.USE OPTION 1 FOR 230V-3PH UNIT MODELUSE OPTION 3 FOR 380V/460V-3PH UNIT MODEL

* 2 2*10 K.W

2

2

2

2

2

2

2

2

2

2

2

2

2

1

7.5 K.W

7.5+10 K.W

12.5 K.W

15 K.W

10 K.W

15 K.W

10 K.W

5 K.W

6 K.W

7.5 K.W

5 K.W

6 K.W

OHT

FL

FL

HEATER DATA TABLEHEATER DATA TABLE

2OPT# STG

1

OLRG1 19

I STG5 K.W

II STG

LVTBG

H4 FLFLFL

OLR

BMC

68

BM

7069T1

E

T3E

T2E

H3

(#2)

OHT

OHT

FL

(#1)OHT

HEATER TYPES

APPLICABLE FOR BM WITH EXTERNAL OLR

TO HVTB

L1 L3L2

H1

OHT

FLOHT

OHT

FLOHT

CONNECTION APPLICABLE FOR ANTI ICE

2) BM RUN &TRIP INDICATION(BM W/O OLR)

BM TRIP/FAIL

AFS

51

48BM RUN

51B

AFS

BMCA-2A

52

49

BMCA-1A51A

BM RUN&TRIP (BM WITH OLR)

BM RUN

BMC-1A

51

48

OLR-2

BM TRIP

52

49

TYPICAL SCHEMATIC WIRING DIAGRAM(Matching with single compressor units)

LEGEND

AI ANTI ICE THERMOSTATAFS AIRFLOW SWITCHATB AUXILIARY TERMINAL BLOCKAR AUXILIARY RELAYBM BLOWER MOTORBMC BLOWER MOTOR CONTACTORCAP CAPACITORECB ELECTRONIC CONTROL BOARDFL FUSE LINKHC HEATER CONTACTORHVTB HIGH VOLTAGE TERMINAL BLOCKHTR HEATERL1 LINE 1L2 LINE 2L3 LINE 3LVTB LOW VOLTAGE TERMINAL BLOCKLUG LUG GROUNDMOHT MANUAL RESET OHTNTB NEUTRAL TERMINAL BLOCKOHT OVERHEAT THERMOSTATOLR OVER LOAD RELAYSM SYSTEMIZERVFC VOLT FREE CONTACT

FIELD WIRINGDISCONNECT TAB - 1/4"FL OR MOHT

_ _ _+

32

NOTES

1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.THERMOSTAT CONTROL VOLTAGE - 24VAC.

2. ANY WIRE REPLACEMENT SHOULD BE OF THE 900COR ITS EQUIVALENT.USE COPPER CONDUCTOR WIRES ONLY.

3. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORT CYCLEPROTECTION FOR COMPRESSOR IS AVAILABLE INZAMIL ELECTRONIC THERMOSTAT.

4. IF HEATERS ARE FACTORY INSTALLED, PLEASEREAD BROKEN LINES AS CONTINUOUS LINES.

5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKERTO BE PROVIDED BY CONSUMER WITH RATING ASRECOMMENDED BY ZAMIL.

6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLTAGEACROSS TERMINAL X1, X2 & 2 IS 230VAC.

7. NTB IS APPLICABLE FOR UNITS WITH 1 PHASEBLOWER MOTOR ONLY.

Page 35: BY-CX series

GECB OLRG1 19 LVTB

G

OLR

BMC

68

BM

7069

APPLICABLE FOR BM WITH EXTERNAL OLR

TO HVTB

L1 L3L2

L1 68

LUG

L3L2 BM

7069

HVTB BMC

APPLICABLE FOR 1PH BM

HEAT

ER1

HEAT

ER2

OUTF

AN1

OUTF

AN2

NEUT

RAL

12v-0-12v

SEC

240v

PRI

LIVE

DIP SWITCH

J_PROG

POWER(GRN)

X2

LOCK2(RED)

SYSTEM2(ORG)

FUSE

SYSTEM1(YEL)

LOCK1(RED)

X1

INFA

N

41A

41B

30 29 14

26BHP2

(LP2)

LP1

LP2

(LP1)

(HP2)

23B22B

23A22A

27B

ECB

(HP1)HP1

COMP

2

P2 P1

COMP

1

27A

26A

28

3B4B 4A 3A

HC1

BMC

HC2

TRAN

S

9

11

15

16

13

14

12

10

CNC

NO

TO CONDENSING UNIT ATB

TO CONDENSING UNIT ATB

TO ATBSEE CONDENSING

UNIT DIAGRAM

TO CU ATB

30 29

13 12

THERMOSTAT / DDC CONTROLLER

FACTORY SETTINGS OF DIP SWITCHES

ONDIP SWITCH #

OFF

S1 S2 S3 S4

S4

ON= TEST MODE ENABLE

ON= COMPRESSOR 1 LEAD

OFF=TEST MODE DISABLE

LOAD BALANCE S2

S1

(Comp1&2 Auto Lead Lag)OFF=

S3 OFF= WITHOUT PUMP DOWN ON= WITH PUMP DOWN OPTION

on-board programming function (always set to on)

LED INDICATORSGreen power on/off indicatorRed system lock-out due to system fault

Yellowsystem 1 fault diagnostic

blinking slow - LPS1 ckt fault blinking fast - HPS1 ckt fault

Orangesystem 2 fault diagnostic

blinking slow - LPS2 ckt fault blinking fast - HPS2 ckt fault

note:Set dip switch # 3 according to unit's option(pump down or no pump down)

ECB DIP SWITCH SETTINGS & LED INDICATORS DIP SWITCH FUCTIONS

TYPICAL SCHEMATIC WIRING DIAGRAM(Matching with dual compressor units)

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.

33

REFER TO UNITNAMEPLATE FORPOWER SUPPLY

Page 36: BY-CX series

T1G

HEATER OPTION-3HEATER OPTION-1

HC2

HC1

T1G

71A

T1F

HEATER1

T3F

29

T2F

73A

72A

F11

F12

HC1

F13

71A

HEATER OPTION-2(SEE TABLE)

HC2

HEATER2

T3G

T2G

28

73B

72B

71B

F14

F15

F16

30

HEATER3

T1H

T2H

T3H

F17

74A

76A

75A

F18

F19

HC4

76B

HEATER4

28

T3I

T1I

HC3

T2I

74B

HC3

75B

F20

F21

29

HC4

F22

HEATER3

(SEE TABLE)F1

9

HC1

28

HEATER1

HC1

T3F

T1F

T2F

73A

72A

F11

F12

F13

T1H

30 HC3

T2H

T3H

74A

76A

75A

F18

F17

HC129

72A

HEATER1

T2F

28

T1F

HC3

71A

F11

T3F

HC1

73A

F12

F13

L1 L2 L3 L3

TO HVTB

L2L1 L3 L1 L2 L2L1 L3 L3

TO HVTB

L1 L2 L3 L2L1TO HVTBL1 L3L2

(SEE TABLE)

HC2

HC2

28 30

HEATER2

T3G

T2G

HEATER3

T3H

T2H

T1H

76A

74A

75A

F17

F18

F19

28

T2I

HEATER4

T1I

T3I

OPTIONS

TO HVTBL2L1 L3

1. ANTI ICE OPTION

NOTES: HTR-35 & 40KW IS APPLICABLE FOR

5 K.W

20 K.W

25 K.W

35 K.W

30 K.W

10 K.W

15 K.W

12 K.W

7.5 K.W

40 K.W

6 K.W

HTR

**

H2

2 1 6 K.W

7.5 K.W

12.5 K.W

2*10 K.W

7.5+10 K.W2*

BY 18 & 25 MODELS ONLY.USE OPTION 1 FOR 230V-3PH UNIT MODELUSE OPTION 3 FOR 380V/460V-3PH UNIT MODEL

* 2 2*10 K.W

2

2

2

2

2

2

2

2

2

2

2

2

2

1

7.5 K.W

7.5+10 K.W

12.5 K.W

15 K.W

10 K.W

15 K.W

10 K.W

5 K.W

6 K.W

7.5 K.W

5 K.W

6 K.W

OHT

FL

FL

HEATER DATA TABLEHEATER DATA TABLE

2OPT# STG

1I STG5 K.W

II STG

H4 FLFLFL

H3

(#2)

OHT

OHT

FL

(#1)OHT

HEATER TYPES

H1

OHT

FLOHT

OHT

FLOHT

ROUTE FPT WIRES TO COND. UNIT.[ TO COND. UNIT ]

2) VFC OPTION FOR BM RUN &TRIP INDICATION

BM RUN TRIP CONNECTION FOR BM WITH OLR

BM TRIP/FAIL

AFS

51

48BM RUN

51B

AFS

BMCA-2A

52

49

BMCA-1A51A

BM RUN

BMC-1A

51

48

OLR-2

BM TRIP

52

49

TYPICAL SCHEMATIC WIRING DIAGRAM(Matching with dual compressor units)

LEGEND

AI ANTI ICE THERMOSTATAFS AIRFLOW SWITCHATB AUXILIARY TERMINAL BLOCKAR AUXILIARY RELAYBM BLOWER MOTORBMC BLOWER MOTOR CONTACTORECB ELECTRONIC CONTROL BOARDFL FUSE LINKHC HEATER CONTACTORHVTB HIGH VOLTAGE TERMINAL BLOCKHTR HEATERL1 LINE 1L2 LINE 2L3 LINE 3LVTB LOW VOLTAGE TERMINAL BLOCKLUG LUG GROUNDLLS LEAD LAG SWITCHMOHT MANUAL RESET OHTNTB NEUTRAL TERMINAL BLOCKOHT OVERHEAT THERMOSTATOLR OVER LOAD RELAYSM SYSTEMIZERVFC VOLT FREE CONTACT

FIELD WIRINGDISCONNECT TAB - 1/4"FL OR MOHT

_ _ _+

34

NOTES

1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.THERMOSTAT CONTROL VOLTAGE - 24VAC.

2. ANY WIRE REPLACEMENT SHOULD BE OF THE 900COR ITS EQUIVALENT.USE COPPER CONDUCTOR WIRES ONLY.

3. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORT CYCLEPROTECTION FOR COMPRESSOR IS AVAILABLE INZAMIL ELECTRONIC THERMOSTAT.

4. IF HEATERS ARE FACTORY INSTALLED, PLEASEREAD BROKEN LINES AS CONTINUOUS LINES.

5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKERTO BE PROVIDED BY CONSUMER WITH RATING ASRECOMMENDED BY ZAMIL.

6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLTAGEACROSS TERMINAL X1, X2 & 2 IS 230VAC.

7. NTB IS APPLICABLE FOR UNITS WITH 1 PHASEBLOWER MOTOR ONLY.

Page 37: BY-CX series

Scroll compressors are designed to operate in single direction only. Hence, care has to be taken to ensure correct rotationwhen the system is operated. Verification of correct rotation is by observing that the suction pressure drops and dischargepressure rises when compressor run. Reverse rotation results in abnormal sound, as well as, substantially low current drawand by interchanging power supply wire L1 & L3 will correct this problem.The operation of the air conditioning unit is controlled by a 24VAC electronic control board.

GENERALThe thermostat normally displays room temperature and mode of operation. The five buttons on the front of the unit allowcomplete control of the thermostat. The thermostat also allows to select continuous fan operation (useful when using an aircleaner) or have the fan come on with the compressor.

SWITCH FUNCTION- On/Off Key : Switch the system On or Off.- Up Key : To increases the set temperature.- Down Key : To decreases the set temperature.- Mode Key : Changes the mode to Fan, Cool, Heat or Auto.- Fan Key : Changes the Fan Operation to Auto or Continuous.- °C/°F selection : By pressing Mode & UP key together, toggles between °C to °F or vice versa.

USER CONTROLSMode:Select the desired mode of operation by pressing of the mode button:

Fan: In this mode of operation, the compressor will be in inactive state. Display shows room temperature. Fan will be running.

Cool: In this mode of operation, the compressor will be ON after a delay depending on the differential of room tempera-ture & Set temperature.

Heat: In this mode of operation, Fan is ON.

Auto: In auto mode, thermostat provide automatic changeover from heating to cooling mode & vice versa. Thermostatautomatically switches to maintain the desired temperature.

DIP SWITCH OPTIONS AND FUNCTIONSThere are 4 small DIP (Dual in line package) switches on the back of the circuit board which must be configured by theinstaller.

CONTROLS & SEQUENCE OF OPERATION

SWITCH ON OFF

1 N. A. -

2 N. A. -

3 N. A. -

4 INDOOR SENSOR REMOTE SENSOR

DIP SWITCH SELECTION

Note:Keep DIP SWITCH 1, 2 & 3 in OFFposition only.

35

SUPPLY FAN CONTROLSTG1 COOLING

STG1 HEATERSTG2 HEATER

STG2 COOLING

W2

RCG

W1Y2Y1

LVTB

THERMOSTAT

Y2W1Y1

G

24V(R)24V(C)

W2

REMOTESENSOR

FAULT 1FAULT 2

SENSOR

OPTIONAL CONNECTION :IF REMOTE TEMPERATURE SENSINGFUNCTION IS REQUIRED.

NOTE:

(ZAC P/N 80065261)

ATBCOMPRESSOR FAULT SIGNAL (VOLT-FREE CONTACT)

COMP 1

COMP 2(COMMON)

24V ac

( OPTIONAL CONNECTION )

HOOK-UP WIRING DIAGRAM

ACCU CONTROL PANEL

LEGEND:ATBLVTB

AUXILIARY TERMINAL BLOCKLOW VOLTAGE TERMINAL BLOCK

( THERMOSTAT CONTROLLER TO AIR HANDLING UNIT )

AHU CONTROL PANEL

Page 38: BY-CX series

INSTALLATION INSTRUCTIONSA. GENERALBlower units are shipped completely wired. Only external power, interconnecting control wiring between outdoor andindoor units and refrigerant pipe connections are needed to complete the installation. For detailed instructions/informa-tions, please refer to corresponding IOM manual.

B. UNIT LOCATION & ACCESS SPACEThe placement of the unit in relationship to the building is very important. A minimum of 36 inches clearance must bekept on the service access side and return air side.When making tubing connections, be sure to provide clearance for electrical connections.

C. TUBING INSTALLATIONDo not remove plugs from the compression fittings until tubing has been run and is ready for connection.a. Make sure the tubing is round, without dent or burrs.b. Cut tubing to the length required with a tube cutter carefully. Do not use a hacksaw.c. Remove burr from inside and outside using file or deburring tool.NOTE: Always use a gear type tube bender when making bends in suction line.When installing tubing through walls or along side of any structural members, be sure the tubing is isolated from thesemembers or walls to avoid any transmission of vibration that may occur, while unit is running.

ELECTRICALSTEP 1: INSTALLATIONA) Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements.Caution: Operation of the unit on improper power supply will result in damage to the unit.NOTE: Use copper wires of proper rating for all field wiring.WarningBefore servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than one discon-nect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death.

B) Ground & power wiresConnect power wires to terminal block per wiring diagram.Connect ground wire to the ground lug inside the control box.

C) Control wiring between outdoor & indoor unitUse 16 gauge color-coded wire between the indoor and outdoor units (control wiring).

STEP 2: START-UPRefer to outdoor unit installation instructions for system start-up instructions and refrigerant charging method details.

STEP 3: SEQUENCE OF OPERATIONWith power supplied to indoor and outdoor units, the unit starts responding to the thermostat mode requirement.

Cooling mode: When thermostat calls for cooling, the blower motor in the indoor unit is switched on. The compressorcontactor is energized to start the compressor and condenser fan.As the conditioned space approaches the thermostat cooling set point, the unit cycles off.

Heating mode: When thermostat calls for heating, the blower motor in the indoor unit is switched on. The contactor forelectric heater is switched on to energize the heaters. If the room temperature is not satisfied and there are two heatersinstalled, the second heater also will be energized.Once, the conditioned space approaches the desired temperature set point, the heating stages cycles off.

Fan mode: In this mode the indoor unit blower motor is switched on alone.

36

Page 39: BY-CX series