building electrical systems design & drafting

103
BUILDING ELECTRICAL SYSTEMS DESIGN & DRAFTING Engineer : AMJED OSMAN ELSAYED

Upload: eisa-ibrahim-eisa

Post on 20-Oct-2015

1.125 views

Category:

Documents


14 download

DESCRIPTION

Electrical Design manual for commercial & residential projects: design of the electrical installation in building used to be simple and straight forward . Such installations generally included electrical service from an electricity board company, power distribution within the building for sockets (receptacles ), air conditioning and other electrical loads ,lighting and few specialty system such as fire alarm and telephone.

TRANSCRIPT

Page 1: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

BUILDING ELECTRICAL SYSTEMS DESIGN & DRAFTING

Engineer : AMJED OSMAN ELSAYED

Page 2: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

INTRODUCTION

design of the electrical installation in building used to be

simple and straight forward . Such installations generally

included electrical service from an electricity board company

, power distribution within the building for sockets

(receptacles ), air conditioniong and other electrical loads ,

lighting and few specialty system such as fire alram and

telephone .

Page 3: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Generation , transmission and distributions of electrical energy

Page 4: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Transmission of Electricity From power station to consumer

Yard transformer

Regional Substation

Zone Substation

DistributionSubstation

11kV, 17kV,

22kV, 23kV

330kV,

500kV

60kV,

132kV

11kV,

33kV

Generation Primary Transmission

Secondary Transmission

High Voltage Distribution

230/400V

Power Station

Page 5: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Distribution of Power

5 5

High Voltage and low voltage distribution system

1 2 3 4

Delta/Star transformer

Three phase four wire distribution low voltage 230/400V

Consumer 1 and 2: 230V two wire

Consumer 3 : 230/400V three wire

Consumer 4 : 230/400V four wire

Three phase, high voltage distribution

Bulk Supply Consumer

Three Phase

Star System

Line 1(A) Line 2(B)

Line 3(C)

Neutral

Page 6: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Types of phase:- There are 3 phase types: 1. Red phase or phase (A) 2. Yellow phase or phase (B) 3. Blue phase or phase (C)

Phase system: There are 3 types of phase system : 1. One ø system or 1 phase system 2. Tow ø system or 2 phase system 3.Three ø system or 3 phase system

Page 7: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

ELECTRICAL CODES AND STANDARDS: Electrical codes :- the principles used in electrical design and installation are know as electrical codes.

Examples : UK- UAE- QATAR- OMAN- SUDAN:- UK, UAE, Qatar ,Oman,Sudan follow B.S (British standards) know IEC(International Electrotechnical Commission)

USA-KSA:- USA,KSA follow NEC codes (National electrical codes) which is chapter no 70 in NFPA book (National fire protection association ) European countries: European countries follow IEC standards (international electrical technical commission ).

Page 8: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Voltages and codes around the world U.K → U.K follow B.S codes (also know as IEE regulation )

Normal voltages 230/400V 50Hz.

USA→ USA follow NEC (NFPA 70) Normal voltage 110/220 60Hz 220/380 60Hz KSA→ KSA follow NEC (NFPA 70) Before 2010 KSA was having 2 voltages 127/220 V 60Hz 220/380 V 60 Hz In 2010 the ministry of electricity decided that new project after 2010 will have only one voltage through out KSA 220/380 60Hz

Page 9: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Voltages and codes around the world UAE → UAE follow B.S Normal voltage 230/400v 50 Hz SUDAN → Sudan follow B.S Normal voltage 240/415v 50 Hz Qatar → Qatar follow B.S Normal voltage 240/415v 50Hz

Page 10: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

SWITCH used for on or off purpose of small equipment like light – ceiling fan

–exhaust fan - socket – water heaters – washing machine – cooking range- window and split A/C – small water pumps.etc

Rating of switch : the maximum current which can flow through switch safety without any damages for switch is know as rating of switch

Page 11: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Standard Rating of Switch

5A 10 A 15 A 20 A 25 A 30A or 32 A Note In Gulf we used 10 A switch for light only In Gulf we used 20 A switch for W/H – W/M etc

Page 12: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Types of Switch One way switch

Two way switch

Intermediate switch

Page 13: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

back box In Gulf they are 2 standard back box size 1. 3×3 2. 6×3

Gang : represents no. of switch in back box

1 Gang 2 gang 3 gang

Page 14: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Gang four gang five gang six gang 4 G 5G 6G

Page 15: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Sockets Types of S/O in BS (Sudan , Oman, Qatar, UAE ) 3pin → 13A general s/o → 15A s/o for A/C → 45A flex outlet for W/H , W/M , C/R

K.S.A : S/Os in NEC standard are know as receptacles Receptacles → 15A/20A , 220 V Receptacles →15A or 20A , 127 V

Page 16: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Sockets Other classification 1. Single S/O outlet : The back box has only one s/o inside .the back box size is used 3×3.

2.Double or twin S/O outlet : The back box has two s/o , the back box size is used 6×3

3.Shaver outlet : (110_ 220 v)

Page 17: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

WIRES AND CABLES:- Wire : conductor + insulation (small size) Cables : conductor + insulation + sheath (large size ) Bare conductor : only conductor (no insulation). Ex, over

head lines in Sudan Units of wires and cables : mm² → Sudan and B.S countries (UAE, K.SA,Qatar) OR AWG →(American Wire Gnage ) mm² : it is cross sectional area of conductor without

insulation

Page 18: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Equivalent of mm² to AWG

MM² AWG REMARK 1.0 mm² 18 AWG AWG For KSA 1.5 mm² 16 AWG AWG For KSA 2.5 mm² 14 AWG AWG For KSA 4 mm² 12 AWG AWG For KSA 6 mm² 10 AWG AWG For KSA 10 mm² 8 AWG AWG For KSA 16 mm² 6 AWG AWG For KSA 25 mm² 4 AWG AWG For KSA 35 mm² 2 AWG AWG For KSA 50 mm² 1 1/0 AWG AWG For KSA 70 mm² 2/0 AWG AWG For KSA 95 mm² 3/0 AWG AWG For KSA 120 mm² 4/0 AWG AWG For KSA 150 mm² 250 kc MIL AWG For KSA 185 mm² 350 kc MIL AWG For KSA 240 mm² 400 kc MIL AWG For KSA 300 mm² 500 kc MIL AWG For KSA

Page 19: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

CORE OF CABLES Core (c) represents the numbers of conductors in the cable , there are two types of the cable based on the cores of cables

1. Single core cable (1c)

2. Multi core cable (a) 2 core cable (2c)

Page 20: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

CORE OF CABLES

(b) Three core cable (3c) (c)Four core cable (4c) (d)3 ½ core or 3.5 core

Page 21: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Run of cable:- Run of cable represents the no .of single core or multi core

Always the earth is separate run and 1c only . no multi core for earth wire

We prefer multi core cables above 6mm², avoid single cables above 6mm²

1.5 mm² → single core (1c) 2.5 mm² → single core (1c) 4 mm² → single core (1c) 6 mm² → single core (1c) 10 mm² → (2c ,3c , 4c, 3.5c) 16 mm² → (2c ,3c , 4c, 3.5c) 25 mm² → (2c ,3c , 4c, 3.5c) : : 300 mm² → (2c,3c , 4c, 3.5c)

Page 22: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Earth wire sizing Earth wire is dependent on phase size Wire or cable size for phase and N Earth wire or cable size

1.0mm² 1.0 mm² 1.5 mm² 1.5 mm² 2.5 mm² 2.5 mm² 4 mm² 4 mm² 6 mm² 6 mm² 10 mm² 10 mm² 16 mm² 16 mm² 25 mm² 16 mm² 35 mm² 16 mm² 50 mm² 25 mm² 70 mm² 35 mm² 95 mm² 50 mm² 120 mm² 70 mm² 150 mm² 95 mm² 185 mm² 95 mm² 240 mm² 120 mm² 300 mm² 150 mm²

Page 23: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Conductor materials :

1. Copper (cu)

2. Aluminum (al)

Page 24: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Insulation materials

1. PVC :(Poly-Viny Chloride) PVC insulated wires are used for smaller loads like light , fans , s/o , w/m , w/h , c/r They can with stand up to 60 C,

2. LSOH : Low Smoke zero Holagen LSOH insulated wires are used for smaller loads like lights , fans , s/o , w/h , w/m . c/r .

Page 25: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Insulation materials XLPE : cross linked polyethylene XLPE insulated cables are used as main feeder cable (service wire) for DB OR SMDB OR MCC OR T/F etc. and for heavy mechanical load like chiller – AHU – Boilers XLPE cables can with stand up to 90º c

FR : Fire Retardant or MICC (Mincal Insulated Cable Conductor )

FR cable are professed for emergency load like lights fire fighting pumps , emergency lights ,fire alarms cables

Page 26: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Types power cable : 1.Un armoured cable

2. Armoured cable a) SWA (Steel Wire Armour ) b) AWA(Aluminum Wire Armour) c) SSA (Steel Strip Armour ) d) ASA (Aluminum Strip Armour)

Page 27: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Voltage classification :- 1. H.V → High Voltage (above 1000 v) 2. M.V → Medium Voltage (250 to 1000v) 3. L.V → Low Voltage (30 to 250 v) 4. ELV → Extra Low Voltage (voltage less

than 30 ac or 54 v dc) Grade of cable : means the with stand voltage whether the

cable is for LV or MV or HV.

Page 28: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Color codes of cable

PHASE In sudan or gulf countries

New color code in europe

Phase (A) or (1) Red Brown

Phase (B) or (2) Yellow Black

Phase (C) or (3) Blue Grey

Neutral Black Blue

Earth Green or Y/G Y/G

Page 29: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Final representation of cables : 1×4c×10mm² ,XLPE/SWA/PVC.Cu,0.6/1kv + 1×1c×10mm², pvc /pvc ,cu Y/G 1 → run 4c→ core 10mm²→size XLPE → insulation SWA→ armour PVC→ sheath Cu → conductor material 0.6/1kv → M.V /L.V grade Earth 1 → run 1c→ core 10mm²→ size PVC → insulation PVC→ sheath Cu → conductor material Y/G → Earth

Page 30: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Electrical faults

Types of electrical faults : Over load Short circuit Earth –fault or shock Over voltage Under voltage

Page 31: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

1. Over load Over load mean current more than rated current of equipment Ex : 10 A rated switch 2A→ safe 6A→ safe 10A→ safe 11A→ un safe (over load current) When over load current passes then the s/w gets

damage.

Page 32: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

2. Short circuit When any phase of neutral or any two phase meet

each other then infinite current flows through them.

Usually thousands of current in 1 ms (KA of current

in 1ms ), this increase the temperature is know as

short- circuit condition

Page 33: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

3.Earth – fault or shock When any phase meet earth wire or any conducting materials eg

(metals – human body – water – etc. ) some a mount of current passes in to ground through the earth wire or any conducting material

This current passing to earth from phase wire is know as earth – leakage current and the fault is know as earth – fault .

Good conductor Bad conductor

Silver (best) wood

Cu and AL Rubber

All metals expect few semi- conductor

Plastic – paper – glass

Human body porcelain

Water Air

Page 34: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Summary P + N → Short circuit P – P → Short circuit P – E or human body → earth fault –

shock N – E or human body → No effect E – human body → No effect

Page 35: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Productive devices

The devices which protected from electrical faults are knows as protective devices

Types of protective devices 1. Fuse → protective from over load only 2. Circuit breaker → protects from over load and s.c faults 3. RCB or ELCB or GFCI→ protects from earth faults or

shock 4. RCBO or RCCB → protects from over load , s.c and

earth faults 5. UVR (Under Voltage Relay)→ protects from under

voltage

Page 36: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Circuit Breaker : The CB is protective devices which can be operated manually and automatically it trips in case of over load and short- circuit condition Standard C.B Rating 5 A to 40 A MCB (Miniature circuit breaker ) 50 A to 600 A MCCB (Modulate Case circuit breaker ) 800 A to 3500 A ACB (Air Circuit Breaker)

Page 37: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Standard short – circuit rating of C.B : 1. 6KA 2. 10KA 3. 6KA 4. 25KA 5. 35KA 6. 50KA Example

Page 38: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

TYPES OF C.B 1.MCB → Miniature Circuit Breaker 2.MCCB→ Modulate Case Circuit Breaker 3.ACB → Air Circuit Breaker other breaker used in H.V (power plants and s/s ) 4.VCB → Vacuum C.B 5. OCB → Oil C.B 6.SF6

Page 39: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Types of MCB

B curve MCB

C curve MCB

D curve MCB

Page 40: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Application of B,C,D curve MCB

1. B curve MCB is preferred for lighting circuit. 2. C curve MCB is preferred for small heavy like W/H – W/M – C/R 3.D curve MCB is preferred for machine like (backing machine ).

Page 41: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

MCCB(Modulate Case circuit breaker ) Rating 50 to 600A

Types of MCCB 1. Adjustable MCCB: here we can set the tripping value normally

2. Fixed or un adjustable MCCB

Page 42: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

ACB : Air Circuit Breaker Rating 800 to 3500A 1.Motorized with drawable ACB :

Here the start and stop push buttons are operated by a motor which is required to be energized and after it is off we can with draw the ACB to avoid are flash

2.Motorized non_ with draw able ACB Here the start and stop push buttons are operated by a motor which is required to be energized and after it is off/on we need to with raw ACB

Page 43: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

RCD or ELCB or GFCI B.S (Sudan and UAE,Qatar) →RCD (Residual Current Devices )

→ELCB (Earth Leakage Circuit Breaker)

NEC (KSA) → GFCI : Ground fault Circuit Breaker

Page 44: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Working principle of RCD

The RCD continuously monitors the current difference between phase and neutral . if the leakage current is equal to sensitivity of RCD then the RCD is trip

Recommended sensitivity of RCD : For lights use 100mA RCD (0.1A) For sockets use 30 Ma RCD (0.03A) For W/H- W/M- C/R use 30 ma (0.03A) For A/C use 100ma RCD (0.1A) For under water lighting use 10ma RCD (0.001A) Note: the RCD is provide with a test buttons to verity that RCD is working propyl

Page 45: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Working principle of RCD

No .of poles : Since neutral is compulsory in RCD we have 1. Two poles RCD

2. Four poles RCD Examples

Page 46: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

RCCB or RCBO : RCCB Residual Current Circuit Breaker

RCBO Residual CB with over current protection (over load & S.C) Note RCCB or RCBO protects from all 3 faults (over load , S.C and

earth fault)Since this technology is now they are very less used

Page 47: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

RCCB or RCBO Ex : (C 40A - 100ma - 10KA) C → type of MCB 40 A→ rating of RCBO 100ma → sensitivity of MCBO 10KA→ short- circuit rating Note In UAE they have both CB and RCD for all lights and W/H.

S/O , A/C In Qatar RCD are minatory for S/O , W/H , W/M only not

require for lights and A/C. In KSA RCD are not used GFCI are minatory only for

equipment inside bath room and kitchen.

Page 48: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Isolator or disconnect switch (D/S): Isolator or D/S is not a protective devices is it doesn’t trip in case of

any fault it is only meant for on and off purpose It can look similar to CB with handle side handle or rotary

handle Important note : In sudan and B.S countries the isolator is used as main breaker knows as (main isolator ) inside the DB or final DB Always install D/S near to every heavy mechanical equipment such as chiller , AHU , Motor and pumps , lights for maintains and repair purpose

Page 49: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

STANDARD ISOLATOR RATING NO .OF POLES FOR ISOLATOR DB:

2P 4P

No.of poles D/S near the heavy mechanical equipment SPN for single phase equipment

TPN for three phase equipment

Page 50: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Wires and cables insulation methods Majorly the wires of cables are said to be installed in two methods Cable in air (2) Cable in ground

No Methods for cable in Air

Methods for cable in ground

1 Free in Air Directly buried or directly laid under ground cable

2 conduit Duct bank or electrical ducts

3 Cable trunking Cable tranch 4 Cable tray 5 Cable ladder

Page 51: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Conduit: (electrical pipe) Material of conduit : PVC

Metallic

GI/GS→ Galvanized Iron/ Galvanized Steel

Page 52: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Conduit: (electrical pipe) Material of conduit : EMT→ Electrical Metallic Tubes

RGS/RGI →Rigid Galvanized Steel/ Rigid Galvanized Iron

Note PVC conduits are used as connected conduit inside the wall , slabs ,

and floor screed. GI/GS or RGI/RGS are used as exposed conduits or the wall , or slab

in India and B.S countries (Qatar , UAE ,Oman) EMT conduits are used as exposed conduits on the wall or slab in

KSA

Page 53: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Standard size of conduits ½ ´´ → 16 mm ¾´´ → 20 mm 1´´ → 25mm 1¼´´→ 32 mm 2´´ → 50 mm 3´´ → 75 mm 4´´ → 100 mm Note ½ ´´ conduits are not recommended ¾´´ (20 mm) 0r 1´´ (25 mm) conduit can be use for wiring

lighting 1´´ (25 mm) or (32mm) conduit can be used for wiring of s/o ,

w/h , w/m , c/r , pumps and low current system like fire alarms wires , CCTV telephone and TV wires.

Page 54: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Conduits accessories: Coupler : coupler used to join 2conduts

Bends : In gulf countries bends are made at site in the same coduit using PVC bending Junction box (JB) or pull box (PB) : There are 2 types of JB 1. Circular JB (used mostly in Sudan and BS) 2. Octagonal JB (used in KSA)

Page 55: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

circular JB is fixed near to every light point , ceiling and exhaust and smoke electors

Types of JB circular JB One way two way through two way angle

two way U three way four way

Page 56: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Junction box octagonal JB

back bax : are used for s/o flex outlet etc

adapter : use for fixing conduit to the back box

Page 57: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Standard mounting heights of wiring accessories All switches → 1250 mm AFFL (After Finish Floor

Level) Light , fan , w/h , w/m . Sockets →450 mm AFFL Tel/sockets →450 mm AFFL Sockets in kitchen → 250 mm above kitchen plat

form s/o for w/h , w/m , A/C , near the equipment

Page 58: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

conduiting laying of conduit is knows as coduiting there are three stages for

conduiting . conduiting in slab

conduiting in wall

conduiting in floor

Page 59: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Cable trunking Cable trunking is used to carry branch of wires (many wires )

Materials' : 1. PVC cable trunking 2. Metallic cable trunking

Page 60: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Standard size of cable trunking 1. 50mm ×50mm (5cm×5cm) 2. 100mm ×100mm (10cm×10cm) 3. 150mm ×150mm (15cm×15cm) 4. 200mm ×200mm (20cm×20cm) 5. 250mm ×250mm (25cm×25cm) 6. 300mm ×300mm (30cm×30cm) 7. 400mm ×400mm (40cm×40cm) 8. 500mm ×500mm (50cm×50cm) Note: other combination are also available ex : 300mm×100mm

Page 61: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Installation methods of cable trunking The cable trunking can be installed is three method as per

requirements On the surface of the wall

Hanging from slab

Under floor trunking

Page 62: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

CABLE TRAY Cable tray is used to carry heavy cable

Types of cable tray: 1. Perforated cable tray : is preferred for carraying power cables 2. Plain cable tray : can be used for low current system like TV , CCTV ,FF

Page 63: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Materials of cable tray: 1. No PVC 2. Metallic (a) Galvanized cable tray (b) Hot dip galvanized cable

Page 64: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Standard cable tray size 1) 50mm ×50mm (5cm×5cm) 2) 150mm ×150mm (15cm×15cm) 3) 200mm ×100mm (20cm×10cm) 4) 250mm ×100mm (25cm×10cm) 5) 300mm ×100mm (30cm×10cm) 6) 400mm ×100mm (40cm×10cm) 7) 500mm ×100mm (50cm×10cm) 8) 600mm×100mm (60cm×10cm) 9) 800mm×100mm (80cm×10cm) 10) 900mm×100mm (90cm×10cm) Note: if more than 900mm cable tray is required then use two cable tray parally

Page 65: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Cable tray installation Cable tray can be installed in three methods : 1. On the surface of wall

2. Hanging from cable

3.Floor mounted (on the floor )

Page 66: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Cable laying methods on cable tray There are three methods of cable laying on cable tray Flat formation – touching Flat formation – spacing Trefoil formation (only for single core cables )

Page 67: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Cable ladder Cable ladder are preferred only for vertical installation only in

electrical shaft or riser

Cable installation in ground : there are three methods of cable tray installation in ground 1.Directly buried or directly laid under ground 2.Duct bank or electrical duct 3.Cable trench

Page 68: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Coordination with mechanical system

1. HAVC (Heating Ventilation and Air Conditioning ) 2. Plumbing

a) water supply b) drainage

3. Fire fighting 4. Conveyors like ,lifts scalolar 5. Swimming pool.

Page 69: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Types of HVAC system 1. Window A/C 2. Split A/C 3.VRV or VRF system

Page 70: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Types of HVAC system 4. Package A/C

5. Central A/C – VAV system 6. Chilled water system

Page 71: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Plumbing system

1. Water supply

2. Central hot water system

3. Drainage system

Page 72: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Plumbing system Fire fighting system

Duty and stand by pumps

Page 73: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Plumbing system

Lift : The installation works of lift etc is done by separate

contractor know as lift contractor The elect.engineer has to provide a D/S inside the lift

room for supply to the lift system Summing pool : are usually done by separate contractor

knows as swimming pool contractor . Sometimes the elec. Engineer has to supply electricity to

under water lights which is done at voltage not greater than 30 v a.c the lights shall be provide with 10ma RCD.

Page 74: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Panel board An enclosure with protection devices such as C.B and

RCD knows as panel board . Ex : DB – SMDB – MCC – MDB (All are panel board) Switch gear : a panel board including instruments is

knows as switch gear. Ex : MDB – MCC

Page 75: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

MCC (motor control center ) MCC is a panel board to which major mechanical motors

or loads are connected. MCC has measuring indicating remote start indicates. Ex : MCC panel has ammeter voltmeter frequency meter

power factor meter , phase indicators motor run off trip indicating lamps auto , manual selector switch CB and motor starters with remote terminal blocks.

Page 76: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Panel board The panel board and switch gear (DB- SMDB – MDB –

MCC ) are manufactured in separate factories knows as switch gear manufacturing company and these panel boards are delivered at site for installation Well – know switch gear companys : 1. ABB 2. Schneider electric 3. Mitsubishi 4. Merlin gerin 5. Siemens 6. L&T

Page 77: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Bus duct system Note : bus duct has a housing with bus bar insulated , bus bar is used

to carry current of very high ratings , ex : above 600A only STANDARD BUS DUCT RATING: 600A 800A 1000A 1230A 1500A 2000A 2500A 3000A 3500A Bus way or bus duct riser : is used for power distribution inside

the high building for each house

Page 78: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

IP PROTECTION

IP →Ingress Protection or International Protection IP is the number assigned to the electrical equipment and motors installed outside the building or in wall areas to protection from water and dust and object

No Protection form object and dust

Protection form water

0 Not protect Not protect 1 Hand protect Vertical water 2 Finger protect 15º 3 Tool protect 60º 4 Wire protect Splashing of water 5 Dust protect Low jets of water 6 Complete protect High jets of water 7 Immession 8 Complete submersible

Page 79: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

TRANSFORMES Types of transformer 1. steps up transformer 2. step down transformer Types base on phase system single phase three phase Types of transformer base on poling oil cooled transformer air cooled transformer

Page 80: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

TRANSFORMES Note: for indoor transformer use air cooled transformer for outdoor transformer use oil cooled transformer in gulf countries the transformer are indoor type

installed in separate room ex substation room or transformer room

oil cooled transformer are not referred inside the building .

air cooled transformer are used inside building unit of transformer is KVA

Page 81: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

TRANSFORMES STANDARD RATING OF TRANSFORMER 1) 50 KVA 2) 60KVA 3) 80KVA 4) 100KVA 5) 150KVA 6) 250KVA 7) 315KVA 8) 500KVA 9) 630KVA 10) 800KVA 11) 1000KVA 12) 1500KVA 13) 2000KVA 14) 2500KVA 15) 3000KVA 16) 3500KVA

Page 82: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

TRANSFORMES Need of transformer Gulf countries Transformer is not require for building whose

total max demand less than 400kva If the total max demand is greater than 400kVA

then we require transformer Max permit transformer size 2500kVA Sometimes is 3000kVA

Page 83: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

TRANSFORMES Steps to calculate the transformer size : 1.Consider Total max demand of MDB = KW 2.Total max demand of MDB in KVA = KW/cosø = KVA 3.Add 10% as future load Total max demand with future load in KVA = kVA ×1.10 4. Transformer size = Total max demand with future load in KVA

Transformer load (90%)

Then select the standard size

Page 84: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

TRANSFORMES Ex : calculate the Transformer size for project inside whose max demand is

100kw Solution : Total max demand of MDB = 100 KW 1.Total max demand of MDB in KVA = KW/cosø = 100/0.8=125KVA 2. Add 10% as future load 3. Total max demand with future load in KVA =125 kVA ×1.10=137.5KVA 4. Transformer size = Total max demand with future load in KVA Transformer load (90%) = 137.5Kva/.90 = 157.7Kva Standard T/F size = 250KVA / oil cooled 11kv/440v / outdoor T/F Y/▲ / z% = 5% 3ø, 4 wires 50 Hz

Page 85: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Capacitor bank Types of load: 1.Resistive load: current is in phase with voltage 2.Inductive load: current lags voltage 3.Capacitive load: current leads voltage Phase angle: angle between voltage and current Note: All loads in our daily life are resistive – inductive loads, ex

(tube light,bulb, motor and pumps ,w/h, w/m , r/c). Hence capacitor bank are required which are connected to MDB ,which improves the over all power factor of the system . Sudan PF = 0.80 (low PF) Final PF = .98 or .96 (improve p.f)

Page 86: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Capacitor bank Note Capacitor bank is not require for single phase equipment or for

small project Capacitor bank required for project involving three phase

equipment or here phase motors or MCC panels and this capacitor bank is connected to MDB.

Unity of capacitor bank: KVAR (Kilo – Volt – Ampere – Reactive) Formula to calculate capacitor bank: Capacitor bank (KVAR) Max demand of MDB in KW {tan(cos-¹ø1) – tan (cos-¹ø2)} Where Ø1 → initial power factor = 0.8 Ø2 → final power factor = 0.98

Page 87: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Capacitor bank standard capacitor bank Types of capacitor bank: 1.Fixed capacitor bank 2.APFC (Automatic Power Factor Corrector) APFC: in this types the capacitor are automatic , they become on and off depending on the load Ex: If full load then all capacitor are on If half load then few capacitor are on If no load then very few capacitor on

Page 88: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

EMERGENCY BACK UP SYSTEM UPS / Inverter (Un interrupted Power Supply)

DG (Disel Generator ) or stand by generator

Page 89: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

UPS / Inverter UPS →Un interrupted Power Supply UPS is used for back up of electronic equipment

,ex(computer, CCTV)

Inverter is used for back up of electrical and electronic equipments

Ex → electrical (fans – lights - w/m ) Ex → electronic (computer – CCTV ) Unit of UPS/Inverter → KVA (Kilo – Volt – Ampere )

Page 90: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

UPS / Inverter Standard of UPS /Inverter Step to calculate UPS/inverter size: 1.Calculate the total load in KW 2.Calculate the total load in KVA 3. UPS/Inverter size = total load in KVA UPS/Inverter loading = total load in KVA 0.80 (80% or 85% loading) 4. select the standard size

Page 91: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

UPS / Inverter Wattages of load: 1. Tube lights = 40 w 2. Ceiling fans = 80 w 3. Computer (a)CRT computer = 300 w (b)LCD computer = 200 w (c)LED computer = 160 w 4. printer = 200 w 5. router = 50 w 6. (6) EPBAX = 50 w 7. (7) CCTV = 50 w

Page 92: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Diesel generator The diesel generator can be connected in two methods 1.C.O.S (Change Over Switch ) manually operated switching 2. A.T.S (Auto Transformer Switch ) automatic switching Units of generator → KVA

Page 93: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Diesel generator Standard generator size Step to calculate generator size: 1. Calculate the total load in kw = (SMDB Comm) 2. Total load in KVA = kw /cosø = KVA 3. Generator size = = total load in KVA generator loading (0.80) 4. Select the standard generator size

Page 94: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Electrical instruments (testing and commission):

1. Voltmeter 2. Ammeter 3. Energy meter or Kwh meter 4. P.F meter 5. Frequency 6. Phase indicators 7. Multi meter

Page 95: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Earthing and lighting protection system

Earthing : connection of wire to the ground is knows as earthing

Types of earthing conductor: 1.Earth continuity conductor (ECC) or protection earth conductor 2.Main earth conductor 3.Equipment bonding conductor 1.Earth continuity conductor (ECC) or protection earth conductor: The earth wire passing to final loads and DB to SMDB or

MDB is knows as ECC. 2.Main earth conductor: The earth wire connected to ground is knows as main earth

conductor usually it is connected to MDB.

Page 96: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Earthing and lighting protection system

3.Equipmential bonding conductor: Every metallic part in the electrical installation shall be

connected to ground (earth) Types of earth pits: 1.Pipe earthing 2.Electrode earthing 3.Plate earthing

Page 97: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Lighting protection system lighting protection system is building above 15 meter lighting system: lamp → any device which gives light is knows as lamp types of lamp: 1.Incandescent lamps

2.Fluorescent lamps a) CFL (compact Fluorescent lamps) b)tube

Page 98: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Types of lamp 3.Mercury vapor lamps

4.Metal halide lamps 5.HPS(High Pressure Sodium)

6.Halogen lamps

Page 99: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Types of lamp Note: Incandescent lamps are not recommended as their

efficiency is very low (high input current , low output current

For indoor purpose the best lamps are fluorescent lampsas their efficiency is very good (less input current or power high out put light

The M.V lamps and metal ,HPS lamps are preferred for out door street light.

Lamp input: is measured in watts Ex : tube light(40w,36w) or CFL (24w , 36w) Lamp output: lamp output is measured in lumens .

Page 100: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Luminaire or lighting fixture Lamp fixed on a frame or reflectors is knows as luminaire Illumination: The lumen output of any luminaire falling on asq.meter room area is knows as illumination It is measured is 1.Lux (Lx) if the room dimensions are in meter 2.Foot candle (F.C) if the room dimension are in feets Relation between LUX and F.C: 1 LUX = 0.1 F.C 1F.C = 10 LUX

Page 101: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Recommended lux level for different rooms by IENSNA IENSNA: Illumination Engineer Society North America Bedroom = 50 lux = 5 FC Hall = 150 lux = 15 FC Kitchen = 300 lux = 30 FC Bathroom =100 lux = 10 FC Coefficient of utilization (Cu): The Cu depends on the reflection factors of ceiling wall and floor colors . also it depends on the work plane height Note: for manual calculation consider cu= 0.45%

Page 102: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Lamp lumen factor (LLF) Lamp lumen factor (LLF) or lumen loss factor(LLF)

or maintenance factor (MF): Ex : tube light (40 w) Today → 2450 lumens After 3 years→ less than 2450 lumens The LLF depends on cleaning of luminaire Note For manual calculation for 3 years maintence consider

LLF= 0.67

Page 103: BUILDING ELECTRICAL SYSTEMS DESIGN &  DRAFTING

Formula

Formula to calculate no.of luminaire in room: No.of luminaires = illumination (lux or FC)× room area ( No .of lamps /luminaire )×(luminaire×cu×LLF)

Cu = .45 LLF = 0.67

Arrangement of luminaire: (x=2x) X → distance from wall to luminaire 2X→distance between luminaire to luminaire