![Page 1: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/1.jpg)
Industrial and Commercial Power SystemsTopic 9
POWER QUALITY
The University of New South Wales
School of Electrical Engineeringand Telecommunications
![Page 2: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/2.jpg)
Power quality (PQ) problem = any problem that causes voltage, current, or frequency deviations in the supply and may result in mal-operation or failure of end-user equipment.
In majority of cases, power quality actually refers to quality of the voltage. Therefore, PQ standards mostly specify requirements on supply voltage.
![Page 3: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/3.jpg)
Some effects
C/B trips when it shouldn’t.
Computers lose data or crash
Neutral conductors overheat
Digital clocks show erratic time
Adjustable speed drives trip or suffer damage
Power factor correction capacitors blow up
Lights flicker
![Page 4: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/4.jpg)
Power quality definitions [Ref: R.C. Dugan]
![Page 5: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/5.jpg)
Factors that cause power quality problems:
Increased use of power quality-sensitive equipment.
Increased use of equipment that generates power quality problems
Increased inter-connectedness of power system
Deregulation of power industry
![Page 6: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/6.jpg)
Tolerance envelope for IT equipment.Developed by Information Technology Industry Council (ITIC), formerly
Computer and Business Equipment Manufacturers Association (CBEMA).
![Page 7: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/7.jpg)
Summary of power quality problems[Ref: R.C. Dugan]
![Page 8: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/8.jpg)
Reliability measures for distribution systems:
Supply availability: actual time supply is available to customers, expressed as percentage.
utilities aim to deliver 4-nine or higher availability (total outage of 52 minutes in one year )
Reliability Index or SAIDI (System Average Interruption Duration Index): average duration lost per customer per year
SAIFI (System Average Interruption Frequency Index)
CAIDI (Customer Average Interruption Duration Index)
MAIFI (Momentary Average Interruption Frequency Index)
![Page 9: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/9.jpg)
[Ref. Electricity Network Operation Standards, July 2004]
![Page 10: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/10.jpg)
NSW Electricity Information (Independent Pricing and Regulatory Tribunal)
![Page 11: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/11.jpg)
Customer Service Standards (EnergyAustralia)
Customers can claim a payment if experience:
(i) too many interruptions in one year or(ii) an interruption that lasts too long
Amount: $80 per claim, max $320 per year per premise
Ref. EACustomer Service Standards brochure
![Page 12: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/12.jpg)
Customer Service Standards (EnergyAustralia)
Ref. EA Customer Service Standards brochure
![Page 13: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/13.jpg)
Principal phenomena causing electromagneticdisturbances as classified by the IEC.
![Page 14: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/14.jpg)
Categories and characteristics of power systemelectromagnetic phenomena [Ref: R.C. Dugan]
![Page 15: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/15.jpg)
Simplified classification system by EnergyAustralia
ENOS Electricity Network Operation Standards, June 2006
![Page 16: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/16.jpg)
Transients:
2 categories: impulsive and oscillatory. These terms reflect waveshape of transient.
Sometimes, also categorized according to their mode: common mode or normal mode.
![Page 17: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/17.jpg)
Transients: Impulsive transients
Uni-directional impulse. Characterized by rise and decay times.
Most common cause is lightning: Voltage impulse wave of 1.2/50µs Current impulse wave of 8/20µs
Due to high frequencies involved, shape of impulsive transients can be changed quickly by network components.
![Page 18: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/18.jpg)
Transients: Impulsive transients
Lightning stroke current impulse transient .
![Page 19: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/19.jpg)
Transients: Oscillatory transients
High-frequency oscillatory transient: primary frequency component >500kHz, typical duration in µs.
Medium-frequency oscillatory transient: primary frequency between 5kHz and 500kHz with duration of tens of µs.
Low-frequency oscillatory transient: primary frequency <5kHz, duration from 0.3 to 50ms. Frequently encountered on sub-transmission and distribution systems. Caused by many types of events, most frequent is capacitor bank energisation.
![Page 20: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/20.jpg)
Oscillatory transient by back-to-back capacitor switching
Low-frequency oscillatory transient caused by capacitor-bank energisation
Low-frequency oscillatory transient caused by ferro-resonance of an unloaded transformer
![Page 21: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/21.jpg)
Long-duration voltage variation:
Over-voltage: increase in rms ac voltage >110% at 50Hz for duration >1 minute
Under-voltage: decrease in rms ac voltage <90% at 50Hz for duration >1 minute
Sustained interruption: voltage is <0.1pu for duration >1 minute
![Page 22: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/22.jpg)
Short-duration voltage variation:
3 types: interruption, sag, swell. Each can be designated as instantaneous (0.01-0.5s), momentary (0.5–3s) or temporary (3-60s).
Interruption: voltage decreases to <0.1 pu for duration <1 minute
Sag (dip): decrease in rms 50Hz ac voltage to between 0.1 and 0.9pu for duration <1 minute
Swell: increase in rms 50Hz ac voltage to between 1.1 and 1.8pu for duration <1 minute.
![Page 23: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/23.jpg)
Short-duration voltage variation:
Momentary interruption due to a fault and reclosing.
![Page 24: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/24.jpg)
Short-duration voltage variation:
Voltage sag caused by single line to ground (SLG) fault.
![Page 25: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/25.jpg)
Short-duration voltage variation:
Temporary voltage sag caused by motor starting.
![Page 26: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/26.jpg)
Short-duration voltage variation:
Instantaneous voltage swell on un-faulted phase during a single-line to ground (SLG) fault.
![Page 27: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/27.jpg)
![Page 28: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/28.jpg)
Voltage sag performance of EnergyAustralia distribution networks.
Note: ITIC Information Technology Industry Council of America voltage tolerance envelope
![Page 29: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/29.jpg)
Voltage imbalance (unbalance):
Result from unbalanced network impedances or unequal distribution of single-phase loads.
can cause overheating and mal-operation of certain types of 3φ motors.
EnergyAustralia’s objective is not to exceed 6% difference between highest and lowest phase or line steady state voltage (5 minute average) for LV network.
![Page 30: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/30.jpg)
Voltage imbalance (or unbalance)
![Page 31: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/31.jpg)
![Page 32: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/32.jpg)
Waveform distortion:
Steady-state deviation from ideal 50Hz sine wave.
5 different types of waveform distortion. DC offset Harmonics Inter-harmonics Notching Noise
![Page 33: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/33.jpg)
Waveform distortion: DC offset
Presence of DC voltage or current
Caused by equipment with different operating characteristics in each half cycle (e.g. half-wave rectification), geomagnetic disturbance
According to NSW Electrolysis Committee, DC voltage component of neutral conductor w.r.t. earth can reach +/-10V.
Corrosion to earthing system.
AS3100 Approval and Test Specification – Definitions and general requirements for electrical materials and equipment.
![Page 34: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/34.jpg)
Current waveform and harmonics of an adjustable-speed-drive.
Waveform distortion: Harmonics
![Page 35: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/35.jpg)
Waveform distortion: Harmonics Sinusoidal voltage/current components at multiple
frequencies of 50Hz (e.g. 150Hz is third harmonic)
Caused by non-linear devices and loads on system.
AS/NZS 61000.3.6.2001 (Electromagnetic compatibility - Assessment of emission limits for distorting loads in MV and HV power systems). Utilities seek to restrict their contribution at the pcc to 30-50% of these limits.
![Page 36: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/36.jpg)
Waveform distortion: Inter-harmonics
Caused by waveforms that have frequency components that are not integral multiples of fundamental (50Hz)
Main causes are static frequency converters, cyclo-converters, induction motors, arcing devices.
Can cause light flicker, audible noise in audio equipment, vibration in induction machines.
Allowable limits specified in IEC Std 1000.3.9
Mains signaling voltages, injected onto network by the utility, e.g. 492, 750 and 1050 Hz.
![Page 37: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/37.jpg)
Waveform distortion: Notching
Periodic voltage disturbance caused by switching operation of power electronic devices (current commutation)
Extent of distortion determined by depth and width of notch
Frequency components due to notching can be quite high
Present Australian standards limit notch depth to 20% of peak supply voltage at point of common coupling.
![Page 38: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/38.jpg)
Waveform distortion – Notching
Voltage notching caused by three-phase converter
![Page 39: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/39.jpg)
Waveform distortion: Noise
Any unwanted signals that cannot be classified as harmonic distortion or transients and have spectral content < 200 kHz
Caused by power electronic devices, control circuits, arcing equipment, switching power supplies.
Improper grounding exacerbates problem.
In Australia, acceptable limits set by Spectrum Management Agency.
![Page 40: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/40.jpg)
Voltage fluctuation:
Rapid changes in voltage within allowable limits of nominal voltage
AS60038-2000 specifies new standard nominal voltage to be 230V (reduced from 240V). Tolerance is +10% to -6% which means actual supply voltage range will not necessarily be lowered.
EnergyAustralia aim to maintain steady-state voltage (ten-minute average) within +/-10% of nominal voltage of 240V (i.e. between 264V and 216V), at consumer’s terminals. If possible, it will aim for 226-253V range.
![Page 41: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/41.jpg)
Voltage fluctuation:
Voltage flicker caused by arc furnace operation
Note: Flicker can cause lamps to blink rapidly, and is visible to human eyes at flickering frequencies of 6-8Hz.
![Page 42: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/42.jpg)
Power frequency variation:
Deviation of power system fundamental frequency from nominal value (50Hz or 60Hz)
Power system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes. .
Standards set by NEMMCO (National Electricity Market Management Co Pty Ltd).
Affect clock accuracy. Policy of maintaining “electrical time” in NSW to within 3s of Australian Eastern Standard time.
![Page 43: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/43.jpg)
Power frequency variation:
![Page 44: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/44.jpg)
Symmetrical components
![Page 45: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/45.jpg)
![Page 46: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/46.jpg)
![Page 47: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/47.jpg)
![Page 48: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/48.jpg)
![Page 49: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/49.jpg)
![Page 50: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/50.jpg)
Harmonic distortion
![Page 51: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/51.jpg)
Very little distortion in sine wave voltage generated at power stationsCaused by non-linear loads at the end-usersHarmonic distortion = periodic distortion in every AC cycle
Current distortion caused by non-linear resistance
![Page 52: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/52.jpg)
Harmonic current flowing through system impedanceresults in harmonic voltage at the load.
![Page 53: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/53.jpg)
Fourier Analysis
Any periodic waveform can be expressed as a Fourier series.Advantage of using Fourier series analysis
![Page 54: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/54.jpg)
![Page 55: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/55.jpg)
Total harmonic distortion (THD):
For voltage:
(IEEE definition)
Note: IEC defines THD as % of total rms
THDV is a meaningful parameter but THDI may not be.
Total demand distortion (TDD) refers to fundamental of peak demand current.
Crest factor (CF):
Measure of effective value of harmonic components
![Page 56: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/56.jpg)
Effects of harmonics on power factor
![Page 57: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/57.jpg)
![Page 58: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/58.jpg)
![Page 59: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/59.jpg)
Harmonicresonance
![Page 60: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/60.jpg)
![Page 61: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/61.jpg)
![Page 62: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/62.jpg)
TroubleshootingPower Quality Problems
![Page 63: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/63.jpg)
What are the problems ?
Where are the problems occurring ?
When do they occur ?
What else is happening at the same time ?
![Page 64: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/64.jpg)
PQ problem solvingflowchart
![Page 65: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/65.jpg)
Equipment for PQ investigations
Voltmeters, ammeters, multi-meters
Oscilloscopes
Harmonic analyzers
Power quality analyzers
Other devices, e.g. infrared detectors
![Page 66: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/66.jpg)
Fluke 43 power qualityAnalyzer (single phase)
Fluke 430 power qualityAnalyzer (three phase)
![Page 67: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/67.jpg)
![Page 68: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/68.jpg)
![Page 69: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/69.jpg)
![Page 70: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/70.jpg)
![Page 71: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/71.jpg)
DRANETZwww.dranetz-bmi.com
![Page 72: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/72.jpg)
Protection measures
![Page 73: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/73.jpg)
Protection measuresEnergyAustralia Electricity Network Operation Standard (June 2006)
![Page 74: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/74.jpg)
Test next week covers:TransformersFault current calculationsProtection
![Page 75: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/75.jpg)
Thank you
![Page 76: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/76.jpg)
The Electrical SystemAs
A Tandem Bicycle
Ref: Stefan Fassbinder, Sept. 2005www.leonardo-energy.org
![Page 77: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/77.jpg)
Tandem bicycle moving at constant speed
loads
Transmissionnetwork
generators
Constant velocity = constant frequencyConstant tension = constant voltage
Gear = transformer
![Page 78: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/78.jpg)
Inductive power and its compensation
Inductive load compensation
![Page 79: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/79.jpg)
Harmonic distortion
Hyperactive blue rider:
Constantly bending forward and backwards
Not at rhythm of bike but few times faster
Causing bike to jerk forward and backwards.
Saddle mounted on castors = harmonic filter
![Page 80: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/80.jpg)
Keeping constant voltage and frequency
Voltage dip
Voltage rise
50Hzin-phase
Connect to system
Disconnect from system
![Page 81: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/81.jpg)
Three different types of power stations
Traditional power stations(coal-fired turbo-generators)
Slow-speed hydro-generators
Wind turbinesvariable speed drives
![Page 82: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/82.jpg)
Three different types of loads
Resistive loads
Reactive loads
Electrical motors
Electrical energy heat
![Page 83: Bow Bowing Substation system frequency directly related to generator rotating speed. Slight variations in frequency as dynamic balance between load and generation changes.. Standards](https://reader034.vdocuments.site/reader034/viewer/2022051800/5ac6606c7f8b9aae1b8e99ea/html5/thumbnails/83.jpg)