boq alia
DESCRIPTION
okTRANSCRIPT
Bill of Quantities
Part 1
June 2009
Construction of Remaining Area of the Second Floor of the North Wing at Hebron Hospital
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
2
Item Description Unit QTY Unit Rate
Section I - Civil Works
1 Preparation Works
1.1 JOB 1
1.2 M2 15
1.3 JOB 1
1.4 M2 450
Total of Preparation Works carried to summary:
The contractor shall visit the proposed site to familiarize himself with the required scope of work and the existing site conditions. Unit price shall include costs of the needed material and the workmanship which are required to complete the work. The price shall include costs for making the necessary temporary works to ensure the safety of the visitors of the functioning hospital and to protect the finished works rendered in the existing hospital. Price shall also include cost of hauling away the demolished material. The contractor shall preserve, protect and make the necessary works to maintain the existing electro-mechanical system to serve the functioning hospital.
Carefully demolish the concrete covering steel reinforcement of the columns starters. The work includes demolishing portions of concrete parapets, walls, slabs... etc., and cleaning of steel rebars with a steel brush to remove any concrete paste, rust, stains, etc. necessary for making proper bonding and connections of the existing structural elements to the new proposed constructions. All as directed by the engineer and as shown on the drawings.
Demolish and remove portion of the existing block wall between the existing corridor and the new constructed one as shown on the drawings.
Dismantle, repair, paint and re-install of staircase steel door (210cm x 120cm) at the existing roof level to the roof of the new construction.
Demolish and haul away the existing sloped light weight concrete layer on the existing roof according to the engineer instruction.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
3
Item Description Unit QTY Unit Rate
2 Concrete Works:
2.1 M3 27
2.2 M2 235
2.3 Ditto, but for 56cm thick ribbed slabs. M2 220
2.4 M3 9
2.5 Supply and cast concrete B300 for walls 20-35cm thick. M3 17
2.6 Supply and cast concrete B300 for roof parapet. M3 20
2.7 M3 5
2.8 M3 1
2.9 TON 28
Total of Concrete Works carried to civil summary:
Unit rates of concrete works includes supplying and casting of a ready mixed concrete. The price shall include all costs of material and workmanship for preparing the formwork, shuttering, fixing of steel reinforcement, vibration, curing making grooves and sleeves ..etc.
Supply and cast concrete B300 for columns of various cross sections .
Supply & cast concrete B300 for 46cm thick ribbed slabs, price includes cost of the required light weight polyester blocks "ETOLITE", and drop beams as shown on drawings.
Supply and cast of B300 for staircase flights, landings and steps .
Supply and cast concrete B300 for suspended solid slabs of various thickness
Supply and cast concrete B300 for machine foundations including vibration insulation rubber pads... etc, as approved by the engineer.
Supply of deformed high yield steel rebar reinforcement of various diameters, characteristic strength FY=4200kg/cm2 for concrete reinforcement, as shown on drawings and according to specifications. The steel reinforcement should be stored in a proper location on site as instructed by the engineer.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
4
Item Description Unit QTY Unit Rate
3 Block Works:
3.1 Ditto, for constructing 10cm hollow concrete block walls M2 650
3.2 Ditto, but 15 cm hollow concrete block . M2 220
3.3 Ditto, but 20 cm hollow concrete block . M2 310
3.4 M3 10
Total of Block Works Carried to Summary:
Supply and construct hollow concrete block walls using cement and sand mortar (1:4) . The price includes cost of cutting, bonding, control and expansion joints, vertical concrete bond beams to columns or walls including steel reinforcement (of 4 steel bars 12mm dia and 8mm stirrups@ 20cm c/c). All as shown on the drawings, the specifications and as directed by the engineer.
Casting horizontal B300 concrete lintels or girdles above block works 20 or 10 cm thick. The price shall include the cost of steel reinforcement of 4steel bars 12mm dia and 8mm stirrups@ 20cm c/c. All in accordance with the engineer's instructions, all as shown on the drawings.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
5
Item Description Unit QTY Unit Rate
4 Sealing Works:
4.1 M2 480
4.2 M2 540
4.3 MR 90
4.4 M2 80
4.5 M2 340
4.6 M2 340
4.7 MR 30
4.8 MR 13
4.9 M2 85
Total of Water Proofing carried to summary:
Supply and cast light weight sloping foam concrete layer, of density 1400kg/M3and compressive strength of 40kg/cm2, on the roof having minimum thickness of 5cm and to the required slope. Unit rate includes performing 2 cm cement screed layer and 12x12 cm cement fillet at the parapet above the light weight concrete layer to receive the water proofing membrane.
Supply and install one layer of water proofing membrane 5mm thick, covered with white gravel, "Pazkar"or equally approved. The unit price shall include cost of a prime coat GS474 at a rate of 0.25 kg /m2 including all the necessary material and workmanship, as specified.
Supply and install sealant cover at groove" NP1 or equally approved" at roof parapet, as shown in drawings.
Supply and apply three coats of hot asphalt layers (25/75) at rate of 500g/m2 for each layer, reinforced by two layers of fiberglass, and a prime coat GS474. All according to the manufacturer instructions and to the engineer's approval.
Insulation of exterior walls with two layers of BONZAL sealant or equally approved. The price also include preparing the surface and applying one layer of cement and sand(2:1) plaster to receive the sealant coat.
Thermal insulation of exterior walls with high density extruded polystyrene boards RANDOPAN or equally approved, 3cm thick
Circular strip with foamed rubber and caulking with elastic compound for vertical and horizontal seams .
Supply and install aluminum clip strip for covering vertical and horizontal expansion joints .
Supply and install 2 cm extruded polystyrene for expansion joints (24 kg/m3).
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
6
Item Description Unit QTY Unit Rate
5 Carpentry and Metal Works:
All door frames of the required widths (metal or wood) shall be of formed galvanized sheet metal 2mm thick. The frames shall be held in place with standard concrete filling. Door frames shall be painted using a prime coat brown unseal ZN, under coat, and the finishing coat.
Wooden door leaf shall be 45mm thick with 70% fill, plywood facing on each side shall be 6mm thick, the door panels frames shall be of hard wood 45*100mm.The doors shall be coated with "PVC" on both sides similar to the existing doors on the same floor or oil-based paint. Price shall include cost of the protection plates, hinges, closing mechanism, door stops, and all needed accessories. All as per drawings and the specifications.
Supply and install heavy duty hinges (three 4" hinges for each door), locks and cylinders are "Yardini" or equally approved. Doors shall have 3 original sub-master keys and 2 general master keys.Door handles shall be steel handles similar to those installed on the existing doors at the same floor or as approved by the engineer
The "pvc" shall be 2mm thick "Tarkett Commercial " # 227 NCS 4010- B90G or equivalent applied on both sides of door panels.
The thickness of the sheet metal of the fire doors shall be 1.5mm insulated with rock wool 50mm thick and density of 80-90kg/m3. The door shall include the emergency door-opening handle, fireproof locks, and hydraulic door closers made in Germany.
All wooden door panels shall be furnish by oak wood frames and should be painted with 3 coats of lacquer paint.
All wooden and metal door panels shall be painted with 2 coats of butty, one coat of under coat and 3 coats of oil base paint.
All exposed edges, louvers and door frames are oak wood and should be painted with 3 coats of lacquer paint.
Rate for smoke proof doors include 100% filling, sealing strips around door panel including bottom of panel.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
7
Item Description Unit QTY Unit Rate
5.1 A-Carpentry
5.1.1 UNIT 12
5.1.2 Single sealed door 90x210 cm, type N-45 in the list UNIT 1
5.1.3 Ditto, but with a wooden louver UNIT 3
5.1.4 Wooden single door 80x210 cm, type N-62in the list UNIT 1
5.1.5 Single door + window 80x210 cm, type N-63 in the list UNIT 11
5.1.6 Four doors closet 240x200x40 cm, type N-85 UNIT 1
5.2 B. Metal Works
5.2.1 Ladder anchored to the wall, type M-21 in the list UNIT 1
5.2.2 Metal door , 200x40cm bent sheet 2mm thick, M-26 UNIT 1
5.2.3 Sheet metal door 35X200 cm type M-27 in the list UNIT 6
5.2.4 Job 1
5.2.5 Job 1
5.2.6 No. 1
Total of Carpentry and metal works….. carried to summary:
Fabricate supply and install the following wooden doors complete with all necessary fixing accessories, glazing, hinges, louvers, grills, hydraulic closures, hardware and ironmongery. All in accordance with the drawings and specifications.
Single sealed door with fixed wooden slats 120x210 cm, type N-24
Fabricate, supply and install steel cover for the main mechanical shaft at existing roof, covered with corrugated white color galvanized sheets of 0.06 mm thick as per the drawings and Engineer instructions. Price to include preparing the shop drawings for approval and painting the steel of three coats of oil paint on one coat of primer.
Fabricate, supply and install steel Fire Escape Stairs. The price shall include preparing the shop drawings for approval, steel handrail for the stairs, painting works, fastening the stairs at both ends, civil works and foundations, and all other works that might be needed as per the drawings and the Engineer instruction.
Supply and install a staircase steel door (210cm x 120cm) similar to the door installed at the existing roof level.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
8
Item Description Unit QTY Unit Rate
6 Stainless Steel Works
6.1 Sink and work area ,255 /60/90cm, type M-51 in the list UNIT 1
6.2 Sink and work area ,215 /60/90cm ,type M-53* in the list UNIT 1
6.3 Sink and work area 302/60cm ,type M-61*in the list UNIT 1
6.4 UNIT 28
6.5 Support handles in toilets, type M-65 in the list UNIT 10
6.6 Corner guard for the walls, to height 210cm ,type M-68 in the list UNIT 35
6.7 Corner guard for the walls, 10-25cm thick, type M-69 in the list UNIT 2
Total of Stainless Steel works….. carried to summary:
7 Plastering Works:
7.1 M2 1320
7.2 M2 90
7.3 M2 400
Total of Plastering Works carried to Summary:
Handholds for toilets for invalids, 270 cm long type M-64 in the list
The contractor shall, when pricing this bill, take into consideration and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract.
Three layers of internal plastering for ceiling, walls, columns, drop beams..ets composed of a bond coat, base coat 1:4, and finish coat 1:5 as specified.
External plastering for parapet, walls and wherever needed composed of 3 coats a bond coat 1:1, base coat 1:4 and finish coat 1:2 with waterproof liquid all as specified.
One layer of cement plastering (Glanse) to ceiling and wall above suspended ceiling level and where ever instructed by the Engineer.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
9
Item Description Unit QTY Unit Rate
8 Flooring and Covering Works:
8.1 M2 290
8.2 Ditto but 30 x 10 x 1 cm terrazzo tiles skirting. MR 260
8.3 M.R 22
8.4 M2 470
8.5 M2 17
8.6 M2 40
8.7 M2 115
8.8 No 24
8.9 Ditto but,10cm high,1cm thick for stair case skirting (triangle). MR 12
8.10 UNIT 40
8.11 Ditto but soap dishes . UNIT 40
8.12 Liquid soap dispenser, model Visio soap AM or equivalent. UNIT 20
8.13 Crystal mirrors, 60/45 cm. 4mm thick. UNIT 50
The contractor shall, when pricing this bill, take into consideration and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract.
Supply and install 30x30cm terrazzo tiles similar to the floor tiles at the 2nd floor. Rate includes the supply and installation of 3 cm mortar, cement sand fill blew tiles, grouting as made by Mrfix or equally approved and polishing all in accordance with the specifications and applicable Standards.
Supply and install 3 cm local marble (Abo alkhabaz) or equally approved thresholds 15-25 cm wide, including aluminum strips
Supply and install 20x20x0.8cm ceramic tile class (A) "Negev" model 9001 similar to the tile installed in existing part of the same floor. The tiles shall be laid and fixed to the walls by Mr fix bonding agents or equally approved, as specified. Price includes cost of surface preparation to receive tiles, which shall include two coats of cement plaster (scratch and float coat) and the approved adhesive materials and grouting.
Ditto but installation (no supply) of green color ceramic tiles (20x20x0.8cm).
Supply and install non-slip 20x20*.8cm ceramic tiles, "Negev" or equivalent class (A) for bathrooms flooring, as specified and approved by the Engineer. The price includes the mortar (1:3) the sand cement fill. The color of the tiles shall be as chosen by the Engineer.
Installation of the granite porcelain tiles (30x30*.8cm), for flooring. The price to include the mortar (1:3)and the sand cement fill. (materials are available in Hospital storage)
Supply and install 3cm thick local marble "Sourmaen" for stair threads 155*34*3 cm polished one face & edge . The threads should be bedded on 3cm mortar (1:3). The rate also includes cost of risers 155*13.66*2 cm and the water stop at each thread and where required
Supply and install stainless steel toilet paper holders, mounted on the wall.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
10
Item Description Unit QTY Unit Rate
8.14 Total of Flooring and Covering Works carried to Summary:
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
11
Item Description Unit QTY Unit Rate
9 Painting Works:
9.1 M2 320
9.2 M2 30
9.3 M2 1000
9.4 Painting of wall with "Acrinol" for mildew and fungus protector M2 50
9.5 M2 230
9.6 M2 85
Total of Painting Works carried to Summary:
The contractor shall, when pricing this bill, take into consideration and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract.
The contractor should allow in his pricing that the engineer will use as many different colors or combination of colors to meet an approved color scheme.
All painting material shall be made by Tambour or equally approved
Supply and apply policed paint for plastered walls and ceiling composed of one coat of primer fill and three coats of policed.
Supply and apply emulsion paint for plastered walls composed of one coat of primer fill two coats putty and 3 coats of emulsion.
Supply and apply oil paint for plastered walls areas composed of primer fill , two coats of putty ,one coat of under coat and 3 coats of " Polyour".
Painting of interior walls with a fine texture coating Tamburtext or equivalent.
Painting of bare exterior concrete with Temglass, price includes preparation of the surface .
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
12
Item Description Unit QTY Unit Rate
10 Aluminum Works:
10.1 Two-pane sliding window, 180/104 cm, type 20-AL in the list UNIT 7
10.2 UNIT 8
10.3 UNIT 82
10.4 UNIT 1
10.5 Screen mesh 90x90 cm for existing windows at same floor. UNIT 41
10.6 Screen mesh 60x90 cm for existing windows at same floor. UNIT 6
Total of Aluminum works carried to summary:
The contractor shall, when pricing this bill, take into consideration and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract.
Fabricate supply and install the following aluminum doors & windows complete with vacuumed double glazing, silicone, handles and locks , all as shown in drawings and the specifications. The type, grade and colors shall match those installed in the existing part of the same floor. Shop drawings must be submitted by the contractor for the Engineer's approval. All windows and doors profiles shall be "Gonzales" product or equally approved. The unit rate shall include cost of the roller and Aluminum shutters as shown on drawings and specifications.
All aluminum windows shall be 2 1/2 tracks for horizontal and vertical partitions, with screen mesh, glazing, weather strips shall be Neoprene or EPDM.
Window with lower part fixed, including roller shade, 180/156cm type 33AL
Rail for curtain around hospital bed, 180 + 240 cm long, type 50-AL in the list.
Aluminum fixed window 60x338 cm divided into four equally parts with 6mm antisun glass, type 61AL in the list
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
13
Item Description Unit QTY Unit Rate
11 Stone Works:
11.1 M2 300
11.2 MR 30
11.3 Ditto, but 38 cm wide. MR 2
11.4 MR 45
11.5 Ditto, but 25 cm wide. MR 8
11.6 Window lintels with stone panels 30 cm wide, 5cm thick. MR 30
11.7 Window lintel with stone panels 25 cm wide, 5cm thick. MR 2
11.8 45cm wide stone coping 6cm thick, "mesamsem" finish MR 95
Total of Stone Works carried to civil summary:
The contractor shall, when pricing this bill, take into consideration the costs and expenses of all requirements stipulated in the preambles, drawings, details, and technical specification of the contract.
Supply and install 5 cm thick 25 cm wide Taltish stone courses, first quality KHALET ENJASSA similar to the existing at the Northern Wing, as shown on drawings. The price also includes 15 cm thick B200 concrete backing and #8 mm steel mesh and anchoring as shown on drawings. Unit price shall also include cost of corner stones, stone grouting and pointing with white cement.
Window sills of stone panels (Matabeh) 43 cm wide 8cm thick as shown on drawings.
Window jamb with stone panels (Matabeh) 30 cm wide, 5cm thick.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
14
Item Description Unit QTY Unit Rate
12 Suspended ceiling:
12.1 M2 40
12.2 M2 150
12.3 M2 15
12.4 M2 25
12.5 M2 17
Total of Suspended Ceiling Works carried to Summary:
The contractor shall, when pricing this bill, take into consideration the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract.
Supply and install non perforated acoustical ceiling made of formed galvanized sheet metal trays for bathrooms and wet areas. The metal tray should be of 0.8 mm thick 45 mm high painted with polyester epoxy paint
Ditto, but perforated sheets with perforation diameter 3.0mm (11% perforation). The trays should be covered with continuous and uniform manner of rock wool mats 25 mm thick of 25kg/m3 density. The rock wool mats shall be wrapped by inflammable polyethylene sacks, (in accordance with the Safety Regulations and Standard).
Ditto, but 60*60cm squared perforated sheets trays with perforation diameter 1.5mm (22% perforation) covered with approved acoustic material,(soundex) or equally approved
Supply and install vertical & horizontal gypsum boards 12mm thick for decorative ceilings and where required.
Galvanized sheet metal trays 0.6 mm thick for closing vertical walls.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
15
Item Description Unit QTY Unit Rate
13 Fixed Furniture:
13.1 UNIT 1
13.2 UNIT 1
13.3 UNIT 1
13.4 UNIT 1
13.5 Storage cabinet 180/55/260 type N -124 UNIT 2
13.6 Storage cabinet, 90/60/180 cm, type N128 in the list. UNIT 3
13.7 four-door closet, 220/60/180 cm, type N130 in the list. UNIT 1
13.8 Storage cabinet , 110/55/180 cm, type N129 in the list. UNIT 1
13.9 MR 250
13.10 MR 15
13.11
13.11.1 Size 25x12 cm NO 25
13.11.2 Size 40x15 cm NO 5
Fabricate, supply and install the following units, as in drawings with all fixing accessories, drawers, shelves, hardware, and iron monger with a master key .All furniture shall be made of plywood and carpenters' board 20mm maid by Etz Lavood,Sepen or equal. All edges shall be protected by oak wood strip, all in accordance with the drawings and specifications.
Maternity nurses' counter, dimensions of 300/60/110 cm, type N107
Bottom closet with stainless steel surface + upper closet, with general dimension of 255/35/60cm+255/58/90 cm, type N109 in the list.
Bottom closet with stainless steel surface + upper closet, with general dimension of 300/35/60cm+300/58/90cm, type N119 in the list.
Bottom closet with stainless steel surface + upper closet, with general dimension of 210/35/60 cm+210/58/90 cm, type N122 in the list.
Wall guard wooden 25x3 cm with 20 cm PVC 2 mm thick similar to the existing wall guard at the same floor.
Fabricate supply and install staircase handrail including fixing accessories, matching the existing handrail and as shown on the drawings. The rate includes surface preparation, 2 coats anti rust primer "Tambour synthetic and three coats of Tambour superlac.
Wall Signs:Supply & install Aluminum wall signs (plaques) with writing in Arabic and English with a special solvent-proof, weather and temperature resistant fixed on the door or the wall. The price include labor work and all fixing materials.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
16
Item Description Unit QTY Unit Rate
Total of Fixed Furniture carried to Summary:
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
17
Item Description Unit QTY Unit Rate
Section II - Mechanical Works14 Cold and Hot Water Supply System:
14.1 M.R 80
14.2 Ditto, for 3/4" pipe. M.R 9014.3 Ditto, for 1" pipe. M.R 10014.4 Ditto, for 1.25 pipe. M.R 4014.5 Ditto, for 1.5 pipe. M.R 4014.6 Ditto, for 2" pipe. M.R 16014.7 Ditto, for 3" pipe. M.R 20
14.8 Ditto, for 4"pipe. M.R 6
14.9 M.R 40
14.10 Ditto, for 3/4" pipe. M.R 5014.11 Ditto, for 1" pipe. M.R 40
14.12 M.R 70
14.13 Ditto, for 3/4" pipe. M.R 7014.14 Ditto, for 1" pipe. M.R 4014.15 Ditto, for 1.25 pipe. M.R 40
14.16 Ditto, for 1.5 pipe. M.R 30
14.17 M.R 20
14.18 Ditto, for 3" pipe M.R 20
14.19 M.R 750
Supply and install "Schedule 40" galvanized 1/2" pipe running along exposed or are within partitions and are fastened to the building, (or penetrate them) like ceilings, walls, bottom of suspended floors, partitions, columns, ducts, tunnels, special horizontal shats for pipes. The price includes all fasteners, supports, brackets, arches, bends, elbows, sleeves, branches, unions, all other required fittings and valves, connection with existing system, and testing. The pipes are joined by threaded joints. All done according to specifications, drawings and the approval of the Engineer.
Supply and install hot water pipe insulation as per Vidoflex or equal, 13mm thick, for 1/2" dia pipe.
Supply and install insulation for exposed hot water 1/2" pipe, with "Vidoflex" sleeves or equally approved, 13 mm thick, wrapped with plastic tape and secured with sheet metal strip and tagged for identification. Price includes insulation of bends, branches, valves , etc.
Supply and install insulation for exposed hot water 2" pipe, with "Vidoflex" sleeves or equally approved, 19 mm thick, wrapped with plastic tape and secured with sheathed with sheet metal strip. Price includes insulation of bends, branches,... etc.
Supply and install pex pipe 16mm with sleeve 25mm by "Aquapex" or equivalent .The price shall include all copper fittings like elbows inside walls 1/2", male and female adaptors, hangers, all needed accessories for connection between copper collectors to the point. All done according to specifications, drawings and the approval of the Engineer.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
18
Item Description Unit QTY Unit Rate
14.20 EYE 15
14.21 Ditto , but 1" collectors. EYE 80
14.22
14.23 Ditto, 3/4" valve. UNIT 314.24 Ditto, 1" valve. UNIT 414.25 Ditto, 11/4"valve. UNIT 414.26 Ditto, 1 1/2" valve. UNIT 414.27 Ditto, 2" valve. UNIT 4
14.28 UNIT 4
14.29 Ditto, 4" valve. UNIT 2
14.30 ASSY 1
14.31 UNIT 1
14.32 UNIT 2
14.33 Supply and install 6 kg fire extinguisher. UNIT 1
14.34 UNIT 1
14.35 UNIT 15
14.36 UNIT 15
14.37 Ditto, model no. A 5398 or equivalent. UNIT 4
Supply and install hot and cold water collectors 3/4" type "Giacomini" or equivalent. Collectors are installed in the ceiling of bathrooms with all required hangers and accessories. The price should include all main valves, sub valves, vents, and all accessories
Supply and install bronze gate valve made by "Giacomini" or equivalent, of the following size:
Supply and install resilient butterfly type valve 3" rilsan coated and lever operated, made by "Hakohav" or equal, with flanges and counter flanges.
Supply and install a hose cabinet reel for fire extinguisher hose. Reel base, made of metal which can be rotated on a central shaft, on which a 3/4" rubber or plastic hose 25 m long is wrapped, provided with a multi-purpose nozzle with quick-opening valve, all to the approval of the Engineer and local fire department.
Supply and install Fire hydrant landing valve 2"-2.5" with "Schturz" couplings for rapid hookup of fabric hose approved by Fire Service.
Supply and install terilyne hose of superior quality, 2" dia. X 25 m long, with multipurpose nozzle. "Schturz" couplings at both hose ends. The hose will be rolled up, tied and stored in fire fighting cabinet (price does not include cabinets).
Supply and install sheet metal cabinet 1.5 mm thick with 80X110 cm size, oven backed paint to freely accommodate all materials described under item 14.9. The cabinet shall be painted in red and identified as "Fire Fighting Cabinet".
Supply and install eccentric silent flush valve, by Shell or equivalent. Price includes shutoff valve, flush pipe, rubber shoe. Shutoff valve, flush pipe and brass disks to be chrome plated for suspended toilet bowl. All done as per specifications, drawings and the approval of the Engineer.
Supply and install 1/2"chrome-plated hot and cold water faucet battery "Ideal Standard Slim line Model no. A5390" or equivalent, Battery of type installed on walls.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
19
Item Description Unit QTY Unit Rate
14.38 UNIT 13
14.39 Supply and install 1/2" angle valve "Giacomini" or equivalent. UNIT 15
14.40 UNIT 15
14.41 UNIT 5
14.42 Supply and install 3/4"-11/2" non-return valve. UNIT 2
14.43 2" non-return valve. UNIT 3
14.44 UNIT 10
14.45 Ditto, but 1". UNIT 4
14.46 Supply and install 3/4" - 2" safety valve. UNIT 1
14.47 JOB 1
Total of Cold and Hot Water Supply….carried to summary:
Supply and install shower Mixer unit Ideal Standard Slim line Model no. A 5394 or equivalent .
Supply and install Hand Spray type Grohi or equivalent and hose made by or equivalent.Supply and install Expansion connectors for water, with 0.5"- 2" tapped joints, for expansion to 30 mm, made by "Tozen'' or equivalent.
Supply and install 3/4" vent valve, made by "Giacomini" or equal.
Supply and Install and test Domestic Pressure Booster system (Factory assembeled and Approved type "WILLO/Germany or equivalent "consisting of 2 pumps one operating and the other stand by Single stage pump with water flow of 20m3/hr and 40 meter head,3 sealed Pressure Vessel with capacity of 1000 liter each,collectors,Strainers,Non return valve,Valves,2 Pressure stat type "Danfuss" or equivalent, electrical control panel. the price include unti-vibrators base ,spring shock absorbers for each pump, all electrical and mechanical switches, wires and cables and connections needed for full installation
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
20
Item Description Unit QTY Unit Rate
15 Wastewater and Drainage Systems:
15.1 M 130
15.2 Ditto, but 1 1/2" dia. M 10015.3 Ditto, but 2 " dia. M 65
15.2 M 250
15.3 UNIT 15
15.4 Ditto but 4"/4" UPVC floor trap. UNIT 15
15.5 UNIT 3
15.6 Ditto 4" clean out . UNIT 18
15.7 Supply and install UPVC vent cap for 4" vent pipes. UNIT 15
15.8 UNIT 4
Supply and install UPVC pipes made by Al-Hilal / Egypt of size 1/14" for waste water, air conditioning drainage, and standpipes. Pipes run exposed and are fastened to walls, partitions, ceilings, shafts, suspended floors, or pipes laid within walls and under floors, Price includes all fittings, supports and fasteners, corrosion protection and 5 cm mortar over pipes under floors, connection with floor drains.
Supply and install 4" UPVC pipe by Al-Hilal-Egypt or equivalent , running exposed along partition, false ceilings, walls, shafts, floor bottoms or laid in walls. Price includes all kind of fittings(by Al-Hilal-Egypt),supports, testing,5cm concrete layer over pipes under floors. The price should include all digging work in concrete walls and floors needed to connect with existing pipes.
Supply and install 4"/2" UPVC floor trap with chrome threads mesh cover 20*20cm, as per Rit or equivalent.
Supply and install 4" UPVC inspection chamber with several inlets, with threaded removable hermetically closed cover of chrome 20*20cm.
Supply and install 2" sink trap made of PVC by " Al-Hilal-Egypt" or equivalent.
Total of Waste and Drainage Systems…carried to summary:
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
21
Item Description Unit QTY Unit Rate
16 Sanitary fixture and their Accessories:
16.1 assy 7
16.2 assy 7
16.3 Supply and install chrome-plated brass towel rack. assy 14
16.4 assy 14
16.5 assy 1
16.6 assy 3
16.7 assy 1
Total of Sanitary Fixtures and…carried to summary:
Supply and install white ceramic wash basin made by Ideal Standard SanRemo model no. E7460 or equivalent, and semi pedestal SanRemo E7492 or equivalent, installed on wall and resting on brackets.
Ditto, Ideal Standard SanRemo model no. E7450 or Equivalent, and semi pedestal SanRemo E7492 or equivalent.
Supply and install suspended wall hung toilet bowl by SANREMO from IS Model no. G6481 or equivalent, including PVC without cover by Ideal Standard or equivalent , all accessories, and required wall preparation.
Supply and install suspended white ceramic slop sink, by" Ideal Standard" Douro model no. R3806 or equivalent, and stainless steel grill type Douro model no. R6378 or equivalent, with chrom-plated fastening screws, strainer, plastic shoe.
Supply and install dish washing sink type 35006 by "Twyfords", "Macintosh" or equivalent, including trap, connection to hot and cold water, mixer type Ideal Standard Slimline model no. A5396 or equivalent, including special wall consoles.
Supply and install refrigerated water fountain, made by Frigeria / Italy or equivalent, of 40 liter/hr capacity, with chrom-plated push- button water faucet, compressor for cooling the water and appropriate motor rotating at 1450 rpm, a 4 liter water reservoir, connection works to water supply and connection to waste water.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
22
Item Description Unit QTY Unit Rate
17 Rainwater Drain Pipes:
17.1 M 30
17.2 UNIT 4
Total of Rainwater Drain Pipes…..carried to summary:
18 Air Conditioning Works:
18.1 M2 200
18.2 M 70
18.3 Ditto but 3/4." M 75
18.4 Ditto but 1". M 30
18.5 Ditto but 11/4". M 45
18.6 Ditto but 11/2". M 80
18.7 Ditto but 2". M 690
18.8 Ditto but 21/2", Jointing by welding, insulation thick 25mm M 20
18.9 Ditto but 3." M 150
18.10 Ditto but 4". M 10
18.11 Ditto but 5". M 10
18.12 Ditto but 6." M 12
Supply and install high quality 4" dia. G.I. grade "B" rainwater thread jointed pipes in columns or walls. The price should include all digging works needed to connect with existing pipes, all types of fittings(elbow,T…etc)and galvanized plugs to close the existing opening.
Supply and install metal rain water outlets dim. 4" with domical grade on roof with flange size 380mm by "Zurn,harmer",or equivalent.
Supply and install galvanized sheet metal air duct, as described, and to SMACNA standard. The price should include all wooden sleeves, all required hanger,supports,flexible connection near(AHU'S,fancoils), fire and volume dampers, and all required accessories. Price to include 1" thick fire insulation of 24 kg/m3 as per specifications.
Supply and install sch-40 black steel pipe1/2" with insulation("Anabid" sleeves 19mm thick wrapped with plastic fabric secured with sheet metal strap),threaded jointing, running along or are within partition or ducts. The price includes all fasteners, supports and hanging parts as per specifications, drawings and the approval of the Engineer.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
23
Item Description Unit QTY Unit Rate
18.13 M 650
18.14 UNIT 4
18.15 Supply and install bronze gate valve 1" by" Crane" or equal. UNIT 2
18.16 Ditto, but 11/4". UNIT 2
18.17 Ditto, but 11/2". UNIT 4
18.18 Ditto, but 2". UNIT 10
18.19 Ditto, but 5". UNIT 2
18.20 UNIT 2
18.21 Ditto, but 4". UNIT 5
18.22 Ditto, but 5". UNIT 2
18.23 Ditto, but 6". UNIT 2
18.24 UNIT 2
18.25 Ditto, but 4" . UNIT 2
18.26 Ditto, but 5". UNIT 2
18.27 UNIT 3
18.28 UNIT 2
18.29 Ditto, but 2" ,threaded. UNIT 2
18.30 Supply and install Pressure regulating valve for 2". UNIT 2
18.31 Ditto, but for 3". UNIT 2
18.32 UNIT 4
18.33 Ditto but pressure gauge. UNIT 10
18.34 UNIT 1
18.35 Ditto, but 4". UNIT 1
18.36 Ditto, but 2" . Crane UNIT 2
18.37 UNIT 4
18.38 Ditto, but 12"*12". UNIT 8
Supply and install Galvanized sheet metal protection 0.7mm, on insulated piping and fittings of various diameters.
Supply and install flexible Connection for various pipe diameters(4"-6") by "Tozen" or equal.
Supply and install butterfly valve 3" with flange and opposed flange by" Hakohav" or equal.
Supply and install regulating bronze globe valve 2" by "Crane" or equal.
Supply and install 3- way modulating valve 1" , including sensor, transmitter and actuator(24V) and thermostat( on -off ,3 speeds) by "Landys & Gear" or equivalent complete with all electrical works needed(material, labor).
Supply and install non-return valve, 3" dia., spring loaded solid disc, by "Hakohav" or equivalent with flanges and counter- flanges, and all required fittings.
Supply and install thermometer 4" on water pipe , by "Kobold" or equal including ball valve 1/2"for mounting and all preparation work.
Supply and install Water filter, 6" dia. "Hakohav" or equal with flanges and counter-flanges.
Supply and install cold forged Aluminum 4-way ceiling diffuser 6"*6" with volume damper, by "Cooling Industries" or equally equivalent.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
24
Item Description Unit QTY Unit Rate
18.39 UNIT 15
18.40 Ditto, but 14"*10". UNIT 3
18.41 Ditto, but 14"*12". UNIT 3
18.42 Ditto, but 24"*18". UNIT 4
18.43 Ditto, but 30"*8". (Provisional) UNIT 3
18.44 UNIT 4
18.45 Ditto, but FC2. UNIT 6
18.46 Ditto, but FC3. UNIT 1
18.47 UNIT 2
18.48 UNIT 1
18.49 L.S 1
18.50 UNIT 1
Supply and install return grill, exhaust grill with volume damper size 8"*4" by "Cooling Industries" or equal.
Supply and install decorative vertical fan coil made by Carrier (France), Daikin (Japan) or equivalent, unit FC1 with cooling capacity shown on drawings, complete with painted plastic cover, washable air filter, 2 shut-off valves, drain pan, double deflection plastic grilles (manually operated) for the supply air and fixed deflection plastic grilles for the return air. The price includes thermostat (on-off ,3 - speed switch) by "Landys & Gear"or equal, and 3-way valve.The price should include also all electrical works needed (material, labor), connection with water lines and drainage.
Supply and install ducted horizontal fan coil made by Carrier (France), Daikin (Japan) or equivalent, unit FC8 without cover with cooling capacity shown on drawing, complete with plenum, aluminum mesh flat filter, drain pan, 2 shut-off valves and hangers. The price should not include thermostat. The price should include all electrical works needed (material, labor), connecting with water and drainage lines, price to include 3-way valve.
(Provisional) Supply and install complete air cooled chilling unit for 85 TR (same as installed in first stage) made by Carrier (France), Daikin (Japan) or equivalent, including condenser, screw type compressors, shock absorbers, accessories, all as described.
(Provisional) Connect the above unit with existing electric switchboard and the control including all material and wiring, cabling and labor.
(Provisional) Supply and install cooling/heating water pumps (same as installed in first stage) as described, by "Grundfos" or equivalent.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
25
Item Description Unit QTY Unit Rate
18.51 L.S 1
18.52 L.S 1
18.53 L.S 1
18.54 UNIT 1
18.55 (Provisional) Supply and install check valve 2'' UNIT 10
18.56 (Provisional) Supply and install Automatic Air Vent UNIT 4
18.57 (Provisional) Supply , install and connect flow switch UNIT 2
18.58 (Provisional) Supply and install pressure break valve for 1". UNIT 4
18.59 UNIT 1
18.60 UNIT 2
18.61 Ditto, but 6" made by Vortice or equivalent. UNIT 4
Total of Air Conditioning Works….carried to summary:
(Provisional) Connect the above unit with existing electric switchboard including all material, cabling, wiring and labor.
(Provisional) Supply and Install chiller Electrical switchboard to be weatherproof including controling,all material and labor. All as per the approval of the Engineer.
(Provisional) Supply and Install pumps Electrical switchboard to be weatherproof including controlling, all material and labor. All as per the approval of the Engineer.
(Provisional) Supply and install hermetic expansion tank 50 lit type Reflex, Elbi or equivalent.
(Provisional) Supply and install floating concrete base with iron profile frame, spring type shock absorbers for pumps as described.
Supply, install and connect in line exhaust fan unit 8" as per vortice or equivalent. Price includes propper connection with the duct system from both sides as per specifications and connection with electrical power and control as per the approval of the Engineer.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
26
Item Description Unit QTY Unit Rate
19 Mr 70
20 Medical Gas Supply:
20.1
20.1.a ½ inch O.D. MR 90
20.1.b 5/8 inch O.D. MR 250
20.1.c 7/8 inch O.D. MR 280
20.1.d 1 3/8 inch O.D. MR 100
20.1.e 1 1/8 inch O.D. MR 130
20.1.f 1 5/8 inch O.D. MR 30
20.2 Supply and Installation of Area Valves Control Boxes:
NO. 1
Supply, install, and test Black steel gas pipes 1/2" diameter coated with extruded Polyethelene,shrinkable sleeves at threaded joints. the line to be laid at 90 cm from ground level. Price to include the excavation and backfilling with 20cm sand around the gas line, compacted base coarse and asphalt.
Copper pipes type (L) degreased medical oxygen compatible seamless type. The pipes must be cleaned and treated for medical gas usage including capping the ends of each pipe to ensure that no foreign bodies, dust, or vapors affect the interior of the pipes. The copper pipes must meet the international standard.
ASTM B-280 and to be cleaned for medical usage (degreased) according to CE 0473. Price includes proper isolation for piping under plastering and in penetrations, hangers, brackets, fasteners, etc.., as well as various fittings and accessories needed to complete the works as shown on drawings and as per specifications. Price also includes proper flushing of the entire piping network using Nitrogen or Medical Compressed Air.
Recessed area valve control box for medical oxygen, medical compressed air and vacuum. Including 3 full-port 3-parts NIBCO shut off valves which controls the supply of gases or vacuum through the pipelines, and line pressure and vacuum gauges. The valves diameter varies between 15 up to 35 mm, as per drawings. The area valves control boxes should also include an emergency external supply port, equipped with disk and clutch mechanism for quick plug-in connection of the emergency external supply source. The front should be made of labeled transparent polycarbonate flexible unbreakable cover to ease access in emergency situation, all as per Silbermann or equally approved
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
27
Item Description Unit QTY Unit Rate
20.3 Supply and Installation of bed head units:
20.3.a NO. 2
The bed head unit is equipped with the following services:
One oxygen outletOne compressed air outletOne vacuum outlet2 electrical sockets, Main line2 electrical sockets, coded-UPS lineone potential grounding socketindirect lightdirect lightdirect light (2 PL BIAX lamps)cut-off switch for direct / indirect lightsone telephone socket
preparation for nurse call socket
20.3.b Same as item 20.3.a, but for two beds NO. 3
20.3.c Same as item 20.3.a, but for three beds NO. 7
20.4NO. 1
Total of Medical Gas Supply…carried to summary:
Factory-preassembled Bed head unit for one bed, according to CE-0473, EN-46001, ISO 9001
Encompassing extruded aluminum duct system, with four cavities, three of which are directly accessed using snap-on covers. Supplying electrical and lighting service, as well as medical gas service. The gas outlets should be installed in a separate compartment, The number of electrical circuits, apart of the low voltage circuit, should be three: main line power circuit, UPS power circuit, and lighting circuit, each connected to a separate terminal at the main special electrical connection compound in the bed-head unit.
The Price should include hanging rail and suction bottles bracket, complete interior wiring, cabling, piping, insulating, etc. for complete installation.
The contractor must provide detailed schemes prior to supply and installation, supported with allr required conformities to standards, to be approved.
Supply and installation of Local Area Pressure and Vacuum Alarm Box:
local audio-visual pressure alarm box for medical oxygen, medical compressed air and vacuum to indicate pressure and vacuum failures by means of green LED, red LED, audio buzzer and pressure or vacuum gauge for each gas, as well as shut-off valves for each gas or vacuum, operated by means of one central PC card (microprocessor card) and pressure/vacuum switches for each gas, recessed type with anodized aluminum panel.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
28
Item Description Unit QTY Unit Rate
Section III - Electrical Works
22 Electrical Points:
a
b
22.1 Comp. 100
22.2 Ditto but for emergency lighting point Comp. 20
22.3 Comp. 40
22.4 Ditto but for fan coil units Comp. 15
22.5 Ditto as item 22.1.03 but double socket. Comp. 20
22.6 Ditto as item 22.1.05but with water proof double socket. Comp. 10
22.7 Ditto as item 22.1.03 but with water proof cover. Comp. 10
22.8 Comp. 2
22.9 Comp. 8
22.10 Comp. 5
22.11 Comp. 11
Note: All materials and accessories to be used shall be according to the Approved Manufacturer List attached to the tender Documents, or equally approved.
Cost of Electrical points shall include cost of connections electric supply from electrical switchboard to first point in circuit is included in the price of that point (by means of cable or leads in conduit).
Conduit and wires or cables to the points by means of or self-extinguishing conduit and cables, as req.
Supply, install and connect standard lighting point (internal or external) embedded in concrete slabs or above false ceiling. Cost of the point shall include 16 mm diameter conduit or trunk, 1.5 sq.mm cross-section leads or cable, lighting switches (single , double, two way or push button), outlet for luminary with junction box and terminals.
Supply, install and connect 16A wall socket points. Cost of point shall include 16 mm dia.conduit or trunks, 3x2.5mm2 leads or cables and (16 A) wall socket .
Supply, install and connect three-phase (5x16) A, single-circuit wall socket point, to include a 23 mm diameter conduit or trunk, (5x2.5) sq.mm cross section leads or cables and a (5x16) single-circuit wall socket accessory .
Supply, install and connect Intercom connection point (Price includes 16 mm diameter conduit with a standard Intercom cable, leading from point to the Intercom section in LV box).
Supply, install and connect Public Address System connection point (Price includes 16 mm diameter conduit with cable, leading from point to the LV box to the nearest point).
Supply, install and connect Fire Alarm connection point (Price includes 16 mm diameter conduit with cable, leading from point to the LV box to the nearest point).
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
29
Item Description Unit QTY Unit Rate
22.12 Comp. 9
22.13 Comp. 94
22.14 Comp. 9
22.15 Comp. 9
22.16 Comp. 11
22.17 Comp. 15
22.18 Comp. 1
22.19 No. 25
22.20 No. 12
22.21 No. 12
Supply, install and connect TV connection point (Price includes 23 mm diameter conduit with cable, leading from point to the LV box).
Supply, install and connect Nurse Call point (Price includes 16 mm diameter conduit with cable, leading from point to the nurse call station).
Supply, install and connect computer outlet point (Price includes 16 mm diameter conduit with pull wire, leading from point to the nearest HUB in the nearest LV box).
Supply, install and connect telephone socket point in 23 mm conduit including 23 mm diameter conduit from nearest telephone cabinet to accessory output in junction box, standard socket telephone accessory, and standard 2x2x.5mm2 telephone lead, inserted from cabinet to accessory including connection at both ends.
Supply, install and connect point for thermostat including16 mm diameter conduit installed on one side near socket for fan coils and termination with a suitable box on other side at thermostat output. 3 mm thick Nylon draw-string shall be inserted inside conduit.
Supply, install and connect 6 sq. mm grounding point - to include a 16 mm diameter conduit, connect at one end to grounding bus-bar in nearest switchboard, and at other end to grounded element (air-conditioning ducts, acoustic ceiling, alum. Partitions etc.
Supply, install and connect emergency push-button point, to include a 16 mm diameter conduit, (3x1.5) sq.mm cross-section leads, and a dual contact emergency push-button installed in a box with frame, transparent plastic cover to be broken in case of emergency, and engraved Bakelite "sandwich" type sign, per plan (box such as TELEMENIA model ZAS-E25).
Supply, install and connect point for bed head units including 3x2.5mm2 NYY cable and 23mm dia conduit from electrical switchboard to BHU junction box with all required accessories and materials.
Supply, install, and connect point as above, but by a 3x1.5 sq.mm NYY cable and16mm dia conduit.
Supply, install and connect point as above, but by a 6 sq.mm cross-section grounding lead and 23 mm diameter conduit.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
30
Item Description Unit QTY Unit Rate
22.22 No. 12
22.23 No. 10
22.24 No. 30
Total of Electrical Points….carried to summary:
23 Conduit, Rigid Piping and Excavation Works:
23.1 23 mm diameter. ML 50
23.2 29 mm diameter. ML 50
24 Cables:
24.1 5x16 sq.mm cross section. M.L. 60
24.2 5x10 sq.mm cross section. M.L. 210
24.3 5x6 sq.mm cross section. M.L. 100
24.4 5x4 sq.mm cross section. M.L. 100
Total of Cables ……carried to summary:
Supply, install and connect point as above, but for communication, by a 23 mm conduit diameter conduit.
Re-route existing power lines at the building to be connected to the new distribution board ( DB-2), the works shall include all necessary materials, cables, conduits, trunks and all needed civil works.
Ditto as above but for general low voltage installations at the building
Supply, install and connect Self-extinguishing type plastic conduit, processed over or under plaster or inside castings, including junction boxes, unions, connectors, etc. including galvanized draw-strings, ready for use (for works not included in points).
Total of Conduit, Rigid Piping and Excv…..carried to summary:
Supply, install and connect XLPE non-armored type thermoplastic copper cables, including insertion into conduit or attachment to structural elements or laying in ductwork, including all associated materials, insulation materials, unions, Ladders, Z Constructions, cable shoes, and connection of cable at both ends.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
31
Item Description Unit QTY Unit Rate
25 Structural Elements, Cabinets and Ductwork:
25.1 20/10 cm. M.L. 45
25.2 40/10 cm. M.L. 45
25.3 Ditto same as item 25.1 but 20/10 with cover M.L. 60
26 Grounding:
26.1 L.S 1
Total of Grounding …..carried to summary:
27 Electrical Switchboards:
a.
b.
c.
d.
e.
g.
27.1 Distribution Board(DB2) Unit 1
Total of Electrical Switchboards…..carried to summary:
Supply, install and connect Prefabricated perforated cable tray mounted on walls or attached to ceilings. Price to include all reinforcing and attaching hardware, structural elements, brackets construction, covers were required and hangers etc.
Total of Structural Elements, Cabinets….. carried to summary:
Supply, install and connect Complete lightning system including exciter,120mm copper conductor, 3-earth electrodes ,earth pit and all required materials and accessories needed to complete the job as specifications and Engineer instructions.
Supply, install and connect the electrical switchboards to the site, including all associated materials and labor, as described in the technical specifications.
Cabinets with no access from the rear, made up of transparent polycarbonate cells, or sheet-metal cabinets with a 25% surplus space.
The switchboards are to be placed on the floor, in a niche against the wall.
Main supply lines enter from the switchboard bottom, top or side, while outgoing lines exit the switchboard from both its bottom and top sides.
Price to include all structural elements required in order to install the switchboard, including bus-bars, terminals, wiring, bolts, clamps, etc. and for the equipment listed below.
Prices for supply, installation and connection of various accessories including all associated labor and materials such as bus-bars, terminals, wiring reinforcements, mounts, engraved "sandwich" type identification plates, etc. including connection to ma
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
32
Item Description Unit QTY Unit Rate
28 Luminaries Supply and Installation:
a.
b.
c. All lamps shall be of the energy-saving type (18,36, 58 Watts).
28.1 Type (A) 2x36W fluorescent light fixture Prismatic type. Unit 20
28.2 Type (AE) Ditto as A but with emergency charger. Unit 14
28.3 Type (B) 2D 16W Globe with opal diffuser. Unit 18
28.4 Unit 1
28.5 Type (G) 5W Recessed night light corrosion proof IP65. Unit 10
28.6 Unit 6
28.7 Unit 7
28.8 Type (KE) Ditto as K but with emergency charger. Unit 8
28.9 Unit 5
28.1 Unit 3
28.11 Unit 3
28.12 Type(PE) as P with 3 hrs emergency kit. Unit 2
Total of Luminaries Supply…carried to summary:
Supply and installation of Lighting fixtures as described below, including all necessary accessories, required in order to light it with lamps and electronic starter, complete.
It is hereby stressed that the client is entitled to furnish all or part of the luminaries through other supply sources.
Type (E) 1 x 8W fluorescent emergency exit sign luminaries with white steel body, for maintained emergency lighting of 3 hour duration, legend panels (3) included (down, left and right).
Type (J) Ceiling mounted lighting 2XPL-L 11 lamp compact fluorescent with opal diffuser controller IP20.
Type (K) 2x36W, fluorescent lighting fixture, ceiling mounted with prismatic diffuser ( Internal primes) IP20.
Type (L) Down light, recessed in false ceiling, with PL-C 13 W compact fluorescent energy saving lamp, cast aluminum cover and ring silver ( frosted) aluminum reflector, IP20.
Type (M) 2x36W, fluorescent lighting fixture, ceiling / pendant. Body of grey fiber-glass reinforced polyester, prismatic polycarbonate diffuser, IP54.
Type (P) 4x18W, fluorescent lighting fixture, recessed in false ceiling, with prismatic diffuser ( Internal primes), IP20.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
33
Item Description Unit QTY Unit Rate
29 Nurse Calling System:
29.1 Master station 30- call master. Unit 1
29.2 Reset button. Unit 11
29.3 Bedside call switch. Unit 31
29.4 NBY-1A metal jack. Unit 31
29.5 Corridor lamp. Unit 11
29.6 Ceiling mount 180mm O(7-1/8"O) NB-L Unit 11
29.7 Moisture resistant pull cord switch. Unit 11
29.8 Power supply for the master station. Unit 1
Total of Nurse Calling System…carried to summary:
30 Fire Alarm System:
30.1 Job 1
30.2 Manually operated alarm call point . Unit 5
30.3 Interior Alarm horn for fire detection system . Unit 2
30.4 Ionization smoke detector . Unit 5
30.5 Ionization heat detector . Unit 1
Total of Fire Alarm System Carried to Summary:
Note: All equipment items for the nurse- calling system shall be according to the approved manufacturer list.. The work to include the supply of the equipment specified, installation of same, connection, wiring, commissioning and all other details, as specified in the technical specification and drawings.
Supply install and connect complete in place and in an operable manner the fire alarm system. The work is to include the supply of the equipment specified, installation of same connection, wiring, cables, commissioning and all of the details and connecting to the existing system as specified in the technical specifications and drawings.
Maintenance work for the existing fire alarm panel, this includes changing any required equipments in side the panel and doing any required repairs for the existing lines of the existing points including changing the glass covers of the broken break glass points.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
34
Item Description Unit QTY Unit Rate
31.00 Intercom System:
31.1 Hands free master station . Unit 1
31.2 Power supply adaptor . Unit 1
31.3 Door phone adaptor . Unit 1
31.4 Door station . Unit 1
31.5 Power supply adaptor . Unit 1
31.6 Door release . Unit 1
31.7 AC transformer for door release . Unit 1
31.8 Digital keypad . Unit 1
31.9 12V AC power supply transformer Unit 1
Total of Intercom System carried to summary:
32 Public Address System:
32.1 Unit 10
Total of Public Address System carried to summary:
33 Telephone System:
33.1 Job 1
33.2 Job 1
Total of Telephone System carried to summary:
Note: All equipment items for the intercom system shall be according to the approved manufacturer list.. Work is to include the supply of the equipment specified installation of same, connection, wiring, commissioning and all other details, as specified in the technical specifications and drawings.
Supply, install, test and commission a public address system, the system shall be according to the approved manufacturer list, including all required connections with the existing system of the Hospital including all required cables and conduits complete ready for work.
9/6 watt ceiling loudspeaker, 8” round with metal grille, screw mount.
Supply install and connect main telephone cables from telephone exchange to the LV2 boxes. Rate to include 2 NO's. 25 pair cables, conduits, terminal blocks and all accessories as specified in the technical specification and drawings.
Adding two internal cards type SLC8 for the existing Alcatel telephone exchange.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
35
Item Description Unit QTY Unit Rate
34 LV Boxes:
34.1
LVB2 Approximate dim. (80x60x25) cm No. 1
Total of LV Boxes carried to summary:
Supply install and connect the following LV boxes. Rate to include all required materials, conduits, wires, cables and accessories manufacturing from galvanized sheet metal sheets, painted with the same color of the switch boards all as specified.
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
36
Amount
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
37
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
38
Amount
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
39
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
41
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
42
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
43
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
45
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
46
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
47
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
48
Amount
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
49
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
51
Amount
0.00
0.000.000.000.000.000.00
0.00
0.00
0.000.00
0.00
0.000.000.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
52
Amount
0.00
0.00
0.00
0.000.000.000.000.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
53
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
54
Amount
0.00
0.000.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
55
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
56
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
57
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
58
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
59
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
60
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
61
Amount
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
62
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
63
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
64
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
65
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
66
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
67
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
68
Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor
69
Amount
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor 16 June 09
AMSEngineering Unit @ UNDP/PAPP
Summary of Part 1
Bill Description
Section I Civil Works Summary
1 Preparation Works
2 Concrete Works
3 Block work
4 Sealing Works
5 Carpentry and Metal Works
6 Stainless Steel Works
7 Plastering Works
8 Flooring and Covering Works
9 Painting Works
10 Aluminum Works
11 Stone Works
12 Suspended ceiling
13 Fixed Furniture
Total of Civil Works
Section II Mechanical Works Summary
14 Cold and Hot Water Supply System:
15 Waste and Drainage Systems:
16 Sanitary fixture and their Accessories:
17 Rainwater Drain Pipes:
18 Air Conditioning Works:
19 Gas System
20 Medical Gas Supply:
Total of Mechanical Works
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor 16 June 09
AMSEngineering Unit @ UNDP/PAPP
Summary of Part 1
Bill Description
Section III Electrical Works Summary
22 Electrical Points
23 Conduit, Rigid Piping and Excavation Works
24 Cables
25 Structural Elements, Cabinets and Ductwork
26 Grounding
27 Electrical Switchboards
28 Luminaries Supply and Installation
29 Nurse Calling System
30 Fire Alarm System
31 Intercom System
32 Public Address System
33 Telephone System
34 LV Boxes
Total Electrical Works
Total of Part 1 (Excluding VAT)
Discount %
Discount Amount
Net Total - Part 1 (Excluding VAT)
NET TOTAL SUM (in words ) :
SIGNED AND SEALED :
AUTHOURIZED PERSON :
TITLE :
SIGNATURE :
DATE :
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor 16 June 09
AMSEngineering Unit @ UNDP/PAPP
Summary of Part 1
Total
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 1: Construction of the remaining works at Alia Hospital 2nd floor 16 June 09
AMSEngineering Unit @ UNDP/PAPP
Summary of Part 1
Total
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
NET TOTAL SUM (in words ) :
SIGNED AND SEALED :
AUTHOURIZED PERSON :
TITLE :
SIGNATURE :
DATE :
Bill of Quantities
Part 2
Prepared By
June 2009
Rehabilitation of the X-ray Department and the Internal Medicine Ward at Hebron Hospital
Lamasat OfficeArchitects & Interior Designers
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
75
Item DESCRIPTION Unit QTY Unit Price
Section I - Civil Works1 Demolishing & Removal Works
1.1 M2 20
1.2 M2 230
1.3 M2 630
1.4 Careful dismantle and preserve the existing doors and frames. NO 48
1.5 M2 100
Total of Demolish & Removal Works carried to civil summary:
2 Block Works
2.1 Ditto for 10 cm block walls M2 240
2.2 Ditto, but for 15 cm block walls M2 60
Total of Block Works carried to civil summary:
The contractor shall visit the proposed site to familiarize himself with the required scope of work and the existing site conditions. Unit price shall include costs of the needed material and the workmanship which are required to complete the work. The price shall include costs for making the necessary temporary works to ensure the safety of the visitors of the functioning hospital and to protect the finished works rendered in the existing hospital. Price shall also include cost of hauling away the demolished material. The contractor shall preserve, protect and make the necessary works to maintain the existing electro-mechanical system to serve the functioning hospital. It shall be clearly understood that all salvaged materials and fittings are the property of the Hospital and must be handed over to the director of Hospital
Demolishing and removal of portions of existing concrete walls to make new openings or enlarge existing opening. The unit price shall include dismantling and preserving the existing doors or windows. For details refer to drawing No. A03. All as directed by the Engineer
Demolishing and removal of existing block, gypsum or wood partition walls. The unit price shall include dismantling and preserving the existing doors and windows. For details refer to drawing No. A03. All as directed by the Engineer
Demolishing and removal of the existing tiles. The unit price shall include dismantling the panel tiles. All as directed by the Engineer.
Chipping off and removal of existing plaster in areas specified by the Engineer and make ready to receive new plastering or tiles.
Supply and construct hollow concrete block (type A, compressive strength 35kg/cm2) walls using cement and sand mortar (1:4) . The price includes cost of cutting, bonding, anchoring, control and expansion joints, utilities openings, dummy columns and reinforced concrete lintels (of 4 steel bars 12mm dia and 8mm stirrups@ 20cm c/c) over doors and windows opening and accross the whole width of the wall. For more details refer to drawing No A04,A11.
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
76
Item DESCRIPTION Unit QTY Unit Price
3 Plastering Works
3.1 For walls, columns,..etc. M2 320
3.2 Two coats plaster to receive ceramic wall tiles M2 110
Total of Plaster Works carried to civil summary:
4 Tiling Works
4.1 M2 630
4.2 M2 640
4.3 WC & kitchen tiles
4.3.1 M2 130
4.3.2 M2 160
Three layers of internal plastering 20mm thick composed of a bond coat, base coat, and finish coat, including plaster stops, corner beads, casing beads, metal laths, scaffoldings, shuttering, bonding agents and all requirements as specified.The surfaces to be plastered are to be dashed with white cement & sand mix 1:1 to from a key, allowed to harden before applying two coats: the first coat mix. 1:1:3 (cement: sand: fine aggregate) and the second coat mix 1:4:1 (cement: sand: lime). The unit rate includes furnishing and installing of reinforcing wire mesh 200mm wide to all chases of electro mechanical works and to junctions of block work & concrete surfaces.
The contractor shall, when pricing this bill, take into consideration and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract.Samples should be submitted for engineers approvalThis item includes spacers
Supply and install 30x30x1cm Turkish "TOBRAC"or equivalent floor tiles similar to existing or equally approved. Rate includes 30cm x 10cm x 1 cm skirting, 3 cm cement sand mortar (1:3 ), sand fill materials, cuttings, fittings, trims, grouting with white cement and polishing, all in accordance with the specifications and applicable Standards. For more details refer to drawing No. A06.
Corridor Walls supply and installation of 200x200x6mm high quality ceramic tiles (Negev or equally approved) laid on 10 mm thick mortar backing (1:1:4). Rates include roughening of walls and all needed preparation work to receive tiles, 2mm thick stainless steel angles to be installed on corners as per the drawings. For more details refer to drawing No. A16.
To walls: 200x200x6mm high quality glazed white ceramic tiles laid on 10 mm thick mortar backing (1:1:4). For more details refer to drawing No A16.
To floor:200x200x8mm high quality no-split ceramic tiles laid on 30mm thick mortar bed (1:3) on sand bed oraggregate as needed. For details refer to drawing No A06
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
77
Item DESCRIPTION Unit QTY Unit Price
4.4 M.R 40
Stair treads:Supply and install 3cm thick, 35cm width and 150cm length polished local marble ( Sour Moeen or equally approved ) round edge nose treads, including sand bed underlay, bedding and jointing in white cement and sand (1:4) and pointing in white or colored approved pointing material cut to size as shown on drawing No. A17 and as per the engineer's instructions. The rate includes an edge piece for water stop.
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
78
Item DESCRIPTION Unit QTY Unit Price
4.5 M.R 40
4.6 M.R 20
Total of Tile Finishing carried to civil summary:
5 False Ceiling Works
5.1 M2 60
5.2 M2 260
5.3 M2 410
Total of False Ceiling Works carried to civil summary:
Stair risers:Supply and install 2cm thick and 150 cm length polished local marble( Sour Moeen or equally approved ) risers, bedding and jointing in white cement and sand (1:4) and pointing in white or colored approved, pointing material cut to size as shown on related details and as per the engineer's instructions & drawing No A17.
Stair case skirting:1.5cm thick variable height polished local marble ( Sour Moeenor equally approved ) skirting bedding and jointing in white cement and sand (1:4) and pointing in white or colored approved pointing material cut to size as shown on drawing No A17and as per the engineer's instructions:
The contractor shall, when pricing this bill ,take into consideration and allow for the costs or expenses of all requirements stipulated in the preambles drawings and technical specifications of the contract.
Supply & install non perforated acoustical ceiling made of formed galvanized sheet metal trays for bathrooms and wet areas. The metal trays should be of 0.8 mm thick 45mm high coated with “pvc”200 microns thick. For details refer to drawing A05.
Supply & install perforated metal sheets (20%-25% perforation). The metal trays should be covered with continuous and uniform manner of rock wool mats 25 mm thick of 25 kg\m³ density. The rock wool mats shall be wrapped by inflammable polyethylene sacks,(in accordance with the safety regulations and standards). For details refer to drawing A05.
Dismantling, cleaning and re-installing existing false ceiling panels. For details refer to drawing A05.
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
79
Item DESCRIPTION Unit QTY Unit Price
6 Painting Works
6.1 M2 1340
6.2 M2 190
6.3 M2 3000
6.4 M2 80
6.5 M2 320
6.6 Supply and apply oil paint for metallic surfaces "Superlac" . M2 66
Total of Painting Works carried to civil summary:
The contractor shall, when pricing this bill, take into consideration and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract, including scrubing of old paint where needed. The contractor should allow in his pricing that the engineer will use as many different colors or combination of colors to meet an approved color scheme.*Colors of paint shall be coordinated with the engineer for approval.*The Contractor shall prepare 1 m2 samples for approval by the Engineer*All painting material shall be made by Tambour or equally approved
Supply and apply one layer of emulsion paint to ceiling and walls above suspended ceiling level and where instructed by the engineer.
Supply and apply one coat of primer fill and three coats of policed paint for plastered walls and ceiling
Supply and apply one coat of primer fill, two coats of putty and three coats of emulsion paint for plastered walls
Supply and apply oil paint for wet areas composed of primer fill ,two coats of putty, one coat of under coat, and three coats of oil paint.
Painting of walls with “Acrinol” by Deluxe or equally approved for mildew and fungus protector
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
80
Item DESCRIPTION Unit QTY Unit Price
7 Carpentry & Joinery
Note: wood works include painting, varnishing, polishing oiling & the like.
7.1 Wood Doors & Frames:
7.1.1 Doors With Half Glazed:
this item includes sand plast glass panels for doors.
Type DR1 overall size 210x140cm NO 1
7.1.2 X-Ray Rooms Doors
a Type DR2 overall size 210x120cm NO 1
b Type DR3 overall size 210x110cm NO 1
7.1.3 WC Doors
this item including 12 cm height aluminum kick plate.
a Type DR4 overall size 210x70cm NO 8
b Type DR12 overall size 210x70cm NO 9
7.1.4 Single Doors
a Type DR5 overall size 210x80cm NO 1
b Type DR6 overall size 210x85cm NO 1
c Type DR7 overall size 210x90cm NO 3
d Type DR8 overall size 210x100cm NO 1
e Type DR9 overall size 210x110cm NO 1
f Type DR10 overall size 210x115cm NO 2
g Type DR11 overall size 210x135cm NO 1
h Type DR13 overall size 210x80cm NO 3
i Type DR14 overall size 210x95cm NO 3
j Type DR15 overall size 210x100cm NO 1
k Type DR16 overall size 210x110cm NO 9
l Type DR17 overall size 210x115cm NO 1
Fabricate, supply and fix in position the following wooden doors, flush faced on both sides with (PVC) laminate complete with and including standard pressed steel door frame fill in all voids with mortar grout, door closer, extruded aluminum kick plate, bolts, door locks by "Yale" or equally approved, door stops, heavy duty hinges, fix glass panels etc. complete as per details and door finishing schedule. (3 Master keys shall be provided).
Supply and fix in position wooden doors for X-ray rooms comprising hard wood edgings (ZAN) 75x32 lead lining 5mm thick both sides, plywood face for both sides 1mm thick (PVC) laminate, 5mm thick gypsum board both sides, softwood core, extruded aluminum kick plate, complete with and including pressed steel frame filled with mortar grout, door closer, bolts, door locks by "Yale" or equally approved, door stop, heavy duty hinges, sealant, etc. as per finishing door schedule (Master key shall be provided).
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
81
Item DESCRIPTION Unit QTY Unit Price
7.2 kitchen cupboards
7.2.1 Top cupboard unit
NO 3
7.2.2 Bottom cupboard unit
NO 3
7.3 Nurses Station desk
M.R 3
7.4 Wood Frame for Reception Desk
M.R 25
7.5 X-Ray Control Booth
M2 5
7.6 Wall Protector
M.R 200
Total of Carpentry & Joinery Works carried to civil summary:
Supply And install plywood kitchen cupboard Overall size 220 x 30 x 60 cm. consisting of three double aluminum doors ,17 mm plywood shelves both sides covered with Formica laminate Complete with, ironmongery, hardware, and painting. All according to drawing A14& engineer instructionsSamples of Formica to be approved by the engineer
Supply And install marble kitchen cupboard Overall size 220 x 60 x 90 cm. consisting of two double aluminum doors ,17 mm plywood shelves both sides covered with Formica laminate and a set of four aluminum face drawers, laminate cover high quality Formica ). Complete with, ironmongery, hardware, and painting. including granite counter top "Tiger eye" with top& bottom skirting, beads, polishing, routings, jointing…etc and all preparatory woks for the installation of the required sink and sanitary fixtures. Amples of Formica to be approved by the engineer All according to drawing A14 & engineer instructions.
Fabricate, supply and install wooden L shape desk as per drawings and specifications, for details refer to drawing A15.
Fabricate, supply and fix in position solid zan wood frame, for details refer to drawing No A13.
Supply and fix in position wooden control booth for X-ray room comprising lead lining 5mm thick both sides, plywood face for both sides , 11mm thick gypsum board both sides, this item including 40*40*1 cm lead- glass panel for window.
Supply and install a wooden wall guards cut to size according to the site requirements as made by (SPM ) or equally approved by the engineer including all necessary fittings. The color will be selected by the Engineer. For details refer to drawing No A 21.
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
82
Item DESCRIPTION Unit QTY Unit Price
8 Insulation Works
Fluid Applied Waterproofing:
8.1 Internal wall insulation:
for details refer to drawing No. A12. M2 25
WC & kitchens floor insulation
8.2 M2 80
8.3 M2 500
8.4 M2 50
8.5 NO 15
Total of Insulation Works carried to civil summary:
9 Glass Works
9.1 Sekurit Glass
9.1.1 Sekurit Glass Panels
M2 12
9.2 Sand Glass Sekurit Panels
M2 1.5
All finishes shall be measured superficially net unless otherwise stated clearly.Triangular shaped fillets and cement and sand lining to gutters shall be measured in linear meter, unless otherwise stated clearly.Rates for cement and sand work shall include for :Hacking concrete, applying cement slurry or raking outjoints of blockwork to form key. Application to any surface. Finish to surface, to falls, cross falls and currents forming bays including joints. Finish to edges and arises. Making good around steel sections, pipes, tubes, bars, brackets, outlets, and the like.Measurement for water proofing shall be for sectional roof area only.Rates for waterproofing and roof sheeting shall include for: Preparation of surface, cuting in edges. overlaps, priming over parapets and stub columns including forming groove to receive edge of elasticized bitumen membrane and sealing with elastic sealer. Side and end laps, fittings including bolts, hook bolts, screws and washers, Sheets of any width or length .
Supply and apply three coats of hot asphalt layers (25\75) at rate of 500 g/m2 for each layer, reinforced by two layers of fiberglass and a prime coat GS474 .all according to the manufacture and to the engineer’s approval
Supply and install one layer of water proofing membrane of bitumen rolls 5mm thick, covered with white gravel, "Pazkar"or equally approved. The unit price shall include cost of a prime coat GS474 at a rate of 0.25 kg /m2 and all sheets flashing, including all the necessary material and workmanship, as specified.This item includes dismantling and removing the existing waterproofing material and cleaning the surface on the existing roof (where needed and as directed by the engineer ) to allow for the new waterproofing works.
Repair and maintenance of certain areas of the existing waterproofing. The unit rates shall include cleaning of the existing waterproofing surfaces and supply and installtion of waterproofing material.
Repair and maintenance of small patches (appox. 100cmx100cm) of existing waterproofing. This item to be measured by the number of patches repaired.
Supply and install 100 cm hight,1cm thick high quality sekurit glass panels, including all accessories. For more dimensions & details refer to drawing A13,A14.
Supply and install sand plast 1cm thick sekurit glass panels for door. For more dimensions & details refer to drawing A14.
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
83
Item DESCRIPTION Unit QTY Unit Price
Total of Glass Works carried to civil summary:
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
84
Item DESCRIPTION Unit QTY Unit Price
10 Metal work10.1 ALUMINUM
10.1.1 WindowsFor windows details refer to drawing A18.
NO 3
10.1.2 DoorsEmergency Door
NO 1
10.2 Metal Cupboards
NO 14
10.3 Wall Signssupply & install wall signs.
a size 25x12 cm NO 40
b size 40x15 cm NO 5
10.4 Curtain Tracks.
a Supply & install L- shape tracks for curtains around beds, 420cm long. NO 12
b Ditto, but 300 cm long (straight). NO 5
10.5 Steel -Wood Handrail
M.R 8
Total of Metal Works carried to civil summary:
All the profiles must be NAPCO 7700 for sliding windows, and NAPCO 2200 for fixed windows or equally approved.Fabricate supply and fix in position the following anodized aluminum windows & doors, complete with double glazing with 6mm thick clear glass for both inner and outer panels similar to existing windows, and 12mm thick air space filled with argon gas, and butyl framing rubber, perforated aluminum frame and polysulphide mastic between aluminum frame and glass, including aluminum woven mesh fly screen, all necessary frames, sub frames, fixing, fittings, accessories weather stripping and hardware as per specifications* Shop drawings & samples to be approved by the Engineer.
Type W1 overall size 728x60cm NAPCO 2200 or equivalent .Complete with frame, glazing, mastic sealant, ironmongery and hardware.
Type door ED1 overall size 228x110cm.Thickness 52 mmWeight =29 kg/m². Complete with galvanized frame, glazing, mastic sealant, paint of door and frame according to engineer instructions and approval, ironmongery and hardware and including 15mm glass vision panel for more details refer to drawing No A18
Supply and install painted metal cupboards overall size 200x47 x60 cm including all accessories all as per drawings and details, for details refer to drawing No A15.
Aluminum plaques in Arabic & English with a special solvent proof,weather and temperature resistant fixed on the door or the wall .The price include labor work and all fixing materials.
All the profiles shall be of Clickeze, InPro Podiatric or equally approved. This item includes overhead metal curtain track, track accessories OPTITRAC (or equivalent), extruded aluminum cubicle track with clear anodized aluminum or white baked acrylic enamel finish. Aluminum shall be 6063-T5. Dimensions: height 3/4" (19.05mm), width 13/8" (34.93mm).
Fabricate and supply and fix in position handrail for emergency stair case as per detail No A17 and Engineer approval. This item includes wood panels and all accessories for fixing in position.
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
85
Item DESCRIPTION Unit QTY Unit Price
11 Sand-blasting Works
Sandblast Cleaning of stone facades M2 1000
Total of Other Works carried to civil summary:
This item includes cleaning of existing stone facades with dry abrasive material forced by compressed air from tank through hose and nozzle. Cleaning material must be dust-free and abrasive. Material size shall be approved by engineer. Air pressure delivered by compressor to blasting tank may range from 40 lbs. to 100 lbs. per square inch according to the first test cleaning which shall approved by the engineer. Lightly sanded, coated, slurry, should not be cleaned by sandblasting.
"pre-cleaning" process includes removing all large mortar particles with hand tools before blasting. Use wooden paddle, the rough edge of a brick, or metal scrape hoe. Chisels may be used if necessary to remove hardened mortar or concrete.
The contractor shall provide adequate protection for all non-masonry surfaces adjacent to work areas, Use plastic sheeting and duct tape to protect windows, doors, etc. If possible, painting, caulking, etc. should be done after sandblast operation is completed.
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
86
Item DESCRIPTION Unit QTY Unit Price
Section II - Mechanical Works12 SANITARY SYSTEM
12.1
12.1.1 size 2 inch diameter M.R 7512.1.3 size 4 inch diameter M.R 50
12.2
12.2.1 size 2 inch diameter M.R 90
12.3 NO 5
12.4 NO 2
12.5 NO 11
12.6 Ditto but floor drain size 4"/2" diameter NO 11
12.7 JOB 1
12.8 NO 30
12.9 NO 3
12.10 NO 22
Supply and install of UPVC, type Redi - Italy made or E.A, drainage pipes to floor drains or to existing sewage pipes with all required fittings", "T" etc. The price includes digging and plastering, incasing with concrete cover for underground pipes, connection to existing riser pipes as shown in drawings, and approval of supervisor engineer.
Supply and install of CPVC - Italy made, suspended and underground condensate drainage pipes from AC units to floor drains or to existing sewage pipes with all required fittings needed for installation. The price includes digging and plastering, concrete cover for underground pipes, hangers and supports for suspended pipes, as shown in drawings, and approval of supervisor engineer.
Supply and install Floor Clean Out 4"UPVC type Redi - Italy made or E.A, including chrome plated (sealed type) cover (15*15 cm) complete with connection to drain pipes as located in drawings , specifications and approval of supervisor engineer.
Supply and install of polypropylene DALLMER type 54 floor drain body with trap,rodding eye,DN 50 outlet, DALLMER grating KE 15
Supply and install 4" floor trap UPVC, type Redi - Italy made or E.A, include chrome plated screw type cover (15*15 cm) completed with connections to drain pipes as located in drawings, specifications and approval of supervisor engineer.
Dismantle all the existing sanitary fixtures with pipes networks (where required) in internal medicine ward and X-Ray Departments with all accessories and fittings as per engineer's instructions and keep safe in hospital store (where possible).
Supply and install fire glazed wall hung washbasin, white colour, of size 55*45 cm type Roca or E.A, complete with chrome plated mixer, type Hamat, 1/2" * 3/8" angle valves, supports, 2" waste outlet down to floor drain, plastic siphon trap, including connections to drain and water outlets, as shown in drawings, and approval of supervisor engineer.
Supply and install fire glazed kitchen sink, white colour, of size 55*45 cm type Roca, or E.A, complete with chrome plated mixer, type Hamat, 1/2" * 3/8" angle valves, supports, 2" waste outlet down to floor drain, plastic siphon trap, including connections to drain and water outlets, as shown in drawings, and approval of supervisor engineer.
Supply and install fire glazed wall mounted vitreous china water closets, white colour, type Roca or E.A, including recessed cistern type Schwab, complete with cistern, valves , fittings, solid seat and cover, toilet roll paper holder , chrome plated 1/2" stop angle valve of approved quality, chrome plated 13mm hose, including connection to drain and water outlets, plug, flexible pipe with the hand spray and all accessories for complete installation, all is according to drawings, and approval of supervisor engineer.
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
87
Item DESCRIPTION Unit QTY Unit Price
12.11 NO 3
12.12 NO 2
Total of Sanitary System Works carried to Mechanical summary:
13 WATER AND FIRE FIGHTING SYSTEMS
13.1
13.1.1 size 2" diameter M.R 1013.1.2 size 1 1/2" diameter M.R 4013.1.3 size 1 1/4" diameter M.R 11013.1.4 size 1" diameter M.R 3013.1.5 size 3/4" diameter M.R 30
13.2
13.2.1 size 2" diameter M.R 1013.2.2 size 1 1/2" diameter M.R 2013.2.3 size 1 1/4" diameter M.R 3013.2.4 size 1" diameter M.R 7513.2.5 size 3/4" diameter M.R 4013.2.6 size 1/2" diameter M.R 15
13.3
13.3.1 Collector 3/4" diameter (Unit is in collector openings) Open. 1013.3.2 Collector 1" diameter (Unit is in collector openings) Open. 66
13.4
13.4.1 80cm X 60cm NO 413.4.2 60cm X 60cm NO 2
Supply and install white glazed shower tray, white colour, type Roca or E.A, of size 90X90cm, complete with chrome plated mixers, type Hamat, plug and chain, 1.5m flexible hose with chrome lever handle and stand, and all associated water supply pipes, and brackets screwed to concrete or block work, sealing joint to worktop or wall with mastic sealant.
Supply and install water mixer for shower, type Hamat, with chrome lever handle and stand. Price includes connections to supply water pipes and all accessories needed to complete the job.
Supply and install SCH40 galvanized steel pipes (Seamless type) for domestic cold water and fire fighting systems, to be connected from the existing main supply suspended pipes in false ceiling up to copper collectors and fire hose cabinets, with all necessary fittings like valves, elbows ,tees, vents, of approved quality. The price include supports, hangers and dismantling the existing pipes (where required) as shown on drawings, and as follows:
Supply and install SCH40 galvanized steel pipes (Seamless type) for domestic hot water system, to be connected from the existing main supply suspended pipes in false ceiling up to copper collectors, with all necessary fittings like valves, elbows ,tees, vents, of approved quality. The price include 13mm vidoflex or Armaflex insulation rolled by plastic bonds, supports, hangers and dismantling the existing pipes (where required) as shown on drawings, and as follows:
Supply and install cold and hot water copper collectors, type Tieme or E.A with all necessary fittings, nipples, nuts, unions, brass fittings adapter, shut off valves on main and branch pipes.....etc. The price should include supplying and installing 16mm pexgol plastic pipes with its 25mm plastic conduits to be connected from the copper collectors openings up to location of sanitary fixtures outlets according to plans and engineer’s instructions.
supply and install metallic painted steel cabinets of approved quality, including cover with double doors for domestic water collectors. The cabinets should be recessed in walls and fixed on wooden frame constructed in the wall. The sizes of the cabinets are as follows:
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
88
Item DESCRIPTION Unit QTY Unit Price
13.5
13.5.1 6 kg Capacity NO 213.5.2 3 kg Capacity NO 3
13.6 NO 2
14 CENTRAL HEATING SYSTEM
14.1 JOB 1
14.2 SEC 380
14.3
14.3.1 size 1 1/2" diameter M.R 1514.3.2 size 1 1/4" diameter M.R 50
14.4
14.4.1 Collector 11/4" diameter (Unit is in collector openings) EYE 58
14.5 NO 3
14.6 Supply only pressure tank of 125 liters capacity, type Reflex or E.A. NO 1
Supply and install Halon Powder fire extinguisher cylinders, of approved quality. The price includes all accessories and fittings needed for installation and fixing on wall. The capacities of cylinders are as follows:
Supply and install 80*80*30 cm steel fire hose reel cabinet, 25mm diam., mounted on swinging reel, an angle isolation valve inside the cabinet, a jet nozzle with an incorporated cock, and 25m long textile hose. Each cabinet should be supplied with 3 kg powder fire extinguisher, as shown on drawings, and approval of supervisor engineer.
Total of Water and Fire Fighting System Works carried to Mechanical summary:
Dismantle all the existing central heating pipes networks and radiators distributed in all spaces and rooms in internal medicine ward and X-Ray Departments with all accessories and fittings as per engineer's instructions and keep safe in hospital store (where possible).
Supply, install and test cast iron radiator, type Chappee, or E.A , of size 68cm, 3 section in depth (68/3). The price includes all necessary fittings, i.e shutt off and control valves, vents, hangers, reducers, chrome nipples, gaskets, plastic covers on nipples and whatever to complete the job, all is according to specifications, drawings and approval of supervisor engineer.
Supply and install black steel of schedule 40 pipes for heating system, including all required insulation by vidoflex of 13mm thickness rolled by plastic bonds, sleeves, gate valves on branch pipes, automatic air vents, gav. hangers and supports, drain cocks with all required fittings and connections, all according to drawings, specifications and approval of supervisor engineer and as follows:
Supply and install copper collectors for central heating system, type Gaicomini or E.A, with all necessary fittings, nipples, nuts, unions, quick shut off valves on main pipes and branch pipes, brass fittings adapter, automatic vents ..Etc of approved quality. The price should also supplying and installing 16mm pexgol plastic pipes with its 25mm plastic conduits with 5cm thick concrete layer to radiator outlets, copper elbows recessed in walls and all civil works needed, all according to drawings and engineer’s instructions, and as follows:
supply and install metallic painted steel cabinets, size (80*60cm) of approved quality, including cover with double doors for heating collectors. The cabinets should be recessed in walls and fixed on wooden frame constructed in the wall.
Total of Central Heating System Works carried to Mechanical summary:
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
89
Item DESCRIPTION Unit QTY Unit Price
15 VENTILATION SYSTEM
15.1
15.1.1 * 950 L/s Air Flow @ 0.8" Static pressure NO 115.1.2 * 750 L/s Air Flow @ 0.8" Static pressure NO 115.1.3 * 560 L/s Air Flow @ 0.5" Static pressure NO 1
15.2
15.2.1 * 135 L/s Air Flow @ 0.2" Static pressure NO 215.2.2 * 120 L/s Air Flow @ 0.2" Static pressure NO 115.2.3 * 100 L/s Air Flow @ 0.2" Static pressure NO 1
15.3
15.3.1 NO 115.3.2 NO 115.3.3 NO 115.3.4 NO 115.3.5 NO 1
15.4 M2 150
15.5
15.5.1 * 60cm X 15cm NO 215.5.2 * 55cm X 15cm NO 315.5.3 * 45cm X 15cm NO 715.5.4 * 35cm X 15cm NO 315.5.5 * 23cm X 23cm NO 1515.5.6 * 15cm X 15cm NO 2
15.6
15.6.1 * 55cm X 35cm NO 2
Supply and install ducted outdoor centrifugal exhaust and fresh air fans, type Wood, S&P or EA. The price includes vibration isolators, metallic steel base, galvanized adapter, flexible connection, insect mesh at fan outlet of fan and all accessories needed for installation and commissioning. The price shall also include electrical and control cables and connections to main distribution board, all according to drawings and engineer’s instructions. The fan capacity is as follows:
Supply and install ducted in-line exhaust fan, type Wood, S&P or EA. The price includes vibration isolators, galvanized adapter, flexible connection and all accessories needed for installation and commissioning. The price shall also include outdoor rain water gravity grilles with insect mesh and shutter according to the sizes shown on drawings, and also electrical and control cables and connections to main distribution board, all according to drawings and engineer’s instructions. The fans capacities are as follows:
Supply, install and commission window and wall type exhaust air fan, type Wood, S&P or E.A, with automatic shutter. The price includes openings in walls or windows, electrical wirings and connections to main distribution board according to engineer’s instructions and as follows:
· 25 L/s Air Flow· 40 L/s Air Flow (suitable for duct connection)· 60 L/s Air Flow· 75 L/s Air Flow· 100 L/s Air Flow
Supply and install galvanized metal sheet duct, with thickness according to ASHRAE Standards, for exhaust and fresh air system. The price includes all joints, sealant compound, fire retardant sealant and all necessary accessories, dampers (where required), splitter dampers, galvanized hangers, and hooks.
Supply and install white anodized Aluminum, of approved quality, exhaust and fresh air grilles, type Cooling Industry or E.A, with registers. The price includes galvanized adapter, opening in false ceiling or gypsum boards, and duct flexible connection of size as shown on the drawings. The sizes of grilles are as follows:
Supply and install white anodized Aluminum, of approved quality, fresh air intake louvers, type Cooling Industry or E.A, with insect mesh and filter. The price includes galvanized adapter, opening in walls and connection to fresh air duct as shown on the drawings. The sizes of grilles are as follows:
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
90
Item DESCRIPTION Unit QTY Unit Price
Total of Ventilation System Works carried to Mechanical summary:
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
91
Item DESCRIPTION Unit QTY Unit Price
16 AIR CONDITIONING SYSTEM
16.1 SET 1
16.2
16.2.1 * 7 kW cooling Cap. & 330 L/s Air Flow NO 216.2.2 * 5.2 kW cooling Cap. & 280 L/s Air Flow NO 316.2.3 * 2.6 kW cooling Cap. & 150 L/s Air Flow NO 3
16.3
16.3.1 * 14 kW cooling Cap. & 540 L/s Air Flow NO 2
16.4
16.4.1 10 kW Cooling Capacity & 380 L/s Air Flow NO 1
16.5 M2 50
16.6
16.6.1 * 30cm X 30cm NO 8
Supply, install and commission outdoor Variable Refrigerant Flow (VRF) heat pump air conditioning sets based on refrigerant R410, type Daikin, Toshiba or E.A, consisting of two units (2 X 20 kW) cooling capacity and (2 X 22 kW) heating capacity. The price include control system, steel bases, gas pipes network from outdoor units till the indoor units located in the X-Ray department, in addition to headers and pipes branches and all accessories needed to complete the job. The price shall also include electrical wirings and connection to main distribution boards.
Supply, install, and commission indoor VRF air conditioning units, type Daikin, Toshiba or E.A, decorative type, complete with remote control, drain pipes to floor drains, builders work, electrical wirings and connections to main distribution boards, all according to drawings, specifications, and approval of supervisor engineer:
Supply, install, and commission indoor VRF air conditioning units, type Daikin, Toshiba or E.A, ducted concealed type, complete with copper pipes connections, acoustic insulation adapter between the units and ducts, room thermostat, drain pan and connections to floor drains, supports and hangers, builders work, flexible connections, connections with supply and fresh air duct, electrical wirings and connections to main distribution boards, all according to drawings, specifications, and approval of supervisor engineer, as follows:
Supply, install, and commission ducted mini-central heat pumps split units, type Daikin, Toshiba or E.A. The price includes all accessories and fittings needed for installation and commissioning, flexible connections, connection of drain pipe, acoustic insulation adapter between the units and ducts, vibration isolators, hangers and supports, high performance washable filters, wall mounted thermostat (three fan speeds – summer/winter changeover – temperature setting module), drain pan, insulated copper pipes, metallic steel base for outdoor units and all electrical wiring and control cable, in addition to connection to MDB. Rate shall also include openings in walls through sleeves of good quality, and refilling works:
Supply and install galvanized metal sheet rectangular duct, with thickness according to ASHRAE Standards, for air conditioning system. The price includes thermal external insulation (1" thick, 24kg/m3 density), all joints, sealant compound, fire retardant sealant, dampers (where required), splitter dampers, galvanized hangers, and hooks.
Supply and install white anodized Aluminum, of approved quality, 4-way supply air diffusers, type Cooling Industry E.A, with registers. The price includes galvanized adapter, opening in false ceiling or gypsum boards, and duct flexible connection of size as shown on the drawings. The sizes of grilles are as follows:
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
92
Item DESCRIPTION Unit QTY Unit Price
16.7
16.7.1 * 60cm X 60cm NO 116.7.2 * 30cm X 30cm NO 1
17 MEDICAL GAS SYSTEM
17.1 NO 1
17.2 NO 1
17.3 NO 11
Two oxygen outletTwo vacuum outletFour electrical sockets, main lineTwo potential grounding socketsIndirect LightDirect LightCutt-off switch for direct-indirect lightsTwo telephone socketspreparation for nurse call sockets
17.4 Ditto, but for one head-Bed Unit. NO 1
17.5
17.5.1 1 1/8'' diameter (O.D) M.R 6017.5.2 7/8'' diameter (O.D) M.R 7517.5.3 5/8'' diameter (O.D) M.R 11017.5.4 3/8'' diameter (I.D) M.R 80
Total of Medical Gas System Works carried to Mechanical summary:
Supply and install white anodized Aluminum, of approved quality, return air grilles, type Cooling Industry or E.A. The price includes opening in false ceiling or gypsum boards. The sizes of grilles are as follows:
Total of Air Conditioning System Works carried to Mechanical summary:
Supply and install area valve control box for medical oxygen and vacuum, including 2-full port, 3 parts shut off valves which controls the supply of oxygen or vacuum through the pipe lines, and line pressure and vacuum gauges. The area valves control boxes should also include an emergency external supply port, equipped with disk and clutch mechanism for quick plug-in connection of the emergency external supply source.
Supply and install local area pressure and vacuum alarm box; local audio-visual pressure alarm box for medical oxygen and vacuum to indicate pressure and vacuum failures by means of green LED, red LED, operated by means of one central PC card and switches, recessed type with anodized aluminum panel.
Supply and install of factory preassembled bed head unit for two beds, according to CE-0473, EN-46001, ISO9001 encompassing extruded aluminum duct system, with four cavities, three of which are directly accessed using snap-on covers. Supply electrical and lighting service, as well as medical gas service. The gas outlets should be installed in a separate compartment. The number of electrical circuits, apart of the low voltage circuit, should be two, main lines power circuit and lighting circuit, each connected to a separate terminal at the main special electrical connection compound in the bed-head unit.
Supply, install, test and commission connect to the served terminals, phosphorous de-oxidized non-arsenical copper (C106) to BS 1172 pipes complete with, such as, but not limited to, fittings, valves, supports, brackets, etc., taking into consideration of all safety prepotions that must be applied to avoid damage of pipes or contaminations. The price also include different gas ID marks & rubber ceiling between band & pipes, all according to drawings and engineer's instruction. The sizes of the pipes are as follows:
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
93
Item DESCRIPTION Unit QTY Unit Price
Section III - Electrical Works18 Lighting
18.1 Light Point:-
NO 153
18.2 Light Fixture:-
18.2.1 NO 6
18.2.2 NO 12
18.2.3 NO 31
18.2.4 NO 2
18.2.5 NO 3
18.2.6 NO 10
18.2.7 NO 64
18.2.8 NO 15
18.2.9 As type D: but with special lamp for dark room NO 4
18.2.10 NO 4
18.2.11 NO 4
18.2.12 NO 2
Total of Lighting System works carried to Electrical summary:
Supply, install, test and commission a complete indoor , outdoor lighting point including all conductors, cables, conduits (PVC or galvanized), switches (type Legrand Mosaic Cross decorative plates range modular components and self-supporting plates or equal approved), boxes, ceiling rose, flexible connection and all other accessories, from appropriate distribution board to lighting point, as specified and detailed on drawings and the Engineer's instructions.
Supply, install, test and commission complete lighting Fixtures, including all supports, lamps, connections, suspensions, clamps, capacitors, internal connections, conductors, bridges, trenching and all other accessories necessary to provide a complete fittings with all terminals according to specifications, drawings and the Engineer's instructions.
TYPE A : 2X26w recessed low energy compact fluorescent cat2 louver type Thorn or equal approved.
TYPE B : 2X26w recessed low energy compact fluorescent cat2 louver type Thorn or equal approved.
TYPE C: 2X13w recessed low energy compact fluorescent with glass IP44 type Thorn or equal approved.
As type A but with non-maintained 3HR conversion packs integrated into lighting fittings throughout, the batteries and inverter gear shall be self contained in the emergency lights. Batteries shall be sealed nickel cadmium or nickel meta-hydride type with life expectancy of 5 year min.
As type B but with non-maintained 3HR conversion packs integrated into lighting fittings throughout, the batteries and inverter gear shall be self contained in the emergency lights. Batteries shall be sealed nickel cadmium or nickel meta-hydride type with life expectancy of 5 year min.
As type C but with non-maintained 3HR conversion packs integrated into lighting fittings throughout, the batteries and inverter gear shall be self contained in the emergency lights. Batteries shall be sealed nickel cadmium or nickel meta-hydride type with life expectancy of 5 year min.
TYPE D : 2X36W high frequency recessed light fixture with prismatic diffuser type Cooper or equal approved.
As type D: but with non-maintained 3HR conversion packs integrated into lighting fittings throughout, the batteries and inverter gear shall be self contained in the emergency lights batteries shall be sealed nickel cadmium or nickel meta-hydride ty
TYPE E: 1x8W Self contained, recessed ceiling mounted edge-lit double sided exit sign for maintained emergency lighting of 3 hour duration.
TYPE F: 2x9 watt surface mounted luminary with opal diffuser type Thorn, RZB or equal approved.
TYPE G : 2X36W Waterproof fluorescent with acrylic diffuser IP65 type Thorn or equal approved.
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
94
Item DESCRIPTION Unit QTY Unit Price
19 Power System Works19.1 Main Feeder:-
19.1.1 M.R 35
19.1.2 M.R 40
19.1.3 M.R 75
19.1.4 M.R 24
19.1.5 M.R 2019.2 Distribution Boards:
19.2.1 DB-X-RAY NO 119.2.2 DB-IMW NO 119.3 Earthing System:-
L.S 1
19.4 Sub-Installation:
NO 66
19.4.1 NO 4
19.4.2 NO 15
19.4.3 NO 8
19.4.4 NO 1
19.4.5 NO 1
19.4.6 NO 1
19.4.7 NO 1
Supply, install, test and commission 600/1000V XLPE copper cables including glands, cable ties, labeling, and all associated accessories according to the drawings, specifications and relevant codes of practice and highest prevailing engineering standards, for the following:
3 X 150 + 70 mm2 + 150 mm2.
3 X 35 + 16 mm2 + 35 mm2.
5 X 25 mm2.
5 X 10 mm2
5 X 6 mm2
Supply, install, test and commission complete main distribution board inclusive of all circuit breakers type Moeller or equal approved for outing and incoming cables, bus bars and their coupling unit, casing spaces for cables, cable clamps/terminals, cable shoes, protection equipment, as required to form a complete unit for. All shall be in accordance with the drawings, specification, the codes of practice and highest prevailing standards of engineering.
The Contractor shall submit detailed shop drawings for the board to take approval from the Engineer before manufacturing.
Supply, install, test and commission a complete ring grounding system for mechanical plants and all big metallic masses, etc., including all conductors, copper bars, clamps, conduits fixing etc., all in accordance with specifications, drawings and codes of practice.
Supply, install, test, number and commission a complete single phase single socket outlets, including all conductors, cables, conduits, boxes, sockets outlets (type Legrand Mosaic Cross decorative plates range modular components and self-supporting plates or equal approved), and all connections between the appropriate distribution board to the terminal point, as specified and as detailed on drawings:
Supply, install, test and commission as per item 1, but 13A single phase double socket outlets.
Supply, install, test and commission as per item 1, but 13A single phase water proof socket outlets.
Supply, install, test and commission as per item 1, but 16A isolating switch for fan coil.
Supply, install, test and commission as per item 1, but 16A 3 phase isolating switch IP65.
Supply, install, test and commission as per item 1, but 63A isolating switch IP65.
Supply, install, test and commission as per item 1, but 16A single phase socket outlets for exhaust fan with indication lamp.
Supply, install Modular flush floor service outlet box 300x200x80mm, three compartments, including double socket outlet, RJ45 data socket outlet, RJ11 telephone socket outlet type Legrand or equal approved..
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
95
Item DESCRIPTION Unit QTY Unit Price
19.4.8 NO 4
19.4.9
19.4.10 30cm wide M.R 7219.5 Bed Head Unit
NO 12
Total of Power System works carried to Electrical summary:
20 Telephone & Computer Networks Systems20.1 Telephone System:
20.1.1 NO 6
20.1.2
a 30 pairs L.S 1b 20 pairs L.S 1
20.2 Computer Networks Systems:
20.2.1 NO 5
20.2.2 L.S 1
20.2.3 NO 8
20.2.4 M.R 42
Supply, install, test and commission a stainless steel hand dryer, automatic type, operated by photo cell, surface type, AC supply, 1500 W, 220V, 50Hz, Including cables, conduits, boxes and all other accessories from appropriate distribution board to the hand dryer as specified and detailed on drawings.
Supply, install, test and commission hot deep galvanized steel perforated cable tray, complete with all mounting accessories, tees, reducers, covers, elbows, etc. as shown on the drawings and specification for the following:
Supply, install, test and commission a complete electrical point for units including conductors, conduits, accessories, boxes, wiring interconnections, earthing, etc., for complete workable unit. Point consist of lighting point, power receptacles points, telephone point, nurse call point, as specified and as detailed on drawings.
Supply, install, test and commission complete telephone point including all conduits, boxes (flush or surface mounted), cabling (Cat5e 4 pair unscreened) type Teldor, RG 45 Cat5e outlet type Legrand or equal approved. According to specifications, and drawings. All Telephone outlets shall be numbered in sequence.
Supply, install, test and commission telephone terminal boards (TTB) complete with all accessories needed for complete work, incoming cables, as specified and as detailed on drawings for the followings:
Supply, install, connect and commission complete data point including all conduits, boxes (flush or surface mounted), cables STP cat6 type Teldor, RG 45 Cat 6 outlet type 3M or equal approved. According to specification and drawings. All Data outlets shall be numbered in sequence.
Supply, install, test, and commissioning Data Panel(DP) 18U including 1 air patch panels,1 patch panels type 3M, power strip all needed internal cables, connections and all accessories to complete the work. as specified and as detailed on drawings, and to the Engineer's instructions.
Supply, install, test and commission complete satellite point including all conduits, cable, conduit accessories, boxes outlet type Legrand or equal approved. According to specifications, and drawings. All outlets shall be numbered in sequence.
Supply, install, test and commission hot deep galvanized steel perforated cable tray, complete with all mounting accessories, tees, reducers, covers, elbows, etc. as shown on the drawings and specification for the following:20cm wide.
Total of Telephone & Computer Networks Systems works carried to Electrical summary:
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
96
Item DESCRIPTION Unit QTY Unit Price
21 Fire Alarm System
21.1 L.S 1
21.2 NO 32
21.3 NO 2
21.4 NO 3
21.5 NO 3
Total of Fire Alarm System works carried to Electrical summary:
22 Nurse Call System:
22.1 L.S 1
22.2 L.S 1
22.3 NO 1
22.4 Supply, install, test and commission as per item 1, but dual jack. NO 11
22.5 NO 9
22.6 Supply, install, test and commission as per item 1, but Zone lamp NO 1
22.7 NO 2
Total of Nurse Call System works carried to Electrical summary:
23 Public Address System
23.1 L.S 1
23.2 NO 6
Supply, install, test and commission new fire alarm loop, this loop shall be connected to existing FACP (the existing fire alarm panel Type Edward) including commission FACP, all conduits, boxes, cabling type Teldor, According to specifications.
Supply, install, test and commission a fire alarm photo-optical smoke detector including all conduits fixing, boxes, and cables (type Teldor or equal approved), . According to specification and drawings. Type Edward
Supply, install, test and commission a fire-alarm heat-detector including all conduits fixing, boxes, and cables. According to specification and drawings.
Supply, install, test and commission a fire alarm electronic sounder Banshee type including all conduits fixing, boxes, and cables. According to specification and drawings.
Supply, install, test and commission a flush mounted fire alarm manual pull station including all conduits fixing, boxes, and cables. According to specification and drawings.
Supply, install, test and commission 50 call master station nurse call including conduits, conduit accessories, boxes, cabling, etc., all in accordance with drawings and specifications and engineer instructions type Aiphone or equal approved
Supply, install, test and commission central control unit including power supply, conduits, conduit accessories, boxes, cabling, etc., all in accordance with drawings and specifications and engineer instructions type Aiphone or equal approved.
Supply, install, test and commission wall mounted single jack including conductors, and/or cables, conduits, boxes, etc., from the appropriate nurse call panel to the point the price includes also beside call switch in accordance with the specifications and drawings.
Supply, install, test and commission as per item 1, but corridor lamp with red lamp
Supply, install, test and commission as per item 1, but emergency bathroom pull cord.
Connect, test and commission the new loudspeaker to existing system including all conduits, boxes, cabling , According to specifications and engineer instructions
Supply, install, test and commission the 6 watt flush-mount ceiling loudspeaker with matching transformer.
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
97
Item DESCRIPTION Unit QTY Unit Price
Total of Public Address System works carried to Electrical summary:
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
98
Total Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
99
Total Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
101
Total Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
102
Total Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
103
Total Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
104
Total Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
105
Total Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
107
Total Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
109
Total Amount
0.000.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
110
Total Amount
0.00
0.00
0.00
0.000.000.000.000.00
0.000.000.000.000.000.00
0.000.00
0.000.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
111
Total Amount
0.000.00
0.00
0.00
0.00
0.00
0.000.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
112
Total Amount
0.000.000.00
0.000.000.00
0.000.000.000.000.00
0.00
0.000.000.000.000.000.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
114
Total Amount
0.00
0.000.000.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
115
Total Amount
0.000.00
0.00
0.00
0.00
0.00
0.00
0.000.000.000.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
116
Total Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
117
Total Amount
0.00
0.00
0.00
0.00
0.00
0.000.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
118
Total Amount
0.00
0.000.00
0.00
0.00
0.00
0.000.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
119
Total Amount
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
Summary of Part 2
Bill Description
Section I Civil Works Summary
1 Demolish and Removal Works
2 Block work
3 Plastering Works
4 Tile Finishing Works
5 False Ceiling Works
6 Painting Works
7 Carpentary & Joinery Works
8 Insulatuion Works
9 Glass Works
10 Metal Works
11 Sand-blasting Works
Total of Civil Works
Section II Mechanical Works Summary
12 Sanitary fixture and their Accessories:
13 Water & Fire Fighting Works
14 Central Heating Works
15 Ventalation Works
16 Air Conditioning Works:
17 Medical Gas Supply:
Total of Mechanical Works
Section III Electrical Works Summary
18 Lighting System Works
19 Power System Works
20 Telephone & IT System
21 Fire Alarm System
22 Nurse Calling System
23 Public Address System
Total of Electrical Works
Total of Part 2 (Excluding VAT)
Discount %
Discount Amount
Net Total - Part 2 (Excluding VAT)
NET TOTAL SUM (in words ) :
SIGNED AND SEALED :
AUTHOURIZED PERSON :
TITLE :
SIGNATURE :
ATLAS # 14163 Part 2: Rehabilitation Works For Alia Hospital
Summary of Part 2
Total
0.000.000.000.000.000.000.000.000.000.000.000.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.000.000.000.000.000.000.000.00
0.00
0.00
NET TOTAL SUM (in words ) :
SIGNED AND SEALED :
AUTHOURIZED PERSON :
TITLE :
SIGNATURE :
ATLAS # 14163 Alia Hospital
Grand Summary (Part 1 + Part 2)
Item Description
Bill 1
Bill 2
Grand Total Part 1 & Part 2 (Excluding VAT)
Discount %
Discount Amount
Net Total Part 1 & Part 2 (Excluding VAT)
NET TOTAL SUM (in words ) :
SIGNED AND SEALED :
AUTHOURIZED PERSON :
TITLE :
SIGNATURE :
DATE :
Part 1: Construction of the remaining works at Alia Hospital 2nd floor
Part 2: Rehabilitation Works For Alia Hospital