Produced by the Employees of © Cleaver-Brooks Division, Aqua-Chem, Inc. 2002 The Boiler Book is protected by copyright and is to be used solely by consulting and specifying engineers for the purpose of selecting and specifying Cleaver-Brooks equipment. Any other use of The Boiler Book is strictly prohibited without written permission from Cleaver-Brooks. Cleaver-Brooks P.O. Box 421 Milwaukee, WI 53201 (414) 359-0600 email: [email protected] www.cleaver-brooks.com Printed in the U.S.A. The Boiler Book iii Performance Proven Worldwide

Upload: moxie22

Post on 04-Oct-2014

267 views

Category:

Documents


22 download

TRANSCRIPT

The Boiler BookProduced by the Employees of

Performance Proven Worldwide

Cleaver-Brooks Division, Aqua-Chem, Inc. 2002

The Boiler Book is protected by copyright and is to be used solely by consulting and specifying engineers for the purpose of selecting and specifying Cleaver-Brooks equipment. Any other use of The Boiler Book is strictly prohibited without written permission from Cleaver-Brooks.

Cleaver-Brooks P.O. Box 421 Milwaukee, WI 53201

(414) 359-0600 email: [email protected] www.cleaver-brooks.com Printed in the U.S.A.

iii

The Boiler Book is intended for use by qualied engineering professionals. All information contained herein is subject to change without notice. Cleaver-Brooks is only responsible for the accuracy of the information and data presented at time of publication. Cleaver-Brooks shall not be responsible for the use of this data or information nor for any systems, designs, or engineering in which the data or information is utilized.

iv

TABLE OF CONTENTSFiretube Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section AA1 General A2 Model CB Boilers A3 Model CB (LE) Boilers A4 Model CBW Boilers A5 Discontinued A6 Model CB Ohio Special Boilers A7 Model CBE Boilers A8 Model CEW Boilers A9 Model CEW-LN Boilers A10 Model CEW Ohio Special Boilers A11 Model CBL Boilers A12 Model ICB Boilers A13 Model ICB-LN Boilers

Commercial Boilers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section BB1 Model FLX Boilers B2 Model 4 Boilers B3 Model 5 Boilers B4 Electric Boilers B5 - TrueFire Boilers B6 - ClearFire Boilers

Industrial Watertube Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section C Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section D Emissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section E Stacks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section F Economizers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section G Feedwater Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section HH1 Spraymaster Deaerators (Single Tank) H2 Spraymaster Deaerators (Duo Tank) H3 Boilermate Deaerators H4 Surge Tanks H5 Boiler Feed Systems H6 Chemical Feed Systems and Metering Pumps H7 Filters H8 Softeners H9 Dealkalizers H10 Blowdown Separators H11 Blowdown Heat Recovery Systems H12 Flash Tank Heat Exchangers H13 Sample Coolers

System Fundamentals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section II1 Boiler Selection Considerations I2 Hot Water Systems I3 Steam Systems I4 General Engineering Data

Glossary/Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section J

Section A1GENERALModel CB Boilers Model CB-LE Boilers Model CBW Boilers Model CBH Boiler (discontinued) Model CB Ohio Special Boilers Model CBE Boilers Model CEW Boilers Model CEW-LN Boilers Model CEW Ohio Special Boilers Model CBL Boilers Model ICB Boilers Model ICB-LN Boilers A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13

A1-112-02

General

Firetube Boilers Heavy duty motor with direct drive, maintenance free, caseless fan. Integral forced draft fan eliminates the need for: Large diameter breeching. High chimneys. Induced draft fans. Barometric dampers. Sequencing draft controls. Thick Fiberglass Insulation: 2" insulation covered with sturdy sheet metal lagging provides maximum efciency and durable construction. All units nished with hard enamel paint coating. Customer Service and Support:

FEATURES AND BENEFITSThe following Cleaver-Brooks retube boiler models (CB, CB-LE, CBW, CB Ohio Special) include the following features and benets. Packaged Design with Integral Front Head: Integral front head provides proper burner/boiler compatibility for maximum efciency and ease of maintenance. Packaged boiler is factory assembled, wired, and tested for guaranteed performance and reliability. Packaged design allows for easy connection of utilities, minimum start-up requirements, and lower long-term maintenance requirements. Built and tested to ASME standards. Single Point Positioning Combustion Control Package: Accurate, repeatable combustion control for responsiveness to load swings. Single point linkage assembly for air and fuel simplies adjustments and reduces start-up and maintenance costs. Unique variable contour.cam assembly allows accurate adjustment and enhances safe operation of the boiler. Computerized burner control provides accurate sequencing and continuous monitoring for optimum safety, efciency, and reliability. Low Stack Temperatures: Guaranteed efciency veried by low stack temperatures. Reduced fuel and operating costs. Low Excess Air: Operates at 3% O2 with less than 200 ppm CO for maximum combustion efciency. High efciency and low maintenance requirements. High Steam Quality: Large steam space and liberal surface area ensure high steam quality, free from entrained particles of moisture. Provides reliable, high quality (98.5% dry) source of steam. Quiet Operation: Integral front head with vibration free combustion air fan provides quiet operation. Ideal for sound critical applications, like hospitals and schools.

Boiler start-up, nal adjustment, and operator training provided with all retube boilers. Emergency service response 24 hours a day, 7 days a week, from the industrys most advanced worldwide computerized parts/service distribution network. Largest network of factory trained technicians provide: System trouble shooting. Operator training. Customized factory-backed planned maintenance programs. Emergency boiler rental. Total after-sale support.

A1-212-02

Firetube Boilers

GeneralThe Model CB Ohio Special Boiler (standard offering) design is based on operator requirements of the state of Ohio, under the rules and regulations for unattended units. 100 hp through 225 hp. Four-pass dryback design (100 hp). Two-pass dryback design (125-225 hp). 150, 200 and 250 psig high pressure steam. 15 psig low pressure steam. Natural gas or light oil ring. The Model CBE Boiler (standard offering) provides high quality steam or hot water, utilizing a baseline boiler/burner design. Three-pass dryback design. 60-350 hp. 15 psig low pressure steam. 150-300 psig high pressure steam. 30 and 125 psig hot water. Natural gas or light oil. The Model CEW Boiler (standard offering) provides high quality steam or hot water, utilizing a baseline boiler/burner design. Three-pass wetback design. 125-800 hp. 15 psig low pressure steam. 150-250 psig high pressure steam. 30 and 125 psig hot water. Natural gas or light oil. The Model CEW-LN Boiler is the baseline retube product offering with a low emission package. Three-pass wetback design. 125-800 hp. 30 ppm package (natural gas). 15 psig low pressure steam. 150-250 psig high pressure steam. 30 and 125 psig hot water. Natural gas or light oil.

PRODUCT OFFERINGCleaver-Brooks retube boilers are available in low pressure steam, high pressure steam, and hot water designs. Burners are available to re natural gas, light oil, heavy oil, or a combination of oil and gas. Optional alternate fuel (propane, mixed gas, digester gas, etc.) burners are also available. The retube product offering is available in the following models. The Model CB Boiler (standard offering) is the premium retube product offering providing maximum boiler efciency, the widest range of size and pressures, and premium control packages. Four-pass dryback design. 15 hp through 800 hp. 150-350 psig high pressure steam. 15 psig low pressure steam. 30 or 125 psig hot water. Natural gas, light oil, or heavy oil ring. The Model CB (LE) Boiler is the premium retube product offering with a low emission package. Four-pass dryback design. 125-800 hp. 20-60 ppm packages (natural gas). 15 psig low pressure steam. 150-300 psig high pressure steam. 30 and 125 psig hot water. Natural gas or light oil. The Model CBW Boiler (standard offering) provides the advantages of the Cleaver-Brooks integral front head in a three-pass wetback design. Three-pass wetback design. 100 hp through 800 hp. 150-250 psig high pressure steam. 15 psig low pressure steam. 30 or 125 psig hot water. Natural gas, light oil, or heavy oil ring.

A1-312-02

GeneralThe Model CEW Ohio Special Boiler (standard offering) baseline design is based on operator requirements of the state of Ohio, under the rules and regulations of unattended units. Three-pass wetback design. 100-225 hp. 15 psig low pressure steam. 150-200 psig high pressure steam. Natural gas or light oil. The Model CBL Boiler (standard offering) line provides high quality steam utilizing a boiler/burner package. Three or four-pass wetback design. 800-1500 hp. 150-250 psig high pressure steam. Natural gas, light oil, or heavy oil ring. The Model ICB Boiler is a baseline retube product, designed to provide high quality steam or hot water. Its revolutionary design incorporates the key features and benets of both the wetback and dry back retube boilers. Three or four-pass Intercooled design. 100 800 hp. 15 psig low pressure steam. 150 300 psig high pressure steam. 30 and 125 psig hot water. Natural gas or light oil ring. The Model ICB-LN Boiler is a baseline retube product, designed to provide high quality steam or hot water with a low emission package. Its revolutionary design incorporates the key features and benets of both the wetback and dry back retube boilers. Three or four-pass Intercooled design. 100 800 hp. 30 ppm package (natural gas). 15 psig low pressure steam. 150 300 psig high pressure steam. 30 and 125 psig hot water. Natural gas or light oil ring.

Firetube Boilers

MODEL NUMBER, FUEL SERIES NUMBER, HORSEPOWER, AND DESIGN PRESSUREThe model designation for Cleaver-Brooks retube boilers includes the following: Light Oil: Series 100 Natural Gas: Series 700 Heavy Oil: Series 600 Light Oil and Natural Gas: Series 200 Heavy Oil and Natural Gas: Series 400 For example, a model CB700-350-150ST would represent a model CB boiler, natural gas red, 350 hp, 150 psig steam design pressure. All Cleaver-Brooks retube boilers are built in accordance with ASME Codes and, with the exception of the Ohio Special Boilers and CBL Boilers, UL/ULC standards. Insurance requirements (e.g., Industrial Risk Insurance IRI, Factory Mutual FM, etc.) or special local code requirements may dictate additional controls or equipment to be included. Please contact your local Cleaver-Brooks authorized representative for assistance in completing your specication or for additional information and optional equipment. Refer to Table A1-1 for information on the standard product offering for each retube boiler model.

A1-412-02

Table A1-1. Quick Comparison of Standard Features for Cleaver-Brooks FIretube Boilers

MODEL Rated Capacity Design PressureA

CB 15-800 HP (SECTION A2) 15-800 hp Steam 15-300 psig Hot Water 30 & 125 psig

CBLE 125-800 HP (SECTION A3) 125-800 hp Steam 15-300 psig Hot Water 30 & 125 psig 4-Pass Dry Back 60" 125-200 hp 78" 250-350 hp 96" 400-800 hp

CBW 100-800 HP (SECTION A4) 100-800 hp Steam 15-250 psig Hot Water 30 & 125 psig 3-Pass Wet Back 60" 100-200 hp 78" 250-400 hp 96" 500-800 hp

CB OHIO SPECIAL 100-225 HP (SECTION A6) 100-225 hp Steam Only 15-250 psig

CBE 60-350 HP (SECTION A7) 60-350 hp Steam 15-300 psig Hot Water 30 & 125 psig

CEW 125-800 HP (SECTION A8) 125-800 hp Steam 15-250 psig Hot Water 30 & 125 psig 3-Pass Wet Back 60" 125-200 hp 78" 250-400 hp 96" 500-800 hp

CEW-LN 125-800 HP (SECTION A9) 125-800 hp Steam 15-250 psig Hot Water 30 & 125 psig 3-Pass Wet Back 60" 125-200 hp 78" 250-400 hp 96" 500-800 hp

CEW OHIO SPECIAL 100-225 HP (SECTION A10) 100-225 hp Steam 15-250 psig

CBL 800-1500 HP (SECTION A11) 800-1500 hp Steam 150-250 psig

ICB 100-800 HP (SECTION A12) 100-800 hp Steam 15-300 psig Hot Water 30 & 125 psig

ICB-LN 100-800 HP (SECTION A13) 100-800 hp Steam 15-300 psig Hot Water 30 & 125 psig

Boiler Type Shell Size

4-Pass Dry Back 36" 15-40 hp 48" 50-100 hp 60" 125-200 hp 78" 250-350 hp 96" 400-800 hp 15-800 hp No. 2 Oil, Gas, Combination Oil/Gas 50-800 hp No. 6 OilB, Gas, Combination Oil/Gas

Passes VaryC 48" 100 hp 60"125-225 hp

3-Pass Dry Back 48" 60-100 hp 60" 125-200 hp 78" 250-350 hp

3 Pass Wet Back 60" 100-225 hp

3 or 4-Pass Wet Back 114" or 126"E

4-Pass Intercooled 4-Pass Intercooled 3-Pass Option 3-Pass Option 55" 100-125 hp 60" 150-200 hp 72" 250-300 hp 78" 350-400 hp 92" 500-600 hp 106" 700-800 hp No. 2 Oil, Natural Gas Combination Oil/ Gas 55" 100-125 hp 60" 150-200 hp 72" 250-300 hp 78" 350-400 hp 92" 500-600 hp 106" 700-800 hp No. 2 Oil, Natural Gas Combination Oil/ Gas

Fuel

No. 2 Oil, Gas, Combination Oil/Gas

No. 2 Oil, Gas, Combination Oil/Gas No. 6 OilB, Gas, Combination Oil/Gas

100-225 hp No. 2 Oil, Gas, Combination Oil/Gas 100 hp No. 6 Oil, Gas, Combination Oil/Gas Full Modulation

No. 2 Oil, Gas, Combination Oil/Gas

No. 2 Oil, Gas, Combination Oil/Gas

No. 2 Oil, Gas, Combination Oil/Gas

No. 2 Oil, Gas, Combination Oil/Gas

800-1300 hp No. 2 Oil, Gas, Combination Oil/Gas 800-1500 hp Gas 800-1000 hp No. 6 Oil, Gas, Combination Oil/Gas

12-02

Firing Method

15-20 hp On-off 30-40 hp Low-High-Low-Off 50-800 hp Full Modulation

Full Modulation

Full Modulation

Full Modulation

Full Modulation

Full Modulation

Full Modulation

Full Modulation

Full Modulation

Full Modulation

Air Damper Type

Single Blade 15-40 hp Rotary 50-800 hp Blue UL & ULC Boiler/Burner McD&M 157 Warrick 3C-2 McD&M PS 750-MT-120

Rotary

Rotary

Rotary

Multi-Blade

Multi-Blade 125-350 hp, Rotary 400-800 hp Blue UL & cUL Boiler/ Burner McD&M 157 Warrick 3C-2 McD&M PS 750-MT-120

Rotary

Multi-Blade

Rotary & Louvers

Multiblade 100-250 hp Rotary 300-800 hpF Blue UL & cUL Boiler/Burner McD&M 157, McD&M 193 Warrick 3C-2 McD&M PS 750-MT-120

Rotary

Paint Color Approvals

Blue UL & ULC Boiler/Burner McD&M 157 Warrick 3C-2 McD&M PS 750-MT-120

Blue UL & ULC Boiler/Burner McD&M 157 Warrick 3C-2 McD&M PS 750-MT-120

Blue N/A

Blue UL & cUL Boiler/Burner McD&M 157 Warrick 3C-2 McD&M PS 750-MT-120

Blue UL & cUL Boiler/Burner McD&M 157 Warrick 3C-2 McD&M PS 750-MT-120

Blue N/A

Blue 800-1000 hp UL & CSA (Burner Only) McD&M 193-7 Warrick 3C-2 N/A

Blue UL & cUL Boiler/Burner McD&M 157, McD&M 193 Warrick 3C-2 McD&M PS 750-MT-120

Steam Trim-Low Water Control Steam Trim Aux Low Water Control Water Trim-Low Water Control

McD&M 157 Warrick 3C-2 N/A

McD&M 157 Warrick 3C-2 N/A

A Consult your local Cleaver-Brooks authorized representative for higher design pressures. B Consult your local Cleaver-Brooks authorized representative for No. 4 & No. 5 oil applications. C Ohio Special-Model CB 100 hp 4-pass dryback, 125-225 hp 2-pass dryback. E Shell varies by square foot of pressure vessel and boiler horsepower. F ICB Three-Pass Boiler utilizes multiblade 100-350 and Rotary 400-800.

Table A1-1. Quick Comparison of Standard Features for Cleaver-Brooks FIretube Boilers (Continued)

MODEL Controls Steam & Hot Water Controls Surface Blowoff Conn. & Dip Tube on top C/L Air Vent Connection Stack Thermometer Drain Valve-HW & 15 psig-Steam Front Door

CB 15-800 HP (SECTION A2) Hi Limit (MR), Oper. Limit, Firing Rate 30-800 hp HPS-Std LPS-Conn. Only HW-Std. Yes No Hinge 15-200 hp Davit/Hinge 250-800 hp Hinge 15-100 hp Davit 125-800 hp 2 inch 3 Phase

CBLE 125-800 HP (SECTION A3) Hi Limit (MR), Oper. Limit, Firing Rate HPS-Std LPS-Conn. Only HW-Std. Yes No Hinge 125-200 hp Davit /Hinge 250-800 hp Davit 2 inch 3 Phase

CBW 100-800 HP (SECTION A4) Hi Limit (MR), Oper. Limit, Firing Rate HPS-Std LPS-Conn. Only HW-Std. Yes No Hinge 100-200 hp Davit/Hinge 250-800 hp Davit 2 inch 3 Phase

CB OHIO SPECIAL 100-225 HP (SECTION A6) Hi Limit (MR), Oper. Limit, Firing Rate HPS-Std LPS-Conn. Only N/A Yes No Hinge

CBE 60-350 HP (SECTION A7) Hi Limit (MR), Oper.Limit, Firing Rate HPS-Std LPS-Conn. Only HW-Std. No No Davit

CEW 125-800 HP (SECTION A8) Hi Limit (MR), Oper. Limit, Firing Rate HPS-Std LPS-Conn. Only HW-Std. No No Davit

CEW-LN 125-800 HP (SECTION A9) Hi Limit (MR), Oper. Limit, Firing Rate HPS-Std LPS-Conn. Only HW-Std. No No Davit

CEW OHIO SPECIAL 100-225 HP (SECTION A10) Hi Limit (MR), Oper. Limit, Firing Rate HPS-Std LPS-Conn. Only N/A No No Davit

CBL 800-1500 HP (SECTION A11) Hi Limit (MR), Oper. Limit, Firing Rate HPS-Std

ICB 100-800 HP (SECTION A12) Hi Limit (MR), Oper. Limit, Firing Rate HPS-Std LPS-Conn. Only HW-Std No No Davit

ICB-LN 100-800 HP (SECTION A13) Hi Limit (MR), Oper. Limit, Firing Rate HPS-Std LPS-Conn. Only HW-Std No No Davit

N/A Yes N/A Davit

Rear Door Insulation Standard Voltage Requirements 12-02 Fuse Protection

Hinge 100 hp Davit 125-225 hp 2 inch 3 Phase

Davit 2 inch 60-80 hp1 Phase 100-350 hp3 Phase Control Circuit & All 3 Phase Loads Except Remote Oil Pump Yes-3 Phase Only Cleaver-Brooks CB110 Ultraviolet

Davit 2 Inch 3 Phase

Davit 2 Inch 3 Phase

Davit 2 Inch 3 Phase

Davit 2 Inch 3 Phase

Davit 2 inch 3 Phase

Davit 2 inch 3 Phase

Control Circuit & All 3 Phase Loads Except Remote Oil Pump Yes Cleaver-Brooks CB780 Infrared

Control Circuit & All 3 Phase Loads Except Remote Oil Pump Yes Cleaver-Brooks CB780 Infrared

Control Circuit & All 3 Phase Loads Except Remote Oil Pump Yes Cleaver-Brooks CB780 Infrared

Control Circuit & All 3 Phase Loads Except Remote Oil Pump Yes Cleaver-Brooks CB780 Infrared

Control Circuit & All 3 Phase Loads Except Remote Oil Pump Yes Cleaver-Brooks CB110 Ultraviolet

Control Circuit & All 3 Phase Loads Except Remote Oil Pump Yes Cleaver-Brooks CB110 Ultraviolet

Control Circuit & All 3 Phase Loads Except Remote Oil Pump Yes Cleaver-Brooks CB110 Ultraviolet

Control Circuit & All 3 Phase Loads Except Remote Oil Pump Yes Cleaver-Brooks CB110 Ultraviolet (Gas & No. 2 Oil) Infrared (No. 6 Oil) Burner without Key Lock LD, FV, LW, FF

Control Circuit & All 3 Phase Loads Except Remote Oil Pump Yes Cleaver-Brooks CB110 Ultraviolet

Control Circuit & All 3 Phase Loads Except Remote Oil Pump Yes Cleaver-Brooks CB110 Ultraviolet

Control Circuit Transformer Flame Safeguard Control Scanner Type

Control Panel Location Indicating Lights Type of Pilot

Front Head with Key Lock 50-800 hp LD, FV, LW, FF Interrupted Gas Pilot-Gas, No. 6 Oil & All Combination 15-800 hp Direct Spark Ignition-No. 2 Oil 15-40 hp Spark Ignited Oil Pilot-No. 2 Oil 50-800 hp

Front Head with Key Lock LD, FV, LW, FF Interrupted Gas Pilot-Gas & All Combination

Front Head with Key Lock LD, FV, LW, FF Interrupted Gas Pilot-Gas, No. 6 Oil & All Combination Spark Ignited Oil Pilot No. 2 Oil

Front Head with Key Lock LD, FV, LW, FF Interrupted Gas Pilot-Gas, No. 6 Oil & All Combination Spark Ignited Oil Pilot No. 2 Oil

Burner without Key Lock LD, FV, LW, FF Interrupted Gas Pilot-Gas & All Combination

Burner without Key Lock LD, FV, LW, FF

Burner without Key Lock LD, FV, LW, FF

Burner without Key Lock LD, FV, LW, FF

On Burner without Key Lock LD, FV, LW, FF

Remote-Right Side without Key Lock LD, FV, LW, FF

Interrupted Gas Interrupted Gas Interrupted Gas Interrupted Gas Interrupted Gas Interrupted Gas Pilot-Gas, No. 2 Oil Pilot-Gas, No. 2 Oil Pilot-Gas, No. 2 Oil Pilot-Gas, No. 2 Oil, Pilot-Gas, No. 2 Oil Pilot-Gas, No. 2 Oil All Combination All Combination No. 6 Oil & & & All Combination & All Combination All Combination All Combination

Spark Ignited Oil Pilot No. 2 Oil

No. 2 Oil Direct Spark Ignition 60-100 hp Gas Pilot 125-350 hp

Table A1-1. Quick Comparison of Standard Features for Cleaver-Brooks FIretube Boilers (Continued)

MODEL Gas Burner Type

CB 15-800 HP (SECTION A2) High Radiant Multi-PortAll Except 125-200 hpAnnular Entry Motorized Buttery Valve Required, Not Included Yes No-15-50 hp Yes-60-800 hp Air Atomizing

CBLE 125-800 HP (SECTION A3) High Radiant Multi-PortAll Except 125-200 hpAnnular Entry Motorized Buttery Valve Required, Not Included Yes Yes

CBW 100-800 HP (SECTION A4) High Radiant Multi-PortAll Except 125-200 hpAnnular Entry Motorized Buttery Valve Required, Not Included Yes Yes

CB OHIO SPECIAL 100-225 HP (SECTION A6) High Radiant Multi-Port 100 hp Annular 125-225 hp

CBE 60-350 HP (SECTION A7) High Radiant Multi-Port

CEW 125-800 HP (SECTION A8) High Radiant Multi-Port

CEW-LN 125-800 HP (SECTION A9) High Radiant Multi-Port

CEW OHIO SPECIAL 100-225 HP (SECTION A10) High Radiant Multi-Port

CBL 800-1500 HP (SECTION A11) High Radiant Multi-Port

ICB 100-800 HP (SECTION A12) High Radiant Multi-Port

ICB-LN 100-800 HP (SECTION A13) High Radiant Multi-Port

Main Gas Valve Main Gas Control System Gas Pressure Regulator Gas Pilot Regulator High & Low Gas Pressure Switches Oil Burner Type

Motorized Buttery Valve Required, Not Included Yes Yes

Solenoid, Motorized Solenoid, Motorized Solenoid, Motorized Solenoid, Motorized Buttery Valve Included Yes Yes Buttery Valve Included Yes Yes Buttery Valve Included Yes Yes Buttery Valve Included Yes Yes

Motorized Buttery Valve Included Yes Yes

Solenoid, Motorized Solenoid, Motorized Buttery Valve Included Yes Yes Buttery Valve Included Yes Yes

Air Atomizing

Air Atomizing

Air Atomizing

Pressure Atomizing Pressure Atomizing 125-200 hp 60-200 hp Air Atomizing Air Atomizing 250-800 hp 250-350 hp Air Compressor Air CompressorShipped loose Shipped Loose Solenoid Metering System Included No. 2 Oil 60-200 hp Burner Mounted No. 2 Oil 250-350 hp Remote Solenoid Metering System Included No. 2 Oil 125-200 hp Burner Mounted No. 2 Oil 250-800 hp Remote No-Use CEW-LN

Air Atomizing Air Compressor 125-300 hpMounted 350-800 hpShipped Loose Solenoid Metering System Included No. 2 Oil 125-800 hp Remote

Air Atomizing

Air Atomizing

Pressure Atomizing 100-150 hp Air Atomizing 200-800 hp Solenoid Metering System Included No. 2 Oil 100-150 hp Burner Mounted No. 2 Oil 200-800 hp Remote No-Use ICB-LN

Air Atomizing

Main Oil Valves Oil Control System Oil Pump Location of Oil Pump 12-02

Solenoid Metering Valve Included No. 2 Oil 15-40 hp on Front Head; 50-800 hp Remote No. 6 Oil 50-800 hp, Remote

Solenoid Metering Valve Included No. 2 Oil 125-800 hp Remote

Solenoid Metering Valve Included No. 2 Oil 100-800 hp Remote

Solenoid Metering Valve Included No. 2 Oil 100-225 hp Remote No. 6 Oil 100-225 hp Remote N/A

Solenoid Metering System Included No. 2 Oil 100-225 hp Remote

Motorized Metering System Included No. 2 Oil Remote

Solenoid Metering System Included No. 2 Oil 100-800 hp Remote

No. 6 Oil 100-800 hp Remote Induced FGRD (LE Option) 125-800 hp 20-60 ppm (Natural Gas) + or-0.25" W.C. No-Use CEW-LN

No. 6 Oil Mounted on Oil Pump/Oil Heater Skid Induced FGR 30 ppm(Natural Gas) N/A Optional-Induced FGR 30 ppm (Natural Gas) up to 1300 hp. + or-0.50" W.C. + or-0.25" W.C. With FGR

NOx Control

No-Use CBLE

N/A

Induced FGR 30 ppm (Natural Gas)

Maximum Stack Pressure Variation Start-Up Included

15-40 hp + or-0.25" W.C. 50-800 hp + or-0.50" W.C. Yes

+ or-0.50" W.C.

+ or-0.25" W.C.

+ or-0.25" W.C.

+ or-0.25" W.C.

+ or-0.25" W.C.

+ or-0.25" W.C.

+ or-0.25" W.C.

+ or-0.25" W.C.

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

D Altitude, size, and fuel series limitations may apply.

General

Firetube Boilers

Notes

A1-812-02

Section A2MODEL CB BOILERS

CONTENTS FEATURES AND BENEFITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-3 PRODUCT OFFERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-3 DIMENSIONS AND RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-4 PERFORMANCE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-21 Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-21 Emissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-21 ENGINEERING DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-24 Blowdown Water Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-24 Sound Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-27 Gas-Fired Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-30 Gas Pressure Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-31 Oil-Fired Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-36 No. 6 Oil Piping, Storage Tank Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-36 Boiler Room Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-44 Stack Support Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-44 Stack/Breeching Size Criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-44 Boiler Room Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-44 SAMPLE SPECIFICATION (MODEL CB BOILER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-47 ILLUSTRATIONS Figure A2-1. Model CB Steam Boiler Dimensions and Weights (15 and 150 psig Design Pressure 15 to 100 hp) Sheet 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-2. Model CB Steam Boiler Dimensions and Weights (15 and 150 psig Design Pressure 125 to 800 hp) Sheet 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-3. Model CB Hot Water Boiler Dimensions (30 psig and 125 psig Design Pressure 15 to 100 hp) - Sheet 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-4. Model CB Hot Water Boiler Dimensions (30 psig and 125 psig Design Pressure 15 to 100 hp) - Sheet 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-5. Space Required to Open Rear Head on Model CB Boilers Equipped with Davits . . . . . . . . . . . . . . . . . . . Figure A2-6. Lifting Lug Location, Model CB Boilers - Sheet 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-7. Model CB Boiler Mounting Piers 20 Figure A2-8. Predicted Stack Temperature Increase for Pressure Greater Than 125 psig . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-9. Standard Gas Train Connection Size and Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-10 A2-12 A2-14 A2-16 A2-18 A2-18 A2-23 A2-34 A2-107-02

Model CB Boilers

Firetube BoilersA2-35 A2-36 A2-37 A2-37 A2-38 A2-38 A2-39 A2-39 A2-40 A2-40 A2-41 A2-41 A2-42 A2-42 A2-43 A2-43 A2-45 A2-45 A2-46

Figure A2-10. Typical Gas Piping Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-11. Model CB Gas Train Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-12. No. 2 Oil Connection Size, Location and Recommended Line Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-13. No. 6 Oil Connection Size, Location and Recommended Line Sizes, Model CB Boiler . . . . . . . . . . . . . . Figure A2-14. No. 2 Oil Piping, Single Boiler Installation, Remote Oil Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-15. No.2 Oil Piping, Single Boiler Installation Oil Pump Integral with Boiler . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-16. No. 2 Oil Piping, Multiple Boiler Installation, Remote Oil Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-17. No. 2 Oil Piping, Multiple Boiler Installation, Oil Pump Integral with Boiler . . . . . . . . . . . . . . . . . . . . . Figure A2-18. No. 2 Oil Piping, Multiple Boiler Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-19. No. 6 Oil Piping, Single Boiler Installation, Remote Oil Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-20. No. 6 Oil Piping, Multiple Boiler Installation, Remote Oil Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-21. No. 6 Oil Piping, Multiple Boiler Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-22. No. 2 Oil Transfer Tank Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-23. Typical Fuel Storage Tank Arrangement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-24. Typical Cross Section of Bundled Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-25. Schematic of Standard Alstrom Hot Water Safety-Type Preheating System . . . . . . . . . . . . . . . . . . . . . . . Figure A2-26. Boiler Room Length (Typical Layout) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-27. Boiler Room Width (Typical Layout) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A2-28. Breeching Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TABLES

Table A2-1. Model CB Steam Boiler Ratings (15 - 100 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-5 Table A2-2. Model CB Steam Boiler Ratings (125 - 800 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-5 Table A2-3. Model CB Hot Water Boiler Ratings (15 - 100 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-6 Table A2-4. Model CB Hot Water Boiler Ratings (125 - 800 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-6 Table A2-5. Steam Boiler Safety Valve Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-7 Table A2-6. Hot Water Boiler Relief Valve Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-8 Table A2-7. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 10 psig, Natural Gas . . . . . . . . . . . . . . . . . A2-22 Table A2-8. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 125 psig, Natural Gas . . . . . . . . . . . . . . . . A2-22 Table A2-9. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 10 psig, No. 6 Oil . . . . . . . . . . . . . . . . . . . A2-22 Table A2-10. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 125 psig, No 6 Oil . . . . . . . . . . . . . . . . . . A2-22 Table A2-11. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 10 psig, No. 2 Oil . . . . . . . . . . . . . . . . . . A2-23 Table A2-12. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 125 psig, No. 2 Oil . . . . . . . . . . . . . . . . . A2-23 Table A2-13. Model CB Boiler Emission Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-24 Table A2-14. Heating Surface, Model CB Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-24 Table A2-15. Steam Volume and Disengaging Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-25 Table A2-16. Water Circulation Rate and Temperature Drop for Hot Water Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-25 Table A2-17. Recommended Steam Nozzle Size (To Maintain 4000 to 5000 fpm Nozzle Velocity) . . . . . . . . . . . . . . . A2-26 Table A2-18. Recommended Non-Return Valve Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-26 Table A2-19. Model CB Blowdown Tank Sizing Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-27 Table A2-20. Sound Pressure Level Summary (50 - 800 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-27 Table A2-21. Model CB Boiler Sound Pressure Level Details (40 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-27 Table A2-22. Model CB Boiler Sound Pressure Level Details (50 - 125 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-28 Table A2-23. Model CB Boiler Sound Pressure Level Details (125 - 200 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-29 Table A2-24. Model CB Boiler Sound Pressure Level Details (250 - 350 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-29 Table A2-25. Model CB Boiler Sound Pressure Level Details (400 - 800 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-30 Table A2-26. Minimum Required Gas Pressure at Entrance to Standard and FM Gas Trains (Downstream of Gas Pressure Regulator) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-31 Table A2-27. Minimum Gas Pressure at Entrance to Gas Trains Equipped with Industrial Risk Insurers (IRI) Requirements (Downstream of Gas Pressure Regulator) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-31 Table A2-28. Under and Oversized Standard and FM Gas Trains, Model CB Boilers (50 - 800 hp) . . . . . . . . . . . . . . . . A2-32 Table A2-29. Under and Oversized IRI Gas Trains, Model CB Boilers (50 - 800 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-33 Table A2-30. Minimum Required Gas Pressure Altitude Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-33 Table A2-31. Maximum Gas Consumption (CFH) for Natural Gas and Propane Vapor & Gas Pilot Data. . . . . . . . . . . . A2-34

A2-207-02

Firetube Boilers

Model CB Boilers Air atomizing oil burner available for proper oil atomization, maximum combustion efciency, and low maintenance requirements. Air atomizing compressor provided with the boiler package for clean oil burning and ease of maintenance. Combination gas/oil burners provide quick fuel changeover without re-adjustment of the burner. Fuel oil controller eliminates the need for over 40 connections, combining gauges, valves, and regulators into a single casting. Retractable oil nozzle provides easy access and cleaning and eliminates coking of oil and nozzle tip when ring gas. Low NOx Capability Available:

FEATURES AND BENEFITSIn addition to the features provided on all Cleaver-Brooks Firetube Boilers, the following features apply specically to Model CB Firetube Boilers. The CB four-pass dryback boiler is the premium retube boiler design available. Four-Pass Dryback Design: Four-pass design provides high ue gas velocities and low stack temperature for guaranteed maximum efciency. Dryback design provides full access to boiler tubes, tube sheet, and furnace for ease of maintenance. Dryback design includes single rear tube sheet construction, providing reduced tube sheet stresses. Five Square Feet of Heating Surface per Boiler hp: Maximum heat transfer with minimum thermal stresses provide guaranteed efciency and long boiler life. Highest guaranteed fuel-to-steam efciencies. Low Furnace Location Furnace located well below water level with generous clearance from bottom of boiler, allowing proper circulation. Low furnace provides additional safety margin between furnace and water level. Reduces water carryover, producing drier steam. Hinged or Davited Front and Rear Doors: Provides full access to front and rear tube sheet and furnace. Reduces maintenance costs. High Turndown Burner: 4:1 turndown (gas and oil) is standard on boilers up to 250 hp. Guaranteed 10:1 turndown (gas red) 8:1 (No. 2 oil red) standard on 250 hp through 800 hp. Advanced burner design provides maximum combustion efciencies and high turndown. Reduced boiler cycling and maintenance. Boiler stays on line during low load conditions for optimum efciency and performance. Gas, No. 2 Oil, No. 6 Oil, and Combination Gas and Oil Burners Available: High radiant multi-port gas burner designed for high gas velocities and complete fuel/air mixing, providing maximum combustion efciencies.

20 ppm NOx guarantee available on Model CB (LE) Boilers.

PRODUCT OFFERINGModel CB Firetube Boilers are available in low pressure steam, high pressure steam, and hot water designs. Burners are available to re natural gas, light oil, heavy oil, or a combination of oil and gas. Optional alternate fuel burners are also available. Model CB Boilers include: Four-pass dryback design. 15 hp through 800 hp. 150 psig - 350 psig high pressure steam. 15 psig low pressure steam. 30 psig or 125 psig hot water. Natural gas, light oil, or heavy oil ring. The Model CBBoiler is the premium retube product offering providing maximum boiler efciency, the widest range of size and pressures, and premium control packages. Available options: For option details, contact your CleaverBrooks authorized representative. Options include the following: Boiler Options Auxiliary low water cut-off (standard on steam boilers). Drain valves. Additional screwed or anged tappings. Special design pressures. Surge load bafes. Seismic design.

A2-307-02

Model CB Boilers Internal hot water coils. Blowdown valves. Non-return valves. Feedwater valves and regulators. Special doors, davited, hinged, left swing. Special base rails. Surface blowdown systems. Combustion relief door. Weather-proong. Blend pump. Burner/Control Options Special modulation controls. Low NOx equipment. Optional ame safeguard controller. Lead/lag system. High altitude design, up to 12,000 ft. Special insurance and code requirements (e.g., IRI, FM, ASME CSD-1). Alarm bell/silence switch. Special motor requirements (TEFC, high efciency). Remote contacts. Special purpose indicator lights. Main disconnect. Elapsed time meter. Voltmeter/micro-ammeter. NEMA enclosures. Low re hold controls. Remote emergency shut-off (115V). Circuit breaker. Day/night controls. Special power requirements. Fuel Options Automatic fuel changeover. Special gas pressure regulator. Oversized/undersized gas trains. Gas strainer. Special fuel shut-off valves. Special pilot.

Firetube Boilers

Alternate fuel ring (propane, digester gas, etc.). Special oil pumps.

DIMENSIONS AND RATINGSDimensions and ratings for the Model CB boilers are shown in the following tables and illustrations: Table A2-1. Model CB Steam Boiler Ratings (15 thru 100 hp) Table A2-2. Model CB Steam Boiler Ratings (125 thru 800 hp) Table A2-3. Model CB Hot Water Boiler Ratings (15 thru 100 hp) Table A2-4. Model CB Hot Water Boiler Ratings (125 thru 800 hp) Table A2-5. Safety Valve Openings Table A2-6. Relief Valve Openings Figure A2-1. Model CB Steam Boiler Dimensions (15 and 150 lb design pressure) (15 thru 100 hp) Figure A2-2. Model CB Steam Boiler Dimensions (15 and 150 lb design pressure) (125 thru 800 hp) Figure A2-3. Model CB Hot Water Boiler Dimensions (30 lb design pressure) (15 thru 100 hp) Figure A2-4. Model CB Hot Water Boiler Dimensions (20 lb design pressure) (125-800 hp) Figure A2-5. Space Required to Open Rear Head on Model CB Boilers Equipped with Davits Figure A2-6. Lifting Lug Locations, Model CB Boilers Figure A2-7. Model CB Boiler Mounting Piers

A2-407-02

Firetube BoilersTable A2-1. Model CB Steam Boiler Ratings (15 - 100 hp)BOILER HP 15C 20C 30C 40C 50 60

Model CB Boilers

70

80

100

RATINGS - SEA LEVEL TO 3000 FT Rated Cap. (lbs steam/hr @212F) Btu Output (1000 Btu/hr) 518 502 690 670 1035 1004 1380 1339 1725 1674 2070 2009 2415 2343 2760 2678 3450 3348

APPROXIMATE FUEL CONSUMPTION AT RATED CAPACITY Light Oil (gph)A

4.5 625 6.3

6.0 835 8.4

9.0 1255 12.6

12.0 1675 16.8

15.0 14.0 2095 21.0

18.0 16.5 2510 25.1

21.0 19.5 2930 29.3

24.0 22.5 3350 33.5

30.0 28.0 4185 41.9

Heavy Oil (gph)B Gas (cfh) 1000 Btu-Nat Gas (Therm/hr)

POWER REQUIREMENTS - SEA LEVEL TO 3000 FT, 60 HZ Blower Motor hp (except gas) Gas Models (only) Oil Pump Motor, hp No. 2 Oil Oil Pump Motor, hp No. 6 Oil Oil Heater kW No. 6 Oil Air Compressor Motor hp (Oil firing Only) 1 1 1 1 1-1/2 1-1/2 2 2 2 2 1/3 1/3 5 2 2 2 1/3 1/3 5 2 2 2 1/3 1/3 5 2 2D 2D 1/3 1/3 5 2 3 3 1/3 1/3 5 2

Belt-Driven From Blower -

Air Compressor Belt-Driven from Blower Motor

NOTES: 1. For altitudes above 3000 ft, contact your local Cleaver-Brooks authorized representative for verification of blower motor hp. A. Based on 140,000 Btu/gal. B. Based on 150,000 Btu/gal. C. No. 6 Oil not available in 15-40 hp range. D. 3 hp above 2000 ft.

Table A2-2. Model CB Steam Boiler Ratings (125 - 800 hp)BOILER HP 125 150 200 250 300 350 400 500 600 700 750 800 RATINGS SEA LEVEL TO 3000 FT J Rated Cap. (lbs steam/hr @ 212F) Btu Output (1000 Btu/hr) 4313 4184 5175 5021 6900 6695 8625 8369 10350 10043 12075 11716 13800 13390 17250 16738 20700 20085 24150 23432 25875 25106 27600 26779

APPROXIMATE FUEL CONSUMPTION AT RATED CAPACITY Light Oil (gph)A Heavy Oil (gph)B Gas (cfh) MBTU-nat Gas (Therm/hr) 37.5 35.0 5230 52.3 45.0 42.0 6280 62.8 60.0 56.0 8370 83.7 74.5 69.5 10460 104.6 89.5 83.5 12555 125.5 104.5 97.5 14650 146.5 119.5 111.5 16750 167.5 149.5 139.5 20925 209.3 179.5 167.5 25100 251.0 209.0 195.5 29300 293.0 224.2 209.2 31385 313.8 239.3 223.4 33480 334.8

POWER REQUIREMENTS - SEA LEVEL TO 3000 FT, 60 HZ Blower Motor hp (except gas) Gas Models (only) Oil Pump Motor, hp No. 2 Oil Oil Pump Motor, hp No. 6 Oil Oil Heater kW No. 6 Oil Air Compressor Motor hp (Oil firing Only) 5 5 1/2 1/2 5 7-1/2 5 1/2 1/2 5 15 10 1/2 1/2 5 7-1/2 7-1/2 1/2 1/2 7-1/2 10C 7-1/2I 3/4 1/2 7-1/2 15D 15 3/4 3/4 7-1/2 10C 10C 3/4 3/4 7-1/2 7-1/2 15E 15E 3/4 3/4 7-1/2K

20F 20F 3/4 3/4 7-1/2K 7-1/2

30G 30G 1 3/4 7-1/2K 7-1/2

40L 40L 1 3/4 7-1/2K 7-1/2

50H 50H 1 3/4 7-1/2K 7-1/2

Air Compressor Belt-Driven From Blower Motor

7-1/2

NOTES: 1. For altitudes above 3000 ft, contact your local Cleaver-Brooks authorized representative for verification of blower motor hp. A. Based on 140,000 Btu/gal. B. Based on 150,000 Btu/gal. C.15 hp above 2500 ft. D. 20 hp above 2500 ft. E. 20 hp above 2000 ft.

F. 30 hp above 2500 ft. G. 40 hp above 2000 ft. H. 60 hp above 3000 ft. I. 10 hp above 2500 ft. J. Sea level to 2,500 ft for 300 and 350 Hp sizes. K. 10 kW on low pressure. L. 50 hp above 2500 ft.

A2-507-02

Model CB BoilersTable A2-3. Model CB Hot Water Boiler Ratings (15 - 100 hp)BOILER HP 15c 20c 30c 40c 50 60 70 80

Firetube Boilers

100A

100

125A

RATINGS - SEA LEVEL TO 3000 FT Rated Cap Btu Output (1000 Btu/hr) 502 670 1004 1339 1674 2009 2343 2678 3348 3348 4184

APPROXIMATE FUEL CONSUMPTION AT RATED CAPCITY Light Oil (gph)A Heavy Oil (gph)B Gas (cfh) MBtu- nat Gas (Therm/hr) 4.5 625 6.3 6.0 835 8.4 9.0 1255 12.6 12.0 1675 16.8 15.0 14.0 2095 21.0 18.0 16.5 2510 25.1 21.0 19.5 2930 29.3 24.0 22.5 3350 33.5 30.0 28.0 4185 41.9 30.0 28.0 4185 41.9 37.5 35.0 5230 52.3

POWER REQUIREMENTS - SEA LEVEL TO 3000 FT, 60 HZ Blower Motor hp (except gas) Gas Models (only) Oil Pump Motor, hp No. 2 Oil Oil Pump Motor, hp No. 6 Oil Oil Heater kW No. 6 Oil Air Compressor Motor hp (Oil firing Only) 1 1 1 1 1-1/2 1-1/2 2 2 2 2 1/3 1/3 5 2 2 2 1/3 1/3 5 2 2 2 1/3 1/3 5 2 2D 2D 1/3 1/3 5 2 3 3 1/3 1/3 5 2 3 3 1/3 1/3 5 2 3 3 1/2 1/2 5 2

Belt-Driven From Blower -

Air Compressor Belt-Driven from Blower Motor

NOTES: 1. For altitudes above 3000 ft, contact your local Cleaver-Brooks authorized representative for verification of blower motor hp. A. Based on 140,000 Btu/gal. B. Based on 150,000 Btu/gal. C. No. 6 Oil not available in 15-40 hp range. D. 3 hp above 2000 ft.

Table A2-4. Model CB Hot Water Boiler Ratings (125 - 800 hp)BOILER HP 150 175A 200 250 300 350 400 500 600 700J

750

800

RATINGS - SEA LEVEL TO 3000 FT Rated Cap. Btu Output (1000 Btu/hr) 5021 5858 6695 8369 10043 11716 13390 16738 20085

23432

25106

26779

APPROXIMATE FUEL CONSUMPTON AT RATED CAPCITY Light Oil (gph)A 45.0 42.0 6280 62.8 52.5 49.0 7320 73.2 60.0 56.0 8370 83.7 74.5 69.5 10460 104.6 89.5 83.5 12555 125.5 104.5 97.5 14650 146.5 119.5 111.5 16750 167.5 149.5 139.5 20925 209.3 179.5 167.5 25100 251.0 209.0 195.5 29300 293.0 224.2 209.3 31385 313.8 239.3 223.4 33480 334.8

Heavy Oil (gph)B Gas (cfh) MBtu-Natural Gas (Therm/hr)

POWER REQUIREMENTS - SEA LEVEL TO 3000 FT, 60 HZ Blower Motor hp (except gas) Gas Models (only) Oil Pump Motor, hp No. 2 Oil Oil Pump Motor, hp No. 6 Oil Oil Heater kW No. 6 Oil Air Compressor Motor hp (Oil firing Only) NOTES: 1. For altitudes above 3000 ft, contact your local Cleaver-Brooks authorized representative for verification of blower motor hp. A. Based on 140,000 Btu/gal. B. Based on 150,000 Btu/gal. C. 15 hp above 2500 ft. D. 20 hp above 2500 ft. E. 20 hp above 2000 ft. 7-1/2 5 1/2 1/2 5 7-1/2 5 1/2 1/2 5 15 10 1/2 1/2 5 7-1/2 7-1/2 1/2 1/2 7-1/2 10C 7-1/2I 3/4 1/2 7-1/2 15D 15 3/4 3/4 7-1/2 10C 10C 3/4 3/4 10 7-1/2 15E 15E 3/4 3/4 10 7-1/2 20F 20F 3/4 3/4 10 7-1/2 30G 30G 1 3/4 10 7-1/2 40K 40K 1 3/4 10 7-1/2 50H 50H 1 3/4 10 7-1/2

F. 30 hp above 2500 ft. G. 40 hp above 2000 ft. H. 60 hp above 3000 ft. I. 10 hp above 2500 ft. J. Sea level to 2,500 ft for 300 and 350 hp sizes. K. 50 hp above 2500 ft.

A2-607-02

Firetube Boilers

Model CB Boilers

Table A2-5. Steam Boiler Safety Valve OpeningsVALVE SETTING BOILER HP 15 PSIG STEAM NO. OF VALVES REQ'D OUTLET SIZE (IN.) 100 PSIG STEAM NO. OF VALVES REQ'D OUTLET SIZE (IN.) 125 PSIG STEAM NO. OF VALVES REQ'D OUTLET SIZE (IN.) 150 PSIG STEAM NO. OF VALVES REQ'D OUTLET SIZE (IN.) 200 PSIG STEAM NO. OF VALVES REQ'D OUTLET SIZE (IN.) 250 PSIG STEAM NO. OF VALVES REQ'D OUTLET SIZE (IN.)

15 20 25 30 40 50 60 70 80 100 125 150 200 250 300 350 400 500 600 700

1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 3 3 3 4 5

1-1/2 1-1/2 2 2 2-1/2 2-1/2 2 2 2-1/2 2-1/2 3 3 2-1/2 (1) 2-1/2 (1) 3 3 (1) 2 (2) 3 (2) 3 (1) 2-1/2 3 (1) 2-1/2 (3) 3 (3) 3 (2)2-1/2 (3) 3 (2)2-1/2 (3) 3 (2)2-1/2

1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 3 3 3 4 5

1 1 1 1-1/4 1-1/4 1-1/2 1-1/2 2 2 2 1-1/2 (1) 2 (1) 1-1/2 2 (1) 2-1/2 (1) 2 2-1/2 (1) 2-1/2 (2) 2 (1) 2 (2) 2-1/2 2-1/2 (3) 2-1/2 (1) 2 (3) 2-1/2 (2) 2 (3) 2-1/2 (2) 2 (3) 2-1/2 (2) 2

1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 3 3 4

3/4 1 1 1 1-1/4 1-1/2 1-1/2 1-1/2 1-1/2 2 (1) 1-1/2 (1) 1-1/4 1-1/2 (2) 1-1/2 2 (1) 2-1/2 (1) 2 2-1/2 2-1/2 (2) 2-1/2 (1) 2 2-1/2 (3) 2-1/2 (1) 2 (3) 2-1/2 (1) 2 (3) 2-1/2 (1) 2

1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 3 3

3/4 3/4 1 1 1 1-1/4 1-1/4 1-1/4 1-1/2 1-1/2 (1) 1-1/2 (1) 1-1/4 (1) 1-1/2 (1) 1-1/4 2) 1-1/2 (1) 2 (1) 1-1/2 2 (1) 2-1/2 (1) 2 (1) 2-1/2 (1) 2 2-1/2 2-1/2 (1) 2 (2) 2-1/2 (1) 2 (2) 2-1/2 (1) 2 (2) 2-1/2 (1)2

1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2

3/4 3/4 3/4 3/4 1 1 1-1/4 1-1/4 1-1/4 1-1/2 (1) 1-1/4 (1) 1 1-1/4 (1) 1-1/2 (1) 1-1/4 1-1/2 (1) 2 (1) 1-1/2 2 2 (1) 2-1/2 (1) 2 2-1/2 2-1/2

1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2

3/4 3/4 3/4 3/4 1 1 1 1-1/4 1-1/4 1-1/4 1 (1) 1 (1) 1-1/4 (2) 1-1/4 (1) 1-1/2 (1) 1-1/4 1-1/2 (1) 1-1/2 (1)2 (1) 2 (1) 1-1/2 2 (1) 2 (1) 2-1/2 2-1/2

750

5

5

4

3

2

2-1/2

2

2-1/2

800

5

5

4

3

2

2-1/2

2

2-1/2

NOTE: Valve manufacturers are Kunkle, Consolidated or Conbraco, depending on availability.

A2-707-02

Model CB BoilersTable A2-6. Hot Water Boiler Relief Valve OpeningsVALVE SETTING BOILER HP 15 20 25 30 40 50 & 50A 60 70 80 100 100A 125 125A 150 175A 200 250 300 350 400 500 600 700 750 800 30 PSIG HW NO. OF VALVES REQ'D 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 3 3 4 4 5 5 5 OUTLET SIZE (IN.) 1 1 1-1/4 1-1/4 1-1/4 2 2 2 2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 (1) 1 (1) 2-1/2 (1) 2-1/2 (1) 1-1/4 (1) 2 (1) 2-1/2 2-1/2 (2) 2-1/2 (1) 1 (1) 2 (2) 2-1/2 (1) 1 (3) 2-1/2 (3) 2-1/2 (1) 2 (1) 1 (4) 2-1/2 (1) 1 (4) 2-1/2 (1) 1 (4) 2-1/2 60 PSIG HW NO. OF VALVES REQ'D 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 3 3 3 3 OUTLET SIZE (IN.) 1 1 1 1 1 1-1/4 1-1/4 2 2 2 2 2 2 2-1/2 2-1/2 2-1/2 2-1/2 (1) 1 (1) 2-1/2 (1) 2-1/2 (1) 2 (1) 2 (1) 2-1/2 (2) 2-1/2 (1) 1-1/4 (2) 2-1/2 (1) 2 (2) 2-1/2 (1) 2 (2) 2-1/2 (1) 2 (2) 2-1/2 100 PSIG HW NO. OF VALVES REQ'D 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 OUTLET SIZE (IN.) 1 1 1 1 1 1 1 1-1/4 1-1/4 1-1/4 1-1/4 2 2 2 2 2 2-1/2 2-1/2 2-1/2 (1) 1 (1) 2-1/2 (1) 2-1/2 (1) 1-1/4 (1) 2 (1) 2-1/2 (2) 2-1/2 (2) 2-1/2 (2) 2-1/2

Firetube Boilers

125 PSIG HW NO. OF VALVES REQ'D 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 OUTLET SIZE (IN.) 1 1 1 1 1 1 1 1 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4 2 2 2 2 2-1/2 2-1/2 2-1/2 (1) 1 (1) 2-1/2 (1) 2-1/2 (1) 1-1/4 (1) 2-1/2 (1) 2 (1) 2-1/2 (1) 2 (1) 2-1/2 (1) 2

NOTES: 1.Hot water relief valves are Kunkle #537. 2. BHP followed by A designates hot water boilers furnished in a smaller vessel size with additional tubes in the upper portion of the vessel.

A2-807-02

Firetube Boilers

Model CB Boilers

NOTES

A2-907-02

Model CB Boilers

Firetube Boilers

NOTE: ALLOW 3 FEET FOR DOOR SWING PER NEC

BOILER HP

DIM

15

20

30 LENGTHS

40

50

60

70

80

100

Overall Shell Base Frame Front Head Extension Rear Head Extension Front Ring Flange to Nozzle - 15 psig Front Ring Flange to Nozzle - 150 psig Ring Flange to Base

A B C D E F F G

96-5/8 62-5/8 59 18-1/2 15-1/2 36 36 1-13/16

96-5/8 62-5/8 59 18-1/2 15-1/2 36 36 1-13/16

114-5/8 80-5/8 77 18-1/2 15-1/2 45 45 1-13/16

140-5/8 106-5/8 103 18-1/2 15-1/2 57 57 1-13/16

129 92 91 18-1/2 18-1/2 46 46 5/8

129 92 91 18-1/2 18-1/2 46 46 1/2

168 131 130 18-1/2 18-1/2 65-1/2 72-1/2 1/2

168 131 130 18-1/2 18-1/2 65-1/2 72-1/2 1/2

187 150 148 18-1/2 18-1/2 75 82 1/2

WIDTHS Overall ID, Boiler Center to Water Column Center to Outside Hinge Center to Lagging Center to Auxiliary LWCO Base, Outside Base, Inside I J K KK L LL M N 61 36 33 22 20 28 28 22 61 36 33 22 20 28 28 22 61 36 33 22 20 28 28 22 61 36 33 22 20 28 28 22 73 48 39 29 27 34 37-5/8 29-5/8 73 48 39 29 27 34 37-3/8 29-5/8 73 48 39 29 27 34 37-3/8 29-5/8 73 48 39 29 27 34 37-3/8 29-5/8 73 48 39 29 27 34 37-3/8 29-5/8

Figure A2-1. Model CB Steam Boiler Dimensions and Weights (15 and 150 psig Design Pressure 15 to 100 hp) Sheet 1 of 2

A2-1007-02

Firetube BoilersBOILER HP DIM 15 20 30 HEIGHTS Base to Steam Outlet (15 psig only) Overall Base to Vent Outlet Base to Steam Outlet (150 psig only) Height of Base Base to Bottom of Boiler PL OO O PH Q R 50-1/4 66 53-1/2 50-1/4 8 12 50-1/4 66 53-1/2 50-1/4 8 12 50-1/4 66 53-1/2 50-1/4 8 12 50-1/4 66 53-1/2 50-1/4 8 12 64-3/4 78-3/4 70 66-31/2 12 16 64-3/4 78-3/4 70 66-1/2 12 16 40 50 60

Model CB Boilers70 80 100

64-3/4 78-3/4 70 66-1/2 12 16

64-3/4 78-3/4 70 66-1/2 12 16

64-3/4 78-3/4 70 64-3/4 12 16

BOILER CONNECTIONS Chemical Feed Feedwater, Right and Left Low Pressure (15 psig only) Steam Nozzle Drain, Front and Rear High Pressure (150 psig only) Surface Blowoff, Top CL Steam Nozzle Blowdown, Front and Rear H S U W T Y W 1 1 4 1 1 1-1/2 1 1 1 4 1 1 1-1/2 1 1 1 4 1 1 2 1 1 1 6A 1-1/4 1 2 1 1 1-1/4 6A 1-1/4 1 3 1-1/4 1 1-1/4 6A 1-1/4 1 3 1-1/4 1 1-1/4 6A 1-1/2 1 3 1-1/4 1 1-1/4 6A 1-1/2 1 3 1-1/4 1 1-1/4 8A 1-1/2 1 4B 1-1/4

VENT STACK Diameter (flgd connection) Front Ring Flange to Vent CL BB CC 6 4 6 4 8 5 8 5 10 6 10 6 12 7 12 7 12 7

MINIMUM CLEARANCES Rear Door SwingC

DD EE FF GG

44 44 56 46

44 44 56 46

44 44 74 64

44 44 100 90

55 55 84 74

55 55 84 74

55 55 123 113

55 55 123 113

55 55 142 132

Front Door SwingC Tube Removal, Rear Tube Removal, Front

MINIMUM BOILER ROOM LENGTH ALLOWING FOR DOOR SWING AND TUBE REMOVAL FROM: Rear of Boiler Front of Boiler Thru Window or Doorway RR RF RD 163 153 151 163 153 151 199 189 169 251 241 195 231 221 202 231 221 202 309 299 241 309 299 241 347 337 260

WEIGHT IN LBS Normal Water Capacity Approx. Ship Wgt - 15 psig Approx. Ship Wgt - 150 psig Approx. Ship Wgt - 200 psig 1340 3000 3100 3300 1300 3100 3200 3400 1710 3650 3800 4100 2290 4350 4500 4700 3130 6900 7000 7400 2920 7000 7200 7600 4620 8100 8800 9300 4460 8200 9000 9500 5088 9000 9500 10000

NOTES: 1. Air compressor belt driven from blower motor on sizes 15 thru 40 2. Air compressor module on sizes 50 thru 100 hp. 3. Accompanying dimensions, while sufficiently accurate for layout purposes, must be confirmed for construction by certified dimension prints. A. ANSI 150 psig flange. B. ANSI 300 psig flange. C. 15 thru 100 hp standard hinged door.

Figure A2-1. Model CB Steam Boiler Dimensions and Weights (15 and 150 psig Design Pressure 15 to 100 hp) Sheet 2 of 2

A2-1107-02

Model CB Boilers

Firetube Boilers

NOTE: ALLOW 3 FEET FOR DOOR SWING PER NEC

BOILER HP

DIM

125

150

200

250

300

350

400

500

600

700

750

800

LENGTHS Overall Shell Base Frame Front Head Extension Rear Head Extension Front Ring Flange to Nozzle 15 psig Front Ring Flange to Nozzle 150 psig Ring Flange to Base A B C D E F F G 174-1/2 125 124 30 19-1/2 62-1/2 55 1/2 199-/12 149 148 31 19-1/2 74-1/2 66 1/2 232-1/2 180 179 33 19-1/2 90 78 1/2 197 144 143 29 24 72 59-1/2 1/2 WIDTHS Overall ID, Boiler Center to Water Column Center to Outside Hinge Center to Lagging Center to Auxiliary LWCO Base, Outside Base, Inside I J K KK L LL M N 85 60 45 35 33 40 52-1/2 44-1/2 85 60 45 35 33 40 52-1/2 44-1/2 85 60 45 35 33 40 52-1/2 44-1/2 103 78 54 51 42 49 64-3/8 52-3/8 103 78 54 51 42 49 64-3/8 52-3/8 103 78 54 51 42 49 64-3/8 52-3/8 123 96 64 62 51 59 72 56 123 96 64 62 51 59 72 56 123 96 64 62 51 59 72 56 123 96 64 62 51 59 72 56 123 96 64 62 51 59 72 56 123 96 64 62 51 59 72 56 227 171 170 32 24 85-1/2 73 1/2 257 201 200 32 24 100-1/2 88 1/2 210 152 151 26 32 76 62 1/2 244 186 185 26 32 93 79 1/2 284 222 221 30 32 111 97 1/2 317 255 254 30 32 127-1/2 127-1/2 1/2 319 255 254 32 32 127-1/2 127-1/2 1/2 319 255 254 32 32 127-1/2 127-1/2 1/2

Figure A2-2. Model CB Steam Boiler Dimensions and Weights (15 and 150 psig Design Pressure 125 to 800 hp) Sheet 1 of 2

A2-1207-02

Firetube Boilers

Model CB Boilers

BOILER HP

DIM

125

150

200

250 HEIGHTS

300

350

400

500

600

700

750

800

Base to Steam Outlet (15 psig only) Overall Base to Vent Outlet Base to Steam Outlet (150 psig only) Davit (Front) Davit (Rear) Height of Base Base to Bottom of Boiler

PL OO O PH DF DR Q R

77 88 85 77 84-3/4 12 16

77 88 85 77 84-3/4 12 16

77 88 85 77 84-3/4 12 16

96 106 106 96 104 104 10 17

96 106 106 96 104 104 10 17

96 106 106 96 104 104 10 17

116 126 126 116 125 126 12 19

116 126 126 116 125 126 12 19

116 126 126 116 125 126 12 19

116 126 126 116 125 126 12 19

116 126 126 116 125 126 12 19

116 126 126 116 125 126 12 19

BOILER CONNECTIONS Chemical Feed Feedwater, Right and Left Low Pressure (15 psig only) Steam Nozzle (Note A) Drain, Front and Rear High Pressure (150 psig only) Surface Blowoff, Top CL Steam Nozzle (Note B) Blowdown, Front and Rear H S U W T Y W 1 1-1/2 8 1-1/2 1 4 1-1/2 1 1-1/2 8 1-1/2 1 4 1-1/2 1 2 10 2 1 4 1-1/2 1 2 10 2 1 6 1-1/2 1 2 12 2 1 6 1-1/2 1 2-1/2 12 2 1 6 1-1/2 1 2-1/2 12 2 1 6 2 1 2-1/2 12 2 1 8 2 1 2-1/2 12 2 1 8 2 1 2-1/2 12 2 1 8 2 1 2-1/2 12 2 1 8 2 1 2-1/2 12 2 1 8 2

VENT STACK Diameter (flgd. connection) Front Ring Flange to Vent CL BB CC 16 9 16 9 16 9 20 10-1/2 20 10-1/2 20 10-1/2 24 12-1/2 24 12-1/2 24 12-1/2 24 12-1/2 24 12-1/2 24 12-1/2

MINIMUM CLEARANCES Rear Door Swing Front Door Swing Tube Removal, Rear Tube Removal, Front DD EE FF GG 32C 67 115 103 32C 67 139 127 32C 67 170 158 43C 89C 131 116 43C 89C 157 142 43C 89C 187 172 53C 108C 135 116 53C 108C 169 151 53C 108C 205 187 53C 108C 238 220 53C 108C 238 220 53C 108C 238 220

MINIMUM BOILER ROOM LENGTH ALLOWING FOR DOOR SWING AND TUBE REMOVAL FROM: Rear of Boiler Front of Boiler Thru Window or Doorway RR RF RD 307 260 224 355 308 248 417 370 279 364 303 275 417 356 302 477 416 332 395 322 313 463 390 347 535 462 383 601 528 416 601 528 416 601 528 416

WEIGHT IN LBS Normal Water Capacity Approx. Ship Wgt - 15 psig Approx. Ship Wgt - 150 psig Approx. Ship Wgt - 200 psig 5750 12200 12800 13400 7250 12900 13800 14500 8625 15200 16300 17100 10670 21800 23400 25200 13000 24000 26000 28000 15465 27300 28500 30000 15340 33500 36500 38300 19300 38400 41400 44000 23425 44000 47000 50500 27790 51400 54100 57700 27790 51400 54100 57700 27790 51400 54100 57700

NOTES: 1. Air compressor belt driven from blower motor on sizes 125 thru 350 hp. 2. Control Panel relocation on boilers 250 hp and up. 3. Air compressor module on sizes 400 thru 800 hp. 4. Accompanying dimensions, while sufficiently accurate for layout purposes, must be confirmed for construction by certified dimension prints. A. ANSI 150 psig flange. B. ANSI 300 psig flange. C. Davit equipped, standard, 125 - 800 hp (rear door). D. Davit equipped, standard, 250- 800 hp (front door)

Figure A2-2. Model CB Steam Boiler Dimensions and Weights (15 and 150 psig Design Pressure 125 to 800 hp) Sheet 2 of 2

A2-1307-02

Model CB Boilers

Firetube Boilers

LWCO

NOTE: ALLOW 3 FEET FOR DOOR SWING PER NEC

BOILER HP

DIM

15

20

30 LENGTHS

40

50

60

70

80/ 100A

100/ 125A

Overall Shell Base Frame Front Head Ext. Rear Head Ext. Front Ring Flange to Return Front Ring Flange to Outlet Ring Flange to Base

A B C D E F G H

97 62-5/8 59 18-1/2 15-1/2 43-5/8 55-1/8 1-13/16

97 62-5/8 59 18-1/2 15-1/2 43-5/8 55-1/8 1-13/16

114-5/8 80-5/8 77 18-1/2 15-1/2 62 73-1/8 1-13/16

140-5/8 106-5/8 103 18-1/2 15-1/2 81 98-1/2 1-13/16

129 92 91 18-1/2 18-1/2 69 84-5/8 5/8

129 92 91 18-1/2 18-1/2 69 84-5/8 5/8

168 131 130 18-1/2 18-1/2 108 123-5/8 5/8

168 131 130 18-1/2 18-1/2 108 123-5/8 5/8

187 150 148 18-1/2 18-1/2 127 142-5/8 1

WIDTHS Overall ID, Boiler Center to Entrance Box Center to Outside Hinge Center to Lagging Base, Outside Base, Inside I J K KK L M N 48-3/4 36 28-3/4 22 20 28 22 48-3/4 36 28-3/4 22 20 28 22 48-3/4 36 28-3/4 22 20 28 22 48-3/4 36 28-3/4 22 20 28 22 63 48 36 29 27 37-5/8 29-5/8 63 48 36 29 27 37-5/8 29-5/8 63 48 36 29 27 37-5/8 29-5/8 63 48 36 29 27 37-5/8 29-5/8 63 48 36 29 27 37-5/8 29-5/8

Figure A2-3. Model CB Hot Water Boiler Dimensions (30 psig and 125 psig Design Pressure 15 to 100 hp) - Sheet 1 of 2

A2-1407-02

Firetube Boilers

Model CB Boilers

BOILER HP

DIM

15

20

30 HEIGHTS

40

50

60

70

80/ 100A

100/ 125A

Overall Base to Vent Outlet Base to Return and outlet Davit (Front) Davit (Rear) Height of Base Base to bottom of boiler

OO O P DF DR Q R

66 53-1/2 50 8 12

66 53-1/2 50 8 12

66 53-1/2 50 8 12

66 53-1/2 50 8 12

72-5/8 70 67 12 16

72-5/8 70 67 12 16

72-5/8 70 67 12 16

72-5/8 70 67 12 16

72-5/8 70 67 12 16

BOILER CONNECTION Waterfill Conn. Right & Left Water Return - Threaded Water Outlet - ThreadedA Air Vent Drain, Front and Rear Auxiliary Connection S T U v W X 1 2-1/2 2-1/2 1 1 1 1 2-1/2 2-1/2 1 1 1 1 3 3 1 1 1 1 3 3 1 1-1/4 1 1-1/4 4 4 1-1/4 1-1/4 1 1-1/4 4 4 1-1/4 1-1/4 1 1-1/4 4 4 1-1/4 1-1/2 1 1-1/4 4 4 1-1/4 1-1/2 1 1-1/4 4 4 1-1/4 1-1/2 1

VENT STACK Diameter (flgd. connection) Front Ring Flange to vent CL BB CC 6 4 6 4 8 5 8 5 10 6 10 6 12 7 12 7 12 7

MINIMUM CLEARANCES Rear Door Swing Front Door Swing Tube Removal, Rear Tube, Removal, Front DD EE FF GG 44 44 56 46 44 44 56 46 44 44 74 64 44 44 100 90 55 55 84 74 55 55 84 74 55 55 123 113 55 55 123 113 55 55 142 132

MINIMUM BOLER ROOM LENGTH ALLOWING FOR DOOR SWING AND TUBE REMOVAL FROM: Rear of Boiler Front of Boiler Thru Window or Doorway RR RF RD 163 153 151 163 153 151 199 189 169 251 241 195 231 221 202 231 221 202 309 299 241 309 299 241 347 337 260

WEIGHT IN LBS Water Capacity Flooded Approx. Ship. Wgt. 30 psig Approx. Ship. Wgt. 125 psig 1500 3000 3300 1460 3100 3400 1915 3650 3880 2585 4350 4580 3665 6800 7100 3500 7000 7300 5420 8000 8350 5250 8100 8450 5960 8800 9150

NOTES: 1. Accompanying dimensions and ratings while sufficiently accurate for layout purposes, must be confirmed for construction by certified dimension prints. 2. Air compressor belt driven from blower motor on sizes 15 thru 40 hp. 3. Air compressor module on sizes 50 thru 100 hp. 4. 15 - 100 hp, hinged door standard. 5. Add 370lbs to the 80 hp ship weight for 100A and 485 lbs to the 100 hp ship weight for the 125A. A. Dip Tube included.

Figure A2-3. Model CB Hot Water Boiler Dimensions (30 psig Design Pressure 15 to 100 hp) - Sheet 2 of 2 A2-1507-02

Model CB Boilers

Firetube Boilers

LWCO

NOTE: ALLOW 3 FEET FOR DOOR SWING PER NEC

A

BOILER HP

DIM

125

150/ 175A

200

250

300

350

400

500

600

700

750

800

LENGTHS Overall Shell Base Frame Front Head Extension Rear Head Extension Front Ring Flange to Return Front Ring Flange to Outlet Ring Flange to Base A B C D E F G H 174-1/2 199-1/2 232-1/2 125 124 30 19-1/2 91 114 1/2 149 148 31 19-1/2 102 136 1/2 180 179 33 19-1/2 131 167 1/2 197 144 143 29 24 227 171 170 32 24 257 201 200 32 24 210 152 151 26 32 244 186 185 26 32 139 170 1/2 284 222 221 30 32 175 206 1/2 317 255 254 30 32 207 239 1/2 319 255 254 32 32 207 239 1/2 319 255 254 32 32 207 239 1/2

104-1/2 131-1/2 161-1/2 111-1/2 131 1/2 WIDTHS 158 1/2 188 1/2 146 1/2

Overall ID, Boiler Center to Entrance Box Center to Outside Hinge Center to Lagging Base, Outside Base, Inside

I J K KK L M N

75-1/2 60 42-1/2 35 33 52-1/2 44-1/2

75-1/2 60 42-1/2 35 33 52-1/2 44-1/2

75-1/2 60 42-1/2 35 33 52-1/2 44-1/2

93 78 51 51 42 64-3/8 52-3/8

93 78 51 51 42 64-3/8 52-3/8

93 78 51 51 42 64-3/8 52-3/8

113 96 62 62 51 72 56

113 96 62 62 51 72 56

113 96 62 62 51 72 56

113 96 62 62 51 72 56

113 96 62 62 51 72 56

113 96 62 62 51 72 56

Figure A2-4. Model CB Hot Water Boiler Dimensions (30 psig Design Pressure - 125 - 800 hp) - Sheet 1 of 2

A2-1607-02

Firetube Boilers

Model CB Boilers

BOILER HP

DIM

125

150/ 175A

200

250 HEIGHTS

300

350

400

500

600

700

750

800

Overall Base to Vent Outlet Base to Return and Outlet Davit (Front) Davit (Rear) Height of Base Base to Bottom of Boiler

OO O P DF DR Q R

88 85 77 84-3/4 12 16

88 85 77 84-3/4 12 16

88 85 77 84-3/4 12 16

106 106 96 104 104 10 17

106 106 96 104 104 10 17

106 106 96 104 104 10 17

126 126 116 125 126 12 19

126 126 116 125 126 12 19

126 126 116 125 126 12 19

126 126 116 125 126 12 19

126 126 116 125 126 12 19

126 126 116 125 126 12 19

BOILER CONNECTION Waterfill Conn. Right & Left Water Return FlangeA Water Outlet Flange Air Vent Drain, Front and Rear Auxiliary Connection S T U V W X 1-1/2 6 6 1-1/2 1-1/2 1 1-1/2 6 6 1-1/2 1-1/2 1 2 6 6 1-1/2 2 1 2 8 8 1-1/2 2 1-1/4 VENT STACK Diameter (flgd. connection) Front Ring Flange to vent CL BB CC 16 9 16 9 16 9 20 10-1/2 20 10-1/2 20 10-1/2 24 12-1/2 24 12-1/2 24 12-1/2 24 12-1/2 24 12-1/2 24 12-1/2 2 8 8 1-1/2 2 1-1/4 2-1/2 8 8 1-1/2 2 1-1/4 2-1/2 10 10 2 2 1-1/4 2-1/2 10 10 2 2 1-1/4 2-1/2 12 12 2 2 1-1/4 2-1/2 12 12 2 2 1-1/4 2-1/2 12 12 2 2 1-1/4 2-1/2 12 12 2 2 1-1/4

MINIMUM CLEARANCES Rear Door Swing Front Door Swing Tube Removal, Rear Tube, Removal, Front DD EE FF GG 32B 67 115 103 32B 67 139 127 32B 67 170 158 43B 89B 131 116 43B 89B 157 142 43B 89B 187 172 53B 108B 135 117 53B 108B 169 151 53B 108B 205 187 53B 108B 238 220 53B 108B 238 220 53B 108B 238 220

MINIMUM BOILER ROOM LENGTH ALLOWING FOR DOOR SWING AND TUBE REMOVAL FROM: Rear of Boiler Front of Boiler Thru Window or Doorway RR RF RD 307 260 224 355 308 248 417 370 279 364 303 275 417 356 302 477 416 332 395 322 313 463 390 347 535 462 383 601 528 416 601 528 416 601 528 416

WEIGHT IN LBS Water Capacity Flooded Approx. Ship. Wgt. 30 psig Approx. Ship. Wgt. 125 psig 7670 12100 12500 9295 12800 13200 11130 15100 15500 13880 21700 22500 16840 23900 24700 20090 27200 28000 20630 33400 34400 25925 38300 39300 31510 43900 44900 36600 51300 52300 36600 51300 52300 36600 51300 52300

NOTES: 1. Accompanying dimensions and ratings while sufficiently accurate for layout purposes, must be confirmed for construction by certified dimension prints. 2. Control panel relocated on boilers 250 hp and up. 3. Air compressor belt driven from blower motor on sizes 125 thru 350 hp. 4. Air compressor module on sizes 400 thru 800 hp. 5. Davited front doors are standard on 250 - 800 hp. 6. Add 480 lbs to the 150 hp ship weight for 175A. A. Dip Tube included. B. Davited rear doors are standard on 125 - 800 hp units.

Figure A2-4. Model CB Hot Water Boiler Dimensions (30 psig Design Pressure - 125 - 800 hp) - Sheet 2 of 2

A2-1707-02

Model CB Boilers

Firetube Boilers

DIMENSION (INCHES) BOILER HP A 15 - 40, 50A 50 - 100, 100A, 125A 125 - 200, 175A 250 - 350 400 - 800 20 27 33 42 51 B 36 48 55 69 88 C 28 38 45 58 71 D 45 60 68 86 109 E 20 26 32 43 53 PLAN VIEW

NOTE: 1. Dimensions in inches. 2. 15 - 100 hp (100A & 125A) boilers are standardly equipped with hinges. Davit available as an option.

Figure A2-5. Space Required to Open Rear Head on Model CB Boilers Equipped with Davits

Figure A2-6. Lifting Lug Location, Model CB Boilers - Sheet 1 of 2

A2-1807-02

Firetube BoilersBOILER HP 15 Steam Hot Water 20 Steam Hot Water 25 Steam Hot Water 30 Steam Hot Water 40 Steam Hot Water 50A Water 50 60 70 80 100 100A 125A 125 150 175A 200 250 All All All All All Hot Water Hot Water All All Hot Water All Steam Hot Water 300 Steam Hot Water 350 Steam Hot Water 400 Steam Hot Water 500 Steam Hot Water 600 Steam Hot Water 700 Steam Hot Water 750 Steam Hot Water 800 Steam Hot Water B B B B B B B B B A B B B B B B B B B B B B B B B B B B B B 50-1/2 68 68 68 68 68 68 68 80-1/4 80-1/4 80-1/4 80-1/4 99 99 99 99 99 99 119 119 119 119 119 119 119 119 119 119 119 119 12 18 18 27 27 27 27 27 29-3/4 29-3/4 29-3/4 29-3/4 36 36 36 36 36 36 34-1/2 34-1/2 34-1/2 34-1/2 34-1/2 34-1/2 34-1/2 34-1/2 34-1/2 34-1/2 34-1/2 34-1/2 82-3/4 57 57 67 67 86 67 100 70-1/2 83-1/2 83-1/2 114-1/2 72 72 99 99 129 129 83 83 117 117 153 153 186 186 186 186 186 186 VIEW A B A B A B A B A B ALL DIMENSIONS IN INCHES A 51-3/4 50-1/2 51-3/4 50-1/2 51-3/4 50-1/2 51-3/4 50-1/2 51-3/4 50-1/2 B 12 12 12 12 12 12 12 12 12 12 C 38-3/4 38-3/4 38-3/4 38-3/4 56-3/4 56-3/4 56-3/4 56-3/4 82-3/4 82-3/4

Model CB Boilers

D 6 6 6 6 6

E 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2

6 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 11 11 11 11 11 11 11 11 11 11 11

2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

NOTE: 1. A, B and C Dimensions may vary by 1/2 inch. 2. BHP followed by A designates hot water boilers furnished in a smaller vessel size with additional tubes in upper portion of vessel.

Figure A2-6. Lifting Lug Location, Model CB Boilers - Sheet 2 of 2

A2-1907-02

Model CB Boilers

Firetube Boilers

BOILER HP 15-20 25-30 40-50A 50-60 70-80, 100A 100, 125A 125 150, 175A 200 250 300 350 400 500 600 700-750-800

A 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

B 8 8 8 8 8 8 9 9 9 12 12 12 14 14 14 14

C 59 77 103 91 130 148 124 148 179 143 170 200 151 185 221 254

D 17 17 17 26 26 26 39-1/2 39-1/2 39-1/2 46 46 46 50 50 50 50

E 33 33 33 42 42 42 57-1/2 57-1/2 57-1/2 70 70 70 78 78 78 78

F 3 3 3 4 4 4 4 4 4 6 6 6 8 8 8 8

G 22 22 22 29-5/8 29-5/8 29-5/8 44-1/2 44-1/2 44-1/2 52-3/8 52-3/8 52-3/8 56 56 56 56

X 9-3/4 9-3/4 9-3/4 8-1/4 8-1/4 8-1/4 10-1/4 10-1/4 10-1/4 22-1/2 22-1/2 22-1/2 24-1/2 24-1/2 24-1/2 24-1/2

NOTE: 1. All numbers in table are in inches. 2. 6-inch high mounting piers recommended for use beneath the boiler base frame. The use of these piers provides increased inspection accessibility to the piping beneath the boiler and added height for washing down the area beneath the boiler.

Figure A2-7. Model CB Boiler Mounting Piers

A2-2007-02

Firetube Boilers

Model CB Boilers4. Any efciency verication testing will be based on the stack loss method. When specifying the efciencies in the tables, be sure to include the specic guarantee conditions to maximize the effectiveness of your efciency specication. If you have any questions regarding the efciency specications, please contact your local Cleaver-Brooks authorized representative. For efciencies and stack temperatures at operating pressures not listed, follow these procedures: When the operating steam pressure is between 10 psig and 125 psig, interpolate the values from the efciency tables. When the operating steam pressure is above 125 psig, estimated efciency can be calculated as follows: Example: Boiler: 350 hp. Fuel: natural gas. Operating steam pressure: 200 psig. Find the fuel-to-steam efciency at 100% ring rate. From Table A2-8 for a 350 hp boiler operating at 100% ring rate and an operating steam pressure of 125 psig, the efciency is 82.5%. Using Figure A2-8, note that the stack temperature increases 36 F at the higher operating pressure. To estimate boiler efciency, use this rule of thumb: For every 40 F increase in stack temperature, efciency decreases by 1%. Since the stack temperature rise is 36 F, the decrease in the boiler efciency at 200 psig operating pressure is calculated as follows: 36/40 = .9%. Therefore, the boiler efciency at 200 psig operating pressure is 82.5 - .9 = 81.6%.

PERFORMANCE DATAEfficiencyTables A2-7, A2-8, A2-9, A2-10, A2-11, and A2-12 show predicted fuel-to-steam efciencies (including radiation and convection losses) for Cleaver-Brooks Model CB Firetube boilers. For specic efciencies on retube boiler offerings not listed here, contact your local Cleaver-Brooks authorized representative. Cleaver-Brooks offers an industry leading fuel-to-steam boiler efciency guarantee for Model CB Firetube Boilers. The guarantee is based on the fuel-to-steam efciencies shown in the efciency tables and the following conditions. The efciency percent number is only meaningful if the specic conditions of the efciency calculations are clearly stated in the specication (see Cleaver-Brooks publication CB-7768 for a detailed description of efciency calculations). The boiler manufacturer shall guarantee that, at the time of startup, the boiler will achieve fuel-to-steam efciency (as shown in the tables listed above) at 100% ring rate (add efciency guarantees at 25%, 50%, and 75% of rating, if required). If the boiler(s) fail to achieve the corresponding guaranteed efciency as published, the boiler manufacturer will rebate, to the ultimate boiler owner, ve thousand dollars ($5,000) for every full efciency point (1.0%) that the actual efciency is below the guaranteed level. The specied boiler efciency is based on the following conditions. 1. Fuel specication used to determine boiler efciency: Natural Gas Carbon, % (wt) = 69.98 Hydrogen, % (wt) = 22.31 Sulfur, % (wt) = 0.0 Heating value, Btu/lb = 21,830 No. 2 Oil Carbon, % (wt) = 85.8 Hydrogen, % (wt) = 12.7 Sulfur, % (wt) = 0.2 Heating value, Btu/lb = 19,420 No. 6 Oil Carbon, % (wt) = 86.6 Hydrogen, % (wt) = 10.9 Sulfur, % (wt) = 2.09 Heating value, Btu/lb = 18,830 2. Efciencies are based on ambient air temperature of 80 F, relative humidity of 30%, and 15% excess air in the exhaust ue gas. 3. Efciencies are based on manufacturers published radiation and convection losses. (For Cleaver-Brooks radiation and convection losses, see Boiler Efciency Facts Guide, publication number CB-7767).

EmissionsThe emission data included in this section consists of typical uncontrolled emission levels for Cleaver-Brooks Model CB Firetube Boilers. Cleaver-Brooks Firetube boilers are available with the standard burner package for Model CB, or optional internal ue gas recirculation on Model CB (LE) (refer to Section A3). The Cleaver-Brooks IFGR packages are integrated boiler/ burner/control packages designed specically for CleaverBrooks boilers. For detailed information on Cleaver-Brooks IFGR packages, refer to Model CB (LE) in Section A3.

NOTICEThe data in Table A2-13 represents typical emission levels only. Guaranteed emission levels are available from your local Cleaver-Brooks authorized representative.

A2-2107-02

Model CB BoilersTable A2-7. Predicted Fuel-to-Steam Efciencies (%), Model CB Boilers - 10 psig, Natural GasBOILER HP 50 60 70 80 100 125 150 200 250 300 350 400 500 600 700 750 800 FIRING RATE (%) 25 83.0 82.9 84.5 84.6 84.4 83.3 84.4 85.0 85.0 85.3 85.3 84.5 85.5 85.7 85.7 85.8 85.8 50 83.2 83.1 84.7 84.8 85.0 83.6 84.6 85.3 84.7 85.3 85.7 84.7 85.7 86.0 86.2 86.1 86.1 75 82.9 82.7 84.3 84.5 84.8 83.4 84.5 85.1 84.0 84.6 85.2 84.6 85.5 85.8 86.0 85.9 85.9 100 82.4 82.3 83.9 84.0 84.4 83.2 84.3 84.9 83.3 83.9 84.5 84.4 85.2 85.6 85.7 85.6 85.6

Firetube BoilersTable A2-9. Predicted Fuel-to-Steam Efciencies (%), Model CB Boilers - 10 psig, No. 6 OilBOILER HP 50 60 70 80 100 125 150 200 250 300 350 400 500 600 700 750 800 FIRING RATE (%) 25 86.8 86.7 88.4 88.5 88.2 87.2 88.4 88.9 88.8 89.1 89.1 88.4 89.4 89.5 89.6 89.7 89.7 50 87.0 86.9 88.6 88.7 88.5 87.4 88.5 89.2 88.5 89.2 89.5 88.5 89.5 89.9 90.0 90.0 90.0 75 86.6 86.5 88.2 88.3 88.3 87.2 88.3 88.9 87.8 88.4 89.0 88.4 89.3 89.7 89.8 89.8 89.8 100 86.1 86.0 87.7 87.8 88.0 87.0 88.1 88.7 87.1 87.7 88.4 88.1 89.2 88.4 89.6 89.5 89.5

Table A2-8. Predicted Fuel-to-Steam Efciencies (%), Model CB Boilers - 125 psig, Natural GasBOILER HP 50 60 70 80 100 125 150 200 250 300 350 400 500 600 700 750 800 FIRING RATE (%) 25 80.2 80.1 81.7 81.8 81.5 80.4 81.5 82.2 82.0 82.6 82.6 81.8 82.8 82.9 83.0 83.1 83.1 50 80.5 80.4 82.0 82.1 82.4 80.9 82.0 82.7 82.0 82.7 83.2 82.2 83.2 83.5 83.6 83.6 83.6 75 80.4 80.3 81.9 82.0 82.3 81.0 82.0 82.7 81.6 82.2 82.8 82.4 83.3 83.6 83.6 83.7 83.7 100 80.1 80.1 81.7 81.8 82.2 81.0 82.1 82.7 81.3 81.9 82.5 82.2 83.1 83.5 83.6 83.5 83.5

Table A2-10. Predicted Fuel-to-Steam Efciencies (%), Model CB Boilers - 125 psig, No 6 OilBOILER HP 50 60 70 80 100 125 150 200 250 300 350 400 500 600 700 750 800 FIRING RATE (%) 25 83.9 83.8 85.5 85.6 84.6 84.1 85.3 86.0 85.8 86.3 86.4 85.5 86.5 86.7 86.8 86.9 86.9 50 84.2 84.1 85.8 85.9 85.8 84.6 85.8 86.5 85.7 86.4 87.0 85.9 86.9 87.3 87.3 87.4 87.4 75 84.0 83.9 85.6 85.7 85.9 84.7 85.8 86.4 85.3 86.0 86.6 86.0 87.0 87.4 87.4 87.5 87.5 100 83.8 83.8 85.4 85.6 85.8 84.8 85.8 86.5 85.0 85.6 86.2 85.9 86.9 87.2 87.4 87.3 87.3

A2-2207-02

Firetube BoilersTable A2-11. Predicted Fuel-to-Steam Efciencies (%), Model CB Boilers - 10 psig, No. 2 OilBOILER HP 50 60 70 80 100 125 150 200 250 300 350 400 500 600 700 750 800 FIRING RATE (%) 25 86.5 86.3 87.9 88.1 87.8 86.7 87.8 88.4 88.3 88.6 88.6 87.9 88.9 89.0 89.1 89.2 89.2 50 86.7 86.6 88.2 88.3 88.4 86.9 88.0 88.7 88.1 88.7 89.0 88.1 89.0 89.4 89.5 89.5 89.5 75 86.3 86.2 87.8 87.9 88.1 86.7 87.8 88.4 87.4 88.0 88.5 87.9 88.9 89.2 89.3 89.3 89.3 100 85.8 85.7 87.3 87.4 87.7 86.6 87.6 88.2 86.7 87.3 87.8 87.6 88.6 89.0 89.1 89.0 89.0

Model CB BoilersTable A2-12. Predicted Fuel-to-Steam Efciencies (%), Model CB Boilers - 125 psig, No. 2 OilBOILER HP 50 60 70 80 100 125 150 200 250 300 350 400 500 600 700 750 800 FIRING RATE (%) 25 83.6 83.5 85.1 85.2 84.8 83.7 84.8 85.6 85.3 85.9 85.9 85.1 86.1 86.2 86.3 86.4 86.4 50 84.0 83.8 85.4 85.6 85.7 84.2 85.3 86.0 85.3 86.0 86.6 85.5 86.5 86.8 86.9 86.9 86.9 75 83.8 83.7 85.3 85.4 85.6 84.3 85.3 86.0 84.9 85.5 86.1 85.6 86.6 86.9 87.0 87.0 87.0 100 83.5 83.5 85.1 85.3 85.5 84.3 85.4 86.0 84.7 85.2 85.8 85.5 86.4 86.8 86.9 86.8 86.8

Figure A2-8. Predicted Stack Temperature Increase for Pressure Greater Than 125 psig

A2-2307-02

Model CB BoilersTable A2-13. Model CB Boiler Emission Data

Firetube Boilers

ESTIMATED LEVELS - UNCONTROLLED POLLUTANT NATURAL GAS CO ppmA Lb/MMBtu ppmA Lb/MMBtu ppmA Lb/MMbtu ppmA Lb/MMBtu ppmA Lb/MMBtu 200 0.15 100 0.12 1 0.001 40 0.016 0.01 NO. 2 OILB 90 0.07 185 0.25 278 0.52 50 0.025 0.025 NO. 6 OILC 95 0.075 502 0.67 278 0.52 70 0.035 0.160

NOx

SOx

HC/VOCs

PM

NOTES: Refer to Section E for detailed emission information. A. ppm levels corrected to 3% O2, dry basis. B. Based on fuel constituent levels of: Fuel-bound nitrogen content = 0.05% by weight Sulfur content = 0.5% by weight Ash content = 0.01% by weight C. Based on fuel constituent levels of: Fuel-bound nitrogen content = 0.7% by weight Sulfur content = 0.5% by weight Ash content = 0.1% by weight Conradson carbon residue = 16% by weight

ENGINEERING DATAThe following engineering information is provided for Model CB Firetube Boilers. Additional detail is available from your local Cleaver-Brooks authorized representative. Refer to Tables A2-14 through A2-18.

Table A2-14. Heating Surface, Model CB BoilersBOILER HP 15 20 25 HEATING SURFACE (SQ-FT) FIRESIDE 75 100 125 150 200 250 300 350 400 500 625 750 1000 1250 1500 1750 2000 2500 3000 3500 3500 3500 WATERSIDE 85 109 144 162 219 266 323 388 441 544 679 820 1092 1346 1623 1932 2151 2691 3262 3810 3810 3810

Blowdown Water RequirementsSome local codes require blowdown tanks to be constructed in accordance with recommendations of the National Board of Boiler and Pressure Vessel Inspectors. The National Boards recommendations base the size of the blowdown tank on the removal of at least 4 inches of water from the boiler. Table A2-19 lists the approximate quantity of water represented by 4 inches of water at normal operating level for Cleaver-Brooks Model CB Boilers.

30 40 50 60 70 80 100 125 150 200 250 300 350 400 500 600 700 750 800

A2-2407-02

Firetube BoilersTable A2-15. Steam Volume and Disengaging AreaSTEAM VOLUME CU-FT BOILER HP 15 20 25 & 30 40 50 60 70 80 100 125 150 200 250 300 350 400 500 600 700-750-800 NOTE: Based on normal water level. A. Based on 150 psig design pressure. B. Based on 15 psig design pressure. 2.9 2.9 3.9 5.3 9.7 9.7 14.3 14.3 16.6 25.4 30.7 37.7 49.2 59.5 70.9 75.8 95.0 115.4 134.0 HIGH PRESSUREA

Model CB BoilersSTEAM RELIEVING AREA, SQ-INB

LOW PRESSURE 5.9 5.9 7.9 10.8 16.0 16.0 23.7 23.7 27.4 36.6 44.3 54.4 70.6 85.3 101.7 102.5 128.5 156.1 181.3

HIGH PRESSUREA 1356 1356 1817 2485 2959 2959 4367 4367 5053 5371 6511 7985 7980 9651 11507 10148 12722 15448 17948

LOW PRESSUREB 1637 1637 2195 2999 3372 3372 4975 4975 5757 5887 7138 8752 8695 10516 12538 10960 13740 16685 19385

Table A2-16. Water Circulation Rate and Temperature Drop for Hot Water BoilerBOILER HP 15 20 30 40 50 60 70 80 100 & 100A 125 &125A 150 175A 200 250 300 350 400 500 600 700 750 800 BOILER OUTPUT (1000) BTU/HR 500 670 1005 1340 1675 2010 2345 2680 3350 4185 5025 5858 6695 8370 10045 11720 13400 16740 20080 23450 25106 26780 SYSTEM TEMPERATURE DROP - DEGREES F 10 20 30 40 50 60 70 80 90 100

MAXIMUM CIRCULATING RATE - GPM 100 134 200 268 335 402 470 536 670 836 1005 1172 1340 1675 2010 2350 2680 3350 4020 4690 5025 5360 50 67 100 134 168 201 235 268 335 418 503 586 670 838 1005 1175 1340 1675 2010 2345 2510 2680 33 45 67 89 112 134 157 179 223 279 335 391 447 558 670 784 895 1120 1340 1565 1675 1785 25 33 50 67 84 101 118 134 168 209 251 293 335 419 503 587 670 838 1005 1175 1255 1340 20 27 40 54 67 80 94 107 134 168 201 234 268 335 402 470 535 670 805 940 955 1075 17 22 33 45 56 67 78 90 112 140 168 195 224 280 335 392 447 558 670 785 840 895 14 19 29 38 48 58 67 77 96 120 144 167 192 240 287 336 383 479 575 670 720 765 12 17 25 33 42 50 59 67 84 105 126 147 168 210 251 294 335 419 502 585 625 670 11 15 22 30 37 45 52 60 75 93 112 130 149 186 223 261 298 372 448 520 555 595 10 13 20 27 33 40 47 54 67 84 100 117 134 167 201 236 268 335 402 470 500 535

NOTES: 1. Minimum recommended return water temperature is 150 F. Minimum recommended outlet temperature for Model CB Hot Water Boilers is 170 F. Contact your local Cleaver-Brooks authorized representative for special hot water application information. 2. See Section H2 for over-pressure requirements.

A2-2507-02

Model CB Boilers

Firetube Boilers

Table A2-17. Recommended Steam Nozzle Size (To Maintain 4000 to 5000 fpm Nozzle Velocity)BOILER HP OPERATING PRESSURE PSIG 15 30 40 50 75 100 125 150 200 250 15 4 2 2 1.5 1.5 1.5 1.5 1.5 1.5 1.5 20 4 2 2 2 2 1.5 1.5 1.5 1.5 1.5 25 4 2.5 2.5 2 2 2 2 2 2 2 30 4 2.5 2.5 2.5 2 2 2 2 2 2 40 6 3 3 2.5 2.5 2 2 2 2 2 50 6 4 3 3 3 3 3 2.5 2.5 2 60 6 4 4 3 3 3 3 2.5 2.5 2 70 6 4 4 4 3 3 3 2.5 2.5 2 80 6 4 4 4 4 3 3 2.5 2.5 2 100 8 6 6 4 4 4 4 2.5 2.5 2 125 8 6 6 6 4 4 4 3 2.5 2.5 150 8 6 6 6 4 4 4 3 3 2.5 200 10 8 6 6 6 6 4 4 4 3 250 10 8 8 6 6 6 6 4 4 4 300 12 8 8 8 6 6 6 6 4 4 350 12 10 8 8 8 6 6 6 4 4 400 12 10 10 8 8 6 6 6 6 4 500 12 10 10 8 8 8 8 6 6 6 600 12 12 10 10 8 8 8 6 6 6 700 12 12 12 10 10 8 8 8 6 6 750 12 12 12 12 10 8 8 8 6 6 800 12 12 12 12 10 10 8 8 6 6

NOTES: 1. Steam nozzle sizes given in inches. 2. Recommended steam nozzle sizes based on 4000 to 5000 fpm steam velocity. Spool pieces (300 lb flanges) are available in the following sizes (in inches): 3x21/2x30, 4x3x30, 6x4x36, 8x6x48, 10x8x48, and 12x8x48. 3. All standard steam nozzle sizes for 150 psig design pressure or greater are the same as 125 psig operating pressure on the above table. To increase or decrease the standard size, request the change with your local Cleaver-Brooks authorized representative.

Table A2-18. Recommended Non-Return Valve SizeBOILER HP 100 125 150 200 250 300 350 400 500 600 700 750 800 BOILER CAPACITY (LBS/HR) 3450 4313 5175 6900 8625 10350 12025 13800 17210 20700 24150 25875 27600 OPERATING PRESSURES (PSIG) 50 3 4 4 4 4 6 6 6 6 8 8 8 8 75 2-1/2 3 4 4 4 4 6 6 6 8 8 8 8 100 2-1/2 3 3 4 4 4 4 4 6 6 6 6 6 125 2-1/2 3 3 3 4 4 4 4 6 6 6 6 6 150 2-1/2 3 3 3 3 4 4 4 4 6 6 6 6 175 2-1/2 2-1/2 3 3 3 4 4 4 4 4 6 6 6 200 2-1/2 2-1/2 2-1/2 3 3 4 4 4 4 4 6 6 6 250 2-1/2 2-1/2 2-1/2 3 3 3 3 4 4 4 6 6 6

Note: Valve sizes (300 psig flanges) given in inches.

A2-2607-02

Firetube BoilersTable A2-19. Model CB Blowdown Tank Sizing InformationBOILER HP 15-20 25-30 40 50-60 70-80 100 125 150 200 250 300 350 400 500 600 700-750 800 WATER (GAL.) 26 34 47 55 80 93 97 118 145 146 176 210 183 230 280 325 325

Model CB BoilersSound LevelTable A2-20 summarizes predicted sound pressure levels for Model CB Boilers. Tables A2-21 through A2-25 give detailed octave band sound pressure levels for each boiler. These values are based on standard motors. Optional motor types and altitude conditions can increase sound levels. Units The units for the sound level tables are dBA (decibels, measured on the A-weighted scale) in reference to 0.0002 microbars (20 micro-Newtons per square meter). They are standardly referenced in specifying and reporting sound pressure levels on industrial equipment. Test Method The sound pressure levels in the above tables were obtained from tests in accordance with the "ABMA Test Code for the Measurement of Sound from Packages Boilers." In accordance with this code, the sound pressure levels reported were measured on the boiler centerline 4-1/2 feet vertically above the bottom of the base rails and 3 feet horizontally in front of the end of the blower motor or front surface of the electrical cabinet. Sound Level Meter The sound level meter used complies with ANSI S1.4, Type 1 (Precision). The readings are taken with the meter set for slow response.

NOTE: Quantity of water removed from boiler by lowering normal water line 4".

Table A2-20. Sound Pressure Level Summary (50 - 800 hp)BOILER HP HFO, dBA LFO, dBA HFG, dBA LFG, dBA 50 79 78 77 72 60 79 78 77 73 70 79 78 78 74 80 79 78 78 75 100 81 79 78 75 125A 82 79 79 75 125 83 81 81 78 150 83 82 80 77 200 83 81 82 78 250 88 86 84 81 300 88 86 86 82 350 89 85 86 83 400 83 80 82 80 500 83 82 82 81 600 83 82 82 81 700 85 82 85 82 750 87 83 86 83 800 88 84 87 84

NOTES: 1. Boiler No. followed by an a designates hot water boilers furnished in a smaller vessel size with additional tubes in the upper portion of the vessel. 2. Sound Pressure levels measured on boilers operating in various locations and expressed in dBA are as follows:

ABBREVIATIONS: HF = High Fire LF = Low Fire O = Oil G = Gas

Table A2-21. Model CB Boiler Sound Pressure Level Details (40 hp)FIRING RATE FUEL SOUND LEVEL dBA OCTAVE BAND SOUND PRESSURE LEVELS IN dB RE .0002 MICROBAR 31Hz 63Hz 125Hz 250Hz A 40HP LFG LFO HFG HFO NOTE: ABBREVIATIONS: HF = High Fire 76 77 79 79 73 73 81 72 LF = Low Fire O = Oil G = Gas 75 75 78 77 72 75 74 77 74 76 80 81 76 75 78 78 70 72 71 73 67 67 69 69 68 66 68 66 64 66 64 66 57 58 58 58 500Hz 1kHz 2kHz 4kHz 8kHz 16kHz

A. The data shown above was taken on the 40 hp. Since the highest Sound Level is below 80 dBA, no additional 36" diameter Firetubes were tested. If Sound Level predictions are required for the 15 thru 30 hp, use the values shown for the 40 hp.

A2-2707-02

Model CB Boilers

Firetube Boilers