boiler auxiliaries performance
TRANSCRIPT
-
7/31/2019 Boiler Auxiliaries Performance
1/25
Boiler Auxiliaries Performance
Many steam generating units are operating day after day with
efficiencies at or near test condition values. Any unit can operate at
these efficiencies with the proper instrumentation , reasonableauxiliaries, proper maintenance program of instrumentation and
auxiliary equipment and proper operating instruments. A standard
procedure should be established by logging the consumption of
individual auxiliaries for different loads.The auxiliaries those need to be monitored for their performance are :
Fans and pumps (CC pumps if provided)
Fuel burning equipment (coal mills, burners)
Wind box dampers (air,fuel,overfire)
Air Preheaters
Dust collecting equipment (ESP)
Soot blowers
-
7/31/2019 Boiler Auxiliaries Performance
2/25
Boiler Auxiliaries Performance
There are essentially two different kinds of fans , 1) The centrifugal fan
in which gas or air accelerates radially outward in a rotor from heel to
tip of blades, discharging into surrounding scroll casing. And 2) The axial
flow fan in which the gas or air is accelerated parallel to the fan axis,
similar to the ordinary desk fan, but with a casing added to develop
static pressure. The axial fans can be a single stage or multiple stage fan.
Both the types of fans are used in practice though axial fans withvariable blade pitch control are preferred for their part load efficiency .
The fans are called Primary Air(PA), Secondary Air(SA), Induced
Draft(ID) fans , Gas Recirculation (GR) fans, Seal Air fans, Scanner Air
fans and Igniter fans depending on the application of their use. FGD
units are provided with booster fans to boost up the pressure.
Fan control : To meet varying requirements of the system, common
methods of fan output control are damper control, variable-speed
control and blade pitch control in case of axial flow fans.
-
7/31/2019 Boiler Auxiliaries Performance
3/25
Fan Performance
Fan Efficiency : The energy used by a fan impeller goes into bearing
friction, flow work, compression, velocity head, and heating. It is
generally assumed in fan work, where the pressures are usually less
than 25.5 cm of water plenum or vacuum, that the fluid is
incompressible. An ordinary manometer reading on the inlet and outlet
of a fan gives the static pressure static pressure relative to theatmosphere. Their difference is the working static pressure of the fan.
Similarly an efficient pitot tube turned into the air stream furnishes an
indication of the sum of static pressure and velocity head on the
attached manometer. This is called total pressure, or dynamic pressure.Static fan efficiency = Static air hp/ Shaft hp.
-
7/31/2019 Boiler Auxiliaries Performance
4/25
Fan PerformanceFan performance is best expressed in graphical form. These functionalrelations are the fan characteristic curves. In these curves capacity incfm is shown horizontally as the independent variable and head (staticpressure), shaft horse power and static efficiency are dependentvariables plotted vertically. Fan speed is constant. Since fan operationfor a given capacity must match single values of head and horsepoweron the characteristic curves, a balance between fan static pressure andsystem resistance is required. If the system resistance for a givencapacity is less than the head indicated on the fan characteristic curve,additional variable flow resistance, such control damper, must be addedto the system. Varying the operating speed to yield a family of curves,will change the numerical performance values of the characteristics.
However, the nature of the curves remains substantially unaltered.Performance at different speeds for the same efficiency can be relatedby the following :
1. Capacity is directly proportional to speed.
2. Head is directly proportional to speed squared.
3. Power output is directly proportional to speed cubed.
-
7/31/2019 Boiler Auxiliaries Performance
5/25
Fan PerformanceSystem resistance along with the fan static pressure characteristics at
various speeds, both as function of volumetric flow rate are plotted. If
the fan operates at constant speed, any output less than that shown at
the intersection of the system resistance and specified rpm curves must
be obtained by throttling the excess fan head. This results in wastage in
power that can be avoided by using a variable speed drive.
Backwardly curvedblade wheels are generally selected for forced draft
service because the high speed is suitable for standard motor drive. The
power demand is self limiting, and the static efficiency is high. These
fans may be satisfactorily operated in parallel.
Induced draft fans operate in gas of much higher temperature and may
handle gases laden with dust. Forwardly curvedblade wheels run at thelowest speed to develop a given pressure, hence are frequently chosen
for induced draft service so that the centrifugal stresses in the wheels
will be least. The forward curvature reduces the blade depth, but gives a
large inlet opening for the gas. conditions.
-
7/31/2019 Boiler Auxiliaries Performance
6/25
Fan Performance
The rising horsepower and pressure characteristics of this type usually
render it unsuitable for parallel operation , for it can overload its driver
under abnormal working conditions.
Axial flow designs are found in forced draft service.
Fan testing : It is difficult to obtain consistent data from field tests of
fans installed in flue and duct systems because straight sections are
seldom long enough to eliminate flow disturbances from such things asbends, change in section and dampers. Structural arrangements at the
fan entrance and discharge also materially affect field performance
results. Manufactures, therefore, generally are reluctant to guarantee
fan performance except on the basis of factory tests on a test blockarranged for measuring under ideal conditions. However plant
engineers may perform fan tests as acceptance test. The pitotstatic
equipment is generally employed, and there should be some provision
for test openings. Experience indicates that the velocities in the ducts
and breechings vary across the flow, so that the area should be divided
-
7/31/2019 Boiler Auxiliaries Performance
7/25
Fan Performance
Into small elements. Rectangular sections are divided into small squares
and readings taken at the centre of each. It is the square roots of
velocity head readings that are arranged for the calculation of flowvelocity, not the readings themselves. On tests where it is not possible
to hold the rpm constant, corrections to the readings must be made
before comparing results with constant speed guarantees. If N is the
rated speed and Nx is the test speed, multiply test volume by N/Nx, testpressure by (N/Nx) square and test powers by (N/Nx) cube before
comparing with the ratings.
Fan Safety Factors : To make sure that the fans will not limit a boilers
performance, margins of safety are added to the calculated or net fan
requirements to arrive at satisfactory test block specification. These
margins are intended to cover conditions encountered in operation that
can be specifically evaluated.
-
7/31/2019 Boiler Auxiliaries Performance
8/25
Fan Performance
For example, variation in fuel ash characteristics or unusual operatingconditions may foul heating surfaces. The unit then requires additionaldraft. A need for rapid load increase or a short emergency overload
often calls for overcapacity of the fans. The customary margins to allowfor such conditions are 15 to 20 % increase in the net weight flow of airor gas, 15to 20% increase in net head, and 25F increase in the air or gastemperature at the fan inlet.
General performance requirements for force draft fans.Reliability : Modern boilers must operate continuously for long periods(up to 18 months) without shut down for repairs or maintenance. Thefan must be well balanced, and the blades so shaped that they will notcollect dirt and disturb this balance.
Efficiency : High efficiency over a wide range of output is necessarybecause boilers operate under varying load conditions.
Pressure : Fan pressure should vary uniformly with output over thecapacity range. This facilitates damper control and assures minimum
disturbance of air flow when minor adjustments to the fuel burningequipment change the system resistance.
-
7/31/2019 Boiler Auxiliaries Performance
9/25
Fan Performance
Capacity : When two or more fans operate in parallel, the pressure out-
put curves should have characteristics similar to the straight blade or
backward curve blade fans in order to share the load equally near the
shut off point.
Horsepower : Motor driven fans require self limiting horse power
characteristics, so that driving motor cannot overload. This means that
the horsepower should reach a peak and drop off near the full load fan
output.
ID fans : Induced draft fans has the same basic requirements as forced
draft fan except that it handles high temperature gas which may contain
erosive ash. Flat, forward curved and occasionally backward curvedblades with less curvature are used. Excessive maintenance from
erosion is sometimes avoided by protecting casing and blades with
replaceable wear strips. Bearings, usually water cooled have radiation
shields on the shaft between rotor and bearings to avoid overheating.
-
7/31/2019 Boiler Auxiliaries Performance
10/25
-
7/31/2019 Boiler Auxiliaries Performance
11/25
-
7/31/2019 Boiler Auxiliaries Performance
12/25
-
7/31/2019 Boiler Auxiliaries Performance
13/25
Axial fan-Fixed pitch, adjustable pitch, variable pitch
Performance control characteristics
Areas of constant efficiencies run parallel to the boiler resistance
line-high efficiency over a wide boiler load range
Control range is very large both above and below the maximumefficiency
The lines of constant blade angle are actually individual fan curves-
as the curves are very steep, change in resistance produces very
little volume change.As the blade angle can be adjusted from minimum to maximum
flow change is nearly linear
-
7/31/2019 Boiler Auxiliaries Performance
14/25
-
7/31/2019 Boiler Auxiliaries Performance
15/25
Stall Characteristics
Axial flow fans can experience stall
Stall is the aerodynamic phenomena which occurs
when a fan operates beyond its performance limit
Flow separation occurs
Fan operation becomes unstable- normal
performance curve not followed
Extended operation in the stall region should beavoided
Unpredictable flow vibration can damage rotating
blades
-
7/31/2019 Boiler Auxiliaries Performance
16/25
The angular relationship between the air flow impinging on theblade of a fan and the blade itself is known as the angle of
attack. In axial flow fan, when this angel exceeds a certain
limit, the air flow over the blade separates from the surface and
centrifugal force then throws the air outwards, towards the rimof blades. This action causes a build up of pressure at the
blade tip, and this pressure increases until it can be relived at
the clearance between the tip and the casing. Under this
condition the operation of the fan becomes unstable, vibration
sets in and the flow starts to oscillate. The risk of stall increases
if a fan is oversized or if the system resistance increase
excessively.
-
7/31/2019 Boiler Auxiliaries Performance
17/25
Stall is aerodynamic phenomenon which occurswhen a fan operates beyond its performance limits
and flow separation occurs around the blade.
http://4.bp.blogspot.com/_4O4AQvDj16o/SjEr90hRqgI/AAAAAAAAAVE/Zy9CVErKHaM/s1600-h/blade+stall.jpg -
7/31/2019 Boiler Auxiliaries Performance
18/25
-
7/31/2019 Boiler Auxiliaries Performance
19/25
Stall prevention
When axial fans are sized properly and the resistance curve is
parabolic chances of stall is less
Possibility of stall increases when the fan is over sized compare to
volume capacity, System resistances increases significantly or fans
are operated improperly
Noise in a FanSingle tone noise is generated when the concentrated flow
encounters a stationary object after leaving the rotating blade
passage.
The distance between the blades and the stationary objects affectsthe sound
The blade passing frequency and its first harmonic is most dominant.
Broad band noise is produced by the fluid passing through the fan
housing, contains a range of frequencies
-
7/31/2019 Boiler Auxiliaries Performance
20/25
Mill Performance
The power consumption of coal mill should be low to minimize
operating cost. The main factor of performance depends on (a) the
grindability of coal. (b) Surface moisture of coal. (c) the fineness of thegrind needed.
Grindability : It is a term used to measure the ease of pulverizing a coal
in comparison with a standard coal chosen as 100(unity) grindability.
Hardgrove index is most often used to measure the grindability of acoal. The method is based on the premise that the work done in
pulverizing is proportional to the new surface produced. A definite
amount of grinding energy is applied is applied to a prepared sample in
a miniature pulverizer (Hardgrove Grindability Machine) and the new
surface is determined by sieving. A coal is harder or easier to grind if its
grindability index is less or greater. If the coal has grindability index of
50, it would require twice the grinding power of the standard coal to
produce a specified particle size.
-
7/31/2019 Boiler Auxiliaries Performance
21/25
-
7/31/2019 Boiler Auxiliaries Performance
22/25
Mill Performance
Fineness : the fineness of the pulverized coal needed for
successful burning depends largely on the ratio of volatile
matter(VM) to the fixed carbon. Since the carbon burns slower the
VM, low VM coals must be ground finer to expose more surface to
permit more coal in a given residence time in the furnace. The
finer the grind more the power needed. Moisture makes the coal
particle adhere to each other, defeating the purpose of grinding.
The coal samples for checking fineness are collected by using bag
collector or a cyclone and the results of sieve analysis are plotted
on a Rosin and Rammler chart. The mill fineness checks are done
periodically to ensure good performance of the mills
-
7/31/2019 Boiler Auxiliaries Performance
23/25
ESP Performance
Efficiency of ESP is defined as the ratio of mass of all particles retained
by collector (ESP) and the mass of all particles entering collector.
The Collection efficiency of ESP is related to the time of particle
exposure to the electrostatic field, the strength of the field, and the
resistivity of the dust particle.
Larger collection-surface areas and lower gas-flow rates increase
efficiency because of the increased time available for electrical activityto treat the dust particles.
An increase in the dust-particle migration velocity to the collecting
electrodes increases efficiency
It is easier to collect large particles than smaller particles.
Care must be taken to maintain the gas temperature entering the
precipitator at or above the design temperature, otherwise local cold
spots result in condensation, fouling and rapid corrosion.
-
7/31/2019 Boiler Auxiliaries Performance
24/25
ESP PERFORMANCE - PROBLEMS OF ESP
BROKEN WIRES
ELECTRODE FAILUREGAS DISTRIBUTION
ALIGNMENT PROBLEMS
CORROSION
BROKEN INSULATORSELECTRICAL SUPPLY PROBLEMS
RAPPING SYSTEM PROBLEMS
HOPPERS CHOKING
-
7/31/2019 Boiler Auxiliaries Performance
25/25
Boiler auxiliaries performance
Fuel air damper will Maintain the length of the flame. Modulate in
proportion to fuel burner pressure or speeder speed.
Auxiliary air damper will maintain the furnace to wind box DP.
Over fire dampers are used to control NOx
Bottom auxiliary damper is used to control unburnt carbon falling in
bottom ash hopper
RAPH should give the designed secondary and primary air temperatures
at all loads and should ensure that the outlet flue gas temperatures are
maintained without exceeding the air leakages across seals.
The excessive O2 is the indication of airheater leakages and differential
pressure measurement across APH on air and flue gas sides indicate the
fouling of airpreheaters.