blue diamond’s exclusive range of perkins powered … › content › pdf ›...

4
PERKINS POWERED DIESEL GENERATORS THE MOST COST EFFECTIVE PERKINS POWER FOR BUSINESS! BLUE DIAMOND’S EXCLUSIVE RANGE OF BDM 15KVA PERKINS GENERATOR 240/415V No disruption to operating your business, lighting, machinery and computer system Keep your security system powered so your premises are protected from theft Keep refrigerators and freezers in continuous use so no loss of refrigerated goods Gain a competitive advantage when your doors stay open to serve customers’ needs in an emergency Maintain safety in an emergency with schools and public buildings able to operate as emergency shelters Benefits of an automatic Perkins powered system: INDUSTRIAL MINING COMMERCIAL

Upload: others

Post on 01-Feb-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

  • PERKINS POWERED DIESEL GENERATORSTHE MOST COST EFFECTIVE PERKINS POWER FOR BUSINESS!

    BLUE DIAMOND’S EXCLUSIVE RANGE OF

    BDM 15KVA PERKINS GENERATOR 240/415V

    •No disruption to operating your business,

    lighting, machinery and computer system

    •Keep your security system powered so

    your premises are protected from theft

    •Keep refrigerators and freezers in

    continuous use so no loss of refrigerated

    goods

    •Gain a competitive advantage when your

    doors stay open to serve customers’

    needs in an emergency

    •Maintain safety in an emergency with

    schools and public buildings able to

    operate as emergency shelters

    Benefits of an automatic Perkins powered system:

    INDUSTRIALMINING COMMERCIAL

  • EXHAUST SYSTEM

    Maximum back pressure 10.2 kpa

    Exhaust outlet size-horizontal/vertical

    42 mm

    ELECTRICAL SYSTEM

    Alternator 65 amps -12 V

    Starter motor Bosch 2 kW -12 V

    FUEL SYSTEM

    Type of injection Indirect injection

    Fuel injection pump Cassette type

    Nozzle opening pressure 14.7 MPa

    Maximum particle size 25 microns

    Blue Diamond’s exclusive Perkins power range has been designed specifically with mining, industrial, and commercial power in mind.

    • Easy to Use premium ComAp controller and ATS connection – makes

    installing the generator to automatically switch on in the event of a

    power failure easy, with the help of an electrician

    • Remote Start and Online Monitoring – Start your generator via the

    web or a downloadable App. Use in conjunction with off grid Solar

    Systems

    • Diesel Engine – Diesel is far safer to store over long periods of time

    than petrol. Also gives better fuel efficiency and is generally safer

    • Low Capital Cost – Our Perkins powerd range are extremely

    cost effective

    • Back up and Support – Blue Diamond operates a Kewdale based

    mechanical work shop with full spare parts and support

    Powered by:

    FUEL CONSUMPTION

    100% load 3.8 L/h

    75% prime power 3.0 L/h

    50% prime power 2.8 L/h

    Fuel tank size 85 L

    Run time @ 75% load 28 H

    MINE SITE USE AND SAFETY

    Bunded fuel tank YES

    Emergency stop YES

    Battery isolator YES

    Australian standards YES

    www.bluedm.com.au

    ENGINE

    Manufacturer PERKINS

    Cylinders 3

    ArrangementVertical in-line three

    Cycle Stroke naturally

    Induction system Aspirated

    Compression ratio 22.5:1

    Bore 84 mm

    Stroke 90 mm

    Cubic capacity 1.496 L

    Estimated total weight (dry)

    197kg

    Engine rated speed 1500 rpm

    Gross engine power-prime 12.5 kW

    Gross engine power-Standby

    13.5 kW

    Brake mean effective pressure

    65 kPa

    Mean piston speed 4.5 m/s

    Engine coolant flow 37.7 L/min

    Combustion air flow 1.1 m3/min

    Exhaust gas flow (max) 2.7 m3/min

    Exhaust gas temperature outlet (max)

    445 C

    DATA

    Model BDM 15 -Perkins 415V

    Prime 15 KVA

    Voltage 240/415V - 50Hz

    Blue Diamond carries all spare parts and supports the

    engine with a 12 month or 1000 hour warranty

    BLUE DIAMOND’S PERKINS POWER DIESEL GENERATORS

    BDM 15Perkins 240/415V Diesel Generator

  • DIMENSIONS & WEIGHTS

    www.bluedm.com.au

    ALTERNATOR

    Frequency and speed 50Hz/1500rpm

    Voltage 240/415V

    Prime power 12.5 kVA

    Standby power 10 kW

    Power efficiency 82.1%

    Input power 12.2 kW

    Voltage regulation 0.5%

    Rated power factor 0.8

    Stator winding 2/3

    Maximum over speed 2250min-1

    Sustained short circuit

    72 Amps

    Cooling air (m3/sec) 0.09

    SOUND PROOF STYLE

    Dimensions

    Length 1550 mm

    Width 780 mm

    Height 950 mm

    Weight 560kg NET

    BDM 15KVA PERKINS GENERATOR 240/415V

    Blue Diamond’s Perkins Series

    Alternators come equipped with

    AVR and are electronically governed.

    This means they are safe to use

    with electronic equipment including

    computers.

    Computer safe

  • CONTROLLER SYSTEM

    www.bluedm.com.au6 Hodgson Way, Kewdale08 9353 4436

    1300 998 647

    Blue Diamond has chosen to partner with CompAp forthe control systems on our Perkins series generators.

    • Easy Plug & Play solution• Simply connected using AirGate

    technology• System works using WebSupervisor

    with all of its benefits• Fleet monitoring and control• Alarm monitoring• On-line notification on alarms• System offers large number of

    monitored units (100-1000+)• Server – client based solution• User-friendly graphical interface• Accessible from any PC with

    Internet connection• Data is periodically updated from

    machines to database server

    • Automatic generation of reports - User defined XLSx files

    • Access from any web enabled device such as PC/netbook, tablet and smartphone.

    • E-mail notification

    • Compact gen-set controller for single operating genset• Manual and remote start (MRS) applications• Full gen-set monitoring and protection• Running hours event and performance log• Multiple languages (user changeable) in controller, even

    more in installation suite• Plug-in extension modules capability• WebSupervisor, AirGate and Locate support*• Automatic SMS on alarm or event & gen-set control over

    SMS*• On-line control and monitoring over web pages

    (embedded web server) via plug & play IB-Lite

    • Optional GSM/GPRS modem/wireless Internet via IL-NT GPRS

    • Fuel theft protection• Alternative switchable configuration• Automatic and manual GCB control• Magnetic pickup input• D+ preexcitation terminal• True RMS measurement• 3 phase power measurement• 3 configurable analog inputs• 6 binary inputs• 6 binary outputs

    Cloud Based System for Monitoring and Controlling of ComAp Controllers

    *Plug-in module required

    InteliLiteNT MRS 10Manual Remote Start (MRS) Gen-set Controller