blokset mw2
TRANSCRIPT
-
http://www.panelbuilders.schneider-electric.com
Catalogue2011
Blokset Mw2High dependability and low voltage switchboard
-
Index 3
1
3
4
6
7
8
2
5
New
Mw2 Table of content
Introduction 1-1
Index 2-1
Descriptionandcharacteristics 3-1
ElectricalDistributionFunctionalUnits 4-1Ue=415V 4-6Ue=690V 4-22
MotorControlcommandFunctionalUnits 5-1Ue=415V 5-15Ue=415V 5-205
Enclosures 6-1Busbars 6-19
Specificadaptation 7-1
Massconsumptionandspareparts 8-1Technicalinformations 8-5
-
Chapter01 1-1
Introduction
New
Mw2
Bloksetpresentation 1-2
Fieldsofapplications 1-13
MotorSysintelligentPower&MotorControlCenter-iPMCCinBlokset 1-14
-
Chapter011-2
-
Chapter01 1-3
A tried and tested switchboardBlokset switchboards have long guaranteed the durability and availability of several tens of thousands of installations the world over.Tried and tested reliability, overall performance and an attractive TCO (Total Cost of Ownership) have caused Blokset to become, in the space of just a few years, the reference switchboard for a large number of panel-builders, industrial site managers and maintenance managers.
Concentrated know-howThroughout all these years, Blokset technology has never cased to evolve to satisfy both end-users in their search for optimised solutions for better, faster and more economic production, and panel-builders in their search for equipment that is more reliable and easier to install and maintain.Today this evolution assumes concrete form with the emergence of a new column dedicated to motor control known as Mw2.
Blokset is a modular offer for the production of LV switchboards for electrical distribution up to 6 300A and for motor control up to 250 kW
-
Chapter011-4
Your installations evolve, our solutions tooIn a constantly changing industrial and economic world, you need to be able to upgrade your installations at all times to remain competitive.Only electrical installations made up of modular switchboards are able to meet the challenges you face.
With Blokset, you are completely free to add new feeders to your motors
Simply modular and open-ended>ThemodularityoftheBloksetfunctionalswitchboardsmeansyoucanmodifyorupgradethemwitheasetoadapttoyourchangingprocessesandincreaseperformance.Thewithdrawabledrawersletyoumaketheseupgradeswhiletheequipmentisenergised,withoutcuttingswitchboardsupplyandincompletesafety.
>Theswitchboardisdesignedwithfreeslotstoaddnewfunctionsorextramotorfeeders,evenatthelastminute.
-
Chapter01 1-5
- use of last generation Schneider Electric products, - perfect electrical and mechanical consistency and the electromagnetic compatibility of all components. Drawers have a real test position that is automatically accessible by simple displacement, thus guaranteeing upstream and downstream insulation of power for maximum operator safety.
and secured All devices can be locked to avoid incorrect operations. Drawers can be plugged out with power on, without stopping the switchboard and without any risk to the operator. The switchgear position mechanical indicators on the front face are 100 % reliable.
New Mw2 column: Compact and economicThe Mw2 column satisfies the motor control needs of exacting processes. The new withdrawable drawers with their integrated front face require no tools to handle them.Tests and maintenance operations are simpler and quicker.Column compactness means that more equipment and functions can be concentrated into the same space, thus reducing the total number of columns. With the new Mw2 column, you optimise the cost of your installations.
An innovative solution With an Mw2 column of the same size, you can now install more motor feeders. The Mw2 column allows a combination of functions, for example motor and distribution incomers and feeders. It adapts to all electrical room configurations. A pre-studied solution, it incorporates all tried and tested Schneider Electric products for all motor applications
rugged and reliable Production of new withdrawable drawers with a greater useful volume was made possible thanks to:- Schneider Electrics know-how in the design of LV equipment in very small volumes.
Blokset: a clever balance of innovation and experience to offer you an extremely reliable multi-potential switchboard
-
Chapter011-6
Step up on safetySafety is a major issue not only to guarantee installation durability but also and above all for operators and maintenance personnel working on a switchboard.
Nothing left to chance>TheBloksetLVswitchboardsincorporatethebestsafetyandprotectionsystems,preventingon-loadoperationtoguaranteesaferoperationandmaintenance.
>LivepartsareprotectedbyscreensguaranteeinganIP20degreeofprotection.
>Thewithdrawabledrawershave3positions:connected,disconnectedandsafetesting.
>Theoperatorinterfacesforswitchboardfunctionalunitconfigurationandsettingaredirectlyaccessibleonthefrontface.
Internal arcBlokset technology reduces arcing hazards thanks to 3 levels of confinement: at the functional unit (AS3439-1), at the column (IEC 61641), at the switchboard.
Tested switchboards
Bloksetisatotally
testedswitchboard
asperstandard
IEC61439-2,thus
guaranteeingelectrical
installationand
operationsafety.
Alltestsarecertified
byASEFAandLOVAG.
Tests conductedTemperatu
reriselimits
Dielectricproperties
Short-circuitwithstand
Protectioncircuiteffici
ency
Clearanceandcreepa
ge
distance
Mechanicaloperation
Degreeofprotection
Internalarcingwithsta
nd
Hoisting,etc.
-
Chapter01 1-7
And continuity of supplyAt all times you must be able to rely on electrical energy availability to guarantee continuity of supply of your production site. Blokset offers an extremely high level of reliability even in the most difficult conditions.
Increased resistance to harsh environments Forinstallationsinseismiczones
>Asanoption,Bloksetbenefitsfromareinforcedframeworktoguaranteeincreasedresistancetoearthquakes(IEC68.3.3).
Forinstallationsincorrosiveenvironments
>Asstandard,Bloksetproposesavarietyofprotectionlevels(IP20,IP31,IP42andIP54)tosatisfytheneedsofapplicationssuchascementworks,ironandsteelindustry,etc.
>Forapplicationssuchaswater,papermillsandrefineries,conductivepartssuchasbusbarsandclampsreceiveaspecificanti-corrosionsurfacetreatment(tin,nickel,etc.).
>Anti-corrosiveBloksetlimitsshort-circuitrisksduetodamagedcopperandcoatings,thusextendingyourequipmentlifetime.
Minimise downtimes Beinformedtoanticipate
>TheoverallreliabilityofaBloksetsolutionminimisesmaintenance.Thankstocommunicatingdevices,youdisposeofallthenecessaryinformationavailableonswitchboardoperationallowingyoutoschedulemaintenancetosuityourproductionloads.Thepossibilitytoworkonfunctionalunitsincompletesafetywiththeswitchboardenergisedincreasesthecontinuityofsupplyofyourinstallations.
Schneider Electric inside
Allthecomponentsofa
Bloksetswitchboard
aredesignedandprodu
cedbySchneiderElectri
c.
Theguaranteeofinve
stinginequipmentthat
isperfectlyoptimised,co
mbiningahighlevel
ofperformancewithtrie
dandtestedreliability
Thecertaintyofrapidre
turnoninvestment.
Thermal monitoring Designed for Schneider Electric LV equipment, this system continuously monitors temperature rises by means of probes fitted at the centre of sensitive areas, such as busbars and drawer contacts. The thermal monitoring system reduces the likelihood of failure and decreases maintenance time.
-
Chapter011-8
Blokset MotorSys iPMCC: more intelligence in your switchboardMotorSys iPMCC is Bloksets most advanced solution. Its architecture is open to the main industrial communication protocols. It can be easily and safely incorporated into the existing infrastructure of your sites.
Optimise motor performance>TheBloksetMotorSysiPMCCsolutionsensuremonitoringandprotectionofmotorswithabehaviouronfailureinaccordancewithstandardIEC/EN60947-7-1.Theyincorporatecommunicatingelectronicprotectionrelaysusingmotorprotectionmodelsofunequalledaccuracy.
>Motorandprotectiondeviceconfigurationisaccessibleatalltimes,thuslettingyouquicklyadjusttheiroperationtoyourproductionrates
Access information in real timeEssentialtooptimisecontrolandmonitoringofyourprocess,maketherightdecisionsattherighttime,ensuretraceabilityofproduction.
>WithBloksetMotorSysiPMCC,allthisinformationisavailablelocallyorremotely:-motoroperatingstatusandtimemonitoring(alarmsandtripping),-parametermonitoringandmanagement:statuses,measurements,diagnostics,histories,-energyconsumption.
Save up to 15% on your electricity consumption
ExampleofprocesslevelEthernetcommunicationarchitecturewithBloksetMotorSysiPMCC
-
Chapter01 1-9
Increase your energy efficiencyElectrical energy accounts for a large part of your global production cost. Blokset allows you to reduce the energy consumption of your equipment while also enhancing its performance.
Make energy savingsTheBloksetsolutionshaveanimmediateandmeasurableimpactonyourelectricalenergyconsumption.
>Theyincludeprogressivestartersandvariablespeeddrivesadaptingmotoroperationtotheloadsrequiredforareductioninconsumptionpeaksof50%ormore.
Eco design and eco production >Rightfromthestartofproductdesign,wetakeintoaccountthematerialsrequiredforitsproductionandusethosethathaveleastimpactontheenvironmentbothintheiroriginandintheirproduction.Ateachstageofproductdevelopment,wehaveaccesstoglobalassessmentofitsimpact,thuslettingusoptimisechoiceofmaterials.
>Theycanbecombinedwithcapacitorstomanagereactivepowercompensationandthermalwithstandcontrol,thuseliminatingreactivepowercostsandextendingthelifetimeofthedevicesconnectedtothenetwork.
>Measurements,particularlyforusefulenergyconsumption,helpdefineandmonitormotorloadprofilesandconsumption,thusenhancingtheperformanceofanenergyefficiencyplan.
And protect the environmentBetter use of the planets energy resources is one of the areas in which we can reduce our carbon footprint. Designing and producing eco compatible products is another. This is Schneider Electrics approach.
End of life treatment >Choiceofmaterialsisalsodictatedbytheeasewithwhichtheycanberecycled.Atendoflife,allSchneiderElectricproductcomponentsandtheirpackagingcanberecycled.
Nohazardoussubstances>OurproductdesigntakesaccountofthevariousinternationalrecommendationsandinparticulartheRoHSEuropeandirective.Bloksetdoesnotcontainanyhazardoussubstances.
-
Chapter011-10
Offer overview
Schneider Electric Best in class products
Its broad choice of columns allows Blokset to satisfy all your requirements and the performance needs of your applications, even in harsh environments.
Power circuit protection and control>Masterpact,CompactNSandCompactNSXArangeofcircuit-breakersforLVACprotection,controlanddisconnectionofcircuitsandloads.
Energy consumption and quality metering>PowerLogicPM800Arangedesignedformanagementofyourenergy:metering,quality,availability.
Motor motion control>Altivar31,61,71andAltistart48Arangeofvariablespeeddrivesandprogressivestartersforverysimplevariablespeedcontrol,offeringawidechoiceofinstallationpowers,applicationsandprotection.
Motor protection and control>TeSysT,TeSysUandTeSysDAbroadrangeofrelays,controllersandmotormanagementsystemscoveringallyourneeds,fromthesimplesttothemostadvanced.
Process automation>Quantum,PremiumandM340Arangeofprogrammablelogiccontrollersforprocesscontrol,includingcommunication,diagnosticanddatastoragefunctions.
D Dc Mf Mw2 Ms
Application
Distribution (PCC)
Motor (MCC)
Fonction
Incoming cubicle
Distribution cubicle
Type
Disconnectable
Withdrawable
Fixed
-
Chapter01 1-11
Technical dataGeneral data
Applications DistributionMotorcontrolReactivepowercorrection
Referencestandards IEC61439-1&2IEC60439-1IEC60529IEC61641
Climaticresistance-dampheatwithstand-dryheatwithstand-lowtemperatures-saltspray
IEC60068-2-30IEC60068-2-2IEC60068-21IEC600068-2-11
Installation Indoor
Environment Type2
Mechanical data
Cableinlet Top/bottom
Access Front/rear
Degreeofprotection(IP) 20/31/42/54
Form 1/2b/3b/4
Withdrawability FFF/WWW
Dimensions:HeightWidthExtensionDepth
2200600/700/800/900/1000/1200200/400400/600/1000
Averageweight 650Kg
Panelcoating Polymerisedepoxy/polyesterpowder(SPO3)>50
Framework Galvanised
Panelcolour RAL9002(lightgrey)/RAL7016(graphitegrey)
Electrical data
Ratedinsulationvoltage(Ui) 1000VAC
Voltagerating(Ue) 690VAC
Ratedfrequency(F) 50/60Hz
Ratedimpactwithstandfrequency(Uimp) 12kV
Auxiliarycircuitratedvoltage 230VACmax.
Surgecategory IV
Degreeofpollution 3
Ratedcurrent(ln) 6300A
Horizontalbusbarrating SJB-4000A/DJB-6300A
Verticalbusbarrating Upto3200A
Horizontalbusbar:Rated1sshort-termcurrent(lcw)Ratedpeakcurrent
30/50/85/100kA63/105/187/220kA
Verticalbusbar:Rated1sshort-termcurrent(lcw)Ratedpeakcurrent
30/50/85kA63/105/178kA
Ratedconditionalshort-circuitcurrent(lsc) 100kA
InternalarcprotectionIEC61641 85kA0.3s
Earthingsystem TT-IT-TNS-TNC
Powerincomingandoutgoinglimits Upto6300A
Motorcontrolfeederlimits Upto250kW400V
-
Chapter011-12
35,rueJosephMonier
F-92500Rueil-Malmaison
FRANCE
Tl.:+33(0)141297000
www.schneider-electric.com
Duetopossiblechangesinstandardsandequipment,thefeaturesdescribedinthisdocumentintheformoftextandimagesaresubjecttoconfirmationbySchneiderElectric.Publication:SchneiderElectricPhotos:SchneiderElectric-LeePrince/LosevskyPavel/ClaudioZaccherini/ShutterstockDeirdreMotto/Jupiterimages-JosA.Rojo-BayHippisley/MattonimagesDesign:pemaco
SchneiderElectricIndustriesSAS
Make the most of your energy
TheyproposeacomprehensiveanduniqueBloksetsupportserviceofferforenhancedreliabilityofyourequipment:>Validatedtoolsandarchitectures.>Proximityservicesfortheinstalledbase:componentavailability,assistanceandtroubleshooting.>Adviceandguidanceformaintenanceandrenovation.>Customisedvocationaltraining,onsiteorinoneofourfiftytrainingcentres.
Associated proximity servicesThroughout the world, our local partners are available to listen to your needs
OverandbeyondtheservicesassociatedwiththeBloksetoffer,SchneiderElectricproposescomprehensiveservicesinthesectorsofauditingandconsulting(engineeringexpertise,installationaudits,energyaudits,globalenergyefficiencysolutions,etc.),andsolutionengineering(projectmanagementandimplementation,sitemodernisation,customerprojectseithercustomisedorforcriticalapplications,processsimulation,energymanagement,etc.).
Services with high added valueYou can rely on the Schneider Electric services to help you increase your performance throughout your installation life cycle.
Partner licencedby
The Blokset panel-builder network guarantees you
optimum proximity service>Thesepartners,selectedfortheirexpertise,aretrainedandregularlyauditedbySchneiderElectrictoguaranteetopqualityequipment.>TheBloksetofferisalsoavailableinSchneiderElectricsregionalequipmentunits.
-
Chapter01 1-13
New
Mw2Introduction Fields of applications
Oil&GasContinuity of service and safety
In Oil&Gas industries, the installation is expected to minimize risks for the people and the environment. InBloksetswitchboards,theintelligenceispresentinthedistributionandmotor
controlapplications,toanticipaterisksoffaultscriticaltotheenvironment. Bloksetprovidesoperationalsafetywithadaptedequipementslimiting a
possible short-circuittothefunctionalunit(Polyfast),andconfining the internal arctothecolumnbusbar(horizontalbusbarscreen). Thankstothesecomponents,repairingoperationsafterafaultarelimitedtothe
concernedareaintheswitchboard,andre-energizing occurs quicklyfollowinganincident.
Minesandminerals
Environment and safety
Dust and gas produced by treatment and combustion in mine and mineral industries are risk factors for a correct operation of electrical equipements in these industries. BloksetIP54versionisdesignedtopreventthesetroubles,withconductiveparts
receivingaspecific coating treatment,inordertolimittheeffectsofthecorrosioncausedbysulfuredatmospheres. IP54gasketsprovideenoughair- and watertightnesstoavoidanydustdeposit
insidetheswitchboards,whichwouldbelikelytocauseinternalshort-circuits.
Infrastructures
Continuity of service and safety
Due to the use of withdrawable solutions or drawers on Polyfast units, Blokset can provide continuity of service, even whilst additional feeders are being added, and maintain safety through the use of innovative solutions (wear-free clamps in busbars, etc.).
Guarantee that all the electrical installations are operating correctly forthesafetyoftheemployees:
airquality, lighting, informationandprotection,
forthesafetyofequipment: faultdetection(fire,powerfailure), smokeextractionstartup, safetyofautomatedoperations.
WatertreatmentContinuity of service and environment
The quality expected in water treatment processes requires a total continuity of service in the installations; the environmental nuisances and the costs induced by production stops demand secured installations:
-
Chapter011-14
New
Mw2Introduction
Intelligent solutions for fast and easy access to information from anywhere, around the clock
MotorSys intelligent Power & Motor Control Center - iPMCC in Blokset
Informationforlocaloperation,maintenanceandupgradingofyourinstallationInformationonelectricaldistribution,motoroperationandpowerconsumptioncanbeaccessed.
>MotorSysiPMCCsolutionscanintegrateadedicatedhuman-machineinterface(HMI)orcommunicateviaapersonalcomputerdirectlyonthemotorstarters.
2
Our MotorSys iPMCC
solutions help your teams
optimise the energy efficiency
of your assets, offering the
following benefits:
Dependability,
eveninsevereindustrial
environments,
Safetyofpersonnel
andassets,maintainabilityand
upgradability,
Leadtimemanagementand
riskaswellascostreduction
throughoutyourinstallation's
entirelifecycle.
RemotecontrolandmonitoringofyourinstallationAcontinuous,real-timecommunicationinterfacewithyourcontrolandmonitoringsystemsforenergymanagementandprocesscontrol.
>MotorSysiPMCCsolutionscommunicatewiththemajorindustriallocalareanetworksonthemarket(EthernetTCP/IP,Profibus-DP,DeviceNet,Modbus,etc.).>Withdatadeliveredinrealtime,youroperationalandmaintenancestaffwillhaveimmediateaccesstotherelevantinformationtocontrolyourmotorsandelectricaldistributionlocallyorremotely.>Warningmessagescanbesentautomaticallytoamobilephoneintheeventofanalarmorgroupofalarms.
Our MotorSys iPMCC solutions for continuous and critical processes were developed through our specific expertise in energy and industrial process control management. Forming the keystone of the energy efficiency of your process units, they incorporate a range of functions to supply power (intelligent Power Control Centre - iPCC), start up, control, protect and monitor your LV network electric motors and loads (intelligent Motor Control Centre - iMCC). The breadth of the range ensures that all types of continuous and critical process as well as specific requirements are covered.
1
1
-
Chapter01 1-15
New
Mw2Introduction
MotorSysTM iPMCC
solutions integrate
perfectly into your
site network
infrastructure,
whatever the
communication
protocol, but also
into energy
management
control systems
and process control
systems
Example of a
MotorSysTM iPMCC
solution integrated
into a site
infrastructure
InformationforsiteengineeringWithinformationdeliveredtoensurethetraceabilityofelectricaldistribution,motoroperationandpowerconsumptiondata,installationsareconstantlyimproved.
>MotorSysiPMCCsolutionsmakeiteasytocollectallthestatisticsyouneedtodevelopeffectiveplanscoveringtheoperation,maintenance,optimisationandupgradingofyourinstallations,aswellasenergyefficiency.
3
2
3
-
Chapter02 2-1
New
Mw2Index
Cat. n Designation Pages Cat. n Designation Pages
0100001215 5rectangulargrommets 8-20700007081 6mmearthbraid 4-30;5-312;6-131700000017260203 Flatgasket18x3mm 7-217418240 Roofgasket 7-21000019088 NG125Rotaryhandle 4-32000027046 C60operatingsubassembly 4-327047 C60rotaryhandle 4-328052 NS80Rotaryhandle 5-1029343 NS100LRotaryhandle 4-3;5-103000032598 NS400LRotaryhandle 4-3;5-105100000051130773 "Donotwalk"adhesive 4-44;5-34851130777 Lighteningadhesive 4-44;5-3488000087139 200waterproofwashersD=6 8-287182 1000selfthrscr/M6x13 8-287187 5auxbusduct4x32A 6-4087196 500selfthrscr/M4x8 8-287265 connectionsupport630A3P 4-36;4-37;4-40;
4-48;4-4987266 connectionsupport630A4P 4-36;4-37;4-40;
4-48;4-4987288 TesysTscrewconnectWeid 5-33687370 downstreamjaws3P630A 4-36;4-37;4-48;
4-4987371 downstreamjaws4P630A 4-36;4-37;4-48;
4-4987461 Keylockdoublebit 6-1387635 greaseelectricalcontact-1kg 8-288600 Spowerconnectionblock3P 4-40;5-336;5-338;
5-34088601 Mpowerconnectionblock3P 4-40;5-336;5-338;
5-340;5-34288603 Spowerconnectionblock4P 4-4088604 Mpowerconnectionblock4P 4-4088606 FPS/Moutgoingsupport 4-36;4-37;4-48;
4-49;5-332;5-333;5-352;5-353
88608 S/MpowerconnectionextY-D 5-338;5-340;5-342
88610 Lpowerconnectionbox 4-40;5-338;5-340;5-342;5-344
88612 connectionPh2Ph3LAg 4-40;5-338;5-340;5-342;5-344
88613 connectionPh1NLAg 4-40;5-338;5-340;5-342;5-344
88616 connectionsupportblocL 4-40;5-338;5-340;5-342;5-344
88617 NS400L690Vinsulatingscreen 4-41;5-34588618 SpacerforSCoutgoingsupportL/XL 4-37;4-49;5-333;
5-35388619 VBBsupport30&50x8 6-3788620 VBBtapeoffoutlet 6-3788621 FPoutgoingsupportL/XL 4-36;4-37;4-48;
4-49;5-332;5-333;5-352;5-353
88622 BBsupport20x8 6-3788624 ThreadedrodinsulatorM82x0.95m 6-3788625 insulatingbraceL18 6-3788626 insulatingbraceL32 6-3788627 insulatingbraceL44 6-3788630 Auxiliaryconnectormechanism 4-42;5-34688631 auxfingerguidesingle 5-346;5-347;4-42;
5-346;5-34788633 auxfingerguidedoubleL/XL 4-42;5-346;5-34788640 SCoutgoingpadS/Mph1/2/3 4-36;4-48;5-332;
5-35288641 SCoutgoingpadS/Mneutral 4-36;4-4888644 RCoutgoingpadS/M 4-37;4-49;5-333;
5-353
88646 maleauxiliaryconnector24p 4-42;4-45;5-346;5-349
88647 femaleauxiliaryconnector24p 4-42;4-45;5-346;5-349
88648 2000malecontacts 4-42;4-45;5-346;5-349
88649 2000femalecontacts 4-42;5-346;4-42;5-346;4-45;5-349
88652 100Cableadaptator2.5mm 4-45;5-34988653 200SELFCLINCHINGCAPTIVESTUDS
M64-30;5-320
88660 bearinganti-tip 4-36;4-48;5-332;5-352
88662 DrawerhandleC100H,C100F,C200H 4-30;5-32088663 Drawerskates 4-40;5-336;4-40;
5-336;5-338;5-340;5-342;5-344
88664 DrawerhandleC200Fandmore 4-30;5-32088668 100codingpins 4-44;5-34888669 FIXPARTPOSITIONNINGPIN 6-3988670 flatgasket25x8mm 7-288671 flatgasket10x6mm 7-288672 DrawerFrontplateaxis 4-30;5-320;6-1288673 Frontplatedrawerlock 4-30;5-32088674 Drawerwheel 4-40;5-338;5-340;
5-342;5-34488675 Bendedhandlefordrawer 4-41;5-33988676 Straighthandlefordrawer 4-41;5-337;5-33988677 Drawermech.indexingspring 4-44;5-337;5-339;
5-341;5-34888678 Drawermech.indexingpinaxis 4-44;5-34888679 interlockingspring 4-41;5-337;5-339;
5-341;5-343;5-345
88680 Indexingpad 4-36;4-48;5-332;5-352
88681 HandleforGV2drawer 4-41;5-337;5-33988682 HandleforGV3drawer 4-41;5-337;5-33988683 Drawerpositionning 4-36;4-48;5-332;
5-35288684 1000ScrewST4.2x13forplasticpart 8-288687 Drawercarryinghandle 5-34188688 DRAWERHANDLEFORNS80C300F 5-341;5-34388690 positionningmicroswitch 4-45;5-34988701 Indexingpushbutton 4-30;5-32088702 Setof4liftinglugsandcaptivenuts 6-1788710 anglesquare 6-888711 anglesquare 6-889451 Keyfordoublebitkeylock 6-1389452 Keyforsquarekeylock 6-1389462 Squarekeylock 6-1389465 SetofwaterproofwashersIP31/54 6-16ESES00141 IP20/54Sidepaneldepth1000complement 6-14ES00142 IP20/54Sidepaneldepth600 6-14ES00144 IP31Sidepaneldepth1000complement 6-14ES00145 IP31Sidepaneldepth600 6-14ES00801 Hinge 6-12ES00804 Locking 6-12ES00814 Outgoingcables 6-16GVGV2APK01 GV2Rotaryhandle 5-10GV2V03 Multipadlockingdevice 4-46;5-350GV3APK01 GV3Rotaryhandle 5-10LTMLTMCU TeSysTHMI 5-312LU9LU9APK01 TesysURotaryhandle 5-10LVLV429338 NSX100/250Rotaryhandle 4-3;5-10LV432598 NSX400/630Rotaryhandle 4-3;5-10VDI77VDI7762 RJ45base 5-320VDI7763 RJ45IP54cap 5-320
Catalogue numbers
-
Chapter03 3-1
New
Mw2Description and
characteristics
Electricalandmechanicaldata 3-2Switchboard 3-2ContactsandBusbars 3-3
-
Chapter033-2
New
Mw2Description and
characteristicsDD40
5109
PD40
1004
Electrical and mechanical data
General dataapplications distribution
motorcontrolstandardreference IEC60439-1
IEC60529IEC61439-2
climaticresistance dampheatwithstandasperIEC60068-2-30dryheatwithstandasperIEC60068-2-2lowtemperatureresistanceasperIEC60068-2-1saltsprayresistanceasperIEC60068-2-11
installation indoorenvironment(EMC) type2
Mechanical data
cableentry top/bottom
access front/rear
IP 20/31/54
departureform 3b/4b
withdrawability WWW
Dimensions
height 2200mm
width 600/800/900/1000mm
depth 600/1000mm
modularity pitchof50mm
averageweight 650kgpersection
finish galvanizedorelectro-galvanizedsteel
coating epoxy/polyesterpowder(SP03)polymerised>50
panellingcolour RAL9002
Electrical dataratedinsulationvoltage(Ui) 1000Vratedoperationalvoltage(Ue) 415/690VACratedfrequency(F) 50/60Hzratedimpulsevoltage(Uimp) 12kVratedauxiliarycircuitvoltage 230VACmax.overvoltagecategory IVpollutiondegree 3mainbusbarrating 6300Amaxdistributionbusbarrating 2000Amaxratedshort-timecurrent(lcw)1smainbusbar(ratedpeakcurrentlpk)
85kArms(187k)
ratedshort-timecurrent(lcw)1sdistributionbusbar(ratedpeakcurrentlpk)
85kArms(187k)
ratedconditionalshort-circuitcurrent(lcc) upto85kAearthingsystem TT-IT-TNS-TNCmotorcontrolfeederlimits upto250kW415/690V
Switchboard
-
Chapter 03 3-3
New
Mw2Description and
characteristicsD
D40
5643
DD
4010
65
DD
4010
64D
D40
5644
PD
4010
05
DD
4056
42DD
4056
61
DD
4056
64
DD
4056
66
DD
4056
65
DD
4056
62
Electrical and mechanical dataContacts and Busbars
Horizontal busbar = main busbar
Double busbar up to 6300A.
Single busbar up to 4000A.
Vertical busbar = distribution busbar
Mw2 vertical busbar: b for feeders cubicle up to 2000A.
Power connector
Auxiliary connector
XL clamp.M connectorS connector L connector
Withdrawable auxiliary blocksrated insulation voltage (Ui) 500 Vrated operation voltage (Ue) 230 V ACrated current (In) 10 Asignal maximum frequency 1 Mb / s max. (*)equipment capacity 1 or 2 blocks of 24 contacts max.(*) in accordance with the following communication buses: - Ethernet - Modbus SL - Profibus DP (1.5 Mb) - DeviceNet - CanOpen.
-
Chapter04a 4-1
Electrical Distribution Functional Units
New
Mw2
Technicaldescription 4-2Typesoffunctionalunits 4-2
Configurationoverview 4-3
MotorSysiPCCDrawers 4-4
Selectionofthedrawer 4-5
MotorSysiPCCDrawers,415V 4-6IP31T35 4-6IP31T40 4-8IP31T45 4-10IP31T50 4-12IP54T35 4-14IP54T40 4-16IP54T45 4-18IP54T50 4-20
MotorSysiPCCDrawers,690V 4-22IP31T35 4-22IP31T40 4-23IP31T45 4-24IP31T50 4-25IP54T35 4-26IP54T40 4-27IP54T45 4-28IP54T50 4-29
Frontfaces 4-30100mmhalfwidth 4-31200mmhalfwidth 4-32200mmfullwidth 4-33300mmfullwidth 4-34400mmfullwidth 4-35
Fixedparts 4-36
Form3and4 4-38
Movingparts 4-40
Auxiliaries 4-42
DrawerAccessories 4-44
Reserve 4-48
-
Chapter04a4-2
Electrical Distribution Functional Units
New
Mw2
Overview
Withdrawable FU in drawer
Technical descriptionTypesoffunctionalunits
b ThewithdrawabledrawerisusedinahugerangeofelectricaldistributionFunctionalUnits,upto630A.
The drawer is used to make up a Functional Unit consisting of several mechanically attached devices, that can assume the plug-in / test / draw-out / withdrawn positions, allowing the padlocking procedures and incorporating the man / switchboard interface elements on the front panel.
b Indistribution,theneedtoindicateandcontrolonthefrontpaneloftheFUandthenecessitytopadlockarethemainchoicecriteria.
b Thefixedpartisinstalledandremovedwithpoweronandsupportstheupstreamanddownstreamplug-inclamps.
b Themovingpartsupportstheswitchgearbymeansofamountingplate.Itisguidedinitsmovementandpositioning,andballbearingsminimisetheoperatingeffort.
b Thefrontpanelofthedrawergivesprioritytoergonomicsandintuitionofoperationsbythearrangementofthelockingfacilitiesandoperatingmechanisms.
b Accesstotheinsideofthedrawermaybenecessaryduringoperation,tomakesettingsorcarryoutathermographiccheck.Adeliberateopeningbyswivellingthefrontpanelispossibleusingatool.
b AnIP2Xdegreeofprotectionismaintainedinthetestanddraw-outpositions.
b Lockingispossibleinallpositionsbyapadlock(3padlocksnotsupplied),asisalsopadlockingofemptycompartments.
(*)liveworkmustbecarriedoutbyauthorisedpersonnel
Drawer positions
Plug-inb Thefunctionalunitisoperational.b Powerandauxiliariesareconnected.
Testb Thepowercircuitisdisconnectedb Onlyauxiliariesareconnected.b Itallowsthefunctionalunitverification.b