High Efficiency Enclosed Vapor Combustors to
Reduce Venting Emissions
VOC Destruction Technology
BGR Combustor Description
Available Models: BGR-18 LP & BGR-24 HP/LP
BGR-24 - 24"x26' free standing LP vapor combustor and HP flareBGR-18 – 18”x10’ free standing LP vapor combustorNo visible flame from low pressure burnersLow pressure volumes:
BGR-24 – 24,048 scfd w/pilot at >99.9% destructionBGR-18 – 12,960 scfd w/pilot at >99.9% destruction
Excellent low pressure turndown ratio of 75:1BGR-24 high pressure volume: 1.7 MMscfd from 3” flare tipL/P burner air inlet provides air assist for H/P flameACL 3200 dual ignition control system with:
Remote start/stopAuto re-lightTemperature sensing and monitoring (if required)Solar operating 12/24 volt dcModbus communication built inData logging
ApplicationsCrude oil, condensate, and produced water tank vents; glycol dehydrator flash tank vents, regenerator still vents, and wet seal compressor vents, and casing gas venting.Sites with no gathering systems for gasFacilities which require low pressure vent control and high pressure flaring
NSPS Subpart OOOO and NESHAP Subparts HH/HHH Certification
U.S. EPA rules require extensive certification testing4 rigorous test conditions with 100% propylene:
90-100% - steady flow70-100-70% - ramping up & down30-70-30% - ramping up & down0-30-0% - ramping up & down
Compliance demonstrated
U.S. EPA BGR-24 Certification
Parameter90 -
100%
70 -100-70%
30 – 70-30%
0 – 30-0%
Limit
CO, ppmvd 4.17 2.81 3.07 4.98 <10
Total HC as C2H6, ppmvw <0.01 0.04 0.29 0.46 <10
Total HC as C2H6 Destruction Efficiency, %
>99.99 >99.99 >99.99 99.99 >95
Excess Air, % 247.8 291.2 386.5 989.7 >150
Stack Temperature, oF 1,243 1,146 928 671 NA
Inlet LP flow – 16.7 scfm or 24,048 scfd (including pilot)Exceeds EPA, AER, and MOE regulation requirements.
U.S. EPA BGR-18 Certification
Parameter90 -
100%
70 -100-70%
30 – 70-30%
0 – 30-0%
Limit
CO, ppmvd 4.29 2.04 3.15 2.60 <10
Total HC as C2H6, ppmvw 0.34 0.10 0.36 0.23 <10
Total HC as C2H6 Destruction Efficiency, %
>99.99 >99.99 >99.99 99.98 >95
Excess Air, % 254.9 254.6 301.1 421.9 >150
Stack Temperature, oF 1,178 1,120 1,036 915 NA
Inlet LP flow – 7.5 scfm or 12,960 scfd (including pilot)Exceeds EPA, AER, and MOE regulation requirements.
High Pressure Dispersion Modeling
Worst-case, conservative, screening approach and assumptions:
H2S at 1.5 volume %; 1.115 MMscfd flowH2S at 1.0 volume %; 1.7 MMscfd flow100% conversion to SO2; 99% destruction of H2SU.S. EPA AERSCREEN model
Results demonstrate compliance with Alberta and Saskatchewan limits
1-hour, 24-hour, annual SO21-hour and 24-hour H2S (no annual limit)
HP Radiation – 26’ High Stack
Recommended thermal radiation levels and calculations based on API Recommended Practice 521.Should be set ~95 feet from personnel work areas.
Benefits of BGR Low Pressure Vapor Combustors?No additional fuel, air, or steam assist required,
can be operated on waste gas only with no visible flameNo expensive control systems or valve trains requiredCan operate via solar power for remote sitesOperate as low as 2 oz pressure from storage tanks while maintaining at least 99.9% destructionEqual combustion efficiencies to more costly thermal incinerators and oxidizersIdeal for storage tank, casing gas and dehy unit low pressure ventingProven technology through 3rd party testing
Benefits of BGR-24 L/P-H/P Vapor Combustor?
High pressure line capable of large volumes during upsets and emergenciesReplaces separate L/P and H/P flare stacks while remaining compliantLow radiation impactsHP flare is NSPS Subpart A (40 CFR 60.18) compliant up to 1.7 MMscfdState of the art ACL Manufacturing burners and burner controlsInexpensive alternative to incinerators and separate L/P and H/P flare stacks
Questions?