![Page 1: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/1.jpg)
Amines in Air Cooled Condensers San Diego Annual Conference
September 24, 2014
Bill Stroman
![Page 2: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/2.jpg)
AIR COOLED CONDENSER• Large iron surface area• Potential for air inleakage• Air inleakage can lead to problems with freezing
![Page 3: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/3.jpg)
Chemistry Control Limits and Action Guidelines for Addressing:
• Steam Cycle Chemistry – Preboiler, Boiler, Steam, Condensate
• Online Monitoring • Routine Grab Sample Testing • Abnormal Conditions-What is done? • Cycling conditions for Startup & Shutdown • Layup
![Page 4: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/4.jpg)
Chemistry Program Requires Representative Sample In Order To:
• Measure • Maintain • Manage • Make Improvements
![Page 5: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/5.jpg)
FAC corrosion in duct and Inlet tube areas
![Page 6: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/6.jpg)
![Page 7: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/7.jpg)
![Page 8: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/8.jpg)
For ~10 years the chemistry was hydrazine/morpholine then was changed during 2006 to ammonia treatment. Problem was not previously noted. This picture was provided to use as DHACI #4
![Page 9: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/9.jpg)
![Page 10: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/10.jpg)
18 inch crack below steam turbine exhaust
![Page 11: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/11.jpg)
Vacuum kPa(a) vs Iron Corrosion
0.000
0.050
0.100
0.150
0.200
0.250
0.300
0.350
0.4001/
1/20
04
4/1/
2004
7/1/
2004
10/1
/200
4
1/1/
2005
4/1/
2005
7/1/
2005
10/1
/200
5
1/1/
2006
4/1/
2006
7/1/
2006
10/1
/200
6
1/1/
2007
4/1/
2007
7/1/
2007
10/1
/200
7
1/1/
2008
4/1/
2008
7/1/
2008
kPa(
a) b
lue/
Iron
cor
rosi
on m
g/L
kPa(a) Iron - mg/l
Started ammonia treatment
air leaks repaired
![Page 12: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/12.jpg)
Corrosion byproduct accumulation
• Leads to deposition and corrosion related failures
• Cost to chemical clean HRSG boilers is very expensive
• Cost to dispose of post chemical cleaning waste is very expensive
• HRSG units are not designed for conventional chemical cleaning methods to address tube corrosion issues
![Page 13: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/13.jpg)
HRSG corrosion by products migrate into boilers
![Page 14: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/14.jpg)
![Page 15: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/15.jpg)
![Page 16: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/16.jpg)
![Page 17: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/17.jpg)
Underdeposit Corrosion
• Problem with HRSG units is the tubes have fins. NDE for oxide thickness not viable.
• If underdeposit corrosion has developed can do some NDE but only the leading row.
• When was a tube specimen removed to evaluate the internal condition?
![Page 18: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/18.jpg)
Amine Use • Have been successfully used in steam
generating equipment for >40 years • Used in essentially all US Nuclear facility
steam generators • EPRI recommends the use of ammonia for
feedwater pH control in all ferrous systems but needs to be maintained in desired pH control range.
• However, if not controlled in desired pH range corrosion occurs in ACC.
![Page 19: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/19.jpg)
~30 years service On Neutralizing amine treatment
![Page 20: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/20.jpg)
Feedwater pH
• pH must be alkaline to minimize iron corrosion
• For all ferrous units 9.2-9.6 is recommended units with ACC 9.4-10 with 9.8-10 preferred.
![Page 21: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/21.jpg)
Common Amines in Steam Production
• Cyclohexylamine • Morpholine • Ethanolamine (monoethanolamine) [MEA] • Methoxypropylamine (MOPA) • Diethylaminoethanol (DEAE)
![Page 22: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/22.jpg)
MEA/Ammonia blend • Plants with discharge limits that prevents
operation in the high 9 pH range require a chemistry treatment to provide better metal passivation.
• MEA/Ammonia was evaluated and found a reduction in iron transport and better passivation with slight increase in specific and cation corrected conductivity.
• Anodamine is in the process of being evaluated to address intermittent operation for better protection while off line.
![Page 23: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/23.jpg)
Ethanolamine (MEA)
• Also called monoethanolamine
• Formula: C2H7NO • Molecular Weight : 61.08 • Amine Type Primary • Carbon: Nitrogen ratio 2:1
![Page 24: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/24.jpg)
![Page 25: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/25.jpg)
![Page 26: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/26.jpg)
B&W filter iron test
MEA & Ammonia Blend
![Page 27: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/27.jpg)
Problem with Grab Sampling
• Filter and iron grab sample is only representing the time when sample was taken and does not capture events that continuous sampling would observe.
• Turbidity and particle counter & monitors can provide continuous monitoring.
![Page 28: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/28.jpg)
![Page 29: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/29.jpg)
![Page 30: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/30.jpg)
Average 2 - 3 micron particle count
0
100
200
300
400
014
4028
8043
2057
6072
0086
40
1008
0
Minute of the week
2 -
3 m
icro
n P
art
icle
Co
un
t
Average Count before MEAAverage Count after MEALinear (Average Count before MEA)Linear (Average Count after MEA)
![Page 31: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/31.jpg)
Average 3 - 5 micron particle count
0
20
40
60
80
100
014
4028
8043
2057
6072
0086
4010
080
Minute of the week
3 -
5 m
icro
n P
arti
cle
Co
un
t
Average Count before MEA
Average Count after MEA
Linear (Average Count before MEA)
Linear (Average Count after MEA)
![Page 32: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/32.jpg)
Average 5 - 7 micron particle count
0
10
20
30
40
50
014
4028
8043
2057
6072
0086
4010
080
Minute of the week
5 -
7 m
icro
n P
arti
cle
Co
un
t
Average Count before MEA
Average Count after MEA
Linear (Average Count before MEA)
Linear (Average Count after MEA)
![Page 33: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/33.jpg)
Average 7 - 10 micron particle count
0
1
2
3
4
5
014
4028
8043
2057
6072
0086
4010
080
Minute of the week
7 -
10 m
icro
n P
arti
cle
Co
un
t
Average Count before MEA
Average Count after MEA
Linear (Average Count before MEA)
Linear (Average Count after MEA)
![Page 34: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/34.jpg)
validation
• Physical inspections
![Page 35: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/35.jpg)
2009 inspection
2011 inspection
![Page 36: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/36.jpg)
2009 inspection
2011 inspection
![Page 37: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/37.jpg)
2009 steam turbine condensate Duct drain.
2011 inspection
![Page 38: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/38.jpg)
Air Cooled Condensers
• Backpressure for air cooled condensers is higher than water cooled condensers.
• When air in-leakage is high enough to affect backpressure it is more difficult to detect with air cooled condensers.
• Elevated air in-leakage increases the potential for corrosion that can affect the rest of the steam cycle.
![Page 39: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/39.jpg)
Concerns-Cycling
• Maintaining condenser vacuum is recommended when cycling.
• Air in-leakage potential is high when offline.
• High dissolved oxygen and carbon dioxide promote corrosion in oxygen pitting, corrosion fatigue, stress corrosion cracking and corrosion byproduct transport and down stream deposition.
![Page 40: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/40.jpg)
Source: GEA Power Cooling Systems, Inc.
![Page 41: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/41.jpg)
Continuous Monitoring
• Provides detection of increases in air in-leakage before backpressure is affected.
• Provides real-time air in-leakage rates. • Awareness is required in order to
implement corrective measures.
![Page 42: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/42.jpg)
![Page 43: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/43.jpg)
Vacuum Decay Test
![Page 44: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/44.jpg)
Anodamine Filming Amine • An Alternative to other off line storage
programs? • Following industry publications such as Power
Plant Chemistry, The International Edition, May 2011 publication showing significant corrosion rates improvement to fossil units that were regulated to intermittent service.
• Conference presentations showing favorable reductions in iron corrosion
• Plant decided to evaluate.
![Page 45: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/45.jpg)
Dosing Anodamine Manufacturer recommends achieving a 2 – 3 ppm Anodamine residual throughout cycle and once this is reached a 300 – 400 ppb injection is recommended to maintain residual.
![Page 46: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/46.jpg)
Plant began trial on an intermittent operation unit with ACC
• Unit did not run much during 2013. • Unit did run for couple of months
beginning 2014 that allowed for the Anodamine to get established.
• The following are inspection pictures during March 2014 scheduled maintenance outage
![Page 47: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/47.jpg)
![Page 48: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/48.jpg)
![Page 49: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/49.jpg)
![Page 50: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/50.jpg)
![Page 51: Bill Stroman - Air-Cooled Condenser Users Groupacc-usersgroup.org/.../2014/...Condensers.Bill-Stroman-KAAM-Group.pdf · Chemistry Control Limits and Action Guidelines for Addressing:](https://reader030.vdocuments.site/reader030/viewer/2022013006/5b0e63a07f8b9a6c388b9c65/html5/thumbnails/51.jpg)
Plant Status
• Plant to continue to dose Anodamine/MEA • Plant in process of installing particle monitor • Plant in process of installing continuous air
meter on air removal system • Operations noted that when returning to service
from being off line the samples not longer have color (corrosion by products) present.
• Upper ACC duct inspection next spring.