UMPI Agricultural Sciences Page 1 of 2 Addendum 1 Laboratory Greenhouse
Bid Addendum #1
Project: UMPI Agricultural Sciences Laboratory Greenhouse
Owner: University of Maine System Date of Issuance: November 29th, 2018
From Engineer: Dirigo Architectural Engineering, LLC Contract and Date: TBD
To: Prospective Bidders DAE Project Number: 16-012
This Addendum forms a part of the Contract Documents and modifies the original Bid Documents and
Specifications dated November 2nd, 2018. Portions of the bid and contract documents not altered by this Addendum
remain in full force.
Acknowledge receipt of this Addendum in the space provided on the Bid Form. Failure to do so may subject Bidder
to disqualification.
This Addendum consists of the following:
RESPONSE TO QUESTIONS
1. Spec section 13 34 13 Glazed Structure has a header at the top of each page that says “This section
furnished by owner, installed by contractor”, contained within this section are the alternates for various
portions of the HVAC system. Does the fact that the HVAC alternates are included under the above
described header mean that the HVAC equipment is furnished by the owner?
Response: THE OWNER WILL BE FURNISHING ALL HVAC IN THIS SPEC SECTION ONLY.
2. At the end of Spec section 13 34 13 there are “Owner Furnished – Contractor Installed” cut-sheets that
are not legible, please provide replacements.
Response: PLEASE SEE CUT SHEETS ATTACHED.
3. The orientation of the greenhouse and sheds does not coordinate when comparing Drawing #C-1 with
A1.0.
Response: THE LOCATION OF THE SHEDS AND UTILITIES SHOULD BE REFERENCED FROM THE
C-1 SHEET.
4. Is pre-insulated Type-L or Type-K copper an acceptable alternative to 2” Insulated PEX tubing.
Response: WE ACCEPT THIS ALTERNATE.
UMPI Agricultural Sciences Page 2 of 2 Addendum 1 Laboratory Greenhouse
GENERAL
Attachment 1 – Plan holder list as of 11/29/2018
• The attendance sheet for the non-mandatory pre-bid meeting held on November 14, 2018
is attached for informational purposes only.
Attachment 2 – Cut sheets from Spec section 13 34 13
END OF ADDENDUM #1
Name Company Email Address
Travis Prashaw Soderberg Co. Inc [email protected]
Ryan St.Peter Patrick St.Peter & Sons [email protected]
Gabe Cheney PNM Construction [email protected]
Rick Nadeau A+L Construction [email protected]
Clyde Lynch Bowman Constructors [email protected]
Tobie Devor Aroostook Electrical Services [email protected]
= attended pre-bid site walk
UMPI Greenhouse Project
Plan Holders List - 11/29/2018
50'
RCP-LAB-01
IO
2
WS
MECHANICAL
ROOM
SHED
CLASSROOM
100
OFFICE/CONTROLS
101
LAB
102
LAB
103
ACCESS POINT
AP
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - SITE AND NW.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
SITE LAYOUT
PAGE 1
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
NORTH
IO NETWORK DEVICE
CONNECTION
IO NETWORK SEGMENT
ACCESS POINT WITH IOPS
LOCATED WITHIN 15' OF
ARGUS COMPUTER
CONTROL NETWORK
SEGMENT
WEATHER STATION
WITH NFLP AND FLP
DRAWING IS A VISUAL
REPRESENTATION OF CONTROLS
AND PANEL LOCATIONS.
CONTROLS EQUIPMENT IS NOT
DRAWN TO SCALE. ALL SIZES AND
DISTANCES ARE APPROXIMATE
PASSIVE COUPLER /
REPEATER
CONTROLS ENCLOSURE
RCP-XX-01
IO
RP
TC
AP
CONTROLLER
NETWORK DEVICE
CONNECTION
WS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
CONTROLLER
NETWORK
LAYOUT
CONTROLLER
I/O
CNTL
TC2-TITAN
CONTROLLER
T
RCP-LAB-01
CONTROLLER
I/O
CNTL
TCAP-ACCESS
POINT
T
ACCESS POINT
PC
USB BACKUP
PHONE
LINE
ETHERNET
SWITCH
SU
RG
E
PR
OT
EC
TO
R
AD2001
AUTODIALER
NETWORK/
INTERNET
CONNECTION
= NETWORK TERMINATOR
ALL TITAN NETWORKS TO BE WIRED WITH
WESTPENN AQ224 CABLE NO SUBSTITUTIONS
ALL BOARDS MUST BE CORRECTLY GROUNDED
FOR PROPER LIGHTNING PROTECTION
T
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD. UOM - SITE AND NW.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
R
CONTROLS
Project Mngr: Drawn by:
Dwg:
BYDESCRIPTIONREV.DATE
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
Current Revision:Creation Date:
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TCAP
IO NETWORK
LAYOUT
TCAP-IOPS[1]
IO NETWORK
POWER
SUPPLY
MAX. 100 FEET
FROM
TCAP-NFLP[1]
= NETWORK TERMINATOR
ALL TITAN NETWORKS TO BE WIRED WITH
WESTPENN AQ224 CABLE NO SUBSTITUTIONS
ALL BOARDS MUST BE CORRECTLY GROUNDED
FOR PROPER LIGHTNING PROTECTION
ACCESS POINT
CONTROLLER
I/O
CNTL
TCAP-ACCESS
POINT
TCAP-NFLP[1]
LIGHTNING
PROTECTION
TCAP-NLP[1]
LIGHTNING
PROTECTION
T
T
T
IO MODULE
TCAP-
IO[WS]
WEATHER
STATION
WS3
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD. UOM - SITE AND NW.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
R
CONTROLS
Project Mngr: Drawn by:
Dwg:
BYDESCRIPTIONREV.DATE
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
Current Revision:Creation Date:
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - AP AND WS.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
ACCESS POINT
LAYOUT
12 VDC (7.2Ah)
TITAN ALARM
BACKUP
BATTERY
AD-2001
AUTOMATIC VOICE/PAGER DIALER
WARNING : Make sure to use correct
polarity when connecting Titan Backup
Battery to Controller.
TITAN ALARM BACKUP
BATTERY
CAUTION : Do not connect backup
battery until Titan controller is powered
from the Titan Network Power Supply
or wall adapter.
ETHERNET
SWITCH
TCAP
TCAP-IOPS[1]
TX
-T
CA
P-01
12
0 V
AC
- 2
4 V
AC
75
V
A
TB
-T
CA
P-0
2
FB
-T
CA
P-0
1
TB
-T
CA
P-0
4
TB
-T
CA
P-0
3
GR
OU
ND
GR
OU
ND
FIELD WIRING INFORMATION
Refer To Equipment Supplier's
Instructions For Connection Details
Use Only Copper Conductors That Are
Rated For A Minimum Of 75°C (167°F)
T.P. = Thermally Protected
Disconnect Switches By Installer
Branch Circuit Protection By Installer
Location:
Terminals:
Torque:
Voltage:
Ø1 FLA:
Maximum Circuit Size:
Largest Motor FLA:
Short Circuit Current:
Wire Range:
SUPPLY TERMINALS
Field Wiring Landing Terminals:
Terminal Blocks
FB-TCAP-01, TB-TCAP-02
N/A
120 VAC, 60HZ, 1Ø
1 Amp
15 Amps
N/A
5kA RMS
Symmetrical
12 AWG - 14 AWG
Height:
Bonding Conductor Size:
Wire Range:
Width: Depth:
Maximum Voltage:
SCCR:
ENCLOSURE INFORMATION
UL Type 12, 13 - Al Enclosure
23" 19" 5"
Door Hinged On Left Side
Painted White With Green Argus
Logo On Panel Door
12 AWG
120 VAC
14 AWG - 12 AWG
5kA RMS Symmetrical
120 VAC Maximum
CONTROLS
R
ACCESS POINT
TX
-T
CA
P-0
1
120 V
AC
- 24 V
AC
75 V
A
TB
-T
CA
P-02
FB
-T
CA
P-01
TB
-T
CA
P-04
TB
-T
CA
P-03
GR
OU
ND
GR
OU
ND
ARGUS
USB
BACKUP
4.75"
5.725"
3.75"
5.250"
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TCAP
TITAN ACCESS POINT
CONNECTIONS
NETWORK
TERMINATOR
I/O
NET
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
+
-
-
+
+
-
-
+C
NT
L N
ET
F
US
E 2
CN
TL
N
ET
F
US
E 1
I/O
N
ET
F
US
E 2
I/O
N
ET
F
US
E 1
1.0A1.0A
1.0A1.0A
I/O
NET
CNTL
NET
SEC : #########
15 VDC
OUTPUT
-
+
-+
18 - 24
VDC
AD
AP
TE
R F
US
E
BA
TT
ER
Y F
US
E
0.5A1.0A
A4
A3
A2
A1
-
+
-
+
-
+
+
-
AD
AP
TE
R F
US
E
BA
TT
ER
Y F
US
E
SD MEMORY CARD
INSTALL WITHIN
15' OF PC
1.0 1.0
1.0 1.0
I/O
N
ET
F
US
E 1
I/O
N
ET
F
US
E 2
CN
TL N
ET
F
US
E 1
CN
TL N
ET
F
US
E 2
TO CNTL NET
POWER SUPPLY
LEGACY DEVICE
NETWORK
CONNECTION
+
-
-
+
+
-
-
+
IO NET POWER FAULT
IO NET POWER STATUS
CNTL NET POWER FAULT
CNTL NET POWER STATUS
CNTL NET ACTIVITY
CNTL NET CPU STATUS
CONTROLLER
STATUS
SECURITY CODE
ALARM OUTPUTS
1.0 0.5
AD
AP
TE
R F
US
E
BATTERY STATUS
ADAPTER STATUS
DIALER
POWER
16 VDC
OUTPUT
BA
TT
ER
Y F
US
E
ETHERNET
PRIMARY
CONNECTION
SD MEMORY CARD
SD CARD STATUS
USB
ALTERNATIVE
SERVICE
CONNECTION
TITANCONTROLLER
I/O NET
CNTL NET
TCAP
GL-ALARM OP 1
CONNECT TO ALARM DIALER
CONNECTS TO
AUTODIALER POWER
BOARD POWER
18-24 VDC
BATTERY BACKUP
TERMINALS
ETHERNET CONNECTION
TO SWITCH
GL-ALARM OP 2
CONNECT TO ALARM
GL-ALARM OP 3
CONNECT TO ALARM
GL-ALARM OP 4
CONNECT TO ALARM
NETWORK
TERMINATOR
CNTL
NET
SEE CNTL NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - AP AND WS.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
LEGEND
Zx = ZONE x
GL = GLOBAL
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
**WARNING**
REFER TO EQUIPMENT SUPPLIER'S
INSTRUCTIONS FOR CONNECTION
DETAILS.
USE ONLY COPPER CONDUCTORS
FIELD WIRING MUST BE RATED
FOR 75°C (167°F)
CALL ARGUS CONTROLS AT
1-888-667-2091 FOR ASSISTANCE.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TCAP-IOPS[1]
TITAN IO NETWORK POWER
SUPPLY WIRING
24 VAC IN
POWER FUSE
6.0
A
I/O
NET
+
-
-
+
6.0
A
POWER FUSE
6A FAST ACTING FUSE X2
24 VAC IN
CPU STATUS
POWER OUT
STATUS
TITAN IO NETWORK POWER SUPPLY
+
-
-
+
I/O NET
TCAP-IOPS[1]
I/O
NET
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
TX-TCAP-01
120 VAC - 24 VAC
75 VA
TB-TCAP-03
TB-TCAP-04
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - AP AND WS.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
LEGEND
Zx = ZONE x
GL = GLOBAL
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
**WARNING**
REFER TO EQUIPMENT SUPPLIER'S INSTRUCTIONS FOR CONNECTION DETAILS.
USE ONLY COPPER CONDUCTORS
FIELD WIRING MUST BE RATED FOR 75°C (167°F)
CALL ARGUS CONTROLS AT 1-888-667-2091 FOR ASSISTANCE.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - AP AND WS.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
PAGE 1
ACCESS POINT
WIRING CONNECTIONS
CLASS 1
FIELD WIRING
TX-TCAP-01
120 VAC24 VAC
75VA
TCAP-IOPS[1]
POWER
TCAP-IOPS[1]
FB-TCAP-01 - 2A
120 VAC 60HZ 1Ø - 15 AMPS
DEDICATED FUSE OR BREAKER
PROVIDED BY INSTALLER
TB-TCAP-02
TB-TCAP-03
TB-TCAP-04
ETHERNET SWITCH
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - AP AND WS.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
TCAP-IO[WS]
WEATHER STATION LAYOUT
R
A
I
N
D
E
T
E
C
T
I
O
N
WIND SPEED
WIND DIRECTION
LIGHT
SENSOR
MOUNTING
MAST
1" NPT
THREAD
TEMPERATURE
SENSOR
NFLP
EARTH
NLP
CONTROLS
R
NORTH
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TCAP-NFLP[1]
NETWORK LIGHTNING
PROTECTION
NFLP
NETWORK
TERMINATOR
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
For maximum lightning protection the WS3 connects to the Titan I/O network via the
supplied Network Lightning Protection Module (NLP) mounted on the outside of the
building which is in turn connected to a Network Fused Lightning Protection (NFLP)
module mounted just inside the building.
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - AP AND WS.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
**WARNING**
REFER TO EQUIPMENT SUPPLIER'S
INSTRUCTIONS FOR CONNECTION
DETAILS.
USE ONLY COPPER CONDUCTORS
FIELD WIRING MUST BE RATED
FOR 75°C (167°F)
CALL ARGUS CONTROLS AT
1-888-667-2091 FOR ASSISTANCE.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TCAP-NLP[1]
NETWORK LIGHTNING
PROTECTION
EARTH
NLP
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
For maximum lightning protection the WS3 connects to the Titan I/O network via the
supplied Network Lightning Protection Module (NLP) mounted on the outside of the
building which is in turn connected to a Network Fused Lightning Protection (NFLP)
module mounted just inside the building.
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - AP AND WS.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
**WARNING**
REFER TO EQUIPMENT SUPPLIER'S
INSTRUCTIONS FOR CONNECTION
DETAILS.
USE ONLY COPPER CONDUCTORS
FIELD WIRING MUST BE RATED
FOR 75°C (167°F)
CALL ARGUS CONTROLS AT
1-888-667-2091 FOR ASSISTANCE.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TCAP-IO[WS] - WS3
WS3 WEATHER STATION
SENSOR WIRING
S/N
: 1
23
45
67
SE
C: 6
04
53
83
53
1
LIGHT
W COM
W DIR
RAIN O
RAIN o
INT H
W SP
LIGHT+LIGHT+
TEMP
TEMP
RAIN H
H COM
IO NET
OMNI
WIND SPEED
WIND COMMON
WIND DIRECTION
TO SENSORS AND
HEATERS
BLACK
RED
GREEN
YELLOW
IO BACKPLANE SECURITY CODE
UNIQUE TO EACH BOARD
MUST BE ENTERED INTO CONTROLLER
SOFTWARE FOR WEATHER STATION TO
COMMUNICATE WITH THE TITAN CONTROLLER
FACTORY WIRED
RAIN DETECTION
RAIN DETECTION
BOARD HEATER
GREEN
WHITE
RED
LIGHT SENSOR COMMON
LIGHT SENSOR SIGNAL
TEMPERATURE
TEMPERATURE
BLACK
BLACK
SIGNAL (-)
SHIELD
RAIN DETECTION POWER
BOARD HEATER COMMON
RED
BLACK
RAIN DETECTION COMMONBLACK
SIGNAL (+)
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
For maximum lightning protection the WS3 connects to the Titan I/O network via the
supplied Network Lightning Protection Module (NLP) mounted on the outside of the
building which is in turn connected to a Network Fused Lightning Protection (NFLP)
module mounted just inside the building.
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - AP AND WS.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
**WARNING**
REFER TO EQUIPMENT SUPPLIER'S
INSTRUCTIONS FOR CONNECTION
DETAILS.
USE ONLY COPPER CONDUCTORS
FIELD WIRING MUST BE RATED
FOR 75°C (167°F)
CALL ARGUS CONTROLS AT
1-888-667-2091 FOR ASSISTANCE.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TC2
IO NETWORK
LAYOUT
TC2-IOPS[1]
IO NETWORK
POWER
SUPPLY
= NETWORK TERMINATOR
ALL TITAN NETWORKS TO BE WIRED WITH
WESTPENN AQ224 CABLE NO SUBSTITUTIONS
ALL BOARDS MUST BE CORRECTLY GROUNDED
FOR PROPER LIGHTNING PROTECTION
RCP-LAB-01
CONTROLLER
I/O
CNTL
TC2-TITAN
CONTROLLER
I/O MODULE
TC2-IO
[LAB-A]
T
T
I/O MODULE
TC2-IO
[LAB-B]
I/O MODULE
TC2-IO
[LAB-C]
I/O MODULE
TC2-IO
[LAB-D]
I/O MODULE
TC2-IO
[LAB-E]
T
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD. UOM - SITE AND NW.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
R
CONTROLS
Project Mngr: Drawn by:
Dwg:
BYDESCRIPTIONREV.DATE
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
Current Revision:Creation Date:
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
RCP-LAB-01 : LAB 100-103
PANEL LAYOUT
HIN
GE
S
ID
E
2TX75
RM-LAB-TX1
2TX75
RM-LAB-TX2
2CGR/OL-1P
RM-LAB-01
2CGR/OL-1P
RM-LAB-02
2CGR/OL-1P
RM-LAB-03
2DP-4
RM-LAB-04
2DP-4
RM-LAB-05
2DP-4
RM-LAB-06
2DP-4
RM-LAB-07
2CGR/OL-1P
RM-LAB-08
2CGR/OL-1P
RM-LAB-09
2CGR/OL-1P
RM-LAB-10
2DP-4
RM-LAB-11
CL
AS
S 2 L
OW
V
OL
TA
GE
W
IR
IN
G
CL
AS
S 2 L
OW
V
OL
TA
GE
W
IR
IN
G
CLASS 2 - LOW VOLTAGE WIRING ONLY
CL
AS
S 2 L
OW
V
OL
TA
GE
W
IR
IN
G
CL
AS
S 1 - L
IN
E V
OL
TA
GE
W
IR
IN
G
TC2-IOPS[1]
TC2-IO[LAB-A]
TC2
TC2-IO[LAB-B]
TC2-IO[LAB-C]
TC2-IO[LAB-E]
GROUND
GROUND
GROUND
GROUND
GROUND
GROUND
GROUND
GROUND
2TX75
RM-LAB-TX3
K-LAB-01
TC2-IO[LAB-D]
CONTROLS
RHIN
GE
S
ID
E
RCP-LAB-01 : LAB 100-103
Height:
Bonding Conductor Size:
Wire Range:
Width: Depth:
Maximum Voltage:
SCCR:
ENCLOSURE INFORMATION
72" 36" 8"
UL Type 4, 12 Steel Enclosure
Door Hinged On Left Side
Painted White With Green Argus
Logo On Panel Door
10 AWG
240 VAC
10 AWG - 22 AWG
5kA RMS Symmetrical
240 VAC Maximum
FIELD WIRING INFORMATION
Refer To Equipment Supplier's
Instructions For Connection Details
Use Only Copper Conductors That Are
Rated For A Minimum Of 75°C (167°F)
T.P. = Thermally Protected
Disconnect Switches By Installer
Branch Circuit Protection By Installer
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
PAGE 1
SECTION 1
SEE PANEL LAYOUT
PAGE 2 FOR FURTHER
DETAILS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
RCP-LAB-01 : LAB 100-103
PANEL LAYOUT
CL
AS
S 2 L
OW
V
OL
TA
GE
W
IR
IN
G
GROUND
GROUND
GROUND
K-LAB-01
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
PAGE 2
SECTION 1
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TC2
TITAN CONTROLLER
CONNECTIONS
NETWORK
TERMINATOR
I/O
NET
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
+
-
-
+
+
-
-
+C
NT
L N
ET
F
US
E 2
CN
TL
N
ET
F
US
E 1
I/O
N
ET
F
US
E 2
I/O
N
ET
F
US
E 1
1.0A1.0A
1.0A1.0A
I/O
NET
CNTL
NET
SEC : #########
SD MEMORY CARD
1.0 1.0
1.0 1.0
I/O
N
ET
F
US
E 1
I/O
N
ET
F
US
E 2
CN
TL
N
ET
F
US
E 1
CN
TL
N
ET
F
US
E 2
TO CNTL NET
POWER SUPPLY
LEGACY DEVICE
NETWORK
CONNECTION
+
-
-
+
+
-
-
+
IO NET POWER FAULT
IO NET POWER STATUS
CNTL NET POWER FAULT
CNTL NET POWER STATUS
CNTL NET ACTIVITY
CNTL NET CPU STATUS
CONTROLLER
STATUS
SECURITY CODE
ETHERNET
PRIMARY
CONNECTION
SD MEMORY CARD
SD CARD STATUS
USB
ALTERNATIVE
SERVICE
CONNECTION
TITANCONTROLLER
I/O NET
CNTL NET
TC2
NETWORK
TERMINATOR
CNTL
NET
SEE CNTL NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
LEGEND
Zx = ZONE x
GL = GLOBAL
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
**WARNING**
REFER TO EQUIPMENT SUPPLIER'S INSTRUCTIONS FOR CONNECTION DETAILS.
USE ONLY COPPER CONDUCTORS
FIELD WIRING MUST BE RATED FOR 75°C (167°F)
CALL ARGUS CONTROLS AT 1-888-667-2091 FOR ASSISTANCE.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TC2-IOPS[1]
TITAN IO NETWORK POWER
SUPPLY WIRING
TTN-TXFORMER
120 VAC - 24 VAC
75 VA
24 VAC IN
POWER FUSE
6.0
A
I/O
NET
+
-
-
+
6.0
A
POWER FUSE
6A FAST ACTING FUSE X2
24 VAC IN
CPU STATUS
POWER OUT
STATUS
TITAN IO NETWORK POWER SUPPLY
+
-
-
+
I/O NET
TC2-IOPS[1]
I/O
NET
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
LEGEND
Zx = ZONE x
GL = GLOBAL
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
**WARNING**
REFER TO EQUIPMENT SUPPLIER'S INSTRUCTIONS FOR CONNECTION DETAILS.
USE ONLY COPPER CONDUCTORS
FIELD WIRING MUST BE RATED FOR 75°C (167°F)
CALL ARGUS CONTROLS AT 1-888-667-2091 FOR ASSISTANCE.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TC2-IO[LAB-A]
TITAN IO MODULE
I/O
NET
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
OP
2O
P3
OP
4
+
-
-
+
OP
1
I/O
N
ET
F
US
E 1
I/O
N
ET
F
US
E 2
1.0A 1.0A
24
V
DC
F
US
E
0.5A
S/N : #######
SEC : #########
SECURITY CODE
OP1
OP4
OP3
OP2
STATUS
PWR FAULT
PWR STATUS
IN7
IN6
IN5
IN4
IN3
IN2
IN1
CHA+
FREQUENCY INPUT
ANALOG INPUT
CHB+
A/B -
AN
AL
OG
C
OM
MO
N
24
V
DC
C
OM
MO
N
+24 VDC POWER
OUTPUT
CO
MM
ON
+2
4 V
DC
O
UT
PU
T
PWR STATUS
ACTIVITY
IO NET
24 VDC
IO NET
IO MODULE
POWER
DISCONNECT
JUMPER
TITANIO MODULE
+
-
-
+
I/O NET
1.0 1.0
I/O
N
ET
F
US
E
I/O
N
ET
F
US
E
0.5
24
V
DC
F
US
E
TC2-IO[LAB-A]
AU
TO
S
TA
TU
S
PWR
PWR
PWR
PWR
TITAN P1T
100/102
NORTH RIDGE
VENT
CLOSE
OPEN
AUTO
OPEN
OFF
CLOSE
C
O
C
O
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
AU
TO
S
TA
TU
S
PWR
PWR
PWR
PWR
TITAN P1T
100/102
SOUTH RIDGE
VENT
CLOSE
OPEN
AUTO
OPEN
OFF
CLOSE
C
O
C
O
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
AU
TO
S
TA
TU
S
PWR
PWR
PWR
PWR
TITAN P1T
100/102
SHADE
CURTAIN
CLOSE
OPEN
AUTO
OPEN
OFF
CLOSE
C
O
C
O
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
TITAN D2
AU
TO
S
TA
TU
S
PWR
A1
A2
PWR
PWR
B2
B1
PWR
PWR
B1
B2
PWR
PWR
A2
A1
PWR
100/102
UNIT HEATER
(CALL FOR FAN)
100/102
UNIT HEATER
(CALL FOR HEAT)
A
AUTO
OFF
ON
B
AUTO
OFF
ON
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
IPB
OMNI
TN21
IPB
SEE SENSOR DRAWING
SIGNAL
COM
SEN-OSM-3.0/RHT
100/102-TEMP & RH
100/102-BACKUP TEMP.
2 WIRE SENSOR
SIGNAL
OMNI PWR
IPB100/102-EXH. FAN FAULT
CUSTOM PART
SEE SENSOR DRAWING
SIGNAL
COM
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
LEGEND
Zx = ZONE x
GL = GLOBAL
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
**WARNING**
REFER TO EQUIPMENT SUPPLIER'S INSTRUCTIONS FOR CONNECTION DETAILS.
USE ONLY COPPER CONDUCTORS
FIELD WIRING MUST BE RATED FOR 75°C (167°F)
CALL ARGUS CONTROLS AT 1-888-667-2091 FOR ASSISTANCE.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TC2-IO[LAB-B]
TITAN IO MODULE
I/O
NET
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
OP
2O
P3
OP
4
+
-
-
+
OP
1
I/O
N
ET
F
US
E 1
I/O
N
ET
F
US
E 2
1.0A 1.0A
24
V
DC
F
US
E
0.5A
S/N : #######
SEC : #########
SECURITY CODE
OP1
OP4
OP3
OP2
STATUS
PWR FAULT
PWR STATUS
IN7
IN6
IN5
IN4
IN3
IN2
IN1
CHA+
FREQUENCY INPUT
ANALOG INPUT
CHB+
A/B -
AN
AL
OG
C
OM
MO
N
24
V
DC
C
OM
MO
N
+24 VDC POWER
OUTPUT
CO
MM
ON
+2
4 V
DC
O
UT
PU
T
PWR STATUS
ACTIVITY
IO NET
24 VDC
IO NET
IO MODULE
POWER
DISCONNECT
JUMPER
TITANIO MODULE
+
-
-
+
I/O NET
1.0 1.0
I/O
N
ET
F
US
E
I/O
N
ET
F
US
E
0.5
24
V
DC
F
US
E
TC2-IO[LAB-B]
TITAN D2
AU
TO
S
TA
TU
S
PWR
A1
A2
PWR
PWR
B2
B1
PWR
PWR
B1
B2
PWR
PWR
A2
A1
PWR
100/102
EXH. FAN
ENABLE
A
AUTO
OFF
ON
B
AUTO
OFF
ON
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
TITAN P1A
ST
AT
US
PWM
SINK
SRCE
+24V
0-5V
0-10V
FAULT
MAN
AUTO
0-10V
0-5V
PWM
SINK
+24V
SRCE
0-2
0m
A
100/102
EXHAUST FAN
SPEED
AUTO
UP
DOWN
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
TITAN D4
ST
AT
US
B
C
D
PWR
A
PWR
PWR
A
B
C
PWR
D
PWR
D
C
B
A
100/102
D. FAN
100/102
CIRC. FAN
AUTO ON
OFF
AUTO
OFF
ON
AUTO
OFF
ON
AUTO
OFF
ON
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
LEGEND
Zx = ZONE x
GL = GLOBAL
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
**WARNING**
REFER TO EQUIPMENT SUPPLIER'S INSTRUCTIONS FOR CONNECTION DETAILS.
USE ONLY COPPER CONDUCTORS
FIELD WIRING MUST BE RATED FOR 75°C (167°F)
CALL ARGUS CONTROLS AT 1-888-667-2091 FOR ASSISTANCE.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TC2-IO[LAB-C]
TITAN IO MODULE
I/O
NET
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
OP
2O
P3
OP
4
+
-
-
+
OP
1
I/O
N
ET
F
US
E 1
I/O
N
ET
F
US
E 2
1.0A 1.0A
24
V
DC
F
US
E
0.5A
S/N : #######
SEC : #########
SECURITY CODE
OP1
OP4
OP3
OP2
STATUS
PWR FAULT
PWR STATUS
IN7
IN6
IN5
IN4
IN3
IN2
IN1
CHA+
FREQUENCY INPUT
ANALOG INPUT
CHB+
A/B -
AN
AL
OG
C
OM
MO
N
24
V
DC
C
OM
MO
N
+24 VDC POWER
OUTPUT
CO
MM
ON
+2
4 V
DC
O
UT
PU
T
PWR STATUS
ACTIVITY
IO NET
24 VDC
IO NET
IO MODULE
POWER
DISCONNECT
JUMPER
TITANIO MODULE
+
-
-
+
I/O NET
1.0 1.0
I/O
N
ET
F
US
E
I/O
N
ET
F
US
E
0.5
24
V
DC
F
US
E
TC2-IO[LAB-C]
TITAN D4
ST
AT
US
B
C
D
PWR
A
PWR
PWR
A
B
C
PWR
D
PWR
D
C
B
A
100/102
LIGHTS Z1
100/102
LIGHTS Z2
103
LIGHTS
AUTO ON
OFF
AUTO
OFF
ON
AUTO
OFF
ON
AUTO
OFF
ON
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
TITAN D4
ST
AT
US
B
C
D
PWR
A
PWR
PWR
A
B
C
PWR
D
PWR
D
C
B
A
103
D. FAN
103
CIRC. FAN
103-EXH.
FAN ENABLE
AUTO ON
OFF
AUTO
OFF
ON
AUTO
OFF
ON
AUTO
OFF
ON
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
TITAN P1A
ST
AT
US
PWM
SINK
SRCE
+24V
0-5V
0-10V
FAULT
MAN
AUTO
0-10V
0-5V
PWM
SINK
+24V
SRCE
0-2
0m
A
103
EXHAUST FAN
SPEED
AUTO
UP
DOWN
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
LEGEND
Zx = ZONE x
GL = GLOBAL
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
**WARNING**
REFER TO EQUIPMENT SUPPLIER'S INSTRUCTIONS FOR CONNECTION DETAILS.
USE ONLY COPPER CONDUCTORS
FIELD WIRING MUST BE RATED FOR 75°C (167°F)
CALL ARGUS CONTROLS AT 1-888-667-2091 FOR ASSISTANCE.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TC2-IO[LAB-D]
TITAN IO MODULE
I/O
NET
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
OP
2O
P3
OP
4
+
-
-
+
OP
1
I/O
N
ET
F
US
E 1
I/O
N
ET
F
US
E 2
1.0A 1.0A
24
V
DC
F
US
E
0.5A
S/N : #######
SEC : #########
SECURITY CODE
OP1
OP4
OP3
OP2
STATUS
PWR FAULT
PWR STATUS
IN7
IN6
IN5
IN4
IN3
IN2
IN1
CHA+
FREQUENCY INPUT
ANALOG INPUT
CHB+
A/B -
AN
AL
OG
C
OM
MO
N
24
V
DC
C
OM
MO
N
+24 VDC POWER
OUTPUT
CO
MM
ON
+2
4 V
DC
O
UT
PU
T
PWR STATUS
ACTIVITY
IO NET
24 VDC
IO NET
IO MODULE
POWER
DISCONNECT
JUMPER
TITANIO MODULE
+
-
-
+
I/O NET
1.0 1.0
I/O
N
ET
F
US
E
I/O
N
ET
F
US
E
0.5
24
V
DC
F
US
E
TC2-IO[LAB-D]
AU
TO
S
TA
TU
S
PWR
PWR
PWR
PWR
TITAN P1T
103
NORTH RIDGE
VENT
CLOSE
OPEN
AUTO
OPEN
OFF
CLOSE
C
O
C
O
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
AU
TO
S
TA
TU
S
PWR
PWR
PWR
PWR
TITAN P1T
103
SOUTH RIDGE
VENT
CLOSE
OPEN
AUTO
OPEN
OFF
CLOSE
C
O
C
O
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
AU
TO
S
TA
TU
S
PWR
PWR
PWR
PWR
TITAN P1T
103
SHADE
CURTAIN
CLOSE
OPEN
AUTO
OPEN
OFF
CLOSE
C
O
C
O
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
TITAN D2
AU
TO
S
TA
TU
S
PWR
A1
A2
PWR
PWR
B2
B1
PWR
PWR
B1
B2
PWR
PWR
A2
A1
PWR
103
UNIT HEATER
(CALL FOR FAN)
103
UNIT HEATER
(CALL FOR HEAT)
A
AUTO
OFF
ON
B
AUTO
OFF
ON
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
IPB
OMNI
TN21
IPB
SEE SENSOR DRAWING
SIGNAL
COM
SEN-OSM-3.0/RHT
103-TEMP & RH
103-BACKUP TEMP.
2 WIRE SENSOR
SIGNAL
OMNI PWR
IPB103-EXH. FAN FAULT
CUSTOM PART
SEE SENSOR DRAWING
SIGNAL
COM
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
LEGEND
Zx = ZONE x
GL = GLOBAL
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
**WARNING**
REFER TO EQUIPMENT SUPPLIER'S INSTRUCTIONS FOR CONNECTION DETAILS.
USE ONLY COPPER CONDUCTORS
FIELD WIRING MUST BE RATED FOR 75°C (167°F)
CALL ARGUS CONTROLS AT 1-888-667-2091 FOR ASSISTANCE.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TC2-IO[LAB-E]
TITAN IO MODULE
NETWORK
TERMINATOR
I/O
NET
SEE IO NETWORK LAYOUT DIAGRAM
FOR FURTHER DETAILS
OP
2O
P3
OP
4
+
-
-
+
OP
1
I/O
N
ET
F
US
E 1
I/O
N
ET
F
US
E 2
1.0A 1.0A
24
V
DC
F
US
E
0.5A
S/N : #######
SEC : #########
SECURITY CODE
OP1
OP4
OP3
OP2
STATUS
PWR FAULT
PWR STATUS
IN7
IN6
IN5
IN4
IN3
IN2
IN1
CHA+
FREQUENCY INPUT
ANALOG INPUT
CHB+
A/B -
AN
AL
OG
C
OM
MO
N
24
V
DC
C
OM
MO
N
+24 VDC POWER
OUTPUT
CO
MM
ON
+2
4 V
DC
O
UT
PU
T
PWR STATUS
ACTIVITY
IO NET
24 VDC
IO NET
IO MODULE
POWER
DISCONNECT
JUMPER
TITANIO MODULE
+
-
-
+
I/O NET
1.0 1.0
I/O
N
ET
F
US
E
I/O
N
ET
F
US
E
0.5
24
V
DC
F
US
E
TC2-IO[LAB-E]
AU
TO
S
TA
TU
S
PWR
NO
NC
PWR
PWR
NC
NO
PWR
PWR
NO
NC
PWR
PWR
NC
NO
PWR
TITAN D2C
100/101
HEAT VALVE
103
HEAT VALVE
A
B
OFF
ON
OFF
AUTO
OFF
ON
OFF
AUTO
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
TITAN D4
ST
AT
US
B
C
D
PWR
A
PWR
PWR
A
B
C
PWR
D
PWR
D
C
B
A
100/101
H. CIRC. PUMP
103
H. CIRC. PUMP
AUTO ON
OFF
AUTO
OFF
ON
AUTO
OFF
ON
AUTO
OFF
ON
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
TITAN D2
AU
TO
S
TA
TU
S
PWR
A1
A2
PWR
PWR
B2
B1
PWR
PWR
B1
B2
PWR
PWR
A2
A1
PWR
GL-BOILER
ENABLE
A
AUTO
OFF
ON
B
AUTO
OFF
ON
CONNECT TO EQUIPMENT INTERFACE
SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND
WIRING DIAGRAM FOR WIRING INFORMATION
REFER TO DATASHEET FOR CONNECTION DETAILS
CLASS II POWER ONLY (3.2 AMPS MAX)
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
LEGEND
Zx = ZONE x
GL = GLOBAL
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
**WARNING**
REFER TO EQUIPMENT SUPPLIER'S INSTRUCTIONS FOR CONNECTION DETAILS.
USE ONLY COPPER CONDUCTORS
FIELD WIRING MUST BE RATED FOR 75°C (167°F)
CALL ARGUS CONTROLS AT 1-888-667-2091 FOR ASSISTANCE.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
RCP-LAB-01 : LAB 100-103
PANEL WIRING
TC2-IOPS[1]
POWER SUPPLY
TO TC2-IO[LAB-A] - OP1
TO TC2-IO[LAB-C] - OP1
TO TC2-IO[LAB-D] - OP1
TO TC2-IO[LAB-E] - OP1
1
2
3
4
SURGE ARRESTOR
5
6
7
8
9
10
11
12
13
14
15
16
SURGE ARRESTOR
RM-LAB-TX1
2TX75
TC2-IOPS[1]
POWER
TX1A: 75 VA
TC2-IO[LAB-A] OP:1-3
CONTROL POWER
TX1B: 75 VA
120 VAC
120 VAC
24 VAC
24 VAC
LINE 1
N
2 AMP FUSES
1
2
3
4
SURGE ARRESTOR
5
6
7
8
9
10
11
12
13
14
15
16
SURGE ARRESTOR
RM-LAB-TX3
2TX75
TC2-IO[LAB-E] OP:1-2
CONTROL POWER
TX3A: 75 VA
TX3B: 75 VA
120 VAC
120 VAC
24 VAC
24 VAC
LINE 1
N
2 AMP FUSES
1
2
3
4
SURGE ARRESTOR
5
6
7
8
9
10
11
12
13
14
15
16
SURGE ARRESTOR
RM-LAB-TX2
2TX75
TC2-IO[LAB-C] OP:1-2
CONTROL POWER
TX2A: 75VA
TC2-IO[LAB-D] OP:1-3
CONTROL POWER
TX2B: 75VA
120 VAC
120 VAC
24 VAC
24 VAC
LINE 1
N
2 AMP FUSES
PAGE 1
CLASS 2
FIELD WIRING
CLASS 1
FIELD WIRING
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
TO TC2-IO[LAB-B] - OP3
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
RCP-LAB-01 : LAB 100-103
PANEL WIRING
PAGE 2
CLASS 2
FIELD WIRING
CLASS 1
FIELD WIRING
P1T
IO[LAB-A] - OP1
24 VAC POWER FROM
RM-LAB-TX1 TB: 7, 9
C
O
P1T
IO[LAB-A] - OP2
C
O
P1T
IO[LAB-A] - OP3
C
O
D2
B
A
IO[LAB-A] - OP4
K1K2
10
11
12
O/L
K1
K2
1
2
3
7
8
9
4
5
6
2CGR/OL-1PH
RM-LAB-01
100/102
NORTH RIDGE
VENT
TESYS-LR2 OL: 1.8-2.6 A
CAUTION TRAVEL
LIMITS BYPASSED
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
SINGLE PHASE
REVERSING MOTOR
FLA = 2.5 AMPS
NEUTRAL
CLOSE
OPEN
M
K1K2
10
11
12
O/L
K1
K2
1
2
3
7
8
9
4
5
6
2CGR/OL-1PH
RM-LAB-02
100/102
SOUTH RIDGE
VENT
TESYS-LR2 OL: 1.8-2.6 A
CAUTION TRAVEL
LIMITS BYPASSED
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
SINGLE PHASE
REVERSING MOTOR
FLA = 2.5 AMPS
NEUTRAL
CLOSE
OPEN
M
K1K2
10
11
12
O/L
K1
K2
1
2
3
7
8
9
4
5
6
2CGR/OL-1PH
RM-LAB-03
100/102
SHADE CURTAIN
TESYS-LR2 OL: 1.8-2.6 A
CAUTION TRAVEL
LIMITS BYPASSED
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
SINGLE PHASE
REVERSING MOTOR
FLA = 2.5 AMPS
NEUTRAL
CLOSE
OPEN
M
100/102-U. HEATER - FAN
24 VAC (3.2 AMPS) MAX
DRY CONTACT
ON/OFF
COMMON
100/102-U. HEATER - HEAT
24 VAC (3.2 AMPS) MAX
DRY CONTACT
ON/OFF
COMMON
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
RCP-LAB-01 : LAB 100-103
PANEL WIRING
PAGE 3
CLASS 2
FIELD WIRING
CLASS 1
FIELD WIRING
D2
B
A
IO[LAB-B] - OP1
D4
A
B
C
D
IO[LAB-B] - OP3
24 VAC POWER FROM
RM-LAB-TX1 TB: 8, 10
100/102-U. HEATER - FAN
24 VAC (3.2 AMPS) MAX
DRY CONTACT
ON/OFF
COMMON
P1A
0-10V
0-5V
PWM
SINK
+24V
SOURCE
IO[LAB-B] - OP2
100/102-EXH. FAN SPEED
0-10V SIGNAL
SOURCED FROM P1A
SIGNAL
COMMON
K2
K1
16
11
12
13
14
15
10
17
19
18
20
K2
COIL
A1 A2
1
2
K1
COIL
A1 A2
3
4
5
6
7
8
2DP-4
9
RM-LAB-04
100/102
DESTRATIFICATION
FAN
100/102
CIRCULATING
FAN
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
T.P. SINGLE PHASE
MOTOR
FLA = 2 x 0.5 AMPS = 1 AMP
LOAD 1
NEUTRAL
M
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
T.P. SINGLE PHASE
MOTOR
FLA = 3 x 1.3 AMPS = 3.9 AMPS
LOAD 1
NEUTRAL
M
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
RCP-LAB-01 : LAB 100-103
PANEL WIRING
PAGE 4
CLASS 2
FIELD WIRING
CLASS 1
FIELD WIRING
D4
A
B
C
D
IO[LAB-C] - OP1
24 VAC POWER FROM
RM-LAB-TX2 TB: 1, 3
D4
A
B
C
D
IO[LAB-C] - OP2
P1A
0-10V
0-5V
PWM
SINK
+24V
SOURCE
IO[LAB-C] - OP3
K2
K1
16
11
12
13
14
15
10
17
19
18
20
K2
COIL
A1 A2
1
2
K1
COIL
A1 A2
3
4
5
6
7
8
2DP-4
9
RM-LAB-05
100/102
LIGHTS ZONE 1
100/102
LIGHTS ZONE 2
K2
K1
16
11
12
13
14
15
10
17
19
18
20
K2
COIL
A1 A2
1
2
K1
COIL
A1 A2
3
4
5
6
7
8
2DP-4
9
RM-LAB-06
103
LIGHTS
103-DESTRATIFICATION
FAN
120 VAC 60HZ 1Ø - 20 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
100/102-LIGHTS ZONE 1
FLA = 16 AMPS MAX
120 VAC 60HZ 1Ø - 20 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
100/102-LIGHTS ZONE 2
FLA = 16 AMPS MAX
120 VAC 60HZ 1Ø - 20 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
103-LIGHTS
FLA = 16 AMPS MAX
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
T.P. SINGLE PHASE
MOTOR
FLA = 2 x 0.5 AMPS = 1 AMP
LOAD 1
NEUTRAL
M
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
T.P. SINGLE PHASE
MOTOR
FLA = 3 x 1.3 AMPS = 3.9 AMPS
LOAD 1
NEUTRAL
M
K2
K1
16
11
12
13
14
15
10
17
19
18
20
K2
COIL
A1 A2
1
2
K1
COIL
A1 A2
3
4
5
6
7
8
2DP-4
9
RM-LAB-07
103
CIRC. FAN
K-LAB-01 : (PILOT DUTY)
103-EXHAUST FAN ENABLE
24 VAC CLASS II 5A MAX, BY INSTALLER
RELAY SUPPLIED
BY CUSTOMER
12
11
14
A1
A2
103-EXH. FAN SPEED
0-10V SIGNAL
SOURCED FROM P1A
SIGNAL
COMMON
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
RCP-LAB-01 : LAB 100-103
PANEL WIRING
PAGE 5
CLASS 2
FIELD WIRING
CLASS 1
FIELD WIRING
P1T
IO[LAB-D] - OP1
24 VAC POWER FROM
RM-LAB-TX2 TB: 7, 9
C
O
P1T
IO[LAB-D] - OP2
C
O
P1T
IO[LAB-D] - OP3
C
O
D2
B
A
IO[LAB-D] - OP4
K1K2
10
11
12
O/L
K1
K2
1
2
3
7
8
9
4
5
6
2CGR/OL-1PH
RM-LAB-08
103
NORTH RIDGE
VENT
TESYS-LR2 OL: 1.8-2.6 A
CAUTION TRAVEL
LIMITS BYPASSED
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
SINGLE PHASE
REVERSING MOTOR
FLA = 2.5 AMPS
NEUTRAL
CLOSE
OPEN
M
K1K2
10
11
12
O/L
K1
K2
1
2
3
7
8
9
4
5
6
2CGR/OL-1PH
RM-LAB-09
103
SOUTH RIDGE
VENT
TESYS-LR2 OL: 1.8-2.6 A
CAUTION TRAVEL
LIMITS BYPASSED
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
SINGLE PHASE
REVERSING MOTOR
FLA = 2.5 AMPS
NEUTRAL
CLOSE
OPEN
M
K1K2
10
11
12
O/L
K1
K2
1
2
3
7
8
9
4
5
6
2CGR/OL-1PH
RM-LAB-10
103
SHADE CURTAIN
TESYS-LR2 OL: 1.8-2.6 A
CAUTION TRAVEL
LIMITS BYPASSED
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
SINGLE PHASE
REVERSING MOTOR
FLA = 2.5 AMPS
NEUTRAL
CLOSE
OPEN
M
103-U. HEATER - FAN
24 VAC (3.2 AMPS) MAX
DRY CONTACT
ON/OFF
COMMON
103-U. HEATER - HEAT
24 VAC (3.2 AMPS) MAX
DRY CONTACT
ON/OFF
COMMON
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL
PROPERTY OF ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS
INTENDED APPLICATION AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION
OF THIS DRAWING SHALL BE REPRODUCED OR USED WITHOUT THE EXPRESS
WRITTEN PERMISSION OF ARGUS CONTROL SYSTEMS LTD.
ALL WIRING MUST FOLLOW
LOCAL CODES AND REGULATIONS
UOM - TC2 - RCP-LAB-01.DWG
UNIVERSITY OF MAINE
PRESQUE ISLE
NG MC
03/17/17 1
RCP-LAB-01 : LAB 100-103
PANEL WIRING
PAGE 6
CLASS 2
FIELD WIRING
CLASS 1
FIELD WIRING
D2C
B
A
IO[LAB-E] - OP1
24 VAC POWER FROM
RM-LAB-TX3 TB: 1, 3
D4
A
B
C
D
IO[LAB-E] - OP2
D2
B
A
IO[LAB-E] - OP3
100/101-HEAT VALVE
24 VAC 6VA MAX (0.25A)
POWER OPEN / POWER CLOSE
103-HEAT VALVE
24 VAC 6VA MAX (0.25A)
POWER OPEN / POWER CLOSE
N.O
COMMON
N.C
N.O
COMMON
N.C
GL-BOILER ENABLE
24 VAC (3.2 AMPS) MAX
DRY CONTACT
ON/OFF
COMMON
K2
K1
16
11
12
13
14
15
10
17
19
18
20
K2
COIL
A1 A2
1
2
K1
COIL
A1 A2
3
4
5
6
7
8
2DP-4
9
RM-LAB-11
100/101
HEAT CIRC. PUMP
103
HEAT CIRC. PUMP
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
T.P. SINGLE PHASE
MOTOR
FLA = 2 AMPS
LOAD 1
NEUTRAL
M
120 VAC 60HZ 1Ø - 15 AMPS
FUSE OR BREAKER
PROVIDED BY INSTALLER
T.P. SINGLE PHASE
MOTOR
FLA = 2 AMPS
LOAD 1
NEUTRAL
M
R
CONTROLS
Project Mngr: Drawn by:
Current Revision:
Dwg:
Creation Date:
BYDESCRIPTIONREV.DATE
#101 - 18445 53RD AVENUE
SURREY, BC
V3S 7A4
604-538-3531
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
Date: 2/24/2017
phone: 303-450-8536
fax: (303) 457-2801
University of Maine, Preqsue Ilse
Nexus Job #: P32463
Submittal Number: NEX-SUB-04
Submittal Description: Exhaust Fan VFD
Manufacturer: ABB
Quantity: 2 ea
ACS320-01U-07 A5-2
230v
3PH
2 HP
37.5 amps
Product Data Information:
UE XN SGREENHOUSE CORPORATION
10983 LEROY DRIVE
NORTHGLENN, CO 80233
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � ! � � � � � � � � � � � � � � � � " � � � � � � � � � � # $ � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � % � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � ! � � � � & � � � � � � � � � � � � � � � � � � � � � � � � � � � � � ' � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � � � ( � ) ( � ) � ' � * + � , ' � ' - , . - ) � ' � ( � � / , / � � � � � � ' 0 . � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �
1 2 3 4 5 4 6 3 7 7 8 9 : ; < = > ? @A B C D B C E F G H G E I J K E C F G C L· M N N O P Q R S T U V W X Y P S Z [ [ S · \ [ Y ] [ Z ^ _ ` a O b b c d c N M M · e T Q Y [ f g c O c h i j M d b b k M · l X m f g c O c h i j M d O c b nA o p q B C F r
· N M c \ s Q Z S T t P u V v T w X x b a i · l Q Z S _ Q y y V Y z ^ _ ` a O n b N d N a n c · e T Q Y [ f g k i O h N k c d i b k c · l X m f g k i O h N k c d i b k iA o p { B K F r· N b j O | R } ~ V Y v T X � \ Z V ] [ � M c O · _ Q y Q Z X � Q P W Z V Y v z ^ _ ` a O k O i d c i i a · e T Q Y [ f g i M k h n b a d M M M j · l X m f g i M k h n b a d j a k bA o p � G L F· n i n P Q R S T � [ z S v X S [ \ Z V ] [ t Y V S _ · � Z X Y � � R Y } S V Q Y ^ _ ` a M n O n d j k n a · e T Q Y [ f g k i O h b N c d N c i i · l X m f g k i O h b N c d O O j a� � � � � � � � �� � � � � � � � � � � � �� � � � � � � � � � � � � � � � � �� � � � � � � ¡ � ¢ £ � � � � £ � � � � � � � ¤ � ¥ ¤ � ¦ ¢§ � � ¨ � � � � � � � � © � ª « � � � ª � � � ¬ � ª � �® � � � � ª � � � ¯ � � � � ¥ °� � � ± ª � � � � �° � ² ª � � � � �� ³ � ¯ § � � ´ µ ¶ § ® ° � ¶ ° £ · ¯ ¯ ³ ³ ° ¸ · ¹ ° ³ ¯ ® ® ¯ º µ � » ° ¼ © µ § ° � · ³ ¯ ¸ ´ ¯ © ¸� ¯ � ¶ µ £ ° ¸ � · µ ¯ � �½ ¾ ¿ À Á Â Ã Ä Å Æ Ç È É É Ê Ë Ì Í ¾ Æ Å Î Ï Ë Ð Æ É É Æ Ï Ñ Ò Ó È Ì Ô ¾ Õ È Í Ö ¿ × Ï Æ Æ Í Ó Æ Ø ÙÚ Û Ü Ý Þ ß à á â ã Ú ã ä Ú å æ ä Ú ç æ ä è é ê Þ ë ì í Þ è ì ì è î í Þ Ý é ï ð ñ ò ì ì è ß éÚ ó è ß ô è õ ò ö Þ Ý é ì Þ Þ ß ÷ è õ ê è õ Þ ßÚ ø ò Þ ÷ Ü ë ñ Þ Ý ù ú è ß ô è õ ò ö Þ Ý é ì Þ Þ ß Ý ë ò ô Þ ÷ ë è ñ Þ è é é Þ ñ ð ß ûÚ á è é ì è ß ï ñ ò õ ï ñ è ò ë ÷ Ü ò ß ð ß è Ý Þ ê ë Ü ê Þ ß ß Þ ëÚ ç è ß ß ð Þ è ë ò õ ú ñ Ü ì Ü ë éÚ á Ü ë ë Ü é ò Ü õ ë Þ é ò é ì è õ ì ÷ è é ì Þ õ Þ ë éÚ ü è ì Þ Ý ÷ Ü ë ý ä ù ä ä ä þ ä ÿ æ � â à � é Þ ß Þ î ì Þ Ý è ì è ß ì ò ì ï Ý ÞÚ æ í ê ù æ ã ä � ã � å äÚ ø ò é î Ü õ õ Þ î ì à � ò ì î í ù � â Û � ã ü Þ õ î ß Ü é ï ë ÞÚ ó ë è ô ò ì û ø è ñ ê Þ ëÚ à í Ü ë ì � è ß ß � Ü ï é ò õ ú � � à � � ó ï è ë ÝÚ à Þ ß Þ î ì Þ Ý Ü ê ì ò Ü õ é è õ Ý è î î Þ é é Ü ë ò Þ é è é õ Ü ì Þ Ý Ü õ è ì ì è î í Þ Ý é ï ð ñ ò ì ì è ß Ë ¾ È É Æ ¾ Î Ï Ä Ø Æ � � � � � � � � � Æ È � � � � � � � � � � � Ë Ï À Á Â� Ì Ï Ï Æ Í ¾ � Æ È Å Ä � Æ Ä Ô � � � Ç Æ Æ Ù Ô Ð Ï Ë Å Ì Ø ¾ Ä Ë Í Ð É Ì Ô � � � Å È ¿ Ô ¾ Ï È Í Ô Ä ¾ ¾ Ä � Æ �� � � � È Ï Ä È Ö É Æ Õ Ï Æ � Ì Æ Í Ø ¿ Ï Ä ! Æ Ô È Ô � Ë É É Ë Ç Ô �Ú Û Ü Ý Þ ß � � à � Á � � � " � � # � � � ÁÚ æ ÿ ä í ê ù ã $ ÿ � è ñ ê éÚ ü è ì Þ Ý ÷ Ü ë ý Ú ê í è é Þ ò õ ù æ ã ä � ã Ü ï ìÚ � % � á � Ý ô è õ î Þ Ý � è õ Þ ß & ' ( ) ä ä *Ú � â Û � ý â õ î ß Ü é ï ë Þ + ò ì ÷ Ü ë Ý ë ò ô ÞÚ â ß Þ î ì ë Ü õ ò î Û Ü ì Ü ë � ô Þ ë ß Ü è Ý éÚ ý æ Û Ü õ ì í � è ë ì é � , ë è ô Þ ß � - è ð Ü ë � è ë ë è õ ì û & � Ü ë ñ è ß ç ï é ò õ Þ é é � Ü ï ë é * Ë ¾ È É Æ ¾ Î Ï Ä Ø Æ . � � � � � � � Æ È � � � � Á � � � � Ë Ï À Á Â/ Í Ô ¾ Ë Ø Ù È ¾ ¾ Ó Æ � È Ø ¾ Ë Ï ¿ Ð É Ì Ô � � � Å È ¿ Ô ¾ Ï È Í Ô Ä ¾ �� É É Ð Ï Ä Ø Ä Í 0 Ä Ô Õ 1 � Õ È Ø ¾ Ë Ï ¿ � Õ Ì É É � Ï Æ Ä 0 Ó ¾ È É É Ë Ç Æ Å ¾ Ë 2 Ë Ö Ô Ä ¾ Æ �3 4 5 6 7 8 9 : ; 8 < 5 6 = > 9 ? 9 5 = @ 9 : ; 8 AB C D E F G D H F I J K L I M N O P F P QB R J D G G F S T N U V L I G K D N N D K L J I V J H W D H H D I K U N D T J H L I M N O P F P QB X H P F H G H F M F L Y F P D Z K F H [ \ ] ^ _ ^ ` C a W L N N T F b H J M F G G F P J I K c F I F E K T O G L I F G G P D U Qd O G K J S F H e Q X Q f g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
phone: 303-450-8536 Date: 2/24/2017
fax: (303) 457-2801
University of Maine, Preqsue Ilse
Nexus Job #: P32463
Submittal Number: NEX-SUB-07
Submittal Description: Unit Heater
Manufacturer: Lennox
Quantity: 2 ea
LF24-75a , 1 in 100/102, 1 in 103
Product Data Information:
UE XN SGREENHOUSE CORPORATION
10983 LEROY DRIVE
NORTHGLENN, CO 80233
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
Project No. Prepared By
Date
Columns with Baseplates9 Roof Purlins
STRUCTURAL CALCULATIONS
(1) 30'-0'' x 80'-0'' 'E' Series Greenhouse
13'- 0'' Column Height 8'- 0'' Bay Spacing
P32463S. Elliott4/5/17
University of Maine-Presque Isle
Presque Isle, ME 04769181 Main Street
IATN OGREENHOUSE CORPORATION
10983 LEROY DRIVENORTHGLENN, CO 80233
303-457-9199
A LN
1/11
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
DESIGN LOADS
DESIGN CODE - 2009 International Building Code/ASCE 7-05 2000 Aluminum Design Manual
OCCUPANCY CATEGORY - II
DEAD LOAD - 1.0 psf (Purlin Design)
2.0 psf (Truss Design)
3.0 psf (Column / Reaction Design)
ROOF LIVE LOAD - 20 psf
SNOW LOAD - Ground Snow, Pg 100 psf
Exposure Factor, Ce 1
Importance Factor, Is 1
Thermal Factor, Ct 0.85
Roof Snow Load, Pf = 0.7CeICtPg = 60 psf
Min. Roof Snow Load, Pfmin 60 psf
WIND LOAD - Design Wind Speed, V 90 mphImportance Factor, I 1Wind Exposure CInterior Pressure Coefficient, GCpi ±0.18
SEISMIC LOAD - Importance Factor, I 1Spectral Response Acceleration
SS 0.285
S1 0.089
Site Class D
LOAD COMBINATIONS - (per ASCE 2.4.1)D+LD+WD+0.7ED+0.75L+0.75WD+0.75L+0.75(0.7E)0.6D+W0.6D+0.7E
2/11
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
WIND LOADS(Per ASCE 7-05 )
DESIGN CRITERIA -
V = 90 mph, Exposure 'C' GCpf = (Fig. 6-10) (MWFRS)KZ = 0.90 I = 1.00 GCp = (Fig. 6-11) (COMP / CLAD)
KZT = 1.0 Kd = 0.85 GCpi = ± 0.18
q = 0.00256 * KZ * KZT * Kd * V2 * I = 0.00256(0.9)(1)(0.85)(90)²(1) = 15.9 psf
MWFRS - P = q [(GCpf) - (GCpi)]
Case A: Lateral Wind
Case 1: GCpi = -0.18
P = 15.9 [(0.55) - (-0.18)] = 11.6 psf (WW)P = 15.9 [(-0.11) - (-0.18)] = 1.1 psf (WR)P = 15.9 [(-0.45) - (-0.18)] = -4.3 psf (LR)P = 15.9 [(-0.39) - (-0.18)] = -3.3 psf (LW)P = 15.9 [(-0.45) - (-0.18)] = -4.3 psf (SW)
Case 2: GCpi = 0.18
P = 15.9 [(0.55) - (0.18)] = 5.9 psf (WW)P = 15.9 [(-0.11) - (0.18)] = -4.6 psf (WR)P = 15.9 [(-0.45) - (0.18)] = -10.0 psf (LR)P = 15.9 [(-0.39) - (0.18)] = -9.1 psf (LW)P = 15.9 [(-0.45) - (0.18)] = -10.0 psf (SW)
Case B: Longitudinal Wind
Case 1: GCpi = -0.18
P = 15.9 [(0.4) - (-0.18)] = 9.2 psf (WW)P = 15.9 [(-0.69) - (-0.18)] = -8.1 psf (WR)P = 15.9 [(-0.37) - (-0.18)] = -3.0 psf (LR)P = 15.9 [(-0.29) - (-0.18)] = -1.7 psf (LW)P = 15.9 [(-0.45) - (-0.18)] = -4.3 psf (SW)
Case 2: GCpi = 0.18
P = 15.9 [(0.4) - (0.18)] = 3.5 psf (WW)P = 15.9 [(-0.69) - (0.18)] = -13.8 psf (WR)P = 15.9 [(-0.37) - (0.18)] = -8.7 psf (LR)P = 15.9 [(-0.29) - (0.18)] = -7.5 psf (LW)P = 15.9 [(-0.45) - (0.18)] = -10.0 psf (SW)
3/11
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
SEISMIC LOADS
DESIGN CRITERIA -
Site Class = DImportance Factor, I = 1.00
SS = 0.285 Fa = 1.572 SMS = Fa x Ss = 0.448
S1 = 0.089 Fv = 2.4 SM1 = Fv x S1 = 0.214
SDS = 2/3 SMS = 0.299
SD1 = 2/3 SM1 = 0.142
Design Category = C
SEISMIC BASE SHEAR - Based on ASCE7-10 12.8 Equivalent Lateral Force Procedure
V = CS W (Equation 12.8-1)
Cs = SDS / (R/I) (Equation 12.8-2)
Lateral Shear
RLAT = 3 [Table 12.2-1 H. Systems Not Specifically Detailed for Seismic Resistance]
W = 30ft(width) * 8ft(bay) * 3psf W = 0.72 Kips per bayCs = 0.10
V = 0.072 Kips (Seismic Base Shear per Bay)
Longitudinal Shear
RLONG = 3 [Table 12.2-1 H. Systems Not Specifically Detailed for Seismic Resistance]
W = 30ft(width) * 80ft(length) * 3psf / 2 Column RowsW = 3.6 Kips per column line
Cs = 0.10
V = 0.359 Kips (Seismic Base Shear per Column line)
4/11
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
PURLIN CHECK
Purlins
[248] 5" I-Beam, 6063-T6 Aluminum
A = 1.325 in2Sx = 2.364 in3 ry = 0.69 in
L = 48 in
L / r = 69.6Fb = 16.7 - 0.073(L / r) = 11.6 ksi
Clear Span of Purlin = 7.83 ft
Purlin Spacing = 3 ft
Maximum Load = Roof Live Load + Purlin Dead Load
60psf + 1psf = 61.0 psf
Maximum Wind Pressure From a 90 mph Wind Load
0.6D+W(Case B.2) = 1.2psf + -13.8psf = -12.6 psf
Mr = w L² / 8 = (61psf * 3ft)(7.83ft)² / 8 = 1402lb-ft = 16.8 k-in
fb = Mn / S = 16.8k-in / 2.364in³ = 7.1 ksi
fb / Fb = 0.61 < 1.0 OK
5/11
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TRUSS MEMBER LABELS
TRUSS MEMBER CHECK
(Data and Formulas Used for Calculation on the Following Page)
[331] 7" I-Beam (#4), 6061-T6 Aluminum Extrusion
A = 7.554 in2S = 19.56 in3
r = 1.544 in[326] Extrusion, 6063-T6 Aluminum Extrusion
A = 1.644 in2S = 1.76 in3
r = 0.846 in[328] Extrusion-double, 6063-T6 Aluminum Extrusion
A = 0 in2S = 0 in3
r = 0 in
COMPRESSION CHECK:
Allowable Load in Compression, Fb
If kL/r < 78 Fb = 14.2 - 0.074(kL/r)
If kL/r 78 Fb = 51,000 / (kL/r)2
TENSION CHECK:Allowable Load in Tension, Ft = 15.0ksi
12 3
45
7
6 8
11
10
9 12
15
14
13
16
21
19
18
27
17 20
2429
33
23
22
32
25
46
28 30
3734
26
36
31
41
38
35
40
44
42
39
45
47
43
6/11
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
TRUSS MEMBER CHECK
Span Aluminum ExtrusionL (in)
kL / rAllow. Comp.
ksiComp.
fa ksi
Allow. Tens.
ksi
Tens. ft
ksi
Result
Top Chord5 [326] Extrusion, 6063-T6 Aluminum 40 47.6 10.7 6.9 15.0 0.9 OK
9 [326] Extrusion, 6063-T6 Aluminum 40 47.6 10.7 7.3 15.0 1.2 OK13 [326] Extrusion, 6063-T6 Aluminum 40 47.6 10.7 6.9 15.0 1.3 OK17 [326] Extrusion, 6063-T6 Aluminum 40 47.6 10.7 6.4 15.0 1.4 OK22 [326] Extrusion, 6063-T6 Aluminum 40 47.6 10.7 6.0 15.0 1.4 OK26 [326] Extrusion, 6063-T6 Aluminum 40 47.6 10.7 6.0 15.0 1.4 OK31 [326] Extrusion, 6063-T6 Aluminum 40 47.6 10.7 6.4 15.0 1.4 OK35 [326] Extrusion, 6063-T6 Aluminum 40 47.6 10.7 6.9 15.0 1.3 OK39 [326] Extrusion, 6063-T6 Aluminum 40 47.6 10.7 7.3 15.0 2.1 OK43 [326] Extrusion, 6063-T6 Aluminum 40 47.6 10.7 6.9 15.0 2.8 OK
Bottom Chord (3 Braces)4 [327] Extrusion, 6063-T6 Aluminum 75 110.1 4.2 1.5 15.0 10.7 OK7 [327] Extrusion, 6063-T6 Aluminum 75 110.1 4.2 0.7 15.0 8.6 OK
11 [327] Extrusion, 6063-T6 Aluminum 75 110.1 4.2 0.9 15.0 8.6 OK15 [327] Extrusion, 6063-T6 Aluminum 75 110.1 4.2 0.8 15.0 7.7 OK21 [327] Extrusion, 6063-T6 Aluminum 75 110.1 4.2 0.3 15.0 5.5 OK27 [327] Extrusion, 6063-T6 Aluminum 75 110.1 4.2 0.3 15.0 5.5 OK33 [327] Extrusion, 6063-T6 Aluminum 75 110.1 4.2 1.0 15.0 7.7 OK37 [327] Extrusion, 6063-T6 Aluminum 75 110.1 4.2 1.6 15.0 8.6 OK41 [327] Extrusion, 6063-T6 Aluminum 75 110.1 4.2 3.0 15.0 8.6 OK45 [327] Extrusion, 6063-T6 Aluminum 75 110.1 4.2 1.5 15.0 10.7 OK
Web Members6 [328] Extrusion, 6063-T6 Aluminum 13 30.1 12.0 3.0 15.0 3.4 OK8 [328] Extrusion, 6063-T6 Aluminum 14 32.8 11.8 2.3 15.0 0.0 OK
10 [328] Extrusion, 6063-T6 Aluminum 39 90.5 6.2 0.0 15.0 2.5 OK12 [328] Extrusion, 6063-T6 Aluminum 34 79.5 8.1 2.4 15.0 0.4 OK14 [328] Extrusion, 6063-T6 Aluminum 51 118.1 3.7 0.4 15.0 2.4 OK16 [327] Extrusion, 6063-T6 Aluminum 54 79.8 8.0 2.5 15.0 0.6 OK18 [328] Extrusion, 6063-T6 Aluminum 44 102.8 4.8 0.5 15.0 1.7 OK19 [327] Extrusion, 6063-T6 Aluminum 44 65.1 9.4 0.6 15.0 2.5 OK20 [328] Extrusion, 6063-T6 Aluminum 24 56.1 10.0 2.1 15.0 0.5 OK23 [327] Extrusion, 6063-T6 Aluminum 44 65.1 9.4 0.8 15.0 3.4 OK24 [328] Extrusion, 6063-T6 Aluminum 84 194.9 1.3 0.0 15.0 0.1 OK25 [327] Extrusion, 6063-T6 Aluminum 44 65.1 9.4 1.0 15.0 3.4 OK28 [328] Extrusion, 6063-T6 Aluminum 24 56.1 10.0 2.1 15.0 0.5 OK29 [327] Extrusion, 6063-T6 Aluminum 44 65.1 9.4 0.8 15.0 2.5 OK30 [328] Extrusion, 6063-T6 Aluminum 44 102.8 4.8 0.5 15.0 1.7 OK32 [327] Extrusion, 6063-T6 Aluminum 54 79.8 8.0 2.5 15.0 0.8 OK34 [328] Extrusion, 6063-T6 Aluminum 51 118.1 3.7 1.4 15.0 2.1 OK36 [328] Extrusion, 6063-T6 Aluminum 34 79.5 8.1 2.1 15.0 1.5 OK38 [328] Extrusion, 6063-T6 Aluminum 39 90.5 6.2 2.7 15.0 0.3 OK40 [328] Extrusion, 6063-T6 Aluminum 14 32.8 11.8 0.3 15.0 2.4 OK42 [328] Extrusion, 6063-T6 Aluminum 13 30.1 12.0 4.7 15.0 1.2 OK
Knee Braces3 [328] Extrusion, 6063-T6 Aluminum 20 46.4 10.8 5.6 15.0 6.3 OK
44 [328] Extrusion, 6063-T6 Aluminum 20 46.4 10.8 8.7 15.0 2.2 OK7/11
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
COLUMN CHECK
[329] 7" I-Beam (#1), 6061-T6 Aluminum
A = 2.224 in2S = 5.157 in3
rs = 2.849 in
rw = 0.849 in
COMPRESSION CHECK:
Unbraced Length, L = 120 in
k L / r = 120 / 2.849 = 42.1 < 66
Allowable load in Compression, Fa = 20.2 - 0.126 (kL/r) = 14.89 ksi
Maximum load in Compression, fa = P / A = 7.665 / 2.224 = 3.4 ksi OK
BENDING CHECK:
Unbraced Length, L = 48 in
L / r = 48 / 0.849 = 56.5 < 79Fb = 23.9 - 0.124(L/r) = 16.9 ksi
M = 4.719 k-ft = 56.63 k-infb = M / S = 11.0 ksi OK
8/11
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
LONGITUDINAL BRACING CHECK
WIND: Maximum Wind Pressures = 9.2 lb/ft2 Windward
-1.7 lb/ft2 Leeward
P = (131ft²) x (9.2lb/ft² + 1.7lb/ft²) = 1.43 kips (Controls)
SEISMIC: P = 0.36 kips x 0.91 = 0.33 kips
RODSTwo sets of rods = P/2T = 0.71 kips
Maximum Load in Tension = Pr = P(14'-3''/7'-8'') = 1.33 k
3/8" diameter all-thread rod, Tallow = 0.6(36ksi)(0.11in2) = 2.38 k OK
3/8" diameter all-thread rod, Tallow = 0.5(50ksi)(0.078in2) = 1.95 k OK
9/11
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
ENDWALL AND SIDEWALL ANALYSIS
Wind Load= 90 mph, Exp. ''C''
Side Wall Wind Load= 20.4 lbs / ft2
Gable Wall Wind Load= 20.4 lbs / ft2
Max. Gable Post Spacing = 6 ftWall Member Spacing = 4.0 ft
GABLE POST CHECK:
[107] 5" I-Beam, 6061-T6 Aluminum
A = 2.381 in2S = 4.122 in3
rs = 2.081 in
rw = 0.917 in
Gable Post Length = 16.5 ftBending Check:
Mr = w l2/8 = (20.4psf x 6ft) x (16.5ft)² / 8 = 4165 lb-ft = 50.0 k-infb = M / S = 50k-in / 4.122in³ = 12.1 ksi
Lu = 48 inchesLu / r = 52
Fb = 23.9 - 0.124(L / r) = 17.4 ksi OK
Compression Check (strong axis):
Pmax = 1.488 kfa = P / A = 1.488k / 2.381in² = 0.6 ksi
Lu = 198 inchesLu / r = 95
Fa = 51,000/(L / r)² = 9.6 ksi OK
Compression Check (weak axis):Pmax = 1.488 k
fa = P / A = 1.488k / 2.381in² = 0.6 ksiLu = 48 inches
Lu / r = 52Fa = 20.2 - 0.126(L / r) = 13.6 ksi OK
HORIZONTAL WALL GIRT CHECK:
[013] 2"x4" Channel, 6063-T6 Aluminum
A = 1.43 in2 S = 1.736 in3 r = 0.617 in
Bending Check: Mr = w l2/8 = (20.4psf x 4ft) x (8ft)² / 8 = 653 lb-ft = 7.8 k-infb = M / S = 7.8k-in / 1.736in³ = 4.5 ksi
Lu = 48 inches
Lu / r = 78
Fb = 16.7 - 0.073(L / r) = 11.0 ksi OK10/11
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
NEXUS CORPORATION10983 LEROY DRIVE
NORTHGLENN, CO 80233
STRUCTURAL COLUMN REACTIONSUniversity of Maine-Presque Isle Greenhouse
Column base reactions based on the following loads:Structure Dead Load (DL) = 3 psfRoof Live/Snow Load (LL) = 60 psfWind Load = 90 mph, exp. 'C'
D LUplift Shear Uplift Shear
Truss Columns 0.4 7.2 1.1 1.0 2.8 0.8
Corner Columns 0.1 0.6 0.1 0.1 0.3 0.5
Gable Posts 0.3 1.2 0.1 0.1 0.3 0.8
All forces are expressed in kips and are based on unfactored/uncombined load cases.
Greenhouse structure has 8'-0" Column/Truss spacing, and 10' column length (on top of 3' knee wall).
W Lat. W Long.
11/11
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
1/7Page:P32463Project number:Version: 2.3.6179.27440
Date: 3/7/2017University of Maine181 MainSt.Presque Isle, ME 04769
Project:
Company name:
Subject/Topic:
Name of the project engineer:
University of Maine181 Main St.Presque Isle, ME 04769
Project name:
Company name:
PROJECT DATA:
Notes/Remarks:
Description:
UofME Anchors.pcp2PDA - Powers Design Assist®
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
2/7Page:P32463Project number:Version: 2.3.6179.27440
Date: 3/7/2017University of Maine181 MainSt.Presque Isle, ME 04769
Project:
Company name:
LOAD ACTIONS: [lb], [ft-lb]
ex = 0.00 inch; ey = 0.00 inch
Eccentric profile
0Muz
0Muy
0Mux
1142Vuy
355Vux
4237Nu
Design loads / actions
GEOMETRY:
UofME Anchors.pcp2PDA - Powers Design Assist®
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
3/7Page:P32463Project number:Version: 2.3.6179.27440
Date: 3/7/2017University of Maine181 MainSt.Presque Isle, ME 04769
Project:
Company name:
SUMMARY:
Issued: 2/1/2012
ESR-2582 (2/1/2012)Approval:
hef = 4.000 inchEffective embedment depth:
AC100+ Gold - 1/2" rod ASTM A F593, Grade304 (stainless)
Selected anchor:
NoSeismic Loads:
DryDrill hole condition:
Hammer drillingDrilling method:
Long term temperature: 75°F, Short term temperature: 104°FTemperature range:
not existentStand-off:
Tension:Condition B | Shear: Condition A
none edge reinforcementor < #4 bar
no reinforcement to limit splitting cracks availableReinforcement:
taken from Section 9.2Load combination:
Normal weight concrete,uncrackedconcrete, f c = 3500 psiConcrete:
ACI 318-08 (Appendix D) & ICC-ES AC193/AC308Design method:Basic principles of Design:
Resulting anchor forces / load distribution:
598 lb2119 lbMaximum
598 lb2119 lb#2
598 lb2119 lb#1
Shear loadTension loadAnchor No.
0 lbResulting compression force:
4237 lbResulting tension force:
0 psiMax. concrete compression stress:
0.00 ‰Max. concrete compression strain:
0.83 ≤ 1.0--Interaction
OK0.26 ≤ 1.04505 lb1156 lbShear load
0.74 ≤ 1.05754 lb4237 lbTension load
StatusCapacityDemandDesign proofCalculations:
none selectedProfile:
not calculatedCalculated plate thickness:
0.500 inchActual plate thickness:
8.00 inch x 7.00 inchLength x width:
fyk = 36000 psiMaterial:Anchor plate:
UofME Anchors.pcp2PDA - Powers Design Assist®
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
4/7Page:P32463Project number:Version: 2.3.6179.27440
Date: 3/7/2017University of Maine181 MainSt.Presque Isle, ME 04769
Project:
Company name:
Nua / (Φ * Nsa) = 2119 lb / 9224 lb = 0.23 ≤ 1.00Design proof:
= 2119 lbNua
D.5.1.2= Φ * Nsa = 0.65 * 14190 lb = 9224 lbΦ * Nsa
D.5.1= 14190 lbNsa
Steel strength:
ReferenceDESIGN PROOF TENSION LOADING:
Nua / (Φ * Ncbg) = 4237 lb / 6399 lb = 0.66 ≤ 1.00Design proof:
= 4237 lbNua
= 0.65 * (144.00 / 144.00) * 1.000 * 1.000 * 0.900 * 1.00 * 0.963 * 11359 lb = 6399 lb
D.5.2.1= Φ * (ANc / ANc0) * ψec,N,x * ψec,N,y * ψed,N * ψc,N * ψcp,N * NbΦ * Ncbg
D.5.2.7= 0.963ψcp,N
= 4.00 inchca,min
= 6.23 inchcac
D.5.2.6= 1.00ψc,N
D.5.2.5= 0.900ψed,N
D.5.2.4= 1.000ψec,N,y
D.5.2.4= 1.000ψec,N,x
= 144.00 inch²ANc
= 144.00 inch²ANc0
D.5.2.2= kc * fc' 0.5 * hef1.5 = 24.00 * 59.16 * 8.000 = 11359 lbNb
= 24.0kc
= 4.000 inchhef
Concrete strength:
UofME Anchors.pcp2PDA - Powers Design Assist®
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
5/7Page:P32463Project number:Version: 2.3.6179.27440
Date: 3/7/2017University of Maine181 MainSt.Presque Isle, ME 04769
Project:
Company name:
Nua / (Φ * Nag) = 4237 lb / 5754 lb = 0.74 ≤ 1.00Design proof:
= 4237 lbNua
= 0.65 * (129.77 / 104.47) * 0.935 * 1.028 * 1.000 * 1.000 * 0.820 * 9042 lb = 5754 lb
= Φ * (ANa / ANa0) * ψed,Na * ψg,Na * ψec,Na,x * ψec,Na,y * ψp,Na * Na0Φ * Nag
D.5.3.14= 0.820ψp,Na
= 4.00 inchca,min
D.5.3.11= 1.000ψec,Na,y
D.5.3.11= 1.000ψec,Na,x
D.5.3.10= 1.028ψg,Na
D.5.3.12= 0.935ψed,Na
= 104.47 inch²ANa0
= 129.77 inch²ANa
D.5.3.9= τK,uncr * π * d * hef = 1515 * π * 0.500 * 4.000 = 9042 lbNa0
= 4.000 inchhef
Pullout / Bond strength:
Vua / (Φ * Vsa) = 598 lb / 5109 lb = 0.12 ≤ 1.00Design proof:
= 598 lbVua
D.6.1.2= Φ * Vsa = 0.60 * 8515 lb = 5109 lbΦ * Vsa
D.6.1= 8515 lbVsa
Steel strength (without lever arm):
ReferenceDESIGN PROOF SHEAR LOADING:
UofME Anchors.pcp2PDA - Powers Design Assist®
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
6/7Page:P32463Project number:Version: 2.3.6179.27440
Date: 3/7/2017University of Maine181 MainSt.Presque Isle, ME 04769
Project:
Company name:
Vua / (Φ * Vcbg) = 1156 lb / 4505 lb = 0.26 ≤ 1.00Design proof:
= 1156 lbVua
= 0.75 * (288.00 / 2592.00) * 0.733 * 1.009 * 1.400 * 1.000 * 52186 lb = 4505 lb
D.6.2.1= Φ * (AVc / AVc0) * ψed,V * ψα,V * ψc,V * ψh,V * VbΦ * Vcb
D.6.2.81.000ψh,V
D.6.2.7= 1.400ψc,V
D.6.2.1c= 1.009ψα,V
D.6.2.6= 0.733ψed,V
= 288.00 inch²AVc
= 2592.00 inch²AVc0
= 7 * 1.516 * 0.707 * 59.161 * 117.58 = 52186 lb
= 7 * ( e / d0)0.2 * d00.5 * fc' 0.5 * ca11.5Vb
D.6.2.4= 24.00 inchc'a1
= 0.500 inchd0
D.6.2= 4.00 inchle
Concrete breakout strength, direction y+:
Pryout strength:
Vua / (Φ * Vcp) = 1196 lb / 12392 lb = 0.10 ≤ 1.00Design proof:
= 1196 lbVua
= 0.70 * (129.77 / 104.47) * 1.000 * 1.000 * 0.935 * 0.820 * 1.028 * 9042 lb * 2.0 = 12392 lb
= Φ * (ANa / ANa0) * ψec,Na,x * ψec,Na,y * ψed,Na * ψp,Na * ψg,Na * Na0 * kcpΦ * Vcpg
D.6.3.2= 2.0kcp
D.5.3.10= 1.028ψg,Na
D.5.3.14= 0.820ψp,Na
D.5.3.12= 0.935ψed,Na
= 4.00 inchca,min
D.5.3.11= 1.000ψec,Na,y
D.5.3.11= 1.000ψec,Na,x
= 104.47 inch²ANa0
= 129.77 inch²ANa
D.5.3.9= τK,uncr * π * d * hef = 1515 * π * 0.500 * 4.000 = 9042 lbNa0
= 4.000 inchhef
UofME Anchors.pcp2PDA - Powers Design Assist®
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
7/7Page:P32463Project number:Version: 2.3.6179.27440
Date: 3/7/2017University of Maine181 MainSt.Presque Isle, ME 04769
Project:
Company name:
(Nu / (Φ * Nn) + Vu / (Φ * Vn)) / 1.2 = (0.74 + 0.26) / 1.2 = 0.83 ≤ 1.0Design proof:
Interaction:
COMBINATION TENSION / SHEAR LOAD:
Fastening ok!
Characteristic bond strengths depend on short-term and long-term service temperatures.
WARNINGS / REMARKS:
UofME Anchors.pcp2PDA - Powers Design Assist®
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
phone: 303-450-8536 Date: 4/7/2017
fax: (303) 457-2801
University of Maine, Preqsue Ilse
Nexus Job #: P32463
Submittal Number: NEX-SUB-06
Submittal Description: Circulating Fan
Manufacturer: Schaefer
Quantity: 4 ea
VK12
120v
1/10 HP
1.3 amps
Product Data Information:
UE XN SGREENHOUSE CORPORATION
10983 LEROY DRIVE
NORTHGLENN, CO 80233
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
Date: 2/24/2017
phone: 303-450-8536
fax: (303) 457-2801
University of Maine, Preqsue Ilse
Nexus Job #: P32463
Submittal Number: NEX-SUB-03
Submittal Description: Exhasust Fans
Manufacturer: Greenheck
Quantity: 2 ea
SCE3-30-620-B20
230 v
3 PH
2 HP
Product Data Information:
UE XN SGREENHOUSE CORPORATION
10983 LEROY DRIVE
NORTHGLENN, CO 80233
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � ! � � � � � � � � � � � � � � � � " � � � � � � � � � � # $ � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � % � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � ! � � � � & � � � � � � � � � � � � � � � � � � � � � � � � � � � � � ' � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � � � ( � ) ( � ) � ' � * + � , ' � ' - , . - ) � ' � ( � � / , / � � � � � � ' 0 . � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �
1 2 3 4 5 4 6 3 7 7 8 9 : ; < = > ? @A B C D B C E F G H G E I J K E C F G C L· M N N O P Q R S T U V W X Y P S Z [ [ S · \ [ Y ] [ Z ^ _ ` a O b b c d c N M M · e T Q Y [ f g c O c h i j M d b b k M · l X m f g c O c h i j M d O c b nA o p q B C F r
· N M c \ s Q Z S T t P u V v T w X x b a i · l Q Z S _ Q y y V Y z ^ _ ` a O n b N d N a n c · e T Q Y [ f g k i O h N k c d i b k c · l X m f g k i O h N k c d i b k iA o p { B K F r· N b j O | R } ~ V Y v T X � \ Z V ] [ � M c O · _ Q y Q Z X � Q P W Z V Y v z ^ _ ` a O k O i d c i i a · e T Q Y [ f g i M k h n b a d M M M j · l X m f g i M k h n b a d j a k bA o p � G L F· n i n P Q R S T � [ z S v X S [ \ Z V ] [ t Y V S _ · � Z X Y � � R Y } S V Q Y ^ _ ` a M n O n d j k n a · e T Q Y [ f g k i O h b N c d N c i i · l X m f g k i O h b N c d O O j a� � � � � � � � �� � � � � � � � � � � � �� � � � � � � � � � � � � � � � � �� � � � � � � ¡ � ¢ £ � � � � £ � � � � � � � ¤ � ¥ ¤ � ¦ ¢§ � � ¨ � � � � � � � � © � ª « � � � ª � � � ¬ � ª � �® � � � � ª � � � ¯ � � � � ¥ °� � � ± ª � � � � �° � ² ª � � � � �� ³ � ¯ § � � ´ µ ¶ § ® ° � ¶ ° £ · ¯ ¯ ³ ³ ° ¸ · ¹ ° ³ ¯ ® ® ¯ º µ � » ° ¼ © µ § ° � · ³ ¯ ¸ ´ ¯ © ¸� ¯ � ¶ µ £ ° ¸ � · µ ¯ � �½ ¾ ¿ À Á Â Ã Ä Å Æ Ç È É É Ê Ë Ì Í ¾ Æ Å Î Ï Ë Ð Æ É É Æ Ï Ñ Ò Ó È Ì Ô ¾ Õ È Í Ö ¿ × Ï Æ Æ Í Ó Æ Ø ÙÚ Û Ü Ý Þ ß à á â ã Ú ã ä Ú å æ ä Ú ç æ ä è é ê Þ ë ì í Þ è ì ì è î í Þ Ý é ï ð ñ ò ì ì è ß éÚ ó è ß ô è õ ò ö Þ Ý é ì Þ Þ ß ÷ è õ ê è õ Þ ßÚ ø ò Þ ÷ Ü ë ñ Þ Ý ù ú è ß ô è õ ò ö Þ Ý é ì Þ Þ ß Ý ë ò ô Þ ÷ ë è ñ Þ è é é Þ ñ ð ß ûÚ á è é ì è ß ï ñ ò õ ï ñ è ò ë ÷ Ü ò ß ð ß è Ý Þ ê ë Ü ê Þ ß ß Þ ëÚ ç è ß ß ð Þ è ë ò õ ú ñ Ü ì Ü ë éÚ á Ü ë ë Ü é ò Ü õ ë Þ é ò é ì è õ ì ÷ è é ì Þ õ Þ ë éÚ ü è ì Þ Ý ÷ Ü ë ý ä ù ä ä ä þ ä ÿ æ � â à � é Þ ß Þ î ì Þ Ý è ì è ß ì ò ì ï Ý ÞÚ æ í ê ù æ ã ä � ã � å äÚ ø ò é î Ü õ õ Þ î ì à � ò ì î í ù � â Û � ã ü Þ õ î ß Ü é ï ë ÞÚ ó ë è ô ò ì û ø è ñ ê Þ ëÚ à í Ü ë ì � è ß ß � Ü ï é ò õ ú � � à � � ó ï è ë ÝÚ à Þ ß Þ î ì Þ Ý Ü ê ì ò Ü õ é è õ Ý è î î Þ é é Ü ë ò Þ é è é õ Ü ì Þ Ý Ü õ è ì ì è î í Þ Ý é ï ð ñ ò ì ì è ß Ë ¾ È É Æ ¾ Î Ï Ä Ø Æ � � � � � � � � � Æ È � � � � � � � � � � � Ë Ï À Á Â� Ì Ï Ï Æ Í ¾ � Æ È Å Ä � Æ Ä Ô � � � Ç Æ Æ Ù Ô Ð Ï Ë Å Ì Ø ¾ Ä Ë Í Ð É Ì Ô � � � Å È ¿ Ô ¾ Ï È Í Ô Ä ¾ ¾ Ä � Æ �� � � � È Ï Ä È Ö É Æ Õ Ï Æ � Ì Æ Í Ø ¿ Ï Ä ! Æ Ô È Ô � Ë É É Ë Ç Ô �Ú Û Ü Ý Þ ß � � à � Á � � � " � � # � � � ÁÚ æ ÿ ä í ê ù ã $ ÿ � è ñ ê éÚ ü è ì Þ Ý ÷ Ü ë ý Ú ê í è é Þ ò õ ù æ ã ä � ã Ü ï ìÚ � % � á � Ý ô è õ î Þ Ý � è õ Þ ß & ' ( ) ä ä *Ú � â Û � ý â õ î ß Ü é ï ë Þ + ò ì ÷ Ü ë Ý ë ò ô ÞÚ â ß Þ î ì ë Ü õ ò î Û Ü ì Ü ë � ô Þ ë ß Ü è Ý éÚ ý æ Û Ü õ ì í � è ë ì é � , ë è ô Þ ß � - è ð Ü ë � è ë ë è õ ì û & � Ü ë ñ è ß ç ï é ò õ Þ é é � Ü ï ë é * Ë ¾ È É Æ ¾ Î Ï Ä Ø Æ . � � � � � � � Æ È � � � � Á � � � � Ë Ï À Á Â/ Í Ô ¾ Ë Ø Ù È ¾ ¾ Ó Æ � È Ø ¾ Ë Ï ¿ Ð É Ì Ô � � � Å È ¿ Ô ¾ Ï È Í Ô Ä ¾ �� É É Ð Ï Ä Ø Ä Í 0 Ä Ô Õ 1 � Õ È Ø ¾ Ë Ï ¿ � Õ Ì É É � Ï Æ Ä 0 Ó ¾ È É É Ë Ç Æ Å ¾ Ë 2 Ë Ö Ô Ä ¾ Æ �3 4 5 6 7 8 9 : ; 8 < 5 6 = > 9 ? 9 5 = @ 9 : ; 8 AB C D E F G D H F I J K L I M N O P F P QB R J D G G F S T N U V L I G K D N N D K L J I V J H W D H H D I K U N D T J H L I M N O P F P QB X H P F H G H F M F L Y F P D Z K F H [ \ ] ^ _ ^ ` C a W L N N T F b H J M F G G F P J I K c F I F E K T O G L I F G G P D U Qd O G K J S F H e Q X Q f g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
EXHAUST AIRFLOW
DAMPER
GUARD
WALL HOUSINGINTERIOR EXTERIOR
Model: SCE3-30-620-B20Sidewall Direct Drive FanMotor Access From Int. of Bldg.
DimensionalQuantity 2
Weight w/o Acc's (lb) 185
Weight w/ Acc's (lb) 334
Max T Motor Frame Size 184
Optional Damper (in.) 32 x 32
Wall Opening (in.) 39.75 x 39.75
PerformanceRequested Volume (CFM) 10,000
Actual Volume (CFM) 10,001
External SP (in. wg) 0.25
Total SP (in. wg) 0.506
Fan RPM 1160
Operating Power (hp) 1.85
Elevation (ft) 194
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.074
Tip Speed (ft/min) 9,111
Static Eff. (%) 43
MotorMotor Mounted Yes
Size (hp) 2
Voltage/Cycle/Phase 230/60/3
Enclosure TEFC
Motor RPM 1160
Windings 1
External SP 0.25 in. wgDirect Drive RPM Adjustment 0.000 in. wgDamper 0.086 in. wgWall Housing 0.17 in. wgTotal SP 0.506 in. wg
Notes:All dimensions shown are in units of in.*Please consult factory for actual motor amp drawLwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
Sound Power by Octave BandSoundData 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 89 92 89 88 85 83 78 74 90 79 31
12/20/2016Printed Date: 28341ML Nexus University of MaineJob:
Alt A2 Exhaust FansMark: SCE3-30-620-B20Model:
Generated by: [email protected] 4.21.2332 M:\SalesGroup\EndUser\Greenheck CAPs Files\28341ML Nexus University of Maine.gfcj Page 1 of 5
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
Model: SCE3-30-620-B20Sidewall Direct Drive FanStandard Construction Features:- Galvanized steel fan panel - Die formed, galv steel drive frame assembly - Castalum airfoil blade propeller - Ball bearing motors - Corrosion resistant fastenersSelected Options & Accessories:UL/cUL 705 Listed - "Power Ventilators"Airflow Direction: ExhaustDamper Mounted, WD-320-PB-32X32, Gravity Operated, Not CoatedShort Wall Hsg, Flush Exterior, w/ OSHA Grd.Motor Access: From Int. of Bldg.Switch, NEMA-3R, Toggle, Shipped with UnitJunction Box Mounted & WiredUnit Warranty: 1 Yr (Standard)
12/20/2016Printed Date: 28341ML Nexus University of MaineJob:
Alt A2 Exhaust FansMark: SCE3-30-620-B20Model:
Generated by: [email protected] 4.21.2332 M:\SalesGroup\EndUser\Greenheck CAPs Files\28341ML Nexus University of Maine.gfcj Page 2 of 5
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
Assembly DrawingType: Sidewall Direct Drive Fan
DRAWING VIEWED FROM INTERIOR
THIS FAN HAS 6 BLADES
END VIEW DIMENSIONS ARE FOR HOUSING NOT FAN PANEL
MOTOR IS ACCESSIBLE FROM INTERIOR OF BUILDINGTHIS IS AN EXHAUST FAN DUE TO MOTOR ORIENTATION
WALL OPENING 39.75 SQ.
EXHAUST AIRFLOW
DAMPER
GUARD
WALL HOUSINGINTERIOR EXTERIOR
38.25
38.25
44.25
44.25
38.00
38.25
Notes: All dimensions shown are in units of in..
12/20/2016Printed Date: 28341ML Nexus University of MaineJob:
Alt A2 Exhaust FansMark: SCE3-30-620-B20Model:
Generated by: [email protected] 4.21.2332 M:\SalesGroup\EndUser\Greenheck CAPs Files\28341ML Nexus University of Maine.gfcj Page 3 of 5
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
DAMPER TYP. SECTION VIEW
32
32
3.5
1.5
2.75
Standard Construction Features:- Model WD-320 is a vertical mount exhaust damper and is constructed of 18 ga galvanized steel with pre-punched mountingholes and a flanged frame - Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge - Steel axlesare 0.188 in. diameter zinc plated mounted steel in acetal bushings - Synthetic axle bearings
Notes: All dimensions shown are in units of in.Width And height furnished approximately 0.125 in. undersize
Vertical Mount Exhaust DamperModel: WD-320
12/20/2016Printed Date: 28341ML Nexus University of MaineJob:
Alt A2 Exhaust FansMark: SCE3-30-620-B20Model:
Generated by: [email protected] 4.21.2332 M:\SalesGroup\EndUser\Greenheck CAPs Files\28341ML Nexus University of Maine.gfcj Page 4 of 5
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
38.25
3838.25
3
Standard Construction Features:- Galvanized steel construction - Heavy gauge mounting flanges - Pre-punched mounting holes - Insideflanges allow damper to be mounted - Overlapping weatherhood flange keeps rain out - OSHA Protectiveguard of welded steel wire completely protects the drive side of the wall housing.
Notes: All dimensions shown are in units of in.
Short Wall Housing
12/20/2016Printed Date: 28341ML Nexus University of MaineJob:
Alt A2 Exhaust FansMark: SCE3-30-620-B20Model:
Generated by: [email protected] 4.21.2332 M:\SalesGroup\EndUser\Greenheck CAPs Files\28341ML Nexus University of Maine.gfcj Page 5 of 5
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
Date: 2/24/2017
phone: 303-450-8536
fax: (303) 457-2801
University of Maine, Preqsue Ilse
Nexus Job #: P32463
Submittal Number: NEX-SUB-08
Submittal Description: Ridge Vent Motor
Manufacturer: Wadsworth
Quantity: 4 ea
VC2000- 2 in 100/102, 2 in 103
115v
1/5 HP
2.5 amp
Product Data Information:
UE XN SGREENHOUSE CORPORATION
10983 LEROY DRIVE
NORTHGLENN, CO 80233
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
FEATURES• Gear motor: 1/5 HP - 115V; 60Hz; 2.5amps - TEFC• Ball bearing motor with copper windings - Class B insulation• Gear reducer: total reduction 1350:1; 1.2 and 3 RPM final output• Output torque 1500 inch lb / 169 Nm• Lifts up to 325’ of 4’ polycarbonate roof ridge vent or 400’ of 4’ polycarbonate side vent
FEATURES• Gear motor: 1/20 HP - 115V; 60Hz; 0.68 amps - TENV• Ball bearing motor with copper windings - Class B insulation• Gear reducer: total gear reduction 1900:1; 0.85 and 2.5 RPM final output• Output torque 500 inch lb / 56 Nm• Lifts up to 75’ of 4’ polycarbonate roof ridge vent or 125’ of 4’ polycarbonate side vent
VC 100A Vent Drive VC 2000 Vent Drive
SHAFT SIZEWadsworth’s drive units can be ordered to fit either a 1-3/8” or a 1-5/8” shaft.Measure the outside diameter (O.D.) of your shaft to determine which size iscorrect for your greenhouse.
• Thermal overload protection – automatic reset – continuous duty• Quick reversing• Worm gear with tapered roller bearings on dual output shafts immersed in synthetic oil• Dual output shaft• Sealed for life; limited or no maintenance required• Superior heat dissipation through fin & casting design
1-3/8” O.D. 1-5/8” O.D.
DriveUnits
BENEFITS
Take advantage of Wadsworth’s 40 plus years of experience in automating vents. Our driveunits set the standard for powerful performance, smooth operation and reliability.
To find out more call 800.821.5829, email [email protected] or visit www.wadsworthcontrols.com
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
VK1212" Versa-Kool Circulation Fan
Able to Ship Small Parcel : Yes
Air Velocity (@ 5 times diameter) : 680
BESS Lab Performance Test No. : 12370
Blade Color : Metallic
Blade Material : Aluminum
CFM (free air) : 1470
CFM Calculation Standard : ANSI/AMCA Standard 230-99
CFM Range (Free Air) : 1001 - 2500
CFM/Watt (free Air) : 14
Component Certifications : Motor - UL/CSA
Cord : Included - Not Wired
Cord Length (feet) : 5
Country of Origin : US
Diameter (inches) : 12
Display Name : VK12
Drive Type : Direct
Fixed or Portable : Fixed
Frequency (Hz) : 60
Guard Color : White
Guard Material & Coating : Powder Coated Steel
Guard Spacing (inches) : 1/2 - 1 UL507
Housing Color : White
Max RPM : 1725
Mount Included : VS12FMT
Mount Type Included : Ceiling
Nameplate Amps : 1.3/.65
Number of Wings : 3
Oscillating : No
Phase : 1
Power (hp) : 1/10
Product Color : White
Product Shipping Dimensions : 15 X 14 X 16
Product Weight (pounds) : 18
Speed Control Compatible : Yes
Speeds : 1
Switch : Not included
VFD Compatible : No
Voltage : 115/230
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
phone: 303-450-8536 Date: 2/24/2017
fax: (303) 457-2801
University of Maine, Preqsue Ilse
Nexus Job #: P32463
Submittal Number: NEX-SUB-05
Submittal Description: Destratification Fan
Manufacturer: Dayton
Quantity: 3 ea
7DX27- 2 each in 100/102, 1 in 103
120v
1 PH
.5 amps
Product Data Information:
UE XN SGREENHOUSE CORPORATION
10983 LEROY DRIVE
NORTHGLENN, CO 80233
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
Date: 2/24/2017
phone: 303-450-8536
fax: (303) 457-2801
University of Maine, Preqsue Ilse
Nexus Job #: P32463
Submittal Number: NEX-SUB-09
Submittal Description: Shade System Motor
Manufacturer: Wadsworth
Quantity: 2 ea
VC2000
115 c
1/5 HP
2.5 amp
Product Data Information:
UE XN SGREENHOUSE CORPORATION
10983 LEROY DRIVE
NORTHGLENN, CO 80233
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS
FEATURES• Gear motor: 1/5 HP - 115V; 60Hz; 2.5amps - TEFC• Ball bearing motor with copper windings - Class B insulation• Gear reducer: total reduction 1350:1; 1.2 and 3 RPM final output• Output torque 1500 inch lb / 169 Nm• Lifts up to 325’ of 4’ polycarbonate roof ridge vent or 400’ of 4’ polycarbonate side vent
FEATURES• Gear motor: 1/20 HP - 115V; 60Hz; 0.68 amps - TENV• Ball bearing motor with copper windings - Class B insulation• Gear reducer: total gear reduction 1900:1; 0.85 and 2.5 RPM final output• Output torque 500 inch lb / 56 Nm• Lifts up to 75’ of 4’ polycarbonate roof ridge vent or 125’ of 4’ polycarbonate side vent
VC 100A Vent Drive VC 2000 Vent Drive
SHAFT SIZEWadsworth’s drive units can be ordered to fit either a 1-3/8” or a 1-5/8” shaft.Measure the outside diameter (O.D.) of your shaft to determine which size iscorrect for your greenhouse.
• Thermal overload protection – automatic reset – continuous duty• Quick reversing• Worm gear with tapered roller bearings on dual output shafts immersed in synthetic oil• Dual output shaft• Sealed for life; limited or no maintenance required• Superior heat dissipation through fin & casting design
1-3/8” O.D. 1-5/8” O.D.
DriveUnits
BENEFITS
Take advantage of Wadsworth’s 40 plus years of experience in automating vents. Our driveunits set the standard for powerful performance, smooth operation and reliability.
To find out more call 800.821.5829, email [email protected] or visit www.wadsworthcontrols.com
13 34 13.1 OWNER FURNISHED - CONTRACTOR INSTALLED COMPONENTS