Belimo Energy Valve™ Delta T Manager™. Presentation Agenda. Low Delta T at the Coil Some of Low Delta T Causes Low Delta T Cost of Overflowing Coil Cost of Chiller Staging Cost of Over Pumping Occupant Comfort Does it Really Work? Benefits. Low Delta T at the Coil. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Belimo Energy Valve™ Delta T Manager™

1Energy Valve Delta T Manager

Belimo Energy Valve™Delta T Manager™

Page 2: Belimo Energy Valve™ Delta T Manager™

Presentation Agenda

• Low Delta T at the Coil• Some of Low Delta T Causes• Low Delta T

• Cost of Overflowing Coil• Cost of Chiller Staging• Cost of Over Pumping• Occupant Comfort

• Does it Really Work?• Benefits

2Energy Valve Delta T Manager

Page 3: Belimo Energy Valve™ Delta T Manager™

3

Low Delta Tat the Coil

Low Coil Delta T = Inefficient Heat Transfer

Increase GPM >> No Increase in Energy output

More Pump HP >> Reduction in Plant Efficiency

Energy Valve Delta T Manager

Page 5: Belimo Energy Valve™ Delta T Manager™

5

Low Delta TCoil Power vs Delta T Behavior

Energy Valve Delta T Manager

Page 6: Belimo Energy Valve™ Delta T Manager™

6

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 800

50000

100000

150000

200000

250000

300000

350000

400000

0

2

4

6

8

10

12

GPM

Pow

er =

BTU

Del

ta T

°F

335000

10.5°F

65 GPM

12°F

55 GPM

330000

CoilPower Curve

Delta T Curve

1

2

Low Delta TCost of Overflowing the Coil…

Energy Valve Delta T Manager

Page 7: Belimo Energy Valve™ Delta T Manager™

7

Pump hp Hp increase = (65/55)3 65%

1 2 ΔBTUh 330,000 335,000 1.5%GPM 55 GPM 65 GPM 18%

3

1

2

1

2

GPMGPM

HPHP

?

Low Delta TCost of Overflowing the Coil…

Energy Valve Delta T Manager

Page 8: Belimo Energy Valve™ Delta T Manager™

Delta T Manager™Cost of Chiller Staging

Chiller Plant Efficiency

• Design ΔT=12oF (54oF - 42oF)

• 360 GPM

• 1 Chiller, 90% Load (180 Ton)

Design Condition

360 GPM Loop flow

8Energy Valve Delta T Manager

Page 9: Belimo Energy Valve™ Delta T Manager™

Chiller Plant Efficiency

Low ΔT

• ΔT=10.4oF (52.4oF - 42oF)

• 415 GPM• 2 Chillers, 45% Load (180 Ton)

No change to the load, but a 2nd Pump and 2nd Chiller are started.

415 GPM Loop flow

9

Delta T Manager™Cost of Chiller Staging

Energy Valve Delta T Manager

Page 10: Belimo Energy Valve™ Delta T Manager™

Low Delta TCost of Over Pumping

Wasted Pumping

10

Delta T Manager Signal

DDC Signal

Delta T Manager On

Delta T Manager On

Energy Valve Delta T Manager

Page 11: Belimo Energy Valve™ Delta T Manager™

Delta T Manager™Occupant Comfort

11

“How can I let the Delta T Manager limit flow if it doesn’t measure discharge air temperature?

What about occupant comfort?!?”

Page 12: Belimo Energy Valve™ Delta T Manager™

Delta T Manager™Occupant Comfort

12

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 800

50000

100000

150000

200000

250000

300000

350000

400000

0

2

4

6

8

10

12

GPM

Pow

er =

BTU

Del

ta T

°F

65 GPM

Power Curve

Delta T Curve

Delta T Manager adjusts the valve if the ΔT drops below the set point in order to maintain peak coil efficiency

55 GPM

Power Saturation

Virtually No Power Reduction

Delta TSet Point

Energy Valve Delta T Manager

335000325000

Page 13: Belimo Energy Valve™ Delta T Manager™

Delta T Manager™

Does it really work?

13Energy Valve Delta T Manager

Page 14: Belimo Energy Valve™ Delta T Manager™

Case StudyLarge Tech Company in North Carolina

Position Control240 GPM

144 GPM

96 GPM

Flow Control

DT Management

14Energy Valve Delta T Manager

Page 15: Belimo Energy Valve™ Delta T Manager™

Case StudyMIT University Hayden Library - Boston, MA

Building and Project Details• 150,000 sq. ft. on 3 floors• 6 AHU provide majority of the cooling

Results• Aug 9 - Oct 9, 2010

DT = 6.15°F

• Aug 9 - Oct 9, 2011DT = 12.14°F

15Energy Valve Delta T Manager

Page 16: Belimo Energy Valve™ Delta T Manager™

Case StudyUniversity of Miami Hospital

Building and Project Details• Rosenstiel Building• 11 AHUs• 2600 Tons of Cooling• Over 10,000 GPM

Results• Delta T raised from

5.5°F to 10.5°F• Flow ~ 5600 GPM• Estimated $66,000/yr savings• Estimated 2.9 year payback

16Energy Valve Delta T Manager

Page 17: Belimo Energy Valve™ Delta T Manager™

Delta T Manager™Benefits

• Coil• ΔT Managing for peak coil efficiency• Optimization in retro-fit applications

• Chiller Plant• Improved chilled water plant efficiency • Released chiller capacity

• Pump• Reduced pump energy

• Occupant Comfort• No reduction in supplied energy

17Belimo Americas Danbury, Connecticut

Page 18: Belimo Energy Valve™ Delta T Manager™

18

Thank You !

Visit (www.EnergyValve.com)

or Contact Belimo(800) 543-9038

Thank You

Energy Valve Delta T Manager