LISA D. NORDSTROM Lead Counsel [email protected] February 5, 2021 VIA ELECTRONIC FILING [email protected] Re: Docket UM 2154 - In the Matter of Idaho Power Company’s Application for Approval of Its Meter Test and Inspection Policy Attention Filing Center: Attached for filing, pursuant to Order No. 20-088, is Idaho Power Company’s Application for Approval of Its Meter Test and Inspection Policy in the above-referenced proceeding. Please contact me at (208) 388-5825, or Regulatory Analyst Zack Thompson at [email protected] with any questions regarding this filing. Very truly yours, Lisa D. Nordstrom LDN:slb Attachment

Upload: others

Post on 01-Apr-2021

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

LISA D. NORDSTROM Lead Counsel [email protected]

February 5, 2021 VIA ELECTRONIC FILING [email protected]

Re: Docket UM 2154 - In the Matter of Idaho Power Company’s Application for Approval of Its Meter Test and Inspection Policy

Attention Filing Center:

Attached for filing, pursuant to Order No. 20-088, is Idaho Power Company’s Application for Approval of Its Meter Test and Inspection Policy in the above-referenced proceeding.

Please contact me at (208) 388-5825, or Regulatory Analyst Zack Thompson at

[email protected] with any questions regarding this filing.

Very truly yours, Lisa D. Nordstrom LDN:slb Attachment

Page 2: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Page 1 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER TEST AND INSPECTION POLICY

BEFORE THE PUBLIC UTILITY COMMISSION OF OREGON

UM 2154

In the Matter of the Application of IDAHO POWER COMPANY for Approval of Its Meter Test and Inspection Policy

APPLICATION

Pursuant to ORS 757.250, Idaho Power Company (“Idaho Power” or “Company”)

respectfully requests the Oregon Public Utility Commission (“OPUC” or “Commission”) issue

an order approving its 2021 Meter Test and Inspection Policy (“2021 Policy”). The 2021

Policy contains Idaho Power’s updated comprehensive metering business policies and

practices necessary to comply with Oregon Administrative Rule 860-023-0015 Testing Gas

and Electric Meters, and the requirements of the Oregon Public Utility Commission Electric

Utility Metering Policy as adopted by the Oregon Public Utility Commission on July 20, 2000

with an effective date of January 1, 2001.1 Attached to this Application is the 2021 Policy

(Attachment 1), along with a redlined version showing the updates from the 2000 Policy

(Attachment 2).

I. BACKGROUND

AMI Meter Installation

Prior to the 2010 deployment of Advanced Metering Infrastructure (“AMI”) in its Oregon

service area, Idaho Power communicated to Commission Staff that the Company would

suspend all meter maintenance until the AMI changeout project was complete. At that time,

representatives from the Company and Commission Staff determined ongoing planned

1 Idaho Power has not identified a docket number or Commission order number where the current policy was adopted. Based on its records, Idaho Power submitted the existing policy (the 2000 Policy) to the OPUC on or around October 5, 2000 and received OPUC approval that same month. Idaho Power has complied with this policy, which meets the requirements of Oregon Administrative Rule 860-023-0015 and the Commission’s electric metering policy adopted on July 20, 2000.

Page 3: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Page 2 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER TEST AND INSPECTION POLICY

maintenance was not necessary because the majority of the meters typically requiring

maintenance would be replaced with new solid-state AMI meters as part of the project’s

rollout. The initial AMI meter changeout project was completed in 2010. In the initial AMI

rollout, the Company installed AMI at all locations found to be cost-effective, resulting in AMI

capability serving approximately 18,000 meters in its Oregon service area, or nearly 90% of its

Oregon customers.

In 2019, the Company started a project to expand its AMI technology, which is

expected to be completed around March of 2021. The project will enable AMI functionality for

1,300 of the approximately 1,500 non-AMI meters left in the Company’s Oregon service area.

The remaining 200 meters are expected to be converted in 2022 or 2023.

Meter Test Plan During AMI Rollout

In alignment with the American National Standard Institute’s (“ANSI”) Code for Electricity

Metering at that time, ANSI C12.1-2008, Idaho Power’s AMI meters were subject to a periodic

in-service test plan after the initial AMI rollout in 2010. The remaining solid-state non-AMI

meters qualified for random sampling or periodic maintenance programs. Consequently, the

Company divided all of the meters in its Oregon service area into periodic meter groups

(“PMG”) by model and/or attribute. Although the ANSI C12.1 2008 did not specifically address

solid-state meters or solid-state meters with automated communication capabilities, the

decision to place all of the Oregon meters into PMGs was in line with ANSI standards and

industry practices.

Beginning in 2014, Idaho Power informed the Commission in each of its Annual Meter

Test and Certification Reports2 that the Company recognized the long-term grouping of all

meters into PMGs was not practical or sustainable due to the updated AMI meter guidance in

2 In compliance with OAR 860-023-0015(3), Idaho Power submits an Annual Meter Test and Certification Report in RE 158. The 2020 Annual Meter Test and Certification Report will be filed in May 2021.

Page 4: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Page 3 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER TEST AND INSPECTION POLICY

ANSI C12.1-2014. Consequently, the Company determined it would develop and implement

other in-service planned testing programs to be approved by the Commission.

II. UPDATED METER TESTING STANDARDS

Idaho Power’s 2021 Policy adopts current meter testing standards.

ANSI C12.1 Standard

The 2021 Policy adopts the most current edition of the ANSI C12.1 standard, the 2014

edition.3 The ANSI C12.1 standard establishes acceptable in-service performance levels for

meters and devices used in revenue metering. In particular, the 2014 edition of ANSI C12.1

gives guidance for the in-service maintenance requirements for solid-state meters and solid-

state meters with automated communication capabilities. ANSI C12.1 also allows for a

combination of testing plans, such as a Periodic Interval Plan, Variable Interval Plan, or a

Random Statistical Sampling Plan.

Idaho Power’s periodic testing interval based on the 2000 Policy is 16 years, which is

consistent with ANSI recommendations from previous editions of the standard. The 2014

edition of ANSI C12.1 recommends using a set interval of eight years for testing solid-state

meters. If Idaho Power were to adopt the 8-year period test interval, almost all meters in

Idaho Power’s Oregon service area would be due for testing immediately because most of the

meters were installed around 2010 during the AMI changeout project. Rather than moving to

an 8-year periodic interval, the Company plans to move to a Random Statistical Sample Test

Plan for self-contained single- and three-phase meters, as well as instrument transformer

rated meters not covered by the Periodic Interval Test Plan. The Random Statistical Sample

Test Plan will adhere to the guidelines and sampling procedures outlined in ANSI Z1.9-2003

(R2018).4 The meters will be divided into homogenous meter groupings (HMG) that will

3 ANSI C12.1-2014, Code for Electricity Metering. 4 ANSI Z1.9-2003 (R2018), Sampling Procedures and Tables for Inspection by Variables for Percent Nonconforming.

Page 5: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Page 4 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER TEST AND INSPECTION POLICY

include meters from across Idaho Power’s service area. Random samples from each HMG

will be tested. Moving to a random sampling plan will allow the Company to properly leverage

current staffing levels as well as streamline the meter testing work going forward.

For Large Industrial customers, the 2021 Policy incorporates a Periodic Interval Test

Plan. This plan ensures correct metering accuracy for the Company’s largest customers that

have high consequence for failure. In-service meters with an average peak demand greater

than 10 MW will be tested once every two-years, and in-service meters with an average peak

demand between 1 MW and 10 MW will be tested once every four years.

ANSI Z1.9 Standard

The 2021 Policy adopts the most up to date edition of the ANSI Z1.9 standard, the

2018 edition.5 The ANSI Z1.9 standard establishes random sampling plans and procedures

for inspection by variables. Idaho Power will adhere to the 2018 edition of the ANSI Z1.9

standard for its in-service random sampling test plan.

ANSI Z1.4 Standard

The 2021 Policy also adopts the newest edition of the ANSI Z1.4 standard, the 2018

edition.6 The standard establishes sampling procedures and tables for inspection by

attributes that Idaho Power will follow for acceptance testing of new meters. Idaho Power

currently tests a 10 percent sample from all new meter lots. Beginning in 2021, the Company

will use the statistical methods from ANSI Z1.4 to determine the sample size needed to accept

or reject new meter lots instead of relying on a 10 percent sample. The adoption of ANSI Z1.4

in the 2021 Policy will result in a more efficient meter acceptance testing process with less

meters to test on average.

IEEE 57.13 Standard

5 Id. 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection.

Page 6: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER TEST AND INSPECTION POLICY

In conjunction with ANSI C12.1-2014, the Policy adopts the Institute of Electrical and

Electronics Engineers’ IEEE 57.13-2016, Standard Requirements for Instrument

Transformers, as it pertains to meter and instrument transformer accuracy requirements that

must be demonstrated by the manufacturer.

III. CONCLUSION

The metering business policies and practices outlined in the 2021 Policy will adopt

current meter testing standards, ensure metering accuracy, confirm correct customer billing,

and streamline testing processes based on the most updated methods and guidelines. The

proposed policy aligns to industry best practices and to the requirements of OAR 860-023-

0015 related to electric meter testing, verification programs, maintenance of watt-hour

standards, and standardization of equipment.

The Company respectfully requests the Commission approve Idaho Power Company's

Metering Test and Inspection Policy for customer meters located in Idaho Power's Oregon

service area.

Respectfully submitted this 5th day of February 2021.

LISA D. NORDSTROM Attorney for Idaho Power Company

Page 7: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

UM 2154

Attachment 1

To

Application of Idaho Power Company for Approval of Its

Meter Test and Inspection Policy

Page 8: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Idaho Power Company Meter Test and Inspection Policy

February 2021 Page i

Table of Contents

Meter Test and Inspection Policy .....................................................................................................1

1. Scope ....................................................................................................................................1

1.1 Scope ....................................................................................................................... 1

2. General .................................................................................................................................1

2.1 General ..................................................................................................................... 1

2.2 Test Loads and Test Equipment ............................................................................... 1

2.3 Compliance .............................................................................................................. 2

3. Definitions............................................................................................................................2

4. References ............................................................................................................................3

5. Standards and Standardizing Equipment .............................................................................4

5.1 Certified Standards .................................................................................................. 4

5.2 Accuracy Requirements for Standards .................................................................... 4

6. Meter Testing and Inspection Plans .....................................................................................4

6.1 New Metering Device Acceptance .......................................................................... 5

6.2 In-Service Random Sample Test Plan ..................................................................... 5

6.3 Periodic Interval Test Plan ....................................................................................... 6

6.4 Additional In-Service Meter Testing ....................................................................... 6

6.5 In-Service Metering System Inspection, Maintenance, and Verification ................ 7

6.6 In-Service Inspection Schedule for Transformer Rated Metering Installations ......................................................................................................................... 8

6.7 In-Service Inspection Schedule for Self-Contained Meter Installations ................. 8

7. Accuracy ..............................................................................................................................8

7.1 Meter and Instrument Transformer Accuracy .......................................................... 8

8. Security ................................................................................................................................9

9. Revenue Protection ............................................................................................................10

9.1 Energy Consumption Investigations ...................................................................... 10

9.2 Energy Diversion Program and Enforcement ........................................................ 10

9.3 Primary Service Level Metering Evaluation ......................................................... 10

9.4 Other Revenue Protection Measures ..................................................................... 10

10. Corrective Action ............................................................................................................... 11

11. Record Keeping ................................................................................................................. 11

Page 9: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Meter Test and Inspection Policy Idaho Power Company

Page ii February 2021

12. Meter Quality System Management ..................................................................................12

12.1 Internal Audit ......................................................................................................... 12

12.2 Annual Meter Management Review ...................................................................... 12

13. Annual Metering Certification Report to the Oregon Public Utility Commission ............12

Page 10: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Idaho Power Company Meter Test and Inspection Policy

February 2021 Page 1 of 12

Meter Test and Inspection Policy

PROCEDURAL REQUIREMENTS FOR MAINTAINING THE ACCURACY OF IDAHO POWER COMPANY’S ELECTRIC

METERS, STANDARDS, AND STANDARDIZING EQUIPMENT

1. Scope

1.1 Scope

a) This document provides an overview of the practices and policies implemented by Idaho Power Company (IPC) to ensure metering accuracy and correct customer billing within the Company’s service area in Idaho and Oregon. This policy aligns to industry best practices and to the requirements of the Oregon Public Utility Commission OAR 860-023-0015 regulation related to electric meter testing and verification programs, maintenance of watt-hour standards and standardizing equipment.

2. General

2.1 General

a) No meter or metering device shall be placed in service, or be allowed to remain in service, that has an incorrect meter constant, is mechanically or electrically defective, incorrectly connected, installed, or applied; or is outside acceptable accuracy levels. No device shall be placed on or in a meter or meter circuit that could adversely affect the accuracy or performance of the meter or meter circuit.

2.2 Test Loads and Test Equipment

a) For meters, the full load test current shall be approximately 100% +/- 3% of the meter nameplate test current at unity power factor and light load test current shall be approximately 10% +/- 3% of the meter nameplate test current at unity power factor. Power factor tests current shall be approximately 100% +/- 3% of the meter nameplate test current at approximately 50% lagging power factor. Meters used with external current transformers shall use full load test current of 100% +/- 3% of meter nameplate test current or 100% +/- 3% of the secondary current rating of the transformer. The light load test for meters used with current transformers shall be equal to 10% of the selected full load value. All meter accuracy testing will be performed with appropriate equipment with accuracy traceable to the National Institute of Standards and Technology (NIST).

Page 11: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Regulatory Compliance Event Standard Idaho Power

Page 2 of 12 February 2021

2.3 Compliance

a) The practices and procedures outlined in this document ensure meters and metering systems accurately measure, register, and record the energy used by customers. These policies are founded on national metering standards and are reviewed and maintained in accordance with applicable regulatory requirements.

b) The Company’s meter testing and verification program shall be reported by jurisdictional area. Homogenous Meter Groups and associated sampling programs and reporting shall include jurisdictional area meters only.

3. Definitions

Acceptance Quality Limit (AQL)—The AQL is the quality level that is the worst tolerable product average when a continuing series of lots is submitted for acceptance sampling.

Action Criteria—Refers to a Lot or population of meters, which exceeds (“fails”) the Threshold Criteria two (2) consecutive years. The Action Criteria group shall be identified by; manufacturer, model or type, and other significant attributes, such as serial number range, manufacture year or engineering change.

Defective Meter Group—An identified group of meters that suffer premature failure due to manufacturer defects. Identified by manufacturer, model or type, and other significant attributes such as serial number range, manufacture year or engineering change.

Field Comparison Instruments—Devices used to determine reasonable in-service performance of metering equipment. Including multi-meters, watt-hour comparators, field instrument transformer test sets, ammeters and phase angle meters.

Homogeneous Meter Group (HMG)—A lot or population of metering devices from which a random sample is selected that, as far as practicable, consists of metering devices of the same basic type of model designation, have the same general construction, produced by the same manufacturer, and have the same relationship of parts.

Laboratory Standard—Standard meters that are used to verify the accuracy of working standards. The standards in the laboratory are the basic reference standards and the transport standards.

NIST—National Institute of Standards and Technology, United States Department of Commerce.

Periodic Meter Group (PMG)—A group of metering systems tested, inspected, and verified in a specific year that are on the same test frequency in a Periodic Meter Test Program.

Periodic Meter Test Program—An established scheduled pattern of meter site verifications where each site will be selected according to the utility’s designated regular time-interval.

Page 12: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Idaho Power Company Meter Test and Inspection Policy

February 2021 Page 3 of 12

Referee Tests—Tests performed at the request of customers or the Commission to resolve disputes.

Reference Standards—Standards with which the accuracy of the watthour is maintained in the laboratory.

Sample Meter Test Program—An established random pattern of testing meters belonging to a Homogeneous Meter Group whereby each meter has an equal opportunity to be selected for testing each year.

Sampling Plan—A specific plan which states the sample size(s) to be used and the associated criteria for accepting the lot.

Standards, National—Standard electrical quantities that are maintained by the NIST.

Transport Standards—Standards of the same nominal accuracy class as the basic reference standards of a laboratory. Such standards are regularly intercompared with the basic reference standards to maintain a history of behavior. The main purpose of the transport standard is to establish traceability from outside the utility and transfer traceability within the utility.

Uniquely Defective Meter—A meter selected for random sampling with accuracy performance characteristics greater than + 5% resulting from unique physical experience or unique electrical experience and is not representative of other in-service meters in its HMG. .

4. References

a) This document references the following documents:

(1) ANSI C12.1-2014 Code for Electricity Metering shall be used as a guide to establish acceptable performance criteria testing programs and standardized equipment.

(2) ANSI Z1.9-2003 (R2018) Sampling Procedures and Tables for Inspection by Variables for Percent Nonconforming shall be used as a guide for the In-Service Random Sampling Plan.

(3) ANSI Z1.4-2003 (R2018) Sampling Procedures and Tables for Inspection by Attributes shall be used for acceptance testing of new meters.

(4) Oregon Administrative Rule 860-023-0015

(5) IEEE C57.13-2016, IEEE Standard Requirements for Instrument Transformers

(6) The Company’s Metering Quality System Manual shall be used to communicate and implement metering policies, standards and procedures internal to the Company

Page 13: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Regulatory Compliance Event Standard Idaho Power

Page 4 of 12 February 2021

5. Standards and Standardizing Equipment

5.1 Certified Standards

a) The Company will follow a chain of intermediate steps between the national standard and watthour meters as outlined in ANSI C12.1-2014. It is the responsibility of the Company to establish and maintain the traceability of watthour standards to the NIST, or an approved testing laboratory that is traceable to NIST. The method used by the Company to ensure traceability to NIST is summarized as follows:

(1) The Company’s “Transport Standard” will be compared annually with the NIST or an approved testing laboratory that is traceable to NIST.

(2) The Company’s “Reference Standard” will be compared twice annually to the “Transport Standard”

(3) All “Portable Field Standards” and “Shop Standards” will be compared a minimum of once per year to the “Reference Standard”.

(4) All Company “tested” meters will have test results traceable to a “Portable Field Standard” or “Shop Standard” that was used for the test.

(5) Meter tests conducted by a qualified independent meter test lab will be required to submit traceability of the standards used annually to the Company.

5.2 Accuracy Requirements for Standards

a) The accuracy requirements for the Company’s Reference Standard and Field/Shop standards are as follows:

(1) Reference standards shall not exceed a percent error more than +/- 0.02% at unity Power Factor and at 50% Power Factor.

(2) Field/Shop standards shall not exceed a percent error more than +/- 0.05% at unity Power Factor and at 50% Power Factor.

6. Meter Testing and Inspection Plans

a) The Company follows an annual in-service performance testing plan in accordance with ANSI C12.1-2014. The purpose of conducting in-service performance testing is to ensure an acceptable degree of metering accuracy and performance throughout the service life of the Company’s meters.

b) Test records are maintained in the Customer Relations and Billing (CR&B) database for all in-service meters and retained for a minimum of two years following

Page 14: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Idaho Power Company Meter Test and Inspection Policy

February 2021 Page 5 of 12

retirement. Analysis of test results shall be made annually to determine if action is needed to address specific metering equipment or metering groups.

c) All meters tested with an as-found error greater than 0.5% will be immediately removed from service and retired. A meter is defined as conforming if the as-found average accuracy is within 100 +/- 0.5% registration. The method used to determine the percentage registration is Method 1 found in ANSI C12.1-2014. The test results for Uniquely Defective Meters will be identified and withheld from the Homogeneous Meter Group Sample Testing analysis. Any meters withheld from the analysis as Uniquely Defective Meters will be reported to the Oregon Public Utilities Commission in the annual Meter Test and Certification report.

6.1 New Metering Device Acceptance

a) The Company will document and implement material standards for metering related equipment. All new meters and instrument transformers shall be 100% tested by the manufacturer prior to being shipped to the Company. Certified test data will be provided to the Company upon receipt of the equipment. The Methods and Materials department within Idaho Power Company will analyze the test data to ensure accuracy specifications are met.

(1) Quality assurance testing of new meters will be conducted in accordance with ANSI Z1.4-2003 (R2018) Sampling Procedures and Tables for Inspection by Attributes with General Inspection Level II, Acceptance Quality Limit of 2.5, and Double Sampling Plan for Normal Inspection.

(2) This testing of new shipments is performed to determine the acceptability of the devices as delivered from the manufacturer.

(3) Accuracy testing will be performed in accordance with ANSI C12.1-2014 section 5.0.3.2.

(4) Meter test accuracy results must be 100% +/- 0.5% for both full load and light load before meters are accepted and placed in service.

(5) The determination of percentage registration is per Method 1 found in section 5.1.4.1 in ANSI C12.1-2014

(6) A minimum sample size will be selected based on the number in a shipment or production lot.

(7) Determination of acceptability will be performed in accordance with ANSI Z1.4-2003 (R2018) section 10.1.2.

6.2 In-Service Random Sample Test Plan

a) A statistical sampling plan will be used for in-service performance testing of:

Page 15: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Regulatory Compliance Event Standard Idaho Power

Page 6 of 12 February 2021

(1) Self-contained single- and three-phase meters.

(2) Instrument transformer rated meters not covered by a Periodic Interval Plan.

b) The Company will follow the principles of statistical sampling found in ANSI Z1.9-2003 (R2018) Sampling Procedures and Tables for Inspection by Variables for Percent Nonconforming. This standard will be used to determine the quantities of meters tested each year and acceptability criteria. Each meter in a HMG will have the same probability of being selected for testing.

c) Under this plan:

(1) Meters are divided into HMGs by manufacturer and model designation.

(2) Samples are selected annually from each HMG.

(3) The determination of sample size is based on Variability Unknown, Standard Deviation Method with Double Specification Limits, General Inspection Level II, and Acceptance Quality Limit (AQL) of 2.5.

(4) Table B-3 in ANSI Z1.9-2003 (R2018) is used to determine the maximum allowable percent nonconforming and used to determine whether the HMG exceeds the threshold criteria.

6.3 Periodic Interval Test Plan

a) A Periodic Interval plan is used for testing in-service meters installed at Large Industrial customer locations that have an average peak demand over 1 MW. This plan ensures correct metering accuracy for the Company’s largest customers that have high consequence for failure. Accuracy testing is performed in conjunction with the inspection, maintenance, and verification program used to identify defective metering equipment which helps determine future maintenance and testing needs.

b) Under this plan:

(1) In-service meters for Large Industrial Customers with an average peak demand greater than 10 MW are tested once every two-years.

(2) In-service meters for Large Industrial Customers with an average peak demand between 1 MW to 10 MW are tested once every four years.

6.4 Additional In-Service Meter Testing

a) Any meter removed from service will be tested prior to being reinstalled. Metering devices removed from service may be retired without a test per ANSI C12.1-2014.

Page 16: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Idaho Power Company Meter Test and Inspection Policy

February 2021 Page 7 of 12

b) Energy Imbalance Market Sites—Meters associated with the Energy Imbalance Market will be tested every twenty-four months or as required by the California Independent System Operator (ISO).

c) Co-Generation and Small Power Production—Meter testing for co-generation and small power production sites will be performed at a frequency established in the contract. Testing intervals vary and will be based on details in the contracts.

d) Intertie Testing—Intertie testing will be conducted on a pre-determine frequency agreed upon by operating utilities.

6.5 In-Service Metering System Inspection, Maintenance, and Verification

a) The Company ensures metering system safety, proper installation, security, and billing validation through an inspection, maintenance, and verification program. A visual inspection will be performed on all self-contained and transformer rated meter installations as part of periodic testing to verify proper:

(1) Component location, condition, connection, and grounding

(2) Safety and security

b) All primary distribution, substation, and transmission service-level metering sites are validated in the field annually. For new installations, an inspection and validation will be performed prior to the first billing. The inspection and validation will verify proper:

(1) Meter circuit location

(2) Voltage magnitude and transformer ratio

(3) Current magnitude and transformer ratio

(4) Phase angle and power factor

(5) Component application, condition, connection, and grounding

(6) Load registration

(7) Registration values and multipliers

(8) Billing system values and multipliers

(9) Safety and security

(10) Load profile recorder accuracy

Page 17: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Regulatory Compliance Event Standard Idaho Power

Page 8 of 12 February 2021

c) The Company’s CR&B database will be used as the system of record for validations. A site that has not been validated in six months will trigger an automated report to ensure that validations occur annually at a minimum.

6.6 In-Service Inspection Schedule for Transformer Rated Metering Installations

a) Within 90 days of new installation or completion of construction.

b) When tested

c) At the time of any metering component change.

6.7 In-Service Inspection Schedule for Self-Contained Meter Installations

a) When tested

7. Accuracy

7.1 Meter and Instrument Transformer Accuracy

a) All new meters and instrument transformers shall meet the requirements of ANSI C12.1-2014 Code for Electricity Metering and IEEE 57.13 -2016, IEEE Standard Requirements for Instrument Transformers as demonstrated by the manufacturer.

b) All new meters and instrument transformers shall be 100% tested by the manufacturer or the Company before being placed into service.

c) Meter test results must be 100% +/- 0.5% for both full load and light load before meters are accepted and placed in-service. Test records will be maintained for all new and in-service meters including the previous and current test results.

d) Meters used for primary service level accounts will be 100% tested by the Company prior to installation.

e) Any meter that is not or cannot be tested as scheduled will be assigned a failure cause code. Meters with errors in registration in excess of 0.5% shall be considered failed and will be reportable by manufacture model, failure date and cause code.

f) The standard accuracy class for instrument transformers is 0.3% or better. No instrument transformer with a transformer correction factor or ratio correction factor greater than +/- 0.3% will be accepted and placed in service.

g) Instrument transformer accuracy tolerance is based on the correction factor of the equipment being used to determine accuracy. Typically, 100% +/- 5%. No instrument

Page 18: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Idaho Power Company Meter Test and Inspection Policy

February 2021 Page 9 of 12

transformer shall be placed in service, or allowed to remain in service, if it shows evidence of physical damage, discolored terminals due to overload, change in texture or resiliency of insulation, or arc tracking on the insulation or bushing.

h) The accuracy of electronic billing data for primary service level metering will be verified against actual meter readings twice each year. The permissible variance for validation shall be < (2 X meter constant). The meter load profile time will be verified to within +/- 2 minutes monthly.

i) All instrument transformer meter installations shall be verified upon initial installation, test, component change, or configuration change. Verification shall include; safety, security, energy diversion, compliance with standards, physical condition (including distribution system), proper registration (through billing), voltage, load (readings vs. registration), instrument transformers and programming.

j) All self-contained meter installations shall be verified upon initial installation, test, or component change. Verification shall include; safety, security, energy diversion, compliance with standards, physical condition (including distribution system), proper registration (through billing), voltage, load (readings vs. registration), instrument transformers and programming.

8. Security

a) The following are measures taken by the Company to ensure metering system security:

(1) The Company will maintain adequate documented procedures to ensure and verify the physical security of metering installations through; control of sealing devices, control of change authority, control of audit trail and control of record retention.

(2) The Company will maintain adequate procedures to ensure and verify the information technology security of metering installations through; control of access, control of change authority, control of audit trail, and control of record retention.

(3) The Company will maintain adequate procedures to ensure and verify the security of metering records physical or electronic through; control of access to records, control of change authority, control of audit trail, and control of record retention.

(4) The Company uses a Two-Way Automatic Communication System (TWACS) based AMI system that provides daily reads. Processes have been established to notify personnel of non-communicating meters that may have been tampered with. Upon notification of a non-communicating meter, an order for a field employee to perform an investigation is created.

Page 19: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Regulatory Compliance Event Standard Idaho Power

Page 10 of 12 February 2021

(5) Meter programming password protection will be maintained in accordance with the Company’s Data Security Policy.

(6) Meter Data Systems will be maintained in accordance with the Company’s Data and Cyber Security Policy.

9. Revenue Protection

a) The following measures are used by the Company to ensure revenue validation:

9.1 Energy Consumption Investigations

a) The Company will maintain “High/Low” thresholds on each account triggering consumption investigation and/or manual override.

9.2 Energy Diversion Program and Enforcement

a) The Company will maintain a training program covering detecting, reporting and disposition of Energy Diversion.

b) The Company will maintain documented procedures for reporting and disposition of Energy Diversion.

c) The Company will maintain a system of recording and reporting of Energy Diversion.

9.3 Primary Service Level Metering Evaluation

a) Meters will be interrogated and information downloaded often enough to minimize risk of lost data.

b) Meter data will be validated for each billing period. Validation shall include; outages, missing intervals, peak consumption, power factor and historic use comparison.

c) Site visits and validations will be accomplished at least annually. A site that has not been validated in six months will trigger an automated report that is used to ensure that validations occur annually at a minimum. Visits will incorporate an inspection and verification of the metering system.

d) Revenue meters utilizing MV90 communication are verified in the field within one business day if reading errors are detected or daily communication fails.

9.4 Other Revenue Protection Measures

a) The Company has established Sarbanes–Oxley (SOX) controls specific to metering that provide revenue protection. Controls are reviewed and certified quarterly to ensure they have not failed.

Page 20: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Idaho Power Company Meter Test and Inspection Policy

February 2021 Page 11 of 12

b) Voltage readings on AMI three-phase meters are taken daily. Any site with a phase voltage below 100VAC will show up on an automated report that is used to generate outage notifications.

c) Transformer-rated irrigation monthly billing usage is compared to the connected horsepower and validation notes for the site. Deviations from expected load to true load result in the creation of an order for a service investigation.

d) The Company has an effective training program for field and billing personnel to detect abnormal usage amounts. The CR&B database has automated triggers for abnormal usage on all customers and meters billed through MV90 have their current usage compared to their historic usage at each billing period.

10. Corrective Action

a) The test results from Sample Testing will be analyzed and reported annually. The weighted average values of the as found test results (method 1 of ANSI C12.1-2014) will be used to determine whether the HMG exceeds the Threshold Criteria.

b) If the Threshold Criteria is exceeded for a HMG, the Company will follow one of the prescribed methods in ANSI C12.1-2014 section 5.0.3.4.4. Any discovered problems with quality or accuracy will be acted upon immediately by performing one or a combination of the following:

(1) Rejecting nonconforming new meter purchases and working with manufacturer for resolution

(2) Implementing an accelerated testing program

(3) Splitting meter groups into two or more subgroups

(4) Implementing a retirement plan

c) Corrective Action Plans will be documented and submitted to the Oregon Public Utilities Commission in the annual Meter Test and Inspection report. The plan shall address corrective action measures, costs, schedules, and impacts to customers and revenue. In the event that a HMG, as part of In-Service Meter Testing, fails for a second time, the HMG shall be removed from service within four years.

11. Record Keeping

a) Records will be maintained for all laboratory and field test standards by serial number. Records will be maintained for the life of the equipment plus five years.

b) Test records will be maintained for all meters and auxiliary transformers for the life of the equipment plus two years.

Page 21: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Regulatory Compliance Event Standard Idaho Power

Page 12 of 12 February 2021

c) Inspection and verification records are maintained for primary delivery rate customer's accounts for three years.

d) All energy diversion investigations will be recorded, and the records will be maintained for three years.

e) Meter and instrument transformer test records will identify; type, serial number, manufacturer, purchase date, test date, test reason code, action taken, test results, and location of test.

12. Meter Quality System Management

12.1 Internal Audit

a) The Company will schedule and conduct audits of the Meter Quality System to determine the extent of compliance with regulatory requirements for metering and for effectiveness of policies, internal standards and procedures.

b) The Company will conduct audits of the effectiveness of corrective and preventative action plans implemented as a result of nonconformance with regulatory or Meter Quality System requirements.

12.2 Annual Meter Management Review

a) Management will review the results of internal audits and develop corrective and preventative action plans for any nonconformity to regulatory and/or Meter Quality System requirements.

b) Management will review the effectiveness of the Meter Quality System and develop action plans for continuous quality improvement.

c) The Company will review the currency of this Meter Test Policy annually to ensure that it is up to date with national and state regulations, standards, and guidelines.

13. Annual Metering Certification Report to the Oregon Public Utility Commission

a) The Company will complete annually a metering certification report to the Commission as required by the Oregon Public Utility Commission Electric Utility Metering Policy.

b) The report will contain the information required in Section S of the Oregon Public Utility Commission Electric Utility Metering Policy for the entire company and for Oregon only.

Page 22: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

UM 2154

Attachment 2

To

Application of Idaho Power Company for Approval of Its

Meter Test and Inspection Policy

Page 23: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Idaho Power Company Meter Test and Inspection Policy

Updated February 2021

PROCEDURAL REQUIREMENTS FOR MAINTAINING THE ACCURACY OF IDAHO POWER COMPANY'S ELECTRIC METERS,

STANDARDS, AND STANDARDIZING EQUIPMENT

1.0 Scope 1.01 Scope

This document provides an overview of the practices and policies implemented by Idaho Power Company (IPC) to ensure metering accuracy and correct customer billing within the Company's service area in Idaho and Oregon. This policy aligns to industry best practices and to the requirements of the Oregon Public Utility Commission OAR 860-023-0015 regulation related to electric meter testing and verification programs, maintenance of watt-hour standards and standardizing equipment. This-standard-establishes the-aeceplableperformaace-efiteria-for-in-SeFVice and new-types-of ac kilowatt hour-metettF,Hilemanel-meters; emend-registers, pulse devises,,-instrunient-tmnsfoffnefs,auxiiiaty-cleylees-and-fo-the-exeoution-of-rocesses, It states acceptable in service-performance-le-yels-fer--meteFs,metei4eYices-and-metering processes-la supput-of-energy-00145M1400/1billlagA4-a-lso inclueles-information-on-measuretnent-standardsv instaliation-requir-ementsrtest-methods,and test schedu-les.

2.0 General 2.01 General

No meter or metering device shall be placed in service, or be allowed to remain in service, that has an incorrect meter constant, fegiste-F-constatorwatt-hour--constan eaH,atio;-oFdial-tfaim is mechanically or electrically defective, incorrectly connected, installed, or applied; or is outside acceptable accuracy performance levels. No device shall be placed on or in a meter or meter circuit that could adversely affect the accuracy or performance of the meter or meter circuit.

2.02 Test Loads and Test equipment For meters, the full load test current shall be approximately 100% +/- 3% of the meter nameplate

test current at unity power factor and light load tests current shall be approximately 10% +/- 3% of the meter nameplate test current at unity power factor. Power factor tests current shall be approximately 100% +/- 3% of the meter nameplate test current at approximately 50% lagging power factor lag. Meters used with external current transformers shall use full load test current of 100% +/- 3% of meter nameplate test current or 100% +/- 3% of the secondary current rating of the transformer. The light load test for meters used with current transformers shall be equal to 10% of the selected full load value. All meter accuracy testing will be performed with appropriate equipment with accuracy traceable to (he National Institute of Standards and Technology (NIST) NIST.

2.03 Compliance The practices and procedures outlined in this document ensure meters and metering systems accurately measure. register. and record the energy used by customers. These policies are founded on national metering standards and are reviewed and maintained in accordance with applicable re=gulatory requirements. Ouistandards, pfactices-arid-proc-Kkire&-fof-maintaining-the-riceitracyof electric meters are-based-on-acceptect-natioaal-metetingend-quality standards and-are-maintained in-compliance with-applicable-regulateFy-Femtirentents-and-roles,

Page 24: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

2.04 The Company's meter metering testing and verification program shall be defined by and reported by jurisdictional area. Homogenous Meter Groups and associated sampling programs and reporting shall include jurisdictional area meters only.

3.0 Definitions Acceptance Quality Limit (AOL): The AQL is the quality level that is the worst tolerable product average when a continuing series of lots is submitted for acceptance sampling. Action Criteria: Refers to a Lot or population of meters, which exceeds ("fails") the Threshold Criteria two (2) consecutive years. The Action Criteria group shall be identified by; manufacturer, model or type, and other significant attributes such as serial number range, manufacture year or engineering change. Defective Meter Group: An identified group of meters that suffer premature failure due to manufacturer defects. Identified by manufacturer, model or type, and other significant attributes such as serial number range, manufacture year or engineering change. Field Comparison Instruments: Devices used to determine reasonable in-service performance of metering equipment. Including multi-meters, watt-hour comparators, field instrument transformer test sets. ammeters and phase angle meters. Homogeneous Meter Groups (HMG): A lot or population of metering devices from which a random sample is selected that, as far as practicable. consists of metering devices of the same basic type of model designation, have the same general construction, produced by the same manufacturer, and have the same relationship of parts. As-a--minimum, g,foups-of metefsprodueed by the same-m-anufactuFer4aving-reIated-type-clesignation, of the-same-dew-and-having-the same-relationship-parts. Other-c444cpia-such-as-manufacture-year-or-sefial member-Fange-may be incorporated to-fnftheF-refine-homogeneous-groups-relating to-action-eFiter-i-a-and-defective-meter groups. Laboratory Standard - Standard meters that are used to verify the accuracy of working standards. The standards in the laboratory are the basic reference standards and the transport standards. NIST — National Institute of Standards and Technology, under the United States Department of Commerce. Periodic Meter Group (PMG) — A group of metering systems tested, inspected. and verified in a specific year that are on the same test frequency in a Periodic Meter Test Program. Periodic Meter Test Program - An established scheduled pattern of meter site verifications where each site will be selected according to the utility's designated regular time-interval. Per44die-Testing est-sehedules-an4-proc-e-dures the-C-oFnpany-maintains-for-testing-ofineter-s-atmi iFtspeetion-of-meteFinstal-lations-te-yeFify-in service-performancre,The-recia-ifernen tl-meetr as-a minimum, AN SI C Fee-efiumendaions-for--test-fivquen d-test-requittements,

Company-requirement-s-for-mor-e-fiequent-ai ing-may-b-e-added-ode4eted as deemed-necessary-by-c-onthict, custemetqoad-ar-other-requirements, Referee Tests: Tests performed at the request of customers or the Commission to resolve disputes. Reference Standards — Standards with which the accuracy or the watthour is maintained in the laboratory.

(also-known-as-"Seleotive Test ii+ter-nake-the-Company-)-The sehethrles-and-procedures-for-randem-selection-of-m-eters-to be tested by-homegeneetvi-grou-ps The-results of the test analy a ing-to-mom-acc-eptabi)-ity criteria? Sample Meter Test Program - An established random pattern of testing meters belonging to a Homogeneous Meter Group whereby each meter has an equal opportunity to be selected for testing each year. Sampling Plan: A specific plan which states the sample size(s) to be used and the associated criteria for accepting the lot. Standards, National: Standard electrical quantities that are maintained by the NIST. Transport Standards - Standards of the same nominal accuracy class as the basic reference standards of a laboratory. Such standards are regularly intercompared with the basic reference standards to maintain a history of behavior. The main purpose of the transport standard is to establish traceability from outside the utility and transfer traceability within the utility.

Page 25: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

Uniquely Defective Meter: A meter selected for random sampling with accuracy performance characteristics greater than + 5% resulting from unique physical experience or unique electrical experience and is not representative of other in-service meters in its HMG. A-meter-with-aeeuracy peffemanee-ohafaeteristics, ttrirelated-te-dessigwor-purpose,resulting-from-physiealdantage-, or-au eleetFic-al-exper-ienee-and not representative-of-othcr in-service-meters-in-the-Itomogenemis-meter group.

4.0 References This document references the following documents:

a) ANSI C12.1-2014 C12.1 1995 Code for Electricity Metering shall be used as a minimum standard for testing programs and standardized equipment.

b) ANSI Z1.9-2003 (R2018) /ASQC Z1.9 1993 Sampling Procedures and Tables for Inspection by Variables for Percent Nonconforming shall be used as a minimum standard for the In-Service Random Sampling Plan. sample testing-pfogram.

c) ANSI Z1.4-2003 (R2018) Sampling Procedures and Tables for Inspection by Attributes shall be used for acceptance testing of new meters.

d) Oregon Administrative Rule 860-023-0015 shall be used as a minimum standard for system compliance.

e) I EEE C57.I3-2016, IEEE Standard Requirements for Instrument Transformers f) The Company's Metering Quality System Manual shall be used to communicate and

implement metering policies, standards and procedures internal to the Company.

5.0 Standards and Standardizing Equipment

5.01 Certified Standards The Company will follow a chain of intermediate steps between the national standard and watthour meters as outlined in ANSI C12.1-20E4. It is the responsibility or the Company to establish and maintain the traceability of watthour standards to the NISI, or an approved testing laboratory that is traceable to NIST. The method used by the Company to ensure traceability to NIST is summarized as follows: The-Company-will-maintain-a-system-of staadafd tr-aeeability-as outlined in ANSI C12.1 1995. a) The Company's "Transport Standard" will be compared annually with the National Institute

of Standards NIST or an approved testing laboratory that is traceable to NIST. b) The Company's "Reference Laboratory Standard" will be compared twice annually to the

"Transport Standard" c) The "Test-Set-StaFtdards" (3) will be compared-twice each-year-to-theAboratory Standarg d) All The "Portable Field Standards" and "Shop Standards" will be compared a minimum of

once per year to twiee-eaek-yeaf-to the "Reference Test Set Standards". e) All Company "tested" meters will have test results traceable to a the "Portable Field

Standard" or "Shop Standard" that was used for the test. f) Meter tests conducted by a qualified independent meter test lab will be required to submit

traceability of the standards used annually to the Company. 4:02 Field Comparison4nstruments

Company-field comparison instruments and ehec-k-meters will be ti:aeeable to the --Test-Set Standard" annually. Results-of a field-eompar-isoavAl-aot-be-eonsideted-meter or meter-device tests-and will Iii.A.-ubst•it Lite-for requiFed-meteF ieter-deviee testing:Comparisen-insumments may-be-used-only-uuder-the-foRowing cireumstances: a) T-o-resolve-l4gli-bill inquiry issues-by-44emenstrating reasonableperformanee-orsingle-phase

watt-hour-metei:s7-it:ac-eeptah-le-to-ihe-eustome h) f-e-provide-evidence-of-ener-gy diversion-and calettlate-lesses-from-energydivemien, 0 To demonstratoreasonable-per-fonnariee-and/or-provide-evidenee-ef-a-need-for-furthePtest-ing

oF-inaintenanee-programs, 5.02 Accuracy Requirements for Standards

The accuracy requirements for the Company's Reference Standard and Field/Shop standards are as follows:

Page 26: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

a) Reference standards shall not exceed a percent error more than +1- 0.02% at unity Power Factor and at 50% Power Factor.

b) Field/Shop standards shall not exceed a percent error more than +/- 0.05% at unity Power Factor and at 50% Power Factor.

6.0 Meter Testing and Inspection Plans Sehedales-fer-Testing-mil-Inspeetion The Company follows an annual in-service performance testing plan in accordance with ANSI C12.1-2014. The purpose of conducting in-service performance testing is to ensure an acceptable degree of metering accuracy and performance throughout the service life of the Company's meters.

Test records are maintained in the Customer Relations and Billing (CR&I3) database for all in-service meters and retained for a minimum of two years following retirement. Analysis of test results shall be made annually to determine ir action is needed to address specific metering equipment or metering groups.

Ail meters tested with an as-found error greater than 0.5% will be immediately removed from service and retired. A meter is defined as conforming if the as-found average accuracy is within 100 +/- 0.5% registration. The method used to determine the percentage registration is Method I found in ANSI C12.1-2014. The test results for Uniquely Defective Meters will be identified and withheld from the Homogeneous Meter Group Sample Testing analysis. Any meters withheld from the analysis as Uniquely Defective Meters will be reported to the Oregon Public Utilities Commission in the annual Meter Test and Certification report.

6.01 New Metering Device Acceptance New-Meters-and instrument-T-ransferniers-T-esting-Sehedule The Company will document and implement material standards for metering related equipment.

All new meters and instrument transformers shall be 100% tested by the manufacture prior to being shipped to the Company. Certified test data will be provided to the Company upon receipt of the equipment. The Methods and Materials department within Idaho Power Company will analyze the test data to ensure accuracy specifications are met. a) Quality assurance testing of new meters will be conducted in accordance with ANSI Z1.4-

2003 (R2018) Sampling Procedures and Tables for Inspection by Attributes with General Inspection Level II. Acceptance Quality Limit or 2.5. and Double Sampling Plan for Normal Inspection.

b) This testing of new shipments is performed to determine the acceptability of the devices as delivered from the manufacturer.

c) Accuracy testing will be performed in accordance with ANSI C12.1-2014 section 5.0.3.2. d) Meter test accuracy results must be 100% +1- 0.5% for both full load and light load before

meters are accepted and placed in service. e) The determination of percentage registration is per Method 1 found in section 5.1.4.1 in ANSI

C12.1-2014 f) A minimum sample size will be selected based on the number in a shipment or production lot. g) Determination of acceptability will be performed in accordance with ANSI Z1.4-2003

(R2018) section 10.1.2.

a) Ail new-meters and instimment-t-ransfertners-shall-be-1-009/04ested-by-the-manufaettire-or-the Company-before-being-plaeed-inte-seprice

b)—For-Form-2-s-meehan-ieaktnetem-e-ight-(8)-meters-w41-1- be elected for test Pern-each pallet (96) of-meters.

e)—New-meters-eqe-ipped-with-dernand-registers; load-prefile-reeerders-er-other attributes that can effect inetering-meuraey-or-qualit all-be- tesfed-by-the-manti-fac-infe -the-Gempany

Page 27: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

beferc-being-placed-into service. Mantt-factureHneter-test-Fesults-will be veFified-b3f a in-iffinunu-1-0440-s-ample-of-each-pufehase-let-before-installat for

6.02 In-Service Random Sample Test Plan Schedule A statistical sampling plan will be used for in-service performance testing of:

a) Self-contained single-phase and three phase meters. b) Instrument transformer rated meters not covered by a Periodic Interval Plan.

The Company will follow the principles of statistical sampling found in ANSI Z1.9-2003 CR2018) Sampling Procedures and Tables for Inspection by Variables for Percent Nonconforming. This standard will be used to determine the quantities of meters tested each year and acceptability criteria. Each meter in a HMG will have the same probability of being selected for testing.

Under this plan: a) Meters are divided into I-IMGs by manufacturer and model designation. b) Samples are selected annually from each HMG. c) The determination of sample size is based on Variability Unknown. Standard Deviation

Method with Double Specification Limits, General Inspection Level II, and Acceptance Quality Limit (AQL) of 2.5.

d) Table B-3 in ANSI Zl.9-2003 (R2018) is used to determine the maximum allowable percent nonconforming, and used to determine whether the HMG exceeds the threshold criteria.

a) Each calendar year, a andom-sampIof-all-aeW-eenta4ned-meters-wkhedemand-g4sters--or meeltan-leal-attacbments,iwsep -1-14e-seleoted-from-eath-applieable-11-omogeneous -MeteF-GfeU-p, The deteFm-i-nation-4-14omogeneous-Meter-Groups-and-selection-or-Farulom samples-wi-1-1-be-Riade-usifttthe-following as-guidelinesi

,defo lectrieity-bletethig e—ANS11-4-SQC-Z1-.-9-1-9-93-Sampliilg-PrfVethireS and Tables fro-Inspection

b) The in i rt im um-inspection-level-441 be ANS/145QC Z1,9 1993 General 11 c) The acceptable-quatity-level-AQL-shall be ANSI1ASQC Z1.9 1993 AQL 2.5

6.03 Periodic Interval Test Plan In Service Periodic Testing-Schedule A Periodic Interval plan is used for testing in-service meters installed at Large Industrial customer locations that have an average peak demand over 1 MW. This plan ensures correct metering accuracy for the Company's largest customers that have high consequence for failure. Accuracy testing is performed in conjunction with the inspection, maintenance, and verification program used to identify defective metering equipment. which helps determine future maintenance and testing needs. Under this plan:

a) In-service meters for Large Industrial Customers with an average peak demand greater than 10 MW are tested once every two-years.

b) In-service meters for Large Industrial Customers with an average peak demand between 1 MW to 10 MW are tested once every four years.

a) Electrotnechanical-watt-houineter-s-with-sufge-pFoof--magnets-and kWh-registem-not-iichuled in-random sample-testing. 14-Yeafs-between-4eRting:

b) Electromechanical-ivatt-hour-ineter-s-with-suFge-pfoo-ki-agnets antl-hlec1umk+1 demand vegisters,1-2-YeeFs-betis*en-Iesting

c) ElectFomeehan-ical-watt-liour-meters-with-surge-proof-magnets-and-electronie-clemand Fegisters,--1-6--Veffs-between-testintk

d-1—E-lectron-ic-Meters,-16--Years-43etween-testing.

6.04 Additional In-Service Meter Testing Schedule

Page 28: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

a) Any meter removed from service will be tested prior to being reinstalled Before retirement or-reinstollation,Metering devices removed from service may be retired without a test per ANSI C12.1-2014 5.0.2.3.

b) Energy Imbalance Market Sites - Meters associated with the Energy Imbalance Market will be tested every twenty-four months or as required by the California independent System Operator. (ISO).

c) Co-Generation and Small Power Production - Meter testing for co-generation and small power production sites will be performed at a frequency established in the contract. Testing intervals vary and will be based on details in the contracts.

d) Intertie Testing - Intertie testing will be conducted on a pre-determine frequency agreed uponb y operating utilities.

0—Company-Intertie-andSpecial ContFac-t:-Aanua-14”r-as-speeified-by-eontraet=0 - 1-Rdusifial- Over- 14-Fnegawatt-Aemitful)-24-eafs-betweenAesting:

g3-P-Fimat-y-Delivet,ti4cate,4--Yeafs-betweett-testing

6.05 In-Service Metering System Inspection, Maintenance. and Verification In Service Inspection Sehedule-fovPfimaty-Delivety-Rate-MeteF-Systein-lostallations

The Company ensures metering system safety, proper installation. security, and billing validation through an inspection, maintenance, and verification program. A visual inspection will be performed on all self-contained and transformer rated meter installations as part of periodic testing to verify proper:

a) Component location, condition, connection. and grounding b) Safety and security

All primary distribution, substation, and transmission service-level metering sites are validated in the field annually. For new installations, an inspection and validation will be performed prior to the first billing. The inspection and validation will verify proper:

a) Meter circuit location b) Voltage magnitude and transformer ratio c) Current magnitude and transformer ratio d) Phase angle and power factor e) Component application, condition, connection. and grounding f) Load registration g) Registration values and multipliers h) Billing system values and multipliers i) Safety and security j) Load profile recorder accuracy

The Company's CR&B database will be used as the system of record for validations. A site that has not been validated in six months will tri er an automated report to ensure that validations occur annually at a minimum.

0 —Before fir-st-bi-14ing-fFeni-a-new-installation,or-an-installation ohaoge-or-atteration: d) Every 6 monthsc) When tested

6.06 In-Service Inspection Schedule for Transformer Rated Metering Installations a) Within 90 days of new installation or completion of construction. b) When tested c) At the time of any metering component change.

Page 29: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

6.07 In-Service Inspection Schedule for Self-Contained Meter Installations a) When tested

7.0 Accuracy 7.01 NevMeter and Instrument Transformer Accuracy

a) All new meters and instrument transformers shall meet the requirements of ANSI C12.1-20144-995 Code for Electricity Metering and IEEE 57.13 -2016, IEEE Standard Requirements for Instrument Transformers as demonstrated by the manufacturer.

b) All new meters and instrument transformers shall be 100% tested by the manufacturer or the Company before being placed into service.

c) Meters test results must be 100% +/- 0.5% for both full load and light load before meters are accepted and placed in-service. Test records will be maintained for all new in: service meters including the previous and current test results.

d) The standard accuracy class for instrument transformers is 0.3% or better. No instrument transformer with a transformer correction factor or ratio correction factor greater than Instrument4iansformer-test-resuits-must-be-100% +/- 0.3% will be to be accepted and placed in service.

e) -=orForin 2s meehaRical-meters,eight-(g)-meters-will-be-selected FrOfil Lech- paliet-(-96-yof meters4oFtest. Meters-test-results-most-be-1-00-044-0,5% for-hoth-fall-toad-and-light4ea4 before-meters are accepted-and-placed in seMee,The-C-ompany-will-work-with-the-supplier-to eorreet-any-deficieneies that may be indicated-before-the-meters-are placed in-service:

49—New-ineters-equipped-with-Elemand-registers7.-loaci-proftle-reeorders-orother attributes-that Gan affect metering aceuracy-or-quality-will-have-mantifac-turerls-test-resttlts-verified as fel-loNvsi

A-minim4m-of-1-0°/o-o.Pmanufaoturerls-test-resolts-shall be verifieid-for-each-metei-type at the time of receipt.

4- 41eters-types-with-no-ifi-servive-performanee-Iti&tory-at I PC-0-(new-tneteFtypes-)-wili-be 4-0014-tested-unti-l-sufrieient-in-servise-per-cormanee-data-is-establ-ished to-dentonstrate satic.faetory-performanee,

fri Aeter lacedAn-semice-on-primary-Eletivery-mtes-will-be-100-110-tested-by-the company.

g) Meters used for primary service level accounts will be I00% tested by the Company prior to installation.

7.01

7.02

riner-Aeeuraey a) The performance of a wait hour meter is consklefed-to be acceptab1e when the iiie -does-aot

ereevand-when-the-pereentage-registration-is-rieHRere-than-141.24-m-lesr,than-98%,Where instrument4ransformers-are-ised411-MailliletiOn-with4he-meterTtheregistration4imits.apply-to the-meter-equipment as a whole:

b) When a test-of-a-watt-haur-meter-imlieates that the-e+HFin-registration-exceeds-4-9,4rat-either tig1 -load-or-hea*Hoad-at-ttnity-power-fac4or--or-eweeds 2% at heavy-toad-at-approximately 04-powe4acter-lagr the-pereeni-registration of the meter shat-1-be-adjusted -The-adjustment must be-to within-0,5 % for light-and-Iteavy-load-at-unity-power-factorand-within-214-at heavy-lead-at-approximately 50%-peNver-faeter; or-the-meter-will-be-remove4from-serv-iee,

c) Any meter that is not or cannot be tested as scheduled will be assigned a failure cause code. Meters with errors in registration in excess of 0.5% 244) shall be considered failed and will be reportable by manufacture model, failure date and cause code.

d) Instrument transformer accuracy tolerance is based on the correction factor of the equipment being used to determine accuracy. Typically 100% +/- 5%. No instrument transformer shall be placed in service, or allowed to remain in service, if it shows evidence of physical damage, discolored terminals due to overload, change in texture or resiliency of insulation, or arc tracking on the insulation or bushing.

The accuracy of electronic billing data for primary service level delivery rate metering will be verified against actual meter readings twice each year. The permissible variance for validation shall be < (2 X meter constant). The meter load profile time will be verified to with in +/- 2 minutes monthly.

Page 30: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

7.03 All instrument transformer meter installations shall be verified upon initial installation, test, component change, or configuration change. Verification shall include; safety, security, energy diversion, compliance with standards, physical condition (including distribution system), proper registration (through billing), voltage, load (readings vs. registration), instrument transformers and programming.

7.04 All self-contained meter installations shall be verified upon initial installation, test, or component change. Verification shall include; safety, security, energy diversion, compliance with standards, physical condition (including distribution system), proper registration (through billing), voltage, load (readings vs. registration), instrument transformers and programming.

8.0 Security The following are measures taken by the Company to ensure metering system security:

8.01 The Company will maintain adequate documented procedures to ensure and verify the physical security of metering installations through; control of sealing devices, control of change authority, control of audit trail and control of record retention.

8.02 The Company will maintain adequate procedures to ensure and verify the information technology security of metering installations through; control of access, control of change authority, control of audit trail, and control of record retention

8.03 The Company will maintain adequate procedures to ensure and verify the security of metering records physical or electronic through; control of access to records, control of change authority, control of audit trail, and control of record retention.

8.04 The Company uses a Two-Way Automatic Communication System (TWACS) based AMI system that provides daily reads. Processes have been established to notify personnel of non-communicating meters that may have been tampered with. Upon notification of a non-communicating meter, an order for a field employee to perform an investigation is created.

8.05 Meter proeramming password protection will be maintained in accordance with the Company's Data Security Policy.

8.06 Meter Data Systems will be maintained in accordance with the Company's Data and Cvber Security Policy.

9.0 Revenue Protection The following measures are used by the Company to ensure revenue validation:

9.01 Energy Consumption Investigations The Company will maintain "High/Low" thresholds on each account triggering consumption investigation and/or manual override.

9.02 Energy Diversion Program and Enforcement a) The Company will maintain a training program covering detecting, reporting and disposition

of Energy Diversion. b) The Company will maintain documented procedures for reporting and disposition of Energy

Diversion. c) The Company will maintain a system of recording and reporting of Energy Diversion.

9.03 Primary Service Level Delivery Rate Metering Evaluation a) Meters will be interrogated and information downloaded often enough to minimize risk of lost

data. b) Meter data will be validated for each billing period. Validation shall include; outages, missing

intervals, peak consumption, power factor and historic use comparison. c) Site Sight-visits and validations will be accomplished at least annually every six months. A

site that has not been validated in six months will trigger an automated report that is used to

Page 31: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

ensure that validations occur annually at a minimum. Visits will incorporate an inspection and verification of the metering system.

d) Revenue meters utilizing MV90 communication are verified in the field within one business day if reading errors are detected or daily communication fails.

9.03 Other Revenue Protection Measures

a) The Company has established Sarbanes Oxley (SOX) controls specific to metering that provide revenue protection. Controls are reviewed and certified quarterly to ensure they have not failed.

b) Voltage readings on AM I three phase meters are taken daily. Any site with a phase voltage below 100VAC will show up on an automated report that is used to generate outage notifications.

c) Transformer-rated irrigation monthly billing usage is compared to the connected horse power and validation notes for the site. Deviations from expected load to true load result in the creation of an order fora service investigation.

d) The Company has an effective training program for field and billing personnel to detect abnormal usage amounts. The CR&B database has automated triggers for abnormal usage on all customers and meters billed through MV90 have their current usage compared to their historic usage at each billing period.

10.0 Corrective Action

10.01 The test results from Sample Testing will be analyzed and reported annually. The weighted average values of the as found test results (method 1 of ANSI C12.1-2014) will be used to determine whether the HMG exceeds the Threshold Criteria.

10.02 If the threshold criteria is exceeded fora HMG, the Company will follow one of the prescribed methods in ANSI C12.1-2014 section 5.0.3.4.4. Any discovered problems with quality or accuracy will be acted upon immediately by performing one or a combination of the following:

• Rejecting nonconforming new meter purchases and working with manufacturer for resolution

• Implementing an accelerated testingprogram • Splitting meter groups into two or more subgroups • Implementinga retirement plan

Corrective Action Plans will be documented and submitted to the Oregon Public Utilities Commission in the annual Meter Test and Inspection report. The plan shall address corrective action measures. costs. schedules. and impacts to customers and revenue. In the event that a HMG. as part of In-Service Meter Testing, fails for a second time, the HMG shall be removed from service within four years.

follow-ing-pfeeess-..411-be-implementeel-as-a-min-imum-aetion:

a) The inpany-v.411-establ4sh-a foeused-perfoonanee-evaluation-on-the "failed" Homogeneous Meter Group-to-determ-Me-the-scope-and-root-eause-of.the-nonconformenee-.

b) The Sample-Testing-process-forthe-failed -lomegeneous-Meter-Gfoup-will-be-pefformedfor next calendar year.

e)-1f--the-Homogeneous-MeteW&Foup-falls-inte.the-Aet-ion-GfiteFia-rthe.company-wi-ll integrate the-fersolts-w-ilb-the-previous-year-s-Sample-Testing results-anclestablish-o-fteused-perfonnanee evaluat4on-to-detefinine-the-scope-am4-4-Ttot-cuuse-of-the-noncon-formance. The-Company wi-11-deolaFe4he-I-lornogeneous-Meter-Gfoup-or-subgroup.as-an-Obsolete Meter Group-based off4be-Aeion-Gritepia-an.d fealsed-nerkmanee-evaktation-results,

4)--The--Sample-Testing process for-the-ulailed temogenemm-lvietep-GFoup-v.414 he performed for--nem-ea4endor-year,

Page 32: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

e) The Comp ill b, ttly-P1-estabtish-R rent Program and schedu l.. f r completion of

the-Retirement-Program for-the-ObsoIete-Meter-Cwoup-or-subgroup, and shall report the schedule to the Commission-as-required-:

I) The Retifement-Progrartt-lirr-the-Obsolete-l'yleter-Greup-or-subgroup-w4-1-eommenee4n-the following year.

g)- Sample Testing of the Obsolete 4eter@onp-an4kr subgroup will continue, the results of fu-rther Sample Testing may-be-used-as-a-basis-te-adjust-the-R-eti

h) The-statos-of the Retittement-Program will-be-ineluded4-the-Annual-Metering-Cei44eation Report-to-the-appl-ieable-Publie-14tility-C--01-11-M-iFsion-as-requ-ired,

11.0 Record Keeping

11.01 Records will be maintained for all laboratory and field test standards by serial number. Records will be maintained for the life of the equipment plus five years.

11.02 Test records will be maintained for all meters and auxiliary transformers for the life of the equipment plus two one years.

11.02 Inspection and verification records are maintained for primary delivery rate customer's accounts for three years.

11.03 Ad*Onents--terneterswill-be-followed by a test and-reeord-ing-of the test-tesalts-en-the device record.

11.04 All energy diversion investigations will be recorded and the records will be maintained for three years.

11.05 Meter and instrument transformer test records will identify; type, serial number, manufacturer, purchase date, test date. test reason code, action taken, test results, and location of test.

12.0 Meter Quality System Management

12.01 Internal Audit a) The Company will schedule and conduct audits of the Meter Quality System to determine the

extent of compliance with regulatory requirements for metering and for effectiveness of policies, internal standards and procedures.

b) The Company will conduct audits of the effectiveness of corrective and preventative action plans implemented as a result of nonconformance with regulatory or Meter Quality System requirements.

12.02 Annual Meter Management Review a) Management will review the results of internal audits and develop corrective and preventative

action plans for any nonconformity to regulatory and/or Meter Quality System requirements. b) Management will review the effectiveness of the Meter Quality System and develop action

plans for continuous quality improvement. c) The Company will review the currency of this Meter Test Policy annually to ensure that it is

up to date with national and state regulations, standards. and guidelines.

Page 33: BEFORE THE PUBLIC UTILITY COMMISSION · 6 ANSI Z1.4-2003 (R2018), Sampling Procedures and Tables for Inspection. Page 5 - APPLICATION OF IDAHO POWER COMPANY FOR APPROVAL OF ITS METER

13.0 Annual Report and Certification to the OPUC Repoptiag-Req-u4renteats The-an-nual-repoi4 a) An Exceati-ye-Summary-ineludit-tg-Management-Rey-iew10—A-Reporting-en-StatisticelArtalysis c) De fi eie,neies- Found-aad-C-erreetive-Aetions el-)--t*speet-ions-and-Test-s-Gompleted4n-Previous-Year e)—hispeetions-and-Tests-Planfied-foGurrent-Year 0 The Numberof-Qualified-Persoanel g)—A-Summary-of-C-hanges-knplemented-or--Planned h3 Meter-Grettp-L-istin-gs-foEkllvIGs-and-PMGs 4-)—U-rtiquely-Defeetive-Meters j) Me jer-14efeets-foEP-M65

.14ontonforrnanee-Revenee--1-mptieations

a) The Company will complete annually a teetering certification report to the Commission as required by the Oregon Public Utility Commission Electric Utility Metering Policy.

11) The report will contain the information required in Section S of the Oregon Public Utility Commission Electric Utility Metering Policy for the entire company and for Oregon only,