www.intermountainenergy partners.com 1109 Main St. #420 Boise, ID 83702 O: 208.342.4836 LOCATION DRAWN BY: LCC DATE: 5-14-15 CHECKED BY: CC DATE: 5-14-15 BECKER SOLAR LLC 45°39'14.34"N 118°56'46.31"W 27 59 81 51 51N TAP LINE 22kV MCOV REV METER RTU SUPV INTERTIE BKR TRIP CTRL/STAT BREAKER STATUS ALARMS TELEMETERING DEV FUNCTION 27 UNDER VOLTAGE 50/51N INST & TD OC GROUND 59 OVER VOLTAGE 81 UNDER/OVER FREQ 50/51 INST & TIME OC 38KV PAD MOUNT SWITCHGEAR 600A, 12.5kA SYM AC, 150kV BIL #1/0 35kV MV-105 VFI M 3 PT’S 3 INVERTER 2.2 MVA ADJ +/- 995.79KVAR, 0.9PF 3300AMPS @ 385VAC (TYP. 5) TO RTU #1/0 AWG 35kV MV-105 TO PV ARRAY NOTES 1. SUFFICIENT FAULT CURRENT RATING OF SWITCHGEAR TO BE VERIFIED. 2. OPEN AIR BREAKERS MAY BE USED IN LIEU OF SWITCHGEAR IN THE FINAL DESIGN. (3) 175:1 150KV BIL (3) 600:5 CT STEP UP TRANSFORMER .385/34.5KV 2.2MVA (TYP. 5) 22kV MCOV

Upload: luke-coleman

Post on 18-Jan-2017

48 views

Category:

Documents


0 download

TRANSCRIPT

  www.intermountainenergy partners.com   1109 Main St. #420   Boise, ID 83702   O: 208.342.4836

LOCATION

DRAWN BY: LCC DATE: 5-14-15CHECKED BY: CC DATE: 5-14-15

BECKERSOLAR LLC

45°39'14.34"N118°56'46.31"W

27 59 81

51 51N

TAP LINE

22kV MCOV

REV METERRTU SUPV

INTERTIE BKR TRIP CTRL/STAT BREAKER STATUS ALARMS TELEMETERING

DEV FUNCTION 27 UNDER VOLTAGE 50/51N INST & TD OC GROUND 59 OVER VOLTAGE 81 UNDER/OVER FREQ 50/51 INST & TIME OC

38KV PAD MOUNT SWITCHGEAR 600A, 12.5kA SYM AC, 150kV BIL

#1/0 35kV MV-105

VFI

M

3 PT’S

3

INVERTER 2.2 MVA ADJ +/- 995.79KVAR, 0.9PF 3300AMPS @ 385VAC (TYP. 5)

TO RTU

#1/0 AWG 35kV MV-105

TO PV ARRAY

NOTES

1. SUFFICIENT FAULT CURRENT RATING OF SWITCHGEAR TO BE VERIFIED.

2. OPEN AIR BREAKERS MAY BE USED IN LIEU OF SWITCHGEAR IN THE FINAL DESIGN.

(3) 175:1 150KV BIL

(3) 600:5 CT

STEP UP TRANSFORMER .385/34.5KV 2.2MVA (TYP. 5)

22kV M

COV