bearing protection rings - trane supply · 2020. 7. 5. · to installing the aegis® bearing...
TRANSCRIPT
BEARING PROTECTION RINGS
AEGIS® Split uKITFeatures• Fits over slingers, seals and shaft shoulders
• Split Ring can be installed without detaching attached equipment
• 4 different brackets included
• Circumferential Conductive MicroFiber rows in Fiberlock™ Channel
• Optional mounting with AEGIS Conductive Epoxy (PN EP2400). Sold separately
Trane PN Split Ring uKITS Motor Shaft Diameter NEMA Frame Sizes
RNG02467 SGR-0.625-UKIT-1A4 0.625” 56
RNG02468 SGR-0.875-UKIT-1A4 0.875” 56HZ, 143T, 145T
RNG02469 SGR-1.125-UKIT-1A4 1.125” 182T, 184T
RNG02470 SGR-1.375-UKIT-1A4 1.375” 213T, 215T
RNG02471 SGR-1.625-UKIT-1A4 1.625” 254T, 256T, 284TS, 286TS
RNG02472 SGR-1.875-UKIT-1A4 1.875” 284T, 286T, 324TS, 326TS, 364TS, 365TS
RNG02473 SGR-2.125-UKIT-1A4 2.125” 324T, 326T, 404TS, 405TS
RNG02474 SGR-2.375-UKIT-1A4 2.375” 364T, 365T, 444TS, 445TS, 447TS, 449TS
RNG02475 SGR-2.875-UKIT-1A4 2.875” 404T, 405T
RNG02476 SGR-3.375-UKIT-1A4 3.375” 444T, 445T, 447T, 449T
RNG02477 SGR-3.625-UKIT-1A4 3.625”
RNG02478 SGR-3.875-UKIT-1A4 3.875”
RNG02479 SGR-4.375-UKIT-1A4 4.375”
RNG02480 SGR-4.875-UKIT-1A4 4.875”
2
Trane PN Solid uKITs Motor Shaft Diameter NEMA Frame Sizes
RNG02453 SGR-0.625-UKIT 0.625” 56
RNG02454 SGR-0.875-UKIT 0.875” 56HZ, 143T, 145T
RNG02455 SGR-1.125-UKIT 1.125” 182T, 184T
RNG02456 SGR-1.375-UKIT 1.375” 213T, 215T
RNG02457 SGR-1.625-UKIT 1.625” 254T, 256T, 284TS, 286TS
RNG02458 SGR-1.875-UKIT 1.875” 284T, 286T, 324TS, 326TS, 364TS, 365TS
RNG02459 SGR-2.125-UKIT 2.125” 324T, 326T, 404TS, 405TS
RNG02460 SGR-2.375-UKIT 2.375” 364T, 365T, 444TS, 445TS, 447TS, 449TS
RNG02461 SGR-2.875-UKIT 2.875” 404T, 405T
RNG02462 SGR-3.375-UKIT 3.375” 444T, 445T, 447T, 449T
RNG02463 SGR-3.625-UKIT 3.625”
RNG02464 SGR-3.875-UKIT 3.875”
RNG02465 SGR-4.375-UKIT 4.375”
RNG02466 SGR-4.875-UKIT 4.875”
AEGIS® Solid uKITFeatures• Fits over slingers, seals and shaft shoulders
• 4 different brackets included
• Circumferential Conductive MicroFiber rows in Fiberlock™ Channel
• Optional mounting with AEGIS Conductive Epoxy (PN EP2400). Sold separately
3
AEGIS® HFGSHigh Frequency Ground Strap
12” HFGS AEGIS PN Terminations NEMA Frame
HFGS-T0410-R0312-12
Term 1: Punched hole 0.41”Term 2: Ring terminal for 5/16” screws
48, 48H, 56, 56H, 143T, 145T, 182T, 184T, 213T, 215T
HFGS-T0660-R0312-12
Term 1: Punched hole 0.66”Term 2: Ring terminal for 5/16” screws
254T, 256T, 284T, 284TS, 286T, 286TS, 324T, 324TS, 326T, 326TS, 364T, 364TS, 365T, 365TS
HFGS-T0940-R0312-12
Term 1: Punched hole 0.94”Term 2: Ring terminal for 5/16” screws
404T, 404TS, 405T, 405TS, 444T, 444TS, 445T, 445TS, 447T, 447TS, 449T, 449TS
HFGS-R0312-R0312-12
Term 1: Ring terminal for 5/16” screwsTerm 2: Ring terminal for 5/16” screws
Universal terminations
24” HFGS AEGIS PN Terminations NEMA Frame
HFGS-T0410-R0312-24
Term 1: Punched hole 0.41”Term 2: Ring terminal for 5/16” screws
48, 48H, 56, 56H, 143T, 145T, 182T, 184T, 213T, 215T
HFGS-T0660-R0312-24
Term 1: Punched hole 0.66”Term 2: Ring terminal for 5/16” screws
254T, 256T, 284T, 284TS, 286T, 286TS, 324T, 324TS, 326T, 326TS, 364T, 364TS, 365T, 365TS
HFGS-T0940-R0312-24
Term 1: Punched hole 0.94”Term 2: Ring terminal for 5/16” screws
404T, 404TS, 405T, 405TS, 444T, 444TS, 445T, 445TS, 447T, 447TS, 449T, 449TS
HFGS-R0312-R0312-24
Term 1: Ring terminal for 5/16” screwsTerm 2: Ring terminal for 5/16” screws
Universal terminations
Trane PN AEGIS PN
CS015 CS015
Coverage: 20-25 applications based on a 3” [76mm] shaft diameter
Used to improve the conductivity of the steel shaft surface. Apply to any VFD driven motor shaft prior to installing the AEGIS® Bearing Protection Ring.
Shelf life is 6 months. GHS SDS available at www.est-aegis.com
Trane PN AEGIS PN
TOL04956 EP2400
Coverage: 2-3 applications
Used to install the AEGIS® Bearing Protection Ring without drilling and tapping into the motor end bell.
Shelf life is 9 months. GHS SDS available at www.est-aegis.com
AEGIS® Conductive Epoxy AEGIS® Colloidal Silver Shaft Coating
4
AEGIS® Shaft Voltage Tester™
AEGIS PN
SVP-KIT-9100MB3 SVP tips, probe holder with two piece extension rod (total length of probe holder with extension rod is 18 inches), AEGIS® Grounding Simulator with alligator ground clip, and magnetic base.
AEGIS-SVP-510AEGIS® Shaft Voltage Probe™ PP510 with BNC connector.1 AEGIS® SVP Tip1 alligator ground clip
SVP-TIP-9100 3 SVP replacement tips only
BAT-9100 Spare/replacement battery
The AEGIS® Shaft Voltage Tester™ kit includes everything you need to start testing motor shaft voltages. At its core is a 2 channel, 100 MHz digital oscilloscope with a 5.7” screen and easy screen capture.
SVP-KIT-9100MB
AEGIS-SVP-510
AEGIS PN AEGIS-OSC-9100 A AEGIS-OSC-9100- W2 AEGIS-OSC-9100 MB - W2 AEGIS-OSC-9100 MB - W2-ICAEGIS® Shaft Voltage Tester™ Digital Oscilloscope
AEGIS® Shaft Voltage Probe™ with Tip InstalledSpare 1X/10X Oscilloscope Probe
USB Probe Calibration Dongle
Multimeter Test Leads
Rechargeable/replaceable Battery
Power Supply (9V, 4A DC; 120/240 VAC)
Compact Carrying Case
USB Flash drive, loaded with manual
AEGIS® Bearing Protection Handbook
Alligator Grounding Clips 1 1 2 2
Spare AEGIS® Shaft Voltage Probe™ Tips 3 3
AEGIS® Shaft Grounding Simulator™
Probe Holder
Magnetic Base
Universal Power Adapter
ISO 17025 Calibration
Warranty Length 90 days 2 years 2 years 2 years
5
AEGIS® uKITs for NEMA motors include: • AEGIS® SGR Bearing Protection Ring (1) • Brackets (4) each of 4 styles –
16 brackets total • 5-40 x 3/8” flat head screws (4) • 6-32 x 3/8” socket head cap screws (4) • #6 split lock washers (4) • #6 flat washers (4) • 5/64” and 7/64” allen wrench
AEGIS® uKIT Brackets
120.0°Typ (3X)
MaximumBolt Circle
MinimumBolt Circle
90°Typ (4X)
SOLID RING ONLYMotor with 3 hole
bracket pattern
Tools for Bolt on Installation: • #36 drill and #6-32 tap • Fine grit emery cloth/sand paper
SOLID AND SPLIT RING Motor with 4 hole bracket pattern
Shaft Min Circle Max Circle0.625” 2.400” 3.200”0.875” 2.650” 3.450”1.125” 2.900” 3.700”1.375” 3.150” 3.950”1.625” 3.400” 4.200”1.875” 3.650” 4.450”2.125” 3.900” 4.700”2.375” 4.150” 4.950”2.875” 4.650” 5.450”3.375” 5.150” 5.950”3.625" 5.400" 6.200"3.875" 5.650" 6.450"4.375" 6.150" 6.950"4.875" 6.650" 7.450"
Mounting bolt circle is the same for 3 or 4 brackets
MotorEndBracket
Shaft Shoulder
.375 ±.010
.1875 ±.010
Shaft
Slinger / Seal
Max Slinger/Seal ODOr Casting Boss =Shaft Ø + 1.0"
Max ShaftShoulder ØShaft Ø + .500"
(.695)
Shaft Min Circle Max Circle0.625” 3.700" 5.375"0.875” 3.950" 5.625"1.125” 4.200" 5.875"1.375” 4.450" 6.125"1.625” 4.700" 6.375"1.875” 4.950" 6.625"2.125” 5.200" 6.875"2.375” 5.450" 7.125"2.875” 5.950" 7.625"3.375” 6.450" 8.125"3.625" 6.700" 8.375"3.875" 6.950" 8.625"4.375" 7.450" 9.125"4.875" 7.950" 9.625"
MotorEndBracket
1.135 ±.010
1.260 ±.010
(1.555)
Max Shaft Shoulder ØShaft Ø + .500”
Max Slinger/Seal ODOr Casting Boss =Shaft Ø + 2.325"
Shaft
Shaft Shoulder
Slinger / Seal
Shaft Min Circle Max Circle0.625” 4.575" 5.375"0.875” 4.825" 5.625"1.125” 5.075" 5.875"1.375” 5.325" 6.125"1.625” 5.575" 6.375"1.875” 5.825" 6.625"2.125” 6.075" 6.875"2.375” 6.325" 7.125"2.875” 6.825" 7.625"3.375” 7.325" 8.125"3.625" 7.575" 8.375"3.875" 7.825" 8.625"4.375" 8.325" 9.125"4.875" 8.825" 9.625"
MotorEndBracket
1.135 ±.0101.260 ±.010
(1.555)
Max Shaft Shoulder ØShaft Ø + .500”
Max Slinger/Seal ODOr Casting Boss =Shaft Ø + 3.200"
Shaft
Shaft Shoulder
Slinger / Seal
Installing AEGIS® uKITs
Tools for Conductive Epoxy Installation: • EP2400 AEGIS® Conductive Epoxy • Dremel tool to remove paint from motor end bell • Heat gun to speed curing of conductive epoxy
AEGIS® CS015 Colloidal Silver Shaft Coating is recommended for all installations.
6
Shaft Min Circle Max Circle0.625” 2.450" 4.325"0.875” 2.700" 4.575"1.125” 2.950" 4.825"1.375” 3.200" 5.075"1.625” 3.450" 5.325"1.875” 3.700" 5.575"2.125” 3.950" 5.825"2.375” 4.200" 6.075"2.875” 4.700" 6.575"3.375” 5.200" 7.075"3.625" 5.450" 7.325"3.875" 5.700" 7.575"4.375" 6.200" 8.075"4.875" 6.700" 8.575"
.120 ±.010
(.445)
Shaft
Shaft Shoulder
MotorEndBracket
Max Shaft Shoulder/Slinger/Seal ODOr Casting Boss =Shaft Ø +.500"
Shaft Min Circle Max Circle0.625” 3.700" 5.375"0.875” 3.950" 5.625"1.125” 4.200" 5.875"1.375” 4.450" 6.125"1.625” 4.700" 6.375"1.875” 4.950" 6.625"2.125” 5.200" 6.875"2.375” 5.450" 7.125"2.875” 5.950" 7.625"3.375” 6.450" 8.125"3.625" 6.700" 8.375"3.875" 6.950" 8.625"4.375" 7.450" 9.125"4.875" 7.950" 9.625"
(1.080)
.635 ±.010
.760 ±.010
Max Shaft Shoulder Ø+ Shaft Ø + .500”
Slinger / Seal
Shaft Shoulder
Shaft
MotorEndBracket
Max Slinger/Seal ODOr Casting Boss =Shaft Ø + 2.325"
Shaft Min Circle Max Circle0.625” 4.575" 5.375"0.875” 4.825" 5.625"1.125” 5.075" 5.875"1.375” 5.325" 6.125"1.625” 5.575" 6.375"1.875” 5.825" 6.625"2.125” 6.075" 6.875"2.375” 6.325" 7.125"2.875” 6.825" 7.625"3.375” 7.325" 8.125"3.625" 7.575" 8.375"3.875" 7.825" 8.625"4.375" 8.325" 9.125"4.875" 8.825" 9.625"
(1.080)
.760 ±.010.635 ±.010
Max Shaft Shoulder ØShaft + .500”
Shaft
Shaft Shoulder
Slinger / Seal
MotorEndBracket
Max Slinger/Seal ODOr Casting Boss =Shaft Ø + 3.200"
Installation using Screws
• Drill (3 or 4) holes using a #36 drill. Avoid drilling into bearing.
• Depth of hole should be 1/4”
• Tap each hole with a #6-32 tap
• Install the uKIT and secure to the motor with the hardware provided. The bolts provide the path to ground. Do not use Loctite© or any other non-conductive material to secure the screws.
Installation using Conductive Epoxy (EP2400)
• Remove paint on the motor end bell where the AEGIS® uKIT brackets will be attached. These areas must be clean and free of any coatings, paint, or other nonconductive material.
• Prepare conductive epoxy per package directions.
• Apply the epoxy to the mounting brackets.
• Install the uKIT. Hold the uKIT in place until epoxy is firmly holding. Allow epoxy to cure for 4 hours at or above 75°F. For quickest curing time, use a heat gun to heat epoxy to 150-250° for 10 minutes then allow to cool.
Preparation • Shaft must be clean
and free of any paint, coatings, or other nonconductive material.
• AEGIS® Rings should not operate over a keyway. Fill keyway with a fast-curing epoxy putty (such as Devcon epoxy putty) in the area of contact.
• To increase conductivity of the shaft, apply AEGIS® Colloidal Silver Shaft Coating to the area where the AEGIS® microfibers will be in contact with the motor shaft. Apply all around the shaft.
• Select bracket size based on the clearance needed from the end bell/slinger/shaft shoulder. For solid ring, use either a 3-hole or 4-hole bracket pattern. For split ring use 4 brackets. Attach brackets to the AEGIS® ring using the 5-40 x 3/8” flat head screws.
• Install the AEGIS® uKIT so that the aluminum ring maintains an even clearance around the shaft. Conductive microfibers should be in contact with the conductive metal surface of the shaft. Mark bracket locations.
Wrong Right
7
AEGIS® Electrical Bearing Damage ProtectionAEGIS® uKITs combine an AEGIS® Shaft Grounding Ring and universal mounting brackets, allowing external mounting of the ring on any motor — even those with shaft shoulders, slingers, seals, or other end bell protrusions. AEGIS® uKITs include:
• AEGIS® Rings sized for NEMA frame motor shaft diameters (NEMA “u” dimension) from 56 to 449T
• Solid and split ring designs • Mounting brackets and hardware for installation of the AEGIS®
Ring on virtually any end bell • Brackets can be mounted with screws or AEGIS® Conductive
Epoxy Adhesive (Epoxy EP2400 sold separately)
SolutionAEGIS® Bearing Protection Rings protect motors by channeling harmful VFD-induced shaft voltages away from bearings and safely to ground, preventing bearing failure and costly unplanned downtime.
ProblemWithout AEGIS® Bearing Protection, induced shaft voltages can cause bearing pitting, frosting, and fluting, dramatically reduce the effectiveness of lubrication, and lead to catastrophic bearing failure.
Form 272-1 5/2017
Motors up to and including 100 HP (75 kW) Low Voltage
Motors Greater than 100 HP (75 kW)
Download the AEGIS® Best Practices Handbook: www.est-aegis.com/handbook
Stator
RotorShaft
Earth Ground
VFDDrivenEquipment
AEGIS® SGR-internal or external (shown) installation
AEGIS® CS015
AEGIS® HF Ground Strap
Stator
RotorShaft
VFDDrivenEquipment
Sleeve
InsulatedBearing
Earth Ground
AEGIS® SGR-internal (shown)
or external installation
AEGIS® HF Ground Strap
AEGIS® CS015
• Install AEGIS® Bearing Protection Ring – either internally or externally – on drive end or the non-drive end of motor. Use AEGIS® Colloidal Silver Shaft Coating (PN CS015) on motor shaft where fibers touch.
Product recommendation: AEGIS® SGR
• Drive End: Install AEGIS® Bearing Protection Ring - Internally on the back of the bearing cap or externally on the motor end bracket. Use AEGIS® Colloidal Silver Shaft Coating on motor shaft.
• Non-Drive End: Isolate bearing housing with insulated sleeve or coating or use insulated ceramic or hybrid bearing to disrupt circulating currents.
Product recommendation: LV Motors up to 500HP: AEGIS® SGRLV Motors over 500HP: AEGIS® PRO SeriesMV Motors: AEGIS® PRO Series