BCI joist hanger. - Backer block. Nail with 10- 10d nails. Filler block. Nail with 10- 10d nails. Backer block required where hanger load exceeds 1000 Ibs. Samples from www.AutoCADDetails.net

Upload: others

Post on 13-Jul-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

BCI joisthanger. -

Backer block.Nail with 10­

~ 10d nails.

Filler block.Nail with 10­10d nails.

Backer block required wherehanger load exceeds 1000 Ibs.

Samples from

www.AutoCADDetails.net

Page 2: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Backer forhorizonal /siding or stucco. ---

Samples from

www.AutoCADDetails.net

Page 3: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

BCI joisthanger. ~

Backer block.Nail with 8­10d nials.

Requires backer block wherehanger load exceeds 1000 Ibs.

Samples from

www.AutoCADDetails.net

Page 4: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Moisture barrier.

Mud Sill -~Stem Wall

Beam As~Required

o

\- Clip angle.

Samples from

www.AutoCADDetails.net

Page 5: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Do not bevel cutVERSA-LAM beyondinside face of wall ----~

Samples from

www.AutoCADDetails.net

Page 6: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

2x-beveled plate for slopegreater than 1/4 -1/12. For slopegreater than 4/12 additionalconnectors maybe required.

Simpson VPI connector or equal canbe used in lieu of beveled plate forslopes from 1/12 to 6/12.

Samples from

www.AutoCADDetails.net

Page 7: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

BCI blocking,--------

centered at cut.

and web after installation.~

Field cut BCI top flange.

Samples from

www.AutoCADDetails.net

Page 8: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Web stiffener required

each side for 14" anddeeper BCI joist only. ---

2x4 blocking -~

for soffit support.

Samples from

www.AutoCADDetails.net

Page 9: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Note: Check with local buildingofficials for use of this detail inareas of high lateral forces.

3/4" (48/24)sheathingrim joist.

'-------- 2x-block

\

1

/

1/16"

Samples from

www.AutoCADDetails.net

Page 10: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Load bearing wall above(stacked over wall below.) ----~

'- 2x-block

\1/16"

Samples from

www.AutoCADDetails.net

Page 11: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

~ Use same boltvalues asDouglasFir-Larch.

'------- Drilling permitted

for standardconnections.

Samples from

www.AutoCADDetails.net

Page 12: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Do not bevel cutjoist beyond insideface of wall. ---------1

Samples from

www.AutoCADDetails.net

Page 13: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Simpson MSTI 36with 10-1 Od. ~--~~--~~-~-~~--

-====-'-===-~~---.~~-

-~----~

I

~-~~~~--~- VERSA-LAMLVL support/

I

beam.Double beveled -~~~-~~~-~,

wood plate.

Samples from

www.AutoCADDetails.net

Page 14: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

VERSA-LAMLVL support

beam.~

Requires SimpsonMSTI 36 strap with

10-10d whereslope exceeds

7/12.

~ Beveled webstiffener eachside.

~ Simpson LSUIhanger or

equal.

Samples from

www.AutoCADDetails.net

Page 15: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Load bearing wall above(stacked over wall below.) ---~

'--------- BCI joist

blocking.

Samples from

www.AutoCADDetails.net

Page 16: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

2x--plate flush with inside ---face of wall or beam.

BCI Joist blocking

BCI joist hanger

Samples from

www.AutoCADDetails.net

Page 17: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Closure.

BCIjoistblocking. --------'

Samples from

www.AutoCADDetails.net

Page 18: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

BCI joist blocking withend blocks. spaced @32" o.c. ---~

Nail BCI joist bl.ocking --~to wall plate usmg4-10d nails. Rim­

joist.

'-------- Simpson strap tieFHA12 or continuoussheathing top andbottom.

Samples from

www.AutoCADDetails.net

Page 19: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

~ Closure.

····~-BCI

joist

blocking.

Samples from

www.AutoCADDetails.net

Page 20: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

~- BCI Joist blocking.

~- BCI joist hanger.

2x--plate flush with inside~--

face of wall or beam.

Samples from

www.AutoCADDetails.net

Page 21: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

BCI joist ­hanger.

'-------- VERSA-LAMLVL beam.

Samples from

www.AutoCADDetails.net

Page 22: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

BCI joisthanger. -,

'-------- VERSA-LAMLVL beam.

Samples from

www.AutoCADDetails.net

Page 23: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Hanger. -

Samples from

www.AutoCADDetails.net

Page 24: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

4

2x--plate flush with inside~-

face of wall or beam.

"-------- BCI joist hanger

Samples from

www.AutoCADDetails.net

Page 25: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

BCI joist---------ha.nger.

'- VERSA-LAMLVL beam.

Note:

Web stiffeners are required where

sides of the hanger do not extend

up to support the top flange laterally.

Samples from

www.AutoCADDetails.net

Page 26: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

~- BCI Joist

~ BCI joist hanger.

2x--plate flush with inside face'---------

of wall or beam.

Samples from

www.AutoCADDetails.net

Page 27: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

/- Tie joists togetherwith 3/4" plywood @floor level change.

Samples from

www.AutoCADDetails.net

Page 28: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

2x--plate flush with inside~-

face of wall or beam.

Sheathing will provide lateral supportneeded without blocking.

Samples from

www.AutoCADDetails.net

Page 29: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Load bearing wall above -----------,

~BCI

rim joist.

Notes: BCI floor joist must be designed

to carry wall above when not stackedover wall below.

Samples from

www.AutoCADDetails.net

Page 30: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

2x- nailed to the side of the BCI joist with wood backer.Nail through the BCI joist and backer intothe 2x- with 2 rows 10d nails at 6" o.c.and clinch.

3 1/2" min.bearing.

WOOd~backer

3 times

cantilever length

I11/2times

cantileverlength

--BCljoist

blocking.

Uniformloads only

Cantilever

length

I~SECTION

Samples from

www.AutoCADDetails.net

Page 31: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

..~- Kneewall w/sheathing.

Kneewall must matchjoist height.

Samples from

www.AutoCADDetails.net

Page 32: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

~-- Kneewall w/sheathing.

Kneewall must matchjoist height.

Samples from

www.AutoCADDetails.net

Page 33: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Load bearing wall above ---~(stacked over wall below.)

~- BCI joistblocking.

Samples from

www.AutoCADDetails.net

Page 34: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

'----- 2x_ Ledger

Toe nail to wall plate using 16d at 12" o.c.or 10d @ 6" o.c. (use 5/6 of lateral nailcapacity.)

Butt sections end toend. Joints should

occur between joists.

Use 5/8" or 3/4"Machine Bolts spacedas required.

Samples from

www.AutoCADDetails.net

Page 35: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

10d nails -,@ 6" o.c.

o

o

o

o

2x4 one side for135 plf max.

2x6 one side for- 240 plf max.

3/4"or 1"backerblock~

o

o

o

o

o

2x post

Samples from

www.AutoCADDetails.net

Page 36: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Webstiffener

~---~_. --~~=-~---~~~~--~~--===>-~----=::::---====--~- -.-

'~-~~ 2-10d I

nails. I

2x support @ BCI 45 ~~~~,

3x support @ BCI 60

Samples from

www.AutoCADDetails.net

Page 37: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

NON-LOAD BEARING CANTILEVER DETAIL

BCI joist should be protected from the weather.

lengthCantilever length

r1--~

t><:I

BCljoist -"" Uniformblocking. loads only

I

~ ~

~ ~

3 times Cantilever.

Samples from

www.AutoCADDetails.net

Page 38: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

2x-outrigger -~Notch aroundflange. ~ BCI joist

'------- End waII

Samples from

www.AutoCADDetails.net

Page 39: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

~- 2x- plate flush with insideface of wall or beam.

<

'--------- BCI joist hanger.

Samples from

www.AutoCADDetails.net

Page 40: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

2x--plate flush with inside face,-----------

of wall or beam

L--_ BCI Joist Hanger

Samples from

www.AutoCADDetails.net

Page 41: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

NOTE:

Web stiffener required---~

each side with 18" anddeeper joists.

PLYWOOD REINFORCEMENT

3/4" plywood--~

closure

DETAIL

- Backer

block

3/4"x48" COX plywood reinforcement or other 3/4" APA 48/24 ratedsheathing must match the full depth of the BCI joist. Nail to theBCI joist with 8d nails at 6" o.c. and nail with 4-8d nailsinto backer block. When reinforcing both sides, staggernails to avoid splitting. Install with face grain horizontal.

Samples from

www.AutoCADDetails.net

Page 42: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Web stiffener attachment for18" and 20" depth.

2" min.4" max.

Small gap 1/8" min.2" max.

20" requires3-8d nails,clinch.

18" requires2-8d nails,clinch.

~ Tight fit.

Plywood web stiffener:5/16"

1" x 2 minimum.

/2" min.4" max.

Samples from

www.AutoCADDetails.net

Page 43: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

4000 pounds per footVertical Load Capacity

Rim Board Attachment

Samples from

www.AutoCADDetails.net

Page 44: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Two layers 3/4" (48/24)(48/24) sheathing rimjoist. (Staggered joints). -------,

For first storyof secondstory application.

Where a plywood rim is used, bracing complyingwith code must be carried to the foundation,or BCI joist solid blocking used a minimun of41 every 251 of bearing wall length.

Samples from

www.AutoCADDetails.net

Page 45: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

~BCI

rim joist.

Note:Minimum 2x6 bearing plate requiredif used with 60 series joist.

Samples from

www.AutoCADDetails.net

Page 46: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

3/4 11 (48/24)sheathingrim joist.

For single storyapplication, or secondstory of two storyapplication.

Where a plywood rim is used, bracing complyingwith code must be carried to the foundation,or BCI joist solid blocking used a minimun of41 every 251 of bearing wall length.

Samples from

www.AutoCADDetails.net

Page 47: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Sloped~seat cut.

Samples from

www.AutoCADDetails.net

Page 48: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

~ Solid block allposts from aboveto bearing below

Samples from

www.AutoCADDetails.net

Page 49: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

'-------- Sol id block allposts from aboveto bearing below

Samples from

www.AutoCADDetails.net

Page 50: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

o

o

o

t

o

o

r--- Strap per code iftop plate is notcontinuous over

header.o

'-------- Trimmers .

Samples from

www.AutoCADDetails.net

Page 51: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Tie strap~

oo

oo

oo

oo

Samples from

www.AutoCADDetails.net

Page 52: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

2x--plate flush with

~- inside face of wall orbeam.

Samples from

www.AutoCADDetails.net

Page 53: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Hanger~

~- Moisture barrier

Wood top plate must be flushwith inside of wall.

Samples from

www.AutoCADDetails.net

Page 54: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

BCI joist ­blocking.

Samples from

www.AutoCADDetails.net

Page 55: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

BCI joisthanger. ~

~VERSA-LAM

LVL beam.

Samples from

www.AutoCADDetails.net

Page 56: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

o

o

'- VERSA-LAMLVL hanger

Samples from

www.AutoCADDetails.net

Page 57: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

4000 pounds per footVertical Load Capacity

Nail Versa-Rim 98to BCI Joists With2-8d nails, one ontop and one at bottom.

Samples from

www.AutoCADDetails.net

Page 58: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

2x-outriggerNotch around

flange.

-- BCI joist

\ -Webstiffeners.

Samples from

www.AutoCADDetails.net

Page 59: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Web stiffener required eachside for 14" and deeperBCI joist only. ---,

Samples from

www.AutoCADDetails.net

Page 60: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

Wood or-~steel column.

o

o~ 0

o

Samples from

www.AutoCADDetails.net

Page 61: BCI Requirement CAD Details · BCI joist hanger. - Backer block. Nail with 10 ~10d nails. Filler block. Nail with 10 10d nails. Backer block required where hanger load exceeds 1000

__--+_-----10

Nin, 0 f 2 II t 0 B0 ltCenter

FSA ANCHOR Fasteners

TO Stud/joist/plate8-10d 1 1/2

TO Foundation2--RFB#4 6 Anchor Bolt

Epo y

oo

oo

o yo

o

FOUNDATION TO FLOOR JOIST(RETROFIT)

Samples from

www.AutoCADDetails.net