bay control rec650 product guide - abb ltd · 52pd pd drp rdre mont. v mmxu meter. iec61850 ansi...

82
Relion ® 650 series Bay control REC650 Product Guide

Upload: others

Post on 03-May-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Relion® 650 series

Bay control REC650Product Guide

Page 2: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Contents

1. 650 series overview..............................................3

2. Application...........................................................3

3. Available functions...............................................6

4. Control................................................................18

5. Current protection..............................................20

6. Voltage protection..............................................22

7. Frequency protection.........................................23

8. Secondary system supervision..........................23

9. Logic...................................................................24

10. Monitoring.........................................................26

11. Metering............................................................28

12. Human Machine interface.................................29

13. Basic IED functions...........................................29

14. Station communication.....................................30

15. Hardware description........................................32

16. Connection diagrams........................................33

17. Technical data...................................................40

18. Ordering............................................................75

Disclaimer

The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumesno responsibility for any errors that may appear in this document.

© Copyright 2011 ABB AB.

All rights reserved.

Trademarks

ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks orregistered trademarks of their respective holders.

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

2 ABB

Page 3: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

1. 650 series overview

The 650 series IEDs provide optimum 'off-the-shelf', ready-to-use solutions. It is configuredwith complete protection functionality anddefault parameters to meet the needs of awide range of applications for generationtransmission and sub-transmission grids.

The 650 series IEDs include:

• Complete ready-made solutions optimizedfor a wide range of applications forgeneration, transmission and sub-transmission grids.

• Support for user-defined names in the locallanguage for signal and functionengineering.

• Minimized parameter setting based ondefault values and ABB's new global basevalue concept. You only need to set thoseparameters specific to your ownapplication, such as the line data.

• GOOSE messaging for horizontalcommunication.

• Extended HMI functionality with 15dynamic three-color-indication LEDs perpage, on up to three pages, andconfigurable push-button shortcuts fordifferent actions.

• Programmable LED text-based labels.• Settable 1A/5A -rated current inputs.

2. Application

REC650 is used for the control, protectionand monitoring of different types of bays inpower networks. The IED is especiallysuitable for applications in control systemswith distributed control IEDs in all bays withhigh demands on reliability. It is intendedmainly for sub-transmission stations. It issuitable for the control of all apparatuses insingle busbar single CB, double busbar singleCB switchgear arrangement.

The control is performed from remote(SCADA/Station) through the communicationbus or from local HMI. Different controlconfigurations can be used, and one controlIED per bay is recommended. Interlockingmodules are available for common types ofswitchgear arrangements. The control isbased on the select before execute principleto give highest possible security. Asynchronism control function is available tointerlock breaker closing. Synchronizingfunction where breaker closes at the rightinstance in asynchronous networks is alsoprovided.

A number of protection functions areavailable for flexibility in use for differentstation types and busbar arrangements. Theauto-reclose includes priority circuits forsingle-breaker arrangements. It co-operateswith the synchrocheck function with high-speed or delayed reclosing.

High set instantaneous phase and earthovercurrent, 4 step directional or non-directional delayed phase and earthovercurrent, thermal overload and two stepunder- and overvoltage functions areexamples of the available functions allowinguser to fulfill any application requirement.

Disturbance recording is available to allowindependent post-fault analysis after primarydisturbances.

Three packages have been defined forfollowing applications:

• Single breaker for single busbar (A01)• Single breaker for double busbar (A02)• Bus coupler for double busbar (A07)

The packages are configured and ready fordirect use. Analog and control circuits havebeen pre-defined. Other signals need to beapplied as required for each application. Themain differences between the packages aboveare the interlocking modules and the numberof apparatuses to control.

The graphical configuration tool ensuressimple and fast testing and commissioning.

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

Revision: -

ABB 3

Page 4: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

REC650-A01 – Single Busbar Single breaker 10AI (4I+1I+5U)

S CSWI

Control

S XCBR

Control

S CSWI

Control

SMB RREC

79 0->1

S CSWI

Control

S CSWI

Control

SMP PTRC

94 1->0

S CSWI

Control

S CSWI

Control

SES RSYN

25 SYNC

TCS SCBR

Cond

TCS SCBR

Cond

SPVN ZBAT

Cond

Other configured functions

S XSWI

Control

S XSWI

Control

S XSWI

Control

S XSWI

Control

S XSWI

Control

OV2 PTOV

59 U>

PH PIOC

50 3I>>

CC RBRF

50BF 3I> BF

V MMXU

Meter.

C MMXU

Meter.

ETP MMTR

Wh<->

QA1

QB1

QB9

QC9

QC2

QC1

EF4 PTOC

51N/67N IN>

Q CBAY

Control

WA1

S CILO

Control

S CILO

Control

S CILO

Control

S CILO

Control

S CILO

Control

S CILO

Control

SEL GGIO

Control

C MSQI

Meter.

V MSQI

Meter.

CV MMXN

Meter.

CC RPLD

52PD PD

DRP RDRE

Mont.

V MMXU

Meter.

IEC61850

ANSI IEC

Function Enabled in Settings

132 kV Bus

1000/1

132kV/110V

132kV/110V

OC4 PTOC

51/67 3I>

IEC09000648-2-en.vsd

S SCBR

Cond

S SIMG

63

DNP

ANSI IEC

Function Disabled in Settings

IEC60870-5-103

ANSI IEC

IEC09000648 V2 EN

Figure 1. A typical protection and control application for a single busbar in single breakerarrangement

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

4 ABB

Page 5: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

REC650-A02 – Double Busbar Single breaker 10AI (4I+1I+5U)

S CSWI

Control

S XCBR

Control

S CSWI

Control

SMB RREC

79 0->1

S CSWI

Control

S CSWI

Control

SMP PTRC

94 1->0

S CSWI

Control

S CSWI

Control

S CSWI

Control

SES RSYN

25 SYNC

TCS SCBR

Cond

TCS SCBR

Cond

SPVN ZBAT

Cond

Other configured functions

S XSWI

Control

S XSWI

Control

S XSWI

Control

S XSWI

Control

S XSWI

Control

S XSWI

Control

OV2 PTOV

59 U>

PH PIOC

50 3I>>

CC RBRF

50BF 3I> BF

V MMXU

Meter.

C MMXU

Meter.

ETP MMTR

Wh<->

QA1

QB1 QB2

QB9

QC9

QC2

QC1

EF4 PTOC

51N/67N IN>

Q CBAY

Control

WA1

WA2

S CILO

Control

S CILO

Control

S CILO

Control

S CILO

Control

S CILO

Control

S CILO

Control

S CILO

Control

SEL GGIO

Control

C MSQI

Meter.

V MSQI

Meter.

CV MMXN

Meter.

CC RPLD

52PD PD

DRP RDRE

Mont.

V MMXU

Meter.

V MMXU

Meter.

OC4 PTOC

51/67 3I>

IEC61850

ANSI IEC

Function Enabled in Settings

132 kV Bus

1000/1

132kV/110V

132kV/110V

132kV/110V

IEC09000649-2-en.vsd

S SIMG

63

S SCBR

Cond

DNP

ANSI IEC

Function Disabled in Settings

IEC60870-5-103

ANSI IEC

IEC09000649 V2 EN

Figure 2. A typical protection and control application for a double busbar in single breakerarrangement

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 5

Page 6: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

REC650-A07 – Bus Coupler single breaker 10AI (6I+4U)

S CSWI

Control

S XCBR

Control

S CSWI

Control

S CSWI

Control

S CSWI

Control

SMP PTRC

94 1->0

S CSWI

Control

S CSWI

Control

S CSWI

Control

SES RSYN

25 SYNC

TCS SCBR

Cond

TCS SCBR

Cond

SPVN ZBAT

Cond

Other configured functions

S XSWI

Control

S XSWI

Control

S XSWI

Control

S XSWI

Control

S XSWI

Control

S XSWI

Control

EF4 PTOC

51N IN>

Q CBAY

Control

S SCBR

Cond

S CILO

Control

S CILO

Control

S CILO

Control

S CILO

Control

S CILO

Control

S CILO

Control

S CILO

Control

SEL GGIO

Control

DRP RDRE

Mont.

QA1

QB1 QB2

QC2

QC1

WA1

WA2

QC11 QC21

CC RBRF

50BF 3I> BF

PH PIOC

50 3I>>

CC RPLD

52PD PD

C MMXU

Meter.

C MSQI

Meter.

V MMXU

Meter.

V MMXU

Meter.

IEC61850

ANSI IEC

Function Enabled in Settings

132 kV Bus

1000/1

132kV/110V 132kV/

110V

OC4 PTOC

51/67 3I>

IEC09000650-2-en.vsd

S SIMG

63

DNP

ANSI IEC

Function Disabled in Settings

IEC60870-5-103

ANSI IEC

IEC09000650 V2 EN

Figure 3. A typical protection and control application for a bus coupler in single breakerarrangement

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

6 ABB

Page 7: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

3. Available functions

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 7

Page 8: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Control and monitoring functions

IEC 61850/Function blockname

ANSI Function description Bay

REC

650 (

A01)

1C

BA

REC

650 (

A02)

1C

BA

B

REC

650 (

A07)

BC

AB

Control

SESRSYN 25 Synchrocheck, energizing check,and synchronizing

1 1 1

SMBRREC 79 Autorecloser 1 1 1

SCILO 3 Logical node for interlocking 8 8 8

BB_ES 3 Interlocking for busbar earthingswitch

3 3 3

A1A2_BS 3 Interlocking for bus-section breaker 2 2 2

A1A2_DC 3 Interlocking for bus-sectiondisconnector

3 3 3

ABC_BC 3 Interlocking for bus-coupler bay 1 1 1

BH_CONN 3 Interlocking for 1 1/2 breakerdiameter

1 1 1

BH_LINE_A 3 Interlocking for 1 1/2 breakerdiameter

1 1 1

BH_LINE_B 3 Interlocking for 1 1/2 breakerdiameter

1 1 1

DB_BUS_A 3 Interlocking for double CB bay 1 1 1

DB_BUS_B 3 Interlocking for double CB bay 1 1 1

DB_LINE 3 Interlocking for double CB bay 1 1 1

ABC_LINE 3 Interlocking for line bay 1 1 1

AB_TRAFO 3 Interlocking for transformer bay 1 1 1

SCSWI Switch controller 8 8 8

SXCBR Circuit breaker 3 3 3

SXSWI Circuit switch 7 7 7

POS_EVAL Evaluation of position indication 8 8 8

SELGGIO Select release 1 1 1

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

8 ABB

Page 9: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

IEC 61850/Function blockname

ANSI Function description Bay

REC

650 (

A01)

1C

BA

REC

650 (

A02)

1C

BA

B

REC

650 (

A07)

BC

AB

QCBAY Bay control 1 1 1

LOCREM Handling of LR-switch positions 1 1 1

LOCREMCTRL LHMI control of Permitted SourceTo Operate (PSTO)

1 1 1

SLGGIO Logic Rotating Switch for functionselection and LHMI presentation

15 15 15

VSGGIO Selector mini switch extension 20 20 20

DPGGIO IEC 61850 generic communication I/O functions double point

16 16 16

SPC8GGIO Single point generic control 8 signals 5 5 5

AUTOBITS AutomationBits, command functionfor DNP3.0

3 3 3

I103CMD Function commands forIEC60870-5-103

1 1 1

I103IEDCMD IED commands for IEC60870-5-103 1 1 1

I103USRCMD Function commands user definedfor IEC60870-5-103

4 4 4

I103GENCMD Function commands generic forIEC60870-5-103

50 50 50

I103POSCMD IED commands with position andselect for IEC60870-5-103

50 50 50

Secondary system supervision

CCSRDIF 87 Current circuit supervision 1 1 1

SDDRFUF Fuse failure supervision 1 1 1

TCSSCBR Breaker close/trip circuit monitoring 3 3 3

Logic

SMPPTRC 94 Tripping logic 1 1 1

TMAGGIO Trip matrix logic 12 12 12

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 9

Page 10: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

IEC 61850/Function blockname

ANSI Function description Bay

REC

650 (

A01)

1C

BA

REC

650 (

A02)

1C

BA

B

REC

650 (

A07)

BC

AB

OR Configurable logic blocks, OR gate 283 283 283

INVERTER Configurable logic blocks, Invertergate

140 140 140

PULSETIMER Configurable logic blocks, Pulsetimer

40 40 40

GATE Configurable logic blocks,Controllable gate

40 40 40

XOR Configurable logic blocks, exclusiveOR gate

40 40 40

LOOPDELAY Configurable logic blocks, loop delay 40 40 40

TIMERSET Configurable logic blocks, timerfunction block

40 40 40

AND Configurable logic blocks, AND gate 280 280 280

SRMEMORY Configurable logic blocks, set-resetmemory flip-flop gate

40 40 40

RSMEMORY Configurable logic blocks, reset-setmemory flip-flop gate

40 40 40

ANDQT Configurable logic Q/T, AND gatewith quality and time

120 120 120

ORQT Configurable logic Q/T, OR gatewith quality and time

120 120 120

INVERTERQT Configurable logic Q/T, invertergate with quality and time

120 120 120

XORQT Configurable logic Q/T, exclusiveOR gate with quality and time

40 40 40

SRMEMORYQT Configurable logic Q/T, set-resetwith memory flip-flop gate withquality and time

40 40 40

RSMEMORYQT Configurable logic Q/T, reset-setwith memory flip-flop gate withquality and time

40 40 40

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

10 ABB

Page 11: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

IEC 61850/Function blockname

ANSI Function description Bay

REC

650 (

A01)

1C

BA

REC

650 (

A02)

1C

BA

B

REC

650 (

A07)

BC

AB

TIMERSETQT Configurable logic Q/T, timerfunction block with quality and time

40 40 40

PULSETIMERQT Configurable logic Q/T, pulse timerwith quality and time

40 40 40

INVALIDQT Configurable logic Q/T, used forinvalidate data

12 12 12

INDCOMBSPQT Configurable logic Q/T, single pointindication logic signal combinatorcombining value with quality andtime

20 20 20

INDEXTSPQT Configurable logic Q/T, single pointindication logic signal gateextracting value with quality andtime

20 20 20

FXDSIGN Fixed signal function block 1 1 1

B16I Boolean 16 to Integer conversion 16 16 16

B16IFCVI Boolean 16 to Integer conversionwith logic node representation

16 16 16

IB16A Integer to Boolean 16 conversion 16 16 16

IB16FCVB Integer to Boolean 16 conversionwith logic node representation

16 16 16

Monitoring

CVMMXN Measurements 6 6 6

CMMXU Phase current measurement 10 10 10

VMMXU Phase-phase voltage measurement 6 6 6

CMSQI Current sequence componentmeasurement

6 6 6

VMSQI Voltage sequence measurement 6 6 6

VNMMXU Phase-neutral voltage measurement 6 6 6

CNTGGIO Event counter 5 5 5

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 11

Page 12: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

IEC 61850/Function blockname

ANSI Function description Bay

REC

650 (

A01)

1C

BA

REC

650 (

A02)

1C

BA

B

REC

650 (

A07)

BC

AB

DRPRDRE Disturbance report 1 1 1

AxRADR Analog input signals 4 4 4

BxRBDR Binary input signals 6 6 6

SPGGIO IEC 61850 generic communication I/O functions

64 64 64

SP16GGIO IEC 61850 generic communication I/O functions 16 inputs

16 16 16

MVGGIO IEC 61850 generic communication I/O functions

16 16 16

MVEXP Measured value expander block 66 66 66

SPVNZBAT Station battery supervision 1 1 1

SSIMG 63 Insulation gas monitoring function 1 1 1

SSIML 71 Insulation liquid monitoring function 1 1 1

SSCBR Circuit breaker condition monitoring 1 1 1

I103MEAS Measurands for IEC60870-5-103 1 1 1

I103MEASUSR Measurands user defined signals forIEC60870-5-103

3 3 3

I103AR Function status auto-recloser forIEC60870-5-103

1 1 1

I103EF Function status earth-fault forIEC60870-5-103

1 1 1

I103FLTPROT Function status fault protection forIEC60870-5-103

1 1 1

I103IED IED status for IEC60870-5-103 1 1 1

I103SUPERV Supervison status for IEC60870-5-103 1 1 1

I103USRDEF Status for user defined signals forIEC60870-5-103

20 20 20

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

12 ABB

Page 13: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

IEC 61850/Function blockname

ANSI Function description Bay

REC

650 (

A01)

1C

BA

REC

650 (

A02)

1C

BA

B

REC

650 (

A07)

BC

AB

Metering

PCGGIO Pulse counter logic 16 16 16

ETPMMTR Function for energy calculation anddemand handling

3 3 3

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 13

Page 14: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Back-up protection functions

IEC 61850/Functionblockname

ANSI Function description Bay

REC

650 (

A01)

1C

BA

REC

650 (

A02)

1C

BA

B

REC

650 (

A07)

BC

AB

Current protection

PHPIOC 50 Instantaneous phase overcurrentprotection

1 1 1

OC4PTOC 51/67 Four step directional phase overcurrentprotection

1 1 1

EFPIOC 50N Instantaneous residual overcurrentprotection

1 1 1

EF4PTOC 51N/67N

Four step directional residualovercurrent protection

1 1 1

SDEPSDE 67N Sensitive directional residualovercurrent and power protection

1 1 1

LPTTR 26 Thermal overload protection, one timeconstant

1 1 1

CCRBRF 50BF Breaker failure protection 1 1 1

STBPTOC 50STB Stub protection 1 1 1

CCRPLD 52PD Pole discordance protection 1 1 1

BRCPTOC 46 Broken conductor check 1 1 1

GUPPDUP 37 Directional underpower protection 1 1 1

GOPPDOP 32 Directional overpower protection 1 1 1

DNSPTOC 46 Negative sequence based overcurrentfunction

1 1 1

Voltage protection

UV2PTUV 27 Two step undervoltage protection 1 1 1

OV2PTOV 59 Two step overvoltage protection 1 1 1

ROV2PTOV 59N Two step residual overvoltageprotection

1 1 1

LOVPTUV 27 Loss of voltage check 1 1 1

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

14 ABB

Page 15: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

IEC 61850/Functionblockname

ANSI Function description Bay

REC

650 (

A01)

1C

BA

REC

650 (

A02)

1C

BA

B

REC

650 (

A07)

BC

AB

Frequency protection

SAPTUF 81 Underfrequency function 2 2 2

SAPTOF 81 Overfrequency function 2 2 2

SAPFRC 81 Rate-of-change frequency protection 2 2 2

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 15

Page 16: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Designed to communicate

IEC 61850/Function blockname

ANSI Function description Bay

REC

650 (

A01)

1C

BA

REC

650 (

A02)

1C

BA

B

REC

650 (

A07)

BC

AB

Station communication

IEC 61850 communicationprotocol, LAN1

1 1 1

DNP3.0 for TCP/IPcommunication protocol, LAN1

1 1 1

IEC61870-5-103 IEC60870-5-103 serialcommunication via ST

1 1 1

GOOSEINTLKRCV Horizontal communication viaGOOSE for interlocking

59 59 59

GOOSEBINRCV GOOSE binary receive 4 4 4

GOOSEDPRCV GOOSE function block to receivea double point value

32 32 32

GOOSEINTRCV GOOSE function block to receivean integer value

32 32 32

GOOSEMVRCV GOOSE function block to receivea mesurand value

16 16 16

GOOSESPRCV GOOSE function block to receivea single point value

64 64 64

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

16 ABB

Page 17: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Basic IED functions

IEC 61850/Function blockname

Function description

Basic functions included in all products

INTERRSIG Self supervision with internal event list 1

SELFSUPEVLST Self supervision with internal event list 1

SNTP Time synchronization 1

TIMESYNCHGEN Time synchronization 1

DTSBEGIN,DTSEND,TIMEZONE

Time synchronization, daylight saving 1

IRIG-B Time synchronization 1

SETGRPS Setting group handling 1

ACTVGRP Parameter setting groups 1

TESTMODE Test mode functionality 1

CHNGLCK Change lock function 1

TERMINALID IED identifiers 1

PRODINF Product information 1

PRIMVAL Primary system values 1

SMAI_20_1-12 Signal matrix for analog inputs 2

3PHSUM Summation block 3 phase 12

GBASVAL Global base values for settings 6

ATHSTAT Authority status 1

ATHCHCK Authority check 1

FTPACCS FTP access with password 1

DOSFRNT Denial of service, frame rate control for front port 1

DOSLAN1 Denial of service, frame rate control for LAN1 1

DOSSCKT Denial of service, socket flow control 1

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 17

Page 18: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

4. Control

Synchrocheck, energizing check,and synchronizing SESRSYN

The Synchronizing function allows closing ofasynchronous networks at the correctmoment including the breaker closing time,which improves the network stability.

Synchrocheck, energizing check, andsynchronizing (SESRSYN) function checksthat the voltages on both sides of the circuitbreaker are in synchronism, or with at leastone side dead to ensure that closing can bedone safely.

SESRSYN function includes a built-in voltageselection scheme for double bus arrangements.

Manual closing as well as automatic reclosingcan be checked by the function and can havedifferent settings.

For systems which are running asynchronousa synchronizing function is provided. Themain purpose of the synchronizing functionis to provide controlled closing of circuitbreakers when two asynchronous systems aregoing to be connected. It is used for slipfrequencies that are larger than those forsynchrocheck and lower than a set maximumlevel for the synchronizing function.

Autorecloser SMBRREC

The autorecloser (SMBRREC) functionprovides high-speed and/or delayed auto-reclosing for single breaker applications.

Up to five reclosing attempts can be includedby parameter setting.

The autoreclosing function can be configuredto co-operate with a synchrocheck function.

Apparatus control APC

The apparatus control functions are used forcontrol and supervision of circuit breakers,disconnectors and earthing switches within abay. Permission to operate is given afterevaluation of conditions from other functionssuch as interlocking, synchrocheck, operator

place selection and external or internalblockings.

Apparatus control features:

• Select-Execute principle to give highreliability

• Selection function to prevent simultaneousoperation

• Selection and supervision of operator place• Command supervision• Block/deblock of operation• Block/deblock of updating of position

indications• Substitution of position indications• Overriding of interlocking functions• Overriding of synchrocheck• Operation counter• Suppression of Mid position

Two types of command models can be used:

• Direct with normal security• SBO (Select-Before-Operate) with enhanced

security

Direct commands are received with no priorselect command. SBO commands arereceived with a select command first and onsuccessful selection, a proceeding operatecommand.

In normal security, the command isprocessed and the resulting position is notsupervised. However with enhanced security,the command is processed and the resultingposition is supervised.

Control operation can be performed from thelocal HMI under authority control if so defined.

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

18 ABB

Page 19: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

IEC09000668-1-en.vsd

IEC09000668 V1 EN

Figure 4. Select before operation withconfirmation of command

IEC09000669-2-en.vsd

CancelOk

IEC09000669 V2 EN

Figure 5. Overriding of synchrocheck

Bay control QCBAY

The Bay control QCBAY function is usedtogether with Local remote and local remotecontrol functions is used to handle theselection of the operator place per bay.QCBAY also provides blocking functions thatcan be distributed to different apparatuseswithin the bay.

Local remote LOCREM /Localremote control LOCREMCTRL

The signals from the local HMI or from anexternal local/remote switch are applied viathe function blocks LOCREM andLOCREMCTRL to the Bay control (QCBAY)function block. A parameter in function blockLOCREM is set to choose if the switch signalsare coming from the local HMI or from anexternal hardware switch connected viabinary inputs.

Interlocking

The interlocking functionality blocks thepossibility to operate high-voltage switchingdevices, for instance when a disconnector isunder load, in order to prevent materialdamage and/or accidental human injury.

Each control IED has interlocking functionsfor different switchyard arrangements, eachhandling the interlocking of one bay. Theinterlocking functionality in each IED is notdependent on any central function. For thestation-wide interlocking, the IEDscommunicate via the station bus or by usinghard wired binary inputs/outputs.

The interlocking conditions depend on thecircuit configuration and status of the systemat any given time.

Logic rotating switch for functionselection and LHMI presentationSLGGIO

The logic rotating switch for functionselection and LHMI presentation function(SLGGIO) (or the selector switch functionblock) is used to get a selector switchfunctionality similar to the one provided by ahardware selector switch. Hardware selectorswitches are used extensively by utilities, inorder to have different functions operating onpre-set values. Hardware switches arehowever sources for maintenance issues,lower system reliability and an extendedpurchase portfolio. The logic selectorswitches eliminate all these problems.

Selector mini switch VSGGIO

The Selector mini switch VSGGIO functionblock is a multipurpose function used for avariety of applications, as a general purposeswitch.

VSGGIO can be controlled from the menu orfrom a symbol on the single line diagram(SLD) on the local HMI.

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 19

Page 20: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

IEC 61850 generic communicationI/O functions DPGGIO

The IEC 61850 generic communication I/Ofunctions (DPGGIO) function block is used tosend double indications to other systems orequipment in the substation. It is especiallyused in the interlocking and reservationstation-wide logics.

Single point generic control 8signals SPC8GGIO

The Single point generic control 8 signals(SPC8GGIO) function block is a collection of8 single point commands, designed to bringin commands from REMOTE (SCADA) tothose parts of the logic configuration that donot need extensive command receivingfunctionality (for example, SCSWI). In thisway, simple commands can be sent directlyto the IED outputs, without confirmation.Confirmation (status) of the result of thecommands is supposed to be achieved byother means, such as binary inputs andSPGGIO function blocks. The commands canbe pulsed or steady.

AutomationBits AUTOBITS

The Automation bits function (AUTOBITS) isused to configure the DNP3 protocolcommand handling.

5. Current protection

Instantaneous phase overcurrentprotection PHPIOC

The instantaneous three phase overcurrentfunction has a low transient overreach andshort tripping time to allow use as a high setshort-circuit protection function.

Four step phase overcurrentprotection OC4PTOC

The four step phase overcurrent protectionfunction OC4PTOC has an inverse or definitetime delay independent for step 1 and 4

separately. Step 2 and 3 are always definitetime delayed.

All IEC and ANSI time delayed characteristicsare available.

The directional function is voltage polarizedwith memory. The function can be set to bedirectional or non-directional independentlyfor each of the steps.

Instantaneous residual overcurrentprotection EFPIOC

The Instantaneous residual overcurrentprotection EFPIOC has a low transientoverreach and short tripping times to allowthe use for instantaneous earth-faultprotection, with the reach limited to less thanthe typical eighty percent of the line atminimum source impedance. EFPIOC can beconfigured to measure the residual currentfrom the three-phase current inputs or thecurrent from a separate current input.EFPIOC can be blocked by activating theinput BLOCK.

Four step residual overcurrentprotection EF4PTOC

The four step residual overcurrent protection(EF4PTOC) has a settable inverse or definitetime delay independent for step 1 and 4separately. Step 2 and 3 are always definitetime delayed.

All IEC and ANSI time delayed characteristicsare available.

The directional function is voltage polarized,current polarized or dual polarized.

EF4PTOC can be set directional or non-directional independently for each of the steps.

A second harmonic blocking can be setindividually for each step.

EF4PTOC can be used as main protection forphase-to-earth faults.

EF4PTOC can also be used to provide asystem back-up for example, in the case ofthe primary protection being out of servicedue to communication or voltage transformercircuit failure.

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

20 ABB

Page 21: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Directional operation can be combinedtogether with corresponding communicationlogic in permissive or blocking teleprotectionscheme. Current reversal and weak-endinfeed functionality are available as well.

Sensitive directional residualovercurrent and power protectionSDEPSDE

In isolated networks or in networks withhigh impedance earthing, the earth faultcurrent is significantly smaller than the shortcircuit currents. In addition to this, themagnitude of the fault current is almostindependent on the fault location in thenetwork. The protection can be selected touse either the residual current or residualpower component 3U0·3I0·cos j, for

operating quantity. There is also availableone non-directional 3I0 step and one non-

directional 3U0 overvoltage tripping step.

Thermal overload protection, onetime constant LPTTR

The increasing utilizing of the power systemcloser to the thermal limits has generated aneed of a thermal overload protection alsofor power lines.

A thermal overload will often not be detectedby other protection functions and theintroduction of the thermal overloadprotection can allow the protected circuit tooperate closer to the thermal limits.

The three-phase current measuring protection

has an I2t characteristic with settable timeconstant and a thermal memory.

An alarm level gives early warning to allowoperators to take action well before the lineis tripped.

Breaker failure protection CCRBRF

Breaker failure protection (CCRBRF) ensuresfast back-up tripping of surrounding breakersin case the own breaker failure to open.CCRBRF can be current based, contact based,or an adaptive combination of these twoprinciples.

A current check with extremely short resettime is used as check criterion to achieve ahigh security against unnecessary operation.

A contact check criteria can be used wherethe fault current through the breaker is small.

Breaker failure protection (CCRBRF) currentcriteria can be fulfilled by one or two phasecurrents, or one phase current plus residualcurrent. When those currents exceed the userdefined settings, the function is activated.These conditions increase the security of theback-up trip command.

CCRBRF function can be programmed to givea three-phase re-trip of the own breaker toavoid unnecessary tripping of surroundingbreakers at an incorrect initiation due tomistakes during testing.

Stub protection STBPTOC

When a power line is taken out of service formaintenance and the line disconnector isopened the voltage transformers will mostlybe outside on the disconnected part. Theprimary line distance protection will thus notbe able to operate and must be blocked.

The stub protection STBPTOC covers thezone between the current transformers andthe open disconnector. The three-phaseinstantaneous overcurrent function isreleased from a normally open, NO (b)auxiliary contact on the line disconnector.

Pole discordance protectionCCRPLD

Circuit breakers and disconnectors can endup with the poles in different positions (close-open), due to electrical or mechanicalfailures. This can cause negative and zerosequence currents which cause thermal stresson rotating machines and can causeunwanted operation of zero sequence ornegative sequence current functions.

Normally the own breaker is tripped tocorrect such a situation. If the situationpersists the surrounding breakers should betripped to clear the unsymmetrical loadsituation.

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 21

Page 22: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

The pole discordance function operates basedon information from the circuit breaker logicwith additional criteria from unsymmetricalphase currents when required.

Broken conductor check BRCPTOC

Conventional protection functions can notdetect the broken conductor condition.Broken conductor check (BRCPTOC)function, consisting of continuous currentunsymmetrical check on the line where theIED is connected will give alarm or trip atdetecting broken conductors.

Directional over/underpowerprotection GOPPDOP/GUPPDUP

The directional over-/under-power protectionGOPPDOP/GUPPDUP can be used wherevera high/low active, reactive or apparent powerprotection or alarming is required. Thefunctions can alternatively be used to checkthe direction of active or reactive power flowin the power system. There are a number ofapplications where such functionality isneeded. Some of them are:

• detection of reversed active power flow• detection of high reactive power flow

Each function has two steps with definitetime delay. Reset times for both steps can beset as well.

Negative sequence basedovercurrent function DNSPTOC

Negative sequence based overcurrentfunction (DNSPTOC) is typically used assensitive earth-fault protection of powerlines, where incorrect zero sequencepolarization may result from mutualinduction between two or more parallel lines.

Additionally, it is applied in applications onunderground cables, where zero sequenceimpedance depends on the fault currentreturn paths, but the cable negative sequenceimpedance is practically constant.

The directional function is current andvoltage polarized. The function can be set to

forward, reverse or non-directionalindependently for each step.

DNSPTOC protects against all unbalancedfaults including phase-to-phase faults. Theminimum start current of the function mustbe set to above the normal system unbalancelevel in order to avoid unintentionalfunctioning.

6. Voltage protection

Two step undervoltage protectionUV2PTUV

Undervoltages can occur in the power systemduring faults or abnormal conditions. Twostep undervoltage protection (UV2PTUV)function can be used to open circuit breakersto prepare for system restoration at poweroutages or as long-time delayed back-up toprimary protection.

UV2PTUV has two voltage steps, where step1 is settable as inverse or definite timedelayed. Step 2 is always definite time delayed.

Two step overvoltage protectionOV2PTOV

Overvoltages may occur in the power systemduring abnormal conditions such as suddenpower loss, tap changer regulating failures,open line ends on long lines etc.

OV2PTOV has two voltage steps, where step1 can be set as inverse or definite timedelayed. Step 2 is always definite time delayed.

OV2PTOV has an extremely high reset ratioto allow settings close to system servicevoltage.

Two step residual overvoltageprotection ROV2PTOV

Residual voltages may occur in the powersystem during earth faults.

Two step residual overvoltage protectionROV2PTOV function calculates the residualvoltage from the three-phase voltage input

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

22 ABB

Page 23: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

transformers or measures it from a singlevoltage input transformer fed from an opendelta or neutral point voltage transformer.

ROV2PTOV has two voltage steps, wherestep 1 can be set as inverse or definite timedelayed. Step 2 is always definite time delayed.

Loss of voltage check LOVPTUV

Loss of voltage check (LOVPTUV) is suitablefor use in networks with an automatic systemrestoration function. LOVPTUV issues a three-pole trip command to the circuit breaker, ifall three phase voltages fall below the setvalue for a time longer than the set time andthe circuit breaker remains closed.

7. Frequency protection

Underfrequency protection SAPTUF

Underfrequency occurs as a result of lack ofgeneration in the network.

Underfrequency protection SAPTUF is usedfor load shedding systems, remedial actionschemes, gas turbine startup and so on.

SAPTUF is provided with an undervoltageblocking.

Overfrequency protection SAPTOF

Overfrequency protection function SAPTOF isapplicable in all situations, where reliabledetection of high fundamental power systemfrequency is needed.

Overfrequency occurs at sudden load dropsor shunt faults in the power network. Closeto the generating plant, generator governorproblems can also cause over frequency.

SAPTOF is used mainly for generationshedding and remedial action schemes. It isalso used as a frequency stage initiating loadrestoring.

SAPTOF is provided with an undervoltageblocking.

Rate-of-change frequencyprotection SAPFRC

Rate-of-change frequency protection function(SAPFRC) gives an early indication of a maindisturbance in the system. SAPFRC can beused for generation shedding, load sheddingand remedial action schemes. SAPFRC candiscriminate between positive or negativechange of frequency.

SAPFRC is provided with an undervoltageblocking.

8. Secondary systemsupervision

Current circuit supervisionCCSRDIF

Open or short circuited current transformercores can cause unwanted operation of manyprotection functions such as differential,earth-fault current and negative-sequencecurrent functions.

It must be remembered that a blocking ofprotection functions at an occurrence of openCT circuit will mean that the situation willremain and extremely high voltages willstress the secondary circuit.

Current circuit supervision (CCSRDIF)compares the residual current from a threephase set of current transformer cores withthe neutral point current on a separate inputtaken from another set of cores on thecurrent transformer.

A detection of a difference indicates a fault inthe circuit and is used as alarm or to blockprotection functions expected to giveunwanted tripping.

Fuse failure supervision SDDRFUF

The aim of the fuse failure supervisionfunction (SDDRFUF) is to block voltagemeasuring functions at failures in thesecondary circuits between the voltage

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 23

Page 24: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

transformer and the IED in order to avoidunwanted operations that otherwise mightoccur.

The fuse failure supervision function basicallyhas three different algorithms, negativesequence and zero sequence basedalgorithms and an additional delta voltageand delta current algorithm.

The negative sequence detection algorithm isrecommended for IEDs used in isolated orhigh-impedance earthed networks. It is basedon the negative-sequence measuringquantities, a high value of voltage 3U2

without the presence of the negative-sequence current 3I2.

The zero sequence detection algorithm isrecommended for IEDs used in directly orlow impedance earthed networks. It is basedon the zero sequence measuring quantities, ahigh value of voltage 3U0 without the

presence of the residual current 3I0.

A criterion based on delta current and deltavoltage measurements can be added to thefuse failure supervision function in order todetect a three phase fuse failure, which inpractice is more associated with voltagetransformer switching during stationoperations.

For better adaptation to system requirements,an operation mode setting has beenintroduced which makes it possible to selectthe operating conditions for negativesequence and zero sequence based function.The selection of different operation modesmakes it possible to choose differentinteraction possibilities between the negativesequence and zero sequence based algorithm.

Breaker close/trip circuitmonitoring TCSSCBR

The trip circuit supervision function TCSSCBRis designed to supervise the control circuit ofthe circuit breaker. The invalidity of a controlcircuit is detected by using a dedicatedoutput contact that contains the supervisionfunctionality.

The function operates after a predefinedoperating time and resets when the faultdisappears.

9. Logic

Tripping logic SMPPTRC

A function block for protection tripping isprovided for each circuit breaker involved inthe tripping of the fault. It provides the pulseprolongation to ensure a trip pulse ofsufficient length, as well as all functionalitynecessary for correct co-operation withautoreclosing functions.

The trip function block includes functionalityfor breaker lock-out.

Trip matrix logic TMAGGIO

Trip matrix logic TMAGGIO function is usedto route trip signals and other logical outputsignals to different output contacts on the IED.

TMAGGIO output signals and the physicaloutputs allows the user to adapt the signalsto the physical tripping outputs according tothe specific application needs.

Configurable logic blocks

A number of logic blocks and timers areavailable for the user to adapt theconfiguration to the specific application needs.

• OR function block.

• INVERTER function blocks that inverts theinput signal.

• PULSETIMER function block can be used,for example, for pulse extensions orlimiting of operation of outputs.

• GATE function block is used for whetheror not a signal should be able to pass fromthe input to the output.

• XOR function block.

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

24 ABB

Page 25: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

• LOOPDELAY function block used to delaythe output signal one execution cycle.

• TIMERSET function has pick-up and drop-out delayed outputs related to the inputsignal. The timer has a settable time delay.

• AND function block.

• SRMEMORY function block is a flip-flopthat can set or reset an output from twoinputs respectively. Each block has twooutputs where one is inverted. The memorysetting controls if the block should be resetor return to the state before theinterruption, after a power interruption. Setinput has priority.

• RSMEMORY function block is a flip-flopthat can reset or set an output from twoinputs respectively. Each block has twooutputs where one is inverted. The memorysetting controls if the block should be resetor return to the state before theinterruption, after a power interruption.Reset input has priority.

Configurable logic Q/TA number of logic blocks and timers with thecapability to propagate timestamp and qualityof the input signals are available. Thefunction blocks assist the user to adapt theIEDs configuration to the specific applicationneeds.

• ORQT function block that also propagatestimestamp and quality of input signals.

• INVERTERQT function block that invertsthe input signal and propagates timestampand quality of input signal.

• PULSETIMERQT function block can beused, for example, for pulse extensions orlimiting of operation of outputs. Thefunction also propagates timestamp andquality of input signal.

• XORQT function block. The function alsopropagates timestamp and quality of inputsignals.

• TIMERSETQT function has pick-up anddrop-out delayed outputs related to theinput signal. The timer has a settable timedelay. The function also propagatestimestamp and quality of input signal.

• ANDQT function block. The function alsopropagates timestamp and quality of inputsignals.

• SRMEMORYQT function block is a flip-flop that can set or reset an output fromtwo inputs respectively. Each block has twooutputs where one is inverted. The memorysetting controls if the block after a powerinterruption should return to the statebefore the interruption, or be reset. Thefunction also propagates timestamp andquality of input signal.

• RSMEMORYQT function block is a flip-flop that can reset or set an output fromtwo inputs respectively. Each block has twooutputs where one is inverted. The memorysetting controls if the block after a powerinterruption should return to the statebefore the interruption, or be reset. Thefunction also propagates timestamp andquality of input signal.

• INVALIDQT function which sets qualityinvalid of outputs according to a "valid"input. Inputs are copied to outputs. If inputVALID is 0, or if its quality invalid bit is set,all outputs invalid quality bit will be set toinvalid. The timestamp of an output will beset to the latest timestamp of INPUT andVALID inputs.

• INDCOMBSPQT combines single inputsignals to group signal. Single positioninput is copied to value part of SP_OUToutput. TIME input is copied to time part ofSP_OUT output. State input bits are copiedto the corresponding state part of SP_OUToutput. If the state or value on the SP_OUT

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 25

Page 26: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

output changes, the Event bit in the statepart is toggled. The function alsopropagates timestamp and quality of inputsignals.

• INDEXTSPQT extracts individual signalsfrom a group signal input. Value part ofsingle position input is copied to SI_OUToutput. Time part of single position input iscopied to TIME output. State bits incommon part and indication part of inputssignal is copied to the corresponding stateoutput. The function also propagatestimestamp and quality of input signal.

Boolean 16 to Integer conversionB16I

Boolean 16 to integer conversion function(B16I) is used to transform a set of 16 binary(logical) signals into an integer.

Boolean 16 to Integer conversionwith logic node representationB16IFCVI

Boolean 16 to integer conversion with logicnode representation function (B16IFCVI) isused to transform a set of 16 binary (logical)signals into an integer.

Integer to Boolean 16 conversionIB16A

Integer to boolean 16 conversion function(IB16A) is used to transform an integer into aset of 16 binary (logical) signals.

Integer to Boolean 16 conversionwith logic node representationIB16FCVB

Integer to boolean conversion with logicnode representation function (IB16FCVB) isused to transform an integer to 16 binary(logic) signals.

IB16FCVB function can receive remote valuesover IEC61850 depending on the operatorposition input (PSTO).

10. Monitoring

Measurements CVMMXN, CMMXU,VNMMXU, VMMXU, CMSQI, VMSQI

The measurement functions are used to get on-line information from the IED. These servicevalues make it possible to display on-lineinformation on the local HMI and on theSubstation automation system about:

• measured voltages, currents, frequency,active, reactive and apparent power andpower factor

• primary and secondary phasors• current sequence components• voltage sequence components

Event counter CNTGGIO

Event counter (CNTGGIO) has six counterswhich are used for storing the number oftimes each counter input has been activated.

Disturbance report DRPRDRE

Complete and reliable information aboutdisturbances in the primary and/or in thesecondary system together with continuousevent-logging is accomplished by thedisturbance report functionality.

Disturbance report DRPRDRE, alwaysincluded in the IED, acquires sampled data ofall selected analog input and binary signalsconnected to the function block that is,maximum 40 analog and 96 binary signals.

The Disturbance report functionality is acommon name for several functions:

• Event list• Indications• Event recorder• Trip value recorder• Disturbance recorder

The Disturbance report function ischaracterized by great flexibility regardingconfiguration, starting conditions, recordingtimes, and large storage capacity.

A disturbance is defined as an activation ofan input to the AxRADR or BxRBDR function

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

26 ABB

Page 27: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

blocks, which are set to trigger thedisturbance recorder. All signals from start ofpre-fault time to the end of post-fault timewill be included in the recording.

Every disturbance report recording is savedin the IED in the standard Comtrade format.The same applies to all events, which arecontinuously saved in a ring-buffer. The localHMI is used to get information about therecordings. The disturbance report files maybe uploaded to PCM600 for further analysisusing the disturbance handling tool.

Event list DRPRDRE

Continuous event-logging is useful formonitoring the system from an overviewperspective and is a complement to specificdisturbance recorder functions.

The event list logs all binary input signalsconnected to the Disturbance report function.The list may contain up to 1000 time-taggedevents stored in a ring-buffer.

Indications DRPRDRE

To get fast, condensed and reliableinformation about disturbances in theprimary and/or in the secondary system it isimportant to know, for example binarysignals that have changed status during adisturbance. This information is used in theshort perspective to get information via thelocal HMI in a straightforward way.

There are three LEDs on the local HMI(green, yellow and red), which will displaystatus information about the IED and theDisturbance report function (trigged).

The Indication list function shows all selectedbinary input signals connected to theDisturbance report function that havechanged status during a disturbance.

Event recorder DRPRDRE

Quick, complete and reliable informationabout disturbances in the primary and/or inthe secondary system is vital, for example,time-tagged events logged duringdisturbances. This information is used fordifferent purposes in the short term (for

example corrective actions) and in the longterm (for example functional analysis).

The event recorder logs all selected binaryinput signals connected to the Disturbancereport function. Each recording can containup to 150 time-tagged events.

The event recorder information is availablefor the disturbances locally in the IED.

The event recording information is anintegrated part of the disturbance record(Comtrade file).

Trip value recorder DRPRDRE

Information about the pre-fault and faultvalues for currents and voltages are vital forthe disturbance evaluation.

The Trip value recorder calculates the valuesof all selected analog input signals connectedto the Disturbance report function. The resultis magnitude and phase angle before andduring the fault for each analog input signal.

The trip value recorder information isavailable for the disturbances locally in theIED.

The trip value recorder information is anintegrated part of the disturbance record(Comtrade file).

Disturbance recorder DRPRDRE

The Disturbance recorder function suppliesfast, complete and reliable information aboutdisturbances in the power system. Itfacilitates understanding system behavior andrelated primary and secondary equipmentduring and after a disturbance. Recordedinformation is used for different purposes inthe short perspective (for example correctiveactions) and long perspective (for examplefunctional analysis).

The Disturbance recorder acquires sampleddata from selected analog- and binary signalsconnected to the Disturbance report function(maximum 40 analog and 96 binary signals).The binary signals available are the same asfor the event recorder function.

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 27

Page 28: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

The function is characterized by greatflexibility and is not dependent on theoperation of protection functions. It canrecord disturbances not detected byprotection functions.

The disturbance recorder information for thelast 100 disturbances are saved in the IEDand the local HMI is used to view the list ofrecordings.

Measured value expander blockMVEXP

The current and voltage measurementsfunctions (CVMMXN, CMMXU, VMMXU andVNMMXU), current and voltage sequencemeasurement functions (CMSQI and VMSQI)and IEC 61850 generic communication I/Ofunctions (MVGGIO) are provided withmeasurement supervision functionality. Allmeasured values can be supervised with foursettable limits: low-low limit, low limit, highlimit and high-high limit. The measure valueexpander block has been introduced toenable translating the integer output signalfrom the measuring functions to 5 binarysignals: below low-low limit, below low limit,normal, above high-high limit or above highlimit. The output signals can be used asconditions in the configurable logic or foralarming purpose.

Station battery supervisionSPVNZBAT

The station battery supervision functionSPVNZBAT is used for monitoring batteryterminal voltage.

SPVNZBAT activates the start and alarmoutputs when the battery terminal voltageexceeds the set upper limit or drops belowthe set lower limit. A time delay for theovervoltage and undervoltage alarms can beset according to definite time characteristics.

In the definite time (DT) mode, SPVNZBAToperates after a predefined operate time andresets when the battery undervoltage orovervoltage condition disappears.

Insulation gas monitoring functionSSIMG

Insulation gas monitoring function (SSIMG) isused for monitoring the circuit breakercondition. Binary information based on thegas pressure in the circuit breaker is used asinput signals to the function. In addition, thefunction generates alarms based on receivedinformation.

Insulation liquid monitoringfunction SSIML

Insulation liquid monitoring function (SSIML)is used for monitoring the circuit breakercondition. Binary information based on theoil level in the circuit breaker is used as inputsignals to the function. In addition, thefunction generates alarms based on receivedinformation.

Circuit breaker monitoring SSCBR

The circuit breaker condition monitoringfunction SSCBR is used to monitor differentparameters of the circuit breaker. Thebreaker requires maintenance when thenumber of operations has reached apredefined value. The energy is calculatedfrom the measured input currents as a sum of

Iyt values. Alarms are generated when thecalculated values exceed the thresholdsettings.

The function contains a blockingfunctionality. It is possible to block thefunction outputs, if desired.

11. Metering

Pulse counter logic PCGGIO

Pulse counter (PCGGIO) function countsexternally generated binary pulses, forinstance pulses coming from an externalenergy meter, for calculation of energyconsumption values. The pulses are capturedby the BIO (binary input/output) moduleand then read by the PCGGIO function. A

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

28 ABB

Page 29: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

scaled service value is available over thestation bus.

Function for energy calculation anddemand handling ETPMMTR

Outputs from the Measurements (CVMMXN)function can be used to calculate energyconsumption. Active as well as reactivevalues are calculated in import and exportdirection. Values can be read or generated aspulses. Maximum demand power values arealso calculated by the function.

12. Human Machineinterface

Local HMI

GUID-23A12958-F9A5-4BF1-A31B-F69F56A046C7 V2 EN

Figure 6. Local human-machine interface

The LHMI of the IED contains the followingelements:

• Display (LCD)• Buttons• LED indicators• Communication port

The LHMI is used for setting, monitoring andcontrolling .

The Local human machine interface, LHMIincludes a graphical monochrome LCD with a

resolution of 320x240 pixels. The charactersize may vary depending on selectedlanguage. The amount of characters and rowsfitting the view depends on the character sizeand the view that is shown.

The LHMI can be detached from the mainunit. The detached LHMI can be wallmounted up to a distance of five meters fromthe main unit. The units are connected withthe Ethernet cable included in the delivery.

The LHMI is simple and easy to understand.The whole front plate is divided into zones,each with a well-defined functionality:

• Status indication LEDs• Alarm indication LEDs which can

indicate three states with the colorsgreen, yellow and red, with userprintable label. All LEDs are configurablefrom the PCM600 tool

• Liquid crystal display (LCD)• Keypad with push buttons for control

and navigation purposes, switch forselection between local and remotecontrol and reset

• Five user programmable function buttons• An isolated RJ45 communication port for

PCM600

13. Basic IED functions

Self supervision with internal eventlist

The Self supervision with internal event list(INTERRSIG and SELFSUPEVLST) functionreacts to internal system events generated bythe different built-in self-supervisionelements. The internal events are saved in aninternal event list.

Time synchronization

Use time synchronization to achieve acommon time base for the IEDs in aprotection and control system. This makescomparison of events and disturbance databetween all IEDs in the system possible.

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 29

Page 30: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Time-tagging of internal events anddisturbances are an excellent help whenevaluating faults. Without timesynchronization, only the events within theIED can be compared to one another. Withtime synchronization, events anddisturbances within the entire station, andeven between line ends, can be compared atevaluation.

In the IED, the internal time can besynchronized from a number of sources:

• SNTP• IRIG-B• DNP• IEC60870-5-103

Parameter setting groups ACTVGRP

Use the four sets of settings to optimize theIED operation for different system conditions.Creating and switching between fine-tunedsetting sets, either from the local HMI orconfigurable binary inputs, results in a highlyadaptable IED that can cope with a variety ofsystem scenarios.

Test mode functionality TESTMODE

The protection and control IEDs have manyincluded functions. To make the testingprocedure easier, the IEDs include the featurethat allows individual blocking of a single-,several-, or all functions.

There are two ways of entering the test mode:

• By configuration, activating an inputsignal of the function block TESTMODE

• By setting the IED in test mode in thelocal HMI

While the IED is in test mode, all functionsare blocked.

Any function can be unblocked individuallyregarding functionality and event signaling.This enables the user to follow the operationof one or several related functions to checkfunctionality and to check parts of theconfiguration, and so on.

Change lock function CHNGLCK

Change lock function (CHNGLCK) is used toblock further changes to the IEDconfiguration and settings once thecommissioning is complete. The purpose is toblock inadvertent IED configuration changesbeyond a certain point in time.

Authority status ATHSTAT

Authority status (ATHSTAT) function is anindication function block for user log-onactivity.

Authority check ATHCHCK

To safeguard the interests of our customers,both the IED and the tools that are accessingthe IED are protected, by means ofauthorization handling. The authorizationhandling of the IED and the PCM600 isimplemented at both access points to the IED:

• local, through the local HMI• remote, through the communication ports

14. Stationcommunication

IEC 61850-8-1 communicationprotocol

The IED supports the communicationprotocols IEC 61850-8-1 and DNP3 over TCP/IP. All operational information and controlsare available through these protocols.However, some communication functionality,for example, horizontal communication(GOOSE) between the IEDs, is only enabledby the IEC 61850-8-1 communication protocol.

The IED is equipped with an optical Ethernetrear port for the substation communicationstandard IEC 61850-8-1. IEC 61850-8-1protocol allows intelligent electrical devices(IEDs) from different vendors to exchangeinformation and simplifies systemengineering. Peer-to-peer communication

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

30 ABB

Page 31: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

according to GOOSE is part of the standard.Disturbance files uploading is provided.

Disturbance files are accessed using the IEC61850-8-1 protocol. Disturbance files areavailable to any Ethernet based applicationvia FTP in the standard Comtrade format.Further, the IED can send and receive binaryvalues, double point values and measuredvalues (for example from MMXU functions),together with their quality, using the IEC61850-8-1 GOOSE profile. The IED meets theGOOSE performance requirements fortripping applications in substations, asdefined by the IEC 61850 standard. The IEDinteroperates with other IEC 61850-compliantIEDs, tools, and systems and simultaneouslyreports events to five different clients on theIEC 61850 station bus.

The event system has a rate limiter to reduceCPU load. The event channel has a quota of10 events/second. If the quota is exceededthe event channel transmission is blockeduntil the event changes is below the quota,no event is lost.

All communication connectors, except for thefront port connector, are placed on integratedcommunication modules. The IED isconnected to Ethernet-based communicationsystems via the fibre-optic multimode LCconnector (100BASE-FX).

The IED supports SNTP and IRIG-B timesynchronization methods with a time-stamping resolution of 1 ms.

• Ethernet based: SNTP and DNP3• With time synchronization wiring: IRIG-B

The IED supports IEC 60870-5-103 timesynchronization methods with a timestamping resolution of 5 ms.

Table 1. Supported communicationinterface and protocol alternatives

Interfaces/Protocols

Ethernet100BASE-

FX LC

STconnector

IEC61850-8-1

DNP3 ●

IEC60870-5-103

● = Supported

Horizontal communication viaGOOSE for interlocking

GOOSE communication can be used forexchanging information between IEDs via theIEC 61850-8-1 station communication bus.This is typically used for sending apparatusposition indications for interlocking orreservation signals for 1-of-n control. GOOSEcan also be used to exchange any boolean,integer, double point and analog measuredvalues between IEDs.

DNP3 protocol

DNP3 (Distributed Network Protocol) is a setof communications protocols used tocommunicate data between components inprocess automation systems. For a detaileddescription of the DNP3 protocol, see theDNP3 Communication protocol manual.

IEC 60870-5-103 communicationprotocol

IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serialcommunication exchanging information witha control system, and with a data transfer rateup to 38400 bit/s. In IEC terminology, aprimary station is a master and a secondarystation is a slave. The communication isbased on a point-to-point principle. Themaster must have software that can interpretIEC 60870-5-103 communication messages.

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 31

Page 32: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

15. Hardware description

Layout and dimensions

Mounting alternatives

The following mounting alternatives areavailable (IP40 protection from the front):

• 19” rack mounting kit• Wall mounting kit• Flush mounting kit• 19" dual rack mounting kit

See ordering for details about availablemounting alternatives.

Flush mounting the IED

H

I

K

J

C

F

G

B

A

ED

IEC09000672.ai

IEC09000672 V1 EN

Figure 7. Flush mounting the IED into a panelcut-out

A 240 mm G 21.55 mm

B 21.55 mm H 220 mm

C 227 mm I 265.9 mm

D 228.9 mm J 300 mm

E 272 mm K 254 mm

F ∅6 mm

A

B

C

IEC09000673.ai

IEC09000673 V1 EN

Figure 8. Flush mounted IED

A 222 mm

B 27 mm

C 13 mm

Rack mounting the IED

A C

B

E

D

IEC09000676.ai

IEC09000676 V1 EN

Figure 9. Rack mounted IED

A 224 mm + 12 mm with ring-lug connector

B 25.5 mm

C 482.6 mm (19")

D 265.9 mm (6U)

E 13 mm

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

32 ABB

Page 33: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

A

BC

E

D

IEC09000677.ai

IEC09000677 V1 EN

Figure 10. Two rack mounted IEDs side by side

A 224 mm + 12 mm with ring-lug connector

B 25.5 mm

C 482.6 mm (19")

D 13 mm

E 265.9 mm (6U)

Wall mounting the IED

C

F

G

B

A

ED

IEC09000678.ai

IEC09000678 V1 EN

Figure 11. Wall mounting the IED

A 270 mm E 190.5 mm

B 252.5 mm F 296 mm

C ∅6.8 mm G 13 mm

D 268.9 mm

GUID-5C185EAC-13D0-40BD-8511-58CA53EFF7DE V1 EN

Figure 12. Main unit and detached LHMIdisplay

A 25.5 mm E 258.6 mm

B 220 mm F 265.9 mm

C 13 mm G 224 mm

D 265.9 mm

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 33

Page 34: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

16. Connection diagrams

1MRK006501-BB 2 PG 1.1 IEC V1 EN

Figure 13. Designation for 6U, 1/2x19" casingwith 1 TRM

Module Slot Rear Position

COM pCOM X0, X1, X4, X9,X304

PSM pPSM X307, X309, X410

TRM p2 X101, X102

BIO p3 X321, X324

BIO p4 X326, X329

BIO p5 X331, X334

BIO p6 X336, X339

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

34 ABB

Page 35: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Connection diagrams for REC650 A01

1MRK006501-DB 3 PG 1.1 IEC V1 EN

Figure 14. Communication module (COM)

1MRK006501-DB 4 PG 1.1 IEC V1 EN

Figure 15. Power supply module (PSM)48-125V DC

1MRK006501-DB 5 PG 1.1 IEC V1 EN

Figure 16. Power supply module (PSM),110-250V DC

1MRK006501-DB 6 PG 1.1 IEC V1 EN

Figure 17. Transformer module (TRM)

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 35

Page 36: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

1MRK006501-DB 7 PG 1.1 IEC V1 EN

Figure 18. Binary input/output (BIO) option(Terminal X321, X324)

1MRK006501-DB 8 PG 1.1 IEC V1 EN

Figure 19. Binary input/output (BIO) option(Terminal X326, 329)

1MRK006501-DB 9 PG 1.1 IEC V1 EN

Figure 20. Binary input/output (BIO) option(Terminal X331, 334)

Connection diagrams for REC650 A02

1MRK006501-CB 3 PG 1.1 IEC V1 EN

Figure 21. Communication module (COM)

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

36 ABB

Page 37: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

1MRK006501-CB 4 PG 1.1 IEC V1 EN

Figure 22. Power supply module (PSM)48-125V DC

1MRK006501-CB 5 PG 1.1 IEC V1 EN

Figure 23. Power supply module (PSM),110-250V DC

1MRK006501-CB 6 PG 1.1 IEC V1 EN

Figure 24. Transformer module (TRM)

1MRK006501-CB 7 PG 1.1 IEC V1 EN

Figure 25. Binary input/output (BIO) option(Terminal X321, X324)

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 37

Page 38: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

1MRK006501-CB 8 PG 1.1 IEC V1 EN

Figure 26. Binary input/output (BIO) option(Terminal X326, X329)

1MRK006501-CB 9 PG 1.1 IEC V1 EN

Figure 27. Binary input/output (BIO) option(Terminal X331, X334)

1MRK006501-CB 10 PG 1.1 IEC V1 EN

Figure 28. Binary input/output (BIO) option(X336, X339)

Connection diagrams for REC650 A07

1MRK006501-BB 3 PG 1.1 IEC V1 EN

Figure 29. Communication module (COM)

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

38 ABB

Page 39: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

1MRK006501-BB 4 PG 1.1 IEC V1 EN

Figure 30. Power supply module (PSM)48-125V DC

1MRK006501-BB 5 PG 1.1 IEC V1 EN

Figure 31. Power supply module (PSM),110-250V DC

1MRK006501-BB 6 PG 1.1 IEC V1 EN

Figure 32. Transformer module (TRM)

1MRK006501-BB 7 PG 1.1 IEC V1 EN

Figure 33. Binary input/output (BIO) option(Terminal X321, X324)

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 39

Page 40: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

1MRK006501-BB 8 PG 1.1 IEC V1 EN

Figure 34. Binary input/output (BIO) option(Terminal X326, X329)

1MRK006501-BB 9 PG 1.1 IEC V1 EN

Figure 35. Binary input/output (BIO) option(Terminal X331, X334)

1MRK006501-BB 10 PG 1.1 IEC V1 EN

Figure 36. Binary input/output (BIO) option(Terminal X336, X339)

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

40 ABB

Page 41: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

17. Technical data

General

Definitions

Referencevalue

The specified value of an influencing factor to which are referred thecharacteristics of the equipment

Nominalrange

The range of values of an influencing quantity (factor) within which, underspecified conditions, the equipment meets the specified requirements

Operativerange

The range of values of a given energizing quantity for which the equipment,under specified conditions, is able to perform its intended functionsaccording to the specified requirements

Energizing quantities, rated valuesand limits

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 41

Page 42: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Analog inputs

Table 2. Energizing inputs

Description Value

Rated frequency 50/60 Hz

Operating range Rated frequency ± 5 Hz

Current inputs Rated current, In 0.1/0.5 A1) 1/5 A2)

Thermal withstandcapability:

• Continuously 4 A 20 A

• For 1 s 100 A 500 A

• For 10 s 20 A 100 A

Dynamic currentwithstand:

• Half-wave value 250 A 1250 A

Input impedance <100 mΩ <20 mΩ

Voltage inputs Rated voltage, Un 100 V AC/ 110 V AC/ 115 V AC/ 120 V AC

Voltage withstand:

• Continuous 420 V rms

• For 10 s 450 V rms

Burden at rated voltage <0.05 VA

1) Residual current2) Phase currents or residual current

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

42 ABB

Page 43: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Auxiliary DC voltage

Table 3. Power supply

Description Type 1 Type 2

Uauxnominal 100, 110, 120, 220, 240 VAC, 50 and 60 Hz

48, 60, 110, 125 V DC

110, 125, 220, 250 V DC

Uauxvariation 85...110% of Un (85...264 V

AC)

80...120% of Un (38.4...150 V

DC)

80...120% of Un (88...300 V

DC)

Maximum load of auxiliaryvoltage supply

35 W

Ripple in the DC auxiliaryvoltage

Max 15% of the DC value (at frequency of 100 Hz)

Maximum interruption time inthe auxiliary DC voltagewithout resetting the IED

50 ms at Uaux

Binary inputs and outputs

Table 4. Binary inputs

Description Value

Operating range Maximum input voltage 300 V DC

Rated voltage 24...250 V DC

Current drain 1.6...1.8 mA

Power consumption/input <0.3 W

Threshold voltage 15...221 V DC (parametrizable in the range insteps of 1% of the rated voltage)

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 43

Page 44: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 5. Signal output and IRF output

IRF relay change over - type signal output relay

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 5 A

Make and carry for 3.0 s 10 A

Make and carry 0.5 s 30 A

Breaking capacity when the control-circuittime constant L/R<40 ms, at U< 48/110/220V DC

≤0.5 A/≤0.1 A/≤0.04 A

Table 6. Power output relays without TCS function

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 8 A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuittime constant L/R<40 ms, at U< 48/110/220V DC

≤1 A/≤0.3 A/≤0.1 A

Table 7. Power output relays with TCS function

Description Value

Rated voltage 250 V DC

Continuous contact carry 8 A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuittime constant L/R<40 ms, at U< 48/110/220V DC

≤1 A/≤0.3 A/≤0.1 A

Control voltage range 20...250 V DC

Current drain through the supervision circuit ~1.0 mA

Minimum voltage over the TCS contact 20 V DC

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

44 ABB

Page 45: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 8. Ethernet interfaces

Ethernet interface Protocol Cable Data transfer rate

LAN/HMI port (X0)1) - CAT 6 S/FTP or better 100 MBits/s

LAN1 (X1) TCP/IP protocol Fibre-optic cablewith LC connector

100 MBits/s

1) Only available for the external HMI option.

Table 9. Fibre-optic communication link

Wave length Fibre type Connector Permitted path

attenuation1)

Distance

1300 nm MM 62.5/125μm glassfibre core

LC <8 dB 2 km

1) Maximum allowed attenuation caused by connectors and cable together

Table 10. X4/IRIG-B interface

Type Protocol Cable

Screw terminal, pinrow header

IRIG-B Shielded twisted pair cableRecommended: CAT 5, Belden RS-485 (9841-9844) or Alpha Wire (Alpha 6222-6230)

Table 11. Serial rear interface

Type Counter connector

Serial port (X9) Optical serial port, type ST for IEC60870-5-103

Influencing factors

Table 12. Degree of protection of flush-mounted IED

Description Value

Front side IP 40

Rear side, connection terminals IP 20

Table 13. Degree of protection of the LHMI

Description Value

Front and side IP 42

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 45

Page 46: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 14. Environmental conditions

Description Value

Operating temperature range -25...+55ºC (continuous)

Short-time service temperature range -40...+70ºC (<16h)Note: Degradation in MTBF and HMIperformance outside the temperature rangeof -25...+55ºC

Relative humidity <93%, non-condensing

Atmospheric pressure 86...106 kPa

Altitude up to 2000 m

Transport and storage temperature range -40...+85ºC

Table 15. Environmental tests

Description Type test value Reference

Cold tests operation storage

96 h at -25ºC16 h at -40ºC 96 h at -40ºC

IEC 60068-2-1

Dry heat tests operation storage

16 h at +70ºC 96 h at +85ºC

IEC 60068-2-2

Damp heattests

steady state cyclic

240 h at +40ºChumidity 93% 6 cycles at +25 to +55ºChumidity 93...95%

IEC 60068-2-78 IEC 60068-2-30

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

46 ABB

Page 47: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Type tests according to standards

Table 16. Electromagnetic compatibility tests

Description Type test value Reference

100 kHz and 1 MHz burstdisturbance test

IEC 61000-4-18IEC 60255-22-1, level 3

• Common mode 2.5 kV

• Differential mode 1.0 kV

Electrostatic discharge test IEC 61000-4-2IEC 60255-22-2, level 4

• Contact discharge 8 kV

• Air discharge 15 kV

Radio frequency interferencetests

• Conducted, common mode 10 V (emf), f=150 kHz...80MHz

IEC 61000-4-6IEC 60255-22-6, level 3

• Radiated, amplitude-modulated

20 V/m (rms), f=80...1000MHz and f=1.4...2.7 GHz

IEC 61000-4-3IEC 60255-22-3, level 3

Fast transient disturbancetests

IEC 61000-4-4IEC 60255-22-4, class A

• Communication ports 2 kV

• Other ports 4 kV

Surge immunity test IEC 61000-4-5IEC 60255-22-5, level 3/2

• Communication 1 kV line-to-earth

• Other ports 2 kV line-to-earth, 1 kV line-to-line

Power frequency (50 Hz)magnetic field

IEC 61000-4-8, level 5

• 3 s 1000 A/m

• Continuous 100 A/m

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 47

Page 48: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 16. Electromagnetic compatibility tests, continued

Description Type test value Reference

Power frequency immunitytest

• Common mode

• Differential mode

300 V rms 150 V rms

IEC 60255-22-7, class AIEC 61000-4-16

Voltage dips and shortinterruptions

Dips:40%/200 ms70%/500 msInterruptions:0-50 ms: No restart0...∞ s : Correct behaviour atpower down

IEC 60255-11IEC 61000-4-11

Electromagnetic emissiontests

EN 55011, class AIEC 60255-25

• Conducted, RF-emission(mains terminal)

0.15...0.50 MHz < 79 dB(µV) quasi peak< 66 dB(µV) average

0.5...30 MHz < 73 dB(µV) quasi peak< 60 dB(µV) average

• Radiated RF-emission

30...230 MHz < 40 dB(µV/m) quasi peak,measured at 10 m distance

230...1000 MHz < 47 dB(µV/m) quasi peak,measured at 10 m distance

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

48 ABB

Page 49: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 17. Insulation tests

Description Type test value Reference

Dielectric tests: IEC 60255-5

• Test voltage 2 kV, 50 Hz, 1 min1 kV, 50 Hz, 1 min,communication

Impulse voltage test: IEC 60255-5

• Test voltage 5 kV, unipolar impulses,waveform 1.2/50 μs, sourceenergy 0.5 J1 kV, unipolar impulses,waveform 1.2/50 μs, sourceenergy 0.5 J, communication

Insulation resistancemeasurements

IEC 60255-5

• Isolation resistance >100 MΏ, 500 V DC

Protective bonding resistance IEC 60255-27

• Resistance <0.1 Ώ (60 s)

Table 18. Mechanical tests

Description Reference Requirement

Vibration response tests(sinusoidal)

IEC 60255-21-1 Class 2

Vibration endurance test IEC60255-21-1 Class 1

Shock response test IEC 60255-21-2 Class 1

Shock withstand test IEC 60255-21-2 Class 1

Bump test IEC 60255-21-2 Class 1

Seismic test IEC 60255-21-3 Class 2

Product safety

Table 19. Product safety

Description Reference

LV directive 2006/95/EC

Standard EN 60255-27 (2005)

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 49

Page 50: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

EMC compliance

Table 20. EMC compliance

Description Reference

EMC directive 2004/108/EC

Standard EN 50263 (2000)EN 60255-26 (2007)

Current protection

Table 21. Instantaneous phase overcurrent protection PHPIOC

Function Range or value Accuracy

Operate current (5-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Operate time 20 ms typically at 0 to 2 x Iset -

Reset time 35 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time 10 ms typically at 0 to 10 x Iset -

Reset time 45 ms typically at 10 to 0 x Iset -

Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

50 ABB

Page 51: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 22. Four step phase overcurrent protection OC4PTOC

Function Setting range Accuracy

Operate current (5-2500)% of lBase ± 1.0% of Ir at I ≤ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Min. operating current (1-10000)% of lBase ± 1.0% of Ir at I ≤ Ir ±1.0%

of I at I > Ir

Independent time delay (0.000-60.000) s ± 0.5% ±25 ms

Minimum operate timefor inverse characteristics

(0.000-60.000) s ± 0.5% ±25ms

Inverse characteristics,see table 65, table 66 andtable 67

17 curve types See table 65, table 66 andtable 67

Operate time,nondirectional startfunction

20 ms typically at 0 to 2 x Iset -

Reset time, nondirectionalstart function

30 ms typically at 2 to 0 x Iset -

Operate time, directionalstart function

30 ms typically at 0 to 2 x Iset -

Reset time, directionalstart funciton

25 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 51

Page 52: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 23. Instantaneous residual overcurrent protection EFPIOC

Function Range or value Accuracy

Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Operate time 20 ms typically at 0 to 2 x Iset -

Reset time 30 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time 10 ms typically at 0 to 10 x Iset -

Reset time 40 ms typically at 10 to 0 x Iset -

Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

52 ABB

Page 53: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 24. Four step residual overcurrent protection EF4PTOC

Function Range or value Accuracy

Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Operate current fordirectional comparison

(1–100)% of lBase ± 1.0% of Ir

Min. operating current (1-10000)% of lBase ± 1.0% of Ir at I < Ir ±

1.0% of I at I < Ir

Minimum operate timefor inverse characteristics

(0.000-60.000) s ± 0.5% ± 25 ms

Timers (0.000-60.000) s ± 0.5% ±25 ms

Inverse characteristics,see table 65, table 66 andtable 67

17 curve types See table 65, table 66 andtable 67

Minimum polarizingvoltage

(1–100)% of UBase ± 0.5% of Ur

Minimum polarizingcurrent

(2-100)% of IBase ±1.0% of Ir

Real part of source Zused for currentpolarization

(0.50-1000.00) W/phase -

Imaginary part of sourceZ used for currentpolarization

(0.50–3000.00) W/phase -

Operate time, non-directional start function

30 ms typically at 0.5 to 2 x Iset -

Reset time, non-directional start function

30 ms typically at 2 to 0.5 x Iset -

Operate time, directionalstart function

30 ms typically at 0,5 to 2 x IN -

Reset time, directionalstart function

30 ms typically at 2 to 0,5 x IN -

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 53

Page 54: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 25. Sensitive directional residual overcurrent and power protection SDEPSDE

Function Range or value Accuracy

Operate level for 3I0·cosjdirectional residualovercurrent

(0.25-200.00)% of lBase At low setting:(2.5-10) mA(10-50) mA

± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir ±0.5 mA±1.0 mA

Operate level for 3I0·3U0

· cosj directional residualpower

(0.25-200.00)% of SBase At low setting:(0.25-5.00)% of SBase

± 1.0% of Sr at S £ Sr

± 1.0% of S at S > Sr

± 10% of set value

Operate level for 3I0 and

j residual overcurrent

(0.25-200.00)% of lBase At low setting:(2.5-10) mA(10-50) mA

± 1.0% of Ir at £ Ir± 1.0% of I at I > Ir ±0.5 mA±1.0 mA

Operate level for non-directional overcurrent

(1.00-400.00)% of lBase At low setting:(10-50) mA

± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir ± 1.0 mA

Operate level for non-directional residualovervoltage

(1.00-200.00)% of UBase ± 0.5% of Ur at U£Ur

± 0.5% of U at U > Ur

Residual release currentfor all directional modes

(0.25-200.00)% of lBase At low setting:(2.5-10) mA(10-50) mA

± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir ±0.5 mA± 1.0 mA

Residual release voltagefor all directional modes

(1.00 - 300.00)% of UBase ± 0.5% of Ur at U£Ur

± 0.5% of U at U > Ur

Reset ratio > 95% -

Timers (0.000-60.000) s ± 0.5% ±25 ms

Inverse characteristics,see table 65, table 66 andtable 67

17 curve types See table 65, table 66 andtable 67Class 5 + 150 ms

Relay characteristic angleRCA

(-179 to 180) degrees ± 2.0 degrees

Relay open angle ROA (0-90) degrees ± 2.0 degrees

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

54 ABB

Page 55: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 25. Sensitive directional residual overcurrent and power protection SDEPSDE,continued

Function Range or value Accuracy

Operate time, non-directional residual overcurrent

80 ms typically at 0.5 to 2 x Iset -

Reset time, non-directional residual overcurrent

90 ms typically at 1.2 to 0.5 x Iset -

Operate time, non-directional residualovervoltage

70 ms typically at 0.8 to 1.5 x Uset -

Reset time, non-directional residualovervoltage

120 ms typically at 1.2 to 0.8 x Uset -

Operate time, directionalresidual over current

260 ms typically at 0.5 to 2 x Iset -

Reset time, directionalresidual over current

170 ms typically at 2 to 0.5 x Iset -

Critical impulse time non-directional residual overcurrent

100 ms typically at 0 to 2 x Iset

20 ms typically at 0 to 10 x Iset

--

Impulse margin time non-directional residual overcurrent

25 ms typically -

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 55

Page 56: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 26. Thermal overload protection, one time constant LPTTR

Function Range or value Accuracy

Reference current (0-400)% of IBase ± 1.0% of Ir

Reference temperature (0-600)°C ± 1.0°C

Operate time:

2 2

2 2ln p

b

I It

I It

æ ö-ç ÷= ×ç ÷-è ø

EQUATION1356 V1 EN (Equation 1)

I = actual measuredcurrentIp = load current before

overload occursIb = base current, IBase

Time constant t = (0–1000) minutes

IEC 60255-8, class 5 + 200 ms

Alarm temperature (0-200)°C ± 2.0% of heat content trip

Trip temperature (0-600)°C ± 2.0% of heat content trip

Reset level temperature (0-600)°C ± 2.0% of heat content trip

Table 27. Breaker failure protection CCRBRF

Function Range or value Accuracy

Operate phase current (5-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio, phase current > 95% -

Operate residual current (2-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio, residual current > 95% -

Phase current level forblocking of contact function

(5-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Timers (0.000-60.000) s ± 0.5% ±10 ms

Operate time for currentdetection

35 ms typically -

Reset time for currentdetection

10 ms maximum -

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

56 ABB

Page 57: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 28. Stub protection STBPTOC

Function Range or value Accuracy

Operating current (1-2500)% of IBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Operating time 20 ms typically at 0 to 2 x Iset -

Resetting time 30 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Table 29. Pole discordance protection CCRPLD

Function Range or value Accuracy

Operate value, currentasymmetry level

(0-100) % ± 1.0% of Ir

Reset ratio >95% -

Time delay (0.000-60.000) s ± 0.5% ± 25 ms

Table 30. Broken conductor check BRCPTOC

Function Range or value Accuracy

Minimum phase current foroperation

(5–100)% of IBase ± 1.0% of Ir

Unbalance current operation (50-90)% of maximumcurrent

± 2.0% of Ir

Timer (0.00-60.000) s ± 0.5% ± 25 ms

Operate time for start function 35 ms typically -

Reset time for start function 30 ms typically -

Critical impulse time 15 ms typically -

Impulse margin time 10 ms typically -

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 57

Page 58: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 31. Directional over/underpower protection GOPPDOP, GUPPDUP

Function Range or value Accuracy

Power level (0.0–500.0)% of SBase ± 1.0% of Sr at S < Sr

± 1.0% of S at S > Sr1)

(1.0-2.0)% of SBase < ± 50% of set value 2)

(2.0-10)% of SBase < ± 20% of set value 3)

Characteristic angle (-180.0–180.0) degrees 2 degrees

Timers (0.010 - 6000.000) s ± 0.5% ± 25 ms

1) Accuracy valid for 50 Hz. At 60 Hz both accuracies are ±2.0%2) Accuracy valid for 50 Hz. At 60 Hz the accuracy is -50/+100%3) Accuracy valid for 50 Hz. At 60 Hz the accuracy is ±40%

Table 32. Negative sequence based overcurrent function DNSPTOC

Function Range or value Accuracy

Operate current (2.0 - 5000.0) % of IBase ± 1.0% of Ir at I <Ir± 1.0% of I at I > Ir

Reset ratio > 95 % -

Low voltage level for memory (0.0 - 5.0) % of UBase < ± 0,5% of Ur

Relay characteristic angle (-180 - 180) degrees ± 2,0 degrees

Relay operate angle (1 - 90) degrees ± 2,0 degrees

Timers (0.00 - 6000.00) s ± 0.5% ± 25 ms

Operate time, non-directional 30 ms typically at 0 to 2 x Iset

20 ms typically at 0 to 10 x Iset

-

Reset time, non-directional 40 ms typically at 2 to 0 x Iset -

Operate time, directional 30 ms typically at 0 to 2 x Iset

20 ms typically at 0 to 10 x Iset

-

Reset time, directional 40 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset

2 ms typically at 0 to 10 x Iset

-

Impulse margin time 15 ms typically -

Dynamic overreach < 10% at t = 300 ms -

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

58 ABB

Page 59: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Voltage protection

Table 33. Two step undervoltage protection UV2PTUV

Function Range or value Accuracy

Operate voltage, low andhigh step

(1–100)% of UBase ± 0.5% of Ur

Reset ratio <105% -

Inverse time characteristicsfor low and high step, seetable 69

- See table 69

Definite time delay, step 1 (0.00 - 6000.00) s ± 0.5% ± 25 ms

Definite time delays, step 2 (0.000-60.000) s ± 0.5% ±25 ms

Minimum operate time,inverse characteristics

(0.000–60.000) s ± 0.5% ± 25 ms

Operate time, start function 30 ms typically at 2 to 0.5 x Uset -

Reset time, start function 40 ms typically at 0.5 to 2 x Uset -

Critical impulse time 10 ms typically at 2 to 0 x Uset -

Impulse margin time 15 ms typically -

Table 34. Two step overvoltage protection OV2PTOV

Function Range or value Accuracy

Operate voltage, low andhigh step

(1-200)% of UBase ± 0.5% of Ur at U < Ur

± 0.5% of U at U > Ur

Reset ratio >95% -

Inverse time characteristicsfor low and high step, seetable 68

- See table 68

Definite time delay, step 1 (0.00 - 6000.00) s ± 0.5% ± 25 ms

Definite time delays, step 2 (0.000-60.000) s ± 0.5% ± 25 ms

Minimum operate time,Inverse characteristics

(0.000-60.000) s ± 0.5% ± 25 ms

Operate time, start function 30 ms typically at 0 to 2 x Uset -

Reset time, start function 40 ms typically at 2 to 0 x Uset -

Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 59

Page 60: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 35. Two step residual overvoltage protection ROV2PTOV

Function Range or value Accuracy

Operate voltage, step 1 (1-200)% of UBase ± 0.5% of Ur at U < Ur

± 0.5% of U at U > Ur

Operate voltage, step 2 (1–100)% of UBase ± 0.5% of Ur at U < Ur

± 0.5% of U at U > Ur

Reset ratio >95% -

Inverse time characteristicsfor low and high step, seetable 70

- See table 70

Definite time setting, step 1 (0.00–6000.00) s ± 0.5% ± 25 ms

Definite time setting, step 2 (0.000–60.000) s ± 0.5% ± 25 ms

Minimum operate time forstep 1 inverse characteristic

(0.000-60.000) s ± 0.5% ± 25 ms

Operate time, start function 30 ms typically at 0 to 2 x Uset -

Reset time, start function 40 ms typically at 2 to 0 x Uset -

Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -

Table 36. Loss of voltage check LOVPTUV

Function Range or value Accuracy

Operate voltage (0–100)% of UBase ± 0.5% of Ur

Reset ratio <105% -

Pulse timer (0.050–60.000) s ± 0.5% ± 25 ms

Timers (0.000–60.000) s ± 0.5% ± 25 ms

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

60 ABB

Page 61: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Frequency protection

Table 37. Under frequency protection SAPTUF

Function Range or value Accuracy

Operate value, start function (35.00-75.00) Hz ± 2.0 mHz

Operate value, restore frequency (45 - 65) Hz ± 2.0 mHz

Operate time, start function At 50 Hz: 200 ms typically at fset

+0.5 Hz to fset -0.5 Hz

At 60 Hz: 170 ms typically at fset

+0.5 Hz to fset -0.5 Hz

-

Reset time, start function At 50 Hz: 60 ms typically at fset -0.5

Hz to fset +0.5 Hz

At 60 Hz: 50 ms typically at fset -0.5

Hz to fset +0.5 Hz

-

Operate time delay (0.000-60.000)s <250 ms

Restore time delay (0.000-60.000)s <150 ms

Table 38. Overfrequency protection SAPTOF

Function Range or value Accuracy

Operate value, start function (35.00-75.00) Hz ± 2.0 mHz atsymmetricalthree-phasevoltage

Operate time, start function At 50 Hz: 200 ms typically at fset

-0.5 Hz to fset +0.5 Hz

At 60 Hz: 170 ms at fset -0.5 Hz to

fset +0.5 Hz

-

Reset time, start function At 50 and 60 Hz: 55 ms typically atfset +0.5 Hz to fset-0.5 Hz

-

Timer (0.000-60.000)s <250 ms

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 61

Page 62: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 39. Rate-of-change frequency protection SAPFRC

Function Range or value Accuracy

Operate value, start function (-10.00-10.00) Hz/s ± 10.0 mHz/s

Operate value, restore enablefrequency

(45.00 - 65.00) Hz ± 2.0 mHz

Timers (0.000 - 60.000) s <130 ms

Operate time, start function At 50 Hz: 100 ms typicallyAt 60 Hz: 80 ms typically

-

Secondary system supervision

Table 40. Current circuit supervision CCSRDIF

Function Range or value Accuracy

Operate current (5-200)% of Ir ± 10.0% of Ir at I £ Ir± 10.0% of I at I > Ir

Block current (5-500)% of Ir ± 5.0% of Ir at I £ Ir± 5.0% of I at I > Ir

Table 41. Fuse failure supervision SDDRFUF

Function Range or value Accuracy

Operate voltage, zero sequence (1-100)% of UBase ± 1.0% of Ur

Operate current, zero sequence (1–100)% of IBase ± 1.0% of Ir

Operate voltage, negativesequence

(1–100)% of UBase ± 0.5% of Ur

Operate current, negativesequence

(1–100)% of IBase ± 1.0% of Ir

Operate voltage change level (1–100)% of UBase ± 5.0% of Ur

Operate current change level (1–100)% of IBase ± 5.0% of Ir

Operate phase voltage (1-100)% of UBase ± 0.5% of Ur

Operate phase current (1-100)% of IBase ± 1.0% of Ir

Operate phase dead line voltage (1-100)% of UBase ± 0.5% of Ur

Operate phase dead line current (1-100)% of IBase ± 1.0% of Ir

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

62 ABB

Page 63: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 42. Breaker close/trip circuit monitoring TCSSCBR

Function Range or value Accuracy

Operate time delay (0.020 - 300.000) s ± 0,5% ± 110 ms

Control

Table 43. Synchronizing, synchrocheck and energizing check SESRSYN

Function Range or value Accuracy

Phase shift, jline - jbus (-180 to 180) degrees -

Voltage ratio, Ubus/Uline 0.2 to 5.0 -

Frequency difference limit betweenbus and line

(0.003-1.000) Hz ± 2.0 mHz

Phase angle difference limitbetween bus and line

(5.0-90.0) degrees ± 2.0 degrees

Voltage difference limit betweenbus and line

± 0.5% of Ur

Time delay output for synchrocheck (0.000-60.000) s ± 0.5% ± 25 ms

Time delay for energizing check (0.000-60.000) s ± 0.5% ± 25 ms

Closing time for the circuit breaker (0.000-60.000) s ± 0.5% ± 25 ms

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 63

Page 64: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 44. Autorecloser SMBRREC

Function Range or value Accuracy

Number of autoreclosing shots 1 - 5 -

Autoreclosing open time:shot 1 - t1 3Ph

(0.000-60.000) s

± 0.5% ± 25 ms

shot 2 - t2 3Phshot 3 - t3 3Phshot 4 - t4 3Phshot 5 - t5 3Ph

(0.00-6000.00) s

Autorecloser maximum wait time for sync (0.00-6000.00) s

Maximum trip pulse duration (0.000-60.000) s

Inhibit reset time (0.000-60.000) s

Reclaim time (0.00-6000.00) s

Minimum time CB must be closed before ARbecomes ready for autoreclosing cycle

(0.00-6000.00) s

CB check time before unsuccessful (0.00-6000.00) s

Wait for master release (0.00-6000.00) s

Wait time after close command beforeproceeding to next shot

(0.000-60.000) s

Logic

Table 45. Tripping logic SMPPTRC

Function Range or value Accuracy

Trip action 3-ph -

Timers (0.000-60.000) s ± 0.5% ± 10 ms

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

64 ABB

Page 65: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 46. Configurable logic blocks

Logic block Quantity with cycle time Range or value Accuracy

5 ms 20 ms 100 ms

AND 60 60 160 - -

OR 60 60 160 - -

XOR 10 10 20 - -

INVERTER 30 30 80 - -

SRMEMORY 10 10 20 - -

RSMEMORY 10 10 20 - -

GATE 10 10 20 - -

PULSETIMER 10 10 20 (0.000–90000.000) s ± 0.5% ± 25 ms

TIMERSET 10 10 20 (0.000–90000.000) s ± 0.5% ± 25 ms

LOOPDELAY 10 10 20

Table 47. Configurable logic Q/T

Logic block Quantity with cycletime

Range orvalue

Accuracy

20 ms 100 ms

ANDQT 20 100 - -

ORQT 20 100 - -

XORQT 10 30 - -

INVERTERQT 20 100 - -

RSMEMORYQT 10 30 - -

SRMEMORYQT 15 10 - -

PULSETIMERQT 10 30 (0.000–90000.000) s

± 0.5% ± 25 ms

TIMERSETQT 10 30 (0.000–90000.000) s

± 0.5% ± 25 ms

INVALIDQT 6 6 - -

INDCOMBSPQT 10 10 - -

INDEXTSPQT 10 10 - -

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 65

Page 66: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Monitoring

Table 48. Measurements CVMMXN

Function Range or value Accuracy

Voltage (0.1-1.5) ×Ur ± 0.5% of Ur at U£Ur

± 0.5% of U at U > Ur

Connected current (0.2-4.0) × Ir ± 0.5% of Ir at I £ Ir± 0.5% of I at I > Ir

Active power, P 0.1 x Ur< U < 1.5 x Ur

0.2 x Ir < I < 4.0 x Ir

± 1.0% of Sr at S ≤ Sr

± 1.0% of S at S > Sr

1)

Reactive power, Q 0.1 x Ur< U < 1.5 x Ur

0.2 x Ir < I < 4.0 x Ir

± 1.0% of Sr at S ≤ Sr

± 1.0% of S at S > Sr

1)

Apparent power, S 0.1 x Ur < U < 1.5 x Ur

0.2 x Ir< I < 4.0 x Ir

± 1.0% of Sr at S ≤ Sr

± 1.0% of S at S > Sr

Apparent power, S Threephase settings

cos phi = 1 ± 0.5% of S at S > Sr

± 0.5% of Sr at S ≤ Sr

Power factor, cos (φ) 0.1 x Ur < U < 1.5 x Ur

0.2 x Ir< I < 4.0 x Ir

< 0.02 2)

1) Accuracy valid for 50 Hz. At 60 Hz both accuracies are ±2.0%2) Accuracy valid for 50 Hz. At 60 Hz the accuracy is <0.04.

Table 49. Event counter CNTGGIO

Function Range or value Accuracy

Counter value 0-10000 -

Max. count up speed 10 pulses/s -

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

66 ABB

Page 67: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 50. Disturbance report DRPRDRE

Function Range or value Accuracy

Current recording - ± 1,0% of Ir at I ≤ Ir± 1,0% of I at I > Ir

Voltage recording - ± 1,0% of Ur at U ≤

Ur

± 1,0% of U at U >Ur

Pre-fault time (0.05–3.00) s -

Post-fault time (0.1–10.0) s -

Limit time (0.5–8.0) s -

Maximum number of recordings 100, first in - first out -

Time tagging resolution 1 ms See timesynchronizationtechnical data

Maximum number of analog inputs 30 + 10 (external +internally derived)

-

Maximum number of binary inputs 96 -

Maximum number of phasors in the TripValue recorder per recording

30 -

Maximum number of indications in adisturbance report

96 -

Maximum number of events in the Eventrecording per recording

150 -

Maximum number of events in the Eventlist

1000, first in - first out -

Maximum total recording time (3.4 srecording time and maximum number ofchannels, typical value)

340 seconds (100recordings) at 50 Hz, 280seconds (80 recordings)at 60 Hz

-

Sampling rate 1 kHz at 50 Hz1.2 kHz at 60 Hz

-

Recording bandwidth (5-300) Hz -

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 67

Page 68: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 51. Event list DRPRDRE

Function Value

Buffer capacity Maximum number of events inthe list

1000

Resolution 1 ms

Accuracy Depending on timesynchronizing

Table 52. Indications DRPRDRE

Function Value

Buffer capacity Maximum number of indications presentedfor single disturbance

96

Maximum number of recorded disturbances 100

Table 53. Event recorder DRPRDRE

Function Value

Buffer capacity Maximum number of events in disturbance report 150

Maximum number of disturbance reports 100

Resolution 1 ms

Accuracy Depending ontimesynchronizing

Table 54. Trip value recorder DRPRDRE

Function Value

Buffer capacity

Maximum number of analog inputs 30

Maximum number of disturbance reports 100

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

68 ABB

Page 69: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 55. Disturbance recorder DRPRDRE

Function Value

Buffer capacity Maximum number of analog inputs 40

Maximum number of binary inputs 96

Maximum number of disturbance reports 100

Maximum total recording time (3.4 s recording time andmaximum number of channels, typical value)

340 seconds (100 recordings)at 50 Hz280 seconds (80 recordings) at60 Hz

Table 56. Station battery supervision SPVNZBAT

Function Range or value Accuracy

Lower limit for the batteryterminal voltage

(60-140) % of Ubat ± 1.0% of set battery voltage

Reset ratio, lower limit <105 % -

Upper limit for the batteryterminal voltage

(60-140) % of Ubat ± 1.0% of set battery voltage

Reset ratio, upper limit >95 % -

Timers (0.000-60.000) s ± 0.5% ± 110 ms

Table 57. Insulation gas monitoring function SSIMG

Function Range or value Accuracy

Pressure alarm 0.00-25.00 -

Pressure lockout 0.00-25.00 -

Temperature alarm -40.00-200.00 -

Temperature lockout -40.00-200.00 -

Timers (0.000-60.000) s ± 0.5% ± 110 ms

Table 58. Insulation liquid monitoring function SSIML

Function Range or value Accuracy

Alarm, oil level 0.00-25.00 -

Oil level lockout 0.00-25.00 -

Temperature alarm -40.00-200.00 -

Temperature lockout -40.00-200.00 -

Timers (0.000-60.000) s ± 0.5% ± 110 ms

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 69

Page 70: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 59. Circuit breaker condition monitoring SSCBR

Function Range or value Accuracy

Alarm levels for open andclose travel time

(0-200) ms ± 0.5% ± 25 ms

Alarm levels for number ofoperations

(0 - 9999) -

Setting of alarm for springcharging time

(0.00-60.00) s ± 0.5% ± 25 ms

Time delay for gas pressurealarm

(0.00-60.00) s ± 0.5% ± 25 ms

Time delay for gas pressurelockout

(0.00-60.00) s ± 0.5% ± 25 ms

Metering

Table 60. Pulse counter PCGGIO

Function Setting range Accuracy

Cycle time for report ofcounter value

(1–3600) s -

Table 61. Function for energy calculation and demand handling ETPMMTR

Function Range or value Accuracy

Energy metering MWh Export/Import,MVArh Export/Import

Input from MMXU. No extra errorat steady load

Hardware

IED

Table 62. Degree of protection of flush-mounted IED

Description Value

Front side IP 40

Rear side, connection terminals IP 20

Table 63. Degree of protection of the LHMI

Description Value

Front and side IP 42

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

70 ABB

Page 71: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Dimensions

Table 64. Dimensions

Description Value

Width 220 mm

Height 265.9 mm (6U)

Depth 249.5 mm

Weight box <10 kg (6U)

Weight LHMI 1.3 kg (6U)

Inverse time characteristics

Table 65. ANSI Inverse time characteristics

Function Range or value Accuracy

Operating characteristic:

( )1= + ×

-

æ öç ÷ç ÷è ø

P

At B k

I

EQUATION1249-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01unless otherwise stated

-

ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 ANSI/IEEE C37.112,class 5 + 40 ms

ANSI Very inverse A=19.61, B=0.491, P=2.0

ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46

ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02

ANSI Long Time ExtremelyInverse

A=64.07, B=0.250, P=2.0

ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0

ANSI Long Time Inverse k=(0.05-999) in steps of 0.01A=0.086, B=0.185, P=0.02

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 71

Page 72: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 66. IEC Inverse time characteristics

Function Range or value Accuracy

Operating characteristic:

( )1= ×

-

æ öç ÷ç ÷è ø

P

At k

I

EQUATION1251-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01 -

IEC Normal Inverse A=0.14, P=0.02 IEC 60255-151,class 5 + 40 ms

IEC Very inverse A=13.5, P=1.0

IEC Inverse A=0.14, P=0.02

IEC Extremely inverse A=80.0, P=2.0

IEC Short time inverse A=0.05, P=0.04

IEC Long time inverse A=120, P=1.0

Table 67. RI and RD type inverse time characteristics

Function Range or value Accuracy

RI type inverse characteristic

1

0.2360.339

= ×

-

t k

I

EQUATION1137-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01 IEC 60255-151,class 5 + 40 ms

RD type logarithmic inversecharacteristic

5.8 1.35= - ×æ öç ÷è ø

tI

Ink

EQUATION1138-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01 IEC 60255-151,class 5 + 40 ms

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

72 ABB

Page 73: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 68. Inverse time characteristics for overvoltage protection

Function Range or value Accuracy

Type A curve:

=- >

>

æ öç ÷è ø

tk

U U

U

EQUATION1436-SMALL V1 EN

U> = Uset

U = Umeasured

k = (0.05-1.10) in steps of0.01 unless otherwise stated

Class 5 +40 ms

Type B curve:

2.0

480

32 0.5 0.035

- >× - -

>

æ öç ÷è ø

tk

U U

U

EQUATION1437-SMALL V1 EN

k = (0.05-1.10) in steps of0.01 unless otherwise stated

Type C curve:

3.0

480

32 0.5 0.035

- >× - -

>

æ öç ÷è ø

tk

U U

U

EQUATION1438-SMALL V1 EN

k = (0.05-1.10) in steps of0.01 unless otherwise stated

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 73

Page 74: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 69. Inverse time characteristics for undervoltage protection

Function Range or value Accuracy

Type A curve:

=< -

<

æ öç ÷è ø

kt

U U

U

EQUATION1431-SMALL V1 EN

U< = Uset

U = UVmeasured

k = (0.05-1.10) in steps of0.01 unless otherwise stated

Class 5 +40 ms

Type B curve:

2.0

4800.055

32 0.5

×= +

< -× -

<

æ öç ÷è ø

kt

U U

U

EQUATION1432-SMALL V1 EN

U< = Uset

U = Umeasured

k = (0.05-1.10) in steps of0.01 unless otherwise stated

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

74 ABB

Page 75: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Table 70. Inverse time characteristics for residual overvoltage protection

Function Range or value Accuracy

Type A curve:

=- >

>

æ öç ÷è ø

tk

U U

U

EQUATION1436-SMALL V1 EN

U> = Uset

U = Umeasured

k = (0.05-1.10) insteps of 0.01

Class 5 +40 ms

Type B curve:

2.0

480

32 0.5 0.035

- >× - -

>

æ öç ÷è ø

tk

U U

U

EQUATION1437-SMALL V1 EN

k = (0.05-1.10) insteps of 0.01

Type C curve:

3.0

480

32 0.5 0.035

- >× - -

>

æ öç ÷è ø

tk

U U

U

EQUATION1438-SMALL V1 EN

k = (0.05-1.10) insteps of 0.01

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 75

Page 76: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

18. Ordering

GuidelinesCarefully read and follow the set of rules to ensure problem-free order management.Please refer to the available functions table for included application functions.

To obtain the complete ordering code, please combine code from the tables, as given in the example below.

Exemple code: REC650*1.1-A01X00-X00-B1A5-B-A-SA-AB1-RA3-AAAA-E. Using the code of each position #1-11specified as REC650*1-2 2-3-4 4-5-6-7 7-8-9 9-10 10 10 10-11

# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 - 10 - 11

REC650* - - - - - - - - -

Posi

tion

SOFTWARE #1 Notes and Rules

Version number

Version no 1.1

Selection for position #1. 1.1

Configuration alternatives #2 Notes and Rules

Single breaker for single busbar, IEC A01

Single breaker for double busbar, IEC A02

Bus coupler for double busbar, IEC A07

ACT configuration

ABB standard configuration X00

Selection for position #2. X00

Software options #3 Notes and Rules

No option X00

Selection for postition #3 X00

First HMI language #4 Notes and Rules

English IEC B1

Selection for position #4.

Additional HMI language #4

No second HMI language X0

Chinese A5

Selection for position #4. B1

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

76 ABB

Page 77: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Casing #5 Notes and Rules

Rack casing, 6 U 1/2 x 19" B

Selection for position #5. B

Mounting details with IP40 of protection from the front #6 Notes and Rules

No mounting kit included X

Rack mounting kit for 6 U 1/2 x 19" A

Wall mounting kit for 6U 1/2 x 19" D

Flush mounting kit for 6U 1/2 x 19" E

Wall mounting bracket 6U 1/2 x 19" G

Selection for position #6.

Connection type for Power supply, Input/outputand Communication modules

#7 Notes and Rules

Compression terminals S

Ringlug terminals R

Power supply

Slot position:

pPSM

100-240V AC, 110-250V DC, 9BO A

48-125V DC, 9BO B

Selection for position #7.

Human machine interface #8 Notes and Rules

Local human machine interface, OL3000, IEC6U 1/2 x 19", Basic

A

Detached LHMI

No detached mounting of LHMI X0

Detached mounting of LHMI incl. Ethernet cable, 1m B1

Detached mounting of LHMI incl. Ethernet cable, 2m B2

Detached mounting of LHMI incl. Ethernet cable, 3m B3

Detached mounting of LHMI incl. Ethernet cable, 4m B4

Detached mounting of LHMI incl. Ethernet cable, 5m B5

Selection for position #8. A

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 77

Page 78: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Connection type for Analog modules #9 Notes and Rules

Compression terminals S

Ringlug terminals R

Analog system

Slot position: p2

Transformer module, 6I + 4U 1/5A, 100/220V A1 Only for A07

Transformer module, 4I, 1/5A+1I, 0.1/0.5A+5U,100/220V

A3 A01 and A02

Selection for position #9.

Binary input/output module

#10 Notes and Rules

Slot position (rear view) p3

p4

p5

p6

Available slots in 1/2 case

No board in slot X

Binary input/output module 9 BI, 3 NOTrip, 5 NO Signal, 1 CO Signal

A A A A p6 optional for A01p6 = A for A02/A07

Selection for position #10. A A A

Communication and processing module

#11 Notes and Rules

Slot position (rear view)

pCO

M

14BI, IRIG-B, Ethernet, LC, ST B

Selection for position #11. B

Accessories

Rack mounting kit for 2 x 6U 1/2 x 19" Quantity: 1KHL400240R0001

Configuration and monitoring tools

Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA

LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA

LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

78 ABB

Page 79: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Manuals

Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical manual,Installation manual, Commissioning manual, Application manual, Communication protocol manual,DNP, Communication protocol manual, IEC61850, Communication protocol manual, IEC60870-5-103,Type test certificate, Engineering manual and Point list manual, DNP3, Connectivity packages and LEDlabel template is always included for each IED.

Rule: Specify additional quantity of IED Connect CD requested

User documentation Quantity: 1MRK 003 500-AA

Rule: Specify the number of printed manuals requested

Operation manual IEC Quantity: 1MRK 500 093-UEN

Technical manual IEC Quantity: 1MRK 511 247-UEN

Commissioning manual IEC Quantity: 1MRK 511 248-UEN

Application manual IEC Quantity: 1MRK 511 246-UEN

Communication protocol manual, DNP3 IEC Quantity: 1MRK 511 241-UEN

Communication protocol manual, IEC 61850 IEC Quantity: 1MRK 511 242-UEN

Communication protocol manual, IEC 60870-5-103 IEC Quantity: 1MRK 511 243-UEN

Engineering manual IEC Quantity: 1MRK 511 245-UEN

Installation manual IEC Quantity: 1MRK 514 014-UEN

Point list manual, DNP3 IEC Quantity: 1MRK 511 244-UEN

Reference information

For our reference and statistics we would be pleased to be provided with the following application data:

Country: End user:

Station name: Voltage level: kV

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

ABB 79

Page 80: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Related documents

Documents related to REC650 Identity number

Application manual 1MRK 511 246-UEN

Technical manual 1MRK 511 247-UEN

Commissioning manual 1MRK 511 248-UEN

Product Guide 1MRK 511 249-BEN

Type test certificate 1MRK 511 249-TEN

650 series manuals Identity number

Communication protocol manual, DNP3 1MRK 511 241-UEN

Communication protocol manual, IEC 61850 1MRK 511 242-UEN

Communication protocol manual, IEC 60870-5-103 1MRK 511 243-UEN

Point list manual, DNP3 1MRK 511 244-UEN

Engineering manual 1MRK 511 245-UEN

Operation manual 1MRK 500 093-UEN

Installation manual 1MRK 514 014-UEN

Bay control REC650 1MRK 511 249-BEN -Product version: 1.1 Issued: February 2011

80 ABB

Page 81: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

81

Page 82: Bay control REC650 Product Guide - ABB Ltd · 52PD PD DRP RDRE Mont. V MMXU Meter. IEC61850 ANSI IEC Function Enabled in Settings 132 kV Bus 1000/1 132kV/110V 132kV/110V OC4 PTOC

Contact us

ABB ABSubstation Automation ProductsSE-721 59 Västerås, SwedenPhone +46 (0) 21 32 50 00Fax +46 (0) 21 14 69 18

www.abb.com/substationautomation

1MR

K 5

11 2

49-B

EN

Cop

yrig

ht 2

011

AB

B. A

ll rig

hts

rese

rved

.