basic operation mcdonnell and miller

Upload: gbogboiwe

Post on 04-Apr-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    1/1812

    BASIC SYSTEM OPERATION

    heyve been with us for over two hundred years, and

    most of the time, theyre so reliable most folks dont

    give them much thought. They sit in buildings all over the

    world, transferring heat from fuel to water, allowing us to

    warm our buildings or complete our processes.

    Steam boilers are simple, efficient and reliable. No

    machine does a better job of moving BTUs from one

    place to another. Weve used them for space heating

    since before the United States Civil War in 1861.

    Even before the Civil War, we used steam boilers for

    industrial processes. Today we use them to run factories,

    press clothes, wash dishes, pasteurize milk, sterilize

    medical equipment, and to heat entire cities! Their capa-

    bilities seem endless.

    But despite its simplicity, any steam boiler can run into

    trouble if its control system doesnt act properly. If the

    energy you put into the boiler exceeds what the boilercan absorb, the boiler can rupture. So you must always

    be on guard.

    A simple safety relief valve of the right capacity and

    relief-pressure setting protects the boiler from over pres-

    sure. But over pressure isnt the only thing that can

    threaten a steam boiler. There are also the dangers of

    dry firing.

    Should the internal water level drop too low, the boiler

    can burn out. So here too, you must always be on guard.

    You see, a steam boiler needs its water to move the heat

    away from its metal surfaces. Without the right internallevel of water, heat quickly accumulates. Too much heat

    creates a very dangerous operating condition.

    Boiler manufacturers have always set up minimum safe

    water level requirements for their equipment. Our con-

    trols help enforce those requirements in two ways:

    By maintaining a minimum safe water level in

    the boiler.

    By signaling the burner to stop should the water

    level drop below that point.

    In this brief Systems Guide we will explain how we do

    these two very important jobs.

    Whats a Normal Water Level?

    The proper steam boiler water level varies from manufac-

    turer to manufacturer, but generally, we can say that its

    normal to start by manually filling the boiler to the two-

    thirds-full point on the gauge glass. As the boiler oper-

    ates, the water will quickly turn to steam and head out

    toward the system (Fig. B).

    Steaming takes place at a constant rate of about one-half

    gpm per 240,000 BTU/HR (D.O.E. Heating Capacity

    T

    Gauge Glass Two-Thirds Full

    Steam Boiler

    Steam Boilers

    Fig. A

    Fig. B

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    2/18 13

    BASIC SYSTEM OPERATION

    Rating). This is a law of physics so it doesnt vary from

    manufacturer to manufacturer. If youre working with a

    boiler with a rating of, say, 1,000,000 BTU/HR, you can

    be assured the water is turning to steam and leaving that

    boiler at the rate of about two gpm. And its leaving at

    speeds measured in miles per hour (sometimes

    exceeding 60 mph!). So its very important for your near-boiler piping to be correct. If its not, the fast moving

    steam will pull water out of the boiler and create

    problems for you in the system and the boiler.

    As the water (in the form of steam) heads out toward the

    system, the water level in the boiler will, of course, drop.

    How far it drops, depends a lot on the size and condition

    of your piping system. You see, ideally, the water should

    begin to return to the boiler before the boilers internal

    water line drops to a critical point. Thats the point at

    which the low water cut-off will cut power to the burner, or

    an automatic water feeder will open.

    Because the water is in the system piping and radiating

    during operation, the normal water level becomes a point

    thats somewhere in the lower-third of the gauge glass

    (Fig. C).

    Remember, youre working with a rangeof operation

    here, not a fixed point. If the water were to stay at the top

    of the gauge glass all the while the burner was firing, you

    probably wouldnt be making steam! So dont get too

    caught up with the word normal because the only thing

    thats normal is that the water level will rise and fall.

    Boiler manufacturers, as we said before, doestablish aminimum safe water level for their boilers, however. That

    point is usually just out of sight of the bottom of the

    gauge glass. Should the water level drop to this point, the

    boiler may be in danger of overheating. We have to find a

    way to protect the boiler from itself (Fig. D).

    All leading authorities and insurance companies

    recognize this need. The ASME Code for Low Pressure

    Heating Boilers, for instance, specifies, Each

    automatically fired steam or vapor steam boiler shall be

    equipped with an automatic low water fuel cut-off.The

    device the code refers to is what most people in the field

    commonly call a low water cut-off. Its job is to stop theburner and protect the boiler.

    What Causes a Low Water

    Condition?ecause its an open system, some evaporative water

    loss is normal for a steam system. How much

    depends on the size and condition of the system. If

    youre losing too much water, however, its time to begin

    troubleshooting. There are many places to look.

    B

    Minimum SafeWater Level

    Gauge Glass One-Third Full

    Gauge Glass Minimum Safe Water Level

    Fig. C

    Fig. D

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    3/1814

    BASIC SYSTEM OPERATION

    Here are a few good places to start:

    The air vents are dirty, not seating properly, and

    passing steam to the atmosphere.

    Someone left the boiler blowdown valve partially open.

    Someone, for whatever reason, has been drawing

    hot water from the boiler.

    The relief valve has discharged.

    The condensate pump isnt working as it should.

    The float may have come loose.

    The condensate may be too hot to pump.

    (Check those steam traps!)

    Improper near-boiler piping may be throwing water

    up into the system, or causing the waterline to tilt

    during operation.

    The wet returns may be leaking. (Always suspect

    anyburied pipe).

    A check valve may be stuck closed or partially closed.

    The boiler may be foaming and priming.

    Check the pH of the water. It should be between

    7 and 9.

    Check the condition of the water. Dirty water will

    prime and foam.

    Check the burners firing rate. Over-firing can

    cause priming.

    The pipes may not be properly pitched.

    The automatic feeder may not be working properly.

    Its chamber may be filled with sediment.

    Its feed line may be clogged.

    All of the condensate may not be returning from the

    system (a common problem with process applications).

    The boiler metal may be corroded and leaking at

    the water line.

    Flood the boiler to its header to check for leaks.

    Good troubleshooters take the time to look over the

    entire system before deciding whats wrong. Take the

    time to do it right, and you ll be the person with the

    answers.

    Watching the Water Levelhe best way to prevent overheating damage to a boiler

    is to stop the burner if the water level falls too low. Thisis the low water cut-offs job. There are several types of

    low water cut-offs you can use. Lets look at them.

    Float Operated Low Water Cut-Offs

    Float operated low water cut-offs have been around

    (Fig. E) since the 1920s and have earned a reputation

    worldwide for reliability. Usually, youll mount this type of

    low water cut-off directly in the boilers gauge glass

    tappings. We make quick hook-up fittings for these units

    to simplify installation.

    T

    Series 67 Float Type Low Water Cut-Off

    Fig. E

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    4/18 15

    BASIC SYSTEM OPERATION

    The water level in the low water cut-offs chamber will

    mimic the water level in the boiler. As the water level

    drops in the boiler during steaming, the level in the

    chamber, and the cut-offs float drops with it. Should the

    float drop to the boilers critical low water cut-off point, the

    float will trip an electrical switch thats wired in series with

    the burner. The burner instantly stops firing. It will stay offuntil the water level rises to a safe operating point.

    This happens when the condensate returns from the

    system or when an automatic water feeder or a boiler

    attendant adds water to the boiler. When the level

    reaches a safe position, the low water cut-off will make its

    electrical connection and the burner will restart.

    When a steam system is well balanced, the low water

    cut-offs job is to stand by and wait. The situation we just

    described suggests that theres something out of balance

    in that system. Well look at this again in a few minutes.

    Probe and Float Type Built-In Low Water Cut-Offs

    There are some jacketed boilers that dont easily accept

    quick hook-up fittings. These boilers will often have a

    tapping for a built-in low water cut-off. These built-in units

    do the same thing as the external units we just looked at,

    but instead of being in a chamber, the built-ins are right

    inside the boiler where they can sense the water level

    directly.

    We make two types of built-in low water cut-offs:

    Probes The boiler manufacturer will specify the point

    where theyd like to have this type of low water cut-offinserted. It will usually sit just below the water line, at a

    point above the boilers crown. A probe uses the boilers

    water to complete an electrical circuit past an insulator

    (the center portion of the probe) back to a ground (the

    threaded portion of the probe). As long as water covers

    the probe an electronic go signal will travel to the

    burner. When water drops off the probe for a continuous

    ten seconds, an electronic stop signal goes to the

    burner, shutting it down and protecting the boiler from a

    low water condition.

    At ITT McDonnell & Miller, we manufacture several

    different types of probe low water cut-offs to meet any ofyour job applications (Fig. F).

    One of those applications might involve the boilers water

    level. The water capacity of todays boilers is

    considerably less than that of boilers from decades ago.

    Along with this, the water level operating range of todays

    boilers is smaller. Further, the amplitude of surging water

    levels is increasing. As a result, the low water cut-off

    must be smart enough to recognize these variations

    and react appropriately. We have done this by

    Series PS-800 Probe Type Low Water Cut-Off

    Fig. F

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    5/1816

    BASIC SYSTEM OPERATION

    incorporating delay features in the probes operating

    logic. These include a delay on break feature (DOB)

    which keeps the burner lit for 10 seconds after water

    leaves the probe. This minimizes the effects of a surging

    water line. Another additionthe delay on make feature

    (DOM)allows an additional feed time of 15 seconds

    once water comes in contact with the probe. Thisminimizes rapid burner and feeder cycling by slightly

    elevating the water level so that water lost to steaming

    will return (in the form of condensate) before the water

    level drops below the probe.

    Float Type In operation, these are similar to the

    external, float operated low water cut-offs we looked at

    before. The difference is that instead of sensing a

    duplicated water level outsidethe boiler, these units

    sense the level directly inside the boiler.

    We make them for you in five mounting-barrel sizes

    (Series 69) to accommodate different boiler insulationthicknesses. When you select a built-in, float type control

    make sure it fits as far as possible into the boiler, without

    the float shield coming contact with the boiler.

    When a low water cut-off stops a burner, it also stops the

    entire heating system. Nothing will happen until the water

    in the boiler returns to a safe operating level.

    While this is very good for the boiler, it may not be the

    best thing for the system. If the heat in the building is off

    for too long a time, water pipes may begin to freeze.

    This is where automatic water feeders come in. An

    automatic feeder will maintain a safe minimum waterlevel in the boiler and keep it operating, even if the

    system is leaking. It keeps the system operating

    automatically until you can make the repairs.

    Combination Low Water Cut-Offs and

    Automatic Water Feeders

    Two of our most popular and versatile feeders are the

    Uni-Match and the 101A (Fig. G and H). These are ideal

    for use in residential or small commercial applications.

    They are versatile in that they are compact and they are

    easily installed to operate with either a probe type OR afloat type low water cut-off. These feeders are always

    ready to add water when given the signal from the low

    water cut-off. The benefits they offer are the convenience

    of not having to manually add waterand most

    importantlythey will protect the boiler from a dry fire

    condition by maintaining a safe minimum water level in

    the boiler should a system leak occur.

    If you use a mechanical automatic water feeder, you can

    keep your burner operating even during a power failure.

    Uni-Match Water Feeder

    Series 101-A Water Feeder

    Fig. G

    Fig. H

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    6/18 17

    BASIC SYSTEM OPERATION

    A mechanical feeder can also protect a boiler (Fig. I)

    should a fuel-regulating device malfunction, causing the

    burner to lock in and stay there. Or suppose someone

    jumps-out a control, putting the burner on continuous

    operation. A mechanical automatic water feeder will

    continue to feed the boiler whenever the level drops to

    the feed point.

    Under normal circumstances, the electrical low water cut-

    off (the second part of the feeder/cut-off combination) is

    always standing by, ready to shut off the burner should

    something go wrong with the automatic feeder.

    An automatic water feeder doesnt feed at the two-thirds

    full point on the gauge glass. You set this by hand when

    you first start the system. As we said before, the normal

    level will range up and down as the system operates. An

    automatic feeder will maintain a safe minimumwater line

    only. By doing this, it will lessen the possibility of human

    error.Consider this. A boiler attendant might put too much

    water in a steam boiler. He doesnt have an automatic

    feeder and hes tired of checking the water level every

    day so he fills the boiler to the two-thirds full point while

    its operating. When the condensate returns, the boiler

    floods. By adding water the attendant has limited the

    boilers steam-making space. Without enough room to

    break free of the water, the steam will now carry water up

    into the system piping. This leads to higher fuel bills,

    uneven heating, water hammer, scale formation in the

    boiler and burner short-cycling. Suddenly, problems

    plague this system, and no one is sure why.Automatic water feeders help you avoid these problems.

    They watch that water level, maintaining a safe minimum.

    They allow the boiler water line to rise and fall naturally

    through its normal operating range.

    How a Feeder/Cut-Off Combination Works

    During Normal Operation This is how a McDonnell &

    Miller feeder/cut-off combination looks on a steam boiler

    (Fig. J). Notice how we have it installed well below the

    boilers normal start-up operating range (thats about

    two-thirds up the gauge glass). We don t want it to feed

    while the water is out in the system as steam.

    Remember, the automatic water feeder is there to

    maintain a safe minimum water line, not a normal, start-

    up water line.

    As you now see it in the drawing, the feeder is closed

    and the burner is firing. The boiler is working, sending

    steam out to the building, and both the automatic water

    feeder and low water cut-off are standing by.

    The Feeder Opens If the boilers water line drops to the

    feeder/cut-off combinations feeder-operating point (which

    is very near the bottom of the gauge glass) (Fig. K), the

    feed valve will open mechanically and add water to the

    BurnerOn

    City Water Supply

    ReturnMain

    Feeder Cut-OffCombination

    Steam Boiler

    City Water Supply

    ReturnMain

    Feeder Cut-OffCombination

    Steam BoilerBurnerOn

    Normal Operation

    Feeder Open & Burner On

    Series 47-2 Combination Mechanical

    Water Feeder/Low Water Cut-Off

    Fig. I

    Fig. J

    Fig. K

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    7/1818

    BASIC SYSTEM OPERATION

    boiler. How much water will enter the boiler depends on

    several things, but there will always be enough to keep

    the boiler operating at a safe minimumwater level. Once

    it has added the right amount of water, the feeder closes.

    While this is happening, the burner continues to run

    because the feeder keeps the boiler from dropping to itslow water cut-off point.

    The Low Water Cut-Off Stops the Burner But suppose

    something happens and the automatic water feeder cant

    keep up with the rate at which the boiler is losing water.

    Suppose, for instance, that a pipe breaks or someone

    opens a boiler drain, causing the boiler to suddenly lose

    water. Should this happen, the water level will drop to a

    preset point, and the automatic feeder/cut-off

    combination will instantly cut power to the burner,

    shutting it down and protecting the boiler from a dry-firing

    condition. Though the burner is off, the automatic feeder

    will continue to add water to the boiler in an attempt torestore a safe minimum water level (Fig. L).

    As you can see, a combination mechanicalwater feeder

    and electricallow water cut-off provides you with boiler

    protection even if the power fails or something goes

    wrong in the burner circuitry.

    Combination Water Feeders and Low Water

    Cut-Offs for Larger Boilers

    As we said earlier, all steam boilers evaporate water at

    the rate of one-half gpm per 1,000 square feet EDR

    (240,000 BTU/HR). To satisfy a larger boiler s needs, anautomatic water feeder must be able to match the boilers

    higher steaming rate. If the feeder cant keep up, the

    burner will suffer from nuisance low water shutdowns. To

    avoid this problem, we make automatic feeder/cut-off

    combinations with wider flow orifices to meet the special

    needs of larger boilers. The operation of these larger

    units is the same as the ones we just looked at. The key

    difference is the increased flow rate (Fig. M).

    Once the larger feeder/cut-off combination satisfies the

    boilers minimum water line needs, it has to be able to

    close against the force of the city water pressure moving

    through that extra wide orifice. This calls for considerable

    float and lever power, and it explains why our feeder/cut-

    off combinations for larger boilers are bigger than those

    for smaller boilers. Weve carefully engineered them to

    get the maximum closing force in the space we have to

    work with. This ensures the unit will close tightly once its

    done its job (Fig. N).

    Codes call for larger boilers to have their gauge glasses

    mounted on water columns, rather than directly into the

    boiler. Consequently, we make our larger automatic

    BurnerOn

    ReturnMain

    City Water Supply

    Steam Boiler

    Feeder Cut-OffCombination

    Large Boilers

    Series 51-2 Mechanical Water Feeder

    City Water Supply

    ReturnMain

    Feeder Cut-OffCombination

    Steam BoilerBurner

    Off

    Feeder Open & Burner Off

    Fig. L

    Fig. M

    Fig. N

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    8/18

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    9/1820

    BASIC SYSTEM OPERATION

    condensate receiver. When the water level inside the

    receiver reaches a certain point, an electrical float switch

    turns the pump on. The pump quickly moves the water

    out of the receiver and back into the boiler.

    Steam boilers served by condensate pumps also need

    low water protection, and our low water cut-offs serve thatpurpose well. You can also use an automatic water feeder

    or a combination feeder/cut-off on these systems. But

    before you do, make sure the system is well balanced.

    What we mean by well balanced is that the condensate

    pump should be able to return the water to the boiler

    before the boilers water level drops to a point where the

    low water cut-off or automatic feeder goes into action.

    If the automatic water feeder adds water to the boiler (to

    maintain a safe minimum operating level), and thenthe

    condensate pump returns its water to the boiler, the

    boiler will most likely wind up with too much water. This

    excess water limits the boilers steam making space.Without enough room to break free of the water, the

    steam can carry water up into the system piping. That

    leads to higher fuel bills, uneven heating, water hammer,

    scale formation in the boiler and burner short cycling.

    So before you use an automatic water feeder on a steam

    boiler thats served by a condensate pump, check to see

    if the system is well balanced. It should run through its

    cycles without going off on low water. In other words, the

    condensate pump should balance the flow of water back

    into the boiler before the level drops to the critical, low

    water point. Keep in mind that a system with a

    condensate pump can become unbalanced if the returnsclog with sediment or if any steam traps fail in an open

    position.

    Good troubleshooters always keep their eyes wide open.

    Steam Systems with Boiler-Feed Pumps

    If you have a system where some steam is going for

    process (meaning, it wont be coming back), or if your

    system isnt well balanced, you should consider using a

    boiler feed pump instead of a condensate pump.

    A boiler feed pump serves the same purpose as a

    condensate pump (Fig. Q). It provides the push thewater needs to get back into the boiler. The difference

    between a condensate pump and a boiler feed pump,

    however, lies in the way we control the two units. Instead

    of having an electrical float switch inside the condensate

    receiver, a boiler feed pump takes its orders from a

    McDonnell & Miller pump controller mounted directly on

    the boiler.

    The pump controller has two switches. The first switch

    (set at the higher of the two levels) operates the boiler

    feed pump. When the boiler needs water, the pump

    SteamBoiler

    Feeder Cut-OffCombination

    Pump Controller

    City WaterSupply

    Boiler Feed Pump Make-Up WaterFeeder

    BurnerOn

    BoilerFeedTank

    BurnerOn

    SteamBoiler

    City WaterSupply

    Boiler Feed Pump

    Pump Control andLow Water Cut-Off

    Make-Up WaterFeeder

    BoilerFeedTank

    Single BoilerFeeder/Cut-Off CombinationUnbalanced System

    Single BoilerUnbalanced System

    Fig. R

    Fig. Q

    controller recognizes the need and starts the pump.

    When the boiler water returns to the proper level in the

    gauge glass, the pump controller stops the pump.

    Should the pump not be able to keep up with the boilers

    need for water, the pump controller will sense this as

    well. The second switch (set at the lower of the two

    levels) will cut the electricity to the burner and protect the

    boiler from a low water condition (Fig. R).

    Feed water enters the system through a make-up water

    feeder in the boiler feed pumps receiver. If you wish, you

    can add a feeder/cut-off combination to operate at a level

    a bit lower than the pump controller. This will give you a

    mechanically operated feeder, which will act as a back-

    up should something go wrong with the pump controller.

    It will also give you a secondary low water cut-off. Its like

    having a belt andsuspenders for your boiler!

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    10/18 21

    BASIC SYSTEM OPERATION

    Meeting the Needs of Systems

    with Multiple Steam Boilers(Fig. S, T U)

    he boiler on the right may be a stand-by to the boiler

    on the left. Every week or so, a boiler attendant

    might switch them, making this one the operating boiler

    and the other the stand by.

    Its a good idea, one weve used for years in larger boiler

    rooms. By having more than one boiler, each is able to

    supply the entire needs of the system. Your chances of

    getting caught without steam are much less.

    Some systems have multiple steam boilers. The idea

    here is to let several boilers join forces to meet the total

    needs of the system. The goal is energy conservation.

    You steam all the boilers on start-up, and then shut a fewdown after youve heated the system and satisfied the

    piping pick-up load. In other words, you put the system

    on simmer after youve heated it completely.

    Steam systems with more than one boiler often have

    problems if the installer fails to realize that steam is

    dynamic and not static. By this, we mean that steam is

    always moving veryquickly from the boiler to the system,

    and as it moves, it loses pressure. And since one ounce

    of pressure represents a water column 13/4 in. (45mm)

    high, the slightest difference in pressure between any

    two boilers interconnected on their return sides can make

    a big difference in the individual water levels.

    A slight burr in a pipe or fitting can create a drop in

    pressure. You can never tune two burners to produce the

    same flame. One boiler will always be closer to the

    system take-off than another. These things speak loudly

    for proper piping and thoughtful management of the

    boiler water line so thats what well look at next.

    T

    Multiple Boiler Systems with a Boiler Feed

    Pump and Motorized Return Valves

    Here we have two boilers served by a single boiler feed

    pump (Fig. S). One boiler may be a stand by to the other

    or they may be sharing the total load. For piping

    purposes, wed handle either application the same way.

    Notice how the condensate returns are independent.

    Each flows from the boiler feed pump receiver to the

    boiler through a motorized valve. This is an important

    detail. If you were to interconnect the returns, the water

    from one boiler would flow into the other.

    Steam Moves Remember, steam is dynamic, not static

    Water doesnt seek its own level when the steam is

    moving out of the boiler. The slightest difference in firing

    rate or piping pressure drop between the two boilers will

    cause one to flood and the other to shut down due to a

    low water condition. This is why those independentreturns are important. Were using motorized valves on

    this installation (Fig. S) to isolate one boiler from the

    other. When either boiler needs water, the McDonnell &

    Miller pump controller on that boiler will drop to a point

    where it will close the higher of its two switches. That

    switch will power that boilers motorized valve, causing it

    to open. When its fully opened, the motorized valve will

    trip an end switch and start the boiler feed pump. Water

    will flow only to the boiler that needs it. The float in the

    pump controller will sense the rising water. When the

    water reaches the proper level, the pump controller will

    break the electrical connection to the motorized valve.

    The valve will begin to close, shutting off the boiler feed

    pump as it does.

    As you can see, when we pipe multiple boilers this way it

    doesnt matter how big or small each is. The boiler feed

    pump, although sized for the totalneeds of all the boilers

    will satisfy the needs of each in turn, no matter what size

    Keeping the Water Flowing Weve installed a make-up

    water feeder in the boiler feed pumps receiver tank. Its

    job is to maintain a minimum water line in the tank so the

    pump will always have a reservoir from which it can draw

    feed water. In this system, all the water will enter the

    boilers through the boiler feed pump. If, for any reason,the boiler feed pump cant keep up with the boilers rate

    of evaporation, the water line in the boiler will drop. The

    lower switch in the McDonnell & Miller pump controller

    will stop the burner.

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    11/1822

    BASIC SYSTEM OPERATION

    BurnerOn

    BurnerOn

    Pump Control andLow Water Cut-Off

    Pump Control andLow Water Cut-Off

    MotorizedValve MotorizedValve

    SteamBoilerNo. 1

    SteamBoilerNo. 2

    City Water Supply

    Make-Up WaterFeeder

    Boiler Feed Tank

    BoilerFeed Pump

    Multiple BoilersBoiler Feed Pump and Motorized Valves

    Feeder Cut-OffCombination

    Feeder Cut-OffCombination

    MotorizedValve

    MotorizedValve

    BurnerOn

    BurnerOn

    SteamBoilerNo.2

    SteamBoilerNo.1

    City Water Supply

    Boiler Feed Tank

    BoilerFeeder Pump

    Make-Up WaterFeeder

    Pump Controller Pump Controller

    Multiple BoilersBoiler Feed Pump, Motorized Valve & Water Feeders

    ElectricProportioning

    Regulator

    ElectricProportioning

    RegulatorHigh Water

    Cut-Off and AlarmHigh Water

    Cut-Off and Alarm

    SteamBoilerNo. 1

    SteamBoilerNo. 2

    Motor OperatedProportioning Valve

    Motor OperatedProportioning Valve

    BalancingValve

    BalancingValve

    Boiler Feed Tank

    City Water Supply

    Make-Up WaterFeederBoiler Feed Pump

    Pump Return By-passWith Balancing ValveOrifice Or Relief Valve

    Multiple BoilersBoiler Feed Pump, Electric Proportioning Regulators and Motorized Valves

    Fig. S

    Fig. T

    Fig. U

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    12/18 23

    BASIC SYSTEM OPERATION

    If you find the pump suddenly cant keep up with the

    boilers needs, check the temperature of the returning

    condensate. As thermostatic radiator steam traps and

    end of main F&T traps age and fail, they pass steam into

    the returns. That can make the condensate hot enough

    to flash when it hits the pumps impeller. Boiler feed

    pumps cant move water once it has flashed to steam.

    The pump will turn and cavitate, but it wont satisfy the

    boiler.

    Ideally, in a low pressure steam heating system, the

    condensate in the pumps receiver shouldnt be hotter

    than 180F (82C).

    Multiple Boiler Systems with a Boiler Feed

    Pump, Motorized Return Valves and Boiler

    Water Feeders (Fig. T)

    This is the same system we just looked at, except weve

    added a combination automatic water feeder and lowwater cut-off to a point just below the pump controller.

    The feeder/cut-offs job will be to add water mechanically

    to the boiler should something happen to the boiler feed

    pump (for instance, if its cavitating because the return

    condensate is too hot).

    Think of the feeder/cut-off as a back-up device to keep

    the boiler in operation should something go wrong

    elsewhere. The low water cut-off will back up the pump

    controllers primary low water cut-off should something

    go wrong there, or if the feeder cant keep up with the

    boilers rate of evaporation for some reason.

    Multiple Boiler Systems with a Boiler Feed

    Pump, Motorized Return Valves and Electric

    Proportioning Regulator (Fig. U)

    Here were controlling the water lines with electric

    proportioning regulators. Were matching the incoming

    feed water to the exact amount of water thats leaving assteam. By doing this, were able to maintain a precise

    water line in both boilers and take advantage of each

    boilers full steaming space.

    There are times when steaming loads will vary

    tremendously. This is especially true of steam heating

    systems in larger buildings. We often set up these

    buildings to operate on outdoor air temperature sensors

    and night set-back devices. When the system first starts

    in the morning the boilers will steam longer than they will

    during the day when the pipes and radiators are hot. This

    is also true of seasonal operation when you run the

    heating system less often.

    This is when proportioning regulators can make a big

    difference. By closely monitoring the water line,

    regardless of varying system conditions, you improve the

    quality of steam leaving the boiler and allow the system

    to operate more efficiently.

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    13/18

    Receiver Tank Controlf you size a boiler feed pumps receiver properly it will

    be able to hold the right amount of water to keep the

    boiler operating during the start-up cycles. It will also be

    able to receive the returning condensate without

    overflowing.

    Receiver sizing is more an art than a science. You have

    to look closely at the entire system to figure out how long

    it will take the condensate to return from the building.

    There are many variables to consider: The type and

    condition of steam traps, the pitch and cleanliness of

    steam mains and returns, the pipe insulation or lack of it,

    the shape of the building and how people use it.

    There are also the times when youll have to deal with

    condensate transfer pumps, or maybe a vacuum/con-

    densate pump. These pumps collect and relay return

    water back to the boiler feed pump. There are manythings that can affect how quickly these secondary

    pumps move condensate back to the primary boiler feed

    pump. You have to consider them all when youre sizing

    a feed pump receiver.

    One thing will be a constant, however. There must

    always be enough water in the receiver for the boiler to

    draw from during the start-up cycle (the time between

    initial steaming and the return of condensate from the

    building). A McDonnell & Miller make-up feeder, set at

    the one-third full point on the receiver tank, will meet the

    boilers needs during this crucial start-up time. Lets take

    a closer look at these.

    Receiver Tank Make-Up Water Feeders

    Here, weve mounted a McDonnell & Miller make-upwater feeder on a one-inch NPT equalizing line thatextends from the top of the tank to the bottom. The level

    in the feeders chamber will be the same as the level inthe tank. As the pump moves water out of the tank and

    into the boiler, the float inside the feeders chamber willopen and constantly replenish the tanks reservoir.

    Weve designed our feeders with the right amount of float

    and lever power to close tightly against city water

    pressure. This ensures that there will always be enoughtank space to receive the returning condensate without

    having it overflow.

    If the tank youre using doesnt have tappings for an

    equalizing line, you can use our internal feeder (Fig. V).

    As you can see, it mounts directly inside the tank and

    feeds water through its integral strainer. We make this

    unit with two flange sizes for both new and retrofit

    installations.

    24

    BASIC SYSTEM OPERATION

    I

    Condensate Receiver Tank

    City Water Supply

    Model 21

    Make-Up Water

    Feeder

    Make-Up Water Feeder

    Fig. V

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    14/18 25

    BASIC SYSTEM OPERATION

    City Water Supply

    Make-Up WaterFeeder

    BoilerFeed Pump

    Low Water

    Cut-OffCondensate Receiver Tank

    Low Water Cut-Offon Receiver Tank

    City WaterSupply

    Cond. Return

    Needle Valve

    Diaphragm Valve

    Check Valve

    Model 25AMake-Up Water

    Feeder

    Large Condensate Receiver Tank

    Make-Up Water FeederUsed as Pilot Valve

    Large Condensate Receiver Tank

    Motorized ValveCity Water

    Supply

    Model 93Controller

    Make-Up Water Feederand Motorized Valve

    A Make-Up Water Feeder Used as a Pilot Valve(Fig. W)

    When you have multiple boilers, the boiler feed pump has

    to be able to meet the needs of allthe boilers should they

    need water simultaneously. During the start-up cycle, the

    draw from the feed pumps receiver can be very heavyand the make-up feeder has to be able to match that flow.

    When we run into this situation, we often use a make-up

    water feeder as a pilot valve to operate a high capacity

    diaphragm valve with dead-end service. When the

    feeder opens it signals the diaphragm valve to snap into

    action. The larger valve quickly maintains the receiver at

    the one-third full point. Once the feed pump shuts off the

    dead-end service valve closes tightly to prevent over

    filling. If returned condensate fills the receiver, the feed

    valve, of course, stays closed. This piping arrangement

    also gives you a lot of freedom because you can put the

    diaphragm valve in a remote location, if youd like, foreasier service.

    A Make-Up Water Feeder with a Motorized Valve(Fig. X)

    Heres another way you can quickly fill the receiver. Use

    a McDonnell & Miller controller to sense the tanks water

    line. As the level rises and falls, the controller will

    electrically operate a high capacity motorized valve. This

    is another piping arrangement that gives you a lot of

    freedom. You can place that motorized valve anywhere

    youd like.

    Low Water Cut-Offs for Receiver Tanks(Fig. Y)

    Theres always the possibility for human error on any job.

    For instance, suppose someone decides to turn off the

    water supply to your receiver tank. The pump controller

    on the boiler will still start the pump, but once the receiver

    goes dry there wont be any water to pump because of

    the closed valve. Or suppose the building loses water

    pressure and the feed pump suddenly finds itself moving

    more water than the water feeder can replace. If the

    pump runs dry, it will cavitate and its mechanical seal will

    quickly heat and break. That leaves you with a costlyrepair and system down time.

    If you install a low water cut-off in an equalizing line

    around the tank, the cut-off will protect the pump no

    matter what happens.

    Fig. W

    Fig. X

    Fig. Y

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    15/1826

    BASIC SYSTEM OPERATION

    BurnerOn

    Compression Tank

    ColdWater

    SupplyLow Water

    Fuel Cut-OffSeries 63

    Test-N-Check

    Valves

    Blow DownValve

    Hot Water Boiler

    ASME ReliefValve

    Series 850 or 900Low WaterCut-Offs

    ReturnMain

    Supply Main

    Hot Water Boiler

    Hot Water Boilersow water protection isnt just for steam boilers. Hot

    water boilers face the same perils of overheating

    damage if the water line drops too low. Many people

    dont think of this as often as they should because hot

    water boilers serve closed systems. They havepressure reducing valves that are supposed to feed

    water automatically should a leak develop.

    The truth, however, is that a pressure reducing valve is no

    substitute for a low water cut-off. Pressure reducing, or

    feed valves, often clog with sediment and wind up not

    feeding at all. A buried pipe can corrode and spring a leak

    that flows faster than a feed valve can satisfy. Relief

    valves can pop and, while dumping water at a great rate,

    actually prevent the feed valve from operating.

    Lets take a closer look at how we can protect these boilers.

    Hot Water Systems (Fig. Z)

    As we said, the things that affect steam boilers also affect

    hot water boilers. If you run them with too much water the

    relief valve will open. If you run them with too little water

    theyll overheat and suffer damage.

    A low water cut-off is the only sure way of protecting a hot

    water boiler from sudden loss of water. The ASME boiler

    code recognizes this by requiring all hot water boilers of

    400,000 BTU/HR or more input to have low water fuel cut-

    off devices.

    ASME doesnt call for low water cut-offs on smaller,residential boilers, but we think allhot water boilers,

    regardless of their size, must have protection. However,

    the International Mechanical Code requires low water cut-

    offs on ALL hot water and steam boilers. ITT McDonnell

    & Miller make several devices, both float and probe type,

    that protect and meet the needs of any boiler whether its

    cast iron, steel, or copper construction (Fig. AA, BB, CC).

    Hot water systems regularly lose water through faulty air

    vents, loose valve stem packing, cracked boiler sections,

    loose nipples, corroded pipes, broken or loose pump seals,

    leaking gaskets, dripping relief valves, to name just a few

    places. Most installers depend on their pressure reducingor feed valve, to replace the lost water automatically. But

    feed valves often clog with sediment, especially in hard

    water areas. And its very easy to close the supply valve to

    a feed valve and forget to open it again.

    Fig. Z

    On systems with buried pipes (say, a radiant heating

    system) a feed valve will open if a pipe breaks. It will feed

    fresh water continuously until it either clogs (and stops

    feeding) or destroys the ferrous components of the

    system with oxygen corrosion. A simple feed valve can

    wind up costing a lot more than its purchase price. This is

    why major suppliers of feed valves, such as ITT Bell &

    Gossett, recommend you close the feed valve once

    youve established your initial fill pressure.

    This is also why we strongly recommend you use a low

    water cut-off on every hot water boiler. Feed valves are

    not a substitute for low water cut-offs. They can't protect

    your boilers from a low water condition. Feed valves are

    fine for filling the system initially, and for helping you vent

    air from the radiators. But once the system is up and

    running, you shouldnt look to them for protection.

    L

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    16/18 27

    BASIC SYSTEM OPERATION

    Series PS-851 Probe Type Low Water Cut-Off

    Series 67 Float Type Low Water Cut-Off

    Series RB-24 Probe Type Low Water Cut-Off

    Over firing

    There are times when hot water boilers dont lock-out on

    safety. Whether by control failure or human error, things

    go wrong. And when they go wrong in a hot water

    heating system, the water temperature can rise quickly to

    a point where the compression tank cant take up theexpansion of the water. This causes the relief valve to

    discharge.

    When the relief valve opens, theres a sudden drop in

    system pressure. The water, which at this point is

    probably much hotter than 212F (100C), will flash into

    steam. This is why ASME insists that relief valves for hot

    water boilers carry steam-discharge ratings.

    If a feed valve doesnt open to replace this rapidly exiting

    water, a low water condition will quickly result. The only

    thing that can protect the boiler at this point is a low water

    cut-off. The feed valve cant protect the boiler because itstypical setting is 12 psig (.83 bar). In other words, the

    system pressure must drop below 12 psig (.83 bar)

    before the feed valve will open.

    The trouble is that while the relief valve is open and

    flashing steam to atmosphere, the internal system

    pressure never drops anywhere near 12 psig (.83 bar). A

    relief valve with a 30 psig (2.1 bar) setting, for instance,

    will open at 30 psig (2.1 bar), and close again when the

    pressure drops to about 26 psig (1.79 bar). The result is

    a loss of water with no make-up. Repeat this cycle

    enough times and the boiler will be in a dangerous, low

    water condition. Keep in mind, steam exerts pressure. Itcan easily fool a feed valve, and thats why feed valves

    offer very little protection at all against low water.

    Fig. AA

    Fig. BB

    Fig. CC

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    17/1828

    BASIC SYSTEM OPERATION

    CirculatingPump

    Cold Water Supply

    Pressure ReducingValve with Built-inCheck Valve

    Return fromSystem

    Relief Valve

    Compression Tank

    Flow

    Flow Switch Zone ControlValves

    Flow Bypass Line

    Compression Tank

    City WaterSupply

    Feeder Cut-OffCombination

    Model 247-2, 51-2,51-S-2, 53-2

    WaterLevel

    Return

    Test-n-Check

    Valves

    Blow DownValve

    BurnerOn

    ASME ReliefValve

    Supply Main

    Series 850 or 900Low WaterCut-Offs

    Return

    Series FS4-3 Flow Switch

    (shown without paddle)

    Hot Water Boiler

    Copper Fin Tube Boiler

    Feeder/Cut-Off Combinations for Cast Iron

    and Steel Hot Water Boilers (Fig. DD)

    To protect a boiler from dry firing, the low water cut-off

    must located above the boilers crown. After the low

    water cut-off shuts off the burner, you should have a way

    to add water to the system to ensure the crown staysunder water.

    A combination water feeder and low water cut-off can do

    this for you. If you position the feeder above the boilers

    crown, it will mechanically feed water if the level should

    drop to that point. This is an important consideration

    because, even if the electricity is cut off, its possible for

    the firing cycle to continue if the fuel feed valve is

    mechanically locked open. The combination units cut-off

    switch will act as a back-up to the primary low water cut-

    off, providing the boiler with additional protection.

    Protecting Copper Fin Tube Boilers (Fig. EE)Copper fin tube boilers move heat from the flame to the

    water almost instantly. This type of boiler depends on the

    proper flow of water across its heat exchanger to move

    the heat quickly out of the boiler and into the system.

    Should flow stop while the burner is operating, heat will

    quickly build and cause the water in the heat exchanger

    to flash into steam. This condition is similar to a dry firing

    in a cast iron or steel boiler.

    A McDonnell & Miller flow switch, installed on the copper

    fin tube boilers hot water outlet, protects it from this

    danger (Fig. FF). The burner cannot fire unless water ismoving across the flow switch. When the flow stops, for

    whatever reason, the McDonnell & Miller flow switch

    immediately cuts electrical power to the burner and

    protects the boiler from overheating.

    Fig. FF

    Fig. DD

    Fig. EE

  • 7/29/2019 Basic Operation Mcdonnell and Miller

    18/18

    BASIC SYSTEM OPERATION

    Series 250 Pressure Relief Valve

    Series 260 Pressure Relief Valve

    Pressure Relief Valves(Fig. GG, HH)

    ood engineering practice calls for every hot water

    boiler to have a pressure relief valve. This spring-

    loaded valve must be able to release the boilers entire

    load at the boilers maximum operating pressure.

    Here are some things that can cause a relief valve to

    open in a hot water heating system:

    The automatic feed valve fails, allowing higher than

    normal pressure to enter the system.

    Someone leaves a hand bypass line open after filling

    the system.

    Someone hydrostatically tests the system at a

    pressure greater than the relief valves setting.

    The air cushion in the diaphragm type compression

    tank doesnt match the systems static fill pressure.

    Keep in mind, most tanks come from the factoryprecharged at 12 psig (.83 bar). If the system needs

    more than 12 psig (.83 bar) pressure, you have to add

    more air to the tank, and you have to do this while you

    have the tank disconnected from the system.

    The compression tank may be too small for the system.

    The boilers aquastat is in a well without heat

    transfer grease. When this happens, the boilers

    temperature will quickly exceed the aquastats

    setting, causing rapid rise in system pressure.

    The circulator may be on the return side of the

    system with the compression tank at its suction. If itis, the circulators head pressure will appear inside

    the boiler as a net increase. It may be enough to

    open the relief valve.

    The burner limit may be jumped-out or stuck in a

    manual position.

    The main thing to keep in mind when youre

    troubleshooting this one is that relief valves pop when

    any of these three things happen:

    The compression tank loses its air cushion

    The system takes on more water.

    The system temperature increases.

    Think methodically, and keep your eyes wide open!

    e hope this Basic System Operation Guide has

    given you insight into the systems on which youre

    now working or will face in the future. We welcome any

    questions or comments you may have about the Guide,

    or about our products.

    Thanks for your support, and for your continuing business.

    Fig. GG

    Fig. HH

    G

    W