ba-184046-inter geno-mat duo we-x - gruenbeck.de · it is divided into several chapters (a letter...

55
Operation manual GENO-mat ® duo WE-X GENO-mat ® duo WE-OSMO-X Edition November 2015 Order no. 024 184 046-inter

Upload: others

Post on 26-Feb-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Operation manualGENO-mat® duo WE-X

GENO-mat® duo WE-OSMO-X

Edition November 2015 Order no. 024 184 046-inter

Page 2: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page
Page 3: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

3

Table of contents A  General notes .......................................................................................................................... 6 1 | Preface .............................................................................................................................................................................. 6 2 | How to use this operation manual ..................................................................................................................................... 6 3 | General safety information ................................................................................................................................................ 7 

3.1  Symbols and notes .................................................................................................................................................... 7 3.2  Operating personnel .................................................................................................................................................. 7 3.3  Designated use .......................................................................................................................................................... 7 3.4  Protection from water damage .................................................................................................................................. 8 3.5  Indication of specific dangers .................................................................................................................................... 8 

4 | Shipping and storage ........................................................................................................................................................ 8 5 | Disposal of used parts and materials ................................................................................................................................ 9 B  Basic information ................................................................................................................. 10 1 | Laws, regulations, standards ........................................................................................................................................... 10 2 | Water, scale, softening .................................................................................................................................................... 10 3 | Ion exchange ................................................................................................................................................................... 11 C  Product description .............................................................................................................. 12 1 | Type designation plate .................................................................................................................................................... 12 2 | Technical specifications .................................................................................................................................................. 12 3 | Designated application .................................................................................................................................................... 15 4 | Application limits .............................................................................................................................................................. 15 5 | Scope of supply ............................................................................................................................................................... 16 

5.1  Basic configuration .................................................................................................................................................. 16 5.2  Optional accessories ............................................................................................................................................... 16 5.3  Consumables ........................................................................................................................................................... 17 5.4  Wearing parts .......................................................................................................................................................... 18 

D  Installation ............................................................................................................................. 19 1 | General installation information ....................................................................................................................................... 19 

1.1  Water installation ..................................................................................................................................................... 20 1.2  Electrical installation ................................................................................................................................................ 21 

2 | Preliminary work .............................................................................................................................................................. 23 2.1  Filling the exchanger tank ........................................................................................................................................ 24 2.2  How to fit the brine line ............................................................................................................................................ 25 

3 | How to connect the system ............................................................................................................................................. 25 3.1  Water connection ..................................................................................................................................................... 25 3.2  How to connect the control unit ............................................................................................................................... 28 

E  Start-up .................................................................................................................................. 29 1 | How to fill the brine tank .................................................................................................................................................. 29 2 | How to set up the system ................................................................................................................................................ 30 

2.1  How to set the blending hardness ........................................................................................................................... 30 2.2  How to set the control unit ....................................................................................................................................... 31 

3 | How to start up the system .............................................................................................................................................. 32 F  Operation ............................................................................................................................... 33 GENO®-IONO-matic WE-X control unit ................................................................................................................................ 33 1 | Introduction ...................................................................................................................................................................... 33 2 | How to operate the control unit ........................................................................................................................................ 33 

2.1  Key functions ........................................................................................................................................................... 33 2.2  Meaning of the LEDs red / yellow / green ............................................................................................................... 34 2.3  Info level – reading the operating status .................................................................................................................. 34 2.4  System status display .............................................................................................................................................. 35 2.5  Setting operating parameters – operator menu ....................................................................................................... 35 2.6  How to release a manual regeneration .................................................................................................................... 36 2.7  Changing system parameters – code 290 ............................................................................................................... 37 

Control via reverse osmosis system GENO®-OSMO-X ........................................................................................................ 38 1 | Introduction ...................................................................................................................................................................... 38 2 | How to operate the control unit ........................................................................................................................................ 40 

2.1  Change, save, reject parameters ............................................................................................................................ 40 2.2  Acknowledgement of errors/signals ......................................................................................................................... 41 2.3  Screen saver ........................................................................................................................................................... 42 

3| System range ................................................................................................................................................................... 42 3.1  System menu I ......................................................................................................................................................... 42 3.2  Manual mode ........................................................................................................................................................... 43 3.3  System setting ......................................................................................................................................................... 43 

G  Faults ..................................................................................................................................... 44 1 | Basic information ............................................................................................................................................................. 44 

1.1  Warnings ................................................................................................................................................................. 44 1.2  Faults ....................................................................................................................................................................... 44 

H  Maintenance .......................................................................................................................... 46 1 | Basic information ............................................................................................................................................................. 46 2 | Inspection (functional check) ........................................................................................................................................... 46 3 | Maintenance .................................................................................................................................................................... 48 

3.1  Operating log ........................................................................................................................................................... 49 4 | Spare parts ...................................................................................................................................................................... 49 5 | Operating log ................................................................................................................................................................... 50  

Page 4: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

4

Publisher's information All rights reserved.

Copyright by Grünbeck Wasseraufbereitung GmbH

Printed in Germany Effective with the date of edition indicated on the cover sheet. -We reserve the right to make modifications, especially with regard to technical progress-

Reprints, translations into foreign languages, electronic storage or digital copying of this operating manual – even in parts – only with explicit written approval of Grünbeck Wasseraufbereitung GmbH.

Any type of duplication not authorised by Grünbeck Wasserauf-bereitung is a copyright violation and subject to legal action.

Responsible for contents: Grünbeck Wasseraufbereitung GmbH Josef-Grünbeck-Straße 1 89420 Höchstädt/Do., Germany Phone +49 9074 41-0 Fax +49 9074 41-100 www.gruenbeck.de [email protected]

Print: Grünbeck Wasseraufbereitung GmbH Josef-Grünbeck-Straße 1, 89420 Höchstädt/Do., Germany

Page 5: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

5

EC Declaration of Conformity

This is to certify that the system designated below meets the safety and health requirements of the applicable European guidelines in terms of its design, construction and execution.

If the system is modified in a way not approved by us, this certificate is void.

Manufacturer: Grünbeck Wasseraufbereitung GmbH Josef-Grünbeck-Straße 1 89420 Höchstädt/Do., Germany

Responsible for documentation: Markus Pöpperl

System designation: GENO-mat® duo WE-X water softener, GENO-mat® duo WE-OSMO-X water softener

System size: Refer to type designation plate

Order no.: Refer to type designation plate

Applicable directives: EMC (2004/108/EC) Low-Voltage (2006/95/EC) RoHS (2011/65/EU)

Applied harmonised standards, in particular:

DIN EN 61000-6-2:2006-03 DIN EN 61000-6-3:2011-09 DIN EN 60335-1:2012-10

Applied national standards and technical specifications, in particular:

DIN 31000/VDE 1000:2011-05

Location, date and signature: Höchstädt, 11.10.2015 p.p. M. Pöpperl Dipl.-Ing. (FH)

Function of signatory: Head of Department for Product Implementation and Product Launch

Page 6: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

6

A General notes

1 | Preface

Thank you for opting for a Grünbeck product. Backed by decades of experience in the area of water treatment, we provide solutions for all kind of processes.

All Grünbeck systems and devices are made of high-quality materials. This ensures reliable operation over many years, provided you treat your water treatment system with the required care. This operation manual assists you with important informa-tion. Therefore, please read the entire operation manual before installing, operating or maintaining the system.

Customer satisfaction is our prime objective and providing customers with qualified advice is crucial. If you have any questions concerning this device, possible extensions or general water and waste water treatment, our field staff, as well as the experts at our headquarters in Hoechstaedt, are available to help you.

Advice and assistance For advice and assistance please contact your local

representative (see www.gruenbeck.de) or get in touch with our service centre which can be reached during office hours:

Phone: +49 9074 41-333

Fax: +49 9074 41-120

Email: [email protected]

We can connect you with the appropriate expert more quickly if you provide the required system data.

2 | How to use this operation manual

This operation manual is intended for the operators of our systems. It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page 1 in alphabetical order. In order to find the specific information you are looking for, check for the corresponding chapter on page 1.

The headers and page numbers with chapter information make it easier to find your way around in the operating manual.

Page 7: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

7

3 | General safety information

3.1 Symbols and notes Important information in this operation manual is characterised by symbols. Please pay particular attention to this information to ensure the hazard-free, safe and efficient handling of the system.

Danger! Failure to adhere to this information will cause serious or life-threatening injuries, extreme damage to property or inadmissible contamination of the drinking water.

Warning! Failure to adhere to this information may cause injuries, damage to property or contamination of the drinking water.

Caution! Failure to adhere to this information may result in damage to the system or other objects.

Note: This symbol characterises information and tips to make your work easier.

Tasks with this symbol may only be performed by Grünbeck's technical service/authorised service company or by persons expressly authorised by Grünbeck.

Tasks with this symbol may only be performed by trained and qualified electrical experts according to the VDE guidelines or according to the guidelines of a similar local institution.

Tasks with this symbol may only be performed by water companies or approved installation companies. In Germany, the installation company must be registered in an installation directory of a water company as per §12(2) AVBWasserV (German Ordinance on General Conditions for the Supply of Water).

3.2 Operating personnel Only persons who have read and understood this operation

manual are permitted to work with the system. The safety guidelines are to be strictly adhered to.

3.3 Designated use The system may only be used for the purpose outlined in the

product description (chapter C). The guidelines in this operation manual as well as the applicable local guidelines concerning the drinking water protection, accident prevention and occupational safety must be adhered to.

In addition, appropriate application also implies that the system may only be operated when it is in proper working order. Any malfunctions must be repaired at once.

Page 8: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

8

3.4 Protection from water damage

Warning! In order to properly protect the installation site from water damage:

a sufficient floor drain system must be available or

a water stop device (see chapter C Accessories) must be installed.

Warning! Floor drains leading to a lifting system do not work in case of a power failure.

3.5 Indication of specific dangers

Danger due to electrical energy! Do not touch electrical parts with wet hands! Disconnect the system from the mains before starting work on electrical parts of the system. Have qualified experts replace damaged cables immediately.

Danger due to mechanical energy! System parts may be subject to overpressure. Danger of injury and damage to property due to escaping water and unexpected movement of system parts. Check the pressure pipes at regular intervals. Depressurise the system before starting repair or maintenance work on the system.

Hazardous to health due to contaminated drinking water! The system may only be installed by a specialist company. The operation manual must be strictly adhered to! Ensure that there is sufficient flow. The pertinent guidelines must be followed for starting-up after extended periods of standstill. Inspections and maintenance must be performed at the intervals specified!

Note: By concluding a maintenance contract, you ensure that all of the required tasks are performed on time. You may perform the interim inspections yourself.

4 | Shipping and storage

Caution! The system may be damaged by frost or high temperatures. In order to avoid damage of this kind:

Protect it from frost during transportation and storage! Do not install or store system next to objects which radiate a lot of heat.

The system may only be transported and stored in its original packing. Ensure that it is handled with care and placed the right side up (as indicated on the packing).

Page 9: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

9

5 | Disposal of used parts and materials

Used parts and materials are to be disposed of, or made available for recycling purposes, according to the applicable local guidelines.

If a material is subject to specific regulations, adhere to the instructions indicated on the packing.

If in doubt, contact your local waste disposal authority or the manufacturer for more information.

Page 10: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

10

B Basic information

1 | Laws, regulations, standards

In the interest of good health, rules cannot be ignored when it comes to the processing of drinking water (raw water). This operation manual takes into consideration the current regulations and stipulates information that you will need for the safe operation of your water treatment system.

Among other things, the regulations stipulate that

only approved companies are permitted to make major modifications to water supply facilities

and that tests, inspections and maintenance on installed devices are to be performed at regular intervals.

2 | Water, scale, softening

The water works provide us with pure water (raw water) that is suitable for drinking. However, this water is much more often used for washing machines, heating systems, water heaters, commercial devices, etc., where it can lead to problems if it is "hard".

Hard water is generated if water containing carbon dioxide* flows through layers of calcium. It dissolves the calcium until the so-called calcium - carbon dioxide - equilibrium has been reached.

If this equilibrium is unsettled (e.g. by heating CO2 escapes) more calcium (CaCO3) is precipitated (scale).

Note: Calcium ions and magnesium ions exist side by side in nature, e.g. in the mineral dolomite.

Hardness ranges according to the German Act on Environmental Sustainability of Detergents and Cleaning Agents (WMRG):

The total hardness of the water is the sum of the concentrations of calcium ions and magnesium ions.

From hardness range "medium" onwards, it is advisable to soften the water for usage. Additional measures may be necessary depending on the original quality of the water and its intended use.

* CO2 from the atmosphere is dissolved in water. In this process, a low amount of carbon dioxide is generated.

Hardness range °dH °f mmol/l =

mol/m3 1 (soft) < 8.4 < 15.0 < 1.50 2 (medium) 8.4 - 14.0 15.0 - 25.0 1.50 - 2.50 3 (hard) > 14.0 > 25.0 > 2.50

Page 11: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

11

3 | Ion exchange

Resin

Fig. B-1: Initial position

The exchange of calcium and magnesium ions for sodium ions causes the water to become soft.

Principle The hard raw water flows through an exchanger. This tank is filled with a resin, to which sodium ions are bonded (see Fig. B-1).

Since the bonding positions at the resin prefer calcium and magnesium ions to sodium ions, these ions are retained while the resin discharges sodium ions into the water (exchange reaction). In this way, all substances causing hardness remain in the exchanger. Soft water loaded with sodium ions leaves the exchanger (Fig. B-2). This process continues until the sodium ions are used up.

Hard water

Soft water

Resin

Fig. B-2: Operation

The exchange reaction can be reversed if a large amount of sodium ions (salt solution = brine) is added (Fig. B-3). By their sheer number, the sodium ions displace the calcium and magnesium ions at the docking positions of the resin.

This process restores the initial state. The resin is regenerated and is again ready for softening.

Drinking water (raw water) As protection against corrosion, we recommend a soft water hardness of at least 3 °dH (5.3 °f, 0.53 mmol/l). According to the German Drinking Water Ordinance, the limit value for sodium ions (200 mg/l) must not be exceeded. This hardness is achieved by adding untreated drinking water (raw water), a process which is commonly called blending.

Resin

Waste water

Brine solution

Fig. B-3: Regeneration

Note: Many popular mineral waters contain significantly more sodium ions. Check for yourself by reading the analysis results on the labels.

Warning! Risk of infection due to germs in the drinking water. Germs can reproduce in stagnant water to the point where they pose a threat. Work with water softeners requires special hygienic measures. Ensure that there is sufficient flow. Disinfect the systems if required.

Single/Twin/Triple water softeners In case of single water softeners, no soft water is available during the regeneration phase.

Twin water softeners have two exchangers that alternate operation. As a result, soft water is available at all times.

Triple water softeners consist of three exchangers. Two exchangers are flown through in parallel while the third is being regenerated.

Sodium ions Calcium ions Magnesium ions

Page 12: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

12

C Product description

1 | Type designation plate

The type designation plate is located at the control valve of the water softener. In order to speed up the processing of your inquiries or orders, please specify the data shown on the type designation plate of your system when contacting Grünbeck. Please copy the indicated information to the table below in order to have it handy whenever necessary.

GENO-mat® duo WE-X / WE-OSMO-X water softener

duo WE-X Serial number:

duo WE-OSMO-X Serial number:

Order no.: 2 | Technical specifications

The GENO-mat® duo WE-X water softener is a twin system for the continuous supply of soft water. The system is equipped with a central control valve for both exchangers and is volume-controlled. The regeneration is released when the pre-set water volume in an exchanger tank has been softened. The system regenerates with soft water.

All system data is summarised in tables C-1 and C-2. The data given refers to standard water softeners. Possible deviations in case of special versions are communicated separately, if applicable.

The GENO-mat® duo WE-OSMO-X water softener is only available with full salting. The control electronics is not equipped with an operating and display unit. The system is operated by means of the control electronics of the OSMO-X reverse osmosis system.

Warning! Extended periods of idleness may cause bacterial growth in drinking water. Automatic regeneration counteracts this effect. Therefore, do not disconnect the system from the water and power supply when you are absent for longer periods of time.

Caution! Electrically operated valves. In case of power failure during the regeneration, water may flow into the drain or brine tank. In the event of power failure, check the system and shut-off the water supply, if necessary.

Page 13: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

13

Table C-1: Technical specifications Water softener GENO-mat® duo WE-X / WE-OSMO-X

Systems with full salting 65 150 300 450 750

Connection data

Nominal connection diameter DN 25 (1" female thread)

DN 40 (1½" female thread)

Min. drain connection DN 50 Power supply [V]/[Hz] 85 -250/50-60

(system operation with protective low voltage 24V DC) Connected load [VA] 10 Protection/protection class IP 54/I

Performance data

Nominal pressure (PN) [bar] 10 Min./max. operating pressure [bar] 2.0/8.0 Max. continuous flow *** at a residual hardness of < 0.1 °dH

[m³/h] 2.0 3.0 5.0 6.0 9.5

Pressure loss at max. continuous flow [bar] 0.6 1.1 2.1 1.5 2.3

KV-value (at p = 1.0 bar) [m³/h] 2.6 2.7 3.1 4.5 5.6

Nominal capacity [mol][m³ x °dH]

12.0 67

26.6 149

53.9 302

80.2 449

133.2 746

Capacity per kg of regeneration salt [mol/kg] 3.33 3.32 3.32 3.16 3.33 Time capacity [m³ x °dH/h] 72 84 145 214 269

Dimensions and weights 1)

Total height [mm] 1310 1530 1790 1840 1970 Overall height (without control unit) **** [mm] 1080 1300 1560

Exchanger tank [mm] 208 257 334 369 469

Brine tank * [mm] 500 570 700 780 900

Overall height of brine tank * [mm] 810 880 870 1100 1250 Height of safety overflow on brine tank * [mm] 700 780 770 980 1120 Connection height of control valve (raw water)

[mm] 940 1160 1420 1710 1830

Min. foundation depth * [mm] 600 700 800 900 1000 Min. length of foundation * [mm] 1460 1500 1700 2100 2400 Approx. operating weight * [kg] 285 435 730 1110 1745

Filling volumes and consumption data **

Resin quantity [l] 18 40 81 115 200 Freeboard (resin in form of sodium), approx. [mm] 270 230 290 390 300 Salt consumption per regeneration, approx. [kg] 3.6 8.0 16.2 25.3 40.0 Max. regeneration salt supply * [kg] 130 190 285 485 760 Total waste water volume per regen., approx. [l] 112 211 451 693 1020 Operating water volume [l] 10 22 45 70 111 Minimum salt fill level * [mm] 50

Ambient data

Max. water/ambient temperature [°C] 30/40

Order no. GENO-mat® duo WE-X 186 100 186 110 186 120 186 130 186 140

Order no. GENO-mat® duo WE-OSMO-X 186300 186 310 186 320 186 330 186 340

* With standard brine tank ** The waste water volume and salt consumption refer to a primary pressure of 3 bar.

The indicated values change at different inlet pressures and only serve as a means for a rough determination. *** The indicated max. continuous flows may decrease in case of high raw water hardness. **** In case of systems with a nominal connection diameter of DN 40, the control unit is fastened between the exchanger

tanks. 1) All indicated dimensions and weights are approximate!

Page 14: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

14

Table C-2: Technical specifications GENO-mat® duo WE-X water softener Systems with economy salting 50 130 230 330 530

Connection data Nominal connection diameter DN 25

(1" female thread) DN 40

(1½" female thread) Min. drain connection DN 50 Power supply [V]/[Hz] 85 -250/50-60

(system operation with protective low voltage 24V DC) Connected load [VA] 10 Protection/protection class IP 54/I Performance data Nominal pressure (PN) [bar] 10 Min./max. operating pressure [bar] 2.0/8.0 Max. continuous flow *** at a residual hardness of > 0.1 °dH

[m³/h] 2.0 3.0 5.0 6.0 9.5

Peak flow in case of blending to 8 °dH and a raw water hardness of 20 °dH

[m³/h] 3.3 5.0 8.3 10.0 15.8

Pressure loss at max. continuous flow [bar] 0.6 1.1 2.1 1.5 2.3 KV value (at p = 1.0 bar) [m³/h] 2.6 2.7 3.1 4.5 5.6 KV value in case of blending to 8 °dH and a raw water hardness of 20 ° dH

[m³/h] 4.3 4.5 5.2 7.5 9.3

Nominal capacity [mol] [m³x°dH]

9.5 53

20.9 117

42.3 237

60.0 336

95.2 533

Capacity per kg of regeneration salt [mol/kg] 5.27 5.22 5.22 5.20 5.90 Time capacity [m³ x °dH/h] 68 81 143 207 243

Dimensions and weights 1)

Total height [mm] 1310 1530 1790 1840 1970 Overall height (without control unit) **** [mm] 1080 1300 1560 Exchanger tank [mm] 208 257 334 369 469

Brine tank * [mm] 410 500 570 700 700 Overall height of brine tank * [mm] 670 810 880 870 870 Height of safety overflow on brine tank * [mm] 570 700 780 770 770 Connection height of control valve (raw water)

[mm] 940 1160 1420 1710 1830

Min. foundation depth * [mm] 500 600 700 800 800 Min. length of foundation * [mm] 1300 1500 1600 2100 2200 Approx. operating weight * [kg] 190 340 555 825 1080 Filling volumes and consumption data **

Resin quantity [l] 18 40 81 115 200 Freeboard (resin in form of sodium), approx. [mm] 270 230 290 390 300 Salt consumption per regeneration, approx. [kg] 1.8 4.0 8.1 11.5 16.0 Max. regeneration salt supply * [kg] 65 130 190 285 285 Total waste water volume per regen., approx. [l] 98 181 376 583 865 Operating water volume [l] 5 11 23 32 44 Minimum salt fill level * [mm] Ambient data Max. water temperature [°C] 30 Max. ambient temperature [°C] 40 Control unit

Order no. GENO-mat® duo WE-X 186 200 186 210 186 220 186 230 186 240 * With standard brine tank ** The waste water volume and salt consumption refer to a primary pressure of 3 bar.

The indicated values change at different inlet pressures and only serve as a means for a rough determination. *** The indicated max. continuous flows may decrease in case of high raw water hardness. **** In case of systems with a nominal connection diameter of DN 40, the control unit is fastened between the exchanger

tanks. 1) All indicated dimensions and weights are approximate!

Page 15: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

15

3 | Designated application

Water softeners of the GENO-mat® duo WE-X series are designed for the softening and partial softening of cold drinking and process water. As twin systems, they are suitable for the continuous supply of soft water. There are system types available with regeneration with full salting or economy salting. In this case, the type of regeneration is type-specific and is not allowed to be changed independently.

Note: In order to soften the water to less than 0.1 °dH, only and exclusively systems with full salting may be applied.

The water to be softened has to be free of iron and manganese (less than 0.2 mg iron and/or 0.05 mg manganese per litre). Its temperature must not exceed 30 °C. The maximum ambient temperature is 40 °C.

The systems are used for the (partial) softening of well, process, boiler feed, cooling and air-conditioning water.

When softening drinking water, the provisions of the German Drinking Water Ordinance are binding (residual hardness of 3 °dH - 8 °dH, max. sodium content of 200 mg/l (chapter E-2.1.). A blending valve for mixing supply water is also needed.

The system is adjusted to the soft water requirements to be expected at the installation site, it is not suitable for major deviations. The maximum continuous flow must not be exceeded under any circumstances.

The system may only be operated if all components are installed properly. Safety devices and equipment must NEVER be removed, bridged or tampered with.

Appropriate application of the device also implies that the information contained in this operation manual and all safety guidelines applying at the installation site be observed. Further-more, the maintenance and inspection intervals have to be observed.

4 | Application limits

The application limit is defined by the maximum continuous flow corresponding to the data in tables C-1 and C-2 for raw water in the hardness ranges 1 - 3. With very hard water (from hardness range 4 onwards), there may be a drop in the continuous flow. In this case, the application limit of the system is defined by the formula:

hardnessBlendinghardnesswaterRaw

capacityTimeflowcontinuousMaximum

The time capacity is summarised in tables C-1 or C-2.

Page 16: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

16

5 | Scope of supply

5.1 Basic configuration 2 double-walled plastic exchanger tanks.

Food-compatible ion exchanger resin

Note: With smaller units (up to GENO-mat® duo WE-X 300), the exchanger tanks are supplied filled with resin.

1 central control valve made of red bronze.

Brine tank made of PE incl. sieve bottom (which separates the salt supply chamber and the brine chamber) and brine valve made of PP with safety float (controls the brine flow). With brine buffer technology.

1 microprocessor controller with LC display (controls all system functions and indicates operating states and disturbances).

GENO-mat® duo WE-OSMO-X without LCD display. The operation is carried out via the control electronics of the reverse osmosis system GENO®-OSMO-X.

Turbine water meter (TWZ) (can be replaced by water meter with counter, refer to Chapter C-4.2.).

Water test kit "total hardness" (refer to Chapter C-4.3).

Operation manual.

5.2 Optional accessories

Note: It is possible to retrofit existing systems with optional components. Please contact your local Grünbeck representative or Grünbeck’s headquarters in Hoechstaedt for details.

Adapter connection 9000 with integrated blending unit; R 1" (standard equipment for duo WE-X 50, 130 and 230, available as an option for duo WE-X 65, 150 and 300)

125 809

Blending valve (to adjust the residual hardness by adding raw water) Connection R 1 ¼"

126 003

Water meter with counter Connection R 1" Connection R 1½"

163 080 163 085

Mounting set 1: (for easy connection to the water installation) Compact valve block R 1", female thread, integrated bypass with shut-off valve, shut-off valves for hard and soft water, outlet for raw water (e.g. garden hose), 2 flexible stainless steel fabric hoses* (connection R 1", female thread, length 600 mm)

125 845

Page 17: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

17

Mounting set 2: (for ease of connection to the water installation) connecting block R 1" male with threaded connectors, ball shut-off valves for hard and soft water, non-return valve, overflow valve, 2 flexible stainless steel woven hoses* (connection R 1" female, length 600 mm)

125 850

Overflow valve, connection R 1" male, opening pressure 0.8 bar (to cover peak demand by adding raw water, to be installed in the bypass),

125 855

Potential-free message (operation and regeneration message)

126 890

Pre-alarm salt supply Infra-red light sensor to register the minimum salt filling level in the brine tank. Message via GENO®-IONO-matic3 control unit

185 335

GENO®-STOP 1" GENO®-STOP for optimum protection against water damage. The new GENO®-STOP safety device provides reliable and comprehensive protection against water damage. The GENO®-STOP may be equipped with up to 2 wired water sensors and with 5 wireless water sensors.

- For additional versions, please inquire -

126 875

5.3 Consumables Only use genuine consumables in order to ensure the reliable

operation of the system.

Regeneration salt (25 kg)

Water test kit "Total hardness“

1 piece 10 pieces

127 001

170 145 170 100

Page 18: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

18

5.4 Wearing parts Seals and control pistons are subject to a certain wear and tear

in the event of heavy duty. Wearing parts are listed below.

Note: Although these are wearing parts, we grant a limited warranty period of 6 months. The same applies for electrical components.

a) Seals, control pistons, injectors, actuator

Fig. C-1: Control valve

nominal connection diameter DN 25

Fig. C-2: Control valve nominal connection diameter DN 40

b) Flat seals, backflow preventer

Fig. C-3: Brine valve

Page 19: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

19

D Installation

1 | General installation information

The installation site must offer adequate space. A foundation of asufficient size and adequate load carrying capacity must be provided. The required connections must be provided prior to the installation. For dimensions and connection data, please refer to table D-1.

Table D-1: Installation data Extract from table C-1, C-2

Water softener GENO-mat® duo WE-X / WE-OSMO-X

with full salting with economy salting2)

65 150 300 450 750 50 130 230 330 530

Connection data

Nominal connection diameter DN 25 (1" female

thread)

DN 40 (1½" female

thread)

DN 25 (1" female

thread)

DN 40 (1½" female

thread)

Min. drain connection DN 50

Power supply [V]/[Hz] 85 -250/50-60 (system operation with protective low voltage 24V DC)

Connected load [VA] 10 Protection/protection class IP 54/I

Dimensions and weights1) Total height** [mm] 1310 1530 1790 1840 1970 1310 1530 1790 1840 1970

Overall height without control unit**** [mm] 1080 1300 1560 1840 1970 1080 1300 1560 1840 1970

Exchanger tank [mm] 208 257 334 369 469 208 257 334 369 469

Brine tank * [mm] 500 570 700 780 900 410 500 570 700 700

Overall height of brine tank * [mm] 810 880 870 1100 1250 670 810 880 870 870

Height of safety overflow on brine tank *

[mm] 700 780 770 980 1120 570 700 780 770 770

Connection height of control valve [mm] 940 1160 1420 1710 1830 940 1160 1420 1710 1830

Min. foundation depth * [mm] 600 700 800 900 1000 500 600 700 800 800

Min. length of foundation * [mm] 1460 1500 1700 2100 2400 1300 1500 1600 2100 2200

Operating weight, approx. * [kg] 285 435 730 1110 1745 190 340 555 825 1080

* With standard brine tank **** For systems with a nominal connection diameter of DN 40, the control unit is mounted between the exchanger tanks. 1) All indicated dimensions and weights are approximate! 2) not applicable for GENO-mat® duo WE-OSMO-X.

Note: Observe the operating manual that have been supplied with the optional accessories (see chapter C, 4.2) for your unit.

Page 20: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

20

1.1 Water installation It is imperative that you comply with certain regulations when installing the GENO-mat® duo WE-X water softener. Additional recommendations are given in order to facilitate the handling of the system. The installation instructions described below are also illustrated in Fig. D-1.

Binding rules

The installation of a water softener represents a major interference with the drinking water system. Therefore, only authorised experts may install such systems.

Please observe the local installation guidelines and the general regulations.

Install a drinking water filter upstream (e.g. BOXER®).

Use corrosion-resistant material for soft water lines OR Meter corrosion inhibitor downstream of the water softener.

Provide a drain connection (minimum DN 50) to discharge the regeneration water.

Note: If the regeneration water is directed to a lifting system, said system must be salt water resistant.

The unit does not carry a DVGW test certificate. Provide additional safety equipment for protection of the drinking water in line with DIN 1988. Therefore:

Isolate the water softener from the drinking water supply in line with DIN 1988 part 4 (e.g. by the use of the GENO® DK 2 Euro system separator).

Recommendations

Provide a sampling valve immediately downstream of the softener. This facilitates the sampling for the regular hardness tests (functional check).

Warning! Floor drains leading to a lifting system do not work in case of a power failure.

Page 21: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

21

1.2 Electrical installation

A shock-proof plug is adequate for the electrical connection. However, it must comply with the specifications given in table D-1, may not be further away from the softener than 1.20 m and must carry constant voltage (do not couple with light switch).

Page 22: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

22

1.2.1 Connections to other subsystems within the water softener The following connections are preset internally at the factory and

must not be modified (cables to be connected by the client are marked with *).

Table D-1: From IONO-matic WE control unit

to component Line Signal

1 Mains cable H05VV-F 3G0.75 mm² E Br 2 N Bl PE Earth wire Ye-gn 3

Reserved terminals

4 5 6 PE 7 8 PE 9 10 PE 11 Microswitch

control valve* LiYY 3x0.5 mm² + 24 V= Strands 1

terminal 7 12 S1 Strands 2

terminal 4 13 + 24 V= 14 S2 Strands 3

terminal 5 20 Step motor control

valve* LiYY 7x0.25 mm² + 24 V= Gn

21 Ph1 Br 22 Ph2 Gr 23 + 24 V= Wh 24 Ph3 Ye 25 Ph4 Rs 26 Water meter* LiYY 3x0.25 mm² + 12 V= Wh 27 pulse Gn 28 GND Br 32 Pot.-free contact, closed when

exchanger tank 1 in operation. Switching capacity max. 30 V~1A 33

34 Pot.-free contact, closed during regeneration. 35 GND1 Connection to the

programming board LiYY 5x0.34 mm² GND-RS Wh

40 RS485B Gr 41 RS485A Gn GND GND Ye 42 + 14 V= Br

Page 23: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

23

1.2.2 Connections to external or optional components From IONO-matic WE control unit

to component Line Signal

15 Programmable input + 24 V= 16 IN 17 Option pre-alarm

salt supply 185335 LiYY 4x0.25 mm² + 24 V= Br

18 IN Bk 19 GND Bl 29 Collective fault Max. 250 V~ /

max. 3 A each 30 Common root 31 Signal contact 1.2.3 Connections to networked GENO®-OSMO-X reverse osmosis From IONO-matic WE control unit

to component Line Signal

38 Bus line to OSMO-X control unit

93 LiYY 3x0.25 mm² (*)

RS485 A 39 94 RS485 B GND2 95 RS485-GND (*) With cable length > 20 m: Use LiYcY 3x0.25 mm² and

connect the shielding at one end either in the OSMO-X control unit or IONO-matic WE/control unit DEA at a free PE terminal.

2 | Preliminary work

1. Unpack all system components.

2. Check for completeness and soundness.

3. Set up both exchanger tanks at the intended site.

Caution! The system only functions if it is set up correctly. Set up the exchanger tank with control valve on the right (seen from the front).

Only with small systems (nominal connection diameter 1"): The connection hoses with pre-installed connection adapters and coupling pieces are exposed.

4. Plug in coupling pieces.

5. Install hoses between control valve and bottle adapter.

6. Fit connection block for raw water connection.

Note: The connection block is supplied with separate installation instructions.

Page 24: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

24

2.1 Filling the exchanger tank

The work described here is only needed with the large systems . Smaller units are supplied with filled exchanger tanks.

Table D-1: Filling in resin

450 / 330 750 / 530

Amount of resin per exchanger container

115 l 200 l

Centre riser pipe, fill with resin

1. Check whether the riser pipes are covered by protective caps, plug on protective caps, if necessary. Protective caps prevent material from entering the riser pipes.

2. Centre riser pipes in the exchanger containers.

3. Pour ion exchange resin into the tanks. Use the funnel provided.

4. Fill up the exchanger tank with drinking water.

Remove the protective cap, fix the control valve in place

5. Centre the riser pipes precisely.

6. On the exchanger containers, clean any adhering ion exchanger resin off the threads and sealing connections for the connections of the control valve or bottle adapter.

7. Remove the protective caps from the riser pipes.

8. Guide the control valve from above with its head nozzle over the riser pipe of the right exchanger tank (as seen from the front) and secure by turning clockwise.

9. Guide the bottle adapter from above with its head nozzle over the riser pipe of the left exchanger tank (as seen from the front) and secure by turning clockwise.

10. Fill the exchanger tank with water.

11. Install connecting pipes between control valve and bottle adapter.

Page 25: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

25

2.2 How to fit the brine line See Fig. D-1 (b), position 7.

1. Set up the brine tank at its intended site.

2. Remove cover from the brine tank.

Note: Remove the brine valve to make installing the brine line easier. To do so, remove the yellow lid and pull the brine valve upwards.

Brine valve with transition nipple and elbow connector

3. Fit the transition nipple (not needed with 750 (530)) and elbow connector onto the brine valve.

4. Cut the brine hose to the required length and insert reinforcing sleeves at both ends.

5. Fit the brine hose onto the brine valve.

6. Only if removed: Insert the brine valve and replace the yellow cover.

3 | How to connect the system

3.1 Water connection 1. Make the water connection as indicated in the installation drawing (Fig. D-1 (a)) while observing the guidelines and recommendations given in section 1.

Note: The supplied water meter must be installed on the soft water side (after the system) without fail.

Caution! Dirt and corrosion particles may damage the system (control valve, ion exchanger resin). Flush the supply pipe prior to start-up.

2. Make the waste water connection: Direct the drain hose to the outlet and secure it.

Caution! Danger of damage and malfunction due to backflow of waste water. Therefore, do not bend the hose and do not lead it higher than the system height.

3. Route the brine tank overflow hose with a gradient to the channel. Do not connect to the drain hose!

Page 26: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

26

Dimensions in Fig. D-1 (a); Extract from table D-1

Water softener GENO-mat® duo WE-X / WE-OSMO-X

with full salting with economy salting2)

65 150 300 450 750 50 130 230 330 530

Dimensions and weights1)

A Total height [mm] 1310 1530 1790 1840 1970 1310 1530 1790 1840 1970

A2 Overall height without control unit [mm] 1080 1300 1560 1840 1970 1080 1300 1560 1840 1970

B Exchanger tank [mm] 208 257 334 369 469 208 257 334 369 469

C Brine tank * [mm] 500 570 700 780 900 410 500 570 700 700

D Total height of brine tank * [mm] 810 880 870 1100 1250 670 810 880 870 870

E Height of safety overflow of brine [mm] 700 780 770 980 1120 570 700 780 770 770

F Connection height of control valve [mm] 940 1160 1420 1710 1830 940 1160 1420 1710 1830

* In systems with standard brine tank 1) All indicated dimensions and weights are approximate! 2) not for GENO-mat® duo WE-OSMO-X.

Fig. D-1 (a): Installation drawing for GENO-mat®-duo WE-X water softeners

Fig. D-1 (b): GENO-mat®-duo WE-X water softener; side view right/rear

1 BOXER® drinking water filter 5 Control valve 9 Connection of hose to drain

2 GENO® DK 2 system separator 6 Exchanger tank 10 Raw water inlet

3 Control unit 7 Brine tank 11 Soft water outlet

4 Water meter 8 Brine line

Page 27: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

27

See Fig. D-3 for detailed view of the brine line connection

Fig. D-2: GENO-mat®-duo WE-X water softener; rear view

Fig. D-3: Exploded view of brine line connection

Druckverlust GENO-mat duo WE

0,00

0,50

1,00

1,50

2,00

2,50

3,00

0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0 11,0 12,0

Durchfluß [m³/h]

Dif

fere

nzd

ruc

k [

ba

r]

50/65

130/150

230/300

330/450

530/750

Fig. D-2: Pressure loss curve

Union nut 3/8“Brass sleeve 3/8“

Brine tube Plasticpinch ring 3/8“

Filter forbrine valve

Transition-nipple

Pressure loss GENO-mat duo WE

Flow rate [m³/h]

Dif

fere

nti

al p

ress

ure

[b

ar]

Page 28: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

28

3.2 How to connect the control unit

The work described here may only be performed by trained electricians or electronics experts.

The control unit must be connected according to the terminal diagram shown in Fig. D-2.

Note: The corresponding connection diagram is contained in the electrical circuit diagram of the reverse osmosis system or the operating instructions for the automatic salt reduction system/compact air washer.

Note: Small systems (nominal connection diameter 1") are supplied pre-assembled. This means steps 1 and 2 can be skipped.

1. Attach the control unit to the connecting pipes using the supplied fastening kit

Danger due to electrical energy! Mains voltage is at terminals L, N and PE. Do not connect system to mains before you have finished this work.

2. Route the 7-core cable for the step motor and the 3-core cable for the micro switch between the control valve and control unit, and connect according to the terminal diagram (chapter D-1.2.).

3. Connect the water meter according to the terminal diagram (chapter D-1.2.1).

4. Connect the mains plug to the socket (chapter D-1.2).

Page 29: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

29

E Start-up

The work described below may only be performed by trained experts. For safety reasons, the start-up must be performed by Grünbeck's trained and authorised technical customer service/authorised service company.

1 | How to fill the brine tank

1. Remove the cover from the brine tank

2. Carefully add water until the water level is about 30 mm above the sieve base.

Caution! Insoluble impurities in the salt may cause malfunctions at the brine valve and at the injector of the control valve. A defined salt quality is required for the reliable function of the water softener.

Only use salt tablets that conform to DIN EN 973 A.

3. Insert salt tablets into the brine tank. The brine tank can be fully filled.

4. Add the operating water volume (Table E-1).

5. Close the brine tank cover.

Table E-1: Filling of brine tank Water softener GENO-mat® duo WE-X /

GENO-mat® duo WE-OSMO-X Systems with full salting 65 150 300 450 750 Max. regeneration salt supply * [kg] 130 190 285 485 760

Operating water volume [l] 10 22 45 70 111

Table E-2: Filling of brine tank Water softener GENO-mat® duo WE-X Systems with economy salting 50 130 230 330 530 Max. regeneration salt supply * [kg] 65 130 190 285 285

Operating water volume [l] 5 11 23 32 44

* In systems with standard brine tank

Page 30: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

30

2 | How to set up the system

2.1 How to set the blending hardness

The small systems with economic salting (GENO-mat® duo WE-X 50, WE-X 130, WE-X 230) are equipped with a blending unit as standard. This blending unit is

available as additional equipment for the GENO-mat® duo WE-X 65, WE-X 150, WE-X 300 systems.

Larger systems can be fitted with a blending valve R 1¼" as additional equipment. If both soft water with 0 °dH and blended water are needed, this blending valve is also recommended for small systems. Refer to the operating manual for the blending valve in systems with this equipment.

Caution! If the water softener is installed before a reverse osmosis system, the feed line to the reverse osmosis system is not allowed to be configured as a blending water line.

Note: The provisions of the German Drinking Water Ordinance are binding when softening drinking water.

Sodium content (max:) 200 mg/l Note point 3.1 with regard to the blending hardness!

Example

Softening of drinking water

Supply water (22 °dH) contains sodium (51.6 mg/l)

Possible addition of sodium during softening:

200 mg/l – 51.6 mg/l = 148.4 mg/l

Sodium content Obtain the sodium content of the supply water from your water supply provider. The sodium content increases by approx. 8.2 mg/l when softening water by 1 °dH. The water cannot be softened unrestrictedly if the provisions of the German Drinking Water Ordinance are to be adhered to. The permissible blending hardness results from the limit value for the sodium content and the supply water hardness.

200 mg/l (limit value according to the Drinking Water Ordinance)

– x mg/l (sodium content in the supply water)

This means that the maximum permissible softening is:

y mg/l (permissible addition of sodium during softening)

Conclusion: Blend to at least 22 – 18 = 4 °dH!

y

8 2,= Z °dH (maximum possible softening)

The supply can be softened to a maximum of Z °dH. Depending on the sodium content of the supply water, a blending hardness needs to be selected which is below the admissible maximum of 200 mg/l.

2.1.1 Recommendations

Blending hardness Blending hardness

Result

3 – 5 °dH Very soft water – ideal for thermal equipment – possible problems when washing off soap

6 – 8 °dH Optimum soft water

Page 31: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

31

Setting the blending unit In the GENO-mat® duo WE-X 50, duo WE-X 130 and duo WE-X 230 systems, the blending unit described here is mounted on the control valve. Optionally, small systems with full salting can be equipped with it. In all other cases, the operating manual for the installed blending valve applies.

1. Open the valve on the raw water inlet.

2. Open the valve on the soft water outlet.

3. Set the adjusting cap (1) to a mean scale value.

4. Take a water sample at the sampling valve downstream of the system.

5. Perform a hardness test using the "Total hardness" water inspection device.

6. Set the blending hardness as required. In order to do so:

Turn the adjusting cap to the left (close) so as to reduce the blending hardness.

Turn the adjusting cap to the right (open) so as to increase the blending hardness.

7. Repeat steps 4. and 5. until the desired blending hardness is reached.

2.2 How to set the control

unit The GENO-mat® duo WE-X water softener is volume-controlled. The operating parameters are already stored in the GENO®-IONO-matic WE-X control unit. During start-up, all parameters must be entered which are required for the automatic calculation of the regeneration interval.

Note: For detailed information on the handling of the GENO®-IONO-matic WE-X control unit, please refer to chapter F.

2.2.1 Setting the time and raw water hardness

Starting from the basic display

Press and hold key P for > 1 second. The parameters can be accessed there.

Page 32: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

32

3 | How to start up the system 1. Open the valve on the raw water inlet.

2. Release a manual regeneration (chapter F). Starting from the basic display, press and hold key for 5 seconds. An exchanger is now regenerated.

3. When the first manual regeneration has finished: Start a manual regeneration again, the second exchanger is now regenerated.

Note: All systems with low-salt alarm have a delay time set bet-ween 2 regenerations (factory setting: 0.2 hours = 12 minutes). At the end of the regeneration, it is necessary to wait for this time to elapse before a manual regeneration can be triggered again.

4. Open the valve on the soft water outlet after regeneration has finished.

5. Perform a visual check. Ensure that no water leaks from the system at any point.

6. Take a water sample at the sampling valve downstream of the system.

7. Perform a hardness test using the "Total hardness" water inspection device. The system is working correctly if the analysis of the water taken just downstream of the exchanger tank gives 0 °dH.

8. Complete the cover sheet and check list / column 1 of the operating log. To do this, carry out the necessary measure-ments and tests.

Page 33: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

33

F Operation

GENO®-IONO-matic WE-X control unit

1 | Introduction

The GENO-mat® duo WE-X water softeners are volume-controlled. They are operated and monitored by means of the control unit.

Fig. F-1: Display of control unit GENO®-IONO-matic WE-X

2 | How to operate the control unit

2.1 Key functions

Accesses parameters for editing (cursor flashing).

Save the modified parameters (cursor stops flashing).

Starting from the basic display (time/residual capacity/time since last regeneration): Press and hold for > 1 sec. = access to the operator menu.

Acknowledge of errors/warnings.

Within a menu: Switch to the next parameter.

Opened parameters: Reduce the set value.

Starting from the basic display (time/residual capacity/time since last regeneration): Press and hold for > 5 sec. = trigger manual regeneration.

Within a menu: Return to the previous parameter.

Opened parameters: Increase the set value.

+

Starting from the basic display (time/residual capacity/time since last regeneration): Access to the code request for menu levels with code protection.

+

Jump back to the basic display (time/residual capacity/time since last regeneration) from any menu level.

Close the opened parameter without saving, the previously set value is maintained.

Page 34: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

34

5 minutes after the last key was pressed, the system jumps back

to the basic display (time/residual capacity/time since last regeneration) from any opened menu. Parameter changes which have not been saved are lost.

The display backlighting is switched off 10 minutes after the last key was pressed. Each new key press activates the backlighting again.

2.2 Meaning of the LEDs red / yellow / green

Green LED is illuminated = everything OK

Yellow LED is illuminated = message (service due, low salt, time incorrect after power failure > 24 hours)

Red LED is illuminated = fault

Also refer to chapter G Faults.

2.3 Info level – reading the operating status

The info level offers the following information about operation of the system:

Current time Residual capacity of the exchanger in operation Time since last regeneration

Press the key to continue or the key to go back

Remaining duration of the service interval

Press the key to continue or the key to go back

Current regeneration step Remaining duration of the current regeneration step

Page 35: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

35

2.4 System status display The residual capacity of the exchanger bottle in operation is displayed in %.

For the exchanger bottle that is undergoing regeneration, the current flow direction is indicated by arrow symbols.

In addition to the water meter symbol, the 0 °dH flow rate currently coming from the system is displayed in m³/h.

If the pre-alarm salt supply (Order no.185335) option is fitted, the brine tank is shown as empty when salt tablets need to be refilled.

2.5 Setting operating parameters – operator menu

On start-up, at least the time and raw water hardness must be programmed for the exchanger bottle in operation (see table below, printed in bold). The raw water hardness must be set to the highest hardness that is encountered, if there are fluctuations in the water quality.

Starting point: Basic display (time/residual capacity/time since last regeneration)

Press and hold P key for > 1 sec. >> Operator menu appears.

Parameters Factory setting Setting

range Comment

Raw water hardness [°dH] 25 1 ... 250 Data logging (*) No No/Yes Interval [min.] 60 1 ... 999 Time XX:XX 00:00…23:59 Date XX.XX.XXXX (*) The Yes setting means the following information is recorded in the set interval:

Residual capacity of the exchanger in operation (C XX.XX m³).

Current flow (Q XX.XX m³/h).

Time since last regeneration (T XXX h).

Current regeneration step 0 = No regeneration 1 = Backwashing 2 = Salting 3 = Slow rinsing 4 = Washing out 5 = Filling brine tank

Time until service is due (S XXX d).

Regeneration counter (XXXXXX).

Soft water meter (XXXXXX m³).

Page 36: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

36

The data is stored on the SD card as a *.txt file, the values are separated from one another by semicolons. This means the file can be imported into MS Excel, for example, without difficulty.

Note: Prior to removing the SD card, make sure that the data logging was terminated with "No"!

Note: The SD card used must be formatted FAT32. We recommend proper formatting instead of quick formatting.

2.6 How to release a manual regeneration

Starting point: Basic display (time/residual capacity/time since last regeneration).

Press and hold the key > 5 sec.: The exchanger bottle that is in operation is regenerated.

The function is not possible

If a regeneration is already in progress (the key command is not stored).

If a regeneration lock is active (either via programmable input or in the form of an interval between two regenerations).

Page 37: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

37

2.7 Changing system parameters – code 290

In this menu, it is possible to set various hardness units and operating languages.

Starting point: Basic display (time/residual capacity/time since last regeneration).

Press and hold P and keys simultaneously, the code request appears

Use the or keys to set code 290 and confirm with the P key.

Parameters Factory setting Setting range Comment Hardness unit °dH °dH / °f / mol/m³ Applies to raw water

hardness and capacity rate

Data record Depending on system size

Set value is not allowed to be changed!

Capacity rate [m³ x °dH] Indication only

Display values cannot be changed Water meter

pulse rate [l/Imp]

Operating language

Deutsch Deutsch / englisch / französisch / niederländisch / italienisch / spanisch / russisch

Page 38: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

38

Control via reverse osmosis system GENO®-OSMO-X

1 | Introduction

The GENO-mat® duo WE-Osmo-X water softeners are volume-controlled. The systems are operated and monitored by means of the control electronics of the GENO®-WE-OSMO-Xreverse osmosis system.

1 Drinking water filter BOXER® K 1“ 6 Reverse osmosis system GENO®-OSMO-X

2 GENO®-DK 2 system separator 7 Permeate tank with sterile air filter and level probe

3 Water softener Delta-p® 8 Pressure booster system GENO®-FU-X 2/40-1 N

4 GENO®-softwatch Komfort

5 Active carbon filter AKF

Fig. F-2: Installation drawing

Page 39: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

39

The following information is stored in the OSMO-X control unit.

This can be found in the subsystem range of the INFO level (can be called up using the or keys).

Residual capacity AT * [m³]

Flow rate Q [m³/h]

Time since last regeneration [h]

Current regeneration step [X]

Time to service due [d]

Regeneration counter [XXX]

Counter soft water [m³]

Software version [X.XX]

Home-button

Operating mode, current measuring values

Access to theGENO®-OSMO-X-

menu

Page 40: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

40

2 | How to operate the control unit

2.1 Change, save, reject parameters

In a menu with permanently stored selections, any choice (line) can be selected by tapping on it. The middle line is in slightly larger print, however.

Save your selection with this button.

Quit the menu with this button without changing the prior selection.

The numerical and the alpha-numerical menu each feature the same operating logic:

Save your selection with this button.

Quit the menu with this button without changing the prior selection.

Save your selection with this button.

Quit the menu with this button without changing the prior selection.

Page 41: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

41

2.2 Acknowledgement of errors/signals In case of a pending signal or error, the status line

changes its colour and on the home screen, the subsystem concerned has a coloured frame.

Yellow = signal

Red = error

Tap on the status line >> Switch to error list

The error list may show one or several entries.

Tap on the entry you are interested in >> switch to the acknowledgement window

Button to return to the Home screen

The acknowledgement window will show an illustration of the subsystem concerned.

Acknowledgement button of the signal/error

Button to call up a help text including the telephone number of the technical customer service.

Button to return to the error list

The error can either be acknowledged or left pending. In any case, you will get back to the error list.

Acknowledge signal/error

Leave signal/error pending

Page 42: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

42

2.3 Screen saver

The screen saver is displayed automatically if the screen is not touched for 5 minutes (or after an adjustable period of time).

As soon as the touch screen is tapped on or a signal or an error occurs the display returns to the basic display.

3| System range

3.1 System menu I System menu I can be accessed without entering a code. The

parameters stored apply to all systems in case more subsystems than just the GENO®-OSMO-X are present and are operated via the GENO®-tronic operating element.

Parameters Factory setting Setting

range Comment

Raw water hardness [°dH] 25 1 ... 250

Page 43: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

43

3.2 Manual mode Manual regeneration Off/On

3.3 System setting

Parameters Factory setting Setting range Comment Hardness unit °dH °dH / °f / mol/m³ Applies to raw water

hardness and capacity rate

Data record Depending on system size

Set value is not allowed to be changed!

Capacity rate [m³ x °dH] Indication only

Display values cannot be changed Water meter

pulse rate [l/Imp]

Activation time 00:00 00:01 - 23:59

Page 44: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

44

G Faults

1 | Basic information

Even carefully designed and manufactured technical systems that are operated properly, may experience malfunctions. There is a difference between warnings and faults:

Warning = signal contact of the control unit opens (terminals 30/31), yellow LED is illuminated

Fault = fault signal contact of the control unit opens (terminals 29/30), red LED is illuminated

As long as the power supply is on and no warning/fault is pending, the signal contact and the fault signal contact are closed.

The warning/fault can be acknowledged using the P key.

Note: Grünbeck's technical customer service/authorised service company must always be notified in the event of faults that cannot be eliminated with the information given in table G-1! When contacting the technical customer service, please indicate the system designation, serial number and the error message displayed.

1.1 Warnings Table G-1: Warnings

This is what you observe This is the cause This is what to do

Service interval The maintenance interval of the water softener has expired

Inform Grünbeck's technical customer service/authorised service company

Low salt Er A Not enough salt in brine tank

Check salt level in brine tank and refill salt tablets as per DIN EN 973 A, if necessary

1.2 Faults Table G-2: Faults

This is what you observe This is the cause This is what to do

Power failure fault Power failure > 1 minute If the power failure has continued for some time, start a manual regeneration to be on the safe side. The water that flowed through the system in the meantime will not have been measured, and the exchanger in operation may have reached the limits of its capacity.

Valve motor fault The next step setting on the control valve was not reached within the required time

If the fault reoccurs within 5 minutes after having been acknowledged, notify Grünbeck's technical customer service/authorised service company

Hard water fault While one exchanger bottle was still undergoing regeneration, the capacity

Malfunction is automatically acknow-ledged as soon as a regenerated exchanger bottle is available again

Page 45: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

45

of the other exchanger bottle already expired.

Restrict the system flow to the max. continuous flow (chapter C, technical data table).

Microswitch fault The signal from microswitch S2 is active at terminal 14 outside a regeneration

Check the wiring and function of the switch, and notify Grünbeck’s customer service/authorised service company if necessary

Motor current fault Monitoring of the step motor current has tripped

If the fault reoccurs within 5 minutes after having been acknowledged, notify Grünbeck's technical customer service/authorised service company

Page 46: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

46

H Maintenance

1 | Basic information

In order to guarantee the reliable function of water softeners over a long period of time, some maintenance work has to be performed at regular intervals. This applies in particular to the softening of drinking water where the required measures are defined in the pertinent regulations and guidelines. All regulations and guidelines which apply at the installation site must be strictly adhered to.

DIN 1988 part 8 / A 12 stipulates:

an inspection must be performed at least every 2 months.

Maintenance must be carried out twice a year. In case of water softeners that carry a DVGW certificate, yearly maintenance is sufficient!

Maintenance must be performed by the Grünbeck’s technical service/authorised service company or by an approved company.

An operating log must be kept in order to document the maintenance work performed.

Notes: A maintenance contract ensures that any required maintenance work is performed in due time.

The operating log is attached to this operation manual.

2 | Inspection (functional check)

You may perform the regular inspections yourself. We recommend inspecting the water softener at shorter intervals after installation, before switching over to the standard inspection cycle. However, an inspection is compulsory at least every 2 months.

Please refer to the following summary for the tasks to be performed within the framework of an inspection.

Summary: Inspection work

Determine the raw water hardness. (Water test kit "Total hardness").

Determine the soft water hardness (0°dH (°f, mmol/l)) or the soft water with blending in case of water softeners with blending valve (Water test kit "Total hardness").

Check control unit settings: a) Time b) Raw water hardness

Check salt level in brine tank. If required, refill salt (refer to chapter H-2.1).

Page 47: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

47

Caution! If the salt level falls below the minimum filling level, hardness may break through. Observe the minimum salt filling level (see Technical Specifications, chapter C). In case of systems where no specific value is indicated, refill the water softener as soon as the level has fallen to just a few centimetres.

Evaluate the salt consumption with reference to the water volume consumed.

Note: Minor deviations are normal and cannot be prevented technically. If you detect major deviations, please contact Grünbeck’s technical service/authorised service company.

Check control valve to drain for tightness (in operating mode).

2.1 How to refill salt

Warning! Impurities in the brine tank may adversely affect the water quality.

For hygienic reasons be very careful when refilling salt.

Caution! Insoluble impurities in the salt may cause malfunctions at the brine valve and at the injector of the control valve. A defined salt quality is required for the reliable function of the water softener.

Only use salt tablets as per DIN EN 973 type A.

A few precautionary measures ensure hygienically and technically perfect conditions:

Only store the salt in dry and clean areas.

Do not use salt from packages that are already open.

Clean the outside of the packages before opening them.

Fill the regeneration salt directly from the package into the brine tank.

Close the brine tank immediately after refilling.

Page 48: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

48

3 | Maintenance

According to DIN 1988 part 8 / A 12, maintenance work at water softeners may only be performed by Grünbeck’s technical service/authorised service company or an approved company.

An operating log must be kept for water softeners. In this operating log, the customer service technician records all maintenance and repair work performed. In case of mal-functions, this log helps to identify possible sources of error. In addition the log documents the proper system maintenance.

Note: Make sure that all maintenance work is recorded in the operating log.

Summary: Maintenance work

Read the water pressure, flow pressure and water meter value.

Determine the hardness Raw water hardness, soft water hardness, 0°dH (°f, mmol/l) test.

Readjust the blending valve and check the blending hardness again, if necessary. With Delta-p®, program the required soft water hardness in the control unit.

Adjust the electronics settings with reference to the measured hardness values.

Check the programming of the control unit.

Check the brine regulation (salting, filling of brine tank) and program settings; readjust them, if necessary.

Check release of regeneration.

Check start of turbine water meter.

Check control valve for tightness, replace wearing seals if necessary, check the proper function of the drive motor of the control valve, clean injector and sieve – typical hydraulic values.

Clean brine tank and brine valve.

Check regeneration salt supply (quantity and quality).

Check hose connections and seals and replace, if necessary.

Caution: Danger of water damage! Damaged or worn hose connections may tear. Therefore, DIN 1988, part 8, paragraph A 12 recommends checking and if necessary replacing the flexible connection hoses.

Page 49: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

49

Safety fitting (e.g. system separator) checked for non-return function. Not required in case of intrinsically safe water softeners, in particular water softeners with DVGW test mark!

In water softeners with a disinfection unit: Functional check of the disinfection unit (measure flow). - With Delta-p®, only possible with code -.

If necessary, read regeneration counter, total soft water volume, error memory. - With Delta-p®, system data printout is possible via serial port -.

If necessary, reset service interval.

Record all data and activities, including repair work in the operating log.

Hand over the water softener and the filled out operating log to the owner-operator.

3.1 Operating log The operating log is attached to this operation manual. When

starting up the system, make sure to record all data on the cover sheet of the operating log and fill in the first column of the checklist.

The customer service technician will fill in a column of the check list whenever maintenance is performed. This document provides evidence of proper maintenance.

4 | Spare parts You may order spare parts and consumables from your local

Grünbeck representative (refer to www.gruenbeck.de).

Note: Detailed specification of the wearing parts (chapter C).

Page 50: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

50

5 | Operating log

Customer Name: ...................................................................

Address: .................................................................

..............................................................................

..............................................................................

GENO®-mat duo water softener

WE-X WE-OSMO-X

50 65 65

130 150 150

230 300 300

330 450 450

530 750 750

(please check appropriate box)

Serial number ..........................................................

Installed by ..............................................................

Filter: Make/type ..................... / ..............................

Connection data: (please check appropriate box)

Drain connection DIN 1988 Yes No

Floor drain available Yes No

Line upstream of water softener

Zinc-plated

Copper

Plastic

Page 51: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

51

Maintenance work on the water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Check list

Please enter measured values. Confirm checks with OK or enter repair work performed.

Maintenance performed (date) Start-up

Measured values

Water pressure [bar]

Flow pressure [bar]

Water meter reading [m³]

Supply hardness ° dH (measured)

Dilution hardness °dH (measured)

0 °dH inspection

Inspections and checks on controller and control valve

Controller setting checked

Regeneration activation checked

Injector and sieve cleaned

Control valve checked for tightness

Function of driving motor checked

Work on brine tank and brine valve

Brine tank and brine valve cleaned

Operation and setting of brine valve checked

Connections, hose connections, seals

Seals and hose connections checked

Safety fitting (e.g. backflow preventer) checked for backflow

Miscellaneous

Notes

Customer service technician

Company

Work time certificate (no.)

Signature

Page 52: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

52

Maintenance work on the water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Check list

Please enter measured values. Confirm checks with OK or enter repair work performed.

Maintenance performed (date)

Measured values

Water pressure [bar]

Flow pressure [bar]

Water meter reading [m³]

Supply hardness ° dH (measured)

Dilution hardness °dH (measured)

0 °dH inspection

Inspections and checks on controller and control valve

Controller setting checked

Regeneration activation checked

Injector and sieve cleaned

Control valve checked for tightness

Function of driving motor checked

Work on brine tank and brine valve

Brine tank and brine valve cleaned

Operation and setting of brine valve checked

Connections, hose connections, seals

Seals and hose connections checked

Safety fitting (e.g. backflow preventer) checked for backflow

Miscellaneous

Notes

Customer service technician

Company

Work time certificate (no.)

Signature

Page 53: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

53

Maintenance work on the water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Check list

Please enter measured values. Confirm checks with OK or enter repair work performed.

Maintenance performed (date)

Measured values

Water pressure [bar]

Flow pressure [bar]

Water meter reading [m³]

Supply hardness ° dH (measured)

Dilution hardness °dH (measured)

0 °dH inspection

Inspections and checks on controller and control valve

Controller setting checked

Regeneration activation checked

Injector and sieve cleaned

Control valve checked for tightness

Function of driving motor checked

Work on brine tank and brine valve

Brine tank and brine valve cleaned

Operation and setting of brine valve checked

Connections, hose connections, seals

Seals and hose connections checked

Safety fitting (e.g. backflow preventer) checked for backflow

Miscellaneous

Notes

Customer service technician

Company

Work time certificate (no.)

Signature

Page 54: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

54

Maintenance work on the water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Check list

Please enter measured values. Confirm checks with OK or enter repair work performed.

Maintenance performed (date)

Measured values

Water pressure [bar]

Flow pressure [bar]

Water meter reading [m³]

Supply hardness ° dH (measured)

Dilution hardness °dH (measured)

0 °dH inspection

Inspections and checks on controller and control valve

Controller setting checked

Regeneration activation checked

Injector and sieve cleaned

Control valve checked for tightness

Function of driving motor checked

Work on brine tank and brine valve

Brine tank and brine valve cleaned

Operation and setting of brine valve checked

Connections, hose connections, seals

Seals and hose connections checked

Safety fitting (e.g. backflow preventer) checked for backflow

Miscellaneous

Notes

Customer service technician

Company

Work time certificate (no.)

Signature

Page 55: BA-184046-inter GENO-mat duo WE-X - gruenbeck.de · It is divided into several chapters (a letter is assigned to each of them) which are listed in the “Table of contents” on page

Water softenerGENO-mat® duo WE-X,

GENO-mat® duo WE-OSMO-X

Order no. 024 184 046-inter Edited by: phar/mrie G:\BA-184046-inter_GENO-mat duo_WE-X.docx

55

Maintenance work on the water softener GENO-mat® duo WE-X, GENO-mat® duo WE-OSMO-X

Check list

Please enter measured values. Confirm checks with OK or enter repair work performed.

Maintenance performed (date)

Measured values

Water pressure [bar]

Flow pressure [bar]

Water meter reading [m³]

Supply hardness ° dH (measured)

Dilution hardness °dH (measured)

0 °dH inspection

Inspections and checks on controller and control valve

Controller setting checked

Regeneration activation checked

Injector and sieve cleaned

Control valve checked for tightness

Function of driving motor checked

Work on brine tank and brine valve

Brine tank and brine valve cleaned

Operation and setting of brine valve checked

Connections, hose connections, seals

Seals and hose connections checked

Safety fitting (e.g. backflow preventer) checked for backflow

Miscellaneous

Notes

Customer service technician

Company

Work time certificate (no.)

Signature