QUICK START
GUIDE
WAVELET 4R
April 2020
P/N 0100711 Rev 1
AYYEKA
AYYEKA WAVELET SCHEMATIC
External (Bottom)
3
It is important that you read the Quick Start Guidein a controlled environment prior to installation.
Set up, activate, and successfully test the entiresystem (Wavelet 4R, sensors, and antennaconnection) indoors, in a controlled environment,before going to the field for installation.
!
1
IMPORTANT
Contact AYYEKA SUPPORT for technical support: [email protected] +1 (310) 876-8040 (US) +31 40 209-1001 (EMEA)
ALWAYS COORDINATE Basic Wavelet Kit installation with the local authority before starting installation works, which should be completed by trained and authorized personnel.
The WARRANTY offered by Ayyeka covers only Ayyeka supplied hardware and software for the duration of the warranty period as per the warranty terms and conditions.
AYYEKA IS NOT LIABLE for damage or injury as a result of handling, installation, or maintenance of its supplied systems.
DO NOT THROW AWAY the Basic Wavelet Kit, as it contains a lithium battery. Please dispose of properly.
CELLULAR NETWORK SIGNAL is required for proper communication.
OPERATING TEMPERATURE RANGE of -40°C to -80°C (-40°F to -176°F).
2
AYYEKA WAVELET SCHEMATIC
External (Bottom)
SCHEMATIC
BOTTOM
Cellular
Sensor Input Port
17.4
cm
(6.9
in)
13.3 cm (5.2 in)
7.3
cm
(2.8
in)
AYYEKA
AYYEKA WAVELET SCHEMATIC
External (Bottom)
3
TURN HERE
DO NOT TURN HERE
GETTING STARTED
GETTING STARTED
BASIC WAVELET KIT
1 2
3 4
Wavelet Device & Protector
M12 Field Attachable Sensor Connector (optional; Ordered separately)
Wavelet Activator
1x
GETTING STARTED
1x1x
1x1x
M8 Female Field Attachable Power Connector (optional; see page 16)
4
Other tools and/or materials may be required (not included):
Electric Screw DriverRotary Hammer
5 6Zip Ties, Screws, and Anchors
Cellular Antenna (REQUIRED; ordered separately)
4x2x 4x
GETTING STARTED
5
NOTE: Special Installation Locations
WEAK SIGNAL LOCATIONS:
If the Wavelet is installed in an area with weak cellular signal, activate the Wavelet and place in the intended installation location with closed doors/access hatch (see step 3).
Log in to home.ayyeka.com to ensure that cellular signal has been recently updated in the last few minutes.
UNDERGROUND/INDOOR WAVELET INSTALLATIONS:
Make sure the cellular antenna is properly installed to provide adaquate signal quality
Wait for at least 15 minutes, then log in to the user interface at home.ayyeka.com to make sure stable communication is confirmed
6
7
TURN HERE
DO NOT TURN HERE
7
TURN HERE
DO NOT TURN HERE
Connect the sensor cable assembly with the field attachable connector to the mating panel connector on the Wavelet. Turn the adjustable stainless steel end piece to secure the field attachable connector to the Wavelet.
1
CAUTION: Do not turn the black plastic hood of the connector. Turning the black hood may cause the wires to disconnect, break, and/or damage the connector pins.
SENSOR CONNECTION
7
EXTERNAL ANTENNA CONNECTION
Connect the cellular antenna to the antenna port (ANT 1).2
WAVELET ACTIVATION
Place the magnetic Wavelet Activator on the embossed Ayyeka logo on the front of the Wavelet enclosure. Wavelet will initiate a 15 minute test mode of high frequency sampling and transmission. The device will then return to its default configuration.
3
IMPORTANT NOTE: The antenna does not appear in the remaining depictions in this guide, but should remain connected once properly secured to the appropriate panel connectors.
Cellular Antenna
8
WAVELET ACTIVATION
Verify the installation with your mobile phone by using AyyekaGo mobile application.
If you haven’t already done so, download the AyyekaGo mobile app for iOS or for Android. Search the App Store or Google Play for “AyyekaGo” or use the QR codes below
There are two ways to pair your phone with your Wavelet:
1. Select ”Get Key Via Web”. This will direct you to enter your log-in credentials for the StreamView user interface.
2. Select ”Enter Key Manually”. The Mobile Pair Key is found in the StreamView user interface in the Devices tab.
4
Access the Ayyeka user interface at home.ayyeka.com using your log-in credentials. Expect data to appear between 5 – 10 minutes after the test mode is initiated.
5
9
WAVELET ACTIVATION
6 The screen display should resemble the following:
If the Wavelet is transmitting properly, you have completed the installation successfully and can begin collecting and viewing your data!
If data does not transmit properly, change the Wavelet installation location and activate again (step 3). If the problem persists, contact Ayyeka for assistance. [email protected] +1 (310) 876-8040 (US) +31 40 209-1001 (EMEA)
10
Attaching the protector
7 After the Wavelet completes the transmission process, place the Wavelet protector above the connector ports and secure the Wavelet protector into the Wavelet enclosure.
CAUTION: The protector is provided to shield the connector from tampering or overexposure that could result in disconnected wiring.
GETTING STARTED
a. Insert the two lower clips into the two lower holes of the Wavelet enclosure.
b. Snap the upper clips into place in the two grooves above the panel connector.
Lower Clips
Upper Clips
a
b
11
11
Secure the Wavelet on a wall, pipe, or other secure mounting location using zip ties or screws.
8
ORWall Mounted
Pipe Mounted
12
YOUR WAVELET 4R IS NOW SUCCESSFULLY INSTALLED!
13
WAVELET 4 – ANALOGANALOG – PANEL CONNECTOR #1 – M12 8-PIN MALE
Connector Pin # Function Name Pin Assignment
1 Signal+ 4-20mA or 0-24V Input #1 Front
2 Common Negative (-)
3 Supply+ Wavelet 12V Power Supply #2 (+)
4 Supply+ Wavelet 12V Power Supply #1 (+)
5 Signal+ 4-20mA or 0-24V Input #4
6 Signal+ 4-20mA or 0-24V Input #3
7 Signal+ 4-20mA or 0-24V Input #2
8 Common Negative (-)
+1 (310) 876-8040 (US) +31 (40) 209-1001 (EMEA) [email protected]
WAVELET PINOUT
PANEL CONNECTOR – M12 8-PIN MALEConnector Pin #
Function Description Pin Assignment
1 Signal 4-20mA or 0-24V Input #1 Front
2 Signal PCNT_0 – pulse counting, edge, periodic, output
Dry contact, open drain, 0V or 2.8V (max)
3 Signal RS485 A and RS232 RX
4 Supply Wavelet 12V Power Supply #1 (+)
5 Signal RS485 B and RS232 TX Back
6 Signal 4-20mA or 0-24V Input #2
AYYEKA WAVELET SCHEMATIC
External (Bottom)
#2
7 Signal PCNT_1 – pulse counting, edge, periodic, output
Dry contact, open drain, 0V or 2.8V (max)
8 Common GND
14
GETTING STARTED
3 pos 4 pos
inner view ( 2 : 1 )
namedate
42K1A316
Strakerjahn26.07.11
16.09.11 Hüther
Female connector M8x1, fieldattachable , axial, screw termination
see table
Indndex: c 18.07.13 KH Ä4842Wire cross section adapted
3 1
Ø14
(RE
F. 4
0)
Ø13,7
Width across flats 13
Width across flats 12
Max. external cablediameter see table
Width across flats 13
4 2
13
Materials: Contact: Contact plating: Contact carrier: Cable sealing: O-Ring: Coupling nut: Housing:
CuZn Au over Niin mating area PA6, UL 94 NBR Silicone / NBR CuZn, Ni PA6 GF, UL 94
Installation specification for locking nutto counter connector: Recommendedtorque: Conec installation tool:
0,4 Nm Torque wrench: 36-000200Insert across flats 13: 36-000220
Description:
SAL - 8 - RKC3-S
Cable-:
4 - 5,5mm
SAL - 8 - RKC4-S 4 - 5,5mm
Part no:
42-00010
42-00012
Pos:
3
4
terminationØ1,9
Technical specification: Rated voltage:IEC 61076-2-104 Current rating:IEC 61076-2-104 Insulation resistance:IEC 60512 Pollution degree:IEC 60664-1 Degree of protection:IEC 60529 Temperature range:IEC 60664-1 Mating cycles:IEC 60512-9a Wire cross section:
3pos 4pos 60 V 30 V 4 A at 40°Cwith 0,5mm²
>= 100 MΩ 3/2 IP 67, in matedcondition -30°C ... +85°C >= 100 AWG 20 / max. 0,5 mm²
SW 0,9
Installation tool forwire termination( included )
4
M8 3-Pin Female Power Connector
Wire To Connect:Cable Wire Cross Section Surface Area
0.14 – 0.5 mm2
Wire Gauge AWG 26-20Cable Ø Diameter 4 – 5.5 mm
+ Installation Tool for Wire Termination (Included)
No Connection 5-28VDC (+)
Negative (-)
POWER CONNECTOR PINOUT
If using an external power source, refer to the pinout below:
EXTERNAL POWER:
4
3 1
POWER – PANEL CONNECTOR #4 – M8 3-PIN MALE
Connector Pin #
Function Description Pin Assignment
1 Supply+ 5-28VDC (+) Front
3 No Signal No Connection
4 Common Negative (-)
POWER – PANEL CONNECTOR #4 – M8 3-PIN MALE
Connector Pin # Function Name Pin Assignment
1 Supply+ 5-28VDC (+) Front
3 No Signal No Connection
4 Common Negative (-)
WAVELET 4 – POWER
43 1
+1 (310) 876-8040 (US) +31 (40) 209-1001 (EMEA) [email protected]
15
NOTES
www.ayyeka.com [email protected] +1 (310) 876-8040 (US) +31 40 209-1001 (EMEA)