axa dali p20 - smartscape connected lighting systems › wp-content › uploads › 2014 › 06 ›...

6
AXA DALI P20 DALI Broadcast Controller Installation Manual

Upload: others

Post on 03-Jul-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AXA DALI P20 - Smartscape Connected Lighting Systems › wp-content › uploads › 2014 › 06 › ... · The DALI P20 is a DALI broadcast controller for control of up to 20 DALI

AXA DALI P20

DALI Broadcast Controller

Installation Manual

Page 2: AXA DALI P20 - Smartscape Connected Lighting Systems › wp-content › uploads › 2014 › 06 › ... · The DALI P20 is a DALI broadcast controller for control of up to 20 DALI

2

THE DALI P20 MUST BE INSTALLED BY A LICENSED ELECTRICIAN

IMPORTANT INFORMATION

ELECTRICIANS MUST READ PRIOR TO INSTALLATION

1) This product must only be installed by persons who are appropriately licensed by the applicable State regulatory body.

2) This product must be connected to circuits that incorporate 10 A rated circuit breaker protection.

3) Hazardous voltage exists at the terminals of this product. Ensure the circuit is isolated before removing this product from the wall or electrical enclosure.

4) Damage caused by incorrect installation, force-majeure, electrical surges, lightning, power grid fluctuations, water or by connection to alternative power supply sources (such as solar inverters, etc.) is not eligible for warranty repair.

5) Appliance not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge.

6) Children should be supervised by a person responsible for their safety to ensure that they do not play with the appliance

DEVICE OVERVIEW

The DALI P20 is a DALI broadcast controller for control of up to 20 DALI fittings. Its integral DALI power supply means no other hardware is required for this controller to operate. With an input for a movement detector and programmable options for Turn on Level, Sensor mode, Run on Timer and Minimum Level the DALI P20 is not only simple to install and use but also extremely flexible in its functionality.

Page 3: AXA DALI P20 - Smartscape Connected Lighting Systems › wp-content › uploads › 2014 › 06 › ... · The DALI P20 is a DALI broadcast controller for control of up to 20 DALI

3

INSTALLATION INSTRUCTIONS

Before installing this product read all instructions carefully and please keep this installation manual for future reference.

WARNING: To prevent electric shock, please ensure that power is isolated before installation.

This product is designed for indoor use only.

The DALI P20 wall plate must be surface mounted onto a fully enclosed wall cavity or be installed on a suitable surface mount enclosure. The DALI P20 circuitry must be electrically concealed. Installation must be carried out by a qualified electrician in accordance with National Wiring Regulations and other applicable regulations. Compliance to AS/NZS Standards and Low Voltage Directives may be invalidated if not used or installed according to the published specification. The DALI P20 contains no user serviceable parts and should be returned to the manufacturer for repair. Wall Cut-out Requirements

The cut-out required is 63mm (L), 50mm (W), 50mm (D) There are four options for wall mounting of the DALI P20. These are:

• Plasterboard with C-Clip mounting flange • Brick with a mounting block • Timber with a mounting block • Direct screwing onto a suitable material

Wiring Diagram

Page 4: AXA DALI P20 - Smartscape Connected Lighting Systems › wp-content › uploads › 2014 › 06 › ... · The DALI P20 is a DALI broadcast controller for control of up to 20 DALI

4

The rear of the DALI P20 has a terminal block that accommodates up to 1.5mm2 wire for electrical and control cable connection.

Terminal Description S Sensor Input (220 – 240V a.c. Trigger Input) A Electrical Active N Electrical Neutral

DA+ DALI Data + DA- DALI Data -

220 -240V AC 50HZ, 2Watt.

Controller Rating

DALI P20 Model Number

AXA Design Manufacturer

DALI Technical Information Installer technical information for DALI based products:

• DALI requires 2 wires to connect between devices. These wires are not polarity dependant.

• These wires are at ELV (Extra Low Voltage) potential and are daisy chained to all devices. Some devices, such as HF ballasts are mains powered, and only provide functional isolation between the mains and the DALI control. This means that DALI control wire must be treated as if it were at mains potential.

• Cable size

DALI Cable Run Length Recommended Minimum DALI Cable Conductor Size

Less than 100 Meters 0.5mm²

100 to 150 Meters 0.75mm²

More than 150 Meters 1.5mm²

More than 300 Meters Not recommended, avoid runs over 300 Meters

• DALI Standard – IEC 62386

PROGRAMMING OPTIONS Option 1: Turn on level

• Mode 1. 100% (default) • Mode 2. Last level

Option 2: Sensor mode. • Mode 1. Manual on, Auto off (default) • Mode 2. Auto on, Auto off • Mode 3. Disabled

Option 3: Sensor run on time (amount of extra time after no 240 input from sensor) • Mode 1. 0 Minutes (default) • Mode 2. 15 Minutes • Mode 3. 30 Minutes • Mode 4. 60 Minutes

Page 5: AXA DALI P20 - Smartscape Connected Lighting Systems › wp-content › uploads › 2014 › 06 › ... · The DALI P20 is a DALI broadcast controller for control of up to 20 DALI

5

Changing Programming Options

1. Press and hold the push button for 10 seconds and you're in programming mode. The Blue LED will flash to indicate which programming option you are in and what mode that option is set to.

2. Press the push button to change to the next mode. 3. Rotate the knob to change to the next option. 4. To exit programming press and hold the push button for 10 seconds or wait 30 seconds

and it will exit programming automatically. Example Press and hold for 10 seconds… “.” … “.” … … “.” … “.” … … Option 1 mode 1 Press the push button “.” … “.” “.” … … “.” … “.” “.” … … Option 1 mode 2 Rotate the knob “.” “.” … “.” … … “.” “.”… “.” … … Option 2 mode 1 Press the push button “.” “.”… “.” “.” … … “.” “.”… “.” “.” … … Option 2 mode 2

SPECIFICATIONS

Electrical Nominal Operating Voltage 220 to 240V AC Nominal Operating Frequency 50Hz Maximum Load 24VA Maximum Wire Size 1.5mm2

Environmental Ambient Operating Temperature Range 0 to 50oC Relative Humidity 5 to 95% non-condensing Altitude 0 to 3000m MSL%

Control Load Per DALI ballast 2mA Maximum Number of DALI Ballasts 20 DALI Operating Mode Broadcast DALI Data Encoding Manchester DALI Data Baud Rate 1200 DALI Data Cable Requirement 2 wire double insulated Maximum DALI Cable Length 300m with 1.5mm cable (2V line drop maximum)

Physical Product Dimension 117mm (L), 73(W), 60mm (D) Installation Cut-out 63mm (L), 50mm (W), 50mm (D) Installation Indoor Use Only

Standard AS/NZS 60335.1:2011(IEC 60335-1 Ed. 5 MOD) including Amendment 1, Including AU variations.

Page 6: AXA DALI P20 - Smartscape Connected Lighting Systems › wp-content › uploads › 2014 › 06 › ... · The DALI P20 is a DALI broadcast controller for control of up to 20 DALI

6

CONTACT DETAILS Postal and Delivery Address

Smartscape Automation

15 Locust St,

The Gap Qld. 4061

Australia

Phone +61 (07) 3357 1922

Website http://www.ssqld.com.au

Email [email protected]

DISCLAIMER Smartscape Automation reserves the right to alter specifications and design without further notice. Smartscape Automation will not be held responsible for the misinterpretation of printed material contained in this manual. Further enquiries should be directed to Smartscape Automation using the listed contact details.