avr on load tap changer

Upload: insan-aziz

Post on 02-Jun-2018

281 views

Category:

Documents


3 download

TRANSCRIPT

  • 8/10/2019 AVR on Load Tap Changer

    1/39

  • 8/10/2019 AVR on Load Tap Changer

    2/39

    On/Under Load Tap Changing Transformer

    Automatic Voltage Regulating Control Relay

  • 8/10/2019 AVR on Load Tap Changer

    3/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays3 3

    Contents

    On Load Tap Changing Transformers

    Voltage Regulation

    Time Delays

    Grading Between Voltage Levels

    Line Drop Compensation

    Parallel Operation

  • 8/10/2019 AVR on Load Tap Changer

    4/39On/Under Load Tap Changing Transformers Voltage Regulating Control Relays4 4

    Voltage RegulationPurpose

    Electrical plant is designed to operate within finite

    voltage limitsTo control the system voltage transformers with tapchangers are commonly used

    Off Load manually changedOn Load automatically adjusted

    Tap changers physically alter the transformer ratio and

    hence the voltage Automatic voltage regulating relay is used to control thetap changer

  • 8/10/2019 AVR on Load Tap Changer

    5/39On/Under Load Tap Changing Transformers Voltage Regulating Control Relays5 5

    Voltage RegulationPerformance Criteria

    Two Mutually Exclusive Parameters

    voltage quality

    number of tap changes

    Voltage Quality

    customer focused quality measurement

    percentage of time outside deadband or statuary limits

    length of voltage disturbance

    Number of Tap Changes

    supplier focused quality measurement

    directly relates to cost of ownership of the tap changer

  • 8/10/2019 AVR on Load Tap Changer

    6/39On/Under Load Tap Changing Transformers Voltage Regulating Control Relays6 6

    On Load Tap Changing Transformers

  • 8/10/2019 AVR on Load Tap Changer

    7/39On/Under Load Tap Changing Transformers Voltage Regulating Control Relays7 7

    On Load Tap Changing TransformersTypical Supply Network

  • 8/10/2019 AVR on Load Tap Changer

    8/39On/Under Load Tap Changing Transformers Voltage Regulating Control Relays8 8

    On Load Tap Changing TransformersTap-Outs and Windings

    Tap-outs can be in the HV or LV winding

    Tap-outs can be at the Line End or Neutral End

    Cause a variation in the impedance of thetransformer

    Transformer impedance calculated at thecentre tap position

  • 8/10/2019 AVR on Load Tap Changer

    9/39On/Under Load Tap Changing Transformers Voltage Regulating Control Relays9 9

    On Load Tap Changing TransformersDevelopment of the Tap Changer

    Developed in the late 1920s

    Two primary considerations

    The load current must not be interrupted

    No windings should be short-circuited

    during transitionsEarly tap changers were reactors, could becontinuously rated useful when mechanisms

    were unreliableResistor transition tap changers now used,reliable stored energy drive mechanisms

    Typical Operation ~75ms

  • 8/10/2019 AVR on Load Tap Changer

    10/39On/Under Load Tap Changing Transformers Voltage Regulating Control Relays10 10

    Voltage Regulation

  • 8/10/2019 AVR on Load Tap Changer

    11/39

  • 8/10/2019 AVR on Load Tap Changer

    12/39On/Under Load Tap Changing Transformers Voltage Regulating Control Relays12 12

    Voltage RegulationExample Operation

    + VoltageDeadband

    - VoltageDeadband

    VoltageSetting

    Time Delay

    t

    V

    Voltage outof deadband

    Voltage restoredto within deadband

  • 8/10/2019 AVR on Load Tap Changer

    13/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays13 13

    Time Delays

  • 8/10/2019 AVR on Load Tap Changer

    14/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays14 14

    Time DelaysInitial Time Delays

    Initial time delay used to filter transient voltage fluctuations

    definite time

    inversely proport ional to the deviation from the voltage setting

    Operating Time

    VoltageV B an

    d +

    V B an d -

    V S e t t i n g

    Definite TimeCharacteristic

    Inverse Time

    Characteristic

    l i l Ch S

  • 8/10/2019 AVR on Load Tap Changer

    15/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays15 15

    Multiple Tap Change SequenceInter-Tap Delay - Definite Time

    VoltageDeviation

    Vs+dVs

    Initial DelayInitial Delay Definite Time)

    Time

    M l i l T Ch S

  • 8/10/2019 AVR on Load Tap Changer

    16/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays16 16

    Multiple Tap Change SequenceInter-Tap Delay - Inverse Time

    VoltageDeviation

    VsdVs

    Initial Delay Inverse Time)

    Time

    The timer is reset after each operation to invoke init ial timer

    I i ti l Ti D l

  • 8/10/2019 AVR on Load Tap Changer

    17/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays17 17

    Initial Time DelaysTypical Setting Ranges

    Initial Time Delay Setting Ranges

    MVGC - 0 to 120s

    KVGC - 0 to 300s

    Inter-tap Delay Setting Ranges

    MVGC - 0 to 10s

    KVGC - 0 to 120s

    Initial Time Delays also ensure time grading betweenvoltage levels

  • 8/10/2019 AVR on Load Tap Changer

    18/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays18 18

    Grading Between Voltage Levels

    Grading Between Voltage Levels

  • 8/10/2019 AVR on Load Tap Changer

    19/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays19 19

    Grading Between Voltage LevelsCauses of Voltage Deviations

    Grid Supply

    Load

    Load

    A

    CB

    Line

    T3T2

    T1

    Load

    Voltage deviations occur for two reasonsChange in downstream load

    Change in upstream supply voltage

    Grading Between Voltage Levels

  • 8/10/2019 AVR on Load Tap Changer

    20/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays20 20

    Grading Between Voltage LevelsTime Grading

    Grid Supply

    Load

    Load

    A

    C

    BT3

    T2

    T1Load

    Discrimination to allow higher voltage to operate firstT1 time delay < T2 time delay < T3 time delay (initial)

    Otherwise hunting can occur between voltage levels

  • 8/10/2019 AVR on Load Tap Changer

    21/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays21 21

    Line Drop Compensation

    Line Drop Compensation

  • 8/10/2019 AVR on Load Tap Changer

    22/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays22 22

    Line Drop CompensationRegulating the Voltage at a Remote Point

    Tap Changer

    Time Delay

    VoltageDeadband

    Voltage Setting AVC Relay

    Supply

    Load

    VT

    CT

    +-

    Bus

    X R

    Feeder

    Voltage Drop

    Line Drop Compensation )(

    FEEDERFEEDER LOADS LOAD jX R I V V +=

    )( AVC AVC AVC S BUS jX R I V V +=

    Simulates voltage drop of the line

    Artificially boosts transformer voltage at times of high loading

    Line Drop Compensation

  • 8/10/2019 AVR on Load Tap Changer

    23/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays23 23

    Line Drop CompensationRelay Implementation

    Calculate the Voltage Drop at nominal load

    Vr Vxl

    RemoteVoltage

    VREM

    LoadIL

    BusVoltage

    VB

    Bus Voltage VBUS

    = VREM

    + Vr + Vxl

    Line Drop Compensation

  • 8/10/2019 AVR on Load Tap Changer

    24/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays24 24

    Line Drop CompensationPhasor Diagram

    IL

    VBUS

    -ILX

    -ILR

    VREM Voltage Setting

    The relay calculates andregulates the V REMmagnitude

    The measuredbus voltage

    Line Drop Compensation

  • 8/10/2019 AVR on Load Tap Changer

    25/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays25 25

    Line Drop CompensationTypical Setting Ranges

    Reactive and Resistive Compensation, Vr andVxl

    MVGC - 0 to 48V

    KVGC - 0 to 50V

  • 8/10/2019 AVR on Load Tap Changer

    26/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays26 26

    Transformers

    Parallel Operation

    Parallel Operation

  • 8/10/2019 AVR on Load Tap Changer

    27/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays27 27

    pTransformer Operating in Parallel

    Transformers in parallel can cause CirculatingCurrents

    Circulating Current affects LDC causing tapchanger runaway

    Circulating Current are damaging to Transformer

    Therefore special control techniques are required

    Paralleling using Master-Follower Control

    Paralleling using Negative Reactance Control

    Paralleling using Circulating Current Control

    Parallel Operation

  • 8/10/2019 AVR on Load Tap Changer

    28/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays28 28

    pMaster - Follower

    One controller designated the master

    All other controllers (followers) follow the master

    Requires that

    Identical transformers / tap changers

    Locality of equipment

    Security of communications is crit ical

    Circulating current should be monitored

    Parallel Operation

  • 8/10/2019 AVR on Load Tap Changer

    29/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays29 29

    pCirculating Currents due to Tap Disparity

    2IL

    T1

    T2

    Ic

    IL-Ic

    IL+Ic

    If T1 is on a highertap than T2

    Current seen by#1 is I L + IC

    Current seen by#2 is I L - IC

    #2

    #1

    Parallel Operation

  • 8/10/2019 AVR on Load Tap Changer

    30/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays30 30

    pCirculating Current Effect on LDC

    2IL

    T1

    T2

    Ic

    Vxl VrIL-Ic

    IL+Ic

    IC is measured in LDC circuit but

    is not present in the feeder

    #2

    #1

    Parallel Operation

  • 8/10/2019 AVR on Load Tap Changer

    31/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays31 31

    LDC on T1

    IL

    VBUS

    -ILX-ILR

    VREM

    ICIL + I C Volts High)

    VREG

    -IcR

    -IcX

    The regulated voltage V REGcontains a -V C component

    VREG will be regulated up to V REM ,therefore increasing the overvoltage even further

    Voltage Setting

    The regulatedvoltage

    The measuredbus voltage

  • 8/10/2019 AVR on Load Tap Changer

    32/39

    Parallel Operation

  • 8/10/2019 AVR on Load Tap Changer

    33/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays33 33

    Negative Reactance Control

    Reverse Reactance Control (non matched tap

    changers or different sources)Utilises the reactance compensation of the LineDrop Compensation circuit

    Reverses reactance and feeds back intocompensation circuit

    Lack of specific feeder reactance in LDC resultsin susceptibility to power factor

    Negative Reactance Control

  • 8/10/2019 AVR on Load Tap Changer

    34/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays34 34

    Compensation on T1

    IL

    VBUS

    VREM

    ICIL + I C Volts High)

    VREG

    Voltage Setting

    ILXt-ILR-ICRC

    Xt

    The measured

    bus voltage

    The regulatedvoltage

    VREM

    VREG

    -ILX

    -ILRIcR

    -IcX

    The reactance of LDC is reversed

    VREG will be regulated correctlyreducing the over voltage

    Negative Reactance Control

  • 8/10/2019 AVR on Load Tap Changer

    35/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays35 35

    Compensation on T2

    IL

    VBUS

    -ILX

    -ILR

    VREM

    IC

    VREG

    -ICR

    -ICX

    Voltage Setting

    ILXt

    -ILR-ICR

    ICXt

    The reactance of LDC is reversed

    VREG will be regulated correctlyincreasing the under voltageL - IC Volts Low)

    The measuredbus voltage

    The regulatedvoltage

    VREM

    VREG

  • 8/10/2019 AVR on Load Tap Changer

    36/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays36 36

    Supplementary Control Functions AVR Relaying

    Supplementary Control Functions

  • 8/10/2019 AVR on Load Tap Changer

    37/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays37 37

    Load Sheddingvoltage setting override ( 10%)

    Over Current / Under Voltage Supervision

    inhibit control during fault conditions

    Excessive Circulating Current

    protects against parallel control failure

    Under Current Inhibit

    stops operations when low forward or reverse power

    Reverse Current Operation Auto/Manual/Remote Operations

    Measurements

    Supplementary Control FunctionsT Ch S i i

  • 8/10/2019 AVR on Load Tap Changer

    38/39

    On/Under Load Tap Changing Transformers Voltage Regulating Control Relays38 38

    Tap Changer Supervision

    Tap Changer Monitoringtap changer confirmation response (time limited)

    voltage monitoring

    voltage change occurs

    in the correct direction

    of sufficient magnitude

    operations with no initiating signalTap Change Operations Counter

    alarms at settable threshold

    frequency alarmsexcessive operations per time period(day / month / maintenance period)

  • 8/10/2019 AVR on Load Tap Changer

    39/39