PRODUCT TECHNICAL GUIDE
ATyS Bypass Single Line & Double Linefrom 40 to 3200 A
2 Product technical guide
Ensures availability of the electricalpower supply under all circumstances
tabl
o_03
5_a
tabl
o_03
7_a
Reliable solution
Safe solution
Integrated solution
• Complete ATS redundancy. • Optimised MTTR. • Inspection, test & maintenance simplified.
• Intuitive and secured operation. • High electrical operation. • Original manufacturing (Made in France).
• Complete solutions or loose components. • New installation & retrofit. • Remote control capabilities.
3Product technical guide
General presentation
Applications Tertiary sector / Critical building / Building
• High-rise & public buildings (security equipments, alarm systems, smoke extraction systems, fire pumps, air compressors, sprinkler systems, lifts…) • Hospitals (surgery, intensive care, hospitalisation…). • It rooms (data centre, banks, insurances, web sites hosting…). • Shopping centers.
Infrastructure
• Airports (navigation, track signs…). • Commercial and military navy (dock connection, embedded supplies). • Highways / motorways (tunnels, tolls…). • Railways (rail signs) / subways • Telecom (self-sufficient power supply).
SOCOMEC, your best asset
European manufacturing group• Created in 1922.• A workforce of almost 3000.• Located on all five continents.
A culture of independence• Family shareholding.• Control of the decision-making process.• Respect of human values.
The spirit of innovation• Almost 10 % of turnover is invested
in R&D.
A flexible manufacturing structure• Competitive production sites.• Lean Management.• Lead times, quality and cost
guaranteed.
The vision of a specialist• Expertise in core technologies.• Product adaptations as per customer
requirements.
A focus on service• Advice, technical assistance
and call-out, training.• Teams located across the globe.
4 Product technical guide
Transfer Switch EquipmentsIntroduction
The Transfer Switch Equipment (TSE) is applied to any application requiring switching operations from one power circuit to another.The transfer concept is mainly applied for two sources which require transfers, one considered as a main / normal supply and the other one as a backup/emergency source.The expression “normal / emergency” is used to name this function.The ATyS switching range has been designed, tested and proven according to the international standard IEC 60947-6-1.
Hence, SOCOMEC ATyS guarantees a high quality product which meets all requirements of an Automatic Transfer Switch Equipment (ATSE).
Applications & ATSE solutions
• Automatic Transfer Switch Equipments (TSE) realise a changeover between main & emergency / backup sources in order to ensure Power supply quality & continuity for economic and / or (people / equipments) safety raisons. The most useful transfer application concerns installations requiring switching to another power supply in case of loss of a main’s network.
ATyS p M range from 40 to 160 A (4 poles)
atys
-mp_
001_
bATyS p range from 125 to 3200 A (3 & 4 poles)
atys
-p_0
01_b
Mains / Genset (Standard)
M
atys
_751
_a_1
_x_c
at
Mains / Mains (Standard)
M
atys
_752
_a_1
_x_c
at
• An ATSE can also be used to ensure power supply self-sufficiency in case of isolated site like telecom relay.
ATyS M range from 40 to 160 A (4 poles)
ATyS d M ATyS C40
+
atys
-md_
002_
b
atys
_599
_c
ATyS range from 125 to 3200 A (3 & 4 poles)
ATyS d ATyS C40
+
atys
_599
_c
atys
-d_0
01_a
Genset / Genset (on request)
M
atys
_753
_a_1
_x_c
atGeneral presentation
IEC 60947-6-1Edition 2.1 2013-12
®
5Product technical guide
General presentation
Bypass Switch EquipmentsThe ATyS Bypass function is a solution which allows on normal / emergency changeover installation to isolate the Automatic Transfer Switch Equipment (ATSE) during the maintenance periods, & keeps the supply available for the installation.So the ATSE, which is subject to high number of operations and risks of damages (lightning, high voltage fluctuation) due to the permanent connection to the mains, can be controlled or replaced without any threat for the operator and without affecting the continuity of the supply.
SOCOMEC ATyS Bypass are available in 2 versions:
Bypass Single Line
Bypass Single Line (BPSL) consists of two elements, an Automatic Transfer Switch & a one-way bypass isolation switch.
Bypass Double Line
Bypass Double Line (BPDL) consists of two elements, an Automatic Transfer Switch & a two-way bypass isolation switch.
Manual TransferSwitch
Load
Bre
ak S
witc
h
Automatic TransferSwitch
Q1
Q2
Load
I1
I2
I3 I4
Voltage Sensing
ATyS Bypass
Manual TransferSwitch
Q1
Q2
Q3
Load
Bre
ak S
witc
h
Automatic TransferSwitch
Load
I1
I2
I3 I4
Manual TransferSwitch
I5 I6
Voltage Sensing
ATyS Bypass
atys
_884
_c
atys
_883
_c
Normal position
The load is supplied by source 1 or source 2 through the ATSE.
Typical functioning
Manual TransferSwitch
Load
Bre
ak S
witc
h
Automatic TransferSwitch
Load
I1
I2
I3 I4
Manual TransferSwitch
I5 I6
Voltage Sensing
ATyS Bypass
atys
_885
_a_1
_gb_
cat
Bypass position
The ATSE is Bypassed, the load is supplied by source 1 or source 2 through the MTSE.
Manual TransferSwitch
Load
Bre
ak S
witc
h
Automatic TransferSwitch
No Blackout
I1
I2
I3 I4
Manual TransferSwitch
I5 I6
Voltage Sensing
ATyS Bypass
atys
_886
_b_1
_gb_
cat
Test position
The load is not supplied by the ATSE but through the MTSE, the Automatic transfer switch can be tested without any perturbation on the load.
Manual TransferSwitch
Load
Bre
ak S
witc
h
Automatic TransferSwitch
Load
I1
I2
I3 I4
Manual TransferSwitch
I5 I6
Voltage Sensing
ATyS Bypass
atys
_887
_a_1
_gb_
cat
6 Product technical guide
Technical presentation
Standard featuresIntroduction
SOCOMEC proposes a complete enclosed ATyS Bypass range from 40 to 3200 A (4 poles in standard & 3 poles on request).The ATyS Bypass system consists of two elements:
An Automatic Transfer Switch Equipment (ATSE) (with built-in microprocessor controller):
• 1 ATyS or 1 ATyS M depending on the rating.
A Manual bypass isolation switch:
• One-way / Single line: - 1 Load Break Switch (LBS): SIRCO (M) 8 poles- 1 Manual Transfer Switch (MTSE): SIRCOVER
• Two-way / Double Line: - 1 Load Break Switch (LBS): SIRCO 8 poles- 2 Manual Transfer Switch (MTSE): SIRCOVER.
SOCOMEC products are Made in France & the complete system is assembled in France.
All these features concern SOCOMEC LBS, MTSE & ATSE.
• Inherently double throw switch for low voltage applications. • Secured disconnection integrated for load isolation, thanks to a double switching technology per pole with fully visualized breaking.
• High number of operations according to IEC 60947-3/ 60947-6-1. • On load Making & Breaking capacity. • Constant pressure on the contacts not affected by voltage variations, vibrations or repulsive force during short-circuits.
L
F’
F’
F F
SOCOMEC sliding contacts Contactors & circuit breakers
• Integrated mechanical interlocking system. • Silver platted & self cleaning contacts > maintenance free, no inspection & replacement needed.
• High dynamic short circuit withstand (result after 10 short-circuits).
• Synchronised neutral closing The neutral contact is fitted on the same moving contact bar > Ensure neutral referencing & avoid surges. Like the most famous switches builder, it’s the SOCOMEC answer for neutral overlapping.
V2 V
1
Y
X1 X1X2X2
X3X3U
ø W
It’s an alternative solution of make before break and break before make for neutral needs.
• Neutral is fully rated in comparison with phases. • Open transition: In order to avoid inrush currents in case of motor load.
Switching
With: • A large range [40 A / 3200 A]. • A high voltage range. • A high frequency range [45 Hz / 65 Hz].
Power supply from: • P-N 160 VAC to 305 VAC (40 to 125 A). • P-N 166 VAC to 332 VAC (160 to 3200 A).
General electrical characteristics
SOCOMEC ATS/BPS offer a solution for all types of installations and loads.
cate
c_47
2_a
cate
c_47
3_a
atys
_822
_a
atys
_823
_a
atys
_802
_a
7Product technical guide
Technical presentation
Automatic Transfer Switch
Mechanical parts
• Integrated mechanical and electrical interlocking system.
atys
m_2
59_a
atys
_768
_a
• The electric mechanism is a single operator momentarily energized. • Making & breaking speeds are independent of the operating mode (manual & motorised). • Stable positions not affected by voltage fluctuations & vibrations. • Product not powered in stable positions. Operator is a momentarily energized mechanism > no consumption & extended operating life.
• Operating mode selector (AUT / MAN) with interlocking.
Open the front cover to activate manual mode
atys
m_0
92_a
atys
_836
_a_1
_cat
Handle housing not possible in Auto mode to secure manual operation. • Emergency manual operation facilities with a single handle.
atys
m_0
15_c
_1_c
at
• Built-in mechanical padlocking system in manual mode in 0 position (3 positions on request).
atys
m_0
16_c
_1_c
at
atys
_836
_a_1
_cat
Automatic & Manual modes are disabled and not possible in padlocked mode. • Easy maintenance.Motor & control relay can be replaced on load = no power loss!During maintenance operations, changeover is always possible manually.
atys
_836
_a
4 screws
90° 90°
I II
0AUT
8 Product technical guide
Technical presentation
Microprocessor controller part
Embedded controller for Mains / Mains & Mains / Genset applicationsThe controller is provided by a single built-in microprocessor completely integrated to the ATSE. The controller is self-supplied by the mains and backup sources.Two models according to the ratings:
ATyS p front face
User-Friendly interface
Facilities on the 2 versions: • Configuration (Password protection to control the access):- Installation parameters configuration.- Independent over/under voltage and over/under frequency
thresholds ±20% of nominal values & hysteresis.- Phase rotation and unbalance control.- Adjustable timers. • Visualisation:- Voltage measurements on the 2 sources (according to the network type).- Frequency measurements on the 2 sources.- Timers settings & countdowns.- Number of cycles & last events.- Remote reporting by digital outputs (dry contacts).
• Exploitation (Password protection to control the access):- Changeover cycle automatic management.- Tests on load & tests off load facilities.- Remote control by digital inputs.
• LED indicator light:- Power On.- Sources availability.- Changeover positions.- “MAN / AUT” modes.- Test & control operations.
All these facilities are also accessible with the serial link RS485 through a Slave JBUS/MODBUS protocol.
ATyS p M front face
atys
m_0
30_d
_1_x
_cat
Measurements
Measurements are true RMS type for the 2 sources.Voltage is accurate to 1% on the complete operating temperature range [-20°C > + 70°C].
The frequency is accurate to 0.1% on the complete operating temperature range [-20°C > + 70°C].These measurements are continuously monitored.
Thresholds & hysteresis
Functions Sources Phases controlled Default value Range
Over voltage (dropout / trip)
1 & 2 (N & E)
3 Ph3 Ph + N
2 Ph2 Ph + N1 Ph + N
(Following network type definition)
115% 102 to 130%
Over voltage hysteresis (pickup / reset) 110% 101 to 129%
Under voltage (dropout / trip) 85% 60 to 98%
Under voltage hysteresis (pickup / reset) 95% 60 to 99%
Over frequency (dropout / trip) 105% 101 to 130%
Over frequency hysteresis (pickup / reset) 103% 100.5 to 129%
Under frequency (dropout / trip) 95% 60 to 99%
Under frequency hysteresis (pickup / reset) 97% 61 to 99,5%
• Nominal Voltage can be set from 180 VAC to 480 VAC in 1 V increment.
• Nominal Frequency can be select between 50 Hz and 60 Hz. • Voltage thresholds & hysteresis can be set in 1% increment.
• Frequency threshold & hysteresis can be set in 0.5% increment. • The controller also realizes phase rotation sensing on the 2 sources according to the configuration in case of 3 phases network.
Automatic Transfer Switch (continued)
9Product technical guide
Technical presentation
Integrated connection RJ45 for remote control interface (D20)The remote control interface is integrated in the SOCOMEC ATS Bypass offer.
Serial communication port RS485 with Slave JBUS/MODUS protocolThis communication link allow configuration, visualisation & remote control up to 1200 meters.
Remote control (digital input)
ATyS p M:
• 3 configurable inputs (self powered) for the following functions: - Inhibition mode,- Test on load & test off load,- Manual retransfer to inhibit the automatic retransfer,- Changeover position control for the 3 positions,- Network priority,- Load shedding.- …
ATyS p:
• 6 configurable inputs (self powered) and up to 8 inputs with optional modules (2 per module) for the following functions:- Inhibition mode,- Test on load & test off load,- Manual retransfer to inhibit the automatic retransfer,- Changeover position control for the 3 positions,- Network priority,- Load shedding.- …
• Up to 4 inputs for optional modules (2 per module) for the following functions:- Manual retransfer to inhibit the automatic retransfer,
- Network priority,- External sources fault (2),- Override Source 2 availability.
Remote reporting (digital output) for BMS system:
ATyS p M:
Auxiliary contacts (NO/NC for the 3 positions) (5 A AC1 250 VAC). • 2 configurable outputs (0.5 A AC1 250A) for the following functions:- Sources availabilities,- Sources on load,- Load shedding order,- Product availability (Auto mode + no fault + power supply).- …
• 1 bi-stable output for Genset start order (0.5 A AC1 250 A).
ATyS p:
Auxiliary contacts (NO/NC for the 2 positions) (5 A AC1 250 VAC). • 1 fixed outputs (0.5 A AC1 250 A) for the following functions:- Watchdog relay.
• Up to 8 outputs for optional modules (2 per module) (0.5 A AC1 250 A) for the following functions:- Sources availabilities,- Sources on load,- Load shedding order,- Product availability (Auto mode + no fault + power supply).
Timers & Automatic cycle
Source failure
Automatic mode (AUT)
End “t” source 1 failure
Source availability
Generator stop(1)
Source availability
End “t” source 2 availability
End “t” stop to position 0End “t” source 1 availability
End “t” stop to position 0
End “t” cool down timer before generator
2
1
1
Switch to position 0
Switch to position II
Switch to position I
Switch to position 0
Generator start(1)
Source 1 : priority power sourceSource 2 : backup power source “t” : timer
Example (generator application):
(1) Only for mains/genset applications.
Timers Designations
ATyS p M ATyS p
Names Def. Values Ranges Names Def. values Ranges
T1 Source 1 failure timer 1FT 3s (0 to 60s) 1FT 3s (0 to 60s)
T2 Delay To Transfer on source 2 (only for genset) 2AT 5s (0 to 60s) 2AT 5s (0 to 3600s)
T3 0 position stway before transfer “failure” 0DT 3s (0 to 20s) 0DT 3s (0 to 20s)
T4 Source 1 return timer before retransfer 1RT 180s (0 to 3600s) 1RT 180s (0 to 3600s)
T5 0 position stay before transfer “return” 0DT 3s (0 to 20s) 0DT 3s (0 to 20s)
T6 Cool down timer before generator set shutdown 2CT 180s (0 to 600s) 2CT 180s (0 to 600s)
Load shedding timer LST 4s (0 to 60s) LST 4s (0 to 60s)
All time delays are adjustable in 1sec increment for timers based on seconds and in 0.1 min for timers based on minutes.
atys
_028
_h_1
_gb_
cat
Automatic Transfer Switch (continued)
10 Product technical guide
Technical presentation
Bypass Isolation Switch
The SOCOMEC ATyS Bypass solutions are Open Transition Automatic Transfer Equipment which allow to changeover & to bypass the load to either sources and permit complete isolation and test of the ATS.
ATyS Bypass Single Line ATyS Bypass Double Line
• Power connections removalAll the power connections on the ATS can be easily removed with standard tools.
• Easy replacement of ATS (from 250 to 3200 A)Allows to change the ATS product in full security, in a minimum time and allows an easiest product handling.
• Protective ScreenEven while the panel door is open, the screen protection will ensure a total protection against direct contacts. All parts under voltage are individually protected by protective screens.
• Bus bar identificationAllows clear identification of the different phases in order to avoid connection mistakes. A bus bar code colour ensures the coherence with the indicator light on the mimic diagram.
No critical position can be reached by the operator! Safe Utilisation
• ATS modeIn the automatic mode, the bypass products are out of power so that they will not carry fault currents.All the changeover functionalities are ensured by the ATS.
• Bypass modeThey are done manually with 2 handles for SL and 3 handles for DL without any key to interlock.- One handle (Q1) to choose between ATS mode & bypass mode.
This handle allow on bypass mode to isolate the ATS from load power conductors.
- One handle (Q2) to select the sources during bypass mode (only with DL version).
- One handle (Q3) to isolate the ATS from all sources and to realise some tests after maintenance.
• Three possible operating modes: - Normal (ATS),- Bypass (on mains or emergency),- Test.
General features for Single Line (SL) & Double Line (DL) Bypass:
Manual TransferSwitch
Load
Bre
ak S
witc
h
Automatic TransferSwitch
Q1
Q2
Load
I1
I2
I3 I4
Voltage Sensing
ATyS Bypass
Manual TransferSwitch
Load
Bre
ak S
witc
h
Automatic TransferSwitch
Load
I1
I2
I3 I4Q1
Q2
Q3
Manual TransferSwitch
I5 I6
Voltage Sensing
ATyS Bypass
atys
_899
_a_1
_gb_
cat
atys
_883
_c
atys
_766
_a
11Product technical guide
Technical presentation
Cables entries
• Steel enclosure (up to 400 A)In the standard solution with steel enclosure, the incoming cables from sources and the outgoing cables to the load arrive are connected to the bottom side of the enclosure.
• Steel cabinet (from 630 A)In the standard solution with steel cabinet, the incoming cables from sources are connected to the bottom side of the cabinet. The outgoing cables to the load can be connected to top or bottom sides. In option, a cabinet extension is available to allow incoming cables connection from the top of the cabinet.
Mimic diagram
Allows the customer to have a full vision of the ATyS Bypass status:- Availability of each source phase,- Normal and bypass positions,- Voltage & frequency measurements.
The mimic diagram consists in 16 LED indicating lights (16 mm industrial grade in option).
LOAD
Q3
Q2
ATS
S2 S1
P2 P1
Q1Normal Bypass
S2 S1
acce
s_27
5_b_
1_x_
cat
Bypass Isolation Switch (continued)
Manual TransferSwitch
Q1
Q2
Q3
Load
Bre
ak S
witc
h
Automatic TransferSwitch
Load
I1
I2
I3 I4
Manual TransferSwitch
I5 I6
Voltage Sensing
ATyS Bypass
atys
_884
_c
12 Product technical guide
Technical presentation
Components presentation & sizing (continued)
Switching equipments
Functions Qties 40 to 100 A 125 & 160 A 250 to 3200 A
ATSAutomatic Transfer Switch 1
ATyS p M ATyS p M ATyS p
LBSLoad Break Switch 1
SIRCO M 8 P SIRCO VM 8 P SIRCO 8 P
MTSManual Transfer Switch 1 / 2(1)
SIRCO M SIRCO VM1 SIRCOVER
HMIHuman Machine Interface 1
Mimic Diagram + D20 Mimic Diagram + D20 Mimic Diagram + D20
Enclosure Dimensions
Ratings (A) Dimensions H x W x D (mm) Type IP Cables entry In / Out
40 … 80 800 x 800 x 300 Steel Enclosure Std: IP41 B / B
100 … 125 1000 x 800 x 300 Steel Enclosure Std: IP41 B / B
160 1000 x 800 x 400 Steel Enclosure Std: IP41 B / B
250 … 400 1200 x 1000 x 550 Steel Enclosure Std: IP41 B / B
630 1600 x 1200 x 600 Steel Cabinet Std: IP41 B / B
800 … 1000 1800 x 1600 x 800 Steel Cabinet Std: IP41 B / B
1250 … 3200 2360 x 2000 x 1000 Steel Cabinet Std: IP41 B / B or T / T in option
References
Type5: Single line6: Double line
178 6 4 063 Rating004: 40 A006: 63 A008: 80 A010: 100 A012: 125 A016: 160 A025: 250 A040: 400 A
063: 630 A080: 800 A100: 1000 A125: 1250 A160: 1600 A200: 2000 A250: 2500 A320: 3200 A
Number of poles4: 4 poles
Product178: ATyS Bypass
ATY
S 8
88 A
GB
*for double line version
13Product technical guide
Technical presentation
Documentation & support provided
• Electrical drawings. • Mechanicals drawings. • ATS manual instruction & troubleshooting guide. • Certificate of compliance with the standards. • Tests report. • Product selection & definition according to the total load rated and environmental conditions.
Codes & Standards
The products meet the applicable European directive and they are marked:
SOCOMEC ATyS Bypass and their components are compliant withapplicable international directives IEC:
Low-voltage switchgear and controlgear assemblies:
• IEC 61439-1: General rules. • IEC 61439-2: Power switchgear and controlgear assemblies.
LOVAG /ASEFA Third-party-certified in accordance with IEC 61439:
Low-voltage switchgear and controlgear:
• IEC 60947-1: General rules. • IEC 60947-3: Switches, Disconnectors, switch-disconnectors and fuse-combination units
• IEC 60947-6-1: Multiple function equipment transfer switching equipment
Electromagnetic Compatibility (EMC):
• Emission general standard. • EN 55022: Conducted emission. • EN 55022: Radiated emission.
Immunity general standard:
Description Std (IEC) Requirement (crireria)
Conducted CISPR 11 Class B
Radiated CISPR 11 Class B
ESD contact 61000-4-2 4 kV (B)
ESD air 61000-4-2 8 kV (B)
Electromagnetic field 61000-4-3 10 V/m (A)
RF Conducted 61000-4-6 10 V (A)
Burst 61000-4-4 2 kV (A) power 1 kV (A) control
Surge differential 61000-4-5 1 kV (A)
Others international directives:
• NBN EN 60947-3 • BS EN 60947-3 • GB 14048-3 • NBN EN 60947-6-1 • BS EN 60947-6-1 • GB 14048-11 • VDE 0660-107
14 Product technical guide
Technical presentation
Optional & additional features (continued)
Power measurements
In option, SOCOMEC ATyS Bypass can be equiped with measurement devices to allow power management.
DIRIS A10 DIRIS A20 DIRIS A40 / A41 DIRIS A60Requirements
Feeder measurement & control • • • •
Energy breakdown & allocation • • • •
Load analysis & management • •
Event monitoring • •
Detection & storage of network perturbations •
Form factor 4 modules panel mounted 96x96 panel mounted 96x96 panel mounted 96x96
MeasurementCurrents, voltages, frequency, active, reactive and apparent power, power factor • • • •
Predictive power • •
Voltage/current unbalance; Tangent •
Temperature(s) • 1 … 4 option 1…4 option
Average currents, voltages and frequency • •
Average power • •
Energy managementEnergy meters (cl. 0.5s IEC 62053-22; cl. 2 IEC 62053-22) • • • •
Pulse meter 1* 2 … 6 option 2 … 6 option
Load curves • •
Quality analysis and event detectionTHD 3U, 3V, 3I/In level 51 level 51 level 63 level 63
Individual harmonics 3V, 3U, 3I/In (level 63) • •
Sag, swell and outages, overcurrent •
RMS 1/2 period curve backup •
Alarm output 1* 1* option 2 … 6 option 2 … 6 option
Measurement and event historyLoad curves in option •
Events & Alarms -/• •/•
Maximum average power kW kW • •
Maximum average currents • • • •* 1 configurable
Remote ATyS Bypass management
In standard, a serial communication port RS485 with slave JBUS / MODUS protocol is provided with a free monitoring software (ATyS Vision software can be downloaded on the SOCOMEC WEB site).In order to extend communication facilities, an optional module can be integrated in the ATyS Bypass to allow communication through Ethernet for the following functions: • Alarm management. • Data logging. • Remote control. • Visualisation via embedded website. • …
Alarm management
Data logging
Remotecontrol
Alarm atys
_761
_a_1
_gb_
cat
Optional & additional features (continued)
15Product technical guide
Technical presentation
Environment
The complete product meets the following environmental requirements :
IP-rating:
In standard, the system is IP41, Other IP (on request).
Operation:
• Temperature:[-20°C to + 70°C] : Above +40°C a de-rating has to be respected for the power circuit.
• Hygrometry:- 80% humidity without condensation at 55°C.- 95% humidity with condensation at 40°C.
• Altitude:- Maximum altitude without de-rating = 2000 m.
Storage:
• Temperature: [-20°C to + 70°C]. • Period: Maximum 1 year (without supply of the ATS).
Optional & additional features
Extension cabinet
From 1200 to 3200 A, in standard, the cables entry are at the bottom for the sources and at the bottom or on the top for the load. In order to allow sources cables entry on the top, we can provide an extension cabinet.
kdry
s_50
4_a_
2_ca
t
Tinned bus bar
In standard, the enclosure in realise with virgin copper. On request, it is possible to provide a tinned Busbar for aggressive environment.
Lightning protection
In order to ensure the ATyS Bypass protection and availability, SOCOMEC proposes in option some lightning protection devices.
kdry
s_50
4_a_
2_ca
t
T12
1411
121114
DP
L1L2L3N
L L L N
D40 D40 D40 D40
LV network Installation
T : TelesignallingDP : Protection device(fuses)
kdry
s_50
4_a_
2_ca
t
www.socomec.com
hEAd offICE
SOCOMEC GROUPSAS SOCOMEC capital 10 686 000 € R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex - FRANCE Tel. +33 3 88 57 41 41 Fax +33 3 88 74 08 00 [email protected]
Socomec worldwide
BELGIUMCritical Power / Power Control & Safety / Energy EfficiencyTel. +32 2 340 02 30 Fax +32 2 346 28 99 [email protected]
FRANCECritical Power / Power Control & Safety / Energy EfficiencyTel. +33 1 45 14 63 00 Fax +33 1 48 67 31 12 [email protected]
GERMANyCritical PowerTel. +49 621 71 68 40 Fax +49 621 71 68 444 [email protected] Control & Safety / Energy EfficiencyTel. +49 7243 65292 0 Fax +49 7243 65292 13 [email protected]
ITALyCritical Power Tel.+39 02 98 242 942 Fax +39 02 98 240 723 [email protected] Control & Safety / Energy EfficiencyTel.+39 02 98 49 821 Fax +39 02 98 24 33 10 [email protected]
NETHERLANDSCritical Power / Power Control & Safety / Energy EfficiencyTel. +31 30 760 0900 Fax +31 30 637 2166 [email protected]
POLANDCritical PowerTel. +48 22 825 73 60 Fax. +48 22 825 73 70 [email protected] Control & Safety / Energy EfficiencyTel. +48 91 442 64 11 Fax +48 91 442 64 19 [email protected]
PORTUGALCritical Power / Power Control & Safety / Energy EfficiencyTel.+351 261 812 599 Fax +351 261 812 570 [email protected]
ROMANIACritical Power / Power Control & Safety / Energy EfficiencyTel. +40 21 319 36 88 Fax +40 21 319 36 89 [email protected]
SERBIACritical Power / Power Control & Safety / Energy EfficiencyTel. +381 11 40 43 246 Fax +381 11 40 43 [email protected]
SLOvENIACritical Power / Power Control & Safety / Energy EfficiencyTel. +386 1 5807 860 Fax +386 1 561 11 73 [email protected]
SPAINCritical Power / Power Control & Safety / Energy EfficiencyTel. +34 93 540 75 75 Fax +34 93 540 75 76 [email protected]
SwITZERLANDCritical PowerTel. +41 44 745 40 80 Fax +41 44 745 40 85 [email protected]
TURKEyCritical Power / Power Control & Safety / Energy EfficiencyTel. +90 216 540 71 20-21-22 Fax +90 216 540 71 27 [email protected]
UNITED KINGDOMCritical PowerTel. +44 1285 863 300 Fax +44 1285 862 304 [email protected] Control & Safety / Energy EfficiencyTel. +44 1462 440 033 Fax +44 1462 431 143 [email protected]
Non
con
trac
tual
doc
umen
t. ©
201
6, S
ocom
ec S
AS
. All
right
s re
serv
ed. -
doc
umen
t prin
ted
on p
aper
from
sus
tain
ably
man
aged
fore
sts.
YoUR dISTRIBUToR / PARTNER
IN ASIA PACIfIC
AUSTRALIACritical Power / Power Control & SafetyTel. +61 2 9325 3900 Fax +61 2 9888 9544 [email protected]
CHINACritical Power / Power Control & Safety / Energy EfficiencyTel. +86 21 52 98 95 55 Fax +86 21 62 28 34 68 [email protected]
INDIACritical Power / Power Control & Safety / Energy EfficiencyTel. +91 44 39215400 Fax +91 44 39215450 & 51 [email protected]
SINGAPORE Critical Power / Power Control & Safety / Energy EfficiencyTel.+65 6506 7600 Fax +65 64 58 7377 [email protected]
THAILANDCritical PowerTel. +66 2 941 1644 7 Fax +66 2 941 1650 [email protected]
IN MIddlE EAST
UNITED ARAB EMIRATESCritical Power / Power Control & Safety / Energy EfficiencyTel. +971 4 29 98 441 Fax +971 4 29 98 449 [email protected]
IN AMERICA
USA, CANADA & MEXICOPower Control & Safety / Energy EfficiencyTel. +1 617 245 0447 Fax +1 617 245 0437 [email protected]
oThER CoUNTRIES
NORTH AFRICAAlgeria / Morocco / [email protected]
AFRICAOther [email protected]
SOUTH EUROPECyprus / Greece / Israel / [email protected]
SOUTH AMERICATel. +34 93 540 75 75 [email protected]
MORE DETAILSwww.socomec.com/worldwide
IN EURoPE
Réf
. DO
C 1
52 0
3 3
- 11
/16