Attachment D
Area Walk-by Checklists (AWCs)
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 1 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-001
Location: Bldg. RAB Floor El. -35 Room, Area1 Safeguards B Room
SWEL Components: SWEL1-012, 036
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• Anchor bolt on SISR-883 missing (1 of 4). See LB-01 in Attachment F.
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• All anchorage is free of significantly degraded conditions.
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 2 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-001
Location: Bldg. RAB Floor El. -35 Room, Area Safeguards B Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 3 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-001
Location: Bldg. RAB Floor El. -35 Room, Area Safeguards B Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Dinesh Patel Date: 10-02-2012
Natalie George 10-02-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 4 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-001
Location: Bldg. RAB Floor El. -35 Room, Area Safeguards B Room
SWEL Components: SWEL1-012, 036
Photographs
Note: Anchor bolt on SISR-883 missing (1 of 4)
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 5 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-002
Location: Bldg. RAB Floor El. -35 Room, Area1 Safeguards Room A
SWEL Components: SWEL1-013, 051
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 6 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-002
Location: Bldg. RAB Floor El. -35 Room, Area Safeguards Room A
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
• Tubes lying around due to ongoing work; no seismic concern
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 7 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-002
Location: Bldg. RAB Floor El. -35 Room, Area Safeguards Room A
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Mild surface corrosion on base plate located by exit, no seismic concern; CR-WF3-2012-05285 and WR 287666 initiated to address corrosion
Evaluated by: Dinesh Patel Date: 10/3/12
Brian Pace 10/3/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 8 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-002
Location: Bldg. RAB Floor El. -35 Room, Area Safeguards Room A
SWEL Components: SWEL1-013, 051
Photographs
Note: Mild surface corrosion on base plate located by exit
Note:
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 9 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-003
Location: Bldg. RAB Floor El. -35 Room, Area1 Room B17
SWEL Components: SWEL1-023, 030
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 10 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-003
Location: Bldg. RAB Floor El. -35 Room, Area Room B17
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 11 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-003
Location: Bldg. RAB Floor El. -35 Room, Area Room B17
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Bolt missing (1 of 6) near RAB sump pump SP EMTR213A AK, no seismic concern; WR 288319 initiated to address missing bolt
• One eye lift missing from cover near RAB sump pump SP EMTR213A AK; no seismic concern
Evaluated by: Natalie George Date: 10/8/12
Chu-Chieh Lin 10/8/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 12 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-003
Location: Bldg. RAB Floor El. -35 Room, Area Room B17
SWEL Components: SWEL1-023, 030
Photographs
Note: Bolt missing (1 of 6) near RAB sump pump SP EMTR213A AK
Note: One eye lift missing from cover near RAB sump pump SP EMTR213A AK
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 13 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-003
Location: Bldg. RAB Floor El. -35 Room, Area Room B17
SWEL Components: SWEL1-023, 030
Note: Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 14 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-004
Location: Bldg. RAB Floor El. -35 Room, Area1 Room B20
SWEL Components: SWEL1-056, 066
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 15 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-004
Location: Bldg. RAB Floor El. -35 Room, Area Room B20
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 16 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-004
Location: Bldg. RAB Floor El. -35 Room, Area Room B20
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Ceiling lights swing; no seismic concern as lights are well anchored and will not interact with other equipment
Evaluated by: Dinesh Patel Date: 10/2/12
Natalie George 10/2/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 17 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-004
Location: Bldg. RAB Floor El. -35 Room, Area Room B20
SWEL Components: SWEL1-056, 066
Photographs
Note: Area
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 18 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-005
Location: Bldg. RAB Floor El. -35 Room, Area1 Boric Acid Makeup Tank A Room
SWEL Components: SWEL1-016, 040, 089
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 19 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-005
Location: Bldg. RAB Floor El. -35 Room, Area Boric Acid Makeup Tank A Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 20 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-005
Location: Bldg. RAB Floor El. -35 Room, Area Boric Acid Makeup Tank A Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Housekeeping issues include loose rope from above and from a ladder; no seismic concern • Boric acid deposits on yoke bolt (bottom) of valve 131A, no seismic concern; CR-WF3-2011-
00024 and WR 224286 previously initiated for this condition • Active oil leak under Boric Acid Makeup Pump; towel dated 8-28-2012 to track amount of
leakage; no seismic concern • Bolts and steel corroded on supports on line connected to valve 113A, no seismic concern;
CR-WF3-2012-05296 and WR 287685 and 287687 initiated to address corrosion • Missing bolt (1 of 10) on B3424-NA, no seismic concern; CR-WF3-2012-05296 and WR
287689 initiated to address missing bolt
Evaluated by: Dinesh Patel Date: 10/3/12
Natalie George 10/3/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 21 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-005
Location: Bldg. RAB Floor El. -35 Room, Area Boric Acid Makeup Tank A Room
SWEL Components: SWEL1-016, 040, 089
Photographs
Note: Housekeeping issues include loose rope from above and from a ladder; trip hazard
Note: Boric acid deposits on yoke bolt (bottom) of valve 131A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 22 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-005
Location: Bldg. RAB Floor El. -35 Room, Area Boric Acid Makeup Tank A Room
SWEL Components: SWEL1-016, 040, 089
Note: Active oil leak under Boric Acid Makeup Pump; towel dated 8-28-2012 to track amount of leakage
Note: Bolts and steel corroded on supports on line connected to valve 113A
Note: Missing bolt (1 of 10) on B3424-NA
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 23 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-006
Location: Bldg. RAB Floor El. -35 Room, Area1 Shutdown Cooling Heat Exchanger A Room
SWEL Components: SWEL1-092
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 24 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-006
Location: Bldg. RAB Floor El. -35 Room, Area Shutdown Cooling Heat Exchanger A Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 25 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-006
Location: Bldg. RAB Floor El. -35 Room, Area Shutdown Cooling Heat Exchanger A Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• 2 hoses hanging from above to floor drain; no seismic concern
Evaluated by: Dinesh Patel Date: 10/3/12
Natalie George 10/3/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 26 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-006
Location: Bldg. RAB Floor El. -35 Room, Area Shutdown Cooling Heat Exchanger A Room
SWEL Components: SWEL1-092
Photographs
Note: 2 hoses hanging from above to floor drain
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 27 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-007
Location: Bldg. RAB Floor El. -35 Room, Area1 Emergency Feedwater Pump (Turbine Driven) Area
SWEL Components: SWEL1-010
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 28 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-007
Location: Bldg. RAB Floor El. -35 Room, Area Emergency Feedwater Pump (Turbine Driven) Area
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
• One contamination protection disposal bin not secured to others. See LB-02 in Attachment F.
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 29 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-007
Location: Bldg. RAB Floor El. -35 Room, Area Emergency Feedwater Pump (Turbine Driven) Area
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Dinesh Patel Date: 10/2/12
Natalie George 10/2/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 30 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-007
Location: Bldg. RAB Floor El. -35 Room, Area Emergency Feedwater Pump (Turbine Driven) Area
SWEL Components: SWEL1- 010
Photographs
Note: Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Note: Bin not secured to others
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 31 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-008
Location: Bldg. CTB Floor El. -35 Room, Area1 Room 59A, Transformer Room
SWEL Components: SWEL1-008
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 32 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-008
Location: Bldg. CTB Floor El. -35 Room, Area Room 59A, Transformer Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 33 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-008
Location: Bldg. CTB Floor El. -35 Room, Area Room 59A, Transformer Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Mild corrosion on cooling tower fan housing, no seismic concern; CR-WF3-2012-04955 and WR 286025 initiated to address corrosion
• Mild corrosion on supports and structural steel, no seismic concern; CR-WF3-2012-04955 and WR 286027 initiated to address corrosion
• Spalled concrete above Fan 2-SB; no seismic concern • Exposed insulation on structural member near Fan 2-SB; no seismic concern
Evaluated by: Brian Pace Date: 10-15-2012
Dinesh Patel 10-15-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 34 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-008
Location: Bldg. CTB Floor El. -35 Room, Area Room 59A, Transformer Room
SWEL Components: SWEL1- 008
Photographs
Note: Mild corrosion of structural steel. Note: Mild corrosion on cooling tower fan
housing.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 35 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-008
Location: Bldg. CTB Floor El. -35 Room, Area Room 59A, Transformer Room
SWEL Components: SWEL1-008
Note: Spalled concrete; no seismic concern. Note: Exposed insulation. No seismic
concern.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 36 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-009
Location: Bldg. CTB Floor El. -35 Room, Area1 B59A, Wet Cooling Tower B Area
SWEL Components: SWEL1-024
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• Anchor bolt missing on pipe support. See LB-03 in Attachment F.
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 37 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-009
Location: Bldg. CTB Floor El. -35 Room, Area B59A, Wet Cooling Tower B Area
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 38 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-009
Location: Bldg. CTB Floor El. -35 Room, Area B59A, Wet Cooling Tower B Area
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Conduit supports are corroded, no seismic concern; CR-WF3-2012-04960 and WR 286054 initiated to address corrosion
• Safety light cover and bulb broken, no seismic concern; CR-WF3-2012-04960 initiated to address light cover and bulb
• Diaphragm of valve CMUMVAAA407B is severely corroded; CR-WF3-2012-04960 and WR 104226 initiated to address corrosion
Evaluated by: Dinesh Patel Date: 10/1/12
Brian Pace 10/1/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 39 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-009
Location: Bldg. CTB Floor El. -35 Room, Area B59A, Wet Cooling Tower B Area
SWEL Components: SWEL1-024
Photographs
Note: Corrosion on conduit supports Note: Missing one bolt from the plate, moderate corrosion on the box
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 40 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-009
Location: Bldg. CTB Floor El. -35 Room, Area B59A, Wet Cooling Tower B Area
SWEL Components: SWEL1-024
Note: Safety light cover and bulb broken Note: Valve diaphragm is severely corroded
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 41 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-010
Location: Bldg. CTA Floor El. -35 Room, Area1 WET COOLING TOWER A AREA
SWEL Components: SWEL1-060
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• All anchorage is free of potentially adverse seismic conditions.
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• No corrosion found on equipment anchorage.
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 42 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-010
Location: Bldg. CTA Floor El. -35 Room, Area WET COOLING TOWER A AREA
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 43 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-010
Location: Bldg. CTA Floor El. -35 Room, Area WET COOLING TOWER A AREA
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Bolts on grounding cable supports on the wall under fan housing shows moderate to severe corrosion; no seismic concern; WR-289630 initiated for this condition
Evaluated by: Brian Pace Date: 10/5/12
Dinesh Patel 10/5/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 44 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-010
Location: Bldg. CTA Floor El. -35 Room, Area WET COOLING TOWER A AREA
SWEL Components: SWEL1-060
Photographs
Note: Bolts on grounding cable supports on the wall under fan housing shows moderate to severe corrosion
Note:
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 45 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-011
Location: Bldg. CTB Floor El. -35 Room, Area1 B60A, WET COOLING TOWER B AREA
SWEL Components: SWEL1-020
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
• Severe corrosion of tube steel supporting conduits • Conduit 30819D-SB corrosion • Corroded struts supporting large bore pipes (below and above) • Corroded angle steel member supporting overhead stairs
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 46 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-011
Location: Bldg. CTB Floor El. -35 Room, Area B60A, WET COOLING TOWER B AREA
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Minor corrosion of steel plate, no seismic concern
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 47 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-011
Location: Bldg. CTB Floor El. -35 Room, Area B60A, WET COOLING TOWER B AREA
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• CR-WF3-2012-05729 initiated to address corrosion conditions documented in this AWC.
Evaluated by: Dinesh Patel Date: 10-01-2012
Chu-Chieh Lin 10-01-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 48 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-011
Location: Bldg. CTB Floor El. -35 Room, Area B60A, WET COOLING TOWER B AREA
SWEL Components: SWEL1-020
Photographs
Note: Corrosion on the pipe Note: Corrosion on the pin
Note: Severe corrosion on the base plate and I beam
Note: Mild corrosion on the plate
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 49 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-011
Location: Bldg. CTB Floor El. -35 Room, Area B60A, WET COOLING TOWER B AREA
SWEL Components: SWEL1-020
Note: Corrosion on the support stud Note: Severe Corrosion on the support of the
walkway
Note: Severe corrosion on the horizontal connector
Note: Conduit 30819D-SB corrosion
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 50 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-013
Location: Bldg. CTA Floor El. -35 Room, Area1 WET COOLING TOWER A AREA
SWEL Components: SWEL1-015
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• Bolts on nearby pipe support are mildly corroded (near SE wall); no seismic concern
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
• Condulet underneath junction box B3CCF284A-SA is mildly corroded; no seismic concern
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 51 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-013
Location: Bldg. CTA Floor El. -35 Room, Area WET COOLING TOWER A AREA
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Steel member overhead has mild surface corrosion on both ends; no seismic concern
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 52 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-013
Location: Bldg. CTA Floor El. -35 Room, Area WET COOLING TOWER A AREA
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Bolts on the blind flange and flange on south east wall has moderate corrosion, no seismic concern; CR-WF3-2012-05301 and WR 287691 initiated to address corrosion
• Electrical junction box B30613-NAB cover has three bolts missing (3 of 8), no seismic concern; CR-WF3-2012-05301 and WR 287695 initiated to address missing bolts
Evaluated by: Brian Pace Date: 10/5/12
Dinesh Patel 10/5/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 53 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-013
Location: Bldg. CTA Floor El. -35 Room, Area WET COOLING TOWER A AREA
SWEL Components: SWEL1-015
Photographs
Note: Bolts on nearby pipe support are mildly corroded
Note: Condulet underneath junction box B3CCF284A-SA is mildly corroded
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 54 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-013
Location: Bldg. CTA Floor El. -35 Room, Area WET COOLING TOWER A AREA
SWEL Components: SWEL1-015
Note: Steel member overhead has mild corrosion on both ends
Note: Bolts on the blind flange and flange on south east wall has mild corrosion
Note: Electrical junction box B30618-NAB cover has three bolts missing (3 of 8)
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 55 of 210
Sheet 1 of 6 Status: Y N U
Area Walk-By Checklist (AWC) AWC-014
Location: Bldg. RAB Floor El. -35 Room, Area1 B59A, MCC AREA
SWEL Components: SWEL1-003
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• Missing bolt on support near valve SPMVAAA328 • Bolts missing on pump base plate
o See LB-04 in Attachment F.
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• SPMVAAA327 severely corroded • Severe corrosion on base plate • Severe corrosion on pipe support
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
• Conduit housing near valve SP MVAAA330 severely corroded
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 56 of 210
Sheet 2 of 6 Status: Y N U
Area Walk-By Checklist (AWC) AWC- 014
Location: Bldg. RAB Floor El. -35 Room, Area B59A, MCC AREA
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 57 of 210
Sheet 3 of 6 Status: Y N U
Area Walk-By Checklist (AWC) AWC- 014
Location: Bldg. RAB Floor El. -35 Room, Area B59A, MCC AREA
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
• Moderate corrosion on valve SP MVAAA326 B
Y N U
Comments (Additional pages may be added as necessary)
• Mild corrosion on fan housing, no seismic concern • Mild corrosion on grate, pump base plate, base plate, etc., no seismic concern • Mild corrosion on supports throughout dry cooling tower area, no seismic concern • Insulation near valve SP MVAAA330 cracked; not a seismic concern • Moderate corrosion tornado/missile shielding structural steel • CR-WF3-2012-04956 was initiated to address all corrosion issues as well as the missing bolt
on the support near valve SPMVAAA328. • CR-WF3-2011-07679 and WR 255628 already addressed the moderate corrosion on valve
SP MVAAA326 B.
Evaluated by: Dinesh Patel Date: 10/01/2012
Chu-Chieh Lin 10/01/2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 58 of 210
Sheet 4 of 6 Status: Y N U
Area Walk-By Checklist (AWC) AWC- 014
Location: Bldg. RAB Floor El. -35 Room, Area B59A, MCC AREA
SWEL Components: SWEL1- 003
Photographs
Note: Bolt missing on the supports near valve SPMVAAA328
Note: SPMVAAA327 severely corroded
Note: Moderate corrosion on valve SP MVAAA326 B
Note: Mild corrosion on grate, pump base plate, base plate, etc
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 59 of 210
Sheet 5 of 6 Status: Y N U
Area Walk-By Checklist (AWC) AWC- 014
Location: Bldg. RAB Floor El. -35 Room, Area B59A, MCC AREA
SWEL Components: SWEL1- 003
Note: Severe corrosion on base plate Note: Bolts missing on pump base plate
Note: Severe corrosion on pipe support Note: Moderate corrosion tornado/missile
shielding structural steel
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 60 of 210
Sheet 6 of 6 Status: Y N U
Area Walk-By Checklist (AWC) AWC- 014
Location: Bldg. RAB Floor El. -35 Room, Area B59A, MCC AREA
SWEL Components: SWEL1- 003
Note: Conduit housing near valve SP MVAAA330 severely corroded
Note: Insulation near valve SP MVAAA330 cracked
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 61 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-015
Location: Bldg. RAB Floor El. +7 Room, Area1 HVAC EQUIPMENT ROOM
SWEL Components: SWEL1-039
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 62 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-015
Location: Bldg. RAB Floor El. +7 Room, Area HVAC EQUIPMENT ROOM
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages, but falling bulbs would have no impact on equipment. No seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
• Housekeeping issues include clothes hanger on top of unit, coins and paper on the ground, and white caution tape on top of conduit; no seismic concern
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 63 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-015
Location: Bldg. RAB Floor El. +7 Room, Area HVAC EQUIPMENT ROOM
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• CHW coil isolation valves CHWMVAAA231 and CHWMVAAA883 show leakage on top; no seismic concern
• SCH inlet isolation valves SCHMVAAA528 and SCHMVAAA553 show mild to moderate surface corrosion, no seismic concern; WR 287827 initiated to address corrosion
Evaluated by: Dinesh Patel Date: 10/2/12
Brian Pace 10/2/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 64 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-015
Location: Bldg. RAB Floor El. +7 Room, Area HVAC EQUIPMENT ROOM
SWEL Components: SWEL1-039
Photographs
Note: SCH inlet isolation valve SCHMVAAA553 shows mild to moderate surface corrosion
Note: SCH inlet isolation valve SCHMVAAA528 shows mild to moderate surface corrosion
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 65 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-015
Location: Bldg. RAB Floor El. +7 Room, Area HVAC EQUIPMENT ROOM
SWEL Components: SWEL1-039
Note: Valve CHWMVAAA883 is leaking and shows signs of mild corrosion
Note: Valve CHWMVAAA231 is leaking and shows signs of mild corrosion
Note: Caution tape left behind piping Note:
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 66 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-016
Location: Bldg. RAB Floor El. +21 Room, Area1 Switchgear A Room
SWEL Components: SWEL1-006, 071, 082, 087
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 67 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-016
Location: Bldg. RAB Floor El. +21 Room, Area Switchgear A Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 68 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-016
Location: Bldg. RAB Floor El. +21 Room, Area Switchgear A Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
• Conduit is rigidly supported to equipment. This is acceptable per drawing B288, S19-1.
Y N U
Comments (Additional pages may be added as necessary)
• Phone cord is a trip hazard; no seismic concern • Bent and missing weld on studs; no seismic concern • Missing clip on dummy breaker storage, bent door; no seismic concern • Base plate on support has eight bolt holes but only four bolts. However, this is acceptable
since all other similar supports have only four bolts; no seismic concern
Evaluated by: Natalie George Date: 10/4/12
Chu-Chieh Lin 10/4/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 69 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-016
Location: Bldg. RAB Floor El. +21 Room, Area Switchgear A Room
SWEL Components: SWEL1-006, 071, 082, 087
Photographs
Note: Phone cord is a trip hazard
Note: Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Note: Note:
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 70 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-016
Location: Bldg. RAB Floor El. +21 Room, Area Switchgear A Room
SWEL Components: SWEL1-006, 071, 082, 087
Note: Bent door on dummy breaker storage Note: Missing clip on dummy breaker storage
Note: Base plate on support has eight bolt holes but only four bolts
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 71 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-017
Location: Bldg. RAB Floor El. +21 Room, Area1 Battery Room B
SWEL Components: SWEL1-070
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 72 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-017
Location: Bldg. RAB Floor El. +21 Room, Area Battery Room B
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 73 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-017
Location: Bldg. RAB Floor El. +21 Room, Area Battery Room B
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Brian Pace Date: 10/2/12
Dinesh Patel 10/2/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 74 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-017
Location: Bldg. RAB Floor El. +21 Room, Area Battery Room B
SWEL Components: SWEL1-070
Photographs
Note: Battery racks and area Note:
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 75 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-018
Location: Bldg. RAB Floor El. +21 Room, Area1 Switchgear Room B
SWEL Components: SWEL1-002, 007, 068, 069, 097
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• Anchorage is in good condition of equipment in the area.
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• No corrosion found on any anchorage in the area.
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
• Conduit rigidly attached to equipment is acceptable per drawing no. B288 sh. 19-1
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 76 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-018
Location: Bldg. RAB Floor El. +21 Room, Area Switchgear Room B
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Lighting is in walkways, posing no seismic concern. • A temporary housing has been installed in the Switchgear B
Room. It has the potential to impact panels near it. The walls are bolted together, but there are no anchors bolting the enclosure to the floor. There is only a 7” clearance from LCP-62 and one side of the enclosure.
o This was resolved using CR-12-5172 and EC40448. See photos. Enclosure was braced at the top and bottom to structural steel members to ensure rigidity of the enclosure.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 77 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-018
Location: Bldg. RAB Floor El. +21 Room, Area Switchgear Room B
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
•
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Brian Pace Date: 10-16-2012
Chu-Chieh Lin 10-16-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 78 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-018
Location: Bldg. RAB Floor El. +21 Room, Area Switchgear Room B
SWEL Components: SWEL1-002, 007, 068, 069, 097
Photographs
Note: Temporary enclosure. Note: Example of temporary enclosure
possibly having an impact on cabinet LCP-62.
Note: Example of resolution to seismic concern.
Note: Example of resolution to seismic concern.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 79 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-020
Location: Bldg. RAB Floor El. +21 Room, Area1 Component Cooling Pump B Room
SWEL Components: SWEL1-009
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• Anchorage of nearby equipment is adequate.
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• No corrosion found on any equipment anchorage.
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 80 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-020
Location: Bldg. RAB Floor El. +21 Room, Area Component Cooling Pump B Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 81 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-020
Location: Bldg. RAB Floor El. +21 Room, Area Component Cooling Pump B Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Minor surface corrosion on valve CHWMVAAA863, no seismic concern; WR 288420 initiated to address issue
Evaluated by: Brian Pace Date: 10-12-2012
Dinesh Patel 10-12-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 82 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-020
Location: Bldg. RAB Floor El. +21 Room, Area Component Cooling Pump B Room
SWEL Components: SWEL1-009
Photographs
Note: Minor surface corrosion on valve CHWMVAAA863.
Note: Additional equipment in area.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 83 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-020
Location: Bldg. RAB Floor El. +21 Room, Area Component Cooling Pump B Room
SWEL Components: SWEL1-009
Note: Properly mounted equipment in area. Note:
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 84 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-021
Location: Bldg. RAB Floor El. +21 Room, Area1 Hallway near CCW Pump AB Room
SWEL Components: SWEL1-094
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 85 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-021
Location: Bldg. RAB Floor El. +21 Room, Area Hallway near CCW Pump AB Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages. Lights are in walkway and falling bulbs would not impact equipment, no seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 86 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-021
Location: Bldg. RAB Floor El. +21 Room, Area Hallway near CCW Pump AB Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Brian Pace Date: 10/4/12
Chu-Chieh Lin 10/4/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 87 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-021
Location: Bldg. RAB Floor El. +21 Room, Area Hallway near CCW Pump AB Room
SWEL Components: SWEL1-094
Photographs
Note: Area around Nitrogen Accumulator #3 Note:
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 88 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-022
Location: Bldg. RAB Floor El. +21 Room, Area1 CCW Pump A Room
SWEL Components: SWEL1-065, SWEL2-010, 011
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 89 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-022
Location: Bldg. RAB Floor El. +21 Room, Area CCW Pump A Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 90 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-022
Location: Bldg. RAB Floor El. +21 Room, Area CCW Pump A Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• CHWMVAAA561 and CHWMVAAA563 are leaking; no seismic concern • Leakage and corrosion around pump, no seismic concern; WR 239478, CR-WF3-2011-04207,
WR 218753, and CR-WF3-2010-06818 in-progress to address issue • Broken insulation near valve CHWMVAAA559; no seismic concern
Evaluated by: Dinesh Patel Date: 10/4/12
Natalie George 10/4/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 91 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-022
Location: Bldg. RAB Floor El. +21 Room, Area CCW Pump A Room
SWEL Components: SWEL1-065, SWEL2-011, 012
Photographs
Note: Valve CHWMVAAA561 is leaking
Note: Valve CHWMVAAA563 is leaking
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 92 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-022
Location: Bldg. RAB Floor El. +21 Room, Area CCW Pump A Room
SWEL Components: SWEL1-065, SWEL2-011, 012
Note: Broken insulation near valve CHWMVAAA559
Note: Leakage and corrosion around CCW Pump
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 93 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-023
Location: Bldg. RAB Floor El. +21 Room, Area1 CCW HX A Room
SWEL Components: SWEL1-090
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 94 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-023
Location: Bldg. RAB Floor El. +21 Room, Area CCW HX A Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
• Harnesses lying on ground near scaffolding; no seismic concern
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 95 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-023
Location: Bldg. RAB Floor El. +21 Room, Area CCW HX A Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Valves CHWMVAAA554 and CHWMVAAA556 are leaking and show mild corrosion; no seismic concern; WR 288402 initiated to address CHWMVAAA554 issues, WR288404 initiated to address CHWMVAAA556 issues
• Cover on drain below HX not secured; no seismic concern
Evaluated by: Natalie George Date: 10/4/12
Chu-Chieh Lin 10/4/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 96 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-023
Location: Bldg. RAB Floor El. +21 Room, Area CCW HX A Room
SWEL Components: SWEL1-090
Photographs
Note: Harnesses lying on ground near scaffolding Note: Valve CHWMVAAA554 is leaking and shows mild corrosion
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 97 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-023
Location: Bldg. RAB Floor El. +21 Room, Area CCW HX A Room
SWEL Components: SWEL1-090
Note: Valve CHWMVAAA556 is leaking and shows mild corrosion
Note: Cover on drain below HX not secured
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 98 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-024
Location: Bldg. RAB Floor El. +21 Room, Area1 CCW HX B Room
SWEL Components: SWEL1-014, 021
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• Anchorage of all equipment is in good condition.
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• Mild corrosion found on pipe support associated with valve CHW-873. No seismic concern.
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 99 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-024
Location: Bldg. RAB Floor El. +21 Room, Area CCW HX B Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Overhead fluorescent lights without cages are overhead. The fixture is well supported. Falling bulbs would have no impact on equipment in the area. There is no seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
• Minor housekeeping issues. A bucket and bottles located on the floor. No seismic concern.
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 100 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-024
Location: Bldg. RAB Floor El. +21 Room, Area CCW HX B Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• A group of valves have mild surface corrosion on the bolts and yokes (CHWMVAAA872, CHWMVAAA873, CHWMVAAA874, CHWMVAAA875)
• CR-WF3-2012-05286 initiated to address corrosion CHWMVAAA872, CHWMVAAA873, CHWMVAAA874, CHWMVAAA875; CHWMVAAA872 covered by WR 287671, CHWMVAAA873 covered by WR 287669, CHWMVAAA874 covered by WR 287672, and CHWMVAAA875 covered by WR 287673
• CHWMVAAA876 has mild surface corrosion on the bolts and yokes • CR-WF3-2010-06306 and WR 216309 previously issued to address corrosion on
CHWMVAAA876 • These pose no seismic concern.
Evaluated by: Brian Pace Date: 10-12-2012
Dinesh Patel 10-12-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 101 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-024
Location: Bldg. RAB Floor El. +21 Room, Area CCW HX B Room
SWEL Components: SWEL1-014, 021
Photographs
Note: Valve CHW-874 mild surface corrosion. Note: Valve CHW-872 with mild surface corrosion.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 102 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-024
Location: Bldg. RAB Floor El. +21 Room, Area CCW HX B Room
SWEL Components: SWEL1-014, 021
Note: Mild corrosion on pipe support associated with valve CHW-873.
Note: Minor housekeeping issues.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 103 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-025
Location: Bldg. RAB Floor El. +21 Room, Area1 Emergency Diesel Generator B Room
SWEL Components: SWEL1-043, 072, 081
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 104 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-025
Location: Bldg. RAB Floor El. +21 Room, Area Emergency Diesel Generator B Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages, but falling bulbs will have not impact on equipment in the room. This is no seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
• Two unsecured disposal cans in front of panel but would have no adverse effect on the panel if it was impacted by cans.
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 105 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-025
Location: Bldg. RAB Floor El. +21 Room, Area Emergency Diesel Generator B Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
• Conduits rigidly attached to equipment are acceptable per drawing no. B288 sh. 19-1
Y N U
Comments (Additional pages may be added as necessary)
• Electrical junction box 2 (conduit 222-7909002-21) has two missing bolts and one loose bolt (out of 14 total); no seismic concern
• Valves EGFMVAAA126B and EGFMVAAA127B near support EGRR-3019 show mild corrosion; no seismic concern
Evaluated by: Dinesh Patel Date: 10/2/12
Brian Pace 10/2/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 106 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-025
Location: Bldg. RAB Floor El. +21 Room, Area Emergency Diesel Generator B Room
SWEL Components: SWEL1-043, 072, 081
Photographs
Note: Electrical junction box 2 has two missing bolts and one loose bolt
Note: Mild corrosion on valves EGFMVAAA126B and EGFMVAAA127B
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 107 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-028
Location: Bldg. RB Floor El. -35 Room, Area1 RB -35 Central Area
SWEL Components: SWEL1-025, 052, 053, 054, 055, 057, 058
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 108 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-028
Location: Bldg. RB Floor El. -35 Room, Area RB -35 Central Area
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages but will not affect equipment if bulbs fall. Fixture is rigid.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 109 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-028
Location: Bldg. RB Floor El. -35 Room, Area RB -35 Central Area
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Clip on SI MVAAA225A not secure; no seismic concern • Hoses on ground due to work in progress; no seismic concern • Leak on BD MPMP0004. WO#319512 addresses this leak. No seismic concern. • One clip on insulation of pipe associated with valve SI MVAAA138-B is broken near the elbow.
No seismic concern.
Evaluated by: Dinesh Patel Date: 10-15-2012
Brian Pace 10-15-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 110 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-028
Location: Bldg. RB Floor El. -35 Room, Area RB -35 Central Area
SWEL Components: SWEL1-025, 052, 053, 054, 055, 057, 058
Photographs
Note: Leak addressed by WO#319512 Note: Clip on SI MVAAA225A not secure
Note: Hoses on ground due to work in progress Note: Broken clip on insulation around pipe
associated with valve SI MVAAA138-B.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 111 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-029
Location: Bldg. RB Floor El. -35 Room, Area1 Diesel Oil Storage Tank A Room
SWEL Components: SWEL1-011, 093
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• Anchorage of equipment is free of adverse conditions.
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• Corrosion and minor oil leaks found on valves near the tank (EGFMVAAA104-A and EGFMVAAA1061 and EGFMVAAA105A).
• Corrosion found on sump pumps SP EMTR213B-7B and SP EMTR213A-7B in the area.
• The level gauge attached to the tank had minor surface corrosion.
• Two pipe supports above this equipment had corroded bolts. • No seismic concerns due to these issues. • CR-WF3-2012-05284 and WR-287663 initiated to address
these conditions.
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 112 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-029
Location: Bldg. RB Floor El. -35 Room, Area Diesel Oil Storage Tank A Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 113 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-029
Location: Bldg. RB Floor El. -35 Room, Area Diesel Oil Storage Tank A Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Brian Pace Date: 10/5/12
Dinesh Patel 10/5/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 114 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-029
Location: Bldg. RB Floor El. -35 Room, Area Diesel Oil Storage Tank A Room
SWEL Components: SWEL1-011, 093
Photographs
Note: Valve EGFMVAAA104-A surface corrosion.
Note: Valve EGFMVAAA1061 with mild surface corrosion.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 115 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-029
Location: Bldg. RB Floor El. -35 Room, Area Diesel Oil Storage Tank A Room
SWEL Components: SWEL1-011, 093
Note: Sump pumps SP EMTR213A-7B and SP EMTR213B-7B near tank have mild surface corrosion.
Note: Pipe support with corroded bolts.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 116 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-030
Location: Bldg. RB Floor El. -4 Room, Area1 B100 / 10A - M
SWEL Components: SWEL1-017, 022, 033, 076
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• Bolt displays mild corrosion; no seismic concern
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 117 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-030
Location: Bldg. RB Floor El. -4 Room, Area B100 / 10A - M
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
• Barrels near column 10A, line N are not properly secured. See LB-05 in Attachment F.
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 118 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-030
Location: Bldg. RB Floor El. -4 Room, Area B100 / 10A - M
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Damage to jacketing near valve BD MVAAA107-A, potential insulation damage; no seismic concern
• Mild corrosion on valves throughout; no seismic concern
Evaluated by: Natalie George Date: 10/5/12
Chu-Chieh Lin 10/5/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 119 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-030
Location: Bldg. RB Floor El. -4 Room, Area B100 / 10A - M
SWEL Components: SWEL1-017, 022, 033, 076
Photographs
Note: Bolts display mild corrosion Note: Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 120 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-030
Location: Bldg. RB Floor El. -4 Room, Area B100 / 10A - M
SWEL Components: SWEL1-017, 022, 033, 076
Note: Barrels near column 10A, line N are not properly secured
Note: Damage to jacketing near valve BD MVAAA107-A; potential insulation damage
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 121 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-032
Location: Bldg. RAB Floor El. +46 Room, Area1 Control Room
SWEL Components: SWEL-084, 085, 086
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 122 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-032
Location: Bldg. RAB Floor El. +46 Room, Area Control Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
• Book case and trash can next to IC ECP08 should be moved or bolted (anchored), book case adjacent to IC ECP22 should be moved or bolted, trash can in front of IC ECP11B should be moved
o After reevaluation of these components, it was determined that all loose items in the control room are anchored. Calculation ECC-095-005 was issued for the loose items in the control room after IPEEE identified these same issues.
o The trash cans were also determined to be made of material that could not damage the surrounding cabinets.
• Table and trash can next to IC ECP20 should be moved o This is not a seismic concern because it is next to
Non-Safety Related equipment, but must be moved for personnel safety.
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 123 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-032
Location: Bldg. RAB Floor El. +46 Room, Area Control Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Natalie George Date: 10/8/12
Chu-Chieh Lin 10/8/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 124 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-032
Location: Bldg. RAB Floor El. +46 Room, Area Control Room
SWEL Components: SWEL-084, 085, 086
Photographs
Note: Book case and trash can next to IC ECP08 should be moved or bolted (anchored) (Determined to not be an issue)
Note: Book case adjacent to IC ECP22 should be moved or bolted (Determined to be anchored)
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 125 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-032
Location: Bldg. RAB Floor El. +46 Room, Area Control Room
SWEL Components: SWEL-084, 085, 086
Note: Table and trash can next to IC ECP20 should be moved
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 126 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-035
Location: Bldg. RAB Floor El. +46 Room, Area1 Emergency Diesel Oil Feed Tank A Room
SWEL Components: SWEL1-074
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• All anchorage of nearby equipment, including the Diesel Oil Feed Tank A, is in good condition.
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• No degraded conditions found on anchors.
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 127 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-035
Location: Bldg. RAB Floor El. +46 Room, Area Emergency Diesel Oil Feed Tank A Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
• A wrench located on top of a structural steel member could fall and damage valve nearby.
• The wrench was removed and brought to the tool room, solving the potentially adverse seismic condition.
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 128 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-035
Location: Bldg. RAB Floor El. +46 Room, Area Emergency Diesel Oil Feed Tank A Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Oil leak from diesel tank flange. Currently being resolved with WR#232292 and CR#11-1860. No seismic concern.
• One drain valves had a slight leak on it as well. No seismic concern.
Evaluated by: Brian Pace Date: 10-08-2012
Dinesh Patel 10-08-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 129 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-035
Location: Bldg. RAB Floor El. +46 Room, Area Emergency Diesel Oil Feed Tank A Room
SWEL Components: SWEL1-074
Photographs
Note: Wrench with potential adverse seismic condition. Note that the wrench was removed and brought to the tool room, removing the condition.
Note: Leak on the diesel oil feed tank.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 130 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-035
Location: Bldg. RAB Floor El. +46 Room, Area Emergency Diesel Oil Feed Tank A Room
SWEL Components: SWEL1-074
Note: Leak on valve in room. Note:
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 131 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-036
Location: Bldg. RAB Floor El. +46 Room, Area E28 Fan Area
SWEL Components: SWEL1-032, 063
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• Anchorage of equipment appears to be in good condition
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• Valve CHWMVAAA201 has surface corrosion on yoke plate and bolts, CR-WF3-2012-05627 and WR 288441 initiated to address corrosion; not a seismic concern
• Bolt and pipe clamp on pipe support near fan E-28 has surface corrosion; not a seismic concern
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 132 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-036
Location: Bldg. RAB Floor El. +46 Room, Area E28 Fan Area
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Overhead lighting is not above any equipment
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 133 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-036
Location: Bldg. RAB Floor El. +46 Room, Area E28 Fan Area
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Crushed insulation on pipe on top of scaffolding by fan E-28; not a seismic concern
Evaluated by: Dinesh Patel Date: 10-08-2012
Brian Pace 10-08-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 134 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-036
Location: Bldg. RAB Floor El. +46 Room, Area E28 Fan Area
SWEL Components: SWEL1-032, 063
Photographs
Note: Surface corrosion on valve CHWMVAAA201
Note: Surface corrosion on valve CHWMVAAA201 from underneath
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 135 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-036
Location: Bldg. RAB Floor El. +46 Room, Area E28 Fan Area
SWEL Components: SWEL1-032, 063
Note: Surface corrosion on pipe clamp on pipe support near fan E-28
Note: Crushed insulation on pipe lying on scaffolding near fan E-28
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 136 of 210
Sheet 1 of 6 Status: Y N U
Area Walk-By Checklist (AWC) AWC-037
Location: Bldg. RAB Floor El. +46 Room, Area1 NORTHWEST RAB +46 AREA
SWEL Components: SWEL1-031, 041, 049, 050, 067, 088
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 137 of 210
Sheet 2 of 6 Status: Y N U
Area Walk-By Checklist (AWC) AWC-037
Location: Bldg. RAB Floor El. +46 Room, Area NORTHWEST RAB +46 AREA
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
• Chain from crane should be re-positioned so it will not interaction w/ panel or piping; see LB-06 in Attachment F.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 138 of 210
Sheet 3 of 6 Status: Y N U
Area Walk-By Checklist (AWC) AWC-037
Location: Bldg. RAB Floor El. +46 Room, Area NORTHWEST RAB +46 AREA
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
• Severe corrosion on valves CHWMVAAA121A and CHWMVAAA788A
o CR-WF3-2012-06472 and WO 196829 initiated for CHWMVAAA121A.
o CR-WF3-2012-05372 and WR287812 were initiated for CHWMVAAA788A.
• Severe corrosion and leakage on valves CHWMVAAA127B, CHWMVAAA436, and CHWMVAAA881
o CR-WF3-2012-05372 and WR 287813 initiated for CHWMVAAA127B.
o CR-WF3-2012-05089 and WR 286898 and WR 286900 already written for CHWMVAAA436 and CHWMVAAA887.
Y N U
Comments (Additional pages may be added as necessary)
• Mild corrosion and leakage on pump CHWMPMP0001B, no seismic concern; CR-WF3-2010-05497 and WR 212221 in-progress to address issues
• Loose screws inside of pump CHWMPMP0001B, no seismic concern; WR 287826 initiated to address issue
• Mild corrosion and leakage on valves CHWMVAAA248, CHWMVAAA550, CHWMVAAA1341B, and CHWMVAAA1343B, no seismic concern
o WR 287824 initiated for CHWMVAAA248, CR-WF3-2012-05732 and WR 287815 and WR 287816 written for CHWMVAAA1341B and CHWMVAAA1343B, WR 44875 in-progress for CHWMVAAA550
Evaluated by: Natalie George Date: 10/15/12
Chu-Chieh Lin 10/15/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 139 of 210
Sheet 4 of 6 Status: Y N U
Area Walk-By Checklist (AWC) AWC-037
Location: Bldg. RAB Floor El. +46 Room, Area NORTHWEST RAB +46 AREA
SWEL Components: SWEL1-031, 041, 049, 050, 067, 088
Photographs
Note: Severe corrosion on valve CHWMVAAA121A
Note: Severe corrosion on valve CHWMVAAA788A
Note: Severe corrosion and leakage on valve CHWMVAAA127B
Note: Mild corrosion and leakage on pump CHWMPMP0001B
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 140 of 210
Sheet 5 of 6 Status: Y N U
Area Walk-By Checklist (AWC) AWC-037
Location: Bldg. RAB Floor El. +46 Room, Area NORTHWEST RAB +46 AREA
SWEL Components: SWEL1-031, 041, 049, 050, 067, 088
Note: Loose screws inside of pump CHWMPMP0001B
Note: Mild corrosion and leakage on valve CHWMVAAA1341B
Note: Mild corrosion and leakage on valve CHWMVAAA1343B
Note: Mild corrosion and leakage on valve CHWMVAAA248
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 141 of 210
Sheet 6 of 6 Status: Y N U
Area Walk-By Checklist (AWC) AWC-037
Location: Bldg. RAB Floor El. +46 Room, Area NORTHWEST RAB +46 AREA
SWEL Components: SWEL1-031, 041, 049, 050, 067, 088
Note: Mild corrosion and leakage on valve CHWMVAAA550
Note: Severe corrosion and leakage on valve CHWMVAAA436
Note: Severe corrosion and leakage on valve CHWMVAAA881
Note: Chain from crane should be re-positioned so it will not interaction w/ panel or piping
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 142 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-038
Location: Bldg. RAB Floor El. +46 Room, Area1 Emergency Vent Air Clean Up Units Area
SWEL Components: SWEL1-029, 061, 062, 064
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 143 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC- 038
Location: Bldg. RAB Floor El. +46 Room, Area Emergency Vent Air Clean Up Units Area
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 144 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC- 038
Location: Bldg. RAB Floor El. +46 Room, Area Emergency Vent Air Clean Up Units Area
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
• Block wall in area acceptable per drawing no. G765 sh. 2, calculation no. Civil Seismic Block Walls, and FSAR Section 3.8.4.8
Y N U
Comments (Additional pages may be added as necessary)
• Damage to insulation on HVC-215A and AH-12B; no seismic concern
Evaluated by: Natalie George Date: 10/9/12
Chu-Chieh Lin 10/9/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 145 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC- 038
Location: Bldg. RAB Floor El. +46 Room, Area Emergency Vent Air Clean Up Units Area
SWEL Components: SWEL1-029, 061, 062, 064
Photographs
Note: Damage to insulation on HVC-215A Note: Damage to insulation on AH-12B
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 146 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-039
Location: Bldg. RAB Floor El. +46 Room, Area1 AH-25B Room
SWEL Components: SWEL1-042
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• All components in the vicinity of CHWMVAAA900 are well anchored.
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• Mild surface corrosion on bolt on AH-25B and steel along bottom of air handler, but this poses no seismic impact; WR 288417 initiated to address corrosion
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 147 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-039
Location: Bldg. RAB Floor El. +46 Room, Area AH-25B Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Overhead lighting has no covers, but falling bulbs would have no impact on equipment underneath. Fixtures are well supported.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
• Unsecured tool box is in designated storage area.
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 148 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-039
Location: Bldg. RAB Floor El. +46 Room, Area AH-25B Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
• There is a piece of steel tied with a rope to base plate at two locations. Once of them is near a valve. It was determined that the steel piece in the vicinity of this valve could not make impact with the valve during a seismic event. Therefore, this is no seismic concern.
• Three ladders in the area are all well secured.
Y N U
Comments (Additional pages may be added as necessary)
• Loose insulation near AH-25B; no seismic concern.
Evaluated by: Dinesh Patel Date: 10-09-2012
Brian Pace 10-09-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 149 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-039
Location: Bldg. RAB Floor El. +46 Room, Area AH-25B Room
SWEL Components: SWEL1-042
Photographs
Note: Hanging steel determined not to have an impact on the nearby valves.
Note: Corrosion on bolt and surrounding steel at the bottom of AH-25B.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 150 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-039
Location: Bldg. RAB Floor El. +46 Room, Area AH-25B Room
SWEL Components: SWEL1-042
Note: Insulation is loose near AH-25B. Note:
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 151 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-040
Location: Bldg. RAB Floor El. +91 Room, Area1 CCW Surge Tank Area
SWEL Components: SWEL1-073, 091
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• Anchorage of equipment is in good condition.
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• Slight surface corrosion on two base plates for pipe supports on LS-CC-7011BS; WR 288395 initiated to address corrosion
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 152 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-040
Location: Bldg. RAB Floor El. +91 Room, Area CCW Surge Tank Area
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 153 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-040
Location: Bldg. RAB Floor El. +91 Room, Area CCW Surge Tank Area
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Brian Pace Date: 10-08-2012
Dinesh Patel 10-08-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 154 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-040
Location: Bldg. RAB Floor El. +91 Room, Area CCW Surge Tank Area
SWEL Components: SWEL1-073, 091
Photographs
Note: Turbine Cooling Water Surge Tank well anchored from walk-by observations.
Note: All additional valves and level switches well supported and cause no spatial interaction concerns.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 155 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-040
Location: Bldg. RAB Floor El. +91 Room, Area CCW Surge Tank Area
SWEL Components: SWEL1-073, 091
Note: Surface corrosion on base plate (one of two shown).
Note:
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 156 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-041
Location: Bldg. RB Floor El. +46 Room, Area AH-32, 34, 35 ROOM (ON ROOF)
SWEL Components: SWEL1-078
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• Degradation of concrete pad near embedded plates to which legs of tank NG-MACC-005 are welded, adverse seismic concern; identified in CR-WF3-2012-05278 and WR 287650
• Cracks in concrete near embedded plates to which legs of tank NG-MACC-006 are welded, adverse seismic concern; identified in CR-WF3-2012-05278 and WR 287650
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
• Severe corrosion on support for conduit lines 32095G-NB and 32095F-NB, adverse seismic concern; CR-WF3-2012-05203 and WR 287462 initiated to address corrosion
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 157 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-041
Location: Bldg. RB Floor El. +46 Room, Area AH-32, 34, 35 ROOM (ON ROOF)
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 158 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-041
Location: Bldg. RB Floor El. +46 Room, Area AH-32, 34, 35 ROOM (ON ROOF)
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Mild corrosion throughout area, no seismic concern; CR-WF3-2012-5203, CR-WF3-2012-05278, WR 287643, WR 287645, WR 287646, and WR 287462 initiated to address corrosion
• Water pooling in recessed embedded plates, no seismic concern; CR-WF3-2012-05278 and WR’s 287643, 287645, 287646, and 287650 initiated to address issue
Evaluated by: Natalie George Date: 10/5/12
Chu-Chieh Lin 10/5/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 159 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-041
Location: Bldg. RB Floor El. +46 Room, Area AH-32, 34, 35 ROOM (ON ROOF)
SWEL Components: SWEL1-078
Photographs
Note: Degradation of concrete pad near embedded plates to which legs of tank NG-MACC-005 are welded
Note: Cracks in concrete near embedded plates to which legs of tank NG-MACC-006 are welded
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 160 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-041
Location: Bldg. RB Floor El. +46 Room, Area AH-32, 34, 35 ROOM (ON ROOF)
SWEL Components: SWEL1-078
Note: Severe corrosion on support for conduit lines 32095G-NB and 32095F-NB
Note: Water pooling in recessed embedded plates
Note: Mild corrosion on MS MVAAA124 AA Note: Mild corrosion on MS MVAAA124 AB
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 161 of 210
Sheet 1 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-042
Location: Bldg. RB Floor El. +46 Room, Area West Wing Area
SWEL Components: SWEL1-001, 034, 044, 045, 046
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 162 of 210
Sheet 2 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-042
Location: Bldg. RB Floor El. +46 Room, Area West Wing Area
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 163 of 210
Sheet 3 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-042
Location: Bldg. RB Floor El. +46 Room, Area West Wing Area
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Mild corrosion throughout, on supports, valves, etc., no seismic concern; CR-WF3-2012-05278 and WR’s 287643, 287645, 287646, and 287650 initiated to address corrosion
• Water pooling at base of pipe support, recessed embedded plate; no seismic concern
Evaluated by: Natalie George Date: 10/5/12
Chu-Chieh Lin 10/5/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 164 of 210
Sheet 4 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-042
Location: Bldg. RB Floor El. +46 Room, Area West Wing Area
SWEL Components: SWEL1-001, 034, 044, 045, 046
Photographs
Note: Mild corrosion on supports throughout area Note: Mild corrosion on valves throughout area
Note: Mild corrosion on supports throughout area Note: Mild corrosion on valves throughout area
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 165 of 210
Sheet 5 of 5 Status: Y N U
Area Walk-By Checklist (AWC) AWC-042
Location: Bldg. RB Floor El. +46 Room, Area West Wing Area
SWEL Components: SWEL1-001, 034, 044, 045, 046
Note: Mild corrosion on valves throughout area Note: Water pooling at base of pipe support
Note: Mild corrosion on valves throughout area and dent on the pipe
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 166 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-043
Location: Bldg. RB Floor El. +46 Room, Area Southeast Wing Area
SWEL Components: SWEL1-035
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 167 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-043
Location: Bldg. RB Floor El. +46 Room, Area Southeast Wing Area
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 168 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-043
Location: Bldg. RB Floor El. +46 Room, Area Southeast Wing Area
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Corrosion throughout area; CR-WF3-2012-05198 initiated to address corrosion • Valve MS MVAAA124-B62 is leaking, previously documented and funnel in place
Evaluated by: Natalie George Date: 10/5/12
Chu-Chieh Lin 10/5/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 169 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-043
Location: Bldg. RB Floor El. +46 Room, Area Southeast Wing Area
SWEL Components: SWEL1-035
Photographs
Note: Corrosion throughout area Note: Valve MS MVAAA124-B62 is leaking,
previously documented and funnel in place
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 170 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-044
Location: Bldg. RB Floor El. +46 Room, Area Northeast Wing Area
SWEL Components: SWEL1-027, 028
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 171 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-044
Location: Bldg. RB Floor El. +46 Room, Area Northeast Wing Area
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 172 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-044
Location: Bldg. RB Floor El. +46 Room, Area Northeast Wing Area
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Mild corrosion throughout area, no seismic concern; CR-WF3-2012-05207, CR-WF3-2012-05278, WR 287493, WR 287643, WR 287645, WR 287646,
and WR 287650 initiated to address issue • Water pooling in structural support, no seismic concern; CR-WF3-2012-05207,
CR-WF3-2012-05278, WR 287493, WR 287643, WR 287645, WR 287646, and WR 287650 initiated to address issue •
Evaluated by: Natalie George Date: 10/5/12
Chu-Chieh Lin 10/5/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 173 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-044
Location: Bldg. RB Floor El. +46 Room, Area Northeast Wing Area
SWEL Components: SWEL1-027, 028
Photographs
Note: Corrosion throughout area Note: Water pooling in structural support
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 174 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-045
Location: Bldg. RAB Floor El. +21 Room, Area1 Emergency Diesel Generator A Room
SWEL Components: SWEL1-095, 096
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 175 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-045
Location: Bldg. RAB Floor El. +21 Room, Area Emergency Diesel Generator A Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 176 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-045
Location: Bldg. RAB Floor El. +21 Room, Area Emergency Diesel Generator A Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Cover not secure on north side of emergency diesel generator; no seismic concern • Housekeeping issue; no seismic concern
o Gloves left in area
Evaluated by: Natalie George Date: 10/8/12
Chu-Chieh Lin 10/8/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 177 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-045
Location: Bldg. RAB Floor El. +21 Room, Area Emergency Diesel Generator A Room
SWEL Components: SWEL1-095, 096
Photographs
Note: Cover not secure on north side of emergency diesel generator
Note: Gloves left in area
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 178 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-046
Location: Bldg. FHB Floor El. +1 Room, Area1 Multiplexer Enclosure West Side
SWEL Components: SWEL2-017, 018, 019
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 179 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-046
Location: Bldg. FHB Floor El. +1 Room, Area Multiplexer Enclosure West Side
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
• Pipe from CCW tank should have been previously analyzed for seismic event; no seismic concern
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 180 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-046
Location: Bldg. FHB Floor El. +1 Room, Area Multiplexer Enclosure West Side
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Several valves are leaking oil (CC MVAAA617, CC MVAAA618, and CC MVAAA622), no seismic concern; WR 288397 initiated for CC MVAAA617, WR288398 initiated for CC MVAAA618, and WR 288399 initiated for CC MVAAA622
Evaluated by: Natalie George Date: 10/10/12
Chu-Chieh Lin 10/10/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 181 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-046
Location: Bldg. FHB Floor El. +1 Room, Area Multiplexer Enclosure West Side
SWEL Components: SWEL2-017, 018, 019
Photographs
Note: Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Note: Example of valve leaking oil
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 182 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-047
Location: Bldg. FHB Floor El. +1 Room, Area1 Fuel Pool Heat Exchanger Room
SWEL Components: SWEL2-020
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• Conduits and pipe supports well anchored
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• No corrosion found
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 183 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-047
Location: Bldg. FHB Floor El. +1 Room, Area Fuel Pool Heat Exchanger Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 184 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-047
Location: Bldg. FHB Floor El. +1 Room, Area Fuel Pool Heat Exchanger Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Brian Pace Date: 10-10-2012
Dinesh Patel 10-10-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 185 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-047
Location: Bldg. FHB Floor El. +1 Room, Area Fuel Pool Heat Exchanger Room
SWEL Components: SWEL2-020
Photographs
Note: Example of pipe support in good condition.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 186 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-048
Location: Bldg. FHB Floor El. +1 Room, Area1 Fuel Pool Pump A Room
SWEL Components: SWEL2-012, 015
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 187 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-048
Location: Bldg. FHB Floor El. +1 Room, Area Fuel Pool Pump A Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 188 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-048
Location: Bldg. FHB Floor El. +1 Room, Area Fuel Pool Pump A Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Natalie George Date: 10/10/12
Chu-Chieh Lin 10/10/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 189 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-048
Location: Bldg. FHB Floor El. +1 Room, Area Fuel Pool Pump A Room
SWEL Components: SWEL2-012, 015
Photographs
Note: Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 190 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-049
Location: Bldg. FHB Floor El. +1 Room, Area1 Fuel Pool Pump B Room
SWEL Components: SWEL2-013, 016
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 191 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-049
Location: Bldg. FHB Floor El. +1 Room, Area Fuel Pool Pump B Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 192 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-049
Location: Bldg. FHB Floor El. +1 Room, Area Fuel Pool Pump B Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Natalie George Date: 10/12/12
Chu-Chieh Lin 10/12/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 193 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-049
Location: Bldg. FHB Floor El. +1 Room, Area Fuel Pool Pump B Room
SWEL Components: SWEL2-013, 016
Photographs
Note: Fuel Pool Pump B Room
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 194 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-050
Location: Bldg. FHB Floor El. -35 Room, Area1 Refuel Canal Drain Pump Area
SWEL Components: SWEL2-014, 022, 023, 024, 025, 026
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• All anchorage in area is in good condition
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• No degraded conditions were found on any anchorage
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 195 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-050
Location: Bldg. FHB Floor El. -35 Room, Area Refuel Canal Drain Pump Area
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Overhead lights with no covers present. No seismically sensitive equipment in vicinity; no seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 196 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-050
Location: Bldg. FHB Floor El. -35 Room, Area Refuel Canal Drain Pump Area
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Brian Pace Date: 10-10-2012
Dinesh Patel 10-10-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 197 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-050
Location: Bldg. FHB Floor El. -35 Room, Area Refuel Canal Drain Pump Area
SWEL Components: SWEL2-014, 022, 023, 024, 025, 026
Photographs
Note: All overhead equipment is properly secured.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 198 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-051
Location: Bldg. FHB Floor El. -35 Room, Area1 Back-Up Fuel Pool Heat Exchanger Room
SWEL Components: SWEL2-021
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• Conduits and pipe supports well anchored
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• No corrosion or any other degraded condition were found on anchorage
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 199 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-051
Location: Bldg. FHB Floor El. -35 Room, Area Back-Up Fuel Pool Heat Exchanger Room
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 200 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-051
Location: Bldg. FHB Floor El. -35 Room, Area Back-Up Fuel Pool Heat Exchanger Room
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Brian Pace Date: 10-10-2012
Dinesh Patel 10-10-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 201 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-051
Location: Bldg. FHB Floor El. -35 Room, Area Back-Up Fuel Pool Heat Exchanger Room
SWEL Components: SWEL2-021
Photographs
Note: Sample of area walk-by Note: Sample of area walk-by
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 202 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-052
Location: Bldg. RAB Floor El. +35 Room, Area1 Relay Room B
SWEL Components: SWEL2-004
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
• Anchorage in area is in good condition.
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
• No degraded conditions were observed.
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 203 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-052
Location: Bldg. RAB Floor El. +35 Room, Area RAB +35
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 204 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-052
Location: Bldg. RAB Floor El. +35 Room, Area RAB +35
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
• Possible surface cracks can be seen in the floor. Most have been filled. These cracks do not pose seismic concerns.
• Blocks walls located around the room are acceptable per drawing no. G765 sh. 2, calculation no. Civil Seismic Block Walls, and FSAR Section 3.8.4.8
Y N U
Comments (Additional pages may be added as necessary)
Evaluated by: Brian Pace Date: 10-10-2012
Dinesh Patel 10-10-2012
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 205 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-052
Location: Bldg. RAB Floor El. +35 Room, Area RAB +35
SWEL Components: SWEL2-004
Photographs
Note: Reinforced block wall Note: Possible surface cracks. Most have been filled
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 206 of 210
Sheet 1 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-053
Location: Bldg. RAB Floor El. +35 Room, Area1 RAB +35
SWEL Components: SWEL1-083, SWEL2-005
Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?
Y N U N/A
2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?
Y N U N/A
3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Y N U N/A
1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area selected should be described. This selected area should be based on judgment, e.g., on the order of about 35 feet from the SWEL item.
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 207 of 210
Sheet 2 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-053
Location: Bldg. RAB Floor El. +35 Room, Area RAB +35
4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
• Fluorescent lights do not have cages. Falling bulbs will not damage equipment and is not a seismic concern.
Y N U N/A
5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?
Y N U N/A
6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?
Y N U N/A
7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Y N U N/A
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 208 of 210
Sheet 3 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-053
Location: Bldg. RAB Floor El. +35 Room, Area RAB +35
8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Y N U
Comments (Additional pages may be added as necessary)
• Operations appendix R supplies locker not anchored; will not interact with equipment if it falls. Referred to Permit # RAB+35-10-488
• Block wall near equipment acceptable per drawing no. G765 sh. 2, calculation no. Civil Seismic Block Walls, and FSAR Section 3.8.4.8
Evaluated by: Natalie George Date: 10/15/12
Chu-Chieh Lin 10/15/12
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 209 of 210
Sheet 4 of 4 Status: Y N U
Area Walk-By Checklist (AWC) AWC-053
Location: Bldg. RAB Floor El. +35 Room, Area RAB +35
SWEL Components: SWEL1-083, SWEL2-005
Photographs
Note: Operations appendix R supplies locker Note: Block wall near equipment
Engineering Report No. WF3-CS-12-00003 Attachment D
Rev. 0 Page 210 of 210