atex installation instructions
DESCRIPTION
ATEX Installation Instructionsfor Micro Motion® Model1700, 2700, and 2750TransmittersTRANSCRIPT
-
Installation InstructionsP/N MMI-20011705, Rev. AJuly 2008
ATEX Installation Instructions for Micro Motion Model 1700, 2700, and 2750 Transmitters
-
Note: For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
2008, Micro Motion, Inc. All rights reserved. ELITE and ProLink are registered trademarks, and MVD and MVD Direct Connect are trademarks of Micro Motion, Inc., Boulder, Colorado. Micro Motion is a registered trade name of Micro Motion, Inc., Boulder, Colorado. The Micro Motion and Emerson logos are trademarks and service marks of Emerson Electric Co. All other trademarks are property of their respective owners.
Information affixed to equipment that complies with the Pressure Equipment Directive can be found on the internet at www.micromotion.com/library.
Reference no. EB-3600636 Rev. I
-
1Model 1700/2700/2750 TransmittersATEX Installation Instructions and Drawings
For installing the following Micro Motion transmitters:- Model 1700/2700/2750 with a 4-wire connection to a core processor- Model 1700/2700/2750 with a 9-wire connection to a junction box- Model 1700/2700/2750 with a remote core processor and remote sensor with a
junction box
Subject: Equipment type Transmitter type *700********** andTransmitter type *750**********
Manufactured and submitted for examination
Micro Motion, Inc.
Address Boulder, Co. 80301, USA
Standard basis EN 60079-0:2006 General requirements
EN 60079-1:2004 Flameproof enclosure d
EN 60079-7:2003 Increased safety e
EN 60079-11:2007 Intrinsic safety i
EN 61241-0:2006 and EN 61241-1:2004
Dust evaluation tD A
EN 60079-26:2004 Equipment Group II, Category 1G
EN 60079-27:2006 FISCO/FNICO
Code for type of protection Ex d [ib] IIB + H2 T6, Ex de [ib] IIB + H2 T5/T6 Ex d [ia/ib] IIB + H2 T6, Ex de [ia/ib] IIB + H2 T5/T6 Ex d [ib] IIC T6, Ex de [ib] IIC T5/T6 Ex d [ia/ib] IIC T6, Ex de [ia/ib] IIC T5/T6 Ex tD A21 IP66/IP67 T65C
ATEX Installation Instructions
-
Model 1700/2700/2750 Transmitters
2 ATEX Installation Instructions
1) Subject and type
Transmitter type *700********** and type *750**********
Instead of the *** letters and numerals will be inserted which characterize the following modifications:
Marking without influence to the type of protection
* 7 5 0 * 1 * * * * * * *
Numeral1 = Single variable transmitter2 = Multivariable transmitter
Letter for conduit connections
Letter for outputsA = One mA, one frequencyB = Config I/O defaultC = Config I/O customD = Intrinsically safe outputsE = Intrinsically safe FOUNDATION fieldbus H1G = PROFIBUS-PAN = Non-I.S. FOUNDATION fieldbus H1J = Config I/O default (Model *750 only)K = Config I/O custom (Model *750 only)
*
Letter for mountingR = Remote mount (4-wire connection)I or S = Integral mountC = Remote mount (9-wire connection)B = Remote mount transmitter with remote mount
core processorD = Integral mount (Model *750 only)E = Remote mount (Model *750 only)
Numeral for display1 = With display: Ex *** IIB + H22 = With backlight display: Ex *** IIB + H23 = Without display: Ex *** IIC4 = With IIC display: Ex *** IIC4 with ETO 12638 = Ex ***IIC with FEP face plate5 = With IIC backlight display: Ex *** IIC5 with ETO 12638 = Ex ***IIC with FEP face plate
ApprovalF = Ex d ****Z = Ex de ****
* 7 0 0 * 1 * * * * * * **
-
Model 1700/2700/2750 Transmitters
ATEX Installation Instructions 3
2) Description
The transmitter is, in combination with a sensor, used for measurement of mass flow and data transmission.
The electrical circuitry of the transmitters is mounted inside a metal enclosure type 1700/2700/*750..*..*..which is divided into three compartments.
In the compartment type of protection Flameproof Enclosure the Terminal Board, Power Supply Board, Feature Board, Digital Board and Fieldbus Board (only type 2700*1******** and type 2750*1********) are mounted.
When executed with display, there are two window covers available, one for IIB + H2 and one for IIC. ETO 12638 adds an FEP plate over the glass window in the display cover. When it is executed without the display, the gas group is IIC.
The compartment Increased Safety (type *7*0*1***Z****) or Flameproof Enclosure (type *7*0*1***F*****) is equipped with terminals for the connection of intrinsically safe fieldbus circuit as well as non intrinsically safe circuits as well as intrinsically safe outputs.
The enclosure is constructed with a terminal compartment for the connection of remotely operating intrinsically safe sensors (type *700R1******** and type *750E1********) or to remote mount core (*700B1********). Alternatively, the enclosure can be mounted directly to the sensor via a transition compartment for the incorporation of the signal processing device type 700 (type *700I1******** and type *750D1********). This type of mounting has to be certified separately.
The transmitter type *7*0C1******** is constructed with a terminal compartment for the incorporation of the signal processing device type 700 and a connection board.
The transmitter is intended to be used in a hazardous dust environment without change to any of the electronics aspects of the design.
Amendment 8 to the ATEX certificate DMT 01 ATEX E 082 X incorporates the new EN 60079 series standards and therefore the marking changed from EEx to Ex. Additionally this amendment uses the new dust standards EN 61241-0:2006 and EN 61241-1:2004 and therefore changed the dust marking by adding "Ex tD A21". This amendment also added the non-IS fieldbus option N and changed the maximum voltage (Um) for the non-IS input/output circuits from 60 Vdc to 33 Vdc.
Amendment 9 to the ATEX Certificate DMT 01 ATEX E 082 X incorporates the new model *750*1********. Additionally this amendment incorporates the revised fieldbus board, analog board, and terminal board. The revised fieldbus board corrects a digital communication issue when transmitting fieldbus data and does not impact safety. The analog board was revised to eliminate a non-safety critical inductor (FL1) and added a pull up resistor to the HART transmit line to correct communication error. The terminal board was revised to replace an obsolete non-safety critical inductor (FL3) with an equivalent inductor requiring an artwork change to accommodate the new inductor spacing.
3) Parameters
3.1) Mains circuit (terminals 910)
3.2) Non intrinsically safe input/output circuits (terminals 16) only for type *700*1*(A, B, C, J, or K)******
Voltage AC/DC 18240 V + 10%Max voltage Um AC/DC 265 V
Voltage Um AC/DC 33 V
-
Model 1700/2700/2750 Transmitters
4 ATEX Installation Instructions
3.2.1) Non-intrinsically safe circuits fieldbus (terminals fieldbus 12) only for type *700*1*N******
3.3) Intrinsically safe output circuits type of protection Ex ia IIC
3.4) Intrinsically safe power and signal circuits for type *700R1******** or *700B1******** or *750E1********
3.4.1) Ambient temperature range
3.4.2) Ambient temperature range
*700*1*N******Fieldbus terminals 12 FNICO(1)
(1) For connection of a FOUNDATION fieldbus circuit in accordance with the FNICO model.
Voltage Um (Vdc) 33Current Im (mA) 380Power Pm (W) 5,32Effective internal inductance L NegligibleEffective internal capacitance C Negligible
*7*0*1*D****** 27*0*1*E****** 27*0*1*G******mA / HARTterminals 12 & 56
FOterminals 34
Fieldbus terminals 12 FISCO(1)
(1) For connection of a FOUNDATION fieldbus circuit in accordance with the FISCO model.
PROFIBUS terminals 12 FISCO(1)
Voltage Ui (Vdc) 30 30 30 30Current Ii (mA) 300 100 380 380Power Pi (W) 1 0,75 5,32 5,32Effective internal inductance Li Negligible Negligible Negligible NegligibleEffective internal capacitance Ci Negligible Negligible Negligible Negligible
Voltage Uo (Vdc) 17,22Current Io (A) 0,484Limited by a fuse with a nominal value of In (A) 0,16Power Po (W) 2,05
Type of protection Ex ib IIC Ex ib IIBMax. external inductance Lo (H) 151 607Max. external capacitance Co (F) 0,333 2,04Max. inductance/resistance ratio Lo/Ro (H/) 17,06 68,2
Models *7*0(R, B, or E)1(1, 2, or 3)******* Ta 40 C up to +60 C
Models *7*0(R, B, or E)1(4 or 5)******* Ta 20 C up to +60 C
-
Model 1700/2700/2750 Transmitters
ATEX Installation Instructions 5
3.5) Intrinsically safe power and signal circuits for type *7*0C1********
The maximum external inductance L (sensor coil) can be calculated with the following term:
whereby E = 40 J for group IIC and E = 160 J for group IIB will be inserted.Ro is the drive coil resistance plus the drive coil series resistor resistance.
3.5.1) Ambient temperature range
3.5.2) Ambient temperature range
Drive circuitterminals 34
Pick-off circuitsterminals 56 and 78
Temperature circuit terminals 1, 2, and 9
Voltage Uo 10,5 Vdc 17,3 Vdc 17,3 VdcCurrent Io 2,45 A 6,9 mA 26 mAPower Po 2,54 W 30 mW 112 mWInternal resistance Ri 4,32
Group IIC IIB IIC IIB IIC IIBMax. external inductance Lo 5,9 H 24 H 742 mH 2,97 H 52,6 mH 210 mHMax. external capacitance Co 2,41 F 16,8 F 353 nF 2,06 F 353 nF 2,06 FMax. inductance/resistance ratio
Lo/Ro 5,5 H/ 22 H/ 1,19 mH/
4,75 mH/
0,32 mH/
1,26 mH/
Models *7*0C1(1, 2, or 3)******* Ta 40 C up to +55 C
Models *7*0C1(4 or 5)******* Ta 20 C up to +55 C
L 2 E Ri Ro+1.5 Uo---------------------- 2=
-
Model 1700/2700/2750 Transmitters
6 ATEX Installation Instructions
4) Marking
5 min. delay time after switch off
Models *7*0*1(1, 2, or 3)******* Ta 40 C up to +55 CModels *7*0*1(4 or 5)******* Ta 20 C up to +55 C
- type - type of protection
*700(B, R, or E)1(1 or 2)(A, B, C, N, J, or K)*F**** 0575 II 2G Ex d[ib] IIB+H2 T6
II 2D Ex tD A21 IP66/IP67 T65 C
*700(B, R, or E)1(1 or 2)(A, B, C, N, J, or K)*Z**** 0575 II 2G Ex de[ib] IIB+H2 T6
II 2D Ex tD A21 IP66/IP67 T65 C
*700(B, R, or E)1(3, 4, or 5)(A, B, C, N, J, or K)*F**** 0575 II 2G Ex d[ib] IIC T6
II 2D Ex tD A21 IP66/IP67 T65 C
*700(B, R, or E)1(3, 4, or 5)(A, B, C, N, J, or K)*Z**** 0575 II 2G Ex de[ib] IIC T6
II 2D Ex tD A21 IP66/IP67 T65 C
*700(B, R, or E)1(1 or 2)(D, E, or G)*F**** 0575 II 2 (1) G Ex d[ia/ib] IIB+H2 T6
II 2D Ex tD A21 IP66/IP67 T65 C
*700(B, R, or E)1(1 or 2)(D, E, or G)*Z**** 0575 II 2 (1) G Ex de[ia/ib] IIB+H2 T6
II 2D Ex tD A21 IP66/IP67 T65 C
*700(B, R, or E)1(3, 4, or 5)(D, E, or G)*F**** 0575 II 2 (1) G Ex d[ia/ib] IIC T6
II 2D Ex tD A21 IP66/IP67 T65 C
*700(B, R, or E)1(3, 4, or 5)(D, E, or G)*Z**** 0575 II 2 (1) G Ex de[ia/ib] IIC T6
II 2D Ex tD A21 IP66/IP67 T65 C
*700(C, I, S, or D)1(1 or 2)(A, B, C, N, J, or K)*F**** 0575 II 2G Ex d[ib] IIB+H2 T5
II 2D Ex tD A21 IP66/IP67 T65 C
*700(C, I, S, or D)1(1 or 2)(A, B, C, N, J, or K)*Z**** 0575 II 2G Ex de[ib] IIB+H2 T5
II 2D Ex tD A21 IP66/IP67 T65 C
*700(C, I, S, or D)1(3, 4, or 5)(A, B, C, N, J, or K)*F**** 0575 II 2G Ex d[ib] IIC T5
II 2D Ex tD A21 IP66/IP67 T65 C
*700(C, I, S, or D)1(3, 4, or 5)(A, B, C, N, J, or K)*Z**** 0575 II 2G Ex de[ib] IIC T5
II 2D Ex tD A21 IP66/IP67 T65 C
*700(C, I, S, or D)1(1 or 2)(D, E, or G)*F**** 0575 II 2 (1) G Ex d[ia/ib] IIB+H2 T5
II 2D Ex tD A21 IP66/IP67 T65 C
*700(C, I, S, or D)1(1 or 2)(D, E, or G)*Z**** 0575 II 2 (1) G Ex de[ia/ib] IIB+H2 T5
II 2D Ex tD A21 IP66/IP67 T65 C
*700(C, I, S, or D)1(3, 4, or 5)(D, E, or G)*F**** 0575 II 2 (1) G Ex d[ia/ib] IIC T5
II 2D Ex tD A21 IP66/IP67 T65 C
*700(C, I, S, or D)1(3, 4, or 5)(D, E, or G)*Z**** 0575 II 2 (1) G Ex de[ia/ib] IIC T5
II 2D Ex tD A21 IP66/IP67 T65 C
-
Model 1700/2700/2750 Transmitters
ATEX Installation Instructions 7
5) Special conditions for safe use / Installation instructions
5.1) For the application of the transmitter in an ambient temperature of less than 20 C suitable cable and cable entries or conduit entries certified for this condition shall be used.
5.2) If certified conduit entries are used for the connection of the transmitter enclosure, the associated stopping boxes shall be installed immediately at the enclosure.
5.3) Addition for version *7*0*1(4 or 5) ** (Z or F) **** CEQ/ETO 12638 only:
Using a dry cloth to clean the display cover can cause static discharge, which could result in an explosion in an explosive atmosphere.To prevent an explosion, use a clean damp cloth to clean the display cover in an explosive atmosphere.
Model 1700/2700/2750 installation drawings
Figure 1: Model 1700/2700/2750 transmitter to remote core processor
I.S.cable See note 5.
VDC
+VD
C
I.S. 1700/2700/2750 outputs to core processor entity parameters
Vdc
Remote installation
(WARNING: SUBSTITUTIONS OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY)
Increased safety version:No DisplayEx de [ia/ib] IIC T5With DisplayIIB cover: Ex de [ia/ib] IIB + H2 T5IIC cover: Ex de [ia/ib] IIC T5
Refer to Model Number on 1700/2700/2750 transmitter tag for specific Hazardous Location
Flameproof version:No DisplayEx d [ia/ib] IIC T5With DisplayIIB cover: Ex d [ia/ib] IIB + H2 T5IIC cover: Ex d [ia/ib] IIC T5
This unit is provided with an internal and external terminal for supplementary bonding connection. This terminal is for use where local codes or authorities permit or require such connection.
For proper installation including I/O, power, gland and hazardous area
location, refer to appropriate 1700/2700/2750 output option ATEX-D-
IS installation instructions
RS48
5ARS
485b
COMBINE THIS DRAWING WITH ONE OF FIGURE 2, 3, 4, OR 5
1. The total Ci is equal to the sum of all Ci values of all devices on the network. Ccable is the total capacitance of all cable on the network.
2. The total Li is equal to the sum of all Li values of all devices on the network. Lcable is the total inductance of all cable on the network.
3. If the electrical parameters of the cable are unknown, then the following values may be used:Cable Capacitance = 197pF/mCable Inductance = 0,66H/m
4. This device must not be connected to any associated apparatus which uses or generates more than 250Vrms with respect to earth ground.
5. Maximum cable length determined by entity parameters and maximum cable inductance.
Installation notes:
Associated apparatus parameter limits
Reference no. EB-20003015 Rev. A
-
Model 1700/2700/2750 Transmitters
8 ATEX Installation Instructions
Figure 2: CMF sensor with enhanced core processor
Figure 3: CMF, D (except D600), DL, F, H, R, CNG and T sensors with core processor
COMBINE THIS DRAWING WITH FIGURE 1
I.S.cable
See note 5.
Hazardous Area Ex ib IIC / IIB
Refer to sensor tag for complete hazardous area classification.
Sensor mounted enhanced core processor
4-wire I.S. and non-incendive core processor entity parameters
Internal ground
Externalground
VdcVD
C +
VDC
R
S485
AR
S485
B
Reference no. EB-20003015 Rev. A
This unit is provided with an internal and external terminal for supplementary bonding connection. This terminal is for use where local codes or authorities permit or require such connection.
COMBINE THIS DRAWING WITH FIGURE 1
I.S.cable
See note 5.Hazardous Area EEx ib IIC / IIB
Refer to sensor tag for complete hazardous area classification.
Sensor mounted core processor
4-wire I.S. and non-incendive core processor entity parameters
Vdc
VDC
VDC+
This unit is provided with an internal and external terminal for supplementary bonding connection. This terminal is for use where local codes or authorities permit or require such connection.
Reference no. EB-3600583 Rev. F
5. Maximum cable length determined by entity parameters and maximum cable inductance.
5. Maximum cable length determined by entity parameters and maximum cable inductance.
-
Model 1700/2700/2750 Transmitters
ATEX Installation Instructions 9
Figure 4: D600 with core processor
Figure 5: Remote core processor with remote transmitter
Hazardous AreaEEx de [ib] IIB T4Refer to sensor and booster amplifier tags for complete hazardous area classification. Core
processor mounted on
sensor booster amplifier
4-wire I.S. and non-incendive core processor entity parameters
Vdc
VDC
VDC+
This unit is provided with an internal and external terminal for supplementary bonding connection. This terminal is for use where local codes or authorities permit or require such connection.
Maximum cable length determined by entity parameters and maximum cable inductance.
I.S.cable
Installation method Fitting required
Per EN6007914
Conduit EEx d IIB Conduit Seal
Cable EEx d IIB Cable GlandConduit or Cable Increased Safety EEx e
1/2"14 NPT or M20 1,5 adaptersupplied as ordered
Conduit Seal Required within 18" of enclosure. To besealed after wiring. (customer supplied)
Power
Ground chassis
To drive coil located in sensor
VAC
To achieve potential equalization the groundterminal must be connected to the appropriate
ground terminal within the hazardous areausing a potential equalizing line.
For remote mount booster amplifier wiring see drawing EB-1005122
Explosion-Proof housing
COMBINE THIS DRAWING WITH FIGURE 1
Reference no. EB-1005121 Rev. C
VDC +
Hazardous Area EEx ib IIB / IIC
Refer to remote core processor tag for complete hazardous area classification.
Ground screwBlack
9-wireIS cable
20 m. maximum cable length
Remote core processor
Maximum cable length determined by entity parameters and maximum cable inductance.
4-wireIS cable
VDC
RedGreenWhite
BlueGrayOrange
BrownViolet
Yellow
Ground screw
4-wire and non-incendive core processor entity parameters
Vdc
COMBINE THIS DRAWING WITH FIGURE 1 AND ALSO WITH ONE OF FIGURE 7, 8, OR 9
Reference no. EB-20001040 Rev. C
-
Model 1700/2700/2750 Transmitters
10 ATEX Installation Instructions
Figure 6: 1700/2700/2750 transmitter with integral core processor
COMBINE THIS DRAWING WITH ONE OF FIGURE 7, 8, OR 9
(WARNING: SUBSTITUTIONS OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY)
Ground screw
RedGreenWhite
Ground screw
BrownViolet
Yellow
BlueGrayOrange
Black
20 m. maximum cable length
Refer to Model Number on 1700/2700/2750 transmitter tag for specific hazardous location.
* Increased Safety version:No DisplayEx de [ia/ib] IIC T5With DisplayIIB cover: Ex de [ia/ib] IIB + H2 T5IIC cover: Ex de [ia/ib] IIC T5
* Flameproof version:No DisplayEx d [ia/ib] IIC T5With DisplayIIB cover: Ex d [ia/ib] IIB + H2 T5IIC cover: Ex d [ia/ib] IIC T5
For proper installation of I/O, power and ground terminals, refer to appropriate ATEXDIS installation drawing
9-wireIS
cable
Reference no. EB-20001048 Rev. C
-
Model 1700/2700/2750 Transmitters
ATEX Installation Instructions 11
Figure 7: CMF, D (except D600), DL, F, H, and T sensor with junction box
Figure 8: D600 with junction box
COMBINE THIS DRAWING WITH ONE OF FIGURE 5 OR 6
Refer to sensor tag for complete hazardous area classification
20 m. maximum cable length
9-wireIS
cable20 m. maximum
cable length
BlueGrayRed
Sensor junction box
VioletYellow
OrangeChassisground
Sensor junction box
Chassis ground
Refer to sensor tag for complete hazardous area classification
ModelD, DL
(EXCEPT D600)Supplied as intrinsically safe
ModelCMF T F H
Supplied as intrinsically safe
Hazardous AreaEEx ib IIB / IIC
Hazardous AreaEEx ib IIB / IIC
GreenWhiteBrown
9-wireIS
cable
BrnRedOrnYelGrnBluVioGryWht
Reference no. EB-20001048 Rev. C
Reference no. EB-1005123 Rev. B
Hazardous Area EExde [ib] IIB
Installation method Fitting required
Per EN6007914
Conduit EEx d IIB conduit seal
Cable EEx d IIB cable glandConduit or cable increased safety EEx e
Cable O.D. must be suitably sized to gland.Intrinsically safe
terminals
To achieve potential equalization the ground terminal mustbe connected to the appropriate ground terminal within the
hazardous area using a potential equalizing line.
Micro Motion mass flowmeter system connection for intrinsically safe operation
VioletYellow
Orange
GreenWhiteBrown
BlueGrayRed
1/2"14 NPT orM20 1.5 adapter supplied as ordered
Conduit seal required within 18" ofenclosure. To be sealed after wiring
(customer supplied).Power
Ground chassis
To drive coil located in
sensor
20 m maximum
cable length
IS cable
For remote mount booster amplifier wiring refer to EB-3007062.
CAUTION:To maintain intrinsic safety, the intrinsically safe wiring must be installed according to EN 60079-14. Transmitter and sensor must be properly grounded.
VAC
COMBINE THIS DRAWING WITH ONE OF FIGURE 5 OR 6
-
Model 1700/2700/2750 Transmitters
12 ATEX Installation Instructions
Figure 9: DT with junction box
Models: DT65, DT100, DT150
DT sensor wire terminations to IS cable
DT sensor wire # IS cable color1 Brown2 Red3 Orange4 Yellow5 Green6 Blue7 Violet8 Gray9 White
Hazardous AreaEEx ib IIb
9-wireIS
cable
20 m maximumcable length
Special conditions for safe use:For the sensor types DT065, DT100, and DT150 the following applies: The minimum medium temperature is +32 C.
DT sensor wires must be connected to IS cable using customer supplied terminal block and
junction box.
Earth ground
DT sensor wires
Micro Motion mass flowmeter system connection for intrinsically safe operation
COMBINE THIS DRAWING WITH ONE OF FIGURE 5 OR 6
Reference no. EB-20000081 Rev. B
-
Model 1700/2700/2750 Transmitters
ATEX Installation Instructions 13
Figure 10: Transmitter outputs (WARNING: SUBSTITUTIONS OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY)
Refer to Model Number on 1700/2700/2750 transmitter tag for specific hazardous location.
Increased safety version:No DisplayEx de [ib] IIC T5With DisplayIIB cover: Ex de [ib] IIB + H2 T5IIC cover: Ex de [ib] IIC T5
Flameproof version:No Display
Ex d [ib] IIC T5With DisplayIIB cover: Ex d [ib] IIB + H2 T5IIC cover: Ex d [ib] IIC T5
Note: Hazardous area classification on an integrally mounted 1700/2700/2750 transmitter can be limited by hazardous area classification of the sensor. Refer to sensor tag.
If the ambient temperature is40 C to 20 C, use cable and cable entries or conduit entries certified for this condition.If certified conduit entries are used, install the associated stopping boxes immediately at the sensor enclosure.
This unit is provided with an external terminal for supplementary bonding connection. This terminal is for use where local codes or authorities permit or require such connection.Equipment ground
(For temporary diagnostic use only)
VDCVAC
USP+USP
1
Model 1700/2700/2750 terminal configurationTerminal Analog
*700*1*A***Intrinsically safe*7*0*1*D***
Config I/O2700*1*B***
Fieldbus27*0*1*E*** or2700*1*N***
PROFIBUS-PA27*0*1*G***
1 I/O 1+ mA / HART + mA1 / HART + mA1 / HART + Channel A Fieldbus + PROFIBUS +2 I/O 1 mA / HART mA1 / HART mA1 / HART Channel A Fieldbus PROFIBUS 3 I/O 2+ FO + FO + mA2 / DO1 / FO + Channel B4 I/O 2 FO FO mA2 / DO1 / FO Channel B5 I/O 3+ RS-485 A mA2 + FO / DO2 / DI + Channel C6 I/O 3 RS-485 B mA2 FO / DO2 / DI Channel C
Model 1700/2700/2750 intrinsic safety parametersIntrinsically safe*7*0*1*D***
Fieldbus27*0*1*E*** or2700*1*N***
PROFIBUS-PA27*0*1*G***
Terminals1 & 2 and 5 & 6
Terminals 3 & 4 Terminals 1 & 2 Terminals 1 & 2
Vmax (Vdc) 30 30 33 33Imax (mA) 300 100 380 380Pmax (W) 1,0 0,75 5,32 5,32Ci (F) 0,0005 0,0005 Negligible NegligibleLi (H) 0,0 0,0 Negligible Negligible
2
3
4
5
6
-
Micro Motion Inc. USAWorldwide Headquarters7070 Winchester CircleBoulder, Colorado 80301T +1 303-527-5200
+1 800-522-6277F +1 303-530-8459
Micro Motion EuropeEmerson Process ManagementNeonstraat 16718 WX EdeThe NetherlandsT +31 (0) 318 495 555F +31 (0) 318 495 556
Micro Motion JapanEmerson Process Management1-2-5, Higashi ShinagawaShinagawa-kuTokyo 140-0002 JapanT +81 3 5769-6803F +81 3 5769-6844
Micro Motion AsiaEmerson Process Management1 Pandan CrescentSingapore 128461Republic of SingaporeT +65 6777-8211F +65 6770-8003
Micro Motion United KingdomEmerson Process Management LimitedHorsfield WayBredbury Industrial EstateStockport SK6 2SU U.K.T +44 0870 240 1978F +44 0800 966 181
2008, Micro Motion, Inc. All rights reserved. P/N MMI-20011705, Rev. A
*MMI-20011705*
For the latest Micro Motion product specifications, view the PRODUCTS section of our web site at www.micromotion.com
/ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False
/CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure false /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles false /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /DocumentCMYK /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /UseDocumentProfile /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice