AT9000 Advanced Transmitter SuperAceJTG Series Gauge Pressure Transmitter
JTG9S/W Model
OverviewThe AT9000 Advanced Transmitter is a smart transmitter which features a built-in microprocessor and outstanding stability. It is capable of measuring the flow rate, pressure, liquid level, etc. of gases, liquids, and vapors, outputting a 4 to 20 mA DC analog signal corresponding to the measured pressure.
Features(1) Outstanding long-term stability•Achievesanextremelyhighlevelofstability:zeropoint
drift of ±0.1 % in 10 years.
(2) Fast response•Responsespeed:100msorless.Canbeutilizedin
applications that require fast response, such as in those related to turbines.
(3) Outstanding usability•Zeroadjustmentcanbeperformedwithoutremovingthe
cover.
(4) A wide variety of functions•Usingacommunicator,historicalinformationregardingexcessivepressure,abnormaltemperature,etc.,canbechecked.
Product Usage Precautions•Thisproductisintendedforthegeneralindustrialmarket.
•Thisproductisnotsubjecttotheregulationspursuantto the Chinese electronic information product pollution control laws. However, if the product is used with semiconductor manufacturing equipment, special-purpose equipment for electronic devices, etc., it may in some cases be necessary to include documents and to mark the product in accordance the Chinese electronic information product pollution control laws. If necessary, please indicate this in advance to our sales department.
No. SS2-ATSG10-0100
1st edition
No. SS2-ATSG10-0100Azbil Corporation
2
SpecificationsMeasuring span/setting range/working pressure range:See Table 1.
Output signal:Analogoutput:4to20mADC
Communications: SFN,HART® HART®Version:5
Supply voltage/load resistance:DC12.5to45VDCFor communication with a communicator, load resistance of atleast250Ωisrequiredbetweenloops.Regardingsupplyvoltage and load resistance, see Figure 1.
Sealed liquid:Siliconeoil(regulartype),fluorineoil(foroxygenorchlorineuse)
Waterproof/dustproofstructure:IP66/IP67
Ambienttemperaturerange:• Normaloperatingrange: Forgeneral-purposeuse:-40to+85°C Forgeneral-purposeuse(withindicators):-25to+80°C Foroxygenorchlorineuse:-10to+75°C
• Operativelimitrange: Forgeneral-purposeuse:-50to+93°C Forgeneral-purposeuse(withindicators):-30to+85°C Foroxygenorchlorineuse:-40to+80°C Foroxygenorchlorineuse (withindicators):-30to+85°C
• TIISspecialexplosion-proofmodel: -20to+60°C(withoutindicators) -20to+55°C(withindicators)
Wettedparttemperaturerange:• Normaloperatingrange: Forgeneral-purposeuse:-40to+110°C Foroxygenorchlorineuse:-20to+75°C
• Operativelimitrange: Forgeneral-purposeuse:-50to+115°C Foroxygenorchlorineuse:-40to+80°C
• TIISspecialexplosion-proofmodel: -20to+60°C(withoutindicators) -20to+55°C(withindicators)
Transportandstoragetemperaturerange:Withoutindicators:-50to+85°CWithindicators:-25to+80°CMeter body cover PVC:-10to+60°C
Ambienthumiditylimits:5to100%RH
Supplyvoltage/voltagecharacteristics:±0.005%FS/VEMC regulation compliance:EN61326-1:2013
IEC61326-2-3Lightning protection characteristics (surge immunity test, IEC61000-4-5) Line-to-line(S+,S-):±1kV Line-to-ground(S+,S-):±2kV Waveform:1.2/50(8/20)µs
Response time: 100msorless(ambienttemperature23±2°C)
Long-termstability(zeropoint):±0.1 %/10 years (JTG940 Model)±0.2%/10years(JTG960/980 Model) Drift under standard operating conditions (23±2°C,atmosphericpressure)Damping time constant:Settable to 10 levels in range 0 to 32 s(HART®communicationprotocolcanbesetinrange0to128s)
Output saturation point: Highlimit:21.6mA Lowlimit:3.6mA
Vibrationcharacteristics: Amplitude:1.5mm/frequency:5to9Hz Acceleration:4.9m/s2(0.5G)/9to200Hz
Shockcharacteristics:Acceleration9.8m/s2 (1 G)
Process pipe connection: Rc1/2internalthread,Rc1/4internal thread,1/2NPTinternalthread, 1/4NPTinternalthread
Electrical conduit connection: G1/2internalthread,1/2NPT internal thread, M20 internal thread
Body material Mainunit:SUS316 Transmittercase:aluminumalloy
Process wetted material: Meter body cover: SCS14A(SUS316equivalent)or
SUSF316,PVC Adapterflange(optional):SCS14A(SUS316equivalent),
PVC Wettedpartofmainunit:SUS316(diaphragm-only
SUS316L),alloyC-276, tantalum,SUS316L
Ventsandplugs:SUS316,PVC Gasketsforwettedpart:FEP
Table 1. Measuring Span/Setting Range/Working Pressure Range (for negative pressure in the working pressure range, see Figures 2 and 3) / overload resistance value
Model No. Measuring Span Setting Range Working Pressure Range Overload Resistant ValueJTG940 35to3500kPa -100to+3500kPa 2.0to3500kPa(Note1) 5250kPaJTG960 0.7to14MPa -0.1to+14MPa 2.0to14MPa(Note2) 21MPaJTG980 0.7to42MPa -0.1to+42MPa 2.0to42MPa(Note3) 63MPa
Notes1: IfmeterbodycovermaterialisPVC(polyvinylchloride),maximumworkingpressureisthesmallerof1.5MPaabsand the working pressure range.
2: IfboltandnutmaterialisSUS304,maximumworkingpressureis10MPa. 3: IfboltandnutmaterialisSUS304,maximumworkingpressureis20MPa.
No. SS2-ATSG10-0100Azbil Corporation
3
Load
Res
istan
ce R
(Ω)
Supply Voltage E (V DC)
E - 12.5
0.0219R=
1345
1482
245
0 17.9 42 4512.5
Operative Limit Range
Normal Operating Range
Note:For communication with the communicator, load resistance of at least 250 Ω is required.
-50 -40 40 50 60 70 80 90 100 115
1.3
2.0
5.7
9.6
16
78
101.3
133.3
Wor
king
Pre
ssur
e P
(kPa
abs
.)
3.4
27
46
Operative Limit Range
Normal Operating Range
Unusable Range
Temperature (°C) 110
-10 40 75-40
54
101.3
Operative Limit Range
Liquid Temperature (°C)0 80
133.3
Normal Operating Range
Wor
king
Pre
ssur
e P
(kPa
abs
.)
Unusable Range
93
Operative Limit Range
Figure 1. Supply Voltage and Load Resistance Characteristics
Figure 2. Wetted Parts Working Pressure and Temperature (General Purpose)
Figure 3. Wetted Parts Working Pressure and Temperature (for Oxygen/Chlorine)
Boltandnutmaterial(formeterbodyfastening):Carbonsteel(SNB7),SUS304,SUS630
Finish: Standard:Bakedacrylicresincoatingfinish Corrosion-prooffinish:Urethanebakedfinish Standardcolor:Casecover:AzbilBold2.5R2.25/5,
silverN-8.2 Case:SilverN-8.2
Built-inindicators:Digital LCD indicators (optional)Engineering unit scale display compatibleCanbesettoavalueintherange-19999to+19999(4.5digits).Specify the following when issuing engineering unit scale commands.•Metercalibrationrange•Engineeringunitscale•ProportionalorsquarerootdisplayAll data setting operations are performed from the communicator.
Failure mode: The following can be selectedUpscale:21.6mA(110%)orhigherDownscale:3.6mA(-2.5%)orlower
Grounding: Dclass(resistance:lowerthan100ohms)
Installation:Mountonhorizontalonvertical2-inchdia.pipe (direct attachment to process pipe also possible)
Mass: Approx.3.7kg(JTG940/960S) Approx.6.3kg(JTG980S) For JTG9W,+1.0kg
No. SS2-ATSG10-0100Azbil Corporation
4
Explosion-proof StructureTIISspecialexplosion-proofmodel(ExdIICT4)Note:Usecableswiththemaximumallowabletemperatureshownbelow.JTG9xxS:65°C(withindicators)
70°C(withoutindicators)JTG9xxW:60°C(withindicators)
65°C(withoutindicators)
OptionsExternalzeroadjustmentfunction:On-sitezeroadjustmentofthetransmittercanbeperformedusing the included magnetic bar.Note:Besuretousethisinconjunctionwiththeindicators.
Long vent drain:Maintenance, process conditions, and safety are addressed byusingadrainwhoselength(60mm)islongerthanthestandardlength(27mm).
Elbow:An adapter for changing the orientation of the electrical conduitconnectionportfromhorizontaltoverticalinordertofittheon-sitewiringconditions.Eitheroneortwocanbeselected as necessary.
High-grademoisture-free(includingoil-freefinish):Shipped with water content and oil content removed from the wetted part. (A small amount of fluorine oil is applied to vent/drain plugs in order to prevent sticking.)
Moisture-freefinish(incl.oil-freefinish):Shipped with water content and oil content removed from the wetted part (including the vent/drain plugs).
Oil-freefinish:Shipped with oil content removed from the wetted part. (A small amount of fluorine oil is applied to vent/drain plugs in order to prevent sticking.)
Highperformancetype:Has improved accuracy and ambient temperature performance.
Electricpowerspecification:Applicable in cases in which particularly strict quality control is required, as in the electric power and gas industries.Stabilitytestsunderhighstaticpressure,confirmationtestsof differential pressure gauge input-output characteristics under high-speed static pressure variation, and the like are performed.
Specialfailuremode(3.2mA):failure mode output values (low limit) during abnormal conditionswillbe3.2mA(-5%)orlower.
Variableoutputsaturationpoint:canbesetwithinthefollowingrange:12mA(50%)≤outputhighlimit≤21.6mA(110%)3.6mA(-2.5%)≤outputlowlimit<12mA(50%)Notes:RegardingtheHART®communicationprotocol
1.OptionJ8:When"Specialfailuremode3.2mA"isselected,3.2mA(-5%)≤outputlowerlimit <12mA(50%).
2.OptionJ8:When"Specialfailuremode3.2mA"isnotselected,3.8mA(-1.25%)≤outputlowerlimit <12mA(50%).
Testreport:Shows the results of having tested the appearance, input-output characteristics, insulation resistance, dielectric strength, etc., of the transmitter.
Millsheet:Shows data related to the chemical composition, heat treatment condition, and mechanical properties of the wetted part material.
Strengthcalculationsheet:Shows the results of having calculated the strength of the meter body cover, flanges, and bolts.
Withstandpressureandairtighttest(general-purposeuse):Shows the results of the wetted part withstand pressure test(waterpressure:10minutes)andairtighttest (N2:10minutes).
Testreport(withtraceabilitycertificate):Comprisedofthreedocuments:atraceabilitydiagram, acalibrationcertificate,andatestreport.
No. SS2-ATSG10-0100Azbil Corporation
5
Product Usage PrecautionsBear in mind the following points when using the product in order to take full advantage of its capabilities. Also be sure to read the operating instructions for the product before use.
Installation Precautions
Warning
•Wheninstallingtheproduct,makesurethatthegasketsdo not stick out at the connections with the process (connections between adapter flanges and connecting pipes and flanges). There is a danger that the measured fluid will leak out and cause scalding and other harmful health effects. If the measured fluid is harmful to the human body, take safety measures such as wearing goggles or a mask so that it does not contact the skin or the eyes, become inhaled, etc.
•Use thisproductwithin the limitsof thedescribedusageconditions (explosionproofing,pressure rating,temperature, humidity, voltage, vibration, shock, installation orientation, ambient atmosphere, and the like). There is a danger of scalding and other harmful healtheffectsasaresultofinstrumentfailure,fire,etc.
•Whenworkinginahazardousarea,performinstallationand deployment according to the construction methods prescribedbythehazardguidelines.
In addition, with the TIIS flameproof model, for flameproof packing cable wiring system, be sure to use flameproofcableglandscertifiedbythiscompany.
Caution
•Afterinstallingthisproduct,donotuseitasascaffold,place your body weight on it, etc. Doing so may cause damage to the product.
•Becarefulnottostriketheglassportionofthedisplaywith tools, etc. The glass can become damaged, and injuriescanoccur.
•Asthisproductisextremelyheavy,wheninstallingitexercisecareregardingscaffolding,andbesuretowearsafety shoes.
•Thisproductisaprecisioninstrument.Besuretoavoidsubjectingittoshock.Shockmaydamagetheproduct.
Wiring Precautions
Warning
•Donotperformwiringwork,turnontheelectricity,etc., when your hands are wet. There is a risk of electric shock.
Caution
•Besuretothoroughlycheckthespecificationstoensurethat the wiring is carried out correctly. Incorrect wiring can cause instrument damage or malfunctions.
•Supplypowercorrectlybasedonthespecifications.Inputting an incorrect power supply can damage the instrument.
•Useapowersupplyforthisproductwhichhasovercurrent protection capability.
Usage Precautions for HART® Devices•Ifoperationusingasecondaryhost(HART®
Communicator, etc.) is necessary, set the communication interval of the primary host (distributed control system, devicemanagementsystem,etc.)to8secondsorlonger,or terminate communication from the primary host before using the secondary host. If the primary host repeatsHART®communicationbefore8secondshaveelapsed, the secondary host may not receive the request (i.e., may not be able to communicate).
•If,asaresultoftheeffectsofelectricalnoiseintheinstallationenvironment,HART®communicationwiththe host is not possible, take countermeasures such as distancing the signal cable from the noise sources, re-evaluating the grounding conditions, and changing the signalcabletoashieldedcable.However,evenifHART®communication is not possible due to noise, control by the 4 to 20 mA analog signal will not be affected.
•Whenusingthisproductinmultidropmode,thereisalimit to the number of units which can be used. If using multidrop, please consult our representative for more details.
No. SS2-ATSG10-0100Azbil Corporation
6
Performance SpecificationsTheperformancespecifications(accuracy/temperaturecharacteristics/staticpressurecharacteristics)showtheabsolutevaluesofthelowerrangevalue(LRV)*1andupperrangevalue(URV)*2ofthecalibrationrange,aswellasthemaximumvalueχinthe span. The value relative to the span is as follows.(Span-relatedvalue)=(χ-relatedvalue)×(χ)/(span)
JTG940 (General Purpose, Wetted Part Material: SUS316)
Accuracy *3 ±0.1 %±(0.025+0.075×140
χ ) %(χ≥140kPa)(χ<140kPa)
Temperaturecharacteristics*(Shift from the set range) 30°Cchange *3
Combinedshift:(incl.zero/spanshift)
±0.44 %±(0.19+0.25×350χ ) %
(χ≥350kPa)(χ<350kPa)
JTG940 (Option "J1", Wetted Part Material: SUS316)
Accuracy *3 ±0.04 %±(0.008+0.032×350χ ) %
(χ≥350kPa)(χ<350kPa)
Temperaturecharacteristics*(Shift from the set range) 30°Cchange *3
Combinedshift:(incl.zero/spanshift)
±0.15%±(0.075+0.075×350χ ) %
(χ≥350kPa)(χ<350kPa)
JTG940 (for Oxygen, for Chlorine / Wetted Part Material: SUS316)
Accuracy *3 ±0.075%±0.1 %±(0.025+0.075×140.0
χ ) %
(χ≥1750kPa)(1750kPa>χ≥140kPa)(χ<140kPa)
Temperaturecharacteristics*(Shift from the set range) 30°Cchange *3(-5to+55°Crange)
Combinedshift:(incl.zero/spanshift)
±0.44 % ±(0.19+0.25×350χ ) %
(χ≥350kPa)(χ<350kPa)
JTG940 (General Purpose, for Oxygen, for Chlorine / Wetted Part Material: C-276, Tantalum, SUS316L)
Accuracy *3 ±0.15%±(0.05+0.1×350χ ) %
(χ≥140kPa)(χ<140kPa)
Temperaturecharacteristics*(Shift from the set range) 30°Cchange *3(-5to+55°Crange)
Combinedshift:(incl.zero/spanshift)
±0.85%±(0.35+0.5×350χ ) %
(χ≥350kPa)(χ<350kPa)
JTG960 (General Purpose, for Oxygen, for Chlorine / Wetted Part Material: SUS316)
Accuracy *3 ±0.1 % ±(0.05+0.05× 2.1
χ) %
(χ≥2.1MPa)(χ<2.1MPa)
Temperaturecharacteristics*(Shift from the set range) 30°Cchange *3
Combinedshift:(incl.zero/spanshift)
±0.41 % ±(0.18+0.23×3.5
χ) %
(χ≥3.5MPa)(χ<3.5MPa)
Notes:*1:URVisthemeasuredvaluewhen100%(20mADC)isoutput. *2:LRVisthemeasuredvaluewhen0%(4mADC)isoutput. *3:RangeisURV≥0,LRV≥0
No. SS2-ATSG10-0100Azbil Corporation
7
JTG960 (for Oxygen, for Chlorine / Wetted Part Material: Alloy C-276, Tantalum, SUS316L)
Accuracy *3 ±0.15%±(0.05+0.1× 2.1
χ ) %(χ≥2.1MPa)(χ<2.1MPa)
Temperature characteristics(Shift from the set range) 30°Cchange
(-5to+55°Crange)
Combinedshift:(incl.zero/spanshift)
±0.85%±(0.35+0.5× 3.5χ ) %
(χ≥3.5MPa)(χ<3.5MPa)
JTG980 (General Purpose, for Oxygen, for Chlorine / Wetted Part Material: SUS316)
Accuracy *3 ±0.1 %±(0.05+0.05× 7
χ ) %(χ≥7MPa)(χ<7MPa)
Temperature characteristics(Shift from the set range) 30°Cchange *3(-5to+55°Crange)
Combinedshift:(incl.zero/spanshift)
±0.41 %±(0.18+0.23× 7
χ ) %(χ≥7MPa)(χ<7MPa)
JTG980 (General Purpose, for Oxygen, for Chlorine / Wetted Part Material: Alloy C-276)
Accuracy *3 ±0.15%±(0.05+0.1× 7
χ ) %(χ≥7MPa)(χ<7MPa)
Temperature characteristics(Shift from the set range) 30°Cchange *3(-5to+55°Crange)
Combinedshift:(incl.zero/spanshift)
±0.85%±(0.35+0.5× 7
χ ) %(χ≥3.5MPa)(χ<3.5MPa)
Notes:*1:URVisthemeasuredvaluewhen100%(20mADC)isoutputted *2:LRVisthemeasuredvaluewhen0%(4mADC)isoutputted *3:RangeisURV≥0,LRV≥0
No. SS2-ATSG10-0100Azbil Corporation
8
Model number configuration tableFor Low Pressure/for Standard Pressure
4 to 20 mA DC (standard)Digital output (DE protocol) Note 14 to 20 mA DC (HART® communication)
G 1/2, water-tightG 1/2, TIIS special explosion-proof model with 1 cable gland attachedG 1/2, TIIS special explosion-proof model with 2 cable glands attached1/2 NPT, non-explosion-proofNo meterDigital meter linear scale (0 to 100 %)Digital meter engineering unit scaleStandard corrosion-proo�ngHeavy corrosion-proo�ngSilver paint (standard corrosion-proo�ng)Silver paint (heavy corrosion-proo�ng)NoneUpscaleDownscaleNoneCarbon steel (square)SUS304 (square)CF8 (SUS304 equivalent, round)
Mounting bracket
X127
Failure modeXUD
Corrosion-resistant �nish
XBCD
IndicatorsX12
Electrical connection / explosion-proof
X23A
No optionsExternal zero adjustment Note 5Long vent drainFor mounting a high load resistance smart meterElbow x 1 (le�)Elbow x 1 (right)Elbow x 2Moisture-free (incl. oil-free) �nishMoisture-free (incl. oil-free) �nish, high-gradeOil-free �nishHigh performance type Note 6Electric power speci�cationSpecial failure mode (3.2 mA)Variable output saturation pointTest reportMill sheetStrength calculation sheetWithstand pressure and air tight test (general-purpose use)Test report (with traceability certi�cate)Other
X XA 2A 5B 7G 1G 2G 3D 1E 6D 2J 1J 2J 8K 9T 1T 2T 5T 6T 8
123
ABCFGHLMNRST
125
EFHKP
135
Rc 1/2, process upper portionRc 1/2, process lower portionRc1/2, process side portion1/2 NPT internal thread, process upper portion1/2 NPT internal thread, process lower portion1/2 NPT internal thread, process side portionRc 1/4, process upper portionRc 1/4, process lower portionRc 1/4, process side portion1/4 NPT internal thread, process upper portion1/4 NPT internal thread, process lower portion1/4 NPT internal thread, process side portionCarbon SteelSUS304 Note 4SUS630
Regular type (silicone oil)For oxygen service (�uorine oil)For chlorine service (�uorine oil) Note 3
SUS316Alloy C-276TantalumSUS316LTantalum
Main unit:Wetted part
SUS316SUS316SUS316SUS316PVC
Vent /drain plugs
SCS14ASCS14ASCS14ASCS14APVC
Meter bodycover
Bolts and nutsmaterial
Process connection
Sealed liquid
Note 2Note 2Note 2Note 2
Process Wetted Material
Output/communication
format
JTG940SJTG940W (with external terminal box)JTG960SJTG960W (with external terminal box)
35 to 3500 kPa
0.7 to 14 MPa
Measuring span
OptionsAdditional SelectionsSelectionsBasic Model No.
Note 1: Cannot be combined with Failure mode "None," variable output saturation point, or external zero adjustment.Note 2: Meter body cover material: SCS14A (SUS316 equivalent) or SUSF316.Note 3: For wetted part of main unit, only "tantalum" can be selected.Note 4: Cannot be used with JTG960S/W. Maximum working pressure: 1.5 MPa. Bolt and nut material
is SUS304.Note 5: Be sure to select indicators.Note 6: Model JTG940S/W only.
No. SS2-ATSG10-0100Azbil Corporation
9
For High Pressure
Note 1: Cannot be combined with Failure mode "None," variable output saturation point, or external zero adjustment.
Note 2: Be sure to select indicators.
G 1/2, water-tightG 1/2, TIIS special explosion-proof model with 1 cable gland attachedG 1/2, TIIS special explosion-proof model with 2 cable glands attached1/2 NPT, non-explosion-proofNoneDigital meter linear scale (0 to 100 %)Digital meter engineering unit scaleStandard corrosion-proo�ngHeavy corrosion-proo�ngSilver paint (standard corrosion-proo�ng)Silver paint (heavy corrosion-proo�ng)NoneUpscaleDownscaleNoneCarbon steel (square)SUS304 (square)CF8 (SUS304 equivalent, round)
Mounting bracket
X127
Failure modeXUD
Corrosion-resistant �nish
XBCD
IndicatorsX12
Electrical connection / explosion-proof
X23
123
A
No optionsX XA 2A 5B 7G 1G 1G 3D 1E 6D 2J 2J 8K 9T 1T 2T 5T 6T 8
External zero adjustment Note 2Long vent drainFor mounting a high load resistance smart meterElbow x 1 (le�)Elbow x 1 (right)Elbow x 2Moisture-free (incl. oil-free) �nishMoisture-free (incl. oil-free) �nish, high-gradeOil-free �nishElectric power speci�cationSpecial failure mode (3.2 mA)Variable output saturation pointTest reportMill sheetStrength calculation sheetWithstand pressure and air tight test (general-purpose use)Test report (with traceability certi�cate)Other
ABFGLMRS
12
EF
135
Regular type (silicone oil)For oxygen service (�uorine oil)Rc 1/2, process upper portionRc 1/2, process lower portion1/2 NPT internal thread, process upper portion1/2 NPT internal thread, process lower portionRc 1/4, process upper portionRc 1/4, process lower portion1/4 NPT internal thread, process upper portion1/4 NPT internal thread, process lower portionCarbon steelSUS304SUS630
SUS316Alloy C-276
Wetted part of main unit
SUS316SUS316
Vent/drain plugs
SUSF316SUSF316
Meter body cover
4 to 20 mA DC (standard)Digital output (DE protocol) Note 14 to 20 mA DC (HART® communication)
Bolt and nut material
Process connection
Sealed liquid
Process Wetted Material
Output /communication
format
JTG980S
JTG980W (with external terminal box)
0.7 to 42 MPaMeasuring span
OptionsAdditional SelectionsSelectionsBasic Model No.
No. SS2-ATSG10-0100Azbil Corporation
10
DimensionsJTG 940S/960S (Upper/Lower Connection)
Round Bracket
Square Bracket
External zero adjustment
(optional)
Electrical conduit connection port
Terminal Connection Diagram
(terminal screw size: M4)
Indicators
(optional)
Electrical conduit connection port
Approx. 6
210 if indicators included
206 if indicators included
265 if indicators included
261 if indicators not included
265 if indicators included
261 if indicators not included
M4 terminal screwfor grounding
Process connection port
4 × M8, depth: 8
Installation dimensions without mounting bracket
Units: mm
When using long vent / drain plug
No. SS2-ATSG10-0100Azbil Corporation
11
JTG 940S/960S (Side Connection)
Round Bracket
Square Bracket
External zero adjustment
(optional)
Electrical conduit connection port
Terminal Connection Diagram
(terminal screw size: M4)
M4 terminal screwfor grounding
4 x M8, depth: 8
Installation dimensions without mounting bracket
Units: mm
See speci�cations
Electrical conduit connection port
See speci�cations
Process connection port
See speci�cations
Indicators
(optional)
approx. 166
210 if indicators included
206 if indicators not included
265 if indicators included
261 if indicators not included
265 if indicators included
261 if indicators not included
No. SS2-ATSG10-0100Azbil Corporation
12
JTG 980S (Upper/Lower Output)
Round Bracket
Square Bracket
Units: mm
External zero adjustment
(optional)
Terminal Connection Diagram
(terminal screw size: M4)Electrical conduit connection port
See speci�cations
Electrical conduit connection port
See speci�cations
M4 terminal screwfor grounding
Process connection port See speci�cations
4 x M8, depth: 8
Installation dimensions without mounting bracket
Indicators
(optional)
approx. 178
223 if indicators included219 if indicators not included
278 if indicators included274 if indicators not included
278 if indicators included274 if indicators not included
When using long vent / drain
plug
No. SS2-ATSG10-0100Azbil Corporation
13
JTG 980S (Side Connection)
Round Bracket
Square Bracket
External zero adjustment
(optional)
Electrical conduit connection port
Electrical conduit connection port
See speci�cations
M4 terminal screwfor grounding
4 x M8, depth: 8
Installation dimensions without mounting bracket
Units: mm
Terminal Connection Diagram
(terminal screw size: M4)
See speci�cations
approx. 178
278 if indicators included
274 if indicators not included
223 if indicators included
219 if indicators not included
278 if indicators included
274 if indicators not included
Indicators
(optional)
Process connection port
See speci�cations
No. SS2-ATSG10-0100Azbil Corporation
14
JTG 940S/960S (Tantalum, SUS316L)
Upper/Lower ConnectionExternal zero adjustment
(optional)
Electrical conduit connection port
Terminal Connection Diagram
(terminal screw size: M4)
See speci�cations
Electrical conduit connection port
See speci�cations
Process connection port
See speci�cations
4 x M8 depth: 8
Installation dimensions without mounting bracket
Units: mmM4 terminal screw
for grounding
approx. 1662B pipe
210 if indicators included206 if indicators included
277 if indicators included273 if indicators included
Indicators
(optional)
External zero adjustment
(optional)
Electrical conduit connection port
Terminal Connection Diagram
(terminal screw size: M4)
See speci�cations
Electrical conduit connection port
See speci�cations
Process connection port
See speci�cations
4 x M8, depth: 8
Installation dimensions without mounting bracket
M4 terminal screwfor grounding
approx. 1662B pipe
210 if indicators included206 if indicators not included
277 if indicators included273 if indicators not included
Indicators
(optional)
When using long vent / drain
plug
No. SS2-ATSG10-0100Azbil Corporation
15
JTG 940S/960S (Cover Material: PVC)
Units: mm
External zero adjustment
(optional)
Electrical conduit connection port
Terminal Connection Diagram
(terminal screw size: M4)
See speci�cations
Electrical conduit connection port
See speci�cations
M4 terminal screwfor grounding
Process connection port
See speci�cations
4 x M8, depth: 8
Installation dimensions without mounting bracket
Indicators
(optional)
2B pipe
(277 if indicators included)
(273 if indicators not included)
210 if indicators included206 if indicators not included
No. SS2-ATSG10-0100Azbil Corporation
16
JTG 940W/960W (Upper/Lower Connection)
Round Bracket
Square Bracket
Terminal Connection Diagram
(terminal screw size: M4)
Process connection port
See speci�cations
4 x M8, depth: 8
Installation dimensions without mounting bracket
Units: mm
M4 terminal screwfor grounding
Indicators
(optional)
External zero adjustment
(optional)
306 if indicators included
302 if indicators not included
306 if indicators included
302 if indicators not included
Electrical conduit connection port
See speci�cations
Electrical conduit connection port
See speci�cations
When using long vent / drain
plug
No. SS2-ATSG10-0100Azbil Corporation
17
JTG 940W/960W (Side Connection)
Round Bracket
Square Bracket
Terminal Connection Diagram
(terminal screw size: M4)
4 x M8, depth: 8
Installation dimensions without mounting bracket
Units: mm
M4 terminal screwfor grounding
Indicators
(optional)Electrical conduit connection port
See speci�cations
Electrical conduit connection port
See speci�cations
External zero adjustment
(optional)
Process connection port
See speci�cations
306 if indicators included
302 if indicators not included
306 if indicators included
302 if indicators not included
No. SS2-ATSG10-0100Azbil Corporation
18
JTG 980W (Upper/Lower Connection)
Round Bracket
Square Bracket
Terminal Connection Diagram
(terminal screw size: M4)
M4 terminal screwfor grounding
Process connection port See speci�cations
4 x M8, depth: 8
Installation dimensions without mounting bracket
Units: mm
Indicators(optional)
External zero adjustment
(optional)
Electrical conduit connection port
See speci�cations
Electrical conduit connection port
See speci�cations
319 if indicators included
315 if indicators not included
319 if indicators included
315 if indicators not included
When using long vent / drain
plug
No. SS2-ATSG10-0100Azbil Corporation
19
JTG 980W (side connection)
Round Bracket
Square Bracket
Terminal Connection Diagram
(terminal screw size: M4)
M4 terminal screwfor grounding
Indicators (optional)Electrical conduit
connection port See speci�cations
Electrical conduit connection port
See speci�cations
External zero adjustment(optional)
Process connection port
See speci�cations
Installation dimensions without mounting bracket
Units: mm
4 x M8 depth: 8
319 if indicators included
315 if indicators not included
319 if indicators included
315 if indicators not included
No. SS2-ATSG10-0100Azbil Corporation
20
JTG 940W/960W (Tantalum, SUS316L)
Side Connection
Upper/Lower Connection
Terminal Connection Diagram
(terminal screw size: M4)
M4 terminal screw
for grounding
Process connection port
See speci�cations
Installation dimensions
without mounting bracket
Units: mm 4 x M8, depth: 8
Electrical conduit connection port
See speci�cations
Electrical conduit connection port
See speci�cations
External zero adjustment
(optional)
External zero adjustment
(optional)
2B pipe
2B pipe
4 x M8, depth: 8
Installation dimensions without mounting bracket
Terminal Connection Diagram
(terminal screw size: M4)
M4 terminal screw
for grounding
Process connection port
See speci�cations
Process connection port
See speci�cations
Electrical conduit connection port
See speci�cations
When using long vent / drain
plug
No. SS2-ATSG10-0100Azbil Corporation
21
JTG 940W/960W (Case Cover Material: PVC)
Terminal Connection Diagram
(terminal screw size: M4)
M4 terminal screwfor grounding
4 x M8, depth: 8
Installation dimensions without mounting bracket
Units: mm
Process connection port
See speci�cations
External zero adjustment
(optional)
2B pipe
Electrical conduit connection port
See speci�cations
Electrical conduit connection port
See speci�cations
Indicators
(optional)
No. SS2-ATSG10-0100Azbil Corporation
22
No. SS2-ATSG10-0100Azbil Corporation
23
No. SS2-ATSG10-0100Azbil Corporation
24
Please read the "Terms and Conditions" from the following URL before ordering or use:
http://www.azbil.com/products/bi/order.html
(10)
1-12-2 Kawana, FujisawaKanagawa 251-8522 Japan
Specifications are subject to change without notice.
No part of this publication may be reproduced or duplicated without the prior written permission of Azbil Corporation.
http://www.azbil.com/1st edition: May 2015