1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19-21, 2010 NIST Conference Center, Gaithersburg, MD, USA Jeongje Park and Jaeseok Choi Gyeongsang National University, Korea Mohammad Shahidehpour Illinois Institute of Technology, USA Roy Billinton University of Saskatchewan , Canada

Upload: others

Post on 20-Mar-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

1

Assessment of CO2 Reduction by Renewable Energy Generators

IEEE PES Conference on Innovative Smart Grid TechnologiesJanuary 19-21, 2010

NIST Conference Center, Gaithersburg, MD, USA

Jeongje Park and Jaeseok Choi

Gyeongsang National University, Korea

Mohammad Shahidehpour

Illinois Institute of Technology, USA

Roy Billinton

University of Saskatchewan , Canada

Page 2: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

2

Contents

Click to add Title1 Introduction1

Click to add Title2 Power Output Model of SCG2

Click to add Title1 Solar Radiation Model3

Click to add Title2 Reliability Evaluation and CO2 Reduction Assessment of SCG

4

Click to add Title1 Case Studies5

Click to add Title2 Conclusion6

Page 3: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

3

1. Introduction

The application of renewable energy in electric power systems is growing rapidly due to its advantages that are minimal pollution, non-depletion and low operating cost.

The proposed method can be used for reliability evaluationof power system including SCG. The use of convolution integral in order to construct the ELDC considering the multi-state model of the SCG

It is possible not only to evaluate of reliability of power system but also to calculate the reduction of CO2 using the proposed method.

Page 4: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

4

2. Power Output Model of SCG

Solar Radiation [W/m2]0 100 200 300 400 500 600 700 800 900 1000

++++++++++++++++++

+

+

0.00

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

Eff.

[%]

25 Deg. C

35 Deg. C

45 Deg. C+

Rc Solar radiation [W/m2]

Eff.

[%]

(G ) G , 0 G RR

, R G

cpv bi bi bi c

c

c c bi

Eff η

η

= ≤ <

= ≤

Page 5: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

5

2P (G ) (G ), 0 G RR

G , R G G P , G G

cbi bi bi bi c

c

c bi c bi std

sn bi std

η

η

= ≤ <

= < ≤= >

Where,Ppv: Solar radiation-to-energy conversion function

of the SCG [MW] Rc: A certain radiation point set as 150W/m2

Gstd: Solar radiation in the standard environment set as 1,000W/m2

Rc G[W/m2]

Ppv[pu·W]

Gstd

Page 6: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

6

3 . Solar radiation model

0 200 400 600 800 1000 12000

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.6

Solar radiation[ W/ m2]

Prob

abilit

y

0.5

0.55

The solar radiation pdf at Jeju Island for ten years (1998-2007)

Page 7: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

7

0 1000

0.002

0.004

0.006

0.008

Solar radiation[ W/ m2]

Prob

abilit

y

0.5

200 300 400 500 600 700 800 900 1000 0 1000

0.002

0.004

0.006

0.008

0.01

0.4

Solar radiation[ W/ m2]

Prob

abili

ty

1000900800700600500400300200

0 1000

0.002

0.004

0.006

0.008

0.01

0.012

0.5

Solar radiation[ W/m2]

Prob

abilit

y

1000900800700600500400300200 0 100 200 300 400 500 6000

0.002

0.004

0.006

0.8

Solar radiation[ W/ m2]

Prob

abili

ty 0.008

0.798

Solar radiation pdf model in March Solar radiation pdf model in June

Solar radiation pdf model in September Solar radiation pdf model in December

Page 8: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

8

The typical pattern of the solar radiation pdf model

Probability

Solar radiation[W/m2]

Page 9: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

9

0 1000 2000 3000 4000 5000 6000 7000 8000 90000

200

400

600

800

1000

Time[hours]

Sola

r rad

iatio

n[W

/m2 ]

Solar Radiation at Jinju 2007

Page 10: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

10

0 200 400 600 800 1000 1200

10- 3

10- 2

10- 1

Solar radiation[ W/m2]

Loga

rithm

Pro

babi

lity

0.5

Page 11: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

11

0 200 400 600 800 1000 12000

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

Solar radiation[W/m2]

Pro

babi

lity

Page 12: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

12

4. Reliability Evaluation of SCG

( , )n nP PB

1 1( , )P PB2 2( , )P PB3 3( , )P PB

Ppv[pu.W]

RC Gstd Solar radiation[W/m2]

Probability

Solar radiation[W/m2]

PDF Table of SCG multi-state model

Power Probability

P1P2···

Pn

PB1PB2

···

PBn

Page 13: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

13

LOLE EENS

[MW]

T

Lp+IC0

Lp

iΦΦ0

IC

Time : The convolution integral operator

Φ0: Original inverted load duration curve (ILDC)

x: Random variable of Φ NS: The total number of statesfoi: The outage capacity pdf of

generator iQkj: Forced outage rate (FOR) of

generator k at state jCkj: Outage capacity of generator k

at state j

-1

NS NS

-1 -1=1 =1

=

= (1- q ) ( ) + q ( - C )

j j oj

kj j kj j kjk k

f

x x

Φ Φ ⊗

Φ Φ∑ ∑

Jeongje Park, Wu Liang, Jaeseok Choi, A. A. El-Keib, Mohammad Shahidehpour and Roy Billinton, “ProbabilisticReliability Evaluation of Power System Including Solar/Photovoltaic Cell Generator” IEEE PES GM2009, July 26-30,2009, Calgary, AB, Canada.

Page 14: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

14

LOLE ( ) [hours/year]NG x ICx

== Φ

EENS ( ) [MWh/year]pIC L

NGIC

x dx+

= Φ∫

EENSEIR = 1-ED

-1E EENS EENS i i i∆ = −

11

PC E (1 FOR) LOLEi

i a i b iλ λ −∆ = ×∆ + × − ×∑CF ( E / CAP / T) 100i i i= ∆ ×

[pu]

[MWh]

[$/year]

[%]

[Ton/year]

Lp : Peak load [MW]ICi : Installed capacity of generator i

[MW]ED : Total demand energy [MWh]NG : The total generator numberΦNG : The final effective load duration

curveλa: Incremental cost coefficientλb: cost constantTCEi : Total CO2 Emission of ith

generatorCEi : CO2 emission of ith generator

CO2 Ei i iρ= ∆

Page 15: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

15

Flow chart

Power output model of SCG

Solar radiation model

Reliability evaluation

SCG power multi-state model

START

END

Capacity Factor calculation

Production cost calculation

CO2 Emission cost calculation

Page 16: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

16

A map of Jeju Island

HNM C/S HVDCJeju T/P

JCN

DJJSNJ

G3 : 40MWD/P : 40MW

10MVAr

SSN

20MVAr20MVAr

10MVAr10MVAr

20MVAr

D/P : 10MW X4T/P : 100MW X2

T/P : 10MW X1 75MW X2

C1, C2: Syn, Con

SJJ

HLM C/C

35MW X3

AND HNR

SSGNMJ

G1

SG2

D1D2 D3D4T4 T3

T3T2T1G1 G2

G3 D

Filter : 27.5MVAr X4ShR : 1375X2.275

JEJU-MS

SSN-MS

SGP-MS

GNS-MS

HLM-SF SSN-SF

HWN-SF

5. Case Studies

Page 17: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

17

Model System

1. It is a Juju island power system sized similar model system.

2. Total capacity is 945MW (CG845MW+SCG100MW).

3. Peak load is 681MW.

4. The OCPDF (outage capacity probability distribution function)

comes from three SCGs at JCN, SSN and HWN.

Page 18: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

18

The generators data of Jeju island power system

Name Type Capacity[MW] Num.

α[Gcal/

MW2h]

β[Gcal/MWh]

γ[Gcal/hr]

Fuel cost[$/Gcal]

CO2emission

[Ton/MWh] FOR

1 HWN WTG 50 1 - - - - - -

2 SSN WTG 30 1 - - - - - -

3 HLM WTG 20 1 - - - - - -

4* HVDC DC 75/150* 2 0.004 1.512 45.207 43.300 0.65 0.010/

0.028*

5 NMJ3 T/P 100 2 0.004 1.512 45.207 43.300 0.65 0.012

6 JJU1 T/P 55 3 0.062 2.100 5.971 43.599 0.96 0.015

7 JJU2 T/P 75 2 0.003 1.832 30.231 43.599 0.70 0.012

8 HLM1 G/T 35 2 0.004 2.401 20.320 77.909 0.95 0.013

9 HLM1 S/T 35 1 0.004 2.401 20.320 77.909 0.95 0.013

10 JJU3 D/P 40 2 0.025 0.364 28.484 43.599 0.59 0.018

11 NMJ1 D/P 10 4 0.006 1.999 1.360 43.300 0.62 0.018

Total 990 21 - - - - -

Page 19: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

19

Patterns of hourly peak load variation curve

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

0 1095 2190 3285 4380 5475 6570 7665 8760

Time [hours]

Load

[pu]

Page 20: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

20

0 200 400 600 800 1000 12000

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.6

Solar radiation[ W/ m2]

Prob

abilit

y

0.5

0.55

Rc G[W/m2]

Ppv[pu·W]

Gstd

SF Name HLM-SF SSN-SF HWN-SF

SCG capacity 20MW 30MW 50MW

Gstd 1,000W/m2 1,000W/m2 1,000W/m2

Rc 150W/m2 150W/m2 150W/m2

The solar radiation pdf at Jeju Island for ten years (1998-2007)

Power output model of SCG

The Parameters of SCG

Page 21: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

21

Results of case studies

without SCG with SCG difference

IRR [%] 24.08 38.77 14.69

EENS [MWh/year] 83.92 60.04 23.88

LOLE [hours/year] 2.25 1.66 0.59

Total production cost [M$/year] 426.91 413.36 13.55

Total CO2 Emission [103Ton/year] 2,727.88 2,641.35 86.53

Total CO2 Emission Cost [M$/Ton] 65.47 63.39 2.08

Page 22: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

22

Production energy and capacity factor of each generatorsNum. of

Gen.

Without SCG With SCG

Production energy[GWh/year]

Capacity factor [%]

Production energy[GWh/year]

Capacity factor [%]

1 - - 63.73 14.552 - - 38.24 14.553 - - 25.49 14.554 2,541.20 96.7 2,541.20 96.75 1,424.80 81.33 1,335.50 76.236 29.41 33.57 24.27 27.77 161.77 12.31 131.02 9.978 7.26 1.18 5.62 0.929 1.17 0.38 0.9 0.29

10 0.60 0.17 0.41 0.1211 0.16 0.05 0.12 0.03

Total 4,166.37 4,166.50

Page 23: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

23

Production cost and CO2 emission of each generators

Num. of Gen.

Without SCG With SCG

Production cost[M$/year]

CO2 Emission [103TON/year]

Production cost[M$/year]

CO2 Emission [103TON/year]

1 - - - -2 - - - -3 - - - -4 265.38 1,651.79 265.37 1,651.765 139.39 926.15 130.07 868.076 4.2 28.23 3.46 23.37 15.95 113.24 12.92 91.728 1.66 6.90 1.29 5.349 0.27 1.11 0.21 0.85

10 0.04 0.35 0.03 0.2411 0.02 0.10 0.01 0.07

Total 426.91 2,727.88 413.35 2,641.35

Page 24: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

24

Production energy and capacity factor of 5th

generator

1,300

1,400

1,500

Without SCG With SCG

PE [M

Wh/

year

]

75

77

79

81

83

85

CF

[%]

PECF

Page 25: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

25

Production cost and CO2 emission of 5th generator

125

129

133

137

141

145

Without SCG With SCG

PC [M

$]

830

850

870

890

910

930

CO

2 E

mss

ion

[kT

on/y

ear]

PCCO2 Emission

Page 26: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

26

PRI-configurationStandardized Configuration

For Index(from WORR Administrator Client)

PSS/EData

EMSData

SCADAData

WAN

Central PRIDWORRISINI

LAN

Indexviewer

ClientConfiguration GUIView/Update-Client configuration

Server GUI View/Update-Static Information-Server/Alarm Setting

External EnvironmentHost Environment

WORRIS Sever

OFF Line Stream-Data

Real Time Stream-Data-Index

WORRIS Data Interface-Computation Data Interface-Scaling

Data Quality Filtering-Error Filtering-Noise Filtering

AlarmProcesser

ThresholdViolations

Index AlarmLog

Triger logic-contingency

EventFile

Real time Cache-Sub-second data

-Second data

OFF Line Cache-Sub-second

-Second

WORRIS(Web based Online Realtime Reliability Information System) Version 1.0

http://worris.gsnu.ac.kr/

Page 27: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

27

6. Conclusions

The one of important reasons that renewable energy has been receiving considerable attention is to reduce environmental pollution as alternative energy

It contributes to reduce emission of CO2 and the proposed method is useful to calculate the reduction of CO2 by adding SCG.

It is expected that proposed method can evaluate the various effects on power system by adding SCG

Page 28: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

28

Reference• [1] Nick Jenkins, Ron Allan, Peter Crossley, David Kirschen and Goran Strbac: EMBEDDED GENERATION, IEE, 2000.• [2] Mukund R. Patel: Wind and Solar Power Systems, CRC, 1999. • [3] Rajesh Karki and Roy Billinton, "Reliability/Cost Implications of PV and Wind Energy Utilization in Small Isolated

Power Systems" IEEE Trans. Energy Conversion, vol.16, no.4, Dec. 2001, pp.368-373. • [4] Jeongje Park, Wu Liang, Jaeseok Choi, and Seungil Moon, "A Study on Probabilistic Reliability Evaluation of Power

System Considering Wind Turbine Generators”, J. of KIEE, Vol. 57, No. 9, pp.1491-1499, Sept. 2008.• [5] Jeongje Park, Wu Liang, Jaeseok Choi, and Junmin Cha, "Probabilistic Production Cost Credit Evaluation of Wind

Turbine Generators", J. of KIEE, Vol. 57, No. 12, pp.2153-2160, Dec. 2008• [6] Jeongje Park, Wu Liang, Jaeseok Choi, and Junmin Cha, "A Study on Probabilistic Reliability Evaluation of Power

System considering Solar Cell Generators", J. of KIEE, Vol. 58, No. 3, pp.486-495, March 2009• [7] Jeongje Park, Jaeseok Choi, "A Study on Probabilistic Production Costing for Solar Cell Generators", J. of KIEE, Vol.58,

No.4, pp.700-707, April 2009.• [8] M. K. C. Marwali, H. Ma, S. M. Shahidehpour, and K. H. Abdul-Rahman, "Short-term generation scheduling in

photovoltaic-utility grid with battery storage" IEEE Trans. Power Syst., vol.13, no.3, Aug. 1998, pp.1057-1062. • [9] Roy Billinton and Dange Huang, "Aleatory and Epistemic Uncertainty Considerations in Power System Reliability

Evaluation" PMAPS2008, Pueto Rico, May 25-29, 2008.• [10] J. Choi, R. Billinton, M. Futuhi-Firuzabed, "Development of A Nodal Effective Load Model Considering Transmission

System Element Unavailabilities", IEE. G.T&D, pp.79-89, Vol.152, No.1, Jan. 2005.• [11] L. L. Garver, “Effective load carrying capability of generating units,”IEEE Transactions on Power Apparatus and

Systems, vol. PAS-85, no. 8, Aug. 1966, pp. 910–919. • [12] J.M. Michaelides, P.P. Votsis, “Energy analysis and solar energy development in Cyprus”, Computing & Control

Engineering Journal, Volume 2, Issue 5, Sept. 1991, pp.211 - 215. • [13] Ruey-Hsun Liang, and Jian-HaoLiao, "A Fuzzy-Optimization Approach for Generation Scheduling With Wind and

Solar Energy Systems" IEEE Trans. Power Syst., vol.22, no.4, Nov. 2007, pp.1665-1674.

Page 29: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

29

Thank you for your kind [email protected]

Page 30: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

30

Appendix

WF Name HLM-WF SSN-WF HWN-WF

WTG capacity 20MW 30MW 50MW

Cut-in speed(Vci) 5m/sec 5m/sec 5m/sec

Rated speed(VR) 14m/sec 15m/sec 16m/sec

Cut-out speed(Vco) 25m/sec 25m/sec 25m/sec

Wind speed range 0~35 0~40 0~45

Mean wind speed 6.4 7.6 8.5

Standard deviation 9 10 11

The data of each WF

Page 31: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

31

Results of Case Studies

without WTG with WTG difference

IRR [%] 24.08 38.77 14.69

EENS [MWh/year] 83.92 44.52 39.4

LOLE [hours/year] 2.25 1.26 0.99

Total production cost [M$/year] 426.91 400.75 26.16

Total CO2 Emission [103Ton/year] 2,727.88 2,561.31 166.57

Total CO2 Emission Cost [M$/Ton] 65.47 61.47 4

Page 32: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

32

Production Energy and Capacity Factor of Each Generators

Num. of Gen.Without WTG With WTG

Production energy[GWh/year] Capacity factor [%] Production energy

[GWh/year] Capacity factor [%]

1 - - 133.97 30.59

2 - - 73.52 27.98

3 - - 38.87 22.19

4 2,541.20 96.70 2,540.80 96.68

5 1,424.80 81.33 1,245.40 71.08

6 29.41 33.57 20.32 23.20

7 161.77 12.31 108.05 8.22

8 7.26 1.18 4.47 0.73

9 1.17 0.38 0.70 0.23

10 0.60 0.17 0.30 0.09

11 0.16 0.05 0.09 0.03

Total 4,166.37 4,166.49

Page 33: Assessment of CO2 Reduction by Renewable …...1 Assessment of CO 2 Reduction by Renewable Energy Generators IEEE PES Conference on Innovative Smart Grid Technologies January 19- 21,

33

Production Cost and CO2 Emission of Each Generators

Num. of Gen.Without WTG With WTG

Production cost[M$/year]

CO2 Emission [103TON/year]

Production cost[M$/year]

CO2 Emission [103TON/year]

1 - - - -

2 - - - -

3 - - - -

4 265.38 1,651.79 265.28 1,651.54

5 139.39 926.15 120.71 809.48

6 4.20 28.23 2.90 19.51

7 15.95 113.24 10.65 75.64

8 1.66 6.90 1.02 4.25

9 0.27 1.11 0.16 0.66

10 0.04 0.35 0.02 0.18

11 0.02 0.10 0.01 0.05

Total 426.91 2,727.88 400.75 2,561.31