ashrae journal - iaq.pdf

3
 ASHRAE JOURNAL  ashrae.org AUGU ST 2014 8 6 COLUMN IAQ APPLICATIONS Roger Hedrick is principal engineer at Architectural Energy Corporat ion, a member of NORESCO Energy and Sustainability Services. He is chair of SSPC 62.1, Ventilation for  Acce ptab le I ndo or A ir Qu ality . BY ROGER HEDRICK, BEMP, MEMBER ASHRAE Fortu nately, or perhaps naturally, revisions to 62.1- 2007 and 62.1-2010 have been much more s traightfor-  ward. In la rge p art, t his is b ecause the major issues have been resolved and the changes are focused on improving the details of the standard. For example , changes to 62.1- 2010 that resulted in 62.1-2013 include:  T able 6.2.2. 2, “Zone Air Distribut ion Effectiv eness,” is modied to increase the effectiveness of underoor air-distribution systems that meet certain conditions.  The “Zone Air Distributio n Effective ness ” (  E  z ) is a factor used in calculating the amount of outdoor air needed at the zone that accounts for how well the ventilation air gets from the diffuser to the occupant breathing zone. For underoor air distribution systems that have vertical throws of less than 50 fpm (0.25 m/s) at a height of 4.5 ft (1.37 m) above the oor, the standard now allows an E  z  of 1.2. These systems may then meet the standard with less outdoor air than systems with lower E  z  value s, de pendin g on the E  z  value in the critical zone.   The requ irements for the qualit y of water used in humidication systems is modied and claried. In previous versions of the standard, the language regard- ing water used in humidication systems was unclear, “Water shall originate directly from a potable source or from a source with equal or better water quality.” In par- ticular, it was not clear to users what water treatment chemicals might be allowed. The language was claried that no chemicals could be added other than those that meet either of two other standards (NSF/ANSI 60-2012,  Dri nking Wa ter Tr eatmen t Chemi cals— Heal th Eff ects and 21 CFR 173.310, Secondary Direct Food Additives Permitted In Food  F or Human Consumpti on). For chemicals meeting 21 CFR 173.310, automated dosing equipment is required to be used to control the chemical concentrations in the water. Building-level pressurization requirements were claried, and a denition of “exltration” was added. Standard 62.1-2010 required that total building outdoor air intake exceed total building exhaust airow “when- ever the mechanical air-conditioning systems are dehu- midifying.” The wording was revised for the 2013 version such that the requirement applies except “When outdoor air dry-bulb temperature is below the indoor zone dew- point design temperature.”   A perfor mance alter native to the presc riptiv e ex- haust rates is added. This approach is similar to the IAQP in that it allows a performance approach. It differs, how- ever, in that monitoring of the concentrations of con- taminants of concern is required and provides the ba- sis for control of exhaust ow rates. Standard 90.1-2010 includes a requirement that garage ventilation systems must vary ow rates based on monitored contaminant levels. Standard 62.1, on the other hand, provided a re- quired exhaust rate for parking garages, but no allow- ance for reducing this ow. Thus, Standards 90.1 and 62.1 contained conicting requirements. 62.1-2013 was mod- ied to include a performance approach for exhaust sys- tems, to address the conict. This approach requires that contaminants of concern be identied based on sources in the zone, that concentration limits be specied, and Roger Hedrick This article was published in ASHRAE Journal, August 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org.

Upload: muhammadzubair7302

Post on 07-Oct-2015

28 views

Category:

Documents


0 download

TRANSCRIPT

  • A S H R A E J O U R N A L a s h r a e . o r g A U G U S T 2 0 1 48 6

    COLUMN IAQ APPLICATIONS

    Roger Hedrick is principal engineer at Architectural Energy Corporation, a member of NORESCO Energy and Sustainability Services. He is chair of SSPC 62.1, Ventilation for Acceptable Indoor Air Quality.

    BY ROGER HEDRICK, BEMP, MEMBER ASHRAE

    Standard 62.1 Update & PlansASHRAEs principal ventilation standard, Standard 62.1-2013, Ventilation for Acceptable Indoor Air Quality, was recently republished with a number of updates. A number of years ago, Standard 62.1 went through some fairly significant changes. The transition from the advisory language of 62-1989 to todays mandatory, code-intended language, which includes much more extensive requirements was long, difficult and contentious.

    Fortunately, or perhaps naturally, revisions to 62.1-

    2007 and 62.1-2010 have been much more straightfor-

    ward. In large part, this is because the major issues have

    been resolved and the changes are focused on improving

    the details of the standard. For example, changes to 62.1-

    2010 that resulted in 62.1-2013 include:

    Table 6.2.2.2, Zone Air Distribution Effectiveness, is modified to increase the effectiveness of underfloor

    air-distribution systems that meet certain conditions.

    The Zone Air Distribution Effectiveness (Ez) is a factor

    used in calculating the amount of outdoor air needed at

    the zone that accounts for how well the ventilation air

    gets from the diffuser to the occupant breathing zone.

    For underfloor air distribution systems that have vertical

    throws of less than 50 fpm (0.25 m/s) at a height of 4.5 ft

    (1.37 m) above the floor, the standard now allows an Ez of

    1.2. These systems may then meet the standard with less

    outdoor air than systems with lower Ez values, depending

    on the Ez value in the critical zone.

    The requirements for the quality of water used in humidification systems is modified and clarified. In

    previous versions of the standard, the language regard-

    ing water used in humidification systems was unclear,

    Water shall originate directly from a potable source or

    from a source with equal or better water quality. In par-

    ticular, it was not clear to users what water treatment

    chemicals might be allowed. The language was clarified

    that no chemicals could be added other than those that

    meet either of two other standards (NSF/ANSI 60-2012,

    Drinking Water Treatment ChemicalsHealth Effects and 21

    CFR 173.310, Secondary Direct Food Additives Permitted In Food

    For Human Consumption). For chemicals meeting 21 CFR

    173.310, automated dosing equipment is required to be

    used to control the chemical concentrations in the water.

    Building-level pressurization requirements were clarified, and a definition of exfiltration was added.

    Standard 62.1-2010 required that total building outdoor

    air intake exceed total building exhaust airflow when-

    ever the mechanical air-conditioning systems are dehu-

    midifying. The wording was revised for the 2013 version

    such that the requirement applies except When outdoor

    air dry-bulb temperature is below the indoor zone dew-

    point design temperature.

    A performance alternative to the prescriptive ex-haust rates is added. This approach is similar to the IAQP

    in that it allows a performance approach. It differs, how-

    ever, in that monitoring of the concentrations of con-

    taminants of concern is required and provides the ba-

    sis for control of exhaust flow rates. Standard 90.1-2010

    includes a requirement that garage ventilation systems

    must vary flow rates based on monitored contaminant

    levels. Standard 62.1, on the other hand, provided a re-

    quired exhaust rate for parking garages, but no allow-

    ance for reducing this flow. Thus, Standards 90.1 and 62.1

    contained conflicting requirements. 62.1-2013 was mod-

    ified to include a performance approach for exhaust sys-

    tems, to address the conflict. This approach requires that

    contaminants of concern be identified based on sources

    in the zone, that concentration limits be specified, and

    Roger Hedrick

    This article was published in ASHRAE Journal, August 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org.

  • A U G U S T 2 0 1 4 a s h r a e . o r g A S H R A E J O U R N A L 8 7

    COLUMN IAQ APPLICATIONS

    monitoring systems be installed to ensure that exhaust

    rates are adequate to maintain concentrations below the

    specified limits.

    Some changes are made to the outdoor airflow rates and zone types in Table 6.2.2.1 (previously known as Ta-

    ble 6-1). These include the addition of refrigerated ware-

    houses and, for sports-related zones, change the ven-

    tilation rate to include a per-occupant component that

    allows the use of demand-controlled ventilation in these

    zones. For refrigerated warehouses, the area component

    of the ventilation rate is set to zero, so no ventilation is

    required when there are no occupants in the zone.

    The filter requirement on air entering wetted cooling coils has been modified to change the MERV rating from 6

    to 8. This change reduces potential for particulate deposi-

    tion on the coils that could lead to biological or other con-

    tamination. The SSPC believes that MERV 8 filters are now

    so common that this change does not impose any signifi-

    cant cost increase on building owners or operators.

    Toilet exhaust air that is cleaned to Class 1 may be re-circulated. This is a change that came from a continuous

    maintenance proposal, and was accepted by the SSPC.

    The requirements for this air cleaning are subjective, but

    include inoffensive odor.

    Addenda in progress continue the trend of improving

    the standard. The major addenda are described here

    as currently drafted, but are subject to revision in the

    approval process.

    Addendum 62.1j will revise the Indoor Air Quality Pro-cedure (IAQP, the performance-based path for determin-

    ing ventilation rates) by adding procedures for addressing

    mixtures of contaminants. Additivity, the effect of combi-

    nations of contaminants each at low concentrations, has

    long been an implicit part of the Ventilation Rate Proce-

    dure. The IAQP, on the other hand, allowed determination

    of ventilation rates on the basis of keeping concentrations

    of each individual contaminant below specified limits and

    ignoring additive effects. Addendum j will require that in

    the presence of mixtures of contaminants (nearly always

    the case in non-industrial indoor environments) that ven-

    tilation rates are calculated to keep the concentration of

    the mixture below specified levels.

    There has been a fair amount of effort in various quar-

    ters aimed at increasing the usability of the IAQP. These

    efforts have not yet resulted in new addenda. However,

    it is hoped that efforts to define adequate filtration

    approaches or lists of contaminants and concentration

    limits, possibly used in conjunction with each other,

    may eventually result in methods of providing accept-

    able indoor air quality with lower ventilation rates and

    the associated reductions in energy consumption.

    Addendum 62.1k will modify the classification of laboratory hood exhaust air. This change will explicitly

    allow EH&S (Environmental Health and Safety) Profes-

    sionals to determine the appropriate air class for labora-

    tory hood exhaust airstreams. Those that are Class 3 or

    better could then use heat wheel energy recovery.

    Addendum 62.1p will allow ventilation air in some zones to be reduced to zero based on occupancy sensors.

    Currently, ventilation air must be provided to all zones

    during periods of expected occupancy, even when zones

    are unoccupied. This addendum will allow occupancy sen-

    sors to be used to determine if a zone is unoccupied and

    then reduce ventilation air to zero. This reduction will only

    be allowed for zones where occupants are the primary con-

    taminant source, i.e., those with an area component of the

    ventilation rate of 0.06 cfm/ft (0.305 L/sm2)

    Addendum 62.1r will modify DCV (demand con-trolled ventilation) control requirements to improve

    clarity. The changes also remove the assumption that the

    Standard is intended for use only as calculations for code

    review and not operation.

    Addendum 62.1q will revise requirements restrict-ing the location of positively pressurized exhaust ducts.

    Draft Addendum DA-53 aims to strengthen require-ments for equipment maintenance and sensor calibra-

    tion. These requirements are particularly aimed are sen-

    sors used for DCV control.

    At the meeting of the Standing Standards Project

    Committee in Denver in June 2013, the committee

    brainstormed ideas for how the standard could be fur-

    ther improved. A fairly extensive list of topics was gener-

    ated. Many of these are concepts for possible addenda.

    Some examples include:

    Requirements for personal ventilation systems and corresponding revision of ventilation rates.

    Additional requirements for building controls and provision of standard sequences of operation.

    Revisions to area components of the ventilation rates in light of lower-emitting building materials.

    Methods to account for emission rate decay as build-ings age.

    Modifications appropriate for areas outside the U.S. and Europe.

  • A S H R A E J O U R N A L a s h r a e . o r g A U G U S T 2 0 1 48 8

    allow existing buildings to show compliance other than

    by meeting all of the requirements intended for new

    construction. This placed weatherization programs in the

    difficult position of applying Standard 62.2 outside of its

    scope or not applying an IAQ standard when weatherizing

    multifamily dwelling in buildings taller than three stories.

    Addendum 62.1a and a corresponding addendum to

    Standard 62.2 will change the scopes of both standards

    such that single family homes and dwelling units in mul-

    tifamily buildings, regardless of height, will be covered

    by Standard 62.2 while the common areas of multifamily

    buildings will be covered by Standard 62.1. This will allow

    weatherization programs to apply the existing building

    appendix of 62.2 to any residential building. It also has the

    benefit of providing uniform ventilation requirements

    for all apartments, regardless of the height of the build-

    ing in which they are located. It also will clarify coverage

    of mixed use buildings of three stories or less. Currently,

    it is unclear which standard covers a building with retail

    on the first floor and apartments on the second and third

    floor. The current scope language for both standards

    defines coverage by building. The proposed scope change

    will explicitly determine coverage at the zone level.

    This change in scope is not expected to have major

    impacts in other areas of the standard. It will, however,

    have a significant impact on users. Nearly all multifam-

    ily residential buildings will need to comply with both

    Standards 62.1 and 62.2. It is unclear how future stan-

    dards will fit with the model codes that are a primary

    user of the standards. There will also be impacts on

    LEED, where compliance with ventilation standards is

    a prerequisite for certification. Finally, Standards 90.1

    and 189.1 have similar scope as the current 62.1, and

    the scope of 90.2 is similar to that of 62.2. The proposed

    changes will impact this symmetry.

    SSPC 62.1 is focused on improving the usability of

    Standard 62.1, while providing flexibility to building

    designers. The tension between providing acceptable

    indoor air quality and reducing energy consumption is a

    never ending issue. SSPC 62.1s primary goal is to assure

    that building occupants are provided with acceptable

    indoor air quality, but we are open to changes that allow

    energy savings but dont compromise IAQ. The SSPC

    welcomes change proposals from ASHRAE members and

    the public. See How to Submit a Proposed Change to a

    Standard at www.ashrae.org/standards-researchtech-

    nology/standards-formsprocedures.

    Inclusion of additional alternate compliance paths, particularly for use in existing buildings.

    Addition of requirements for low humidity limits. Improvements to the natural ventilation procedure. Further improvements to DCV requirements.

    One exception to the theme of improving the details

    of the standard is Addendum 62.1a. This addendum will

    change the scope of the standard. Currently Standard

    62.1 covers all buildings except residential buildings three

    stories high or less. Standard 62.2 covers single family

    houses and multifamily buildings up to three stories. The

    two standards result in significantly different require-

    ments between multifamily buildings that are three (62.2)

    or four (62.1) stories tall. More significantly, Standard

    62.2 has an appendix that provides alternative compli-

    ance methods for existing buildings. This appendix is

    heavily used by residential weatherization programs.

    When residences are weatherized under these programs,

    compliance with Standard 62.2 is often required to

    assure that measures do not compromise the IAQ in the

    homes. Standard 62.1 has no corresponding method to

    COLUMN IAQ APPLICATIONS

    Advertisement formerly in this space.