as6 profibus instruction manual

Upload: juan-i-meza-lozano

Post on 14-Apr-2018

245 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 AS6 Profibus Instruction Manual

    1/42

    Document number: 01-2117-01Edition: r1

    Date of release: 2000-01-14

    Saftronics retain the right to change specifications and illustra-

    tions in the text, without prior notification. The contents of

    this document may not be copied without the explicit per-

    mission of Saftronics, Inc..

    F IELD B U S I /O OPT I0N

    INSTRUCTION MANUAL - ENGLISH

    SAFTRONICS

    AS6

    PROFIBUS - DP

  • 7/27/2019 AS6 Profibus Instruction Manual

    2/42

    2

    Instruction manual

    I t is important to be familiar with the main product (softstarter/inverter) to fully understand this instruction manual.

    Technically qualified personnel

    Installation, commissioning, demounting, making measurements,etc. of or on the Saftronics products may only be carried out bypersonnel technically qualified for the task.

    Installation

    T he installation must be made by authorised personnel and mustbe made according to the local standards.

    Opening the softstarter

    DANGER! ALWAYS SWITCH OFF THE MAINS VOLTAGE

    BEFORE OPENING THE UNIT AND WAIT AT LEAST 5

    MINUTES TO ALLOW THE BUFFER CAPACITORS TO

    DISCHARGE.

    Always take adequate precautions before opening thesoftstarter. Although the connections for the controlsignals and the jumpers are isolated from the main voltage.Always take adequate precautions before opening thesoftstarter.

    EMC Regulations

    EM C regulations must be followed to fulfill the EM C standards.

    S A F E T Y I N S T R U C T I O N S

  • 7/27/2019 AS6 Profibus Instruction Manual

    3/42

    3

    C O N T E N T

    1 . Q U I C K S E T - U P . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    2 . G E N E R A L I N F O R M A T I O N . . . . . . . . . . . . . . . 6

    2.1 Introduction .................................................................. 6

    2.2 Description. ................................................................... 6

    2.3 Users ............................................................................ 6

    2.4 Safety ........................................................................... 7

    2.5 Delivery and Unpacking. ................................................. 7

    3 . F i e l d B u s I / O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    3.1 Introduction .................................................................. 83.2 HMS ............................................................................. 8

    3.3 Interfaces of communication .......................................... 8

    3.4 Setting up ..................................................................... 9

    3.5 Description of Jumpers and LED s .................................. 9

    3.6 Recommendation ......................................................... 10

    4 . P r o f i B u s - D P . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    4.1 Introduction ................................................................ 11

    4.2 Setting up ................................................................... 11

    5 . A S 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3

    5.1 Response time ............................................................ 13

    5.2 Installation in AS6 Softstarters ..................................... 13

    5.3 Installation AS6-180 and Larger............................................ 155.4 Set-up Communication Parameters ............................... 17

    5.5 Selection of control sources ......................................... 20

    5.6 Using serial comm. with Fieldbus ................................ 20

    5.7 Using serial communication with RS-232 Modbus RTU ..21

    5.8 Map ............................................................................ 21

    5.9 Getting started - simple communication example 25

  • 7/27/2019 AS6 Profibus Instruction Manual

    4/42

    4

    List of tablesTable 1 9-pin D-sub connector. ............................................. 11

    Table 2 LED indication ......................................................... 12

    Table 3 Map of input pins to the MSF ................................... 22

    Table 4 Map of output pins from the MSF ............................. 23

    List of figuresFig. 1 Step by step guide. .................................................... 5

    Fig. 2 Ways to communicate ............................................... 8

    Fig. 3 Jumper 1 ................................................................... 9

    Fig. 4 Profibus interface. ................................................... 11

    Fig. 5 Jumper J2. ............................................................... 12

    Fig. 6 Bytes. ..................................................................... 21

  • 7/27/2019 AS6 Profibus Instruction Manual

    5/42

    QUICK SET-UP 5

    1 . Q U I C K S E T - U P

    Following flowchart is a step by step guide for advanced users,with references to chapters with detailed information.

    Fig. 1 Step by step guide.

    Set FieldBus I / O Address

    * Profibus, see 4.2.3

    Set FieldBus I / O Baudrate

    * Profibus, automatically selected

    Set Internal C ommunications Address

    * AS6, use address 1, see 8.4

    Set Internal C ommunications Baudrate

    * AS6, use 19.2 kBaud, see 8.4

    Set Internal C ommunications Parity

    * AS6, use No Parity, see 8.4

    Set C ontrol M ode

    * AS6, parameter 006, used mode 3, see 8.6.1

  • 7/27/2019 AS6 Profibus Instruction Manual

    6/42

    6 GENERAL INFORMATION

    2 . G E N E R A L I N F O R M A T I O N

    2.1 IntroductionT he FieldBus I / O interface allows external equipment toexchange data and run our products.

    T he FieldBus I/ O interface acts as a slave in a master slaveconfiguration.

    Physical connection can be either R S-232 or one of the avail-able fieldbuses.

    2.2 Description.T his instruction manual describes the installation and operationof the FieldBus I / O option card, which can be built into the fol-lowing products:

    AS6 Softstarters:AS6-30 - AS6-800

    Specific information about the softstarters is in chapter 5.

    2.3 Users

    T his instruction manual is intended for:- Installation engineers- Designers- M aintenance engineers- Service engineers- Programmers

  • 7/27/2019 AS6 Profibus Instruction Manual

    7/42

    GENERAL INFORMATION 7

    2.4 SafetyBecause this option is a supplementary part of thesoftstarter, the user must be aquatinted with the originalinstruction manual of the AS6 softstarter.All safety instructions, warnings etc. as mentionedin these instruction manuals are to be known to the user.

    T he following indications can appear in this manual. Alwaysread this first and be aware of their content before continuing.

    2.5 Delivery and Unpacking.C heck for any visible signs of damage. Inform your supplierimmediately of any damage found. Do not install the option cardif damage is found.

    I f the option card is moved from a cold storage room to theroom where it is to be installed, condensation can form on it.Allow the option card to become fully acclimatised and waituntil any visible condensation has evaporated before installing itin the inverter or softstarter.

  • 7/27/2019 AS6 Profibus Instruction Manual

    8/42

    8 FieldBus I/O

    3 . F I E L D B U S I / O

    3.1 IntroductionT he FieldBus I/ O O ption consists of 2 parts. O ne part is an Any-Bus I / O M odule. T his module is a third part and comes fromHMS.

    W e have chosen to buy this part because of the complexityand amount of fieldbuses.

    3.2 HMST his is how H M S present themselves:

    "H MS develops and supplies high tech electronics to quality consciouscustomers worldwide. H MS was one of the first companies to developinterfaces for all major fieldbus systems. T oday, ten years later, wehaveexpanded both thetechnology and our own skills. W e are now oneof theworlds leading companies in the fieldbus technology sphere, and are theglobal leaders in embedded O E M fieldbus modules for industrial prod-ucts."

    3.3 Interfaces of communication

    Fig. 2 W ays to communicate

  • 7/27/2019 AS6 Profibus Instruction Manual

    9/42

    FieldBus I/O 9

    3.4 Setting up

    3.4.1 Steps

    Several steps must be done for a complete set-up. B oth FieldBusI/ O O ption and the product must be set for a complete andworking system. T he FieldBus I / O O ption is also divided into 2parts; FieldBus and R S-232.

    3.5 Description of Jumpers and LEDs

    Fig. 3 Jumper 1

    3.5.1 Mode

    U ser can choose between R S-232 and FieldBus with jumper J1.I t is not possible to communicate in both ways at the same time.

    3.5.2 I/O Modules

    H M S presents two sizes of I / O modules. T he size can be set withjumper J2. For the time being we are only using the 64I/ O module and this should be set.

    64 32

    COM.F

    AILUR

    E

    RUN

    TESTMODE2

    TESTMODE1

    FIELD-

    BUS RS-232

    J1J2

  • 7/27/2019 AS6 Profibus Instruction Manual

    10/42

    10 FieldBus I/O

    3.5.3 LED indication

    Four L EDs indicates what status the FieldBus I / O O ption have.LED 1 and 2 are only for internal use at production.LED 3 (green) indicates that the FieldBus communication isworking and running.LED 4 (red) indicates that external communication is broken.LED 3 and 4 (red and green) indicates that the FieldBus I / OO ption is trying to achieve internal communication with theproduct. T his state is seen when the product is started. I f theproduct is not correct set the Fieldbus I / O O ption will remain inthis state.

    3.6 RecommendationW e suggest that installation, cables and connectors must be fol-lowed as specified by each fieldbus organisation.

  • 7/27/2019 AS6 Profibus Instruction Manual

    11/42

    ProfiBus - DP 11

    4 . P R O F I B U S - D P

    4.1 IntroductionPR O FI BU S-DP is designed for high-speed data communicationat the device level. H ere, central controllers (e.g., PL C s/PC s)communicate with their distributed field devices (I / O , drives,valves, etc.) via a high-speed serial link. M ost of the data com-munication with these distributed devices is done in a cyclicmanner. T he functions required for these communications arespecified by the basic PR O FI BU S-D P functions in accordance

    with E N 50 170.

    4.2 Setting upBefore commencing communication with the FieldBus I/ Ooption, the option and the product will need some settings. Forproduct settings information see the product specific chapters.

    4.2.1 Picture of interface

    Fig. 4 Profibus interface.

    4.2.2 Connection

    T able 11 9-pin D-subconnector.

    D-sub Description

    8 A-Line

    3 B-LineHousing Shield

    5 GND

    6 Vcc

    4 RTS

    AddressX10 X1

    Connection LEDS S3 S2

    Terminating resistor

  • 7/27/2019 AS6 Profibus Instruction Manual

    12/42

    12 ProfiBus - DP

    4.2.3 Address

    Address can be set from 00 to 99 by rotary switches S2 and S3.T o calculate the address, multiply S3s value by 10 and then addthe values.

    4.2.4 Baudrate

    T he baudrate is automatically selected from 9600 Baud to 12MBaud.

    4.2.5 32 I/O or 64 I/O

    32 I/ O or 64 I/ O is chosen with the jumper J2.

    Fig. 5 Jumper J2.

    4.2.6 Termination

    T ermination of the fieldbus requires a terminating resistor at eachend of the fieldbus. Switching S1 to O N can connect the termi-nation resistor.

    4.2.7 Led indication

    T able 12 L E D indication

    Led Colour Function

    Error Red Bus off/error

    DIA Green Not implemented

    Power Green Power on

    64 32

  • 7/27/2019 AS6 Profibus Instruction Manual

    13/42

    AS6 13

    5 . A S 6

    NOTE! This chapter explaines communication with fieldbus only.

    5.1 Response timeIn normal case there is a 50-70ms response time. Due to varia-tions in workload the response time can be up to 300ms.

    5.2 Installation in AS6 Softstarters

    The following pictures shows the parts of the FieldBus I/Ooption.

    Remove first the lid on the top side of the softstarter and thenremove the PPU (1). Then remove the two screws and loosenthe metal plate on the top (2).

    1 2

  • 7/27/2019 AS6 Profibus Instruction Manual

    14/42

    14 AS6

    Mount the option card according to the following pictures. Fas-

    ten the flat cable first (3) and then put the option card in positionand fasten it with the screws again. Then connect the flat cable tothe option card (4).

    Put the PPU back on again (5).

    3 4

    5

  • 7/27/2019 AS6 Profibus Instruction Manual

    15/42

    AS6 15

    5.3 Installation AS6-180 and Larger

  • 7/27/2019 AS6 Profibus Instruction Manual

    16/42

    16 AS6

  • 7/27/2019 AS6 Profibus Instruction Manual

    17/42

    AS6 17

    5.4 Set-up Communication ParametersThe following parameters have to be set-up:

    - Unit address.

    Comm unit address

    Default: 1

    Range: 1-247

    Select the unit address to 1 in fieldbus mode and any value

    in the range for RS-232 Modbus mode.

    1

    111

  • 7/27/2019 AS6 Profibus Instruction Manual

    18/42

    18 AS6

    - Baud rate.

    - Parity

    Comm baudrate

    Default: 9.6

    Range: 2.4, 4.8, 9.6, 19.2, 38.4 kBaud

    Select the baudrate to 19.2 kBaud between AS6 and field-

    bus I/O option board in fieldbus mode and any value in therange for RS-232 Modbus mode.

    Comm parity

    Default: 0

    Range: 0, 1

    Select 0=No parity in fieldbus mode and any value in the

    range for RS-232 Modbus mode.

    1 9. 2

    112

    0

    113

  • 7/27/2019 AS6 Profibus Instruction Manual

    19/42

    AS6 19

    - Behaviour when contact interrupted.

    If an alarm occurs, it is automatically reset if the communicationis re-established. It is also possible to reset the alarm from the softstarter keyboard. This alarm function is available in both fieldbusmode and RS-232 Modbus mode.

    If control mode is Serial comm. control and no contact isestablished or contact is interrupted the softstarter consider thecontact to be interrupted after 15 sec, the softstarter can act in

    three different ways:1 Continue without any action at all.2 Stop and alarm after 15 sec.3 Continue and alarm after 15 sec.

    Setting up the communication parameter must be made in localKeyboard control mode, menu 06=01, see AS6 instructionmanual 7.2.

    Comm. contact interrupted

    Default: 1

    Range: oFF, 1, 2

    This parameter will control the behaviour in the softstarterwhen the comm. is interrupted.

    oFF No alarm and continue operation.

    1 Alarm and stop operation.

    2 Alarm and continue operation.

    1

    114

  • 7/27/2019 AS6 Profibus Instruction Manual

    20/42

    AS6 20

    5.5 Selection of control sourcesSetting up the control mode has to be done from the local AS6keyboard.

    In all control modes it is possible to readout all the bit map (see5.7.1) information in the softstarter via serial communication.

    See also 7.2 Overview of softstarter operation and parame-ter set-up in the AS6 Instruction manual.

    5.6 Using serial comm. with FieldbusThe source from where operation and parameter settings aremade is selected in the Control Mode parameter menu 006.When serial communication control mode (menu 006=03) isselected, it is possible to:

    - Operate the softstarter only via serial comm.- Set-up parameters only via serial comm.- Readout all bitmap information (see 8.7.1).- Set-up the control mode parameter from local

    AS6 keyboard, but not via serial comm.- View all parameters and open the menu expansions from local AS6 keyboard.

    Selection of control mode

    Default: 2

    Range: 1, 2, 3

    This parameter will select the control mode (source).

    1 Keyboard control.

    2 Remote input control.

    3 Serial communication fieldbus control.

    3

    006

  • 7/27/2019 AS6 Profibus Instruction Manual

    21/42

    AS6 21

    5.7 Using serial communication with

    RS-232 Modbus RTUThe source from where operation and parameter settings aremade is selected in the Control Mode parameter menu 006.

    When serial communication control mode (menu 006=3) isselected, it is possible to:

    - Operate the softstarter only via serial comm.- Set-up parameters only via serial comm.- Readout all view information and all parameters.- Set-up the control mode parameter from local AS6 keyboard, but not via serail comm.- Inspect all parameters and open the menu expansions from local AS6 keyboard.

    5.8 Map

    5.8.1 Definitions

    This is the definitions of bits and bytes.

    Fig. 6 Bytes.

    Explanation:0 ->1 = edge trigged function, the switch from low to

    high activates the function once.1 ->0 = edge trigged function, the switch from high to

    low activates the function once.1 = level trigged function which is active0 = level trigged function which is not active

    LSB (Least significant bit) has the lowest number for each func-tion. For example: Parameter set = 1; pin 4 = 1, pin 5 = 0,pin 6 = 0

  • 7/27/2019 AS6 Profibus Instruction Manual

    22/42

    22 AS6

    5.8.2 RequestTable 13 Map of input pins to the AS6

    BITInput to

    AS6Setting Comment

    AS6 Manualreference

    0Run /Stop

    Run = 0 -> 1,Stop = 1 -> 0

    1AlarmReset

    Reset = 0 ->1

    2 Auto Set Auto set =0->1

    Sets power limits for load monitor refer-ring to actual load. New Autoset levelis set, when output pin 14 chnage to 1.When output pin 14 is set to 0.

    See AS6 manual

    3 Parame-ter Set

    BIT 5 4 3Par set 0 = 0 0 0Par set 1 = 0 0 1Par set 2 = 0 1 0Par set 3 = 0 1 1Par set 4 = 1 0 0

    Par set 0 =Parameter set selected viaterminal 16 & 17.

    See AS6 manual4

    5

    6Jog For-ward

    Off = 0On = 1

    Only possible to use JOG function whensoftstarter is stopped

    When using JOGfunction be surenot to overheatmotor due to thedecreased cool-ing. see MSFmanual.Menu103 &104 mustbe on.

    7

    JogReverse

    Off = 0On = 1

    Only possible to use JOG function whensoftstarter is stopped

    8

    Viewvalueselection

    BIT12 11 10 9 81 = 0 0 0 0 12 = 0 0 0 1 03= 0 0 0 1 14 = 0 0 1 0 05 = 0 0 1 0 16 = 0 0 1 1 07 = 0 0 1 1 18 = 0 1 0 0 09 = 0 1 0 0 110=0 1 0 1 011=0 1 0 1 112=0 1 1 0 013=0 1 1 0 114=0 1 1 1 0

    1=Current, menu 2012=Line main voltage, menu 2023=Output shaft power, menu 2034=Power factor, menu 2045=Shaft torque, menu 2076=Current phase L1, menu 2117=Current phase L2, menu 2128=Current phase L3, menu 2139=Line main voltage L1-L2, menu 21410=Line main voltage L1-L3, menu 21511=Line main voltage L2-L3, menu 21612=Used thermal capacity, menu 07313=Phase sequence, menu 8714=Input power

    Will not affectselected valuefor analogue out-put (terminal 19)see AS6 manual

    9

    10

    11

    12

    13

    Full

    VoltageStart

    Off = 0On = 1 Direct on line start (DOL) See AS6 manual

    14 Not used

    15-31

    Not used

  • 7/27/2019 AS6 Profibus Instruction Manual

    23/42

    AS6 23

    5.8.3 ResponseTable 14 Map of output pins from the AS6

    PinOutput

    from AS6Setting Comment

    AS6 Manualreference

    0Running/Stopped

    Running = 1,Stopped = 0

    1Max pre-alarmstatus

    Pre-alarm = 1no pre-alarm =0

    See AS6manual

    2Min pre-alarmstatus

    Pre-alarm = 1no pre-alarm=0

    See AS6manual

    3 ActualParameterSet

    BIT 5 4 3Par set 1 = 0 0 1Par set 2 = 0 1 0Par set 3 = 0 1 1Par set 4 = 1 0 0

    See AS6manual4

    5

    6 Operationmode

    BIT 8 7 61 = 0 0 12 = 0 1 03= 0 1 14 = 1 0 05 = 1 0 16 = 1 1 07 = 1 1 1

    1 = Voltage control2 = Torque control3 = Current limit control4 = Ramp with current limit5 = Pump application6 = Analogue input voltage

    control7 = Direct On Line star

    See AS6manual7

    8

    9 Operationstatus

    BIT 12 11 10 91 = 0 0 0 1

    2 = 0 0 1 03= 0 0 1 14 = 0 1 0 05 = 0 1 0 16 = 0 1 1 07 = 0 1 1 18 = 1 0 0 09 = 1 0 0 110 = 1 0 1 011 = 1 0 1 1

    1 = Stopped2 = Stopped with alarm condition

    3 = Run with alarm condition4 = Run acceleration5 = Run full voltage6 = Run deceleration7 = Run bypassed8 = Run power factor control9 = Run DC brake10 = Run at slow speed forward11 = Run at slow speed reverse12= Jog forward13= Jog reverse

    10

    11

    12

    13Controlmode

    Serial comm. notactive=0Serial comm.active=1

    14 Autsetstatus

    Ready for new

    Autoset=0New Autoset levelOK=1

    The Autoset status switch to low wheninput pin 2 is low.

  • 7/27/2019 AS6 Profibus Instruction Manual

    24/42

    24 AS6

    15 Alarmstatus

    BIT 19181716150 = 0 0 0 0 0F1 = 0 0 0 0 1F2 = 0 0 0 1 0F3= 0 0 0 1 1F4 = 0 0 1 0 0F5 = 0 0 1 0 1F6 = 0 0 1 1 0F7 = 0 0 1 1 1F8 = 0 1 0 0 0

    F9 = 0 1 0 0 1F10=0 1 0 1 0F11=0 1 0 1 1F12=0 1 1 0 0F13=0 1 1 0 1F14=0 1 1 1 0F15=0 1 1 1 1F16=1 0 0 0 0

    0 = No alarmF1 = Phase input failureF2 = Motor protectionF3 = Softstarter overheatedF4 = Current limit timeoutF5 = Locked rotorF6 = Above max power limitF7 = Below min alarmF8 = Voltage unbalanceF9 = Over voltage

    F10 = Under voltageF11 = Starts / hour exceededF12 = Shorted thyristorF13 = Open thyristorF14 = Motor terminal openF15 = Serial com. brokenF16 = Phase reversal alarm

    See AS6manual16

    17

    18

    19

    20

    View valueView valuebetween 0 - 4000

    FULL RANGE1 = Current, 5 X In [A], In set in

    menu 422= Line main 1,5 X Un[V],Un set voltage, in menu 413= Output shaft 1,5 X Pn [KW], power, set in menu 434= Power factor, 1.0

    5= Shaft torque, 2,5 x Tn6= Current phase 5 X In [A], In set L1, in menu 427= Current phase 5 X In [A], In set L2, in menu 428= Current phase 5 X In [A], In set L3, in menu 429= Line main 1,5 X Un[V],Un

    voltage L1-L2 set in menu 4110= Line main 1,5 X Un [V], Un voltage L1-L3 set in menu 4111= Line main 1,5 X Un [V], Un voltage L2-L3 set in menu 4112=Used thermal 150 %

    capacity,13=Phase seq., 1=123,2=32114=Input power, 1,5 X Pn [KW],

    Pn set in menu 43

    PnTn= --------------------- (Nn*2*pi)/60

    Nn [rpm], setvalue in menu44

    21

    22

    23

    24

    25

    2627

    28

    29

    30

    31

    Table 14 Map of output pins from the AS6

    PinOutput

    from AS6Setting Comment

    AS6 Manualreference

  • 7/27/2019 AS6 Profibus Instruction Manual

    25/42

    AS6 25

    5.9 Getting started - simple

    communication exampleTo obtain a connection to the AS6 softstarter follow Quick Set-up in chapter 1. page 5 step by step. This example shows how toselect a Parameter Set, select current as view value and to make astart.

    - Set all Pins In AS6 to 0.- Set Pin 4=1 to select Parameter Set 2.- Set Pin 8=1 to select Current as view value.- Set Pin 0=1 to make a start.

    The Bit Map in to AS6 is now complete.

    If everything went ok in the softstarter, the response in Pins OutAS6 will be as follows;

    - Pin 0=1 Softstarter is running- Pin 1-2=0, No Pre-alarms- Pin 3=0, Pin 4=1, Pin 5=0, Actual Parameter Set is 2.- Pin 6=1, Pin 7-8=0, Default voltage control mode.- Pin 9=1, Pin 10=0, Pin 11=1, Pin 12=0, Run acceleration.- Pin 13=1, Serial comm. control mode.- Pin 14=0, No Auto Set.- Pin 15-19=0, No alarm.

    - Pin 20-31=0,0,0 0,0,0,0,1,0,0=640, if nominal current is17A the actual current is 640/4000x5x17=13.6A

  • 7/27/2019 AS6 Profibus Instruction Manual

    26/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    27/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    28/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    29/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    30/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    31/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    32/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    33/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    34/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    35/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    36/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    37/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    38/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    39/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    40/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    41/42

  • 7/27/2019 AS6 Profibus Instruction Manual

    42/42