as-202 en1366-4 report

80
© Exova Warringtonfire Aus Pty Ltd 2018 EWFA CERTIFICATE OF TEST CERTIFICATE No.: SFC 53596800c.1 Page 1 of 1 Report Sponsor Summary Issue Date Alseal Marketing Sdn. Bhd. Lot 2291, Jalan Kampung Baru, kg. Baru, Sungai Buloh, 47000 Selangor DE, Malaysia 25/09/2018 Introduction The element of construction described below was tested by this laboratory on behalf of the test sponsor in accordance with the stated test standard and achieved the results stated below. Refer to the referenced test report for more information. Referenced Report Test Date Test Standard EWFA 43878800g.1 15/06/2017 EN 1366-4:2006 EWFA 53596800d.2 26/03/2018 EN 1366-4:2006 EWFA 53596801d.1 12/06/2018 EN 1366-4:2006 Description of Services The EWFA 43878800 test assembly comprised a nominal 1584mm long × 1600mm wide × 250mm thick Hebel floor, that was penetrated by three control joints at a nominal length of 1000mm. Starting from the eastern side the joints were 12mm, 30mm and 50mm wide respectively. The control joints were protected by Alseal AS-202 Fire Retardant Silicone Sealant and were sealed from the unexposed side at a depth of half the width of the control joint with a backing rod placed in the control joint. Service Description Fire Protection System Integrity Insulation D 50mm wide at 25mm deep from the unexposed side. Alseal AS-202 Fire Retardant Silicone Sealant No Failure at 301 minutes Failure at 148 minutes E 30mm wide at 15mm deep from the unexposed side. Alseal AS-202 Fire Retardant Silicone Sealant No Failure at 301 minutes Failure at 97 minutes F 12mm wide at 6mm deep from the unexposed side. Alseal AS-202 Fire Retardant Silicone Sealant No Failure at 301 minutes No Failure at 301 minutes The EWFA 53596800 test assembly comprised a nominal 1600mm wide × 1600mm long × 250mm thick Hebel wall, that was penetrated by five control joints at a nominal length of 1000mm. Starting from the western side the joints were 30mm, 30mm, 30mm, 50mm and 12mm wide respectively. The control joints were protected by Alseal AS-202 Fire Retardant Silicone Sealant and were sealed from either the exposed side or both the exposed and unexposed side starting from the western side at 30mm depth from the exposed and unexposed side, 20mm depth from the exposed and unexposed side, 15mm depth from the exposed side only, 25mm depth from the exposed and unexposed side and 6mm depth from the exposed and unexposed side respectively with backing rods placed in the control joint. Service Description Fire Protection System Integrity Insulation A 30mm wide at 30mm deep from both the exposed and unexposed side. Alseal AS-202 Fire Retardant Silicone Sealant No Failure at 301 minutes Failure at 245 minutes Exova Warringtonfire Aus Pty Ltd Unit 2, 409-411 Hammond Road Dandenong, Victoria 3175 Australia Postal Address: PO Box 4282 Dandenong South, Victoria 3164 Australia T: +61 (0)3 9767 1066 E: [email protected] W: www.exova.com

Upload: others

Post on 11-Jan-2022

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AS-202 EN1366-4 Report

© Exova Warringtonfire Aus Pty Ltd 2018

EWFA CERTIFICATE OF TEST CERTIFICATE No.: SFC 53596800c.1 Page 1 of 1

Report Sponsor Summary Issue Date

Alseal Marketing Sdn. Bhd.

Lot 2291, Jalan Kampung Baru,

kg. Baru, Sungai Buloh, 47000 Selangor DE,

Malaysia

25/09/2018

Introduction

The element of construction described below was tested by this laboratory on behalf of the test sponsor in accordance with the stated test standard and achieved the results stated below. Refer to the referenced test report for more information.

Referenced Report Test Date Test Standard

EWFA 43878800g.1 15/06/2017 EN 1366-4:2006

EWFA 53596800d.2 26/03/2018 EN 1366-4:2006

EWFA 53596801d.1 12/06/2018 EN 1366-4:2006

Description of Services

The EWFA 43878800 test assembly comprised a nominal 1584mm long × 1600mm wide × 250mm thick Hebel floor, that was penetrated by three control joints at a nominal length of 1000mm. Starting from the eastern side the joints were 12mm, 30mm and 50mm wide respectively. The control joints were protected by Alseal AS-202 Fire Retardant Silicone Sealant and were sealed from the unexposed side at a depth of half the width of the control joint with a backing rod placed in the control joint.

Service Description Fire Protection System Integrity Insulation

D 50mm wide at 25mm deep from the unexposed side.

Alseal AS-202 Fire Retardant Silicone Sealant

No Failure at 301 minutes

Failure at 148 minutes

E 30mm wide at 15mm deep from the unexposed side.

Alseal AS-202 Fire Retardant Silicone Sealant

No Failure at 301 minutes

Failure at 97 minutes

F 12mm wide at 6mm deep from the unexposed side.

Alseal AS-202 Fire Retardant Silicone Sealant

No Failure at 301 minutes

No Failure at 301 minutes

The EWFA 53596800 test assembly comprised a nominal 1600mm wide × 1600mm long × 250mm thick Hebel wall, that was penetrated by five control joints at a nominal length of 1000mm. Starting from the western side the joints were 30mm, 30mm, 30mm, 50mm and 12mm wide respectively. The control joints were protected by Alseal AS-202 Fire Retardant Silicone Sealant and were sealed from either the exposed side or both the exposed and unexposed side starting from the western side at 30mm depth from the exposed and unexposed side, 20mm depth from the exposed and unexposed side, 15mm depth from the exposed side only, 25mm depth from the exposed and unexposed side and 6mm depth from the exposed and unexposed side respectively with backing rods placed in the control joint.

Service Description Fire Protection System Integrity Insulation

A 30mm wide at 30mm deep from both the exposed and

unexposed side.

Alseal AS-202 Fire Retardant Silicone Sealant

No Failure at 301 minutes

Failure at 245 minutes

Exova Warringtonfire Aus Pty Ltd

Unit 2, 409-411 Hammond Road

Dandenong, Victoria 3175

Australia

Postal Address:

PO Box 4282

Dandenong South, Victoria 3164

Australia

T: +61 (0)3 9767 1066

E: [email protected]

W: www.exova.com

Page 2: AS-202 EN1366-4 Report

© Exova Warringtonfire Aus Pty Ltd 2018

B 30mm wide at 20mm deep from both the exposed and

unexposed side.

Alseal AS-202 Fire Retardant Silicone Sealant

No Failure at 301 minutes

Failure at 150 minutes

C 30mm wide at 15mm deep from both the exposed side

only.

Alseal AS-202 Fire Retardant Silicone Sealant

Failure at 28 minutes

Failure at 22 minutes

D 50mm wide at 25mm deep from both the exposed and

unexposed side.

Alseal AS-202 Fire Retardant Silicone Sealant

Failure at 242 minutes

Failure at 159 minutes

E 12mm wide at 6mm deep

from both the exposed and unexposed side.

Alseal AS-202 Fire Retardant Silicone Sealant

No Failure at 301 minutes

No Failure at 301 minutes

The EWFA 53596801 test assembly comprised a nominal 1200mm wide × 1200mm long × 250mm thick Hebel wall, that was penetrated by one control joint at a nominal length of 1000mm and 30mm wide. The control joint was protected by Alseal AS-202 Fire Retardant Silicone Sealant and were sealed from both the unexposed and exposed at 15mm depth with backing rods placed in the control joint.

Service Description Fire Protection System Integrity Insulation

A 30mm wide at 15mm deep from both the exposed and

unexposed side.

Alseal AS-202 Fire Retardant Silicone Sealant

No Failure at 301 minutes

Failure at 188 minutes

Notes

THIS CERTIFICATE IS PROVIDED FOR GENERAL INFORMATION ONLY AND DOES NOT COMPLY WITH THE REGULATORY REQUIREMENTS FOR EVIDENCE OF COMPLIANCE.

Reference should be made to the relevant test report to determine the applicability of the test result to a proposed installation and for a full description of the tested construction.

The results of these fire tests may be used to assess fire hazard, but it should be recognised that a single test method will not provide a full assessment of fire hazard under all conditions.

TESTING AUTHORITY Exova Warringtonfire Aus Pty Ltd

Address PO Box 4282 DANDENONG SOUTH VIC 3164

Unit 2, 409-411 Hammond Road, DANDENONG VIC 3175

Phone +61 (0) 3 9767 1000

ABN 81 050 241 524

Email / Home Page www.exova.com

Authorisation Prepared By: Reviewed By:

Kai Loh Mandeep Kamal

Page 3: AS-202 EN1366-4 Report

Testing, calibrating, advising

TEST REPORT

Fire resistance test in accordance with EN 1366-4:2006 of five control joints in a Hebel block wall (AAC) protected with Alseal AS-

202 Fire Retardant Silicone Sealant.

EWFA Report No:

53596800d.2

Report Sponsor:

Alseal Marketing Sdn. Bhd.

Lot 2291, Jalan Kampung Baru,

Kg. Baru, Sungai Buloh, 47000 Selangor DE, Malaysia

Test Date:

26 March 2018

Page 4: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 2 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

DOCUMENT REVISION STATUS

Date Issued Issue No Description

6/09/2018 53596800d.1 Initial Issue.

20/09/2018 53596800d.2 Typographical Amendment.

CONTACT INFORMATION

Exova Warringtonfire Aus Pty Ltd - ABN 81 050 241 524

NATA Registered Laboratory

Unit 2, 409-411 Hammond Road Dandenong Victoria 3175 Australia

T: +61 (0)3 9767 1000

SIGNATORIES

Prepared by Reviewed by Reviewed by

Kai Loh Mandeep Kamal Steven Halliday

GENERAL CONDITIONS OF USE

This report may only be reproduced in full without modifications by the report sponsor only. Copies, extracts or abridgments of this report in any form shall not be made distributed or published by other organisations or individuals without the permission in writing from a Director of Exova Warringtonfire Aus Pty Ltd.

Page 5: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 3 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

CONTENTS

1 Construction Details 4 Test Assembly 4 Test Specimens 4 Assembly and Installation Methods 4 Orientation 4

2 Schedule of Components 5

3 Test Procedure 7 Statement of compliance 7 Variations to test method 7 Pre-test conditioning 7 Sampling / Specimen Selection 7 Ambient Temperature 7 Test Duration 7 Instrumentation and Equipment 7

4 Test Measurements 8 Furnace Temperature and Pressure Measurements 8 Specimen Temperatures 8 Observations 8

5 Test Results 9

6 Application of Test Results 10 Test Limitations 10 Variations from the Tested Specimens 10 Uncertainty of measurement 10

APPENDIX 1 DRAWINGS OF TEST ASSEMBLY 11

APPENDIX 2 TEST OBSERVATIONS 13

APPENDIX 3 DIRECT FIELD OF APPLICATION 16 General 16 Orientation 16 Supporting Construction 16 Seal Position 17 Mechanically Induced Movement 17

APPENDIX 4 INSTRUMENTATION POSITIONS 18

APPENDIX 5 TEST DATA 20 Furnace Temperature 20 Furnace Pressure 21 Specimen Temperatures 22 deflection Measurements 27

APPENDIX 6 PHOTOGRAPHS 28

Page 6: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 4 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

1 CONSTRUCTION DETAILS

TEST ASSEMBLY

The test assembly comprised five control joints in a nominal 1600mm wide × 1600mm long × 250mm thick wall constructed of Hebel blocks.

TEST SPECIMENS

The test specimen comprised of five control joints at a nominal length of 1000mm with varying widths.. The control joints were protected by AS-202 Fire Retardant Silicone Sealant. The test assembly is summarised in the table below.

The full description of the specimen is provided in Figures A1.1 to A1.2 and the ‘Schedule of Components’ in Section 2.

Joint Joint Width (mm) Primary Protection Sealant Depth

(mm) Sealant Application

Side

A 30

AS-202 Fire Retardant Silicone Sealant

30 Exposed and

Unexposed Side

B 30 20 Exposed and

Unexposed Side

C 30 15 Exposed Side

D 50 25 Exposed and

Unexposed Side

E 12 6 Exposed and

Unexposed Side

ASSEMBLY AND INSTALLATION METHODS

The Hebel block works completed assembly on the 28 February 2018 and the sealant were applied into the control joint on the 2 March 2018.

ORIENTATION

The assembly was asymmetrical, due to the varying width and application of the sealant.

Page 7: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 5 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

2 SCHEDULE OF COMPONENTS

Item Description

1

Separating Element

Item Name Hebel Blocks

Product Name CSR Hebel Thermoblock AAC Masonry

Size 200mm wide × 250mm deep × 600mm high

Density 558 kg/m3 (measured)

Installation The Hebel blocks were installed as per Figure A1.1.

Sealant

2

Product Name Alseal AS-202 Fire Retardant Silicone Sealant

Density 1245kg/m3 (measured)

Installation

The sealant was applied in the control joint to the specified depth, width and full height of the service. The sealant ended flush with the surface of the Hebel blocks (item 1) at the time of application.

See Appendix 1 for more details.

Backing Rod

3

Product Name Open Cell Polyethylene foam backing rod

Size 50mm wide × 50mm deep (cut to size).

Installation

Installed within the control joint to the specified depth and full height of the service. Sealant (item 2) was then applied over the backing rod.

See Appendix 1 for more details.

SERVICE A

4

Control Joint

Joint Dimensions

30mm wide ×1000mm high

Sealant Application Depth

30mm deep

Installation

The backing rod (item 3) was installed on both the exposed and unexposed side of the Hebel blocks (item 1) at a depth of 30mm from the face of the Hebel blocks. Sealant (item 2) was then applied on both the exposed and unexposed side to a depth of 30mm either side.

See Appendix 1 for more details.

SERVICE B

5

Control Joint

Joint Dimensions

30mm wide ×1000mm high

Sealant Application Depth

20mm deep

Page 8: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 6 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

Item Description

Installation

The backing rod (item 3) was installed on both the exposed and unexposed side of the Hebel blocks (item 1) at a depth of 20mm from the face of the Hebel blocks. Sealant (item 2) was then applied on both the exposed and unexposed side to a depth of 20mm either side.

See Appendix 1 for more details.

SERVICE C

6

Control Joint

Joint Dimensions

30mm wide ×1000mm high

Sealant Application Depth

15mm deep

Installation

The backing rod (item 3) was installed on the exposed side of the Hebel blocks (item 1) at a depth of 15mm from the face of the Hebel blocks. Sealant (item 2) was then applied on the exposed side to a depth of 15mm on the exposed side only.

See Appendix 1 for more details.

SERVICE D

7

Control Joint

Joint Dimensions

50mm wide ×1000mm high

Sealant Application Depth

25mm deep

Installation

The backing rod (item 3) was installed on both the exposed and unexposed side of the Hebel blocks (item 1) at a depth of 25mm from the face of the Hebel blocks. Sealant (item 2) was then applied on both the exposed and unexposed side to a depth of 25mm either side.

See Appendix 1 for more details.

SERVICE E

8

Control Joint

Joint Dimensions

12mm wide ×1000mm high

Sealant Application Depth

6mm deep

Installation

The backing rod (item 3) was installed on both the exposed and unexposed side of the Hebel blocks (item 1) at a depth of 6mm from the face of the Hebel blocks. Sealant (item 2) was then applied on both the exposed and unexposed side to a depth of 6mm either side.

See Appendix 1 for more details.

Page 9: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 7 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

3 TEST PROCEDURE

STATEMENT OF COMPLIANCE

The test was performed in accordance with the requirements of EN 1366-4:2006 subject to the variations below.

VARIATIONS TO TEST METHOD

The pressure was up to 11Pa above the limits prescribed in the standard during the 15-20, 30-35, 55-60, 80-90, 115-155, 220-225, 255-265, and 280-285 minute periods. The pressure and temperature were within the limits for rest of the test duration.

PRE-TEST CONDITIONING

The construction of the specimen was finished on the 2 March 2018 and was tested on 26 March 2018. During this period the test specimen was subject to normal laboratory temperatures and relative humidity conditions.

SAMPLING / SPECIMEN SELECTION

The laboratory was not involved in the sampling or selection of the test specimen for the fire resistance test.

AMBIENT TEMPERATURE

The ambient temperature at the start of the test was 19°C and varied between 19°C and 26°C during the test.

TEST DURATION

The test duration was 301 minutes.

INSTRUMENTATION AND EQUIPMENT

The instrumentation was provided in accordance with EN 1363-1:2012 and as detailed below:

The furnace temperature was measured by four (4) 100mm × 100mm × 0.7mm plate thermocouples with mineral insulated metal sheathed Type K thermocouples with an overall diameter of 1mm with the measuring junction insulated from the sheath. The plate thermocouples included 97mm × 97mm × 10mm inorganic insulating pads.

The unexposed side specimen temperatures were measured by Type K thermocouples with wire diameters less than 0.5mm soldered to 12mm diameter × 0.2mm thick copper discs covered by 30mm × 30mm × 2.0 mm inorganic insulating pads. The thermocouple positions are described in Table A4.1, and are shown on Figure A4.1 in Appendix 4.

A roving thermocouple was available to measure temperatures at positions that appeared hotter than the positions monitored by the fixed thermocouples.

The furnace pressure was measured mid-height of the control joints.

Cotton pads were available during the test to assess the performance under the criteria for integrity.

Deflection measurements were taken from calibrated tapes fixed to the block wall using a Dewalt DW0893 Beam Line Laser at the positions shown of Figure A4.1 in Appendix 4.

Page 10: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 8 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

4 TEST MEASUREMENTS

FURNACE TEMPERATURE AND PRESSURE MEASUREMENTS

Furnace temperature and pressure data are provided in Figure A5.1 and Table A5.1 in Appendix 5.

SPECIMEN TEMPERATURES

Specimen temperature data is provided in A 5.3 and Table A5.2 in Appendix 5.

OBSERVATIONS

A table that includes observations of the significant behaviour of the specimen and details of the occurrence of the various performance criteria specified in EN 1366-4:2006 (EN 1363-1) is provided in Appendix 2. Photographs of the specimen are included in Appendix 6.

Page 11: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 9 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

5 TEST RESULTS

The specimens listed below achieved the following performance when tested in accordance with EN 1366-4:2006, subject to the variations listed in Section 3.

Service Criteria Result

A

Structural Adequacy Not applicable

Integrity No failure at 301 minutes

Insulation Failure at 245 minutes

B

Structural Adequacy Not applicable

Integrity No failure at 301 minutes

Insulation Failure at 150 minutes

C

Structural Adequacy Not applicable

Integrity Failure at 28 minutes

Insulation Failure at 22 minutes

D

Structural Adequacy Not applicable

Integrity Failure at 242 minutes

Insulation Failure at 159 minutes

E

Structural Adequacy Not applicable

Integrity No failure at 301 minutes

Insulation No failure at 301 minutes

Page 12: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 10 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

6 APPLICATION OF TEST RESULTS

TEST LIMITATIONS

The results of this fire test may be used to directly assess fire hazard, but it should be recognized that a single test method will not provide a full assessment of fire hazard under all fire conditions. The results only relate to the behaviour of the specimen of the element of the construction under the particular conditions of the test; they are not intended to be the sole criteria for assessing the potential fire performance of the element in use nor do they necessarily reflect the actual behaviour in fires.

VARIATIONS FROM THE TESTED SPECIMENS

This report details the methods of construction, the test conditions and the results obtained when the specific element of construction described herein was tested following the procedure outlined in EN 1366-4, and where appropriate EN 1363-2. Any significant deviation with respect to size, constructional details, loads, stresses, edge or end conditions, other than those allowed under the field of direct application in the relevant test method, is not addressed by this report. It is recommended that any proposed variation to the tested configuration other than as permitted under the field of direct application specified in Appendix 3 should be referred to the test sponsor in the first instance to obtain appropriate documentary evidence of compliance from Exova Warringtonfire Aus Pty Ltd or another Registered Testing Authority.

UNCERTAINTY OF MEASUREMENT

Because of the nature of fire resistance testing and the consequent difficulty in quantifying the uncertainty of measurement of fire resistance, it is not possible to provide a stated degree of accuracy of the result.

Page 13: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 11 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 1 DRAWINGS OF TEST ASSEMBLY

Figure A1.1: Plan of Test Specimen from the unexposed side.

Page 14: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 12 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

Figure A1.2: Cross-Section A-A

Page 15: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 13 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 2 TEST OBSERVATIONS

The following include observations of the significant behaviour of the specimen.

Time Observations

min sec

Service A

00 00 Fire resistance test commenced, and the ambient temperature was approximately 19°C.

30 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

33 57 Smoke emitting from the top of the specimen.

60 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

64 00 Smoke emitting from the bottom of the specimen.

90 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

120 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

130 00 Smoke emitting from the lower west corner of the specimen.

165 00 Smoke emitting from the lower west corner of the specimen.

180 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

240 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

245 50

TC011 on the control joint, 250mm above mid-height of the specimen, recorded a temperature of 200°C.Failure of insulation in accordance with EN 1366-4:2006 clause

11.1, where the maximum temperature of Thermocouple TC 011 exceeded the initial temperature by more than 180K.

300 00 Specimen continued to maintain integrity in accordance with EN 1366-4:2006.

301 00 Fire resistance test ended.

Service B

00 00 Fire resistance test commenced, and the ambient temperature was approximately 19°C.

30 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

52 02 Smoke emitting from the bottom of the specimen.

60 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

71 00 Smoke emitting from the bottom of the specimen.

82 00 Brownish liquid substance dripping from the lower west corner of the specimen.

90 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

116 00 Slight discolouration on the wall on the top east corner of the specimen.

118 00 Smoke emitting from the lower west corner of the specimen.

120 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

150 15 TC025 on the control joint, 250mm above mid-height of the specimen recorded a

temperature of 200°C.Failure of insulation in accordance with EN 1366-4:2006 clause

Page 16: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 14 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

Time Observations

min sec

11.1, where the maximum temperature of Thermocouple TC 025 exceeded the initial temperature by more than 180K.

180 00 Specimen continued to maintain integrity in accordance with EN 1366-4:2006.

240 00 Specimen continued to maintain integrity in accordance with EN 1366-4:2006.

300 00 Specimen continued to maintain integrity in accordance with EN 1366-4:2006.

241 00 Fire resistance test ended.

Service C

00 00 Fire resistance test commenced, and the ambient temperature was approximately 19°C.

03 29 Smoke emitting from the specimen.

20 28 Increase in smoke activity from the specimen, glowing can be seen on the sealant.

22 00 A 30 second cotton pad test was carried out in accordance with EN 1366-4:2006, clause 2.13.2.2 at bottom of the specimen. No failure.

22 30 The sealant has fallen off at the bottom of the control joint, the furnace can be viewed.

22 40

TC043 on the control joint, 250mm below mid-height of the specimen, recorded a

temperature of 200°C.Failure of insulation in accordance with EN 1366-4:2006 clause

11.1, where the maximum temperature of Thermocouple TC 043 exceeded the initial temperature by more than 180K.

23 43 A 30 second cotton pad test was carried out in accordance with EN 1366-4:2006, clause 2.13.2.2 at top of the specimen. No failure.

24 00 Most of the sealant has fallen off, the furnace can be viewed.

25 02 A 30 second cotton pad test was carried out in accordance with EN 1366-4:2006, clause 2.13.2.2 at top of the specimen. No failure.

26 33 A 30 second cotton pad test was carried out in accordance with EN 1366-4:2006, clause 2.13.2.2 at mid-height of the specimen. No failure.

28 24

A 30 second cotton pad test was carried out at top of the specimen resulting in flaming of the cotton pad. Failure of integrity of the specimen in accordance with EN 1366-4:2006, clause 11.12, where ignition of the cotton had occurred.

301 00 Fire resistance test ended.

Service D

00 00 Fire resistance test commenced, and the ambient temperature was approximately 19°C.

30 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

60 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

75 00 Liquid substance dripping from the lower west corner of the specimen.

90 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

104 00 Smoke emitting from the lower west corner of the specimen.

120 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

159 10 TC057 on the control joint, 250mm below mid-height of the specimen recorded a temperature of 200°C.Failure of insulation in accordance with EN 1366-4:2006 clause 11.1, where the maximum temperature of Thermocouple TC 057 exceeded the initial

Page 17: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 15 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

Time Observations

min sec

temperature by more than 180K.

180 00 Specimen continued to maintain integrity in accordance with EN 1366-4:2006.

200 00 A layer of sealant above TC104 has come off the wall, with smoke emitting. Sealant appears to be expanding out.

228 00 Glowing can be seen on the lower east edge of the specimen.

240 00 Specimen continued to maintain integrity in accordance with EN 1366-4:2006.

242 00

A 30 second cotton pad test was carried out at top of the specimen resulting in flaming of the cotton pad. Failure of integrity of the specimen in accordance with EN 1366-4:2006, clause 11.2, where ignition of the cotton had occurred.

301 00 Fire resistance test ended.

Service E

00 00 Fire resistance test commenced, and the ambient temperature was approximately 19°C.

09 45 Smoke emitting from the top of the specimen.

30 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

60 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

90 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

120 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

180 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

240 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

300 00 Specimen continued to maintain integrity in accordance with EN 1366-4:2006.

301 00 Fire resistance test ended.

Page 18: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 16 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 3 DIRECT FIELD OF APPLICATION

Reference Note: References in this section refer to those found in the standard and not this report.

GENERAL

EN 1366-4:2006 indicates that the results of the fire test contained in the test report are directly applicable without reference to the testing authority to similar constructions where one or more of the changes have been made:

ORIENTATION

The field of application regarding the orientation of the linear joint is given in Table 1. The possible orientation of linear joints (A to E) and of the specimens in the test (A to C) is illustrated in Figure 12.

Table 1 – Field of application regarding orientation

Tested Orientation Application

A A, D, E a

B B

C C, D b

a Orientation E will only be covered by test orientation A if shear movement was chosen and one face of the joint was fixed and the other face was removed.

b Orientation D will only be covered by test orientation C if shear movement was chosen and one face of the joint was fixed and the other face was moved.

Key A linear joint in a horizontal test construction B vertical linear joint in a vertical test construction C horizontal linear joint in a vertical test construction D horizontal wall joint abutting a floor, ceiling or roof E horizontal floor joint abutting a wall Table 1 only applies when both the supporting construction and the location of the seal within the linear joint remain unchanged. See 13.3

SUPPORTING CONSTRUCTION

Results obtained with autoclaved aerated concrete standard supporting constructions apply to concrete, block work and masonry separating elements of a thickness and density equal to or greater than that tested. Results obtained with normal concrete standard supporting constructions apply to concrete and block work separating elements of a thickness and density equal to or greater than that tested. Results obtained with timber standard supporting construction apply to timber separating elements of a thickness and density equal to or greater than that tested. Results obtained with the steel angle standard supporting construction as described in 7.2.2.3 apply to separating element constructions made of metals with a melting point higher than 1000 °C. Results obtained with a combination of a standard supporting construction as described in 7.2.2.1 and a standard supporting construction as described in 7.2.2.3 apply to concrete, block work and masonry separating elements of a thickness and density equal to or greater than that tested forming one joint face and separating element constructions made of metals with a melting point higher than 1000 °C forming the other joint face. A fire resistance time obtained on a specific non-standard supporting construction applies only to that particular construction.

Page 19: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 17 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

SEAL POSITION

Test results are valid only for the position (see Figure 3) in which the seal was tested, except that where the linear joint seal was fitted flush with the surface of the supporting construction and is exposed to the fire (see Figure 3, test specimen B), the result will also be applicable to test specimen C and E.

MECHANICALLY INDUCED MOVEMENT

If the movement capability of a linear joint seal is less than 7,5 %, the linear joint seal may be tested without mechanically induced movement and the result applies to the movement capability reported. Results obtained with mechanically induced movement prior to or during the tests are only valid for the movement capability tested or lower.

Page 20: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 18 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 4 INSTRUMENTATION POSITIONS

Figure A4.1: Plan view of thermocouple and deflection locations.

Page 21: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 19 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

Table A4.1: Thermocouple Locations

Service T/C No. Description

A

011 On the sealant, 250mm from the top of the control joint.

012 On the sealant, 500mm from the top of the control joint.

013 On the sealant, 750mm from the top of the control joint.

014 15mm west of the sealant, 250mm from the top of the control joint.

015 15mm west of the sealant, 750mm from the top of the control joint.

016 15mm east of the sealant, 250mm from the top of the control joint.

017 15mm east of the sealant, 750mm from the top of the control joint.

B

025 On the sealant, 250mm from the top of the control joint.

026 On the sealant, 500mm from the top of the control joint.

027 On the sealant, 750mm from the top of the control joint.

028 15mm west of the sealant, 250mm from the top of the control joint.

029 15mm west of the sealant, 750mm from the top of the control joint.

030 15mm east of the sealant, 250mm from the top of the control joint.

031 15mm east of the sealant, 750mm from the top of the control joint.

C

041 On the sealant, 250mm from the top of the control joint.

042 On the sealant, 500mm from the top of the control joint.

043 On the sealant, 750mm from the top of the control joint.

044 15mm west of the sealant, 250mm from the top of the control joint.

045 15mm west of the sealant, 750mm from the top of the control joint.

046 15mm east of the sealant, 250mm from the top of the control joint.

047 15mm east of the sealant, 750mm from the top of the control joint.

D

055 On the sealant, 250mm from the top of the control joint.

056 On the sealant, 500mm from the top of the control joint.

057 On the sealant, 750mm from the top of the control joint.

058 15mm west of the sealant, 250mm from the top of the control joint.

059 15mm west of the sealant, 750mm from the top of the control joint.

060 15mm east of the sealant, 250mm from the top of the control joint.

101 15mm east of the sealant, 750mm from the top of the control joint.

E

125 15mm west of the sealant, 250mm from the top of the control joint.

126 15mm west of the sealant, 750mm from the top of the control joint.

127 15mm east of the sealant, 250mm from the top of the control joint.

128 15mm east of the sealant, 750mm from the top of the control joint.

Table A4.2: Deflection Locations

Ref Description

D1 Mid-height of the specimen, 100mm west of service A.

D2 Mid-height of the specimen, 100mm west of service B.

D3 Mid-height of the specimen, 100mm west of service C.

D4 Mid-height of the specimen, 100mm west of service D.

D5 Mid-height of the specimen, 100mm east of service D.

D6 Mid-height of the specimen, 100mm west of service E.

D7 Mid-height of the specimen, 100mm east of service E.

Page 22: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 20 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 5 TEST DATA

FURNACE TEMPERATURE

Figure A5.1: Furnace Temperatures vs. Time

0

200

400

600

800

1000

1200

0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300

Tem

pera

ture

(°C

)

Time (Minutes)

EN 1363-1 Mean Furn Max Furn Min Furn

Page 23: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 21 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

FURNACE PRESSURE

The furnace pressure was measured at mid-height of the control joints.

Table A5.1: Pressure

Time

(minutes)

Pressure (Pa)

Avg.

Time

(minutes)

Pressure (Pa)

Avg.

Time

(minutes)

Pressure (Pa)

Avg.

5-10 18 105-110 15 205-210 14

10-15 17 110-115 17 210-215 14

15-20 25 115-120 19 215-220 13

20-25 13 120-125 24 220-225 18

25-30 14 125-130 27 225-230 19

30-35 19 130-135 21 230-235 15

35-40 16 135-140 23 235-240 15

40-45 14 140-145 27 240-245 16

45-50 16 145-150 29 245-250 16

50-55 17 150-155 27 250-255 15

55-60 19 155-160 12 255-260 14

60-65 15 160-165 14 260-265 27

65-70 14 165-170 16 265-270 20

70-75 16 170-175 17 270-275 14

75-80 17 175-180 18 275-280 14

80-85 23 180-185 18 280-285 16

85-90 20 185-190 17 285-290 19

90-95 16 190-195 16 290-295 18

95-100 13 195-200 15 295-230 16

100-105 15 200-205 14

Page 24: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 22 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

SPECIMEN TEMPERATURES

Figure A5.2: Service A. Temperature vs. time

Figure A5.3: Service B. Temperature vs. time

0

50

100

150

200

250

300

0 30 60 90 120 150 180 210 240 270 300

Tem

pera

ture

(°C

)

Time (minutes)

011 012 013 014 015 016 017

0

100

200

300

400

500

600

0 30 60 90 120 150 180 210 240 270 300

Tem

pera

ture

(°C

)

Time (minutes)

025 026 027 028 029 030 031

Page 25: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 23 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

Figure A5.4: Service C. Temperature vs. Time

(TC041 malfunctioned after the 204 minute period, TC042 malfunctioned after the 26 minute period, TC043 malfunctioned after the 211 minute period, TC044 and TC045 malfunctioned after the 31 minute

period.)

Figure A5.5: Service D. Temperatures vs. Time

(TC055, TC056, TC057 malfunctioned after the 240 minute period.)

0

200

400

600

800

1000

1200

0 30 60 90 120 150 180 210 240 270 300

Tem

pera

ture

(°C

)

Time (minutes)

041 042 043 044

045 046 047 Integrity Failure

0

50

100

150

200

250

300

350

0 30 60 90 120 150 180 210 240 270 300

Tem

pera

ture

(°C

)

Time (minutes)

055 056 057 058

059 060 101 Integrity Failure

Page 26: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 24 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

Figure A5.6: Service E Temperature vs. Time

0

20

40

60

80

100

120

140

160

0 30 60 90 120 150 180 210 240 270 300

Tem

pera

ture

(°C

)

Time (minutes)

125 126 127 128

Page 27: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 25 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

Table A5.2: Test Specimen Temperatures

Service T/C No. Description2

Temp (°C) at t (minutes) Limit1 (Mins)

t=0 t=60 t=120 t=180 t=240 t=300

A

011 On the sealant, 250mm from the top of the control joint.

20 39 123 162 196 242 245

012 On the sealant, 500mm from the top of the control joint.

19 27 107 138 168 187 -

013 On the sealant, 750mm from the top of the control joint.

19 23 105 141 175 214 279

014 15mm west of the sealant, 250mm from the top of the control joint.

20 29 84 127 166 207 290

015 15mm west of the sealant, 750mm from the top of the control joint.

19 21 78 105 140 177 -

016 15mm east of the sealant, 250mm from the top of the control joint.

20 28 88 131 171 211 282

017 15mm east of the sealant, 750mm from the top of the control joint.

19 22 77 101 138 176 -

B

025 On the sealant, 250mm from the top of the control joint.

20 115 180 212 389 426 150

026 On the sealant, 500mm from the top of the control joint.

19 106 168 204 377 448 174

027 On the sealant, 750mm from the top of the control joint.

19 102 176 208 358 412 163

028 15mm west of the sealant, 250mm from the top of the control joint.

20 75 127 183 255 306 198

029 15mm west of the sealant, 750mm from the top of the control joint.

19 64 124 178 250 298 206

030 15mm east of the sealant, 250mm from the top of the control joint.

20 87 163 227 318 368 152

031 15mm east of the sealant, 750mm from the top of the control joint.

20 68 120 172 232 292 215

C

041 On the sealant, 250mm from the top of the control joint.

19 871 967 1051 # # 24

042 On the sealant, 500mm from the top of the control joint.

19 # # # # # 24

043 On the sealant, 750mm from the top of the control joint.

19 892 990 1026 # # 22

044 15mm west of the sealant, 250mm from the top of the control joint.

19 # # # # # 26

045 15mm west of the sealant, 750mm from the top of the control joint.

19 # # # # # 27

046 15mm east of the sealant, 250mm from the top of the control joint.

19 121 140 179 200 237 238

047 15mm east of the sealant, 750mm from the top of the control joint.

19 158 203 255 288 342 117

D

055 On the sealant, 250mm from the top of the control joint.

19 81 150 211 280 # 168

056 On the sealant, 500mm from the top of the control joint.

19 58 136 190 219 # 192

Page 28: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 26 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

Notes 1 Limit time is the time to the nearest whole minute, rounded down to the nearest minute, at which the temperature recorded by the thermocouple does not rise by more than 180K above the initial temperature.

2 Refer to Appendix 4 for locations of thermocouples as only a generic description is included in the table.

3 No insulation failure prior to thermocouple failure.

# Thermocouple failure

* Service failure

‘-’ Under limit column indicates the temperature limit was not exceeded during the test period or up until the time of integrity failure if a failure occurred.

057 On the sealant, 750mm from the top of the control joint.

19 71 164 215 275 180 159

058 15mm west of the sealant, 250mm from the top of the control joint.

19 59 129 201 278 286 179

059 15mm west of the sealant, 750mm from the top of the control joint.

19 48 129 200 257 294 180

060 15mm east of the sealant, 250mm from the top of the control joint.

19 54 113 172 233 244 204

101 15mm east of the sealant, 750mm from the top of the control joint.

20 48 137 207 275 298 174

E

125 15mm west of the sealant, 250mm from the top of the control joint.

20 41 62 80 105 126 -

126 15mm west of the sealant, 750mm from the top of the control joint.

20 35 53 70 78 103 -

127 15mm east of the sealant, 250mm from the top of the control joint.

20 48 71 85 116 148 -

128 15mm east of the sealant, 750mm from the top of the control joint.

19 36 53 65 77 102 -

Page 29: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 27 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

DEFLECTION MEASUREMENTS

Figure A5.7: Deflection of the wall vs. Time

0

1

2

3

4

5

6

0 50 100 150 200 250 300

De

fle

ctio

n (

mm

)

Time (minutes)

D1 D2 D3 D4 D5 D6 D7

Page 30: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 28 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 6 PHOTOGRAPHS

Figure A6.1: Unexposed face of specimen before commencement of the fire-resistance test

Figure A6.2: Exposed face of specimen before commencement of the fire-resistance test

East West

West East

A B C D E

D E C B A

Page 31: AS-202 EN1366-4 Report

Report No. 53596800d.2 Page 29 of 29

© Exova Warringtonfire Aus Pty Ltd 2018

Figure A6.3: Unexposed face of specimen at the end of the test.

Figure A6.4: Exposed face of specimen at the end of the test.

East

East

West

West

Page 32: AS-202 EN1366-4 Report

Testing, calibrating, advising

TEST REPORT

Fire resistance test in accordance with EN 1366-4:2006 of a control joint in a Hebel

block wall (AAC) protected with Alseal AS-202 Fire Retardant Silicone Sealant.

EWFA Report No:

53596801d.1

Report Sponsor:

Alseal Marketing Sdn. Bhd.

Lot 2291, Jalan Kampung Baru,

Kg. Baru, Sungai Buloh, 47000 Selangor DE, Malaysia

Test Date:

12 June 2018

Page 33: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 2 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

DOCUMENT REVISION STATUS

Date Issued Issue No Description

6/09/2018 53596801d.1 Initial Issue

CONTACT INFORMATION

Exova Warringtonfire Aus Pty Ltd - ABN 81 050 241 524

NATA Registered Laboratory

Unit 2, 409-411 Hammond Road Dandenong Victoria 3175 Australia

T: +61 (0)3 9767 1000

SIGNATORIES

Prepared by Reviewed by Reviewed by

Durai Krish Mandeep Kamal Steven Halliday

GENERAL CONDITIONS OF USE

This report may only be reproduced in full without modifications by the report sponsor only. Copies, extracts or abridgments of this report in any form shall not be made distributed or published by other organisations or individuals without the permission in writing from a Director of Exova Warringtonfire Aus Pty Ltd.

Page 34: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 3 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

CONTENTS

1 Construction Details 4 Test Assembly 4 Test Specimens 4 Assembly and Installation Methods 4 Orientation 4

2 Schedule of Components 5

3 Test Procedure 6 Statement of compliance 6 Variations to test method 6 Pre-test conditioning 6 Sampling / Specimen Selection 6 Ambient Temperature 6 Test Duration 6 Instrumentation and Equipment 6

4 Test Measurements 7 Furnace Temperature and Pressure Measurements 7 Specimen Temperatures 7 Observations 7

5 Test Results 8

6 Application of Test Results 9 Test Limitations 9 Variations from the Tested Specimens 9 Uncertainty of measurement 9

APPENDIX 1 DRAWINGS OF TEST ASSEMBLY 10

APPENDIX 2 TEST OBSERVATIONS 11

APPENDIX 3 DIRECT FIELD OF APPLICATION 12 General 12 Orientation 12 Supporting Construction 12 Seal Position 13 Mechanically Induced Movement 13

APPENDIX 4 INSTRUMENTATION POSITIONS 14

APPENDIX 5 TEST DATA 16 Furnace Temperature 16 Furnace Pressure 17 Specimen Temperatures 18 deflection Measurements 20

APPENDIX 6 PHOTOGRAPHS 21

Page 35: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 4 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

1 CONSTRUCTION DETAILS

TEST ASSEMBLY

The test assembly comprised one control joint in a nominal 1200mm wide × 1200mm long × 250mm thick wall constructed of Hebel blocks.

TEST SPECIMENS

The test specimen comprised of one control joint at a nominal length of 1000mm × 30mm wide. The control joint was protected by AS-202 Fire Retardant Silicone Sealant. The test assembly is summarised in the table below.

The full description of the specimen is provided in Figures A1.1 to A1.2 and the ‘Schedule of Components’ in Section 2.

Joint Joint Width (mm) Primary Protection Sealant Depth

(mm) Sealant Application

Side

1 30 AS-202 Fire Retardant

Silicone Sealant 15

Exposed and Unexposed Side

ASSEMBLY AND INSTALLATION METHODS

The Hebel block works completed assembly and the sealant were applied into the control joint on the 14 May 2018.

ORIENTATION

The assembly was symmetrical.

Page 36: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 5 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

2 SCHEDULE OF COMPONENTS

Item Description

1

Separating Element

Item Name Hebel Blocks

Product Name CSR Hebel Thermoblock AAC Masonry

Size 200mm wide × 250mm deep × 600mm high

Density 558 kg/m3 (measured)

Installation The Hebel blocks were installed as per Figure A1.1.

Sealant

2

Product Name Alseal AS-202 Fire Retardant Silicone Sealant

Density 1245kg/m3 (measured)

Installation

The sealant was applied in the control joint to the specified depth, width and full height of the service. The sealant ended flush with the surface of the Hebel blocks (item 1) at the time of application.

See Appendix 1 for more details.

Backing Rod

3

Product Name Open Cell Polyethylene foam backing rod

Size 50mm wide × 50mm deep (cut to size).

Installation

Installed within the control joint to the specified depth and full height of the service. Sealant (item 2) was then applied over the backing rod.

See Appendix 1 for more details.

SERVICE

4

Control Joint

Joint Dimensions

30mm wide ×1000mm high

Sealant Application Depth

15mm deep

Installation

The backing rod (item 3) was installed on both the exposed and unexposed side of the Hebel blocks (item 1) at a depth of 15mm from the face of the Hebel blocks. Sealant (item 2) was then applied on both the exposed and unexposed side to a depth of 15mm either side.

See Appendix 1 for more details.

Page 37: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 6 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

3 TEST PROCEDURE

STATEMENT OF COMPLIANCE

The test was performed in accordance with the requirements of EN 1366-4:2006 subject to the variations below.

VARIATIONS TO TEST METHOD

The pressure was up to 3Pa above the limits prescribed in the standard during the 45-50 and 180-185 minute period. The pressure and temperature were within the limits for rest of the test duration.

PRE-TEST CONDITIONING

The construction of the specimen was finished on the 14 May 2018 and was tested on 12 June 2018. During this period the test specimen was subject to normal laboratory temperatures and relative humidity conditions.

SAMPLING / SPECIMEN SELECTION

The laboratory was not involved in the sampling or selection of the test specimen for the fire resistance test.

AMBIENT TEMPERATURE

The ambient temperature at the start of the test was 16°C and varied between 16°C and 19°C during the test.

TEST DURATION

The test duration was 301 minutes.

INSTRUMENTATION AND EQUIPMENT

The instrumentation was provided in accordance with EN 1363-1:2012 and as detailed below:

The furnace temperature was measured by four (4) 100mm × 100mm × 0.7mm plate thermocouples with mineral insulated metal sheathed Type K thermocouples with an overall diameter of 1mm with the measuring junction insulated from the sheath. The plate thermocouples included 97mm × 97mm × 10mm inorganic insulating pads.

The unexposed side specimen temperatures were measured by Type K thermocouples with wire diameters less than 0.5mm soldered to 12mm diameter × 0.2mm thick copper discs covered by 30mm × 30mm × 2.0 mm inorganic insulating pads. The thermocouple positions are described in Table A4.1, and are shown on Figure A4.1 in Appendix 4.

A roving thermocouple was available to measure temperatures at positions that appeared hotter than the positions monitored by the fixed thermocouples.

The furnace pressure was measured mid-height of the control joint.

Cotton pads were available during the test to assess the performance under the criteria for integrity.

Deflection measurements were taken from calibrated tapes fixed to the block wall using a Dewalt DW0893 Beam Line Laser at the positions shown of Figure A4.1 in Appendix 4.

Page 38: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 7 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

4 TEST MEASUREMENTS

FURNACE TEMPERATURE AND PRESSURE MEASUREMENTS

Furnace temperature and pressure data are provided in Figure A5.1 and Table A5.1 in Appendix 5.

SPECIMEN TEMPERATURES

Specimen temperature data is provided in A 5.3 and Table A5.2 in Appendix 5.

OBSERVATIONS

A table that includes observations of the significant behaviour of the specimen and details of the occurrence of the various performance criteria specified in EN 1366-4:2006 (EN 1363-1) is provided in Appendix 2. Photographs of the specimen are included in Appendix 6.

Page 39: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 8 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

5 TEST RESULTS

The specimens listed below achieved the following performance when tested in accordance with EN 1366-4:2006, subject to the variations listed in Section 3.

Service Criteria Result

A

Structural Adequacy Not applicable

Integrity No failure at 301 minutes

Insulation Failure at 188 minutes

Page 40: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 9 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

6 APPLICATION OF TEST RESULTS

TEST LIMITATIONS

The results of this fire test may be used to directly assess fire hazard, but it should be recognized that a single test method will not provide a full assessment of fire hazard under all fire conditions. The results only relate to the behaviour of the specimen of the element of the construction under the particular conditions of the test; they are not intended to be the sole criteria for assessing the potential fire performance of the element in use nor do they necessarily reflect the actual behaviour in fires.

VARIATIONS FROM THE TESTED SPECIMENS

This report details the methods of construction, the test conditions and the results obtained when the specific element of construction described herein was tested following the procedure outlined in EN 1366-4, and where appropriate EN 1363-2. Any significant deviation with respect to size, constructional details, loads, stresses, edge or end conditions, other than those allowed under the field of direct application in the relevant test method, is not addressed by this report. It is recommended that any proposed variation to the tested configuration other than as permitted under the field of direct application specified in Appendix 3 should be referred to the test sponsor in the first instance to obtain appropriate documentary evidence of compliance from Exova Warringtonfire Aus Pty Ltd or another Registered Testing Authority.

UNCERTAINTY OF MEASUREMENT

Because of the nature of fire resistance testing and the consequent difficulty in quantifying the uncertainty of measurement of fire resistance, it is not possible to provide a stated degree of accuracy of the result.

Page 41: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 10 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 1 DRAWINGS OF TEST ASSEMBLY

Figure A1.1: Plan of Test Specimen from the unexposed side.

Figure A1.2: Cross-Section A-A

Page 42: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 11 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 2 TEST OBSERVATIONS

The following include observations of the significant behaviour of the specimen.

Time Observations

min sec

Service A

00 00 Fire resistance test commenced, and the ambient temperature was approximately 16°C.

14 03 Smoke emitting from the bottom of the specimen.

21 10 Smoke emitting become lean.

30 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

60 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

63 20 Sealant beginning to bulge.

70 00 Sealant continued to bulge up to 75% of the surface from the top to bottom.

90 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

120 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

180 00 Specimen continued to maintain integrity and insulation in accordance with EN 1366-4:2006.

188 25

TC013 on the control joint, 250mm lower mid-height of the specimen, recorded a

temperature of 195°C. Failure of insulation in accordance with EN 1366-4:2006

clause 11.1, where the maximum temperature of Thermocouple TC013 exceeded the initial temperature by more than 180K.

225 00 Slight charring of sealant and smoke emission both at mid-height of the specimen near the east edge.

240 00 Specimen continued to maintain integrity in accordance with EN 1366-4:2006.

245 00 Glowing can be seen at mid-height of the specimen near the east edge.

260 00 Slight discoloration at Hebel block near the lower west side of the specimen.

275 00 Sealant discoloration and changing into white colour.

278 20 A 30 second cotton pad test was carried out in accordance with EN 1366-1:2006, clause 2.13.2.2 at bottom of the specimen. No failure.

296 40 A 30 second cotton pad test was carried out in accordance with EN 1366-1:2006, clause 2.13.2.2 at bottom of the specimen. No failure.

300 00 Specimen continued to maintain integrity in accordance with EN 1366-4:2006.

301 00 Fire resistance test ended.

Page 43: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 12 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 3 DIRECT FIELD OF APPLICATION

Reference Note: References in this section refer to those found in the EN 1366-4:2006 standard and not this report.

GENERAL

The EN 1366-4:2006 standard indicates that the results of the fire test contained in the test report are directly applicable without reference to the testing authority to similar constructions where one or more of the changes have been made:

ORIENTATION

The field of application regarding the orientation of the linear joint is given in Table 1. The possible orientation of linear joints (A to E) and of the specimens in the test (A to C) is illustrated in Figure 12.

Table 1 – Field of application regarding orientation

Tested Orientation Application

A A, D, E a

B B

C C, D b

a Orientation E will only be covered by test orientation A if shear movement was chosen and one face of the joint was fixed and the other face was removed.

b Orientation D will only be covered by test orientation C if shear movement was chosen and one face of the joint was fixed and the other face was moved.

Key A linear joint in a horizontal test construction B vertical linear joint in a vertical test construction C horizontal linear joint in a vertical test construction D horizontal wall joint abutting a floor, ceiling or roof E horizontal floor joint abutting a wall Table 1 only applies when both the supporting construction and the location of the seal within the linear joint remain unchanged. See 13.3

SUPPORTING CONSTRUCTION

Results obtained with autoclaved aerated concrete standard supporting constructions apply to concrete, block work and masonry separating elements of a thickness and density equal to or greater than that tested. Results obtained with normal concrete standard supporting constructions apply to concrete and block work separating elements of a thickness and density equal to or greater than that tested. Results obtained with timber standard supporting construction apply to timber separating elements of a thickness and density equal to or greater than that tested. Results obtained with the steel angle standard supporting construction as described in 7.2.2.3 apply to separating element constructions made of metals with a melting point higher than 1000 °C. Results obtained with a combination of a standard supporting construction as described in 7.2.2.1 and a standard supporting construction as described in 7.2.2.3 apply to concrete, block work and masonry separating elements of a thickness and density equal to or greater than that tested forming one joint face and separating element constructions made of metals with a melting point higher than 1000 °C forming the other joint face. A fire resistance time obtained on a specific non-standard supporting construction applies only to that particular construction.

Page 44: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 13 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

SEAL POSITION

Test results are valid only for the position (see Figure 3) in which the seal was tested, except that where the linear joint seal was fitted flush with the surface of the supporting construction and is exposed to the fire (see Figure 3, test specimen B), the result will also be applicable to test specimen C and E.

MECHANICALLY INDUCED MOVEMENT

If the movement capability of a linear joint seal is less than 7,5 %, the linear joint seal may be tested without mechanically induced movement and the result applies to the movement capability reported. Results obtained with mechanically induced movement prior to or during the tests are only valid for the movement capability tested or lower.

Page 45: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 14 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 4 INSTRUMENTATION POSITIONS

Figure A4.1: Plan view of thermocouple and deflection locations.

Page 46: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 15 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

Table A4.1: Thermocouple Locations

Service T/C No. Description

A

011 On the sealant, 250mm from the top of the control joint.

012 On the sealant, 500mm from the top of the control joint.

013 On the sealant, 750mm from the top of the control joint.

014 15mm west of the sealant, 250mm from the top of the control joint.

015 15mm west of the sealant, 750mm from the top of the control joint.

016 15mm east of the sealant, 250mm from the top of the control joint.

017 15mm east of the sealant, 750mm from the top of the control joint.

Table A4.2: Deflection Locations

Ref Description

VE Mid-height of the specimen, 100mm east of service.

VW Mid-height of the specimen, 100mm west of service.

Page 47: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 16 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 5 TEST DATA

FURNACE TEMPERATURE

Figure A5.1: Furnace Temperatures vs. Time

0

200

400

600

800

1000

1200

0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300

Tem

pera

ture

(°C

)

Time (Minutes)

EN 1363.1 Mean Furn Max Furn Min Furn

Page 48: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 17 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

FURNACE PRESSURE

The furnace pressure was measured at mid-height of the control joint.

Table A5.1: Pressure

Time

(minutes)

Pressure (Pa)

Avg.

Time

(minutes)

Pressure (Pa)

Avg.

Time

(minutes)

Pressure (Pa)

Avg.

5-10 18 105-110 15 205-210 15

10-15 17 110-115 16 210-215 15

15-20 17 115-120 16 215-220 14

20-25 17 120-125 17 220-225 14

25-30 15 125-130 14 225-230 14

30-35 15 130-135 15 230-235 15

35-40 16 135-140 16 235-240 16

40-45 16 140-145 17 240-245 16

45-50 21 145-150 17 245-250 16

50-55 15 150-155 16 250-255 16

55-60 16 155-160 15 255-260 16

60-65 16 160-165 16 260-265 15

65-70 16 165-170 17 265-270 15

70-75 15 170-175 16 270-275 15

75-80 16 175-180 16 275-280 15

80-85 16 180-185 19 280-285 15

85-90 14 185-190 14 285-290 14

90-95 15 190-195 14 290-295 15

95-100 15 195-200 14 295-300 14

100-105 15 200-205 16

Page 49: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 18 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

SPECIMEN TEMPERATURES

Figure A5.2: Test Specimen. Temperature vs. time

Figure A5.3: Test Specimen. Temperature vs. time

0

100

200

300

400

500

600

700

0 30 60 90 120 150 180 210 240 270 300

Tem

pera

ture

(°C

)

Time (minutes)

011 012 013

0

50

100

150

200

250

300

0 30 60 90 120 150 180 210 240 270 300

Tem

pera

ture

(°C

)

Time (minutes)

014 015 016 017

Page 50: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 19 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

Table A5.2: Test Specimen Temperatures

Notes 1 Limit time is the time to the nearest whole minute, rounded down to the nearest

minute, at which the temperature recorded by the thermocouple does not rise by more than 180K above the initial temperature.

2 Refer to Appendix 4 for locations of thermocouples as only a generic description is included in the table.

3 No insulation failure prior to thermocouple failure.

# Thermocouple failure

* Service failure

‘-’ Under limit column indicates the temperature limit was not exceeded during the test period or up until the time of integrity failure if a failure occurred.

Service T/C No. Description2

Temp (°C) at t (minutes) Limit1 (Mins)

t=0 t=30 t=60 t=90 t=120 t=180 t=240 t=300

A

011 On the sealant, 250mm from the top of the control joint.

15 16 73 101 138 191 225 375 198

012 On the sealant, 500mm from the top of the control joint.

15 16 66 99 124 181 224 548 205

013 On the sealant, 750mm from the top of the control joint.

15 16 47 86 123 190 236 354 188

014 15mm west of the sealant, 250mm from the top of the control joint

15 15 49 84 90 137 199 269 237

015 15mm west of the sealant, 750mm from the top of the control joint.

472 15 33 78 86 126 185 241 235

016 15mm east of the sealant, 250mm from the top of the control joint.

15 15 46 85 91 114 176 246 257

017 15mm east of the sealant, 750mm from the top of the control joint.

15 15 34 81 89 118 177 240 258

Page 51: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 20 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

DEFLECTION MEASUREMENTS

Figure A5.4: Deflection of the wall vs. Time

-2

-1.5

-1

-0.5

0

0.5

1

1.5

2

0 50 100 150 200 250 300

Deflection (

mm

)

Time (minutes)

VE VW

Page 52: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 21 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 6 PHOTOGRAPHS

Figure A6.1: Unexposed face of specimen before commencement of the fire-resistance test

Figure A6.2: Exposed face of specimen before commencement of the fire-resistance test

East West

West East D

Page 53: AS-202 EN1366-4 Report

Report No. 53596801d.1 Page 22 of 22

© Exova Warringtonfire Aus Pty Ltd 2018

Figure A6.3: Unexposed face of specimen at the end of the test.

Figure A6.4: Exposed face of specimen at the end of the test.

East West

West East

Page 54: AS-202 EN1366-4 Report

Testing, calibrating, advising

TEST REPORT

Fire resistance test in accordance with EN 1366-4: 2006 of three control joints in a

Hebel panel Floor (AAC) protected with Alseal AS-202 Fire Retardant Silicone

Sealant.

EWFA Report No:

43878800g.1

Report Sponsor:

Alseal Marketing Sdn. Bhd.

Lot 2291, Jalan Kampung Baru,

Kg Baru, Sungai Buloh, 47000, Selangor DE, Malaysia

Test Date:

15 June 2017

Page 55: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 2 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

DOCUMENT REVISION STATUS

Date Issued Issue No Description

6/09/2018 43878800g.1 Initial Issue

CONTACT INFORMATION

Exova Warringtonfire Aus Pty Ltd - ABN 81 050 241 524

NATA Registered Laboratory

Unit 2, 409-411 Hammond Road Dandenong Victoria 3175 Australia

T: +61 (0)3 9767 1000

SIGNATORIES

Prepared by Reviewed by

Patrick Chan Steven Halliday

GENERAL CONDITIONS OF USE

This report may only be reproduced in full without modifications by the report sponsor only. Copies, extracts or abridgments of this report in any form shall not be made distributed or published by other organisations or individuals without the permission in writing from a Director of Exova Warringtonfire Aus Pty Ltd.

Page 56: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 3 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

CONTENTS

1 Construction Details 4 Test Assembly 4 Test Specimens 4 Assembly and Installation Methods 4 Orientation 4

2 Schedule of Components 5

3 Test Procedure 7 Statement of compliance 7 Variations to test method 7 Pre-test conditioning 7 Sampling / Specimen Selection 7 Ambient Temperature 7 Test Duration 7 Instrumentation and Equipment 7

4 Test Measurements 8 Furnace Temperature and Pressure Measurements 8 Specimen Temperatures 8 Observations 8

5 Test Results 8

6 Application of Test Results 9 Test Limitations 9 Variations from the Tested Specimens 9 Uncertainty of measurement 9

APPENDIX 1 DRAWINGS OF TEST ASSEMBLY 10

APPENDIX 2 TEST OBSERVATIONS 11

APPENDIX 3 DIRECT FIELD OF APPLICATION 13 General 13 Orientation 13 Supporting Construction 13 Seal Position 14 Mechanically Induced Movement 14

APPENDIX 4 INSTRUMENTATION POSITIONS 15

APPENDIX 5 TEST DATA 17 Furnace Temperature 17 Furnace Pressure 18 Specimen Temperatures 19

APPENDIX 6 PHOTOGRAPHS 26

Page 57: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 4 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

1 CONSTRUCTION DETAILS

TEST ASSEMBLY

The test assembly comprised of six control joints in a nominally 1584mm wide × 1600mm long × 250mm thick floor constructed of Hebel panels.

TEST SPECIMENS

The Hebel floor was penetrated by three horizontal control joints at a nominal length of 1000mm. Starting on the east were control joints that were 12mm, 30mm, and 50mm wide, respectively, that were protected by Alseal AS-202 Fire Retardant Silicone Sealant. The control joints were sealed from the unexposed side at a depth of half the width of the control joint with a backing rod placed in the control joint.

The full description of the specimen is provided in Figures A1.1 to A1.2 and the ‘Schedule of Components’ in Section 2.

ASSEMBLY AND INSTALLATION METHODS

The Hebel blocks were cut into sections and installed into a restraint frame by representative of EWFA. The backing rods and sealant were installed by representative of EWFA on the 15th of May 2017.

ORIENTATION

The assembly was asymmetrical. The control joints were only protected on the unexposed side only.

Page 58: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 5 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

2 SCHEDULE OF COMPONENTS

Item Description

CONTROL JOINTS

1

SERVICE D

Dimensions The control joint was nominally 50mm wide × 1000mm long.

Sealant Fire Retardant Silicone Sealant (item 7)

Backing Rod Open Cell (item 5)

Installation

A backing rod the full length of the control joint was installed on the unexposed side at a depth of 25mm. The sealant was then applied on the unexposed side at a depth of 25mm.

The sealant was installed such that the surface was flush with the face of the Hebel blocks (item 7) at the time of the installation.

2

SERVICE E

Dimensions The control joint was nominally 30mm wide × 1000mm high.

Sealant Fire Retardant Silicone Sealant (item 7)

Backing Rod Close Cell (item 6)

Installation

A backing rod the full length of the control joint was installed on the unexposed side at a depth of 15mm. The sealant was then applied on the unexposed side at a depth of 15mm.

The sealant was installed such that the surface was flush with the face of the Hebel blocks (item 4) at the time of the installation.

3

SERVICE F

Dimensions The control joint was nominally 12mm wide × 1000mm high.

Sealant Fire Retardant Silicone Sealant (item 7)

Backing Rod Close Cell (item 6)

Installation

A backing rod the full length of the control joint was installed on the unexposed side at a depth of 6mm. The sealant was then applied on the unexposed side at a depth of 6mm.

The sealant was installed such that the surface was flush with the face of the Hebel blocks (item 4) at the time of the installation.

SEPERATING ELEMENT

4

Item Name Hebel Blocks

Product Name CSR Hebel Thermoblock AAC Masonry

Size 200mm wide × 250mm deep × 1600mm high

Density 558 kg/m3 (measured)

Installation Installed as per Figure A1.1

BACKING ROD

5 Item Name Open Cell Polyethylene foam backing rod

Size Ø50mm

6 Item Name Close Cell Polyethylene foam backing rod

Size Ø20mm (Double up when inserted into 30mm gap)

SEALANT

7 Item Name Fire Retardant Silicone Sealant

Page 59: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 6 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

Item Description

Product Name AS-202 Fire Retardant Silicone Sealant

Density 1241 kg/m3 (measured)

Page 60: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 7 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

3 TEST PROCEDURE

STATEMENT OF COMPLIANCE

The test was performed in accordance with the requirements of EN 1366-4:2006 subject to the variations below.

VARIATIONS TO TEST METHOD

The pressure for the 5-30, 60-65, 75-85,110-115, 209-240, 270-275 minute period was above the limits prescribed in BS EN 1366-4 2006 up to 10 Pa. This exceeded the pressure requirement of the standard and was therefore more severe than required by the standard. Based on the above the results of this test remain valid. The furnace pressure was below the limits stated in BS EN 1366-4 2006 by 10Pa between 135-145 minutes due to deterioration of the specimen. See table A5.2 for details. No deflection measurements were taken.

PRE-TEST CONDITIONING

The construction of the specimen was finished on the 15 May 2017 and was tested on the 14 June 2017. During this period the test specimen was subject to normal laboratory temperatures and relative humidity conditions.

SAMPLING / SPECIMEN SELECTION

The laboratory was not involved in the sampling or selection of the test specimen for the fire resistance test.

AMBIENT TEMPERATURE

The ambient temperature at the start of the test was 15°C and varied between 15°C and 21°C during the test.

TEST DURATION

The test duration was 301 minutes.

INSTRUMENTATION AND EQUIPMENT

The instrumentation was provided in accordance with EN 1363-1:2012 and as detailed below:

The furnace temperature was measured by 4-off 100mm × 100mm × 0.7 mm plate thermocouples with mineral insulated metal sheathed Type K thermocouples with an overall diameter of 1mm with the measuring junction insulated from the sheath. The plate thermocouples included 97mm × 97mm × 10mm inorganic insulating pads.

The non-fire side specimen temperatures were measured by Type K thermocouples with wire diameters less than 0.5mm soldered to 12mm diameter × 0.2mm thick copper discs covered by 30mm × 30mm × 2.0 mm inorganic insulating pads. The thermocouple positions are described in Table A4.1, and are shown on Figure A4.1 in Appendix 4.

A roving thermocouple was available to measure temperatures at positions that appeared hotter than the positions monitored by the fixed thermocouples.

The furnace pressure was measured at the mid-height of the control joint.

Cotton pad were available during the test to assess the performance under the criteria for integrity.

Page 61: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 8 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

4 TEST MEASUREMENTS

FURNACE TEMPERATURE AND PRESSURE MEASUREMENTS

Furnace temperature and pressure data are provided in Figure A5.1 and Table A5.1 in Appendix 5.

SPECIMEN TEMPERATURES

Specimen temperature data is provided in A 5.3 and Table A5.2 in Appendix 5.

OBSERVATIONS

A table that includes observations of the significant behaviour of the specimen and details of the occurrence of the various performance criteria specified in EN 1366-4:2006 (EN 1363-1) is provided in Appendix 2. Photographs of the specimen are included in Appendix 6.

5 TEST RESULTS

The specimens listed below achieved the following performance when tested in accordance with EN1366-4:2006, subject to the variations listed in Section 3.

Service Criteria Result

D

Structural Adequacy Not applicable

Integrity No failure at 301 minutes

Insulation Failure at 148 minutes

E

Structural Adequacy Not applicable

Integrity No failure at 301 minutes

Insulation Failure at 97 minutes

F

Structural Adequacy Not applicable

Integrity No failure at 301 minutes

Insulation No failure at 301 minutes

Page 62: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 9 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

6 APPLICATION OF TEST RESULTS

TEST LIMITATIONS

The results of this fire test may be used to directly assess fire hazard, but it should be recognized that a single test method will not provide a full assessment of fire hazard under all fire conditions. The results only relate to the behaviour of the specimen of the element of the construction under the particular conditions of the test; they are not intended to be the sole criteria for assessing the potential fire performance of the element in use nor do they necessarily reflect the actual behaviour in fires.

VARIATIONS FROM THE TESTED SPECIMENS

This report details the method of construction, the test conditions and the results obtained when the specific element of construction described herein was tested following the procedure outlined in EN 1363-1, and where appropriate EN 1363-2. Any significant deviation with respect to size, constructional details, loads, stresses, edge or end conditions other than those allowed under the field of direct application in the relevant test method is not covered by this report. It is recommended that any proposed variation to the tested configuration other than as permitted under the field of direct application specified in Appendix 3 should be referred to the test sponsor in the first instance to obtain appropriate documentary evidence of compliance from Exova Warringtonfire Aus Pty Ltd or another Registered Testing Authority.

UNCERTAINTY OF MEASUREMENT

Because of the nature of fire resistance testing and the consequent difficulty in quantifying the uncertainty of measurement of fire resistance, it is not possible to provide a stated degree of accuracy of the result.

Page 63: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 10 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 1 DRAWINGS OF TEST ASSEMBLY

Figure A1.1: Elevation of Test Specimen, Unexposed side

Figure A1.2: Horizontal Cross-Section A-A

Page 64: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 11 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 2 TEST OBSERVATIONS

The following include observations of the significant behaviour of the specimen.

Time Observations

min sec

Service D

00 00 Fire resistance test commenced and the ambient temperature was approximately 15°C.

27 56 Smoke emission appeared from the joint on the north edge

27 56 Mastic appeared to have bended up from the floor.

30 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1366-4

60 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1366-4

73 00 The mastic had expanded.

90 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1366-4

120 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1366-4

138 00 Small patch of discoloration (The mastic turn to white colour) on the control joint surface

148 05 TC 042, at the mid length of the control joint recorded a temperature of 194°C. Failure of insulation in accordance with EN 1363-1 clause 11.3, where the maximum temperature of Thermocouple TC 042 exceeded the initial temperature by more than 180°C.

180 00 The specimen had continued to maintain integrity in accordance with EN 1363-1

200 27 Amount of smoke emission had increased.

270 00 Glowing appeared on the north edge of the control joint

300 00 The specimen had continued to maintain integrity in accordance with EN 1366-4

Service E

00 00 Fire resistance test commenced and the ambient temperature was approximately 15°C.

30 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1366-4

60 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1366-4

90 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1366-4

120 00 The specimen had continued to maintain integrity in accordance with EN 1366-4

167 00 A crack opened up on the interface between the Hebel panel and the mastic at 650 - 700mm from the north edge. Glowing can be observed through the gap

170 00 A 30 second cotton pad test was carried out in accordance with EN 1363-1. No glowing or flaming had become evident

172 30 A 30 second cotton pad test was carried out in accordance with EN 1363-1. No glowing or flaming had become evident

180 00 The specimen had continued to maintain integrity in accordance with EN 1363-1

194 30 A 30 second cotton pad test was carried out in accordance with EN 1363-1. No glowing or flaming had become evident

240 00 The specimen had continued to maintain integrity in accordance with EN 1366-4

Page 65: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 12 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

300 00 The specimen had continued to maintain integrity in accordance with EN 1366-4

301 00 Test terminated at the request of the sponsor.

Service F

00 00 Fire resistance test commenced and the ambient temperature was approximately 15°C.

30 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1366-4

60 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1366-4

90 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1366-4

120 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1366-4

180 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1363-1

300 00 The specimen had continued to maintain integrity and insulation in accordance with EN 1366-4

301 00 Test terminated at the request of the sponsor.

Page 66: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 13 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 3 DIRECT FIELD OF APPLICATION

Reference Note: References in this section refer to those found in the standard and not this report.

GENERAL

EN 1366-4:2006 indicates that the results of the fire test contained in the test report are directly applicable without reference to the testing authority to similar constructions where one or more of the changes have been made:

ORIENTATION

The field of application regarding the orientation of the linear joint is given in Table 1. The possible orientation of linear joints (A to E) and of the specimens in the test (A to C) is illustrated in Figure 12.

Table 1 – Field of application regarding orientation

Tested Orientation Application

A A, D, E a

B B

C C, D b

a Orientation E will only be covered by test orientation A if shear movement was chosen and one face of the joint was fixed and the other face was removed.

b Orientation D will only be covered by test orientation C if shear movement was chosen and one face of the joint was fixed and the other face was moved.

Key A linear joint in a horizontal test construction B vertical linear joint in a vertical test construction C horizontal linear joint in a vertical test construction D horizontal wall joint abutting a floor, ceiling or roof E horizontal floor joint abutting a wall Table 1 only applies when both the supporting construction and the location of the seal within the linear joint remain unchanged. See 13.3

SUPPORTING CONSTRUCTION

Results obtained with autoclaved aerated concrete standard supporting constructions apply to concrete, block work and masonry separating elements of a thickness and density equal to or greater than that tested. Results obtained with normal concrete standard supporting constructions apply to concrete and block work separating elements of a thickness and density equal to or greater than that tested. Results obtained with timber standard supporting construction apply to timber separating elements of a thickness and density equal to or greater than that tested. Results obtained with the steel angle standard supporting construction as described in 7.2.2.3 apply to separating element constructions made of metals with a melting point higher than 1000 °C. Results obtained with a combination of a standard supporting construction as described in 7.2.2.1 and a standard supporting construction as described in 7.2.2.3 apply to concrete, block work and masonry separating elements of a thickness and density equal to or greater than that tested forming one joint face and separating element constructions made of metals with a melting point higher than 1000 °C forming the other joint face. A fire resistance time obtained on a specific non-standard supporting construction applies only to that particular construction.

Page 67: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 14 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

SEAL POSITION

Test results are valid only for the position (see Figure 3) in which the seal was tested, except that where the linear joint seal was fitted flush with the surface of the supporting construction and is exposed to the fire (see Figure 3, test specimen B), the result will also be applicable to test specimen C and E.

MECHANICALLY INDUCED MOVEMENT

If the movement capability of a linear joint seal is less than 7,5 %, the linear joint seal may be tested without mechanically induced movement and the result applies to the movement capability reported. Results obtained with mechanically induced movement prior to or during the tests are only valid for the movement capability tested or lower.

Page 68: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 15 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 4 INSTRUMENTATION POSITIONS

Figure A4.1: Unexposed surface thermocouple locations

Page 69: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 16 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

Table A4.1: Thermocouple Locations

Service T/C No. Description

D

041 At the centre of the control joint, 250mm from the north of the control joint.

042 At the centre of the control joint, 500mm from the north of the control joint.

043 At the centre of the control joint, 750mm from the north of the control joint.

044 On the west side of the control joint, 20mm from the north of the control joint

045 On the west side of the control joint, 480mm from the north of the control joint.

046 On the west side of the control joint, 20mm from the south of the control joint.

047 On the east side of the control joint, 150mm from the north of the control joint.

048 On the east side of the control joint, 350mm from the north of the control joint.

049 On the east side of the control joint, 150mm from the south of the control joint.

E

051 At the centre of the control joint, 250mm from the north of the control joint.

052 At the centre of the control joint, 500mm from the north of the control joint.

053 At the centre of the control joint, 750mm from the north of the control joint.

054 On the west side of the control joint, 20mm from the north of the control joint

055 On the west side of the control joint, 480mm from the north of the control joint.

056 On the west side of the control joint, 20mm from the south of the control joint.

057 On the east side of the control joint, 150mm from the north of the control joint.

058 On the east side of the control joint, 350mm from the north of the control joint.

059 On the east side of the control joint, 150mm from the south of the control joint.

F

101 At the centre of the control joint, 250mm from the north of the control joint.

102 At the centre of the control joint, 500mm from the north of the control joint.

103 At the centre of the control joint, 750mm from the north of the control joint.

104 On the west side of the control joint, 20mm from the north of the control joint

105 On the west side of the control joint, 480mm from the north of the control joint.

106 On the west side of the control joint, 20mm from the south of the control joint.

107 On the east side of the control joint, 150mm from the north of the control joint.

108 On the east side of the control joint, 350mm from the north of the control joint.

109 On the east side of the control joint, 150mm from the south of the control joint.

Page 70: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 17 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 5 TEST DATA

FURNACE TEMPERATURE

Figure A5.1: Furnace Temperatures vs. Time

0

200

400

600

800

1000

1200

1400

0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300

Tem

pera

ture

(°C

)

Time (Minutes)

EN 1363-1 Mean Furn

Page 71: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 18 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

FURNACE PRESSURE

The furnace pressure was measured 100mm below the separating element.

Table A5.1: Pressure

Time

(minutes)

Pressure (Pa)

Avg.

Time

(minutes)

Pressure (Pa)

Avg.

Time

(minutes)

Pressure (Pa)

Avg.

5-10 30 105-110 23 205-210 18

10-15 27 110-115 23 210-215 29

15-20 25 115-120 21 215-220 38

20-25 25 120-125 20 220-225 32

25-30 24 125-130 22 225-230 36

30-35 18 130-135 22 230-235 25

35-40 19 135-140 7 235-240 24

40-45 19 140-145 6 240-245 22

45-50 20 145-150 17 245-250 21

50-55 20 150-155 18 250-255 16

55-60 20 155-160 18 255-260 22

60-65 24 160-165 19 260-265 18

65-70 22 165-170 19 265-270 19

70-75 22 170-175 20 270-275 24

75-80 23 175-180 19 275-280 13

80-85 23 180-185 18 280-285 21

85-90 22 185-190 18 285-290 19

90-95 23 190-195 19 290-295 17

95-100 21 195-200 18 295-300 18

100-105 23 200-205 19

Page 72: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 19 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

SPECIMEN TEMPERATURES

Figure A5.2: Service D on the Hebel (west side of the control joint). Temperatures vs. time

Figure A5.3: Service D on the sealant (mid-wide of the control joint). Temperatures vs. time

0

50

100

150

200

250

300

350

400

0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300

Tem

pera

ture

(°C

)

Time (minutes)

041 042 043

0

50

100

150

200

250

300

350

400

0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300

Tem

pera

ture

(°C

)

Time (minutes)

044 045 046

Page 73: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 20 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

Figure A5.4: Service D on the Hebel (east side of the control joint). Temperatures vs. time

Figure A5.5: Service E on the Hebel (west side of the control joint). Temperatures vs. time

0

50

100

150

200

250

300

350

400

0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300

Tem

pera

ture

(°C

)

Time (minutes)

047 048 049

0

100

200

300

400

500

600

700

0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300

Tem

pera

ture

(°C

)

Time (minutes)

051 052 053

Page 74: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 21 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

Figure A5.6: Service E on the sealant (mid-wide of the control joint). Temperatures vs. time

Figure A5.7: Service E on the Hebel (east side of the control joint). Temperatures vs. time

0

50

100

150

200

250

300

350

400

0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300

Tem

pera

ture

(°C

)

Time (minutes)

054 055 056

0

50

100

150

200

250

300

350

400

0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300

Tem

pera

ture

(°C

)

Time (minutes)

058 059

Page 75: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 22 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

Figure A5.8: Service F on the Hebel (west side of the control joint). Temperatures vs. time

Figure A5.9: Service F on the sealant (mid-wide of the control joint). Temperatures vs. time

0

20

40

60

80

100

120

140

160

180

200

0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300

Tem

pera

ture

(°C

)

Time (minutes)

101 102 103

0

20

40

60

80

100

120

140

160

180

200

0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300

Tem

pera

ture

(°C

)

Time (minutes)

104 105 106

Page 76: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 23 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

Figure A5.10: Service F on the Hebel (east side of the control joint). Temperatures vs. time

Table A5.2: Test Specimen Temperatures

Service T/C No. Description2

Temp (°C) at t (minutes) Limit1 (Mins) t=0 t=30 t=60 t=120 t=180 t=240 t=300

D

041 At the centre of the control joint, 250mm from the north of the control joint.

14 81 107 134 174 199 257 224

042 At the centre of the control joint, 500mm from the north of the control joint.

14 95 124 181 220 298 # 148

043 At the centre of the control joint, 750mm from the north of the control joint.

14 56 85 111 146 176 207 250

044 On the west side of the control joint, 20mm from the north of the control joint

14 53 92 133 174 210 284 212

045 On the west side of the control joint, 480mm from the north of the control joint.

14 61 100 159 210 353 291 158

046 On the west side of the control joint, 20mm from the south of the control joint.

14 49 87 132 172 262 301 214

047 On the east side of the control joint, 150mm from the north of the control joint.

14 57 94 150 206 242 288 166

0

20

40

60

80

100

120

140

160

180

200

0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300

Tem

pera

ture

(°C

)

Time (minutes)

107 108 109

Page 77: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 24 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

048 On the east side of the control joint, 350mm from the north of the control joint.

14 59 90 148 205 242 282 166

049 On the east side of the control joint, 150mm from the south of the control joint.

14 50 77 121 168 202 231 227

E

051 At the centre of the control joint, 250mm from the north of the control joint.

14 100 149 204 417 436 402 105

052 At the centre of the control joint, 500mm from the north of the control joint.

14 101 154 212 469 382 408 97

053 At the centre of the control joint, 750mm from the north of the control joint.

14 107 144 192 361 299 229 125

054 On the west side of the control joint, 20mm from the north of the control joint

14 63 100 137 166 200 265 231

055 On the west side of the control joint, 480mm from the north of the control joint.

14 67 101 156 207 273 310 167

056 On the west side of the control joint, 20mm from the south of the control joint.

14 77 113 161 208 260 269 163

057 On the east side of the control joint, 150mm from the north of the control joint.

# # # # # # # #

058 On the east side of the control joint, 350mm from the north of the control joint.

14 73 112 167 266 279 277 142

059 On the east side of the control joint, 150mm from the south of the control joint.

14 45 69 98 120 148 188 -

F

101 At the centre of the control joint, 250mm from the north of the control joint.

15 55 82 113 128 137 156 -

102 At the centre of the control joint, 500mm from the north of the control joint.

14 49 75 112 132 150 173 -

103 At the centre of the control joint, 750mm from the north of the control joint.

14 46 66 106 122 121 129 -

104 On the west side of the control joint, 20mm from the north of the control joint

14 53 73 91 104 113 137 -

105 On the west side of the control joint, 480mm from the north of the control joint.

14 47 70 98 118 136 168 -

106 On the west side of the control joint, 20mm from the south of the control joint.

14 39 51 67 84 94 105 -

Page 78: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 25 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

107 On the east side of the control joint, 150mm from the north of the control joint.

14 56 77 95 108 113 130 -

108 On the east side of the control joint, 350mm from the north of the control joint.

14 48 69 90 102 116 139 -

109 On the east side of the control joint, 150mm from the south of the control joint.

14 40 53 74 85 87 93 -

Notes 1 Limit time is the time to the nearest whole minute, rounded down to the nearest minute, at which the temperature recorded by the thermocouple does not rise by more than 180K above the initial temperature.

2 Refer to Appendix 4 for locations of thermocouples as only a generic description is included in the table.

3 No insulation failure prior to thermocouple failure.

# Thermocouple failure.

* Service failure

‘-’ Under Limit column indicates the temperature limit was not exceeded during the test period or up until the time of integrity failure if a failure occurred.

Page 79: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 26 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

APPENDIX 6 PHOTOGRAPHS

Figure A6.1: Unexposed face of specimen before commencement of the fire-resistance test

Figure A6.2: Exposed face of specimen before commencement of the fire-resistance test

East West

D E F

D E F

East West

Page 80: AS-202 EN1366-4 Report

Report No. 43878800g.1 Page 27 of 27

© Exova Warringtonfire Aus Pty Ltd 2018

Figure A6.3: Unexposed face of specimen at the end of the test.

Figure A6.4: Exposed face of specimen at the end of the test.

East West

West West

D E F

D E F