areva p343 p344 p345 xrio converter manual enu tu2.22 v1.001
TRANSCRIPT
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
1/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 1/16
OMICRON PTL
XRIO Converter
AREVA P34x
User Manual
V1.000
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
2/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 2/16
Contents
Contents........................................................................................................................................................2
1 General Information ..................................................................................................................................4
2 Quick Start Information ............................................................................................................................4
3 Using the Converter..................................................................................................................................5
4 Required Software Version......................................................................................................................5
5 Functional Range ......................................................................................................................................5
6 Not Supported Functions.........................................................................................................................7
7 OMICRON Test Strategy...........................................................................................................................7
8 Converter Structure ..................................................................................................................................7
8.1 P34x Section ........................................................................................................................................7
8.1.1 Relay Parameter Section................................................................................................................7
8.1.2 Additional Information.....................................................................................................................8
8.1.3 RIOPlus (Advanced view)...............................................................................................................9
8.1.3.1 NamePlate...............................................................................................................................9
8.1.3.2 PowerSystemParameters .......................................................................................................9
8.1.3.3 GeneratorProtection................................................................................................................9
8.1.3.3.1 FrequencyElements..........................................................................................................9
8.1.3.3.2 VoltageElements ..............................................................................................................9
8.1.3.3.3 PowerElements ................................................................................................................9
8.1.3.3.4 VoltsPerHertzElements ....................................................................................................9
8.1.3.3.5 DifferentialElements .........................................................................................................9
8.1.3.3.6 InadvertentEnergizingElements......................................................................................10
8.1.3.3.7 UnderExcitationElements ...............................................................................................10
8.1.3.3.8 Thermal Protection .........................................................................................................10
8.1.3.3.9 OutOfStepElements........................................................................................................10
8.1.3.4 DistanceProtection ................................................................................................................10
8.1.3.5 OvercurrentProtection ...........................................................................................................10
8.1.3.6 OvercurrentProtection (E/F CT) ............................................................................................10
8.1.3.7 SEF .......................................................................................................................................11
8.1.4 TemplateController (Advanced view) ...........................................................................................11
8.1.4.1 Circuit Breaker.......................................................................................................................11
8.2 RIO .....................................................................................................................................................12
8.2.1 Generator Differential ...................................................................................................................12
8.2.2 Low Z REF....................................................................................................................................12
8.2.3 Distance........................................................................................................................................12
8.2.4 Pole Slip........................................................................................................................................12
8.2.5 Field Failure Trip...........................................................................................................................12
8.2.6 Field Failure Alarm .......................................................................................................................13
8.2.7 Phase Overcurrent Forward .........................................................................................................13
8.2.8 Phase Overcurrent Reverse .........................................................................................................13
8.2.9 NPS Overcurrent Forward ............................................................................................................13
8.2.10 NPS Overcurrent Reverse..........................................................................................................13
8.2.11 ThermalOverload Trip.................................................................................................................14
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
3/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 3/16
8.2.12 ThermalOverload Alarm .............................................................................................................14
8.2.13 NPS Thermal ..............................................................................................................................14
8.2.14 NPS Alarm ..................................................................................................................................14
8.2.15 Earth Fault ..................................................................................................................................14
8.2.16 Voltage dependent OC (Vtest>Vs1)...........................................................................................15
8.2.17 Voltage dependent OC (Vtest
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
4/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 4/16
1 General Information
The AREVA P34x converter is designed for use with the OMICRON Test Universe2.22 software fortesting the P34x generator protection relays. The converter provides all necessary data for testing the
generator protection functions (see chapter 2 ) of the P34x relays.
Note:This converter is tested with the relay described above. It may work with similar relays, too.
2 Quick Start Information
To work with the AREVA P34x XRIO converter:
1. Start a new OMICRON Control Center(OCC) document or open an existing OCC document.
2. Insert a new test object or open the existing test object.
3. On the Filemenu, click Import.
4. Browse to the latest OMICRON P34x.xrio file.5. Click Open.
6. Enter all necessary settings in the Relay Parameter Section, Additional Information General/Power System Parameters/Circuit Breaker Information/Test Parameters(seechapter 8.1.1 and 8.1.2 ).
7. Click OK.
Figure 1: Opening and importing the AREVA P34x XRIO converter
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
5/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 5/16
3 Using the Converter
The AREVA P34x XRIO converter can be used as a stand-alone converter or in association with a relayspecific test template, for example with the OMICRON Generator Protectiontemplate for the P34x relays.
In any way the converter is used, follow the quick start instructions and create your test using LinkToXRIOor start using the relay specific test template (for more information, see the test template documentation).
4 Required Software Version
To use this converter, you must have a valid license for the OMICRON Test Universe2.22 software.
5 Functional Range
The AREVA P34x XRIO converter implements the following functions:
81 Over/Underfrequency protection
27 Phase Undervoltage protection
59 Phase Overvoltage protection
47 Negative Sequence Overvoltage protection
59N Neutral Overvoltage protection
24 Volts/Hz protection
87 Generator Differential protection
46 Stator Overload protection
46T NPS Thermal
49 Stator Overload protection
46 Negative Phase Sequence Overcurrent protection
50, 51 Phase Overcurrent protection
50/27 Dead Machine protection
32 Over/Underpower protection
21/51V System backup protection
40 Fields Failure protection
78 Pole Slipping protection
27T/59T 100% Stator protection
67N Sensitive Earth Fault Overcurrent
64 High Impedance Restricted Earth Fault protection 64 Low Impedance Restricted Earth Fault protection
50N/51N Earth Fault Overcurrent
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
6/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 6/16
Figure 2: Functional range of the AREVA P34x XRIO converter
Some of the functions listed above use the RIO interface of the Test Universesoftware. Consequently, thetest modules are configured automatically without using LinkToXRIO.
The following functions use the RIO interface:
87 Biased Differential protection
21 Impedance protection
78 Out of Step protection
40 Field Failure protection
46 Negative sequence
50, 50N, 50DT, 51N, 51V, 67N Instantaneous/Definite/Inverse Timed Phase/Neutral Overcurrentprotection
49 Thermal overload protection
46 NPS Thermal protection
For testing the other functions, you must use LinkToXRIO.
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
7/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 7/16
6 Not Supported Functions
The following functions are currently not supported:
64S 100% Stator Ground protection-low frequency injection
Earth fault (P341 relay)
59N Residual voltage protection (VN2-input)
67N SEF protection with option wattmetric, cos(Phi) and sin(Phi)
32N Sensitive Power
Supervision
CB Fail
RTD Inputs
7 OMICRON Test Strategy
The OMICRON test strategy is described in the OMICRON Protection Test Template(PTT) Generatordocumentation. For detailed information, see the PTT Generatordocumentation.
8 Converter Structure
The converter is divided into two sections: the P34x section and the RIO section. Both sections consist ofseveral function blocks. The converter comes up in the standard view; the RIOplus section and thetemplate controller section can only be seen in the advanced view.
8.1 P34x Section
The P34xsection is divided into four groups: the Relay Parameter Section, the Additional Informationsection, the RIO Plussection and the TemplateControllersection.
8.1.1 Relay Parameter Section
The Relay Parameter Sectionincludes the parameters which have to be changed by the user. All relayparameters are included in this section and have to be set to the actual relay values. The parameters aregrouped and named as in the AREVA MiCOM S1 Studio software. Each parameter in this block isidentified by a Foreign ID (witch corresponds to the Address in the relay software).
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
8/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 8/16
Figure 3: Setting the parameters in the Relay Parameter Section
8.1.2 Additional Information
This block contains additional data for testing the P34x relay functionality. The block is divided into thefollowing sections:
General section includes detailed information needed for the test report like manufacturer,device type, substation name etc. This section includes parameters which have to be changed bythe user according to the customer relay type and substation.
Relay Informationsection - This block has been added for relay specific parameters such astolerances which cannot be set by the user, because they are constant values. All values set inthis block can be found in the "P34x Generator Protection Relay" manual. Typically, these blocksdo not have to be changed, as they are already set to the values given in the user manual of the
relay. Circuit Breaker Informationsection includes information which is required for the CB test.
Test Tolerancesection includes an additional test tolerance to calculate the start and end valuefor trip and pickup tests by using theOMICRON TU Rampingmodule.
Test Parameterssection includes additional test parameters for testing adaptive functionswitch are not directly supported by the OMICRON TU test modules e.g. a voltage level for the 51Vtests. Furthermore it includes additional test parameters which are needed for testing theprotection function but not found in the relay settings. e.g. high operating current stage for the 87Phase Differential protection function. This section includes parameters which have to bechanged by the user.
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
9/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 9/16
8.1.3 RIOPlus (Advanced view)
The RIO Plus section contains the interface, which provides the link between the XRIO converter and alltest modules which have no access to RIO functions. All tests using basic test modules like RampingorState Sequencerhave to be linked to the parameters in the RIO Plussection of the converter.
8.1.3.1 NamePlate
The NamePlateblock contains all necessary information to identify the protection device to be tested. Thisblock contains the relay vendor, serial number, model, the relay location, hardware revision, softwarerevision and a description.
8.1.3.2 PowerSystemParameters
The number of phases, phase rotation and the nominal frequency are stored in this block.
8.1.3.3 GeneratorProtection
This block contains all data necessary for testing the functional range (see chapter 5 ) of the AREVA
P34x relays except the underimpedance and overcurent protection functions. The nominal values and CTsettings for both generator sides used by these protection functions can be found here. The followingprotection functions are included in this section:
8.1.3.3.1 FrequencyElements
This block contains all necessary data for testing the over- and under frequency protection functions. Allstages of the under frequency and over frequency protection function in the relay are modeled as subblocks of the FrequencyElementsblock. Each stage sub block stores information about the pickup value,operating time and the pickup drop-off ratio.
8.1.3.3.2 VoltageElements
This block contains all necessary data for testing the over- and under voltage protection functions. Allstages of the voltage protection function in the relay are modeled as sub blocks of the VoltageElements
block. Each stage sub block stores information about the pickup value, operating time and the pickupdrop-off ratio.
8.1.3.3.3 PowerElements
This block contains all necessary data for testing the over- and under power protection function. All stagesof the directional power protection function in the relay are modeled as sub blocks of the PowerElementsprotection block. Each stage sub block stores information about the pickup value, operating time and thepickup drop-off ratio.
8.1.3.3.4 VoltsPerHertzElements
This block contains all necessary data for testing the Volts per Hertz (Overfluxing) protection. All stages ofthe VoltsPerHertz protection function in the relay are modeled as sub blocks of the VoltsPerHerzElementsblock. Each stage sub block stores information about the pickup value, operating time, the pickup drop-offratio and the operating curve.
8.1.3.3.5 DifferentialElements
This block contains all necessary data for testing the 87G differential and the 64 restricted earth faultprotection function. The following protection function curves are modeled as sub blocks of theDifferentialElementsblock:
biased differential curve,
high impedance differential curve,
interturn differential curve,
low impedance restricted earth fault curve and
high impedance restricted earth fault curve
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
10/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 10/16
Each sub block stores information about the pickup value, operating time, HarmonicRestraintElementsand the operating curve.
8.1.3.3.6 InadvertentEnergizingElements
This block contains all necessary data for testing the inadvertent energizing protection function. The blockcontains an InstantaneousObercurrentElement and an UnderVoltageElementsub blocks. Each sub block
stores information about the pickup and pickup drop-off ratio and the operating time.
8.1.3.3.7 UnderExcitationElements
This block contains all necessary data for testing the Field Failure protection function. The Field Failuretripping elements are modeled as sub blocks of the UnderExcitationElementsblock. Each tripping elementsub block (FF1, FF2and FFAlarm) stores information about:
the impedances in the BorderElementsand GenericShapesub blocks
the reach and phi values and tolerances in the Reachsub block
the operating and reset delay time values and tolerances in the OperateDelayTimesub block
8.1.3.3.8 Thermal Protection
This block contains all necessary data for testing the stator overload protection. All stages of the stator
overload protection function in the relay are modeled as sub blocks of the StatorOverloadElementsblock.Each sub block stores information about the stator overload characteristics of the relay.
8.1.3.3.9 OutOfStepElements
This block contains all necessary data for testing the out of step protection function. The out of stepdetection element and the starting element of the out of step protection function in the relay are modeledas sub blocks of the OutOfStepElementsblock. The sub block StartingElementsblock stores informationabout voltage pickup element. The sub block ImpedanceZoneElementincludes the different pole slipdetection elements and the reset delay time. Each SlipDetectionElementstores information about:
the impedances in the BorderElementsand GenericShapesub blocks
the reach and phi values and tolerances in the Reachsub block
the operating and reset delay time values and tolerances in the OperateDelayTimesub blocks
8.1.3.4 DistanceProtection
This block contains all necessary data to test the distance protection circle. The nominal values and theCT / VT settings used by the distance protection functions can be found here. All zones of the distanceprotection function in the relay are modeled as sub blocks of the ImpedanceZoneElementsblock. Eachzone sub block stores information about:
the grounding factors in the GroundingFactorsub block
the impedances in the BorderElementsand GenericShapesub blocks
the reach and phi values and tolerances in the Reachsub block
the operating and reset delay time values and tolerances in the OperateDelayTimesub blocks
8.1.3.5 OvercurrentProtection
This block contains all necessary data for testing the overcurrent protection elements witch use the phasecurrent transformers. All stages of the overcurrent protection function in the relay are modeled as subblocks of the OvercurrentElementsblock. Each stage sub block stores information about the pickup value,operating time, pickup drop-off ratio and the curve type. The sub block Voltage Dependent OC (SystemBackup) block contains all necessary data for testing the voltage dependent overcurrent function.
8.1.3.6 OvercurrentProtection (E/F CT)
This block contains all necessary data for testing the overcurrent protection elements which use theneutral transformers. All stages of the overcurrent protection which use the E/F CT in the relay aremodeled as sub blocks of the OvercurrentElements block. Each stage sub block stores information about
the pickup value, operating time, pickup drop-off ratio and the curve type.
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
11/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 11/16
8.1.3.7 SEF
This block contains all necessary data for testing the overcurrent protection elements which use theneutral transformers. All stages of the overcurrent protection which use the SEF CT in the relay aremodeled as sub blocks of the OvercurrentElements block. Each stage sub block stores information aboutthe pickup value, operating time, pickup drop-off ratio and the curve type.
8.1.4 TemplateController (Advanced view)
The TemplateControllerblock contains special values needed for some tests, especially for tests usingLinkToXRIO. These are mainly calculated values which cannot be calculated in the RIOPlus. Thesevalues are needed for using LinkToXRIO. Furthermore this block contains special functionalities like e.g.an OC sort function. These values with its special functions are linked to the RIO section and are neededfor the use of the OMICRON test modules.
Figure 4: Structure of the Template Controller
Note:Other values needed for customer designed test can be stored in this block.
8.1.4.1 Circuit Breaker
The circuit breaker block contains all necessary data for testing protection functions together with thecircuit breaker. The modeled parameter is the trip time.
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
12/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 12/16
8.2 RIO
The RIOsection of the converter contains all specialized RIO functions needed to use the morespecialized test modules (like e.g. Advanced Differentialor Overcurrent) provided by the OMICRON TestUniversesoftware.
Warning:Do not change any values in this section. The values have been set using the relay settings ofthe Relay Parameter Section.
Note:Do not activate the former test object view in the advanced mode of the XRIO test object. Changingparameters in this view could disable formulas in the RIO section.
8.2.1 Generator Differential
The RIO Differentialfunction provides the necessary values for testing the Biased Differential protectionfunction of the P34x relay. The RIO differential function contains all values needed for using the followingOMICRON Test Universemodules:
Diff Configuration
Diff Characteristic
8.2.2 Low Z REF
The RIO Differentialfunction provides the necessary values for testing the Low Impedance RestrictedEarth Fault protection function of the P34x relay. The RIO differential function contains all values neededfor using the following OMICRON Test Universemodules:
Diff Configuration
Diff Characteristic
8.2.3 Distance
This RIO Distancefunction provides the necessary values for testing the distance protection functions ofthe P34X relay with the Advanced Distancetest module. The protection functions supported by this RIOfunction include:
21 Underimpedance
The following RIO function for testing these distance protection functions is available:
Distance
8.2.4 Pole Slip
The RIO Pole Slipblock provides the necessary values for testing the out of step function of the P34xrelay with the StateSequencermodule with distance curve view.
8.2.5 Field Failure Trip
This RIO Field Failure function provides the necessary values for testing the trip time of the field failureprotection function of the P34x relay with the Advanced Distancetest module. The protection functionssupported by this RIO function include:
40 Filed Failure tripping zones
The following RIO function for testing these distance protection functions is available:
Distance
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
13/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 13/16
8.2.6 Field Failure Alarm
This RIO Loss of Field Alarmfunction provides the necessary values for testing the alarm signal of thefield failure protection functions of the P34x relay with the Advanced Distancetest module. The protectionfunctions supported by this RIO function include:
40 Field Failure tripping zones
The following RIO function for testing these distance protection functions is available:
Distance
8.2.7 Phase Overcurrent Forward
This RIO PhaseOvercurrent Forwardblock provides the necessary values for testing the trip times of thePhase Overcurrent function in forward direction. The protection functions supported by this RIO functioninclude:
50,51,67 Phase Overcurrent
The following RIO function for testing these distance protection functions is available:
Overcurrent
8.2.8 Phase Overcurrent Reverse
This RIO PhaseOvercurrent Reverseblock provides the necessary values for testing the trip times of thePhase Overcurrent function in reverse direction. The protection functions supported by this RIO functioninclude:
50,51,67 Phase Overcurrent
The following RIO function for testing these distance protection functions is available:
Overcurrent
8.2.9 NPS Overcurrent Forward
This RIO NPSOvercurrent Forwardblock provides the necessary values for testing the trip times of theNPS Overcurrent function in forward direction. The protection functions supported by this RIO functioninclude:
46 NPS Overcurrent
The following RIO function for testing these distance protection functions is available:
Overcurrent
8.2.10 NPS Overcurrent Reverse
This RIO NPSOvercurrent Reverseblock provides the necessary values for testing the trip times of theNPS Overcurrent function in reverse direction. The protection functions supported by this RIO functioninclude::
46 NPS Overcurrent
The following RIO function for testing these distance protection functions is available:
Overcurrent
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
14/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 14/16
8.2.11 ThermalOverload Trip
The RIO ThermalOverloadfunctions for testing the trip time of the thermal overload protection functionwith Test Universeare implemented in the RIO block of the P34x XRIO converter:
Thermal Overload (tripping element)
This module contains the stator overload characteristic curve.
The following RIO function for testing these distance protection functions is available:
Overcurrent
8.2.12 ThermalOverload Alarm
The RIO ThermalOverloadfunctions for testing the alarm time of the thermal overload protection functionwith Test Universeare implemented in the RIO block of the P34x XRIO converter:
Thermal Overload (tripping element)
This module contains the stator overload characteristic curve.
The following RIO function for testing these distance protection functions is available:
Overcurrent
8.2.13 NPS Thermal
The RIO NPS Thermalfunctions for testing the NPS thermal protection function with Test Universeareimplemented in the RIO block of the P34x XRIO converter:
NPS Thermal (tripping element)
This module contains the rotor overload characteristic curve.
The following RIO function for testing these distance protection functions is available:
Overcurrent
8.2.14 NPS Alarm
The RIO NPS Alarmfunctions for testing the alarm signal of the NPS thermal protection function with TestUniverseare implemented in the RIO block of the P34x XRIO converter:
NPS Thermal (tripping element)
This module contains the rotor overload characteristic curve.
The following RIO function for testing these distance protection functions is available:
Overcurrent
8.2.15 Earth Fault
This RIO Earth Faultblock provides the necessary values for testing the trip times of the Earth FaultOvercurrent. The protection functions supported by this RIO function include:
50N,51N Earth Fault Overcurrent
The following RIO function for testing these distance protection functions is available:
Overcurrent
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
15/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 15/16
8.2.16 Voltage dependent OC (Vtest>Vs1)
This RIO Voltage dependent Overcurrentfunction provides the necessary values for testing the voltagerestrained/controlled inverse time overcurrent protection function with test voltages above the MiCOM Vs1setting of the P34x relay with the Overcurrenttest module. The protection functions supported by this RIOfunction include:
51V overcurrent
The following RIO function for testing these distance protection functions is available:
Overcurrent
8.2.17 Voltage dependent OC (Vtest
-
7/21/2019 Areva p343 p344 p345 Xrio Converter Manual Enu Tu2.22 v1.001
16/16
OMICRON PTL AREVA P34x XRIO Converter User Manual
OMICRONelectronics GmbH 16/16
8.3 Activating the RIO functions
The RIO functions have to be set to active manually in each Overcurrenttest module if the converter isused in the stand-alone mode. Activate the RIO function you intend to use in the localhardwareconfiguration as shown below.
Figure 5: Activating a RIO function
8.4 Specific Features
This section deals with special requirements of some of the converter's functions. Functions not listedhere have no known limitations to their functionalities.
8.4.1 Not-Supported IDMT curves
The converter doesnt support the Operating curves typeIDG.
8.4.2 Phase / Neg Seq / Earth Fault / SEF Overcurrent
For the successful phase overcurrent testing with the P34x converter, it is allowed to set only one stageas IDMTin each direction. The other stages should be set to DMT (ANSI Def. Time or IEC Def. Time).The IDMT stage must have the lowest pickup value!