TEST REPORT
Report No.: A7529.01‐109‐44
Rendered to:
LEED‐HIMMEL INDUSTRIES, INC. Hamden, Connecticut
INSULPANE OF CT INC. Hamden, Connecticut
PRODUCT TYPE: Curtain Wall System
SERIES/MODEL: 250
Title Summary of Results Design Pressure ±2400 Pa (±50.13 psf) Air Infiltration <0.1 L/s/m2 (<0.01 cfm/ft2)
Water Penetration Resistance Test Pressure 720 Pa (15.04 psf) Uniform Load Structural Test Pressure ±3600 Pa (±75.19 psf)
Reference must be made to Report No. A7529.01‐109‐44, dated 05/25/11 for complete test specimen description and detailed test results.
Architectural Testing
Test Report No.: A7529.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 1 of 6
1.0 Report Issued To: Leed‐Himmel Industries, Inc. 75 Leeder Hill Drive Hamden, Connecticut 06517
Insulpane of CT Inc. 30 Edmond Street Hamden, Connecticut 06517
2.0 Test Laboratory: Architectural Testing, Inc. 130 Derry Court York, Pennsylvania 17406‐8504 717‐764‐7700
3.0 Project Summary:
3.1 Product Type: Curtain Wall System
3.2 Series/Model: 250
3.3 Compliance Statement: Results obtained are tested values and were secured by using the designated test method(s). Test specimen description and results are reported herein.
3.4 Test Date: 04/05/11
3.5 Test Location: Architectural Testing, Inc. test facility in York, Pennsylvania.
3.6 Test Sample Source: The test specimen was provided by the client. Representative samples of the test specimen(s) will be retained by Architectural Testing for a minimum of four years from the test completion date.
3.7 Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimen(s) reported herein. Test specimen construction was verified by Architectural Testing per the drawings located in Appendix B. Any deviations are documented herein or on the drawings.
3.8 List of Official Observers:
Name Company Adam Stern Leed‐Himmel Industries, Inc. John Harris Leed‐Himmel Industries, Inc. Michael D. Stremmel, P.E. Architectural Testing, Inc. Eric M. Brennan Architectural Testing, Inc.
www.archtest.com
Test Report No.: A7529.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 2 of 6
4.0 Test Method(s):
ASTM E 283‐04, Test Method for Determining Rate of Airflow Through Exterior Windows, Curtain Walls and Doors Under Specified Pressure Differences Across the Specimen. ASTM E 330‐02, Test Method for Structural Performance of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference. ASTM E 331‐00, Test Method for Water Penetration of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference. ASTM E 547‐00, Test Method for Water Penetration of Exterior Windows, Curtain Walls and Doors by Cyclic Static Air Pressure Difference. ASTM F 588‐07, Test Methods for Resistance of Window Assemblies to Forced Entry Excluding Glazing.
5.0 Test Specimen Description:
5.1 Product Sizes:
Width Height Overall Area: 7.4 m² (80.0 ft2) millimeters inches millimeters inches Overall size 2438 96 3048 120
5.2 Frame Construction:
Frame Member Material Description All frame members Aluminum Extruded
www.archtest.com
Test Report No.: A7529.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 3 of 6
5.0 Test Specimen Description: (Continued) 5.2 Frame Construction: (Continued)
Joinery Type Detail
Vertical/horizontal intersections
Square‐cut and butted
All horizontal members were secured to the vertical members with an extruded aluminum shear block/anchor clip. The shear block was secured to the vertical member with three #14 x 1‐1/2" long self‐tapping hex head screws. The horizontal members were secured to the shear block with two #8 x 1" long flat head screws. The shear blocks on either side of the center vertical member at the center horizontals were secured to each other with two 3/8 x 4" long bolts through the center vertical member.
Pressure plates N/A
All pressure plates were secured to the main frame members with 1/4" x 1" long hex head screws spaced 16" on center. All pressure plates utilized a snap‐fit aluminum cover.
5.3 Weatherstripping:
Description Quantity Location Kerf‐mounted custom shaped, hollow vinyl bulb gasket 1 Row Glazing legs of the exterior pressure
plate.
Kerf‐mounted rubber gasket 1 Row Frame exterior, under the pressure plate.
5.4 Glazing: Glass Type
Spacer Type
Interior Lite
Exterior Lite
Glazing Method
1/8" tempered
1/8" tempered
0.090" PVB interlayer
0.090" PVB interlayer
1" IG Aluminum box
1/8" tempered
1/8" tempered
The glass was exterior glazed against an EPDM gasket and a bed of silicone and secured with an exterior mounted aluminum pressure plate with a gasket against the glass.
www.archtest.com
Test Report No.: A7529.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 4 of 6
5.0 Test Specimen Description: (Continued) 5.4 Glazing: (Continued)
Daylight Opening Location Quantity
millimeters inches Glass Bite
Fixed daylight opening 4 1124 x 1422 44‐1/4 x 56 1/2" 5.5 Drainage: No drainage was utilized. 5.6 Hardware: No hardware was utilized. 5.7 Reinforcement: No reinforcement was utilized.
6.0 Installation: The specimen was installed into a Spruce‐Pine‐Fir wood buck. The rough opening allowed for a 1/4" shim space. The exterior perimeter of the window was sealed with sealant. Location Anchor Description Anchor Location
Vertical member ends 1/2" x 3" long lag bolts
Two anchors were utilized through each shear block/anchor clip into the wood buck at the end of each vertical member (Reference Testing Mock‐up Drawing, Sheet 1).
www.archtest.com
Test Report No.: A7529.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 5 of 6
7.0 Test Results: The temperature during testing was 22°C (72°F). The results are tabulated as follows:
Title of Test Results Allowed Note Air Leakage, per ASTM E 283 at 75 Pa (1.57 psf) at 300 Pa (6.27 psf)
<0.1 L/s/m2 (<0.01 cfm/ft2)
0.5 L/s/m2 (0.10 cfm/ft2) max.
Water Penetration, per ASTM E 547 and ASTM E 331
at 720 Pa (15.04 psf) Pass No leakage 1 Uniform Load Deflection,
per ASTM E 330 taken at intermediate frame jamb
+2400 Pa (+50.13 psf) ‐2400 Pa (‐50.13 psf)
6.1 mm (0.24") 5.6 mm (0.22")
17.5 mm (0.69") max. 17.5 mm (0.69") max. 2, 3
Uniform Load Deflection, per ASTM E 330
taken at horizontal member +2400 Pa (+50.13 psf) ‐2400 Pa (‐50.13 psf)
0.3 mm (0.01") 0.5 mm (0.02")
6.4 mm (0.25") max. 6.4 mm (0.25") max. 2, 3
Uniform Load Structural, per ASTM E 330
taken at intermediate frame jamb+3600 Pa (+75.19 psf) ‐3600 Pa (‐75.19 psf)
0.3 mm (0.01") 0.3 mm (0.01")
3.0 mm (0.12") max. 3.0 mm (0.12") max. 2,3
Uniform Load Structural, per ASTM E 330
taken at horizontal member +3600 Pa (+75.19 psf) ‐3600 Pa (‐75.19 psf)
0.3 mm (0.01") 0.3 mm (0.01")
1.0 mm (0.04") max. 1.0 mm (0.04") max. 2, 3
Forced Entry Resistance, per ASTM F 588
Type: D ‐ Grade: 10 Pass No entry General Note: All testing was performed in accordance with the referenced standard(s). Note 1: Without insect screen. Note 2: Loads were held for 10 seconds. Note 3: Tape and film were not used to seal against air leakage during structural testing.
www.archtest.com
Test Report No.: A7529.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 6 of 6
The service life of this report will expire on the stated Test Record Retention End Date, at which time such materials as drawings, data sheets, samples of test specimens, copies of this report, and any other pertinent project documentation, shall be discarded without notice. If test specimen contains glazing, no conclusions of any kind regarding the adequacy or inadequacy of the glass in any glazed test specimen(s) can be made. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, Inc. ___________________________________________ ______________________________________________ Eric M. Brennan Michael D. Stremmel, P.E. Technician Senior Project Engineer EMB:dem Attachments (pages): This report is complete only when all attachments listed are included. Appendix‐A: Photograph (1) Appendix‐B: Drawings (3) This report produced from controlled document template ATI 00479, issued 03/01/11.