Advanced Protection Technologies
Overview of UL 1449 Third Edition
Narrated by:
Robert Stanley
2
Surge Protection..
MOV/SPD
Load
..in ACTION!
3
Surge Protection..
MOV/SPD
Load
..in ACTION!
UL 1449 THIRD Edition
Safe Surge Protection Specification Interpretation Ordering Procedures
Product ApplicationsNext Generation of SPD Products and FeaturesOur Services and Support
Today you will leave here knowing….
UL 1449 THIRD Edition
SPD
TVSS
Surge Arresters
Combine TVSS and Surge Arrestersinto one UL Standard, UL 1449 3rd
Edition renamed: Surge Protective Devices (SPDs)Effective: Sept 29, 2009
• New SPD Types: Types 1, 2, 3 & 4• New Voltage Protection Ratings (VPRs) replace
old-style Suppressed Voltage Ratings (SVRs)• New I nominal ratings• Bid Specifications become Obsolete as product
evaluation & ratings change
6
UL 1449 THIRD Edition & 2008 NEC Art 285
• Changing term TVSS to SPD TVSS SPD• Creates Types 1, 2, 3 & 4 SPDs
• Type 1 – Installed on line or load side of Main OCP - similar to what you knew as SSA, except now includes rigorous safety testing. Includes all OCP & safety apparatus inside SPD
• Type 2 – Installed on load side of Main OCP - similar to what you know as hardwired TVSS. May require external OCP
• Type 3 – Point of Utilization – direct plug in - similar to what you know as surge strips - 10 meters from panel (rational based on being IEEE Cat. A location)
• Type 4 – surge suppression components, could be basic component or complete module. Type 4 components can be tested for Type 1, Type 2 or Type 3 applications.
X X
7
UL 1449 THIRD Edition & 2008 NEC Art 285
• Changing term TVSS to SPD TVSS SPD• Creates Types 1, 2, 3 & 4 SPDs
• Type 1 – Installed on line or load side of Main OCP - similar to what you knew as SSA, except now includes rigorous safety testing. Includes all OCP & safety apparatus inside SPD
• Type 2 – Installed on load side of Main OCP - similar to what you know as hardwired TVSS. May require external OCP
• Type 3 – Point of Utilization – direct plug in - similar to what you know as surge strips - 10 meters from panel (rational based on being IEEE Cat. A location)
• Type 4 – surge suppression components, could be basic component or complete module. Type 4 components can be tested for Type 1, Type 2 or Type 3 applications.
X X
UL 1449-3 & 2008 NEC Art 285
SPD Types: Types 1, 2, 3 & 4Based on Location within electrical distribution system
Trans
MeterSvc. Disc.
Panel
Type 1
10m (30feet)
Type 2
Type 3
OCP built in to SPD, more rigorous testing
9
UL 1449 THIRD EditionPerformance Test Format Changed
New Testing uses Six (6) Times More Energy
Old – 6kV / 500ASuppressed Voltage Ratings
(SVR)
New – 6kV / 3,000A Voltage Protection Ratings
(VPR)
500A
3000A• As surge amplitude goes up, clamping voltage goes up too• Specs become obsolete• Need new VPRs in specs
New Clamping Voltages
UL 1449 THIRD EditionI nominal Testing – In - (Nominal Discharge Current)- New Concept to USA – Originated from IEC 61643- Duty Cycle Testing- 15 8x20s surges through every mode of three samples used for VPR testing
Type 1 – 20kA or 10kAType 2 – 20kA, 10kA, 5kA or 3kAType 3 – 3kAType 4 – Based on intended usage as Types 1, 2 or 3
UL 96A Master Label requires 20kA In from Type 1 or Type 2 SPD
What to look for in a spec….
…continued
APT offers a full breadth of Type 1 and Type 2 SPD’s. Our Type 1 SPD’s use Large Block 50kA MOV’s that have Thermal Protection and are very reliable and robust. Each Series offers protection which is ideal for remote locations and extreme duty applications where downtime is unacceptable, to models ideal for downstream applications. Our units offer protection from 50kA per phase up to 1000kA per phase.
Advanced Protection Technologies
SPD Products from Advanced Protection Technologies
Low UL 1449 Third Edition VPRs – Voltage Protection Ratings
SCCR tested to 200kA and service entrance (C High - C3) rated
“Always On” diagnostics with audible alarm that continuously monitor SPD unit status
AC tracking filter with EMI/RFI Filtering up to -50db from 10kHZ to 100MHZ
• 10 Year Warranty*(Also available in 20 & 30)*Does NOT include SPDee or DIN Rail*
UnitizedReplaceable Module
DIN Rail
XB SeriesDependable protection at Service Entrance,
Distribution Panels and Downstream• Redundant Suppression Modules (2 per phase).• XBS: Standard modes (L-N, L-G, L-L, N-G) • XBL: Includes direct L-L protection for 10 mode Wye Systems (L-N, L-G, L-L, N-G) • Surge current ratings of 400kA, 500kA, 600kA, 1000kA per Phase (XBL 10 Mode: 600 or 900kA)• Internal Disconnect Switch: Standard• All Overcurrent Protection included inside SPD• Options: Dry Contacts, Surge Counter • Standard Enclosure: NEMA 1, 12, 3R, 4• Optional Enclosures: 4S, 4X, FM• UL Recognized Case-less model for switchboard and switchgear mounting (See XW Series)• 200kA & 100kA SCCRs
• UL & NEC Type 1 SPD• 20kA In Rating (Nominal Discharge Current)• EMI/RFI Noise Filtering
XA SeriesFor Critical Loads at Service Entrance
Switchboards/Switchgear
• XAS: Standard modes (L-N, L-G, L-L, N-G) • XAL: Includes direct L-L protection for 10 mode Wye Systems (L-N, L-G, L-L, N-G) • Surge current ratings: 100kA, 150kA, 200kA, 250kA, 300kA, 400kA, 500kA per Phase • Internal Disconnect Switch: Optional• All Overcurrent Protection included inside SPD• Options: Dry Contacts, Surge Counter • Standard Enclosure: NEMA 1, 12, 3R, 4• Optional Enclosures: 4S, 4X, FM• UL Recognized Case-less model for switchboard and switchgear mounting (See XR & W Series)• 200kA & 100kA SCCRs
• UL & NEC Type 1 SPD• 20kA In Rating (Nominal Discharge Current) (Most models)• EMI/RFI Noise Filtering
TE/XGA Series Full Featured workhorse for service entrance, distribution and branch panels.
• All modes: L-N, L-G, L-L, N-G• Surge current ratings: 160kA, 240kA per Phase • Optional Hybrid MOV/SAD: 90kA, 130kA, 170kA per Phase• All Overcurrent Protection included inside SPD• Options: Dry Contacts, Surge Counter • Standard Enclosure: NEMA 1, 12, 3R, 4• Optional Enclosures: 4S, 4X, FM• UL Recognized Case-less model for switchboard and switchgear mounting (See XTE/XGA Series)• 200kA SCCR
• UL & NEC Type 2 SPD• TranSafe Redundant Circuitry• Large Block 40kA MOVs• EMI/RFI Noise Filtering
TE/HP
TE/HP Series Dependable protection at service entrance, distribution panels and
downstream.
• All modes: L-N, L-G, L-L, N-G• Surge current ratings: 120kA, 160kA per Phase • Phase Replaceable Modules• Phase Replaceable Fuses• All Overcurrent Protection included inside SPD• Options: Dry Contacts, Surge Counter • Standard Enclosure: NEMA 1, 12, 3R, 4• Optional Enclosures: 4S, 4X, FM• UL Recognized Case-less model for switchboard and switchgear mounting (See XTE/HP Series)• 200kA SCCR
• UL & NEC Type 2 SPD• Large Block 40kA MOVs• EMI/RFI Noise Filtering
TE/HPS
TE/HPS Series Budget conscious protection for service entrance, distribution and branch
panels.
• All modes: L-N, L-G, L-L, N-G• Surge current ratings: 80kA, 120kA & 160kA per Phase • Phase Replaceable Modules• Phase Replaceable Fuses• All Overcurrent Protection included inside SPD• Options: Dry Contacts• Standard Enclosure: NEMA 1, 12, 3R, 4• Optional Enclosures: 4S, 4X, FM• UL Recognized Case-less model for switchboard and switchgear mounting (See XTE/HPS Series)• 200kA SCCR
• UL & NEC Type 2 SPD• Large Block 40kA MOVs• EMI/RFI Noise Filtering
XDS SeriesFor Distribution and Branch Applications
• All modes: L-N, L-G, L-L, N-G• Surge Current Ratings: 100kA, 150kA, 200kA Per Phase• Enclosure: NEMA 4X Standard• Options:
• Dry Contact & Audible Alarm• Delete Noise Filtering• FM – Flushmount
• UL & NEC Type 1 SPD• 20kA In Rating (Nominal Discharge Current) (Most Models)• EMI/RFI Noise Filtering
XCS SeriesFor Branch Panel Applications
• All modes: L-N, L-G, L-L, N-G• Surge Current Rating: 100kA per phase • Enclosure: NEMA 4X Standard• Options:
• Dry Contact & Audible Alarm• FM – Flushmount • UL & NEC Type 1 SPD
• 20kA In Rating (Nominal Discharge Current) (Most Models)
SPDEE Series• Versatile – Numerous voltage configurations: 1Pole, 2 Pole (Split Phase), 3 Phase• 50kA or 100kA (Split-Phase) Per Phase• Always On Green LED• Options
• N-G protection • Dry Contact & Audible Alarm• Other configurations available for OEM – Call
• Tri-Mount Installation• Nipple• Din-Rail• Backplane
• UL & NEC Type 1 SPD• Replaces Secondary Arrestors• Meets UL 96A Lightning Protection Master Label @ 20kA In• 20kA In Rating (Nominal Discharge Current) (Most models)
APT DIN Rail Surge Protection Devices
• APT AC DIN Rail mounted SPDs are designed for downstream load protection. They are parallel connected devices which utilize large block MOVs, housed in UL 94V-0 thermoplastic enclosures. Each device includes internal thermal disconnects and visual failure mode status indicators with optional relay contacts.
• These devices are intended for use in IEC Class II, UL 1449 Type 2, Type 4, and IEEE Category C, B & A load applications..
• APT Low Voltage DIN Rail SPDs utilize a hybrid mix of Tranzorbs, inductors, gas tubes, and resistors for complete low-voltage/data protection.
• These products are intended for use on a wide range of low-voltage applications, protect up to 4 wires in a single enclosure, adhere to UL 497B and are IEC / CE compliant.
• Offered in a full range of AC service voltages;
120V Single Phase 120/208V 3-Phase Wye 120/240V Split Phase 480V 3-Phase Delta230V Single Phase 277/480V 3-Phase Wye 240V 3-Phase Delta 347/600V 3-Phase Wye 277V Single Phase
• The following DC low voltage are also available:
5V / 4-wire 12V / 4-wire24V / 4-wire 48V / 4-wire60V / 4-wire
Qualifying things to know:
• System Voltage• Panel Information• Panel Amperage ?
Qualifying things to know:
• System Voltage• Panel Information• Panel Amperage• Available Breaker• SPD Options ?
APT SPD - Ordering
28
Verifying at www.UL.com
ClickCertifications
Category Code #’s: XUHT for TVSS (<Oct 09) OWHX for Arrestors (<Oct 09) VZCA for SPDs
APT – the answer to all your surge protection needs!!!
• Some of our services include:– Competitor Product Comparison – Competitively priced in the current
market – Proper Product Selection – Based on specification/engineer requirements– Specification Interpretation with Engineering Assistance– Consulting Engineering History – Extensive database, compiled over the
last 25 years, we know engineers likes/dislikes– Never sell direct to contractors – You deal direct with the factory– Submittals – E-mailed in minutes– Experience in the Industrial Market - New Din Rail Products – Live Interactive Internet Based Training – Seminars also hosted here at our
factory– Stocking Program – No minimums or penalties – Troubleshooting, Returns
APT: 800.237.4567www.apttvss.com, www.aptspd.com